AG1-185 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:54
Pamplin-Chase City 115 kV
48.91 MW Capacity / 0.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-185 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Storage generating facility located in the Dominion zone — Charlotte County, Virginia. This project is an increase to the Interconnection Customer's AG1-181 project, which will share the same point of interconnection. The AG1-185 queue position is a 0.0 MW uprate (48.91 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 150.0 MW with 150 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this project is Friday, June 30, 2023. This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AG1-185 |
Project Name | Pamplin-Chase City 115 kV |
Developer Name | Drakes Branch Solar, LLC |
State | Virginia |
County | Charlotte |
Transmission Owner | Dominion |
MFO | 150.0 MW |
MWE | 0.0 MW |
MWC | 48.91 MW |
Fuel Type | Storage |
Basecase Study Year | 2024 |
Point of Interconnection
AG1-185 will interconnect with the Dominion transmission system as an uprate to AG1-181, sharing the POI and Attachment Facilities which is a tap between Pamplin - Chasecity 115 kV Line.
Summer Peak Analysis
The Queue Project was evaluated as a 0.0 MW (Capacity 48.91 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 168.46 % | 192.22 % | 205.86 | B | 395.7 | 48.91 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 168.47 % | 192.22 % | 205.86 | B | 395.71 | 48.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 235-A
CONTINGENCY 'DVP_P1-2: LN 235-A' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Single | AC | 176.29 % | 184.82 % | 182.64 | B | 337.55 | 15.86 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 125.56 % | 138.0 % | 182.64 | B | 252.05 | 22.74 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 165.7 % | 168.53 % | 559.3 | B | 942.6 | 15.06 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 163.41 % | 166.19 % | 571.52 | B | 949.83 | 15.05 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 2201
CONTINGENCY 'DVP_P1-2: LN 2201' OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD 230.0 - 6CLUBHSE 230.0 END |
Single | AC | 166.89 % | 169.71 % | 182.64 | B | 309.96 | 5.16 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
Base Case | Single | AC | 102.72 % | 110.68 % | 186.12 | A | 206.0 | 15.27 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 165.39 % | 168.19 % | 559.3 | B | 940.7 | 15.06 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 104.4 % | 122.04 % | 269.78 | B | 329.23 | 48.91 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 163.54 % | 166.33 % | 571.52 | B | 950.6 | 15.05 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 254
CONTINGENCY 'DVP_P1-2: LN 254' OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD 230.0 - 6LAKEVEW 230.0 END |
Single | AC | 155.83 % | 158.59 % | 182.64 | B | 289.66 | 5.17 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
PJM_PLANT BEAR GARDEN
CONTINGENCY 'PJM_PLANT BEAR GARDEN' REMOVE MACHINE G1 FROM BUS 315191 /*1BEARGRDN G1 18.0 REMOVE MACHINE G2 FROM BUS 315192 /*1BEARGRDN G2 18.0 REMOVE MACHINE S1 FROM BUS 315193 /*1BEARGRDN S1 22.0 END |
Single | AC | 98.38 % | 105.51 % | 205.86 | B | 217.21 | 15.27 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 104.87 % | 111.78 % | 198.06 | B | 221.4 | 13.88 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 144.62 % | 146.35 % | 718.0 | B | 1050.81 | 11.34 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 141.67 % | 143.51 % | 674.92 | B | 968.57 | 11.34 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 104.6 % | 122.34 % | 269.78 | B | 330.04 | 48.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
Base Case | Single | AC | 100.5 % | 106.28 % | 176.81 | A | 187.92 | 10.24 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 144.72 % | 146.45 % | 718.0 | B | 1051.52 | 11.34 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 87.33 % | 102.07 % | 331.82 | B | 338.7 | 48.91 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 141.7 % | 143.53 % | 674.92 | B | 968.75 | 11.34 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 135.91 % | 137.22 % | 661.76 | B | 908.07 | 8.89 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 131.94 % | 133.25 % | 661.76 | B | 881.8 | 8.89 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 131.71 % | 133.02 % | 661.76 | B | 880.28 | 8.89 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 128.59 % | 129.9 % | 661.76 | B | 859.64 | 8.89 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 127.74 % | 129.05 % | 661.76 | B | 854.01 | 8.89 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 127.66 % | 129.04 % | 678.68 | B | 875.79 | 9.72 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 104.98 % | 122.89 % | 269.78 | B | 331.55 | 48.91 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 124.69 % | 126.0 % | 661.76 | B | 833.84 | 8.89 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 125.57 % | 126.95 % | 678.68 | B | 861.6 | 9.72 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 87.33 % | 102.07 % | 331.82 | B | 338.7 | 48.91 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 123.51 % | 124.91 % | 678.68 | B | 847.72 | 9.72 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 121.43 % | 122.82 % | 678.68 | B | 833.57 | 9.72 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
Base Case | Single | AC | 98.31 % | 101.13 % | 176.81 | A | 178.81 | 5.18 | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 117.16 % | 118.71 % | 269.78 | B | 320.25 | 4.37 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-B
CONTINGENCY 'DVP_P1-2: LN 1012-B' OPEN BRANCH FROM BUS 963320 TO BUS 965590 CKT 1 /*AG1-181 TAP 115.0 - AG1-427 TAP 115.0 END |
Single | AC | 86.62 % | 101.81 % | 331.82 | B | 337.83 | 48.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 272.2 % | 285.17 % | 208.7 | C | 595.16 | 27.08 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.93 | 48.91 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.93 | 48.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 206.66 % | 216.51 % | 221.4 | C | 479.35 | 21.81 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.93 | 48.91 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.93 | 48.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 166.17 % | 171.92 % | 221.4 | C | 380.63 | 13.88 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.94 | 48.91 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 158.75 % | 172.76 % | 349.0 | C | 602.94 | 48.91 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 132.96 % | 147.34 % | 349.0 | C | 514.23 | 48.91 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 186.07 % | 188.29 % | 684.0 | C | 1287.9 | 15.07 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 186.07 % | 188.29 % | 684.0 | C | 1287.88 | 15.07 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 186.01 % | 188.24 % | 684.0 | C | 1287.53 | 15.07 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 183.61 % | 185.78 % | 699.0 | C | 1298.58 | 15.07 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 183.6 % | 185.78 % | 699.0 | C | 1298.57 | 15.07 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 183.55 % | 185.72 % | 699.0 | C | 1298.22 | 15.07 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 133.17 % | 147.65 % | 349.0 | C | 515.29 | 48.91 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 314835 /*3CAROL_1 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 128.82 % | 132.62 % | 199.0 | B | 263.91 | 7.82 | |
| DVP |
3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line
313898 to 314267 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 160.49 % | 162.56 % | 349.0 | C | 567.35 | 7.24 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 133.34 % | 145.27 % | 349.0 | C | 507.01 | 41.65 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P4-2: 3202
CONTINGENCY 'DVP_P4-2: 3202' OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1 /*3WELCOTAP 115.0 - 3REEDY C 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1 /*3WELCOTAP 115.0 - 3S BOSTN 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1 /*3WELCOTAP 115.0 - 3WELCO 115.0 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1 /*3SEDGE HILL 115.0 - 3SINAI 115.0 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1 /*3SINAI 115.0 - 3S BOSTN 115.0 OPEN BUS 313852 /*3WELCOTAP 115.0 OPEN BUS 314717 /*3SINAI 115.0 OPEN BUS 314718 /*3S BOSTN 115.0 OPEN BUS 314724 /*3WELCO 115.0 END |
Breaker | AC | 134.68 % | 137.65 % | 279.1 | C | 384.19 | 8.34 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 111.31 % | 114.2 % | 199.0 | B | 227.26 | 6.83 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 111.31 % | 114.2 % | 199.0 | B | 227.26 | 6.83 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 134.22 % | 149.2 % | 349.0 | C | 520.72 | 48.91 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 109.77 % | 113.6 % | 349.0 | C | 396.45 | 13.36 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 316085 CKT 1 /*3EMPORIA 115.0 - 3IVORY LANE 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 126.55 % | 127.78 % | 288.6 | C | 368.76 | 4.2 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 108.68 % | 112.51 % | 349.0 | C | 392.65 | 13.36 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 99.8 % | 103.27 % | 406.0 | C | 419.28 | 14.5 | |
| DVP |
AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line
936260 to 313898 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 120.19 % | 122.0 % | 400.0 | C | 488.01 | 7.25 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 97.89 % | 101.33 % | 406.0 | C | 411.4 | 14.44 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 14852
CONTINGENCY 'DVP_P4-2: 14852' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 END |
Breaker | AC | 115.4 % | 116.63 % | 288.6 | C | 336.59 | 4.2 | |
| DVP |
AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line
961890 to 314725 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 110.2 % | 112.28 % | 349.0 | C | 391.86 | 7.25 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 7152
CONTINGENCY 'DVP_P4-2: 7152' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314516 TO BUS 314676 CKT 1 /*3BRUNWICK_1 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314693 CKT 1 /*3CLUBHSE71 115.0 - 3FRMAN D 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314850 CKT 1 /*3CLUBHSE71 115.0 - 3CLUBHSE71_1 115.0 OPEN BRANCH FROM BUS 314675 TO BUS 314676 CKT 1 /*3BRODNAX 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314676 TO BUS 314704 CKT 1 /*3BRUNWICK 115.0 - 3LAWRENC 115.0 OPEN BRANCH FROM BUS 314693 TO BUS 314704 CKT 1 /*3FRMAN D 115.0 - 3LAWRENC 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314516 /*3BRUNWICK_1 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314565 /*3CLUBHSE71 115.0 OPEN BUS 314676 /*3BRUNWICK 115.0 OPEN BUS 314693 /*3FRMAN D 115.0 OPEN BUS 314704 /*3LAWRENC 115.0 OPEN BUS 314782 /*2BRUNWICK 69.0 OPEN BUS 314785 /*2DANLTWN 69.0 OPEN BUS 314786 /*2GASBURG 69.0 OPEN BUS 314787 /*2BRUNWICK2 69.0 OPEN BUS 314850 /*3CLUBHSE71_1 115.0 OPEN BUS 314872 /*2BRUNSWICKDP 69.0 END |
Breaker | AC | 114.7 % | 115.93 % | 288.6 | C | 334.56 | 4.2 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 93T140
CONTINGENCY 'DVP_P4-2: 93T140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Breaker | AC | 116.5 % | 117.5 % | 288.6 | C | 339.11 | 3.72 | |
| DVP |
3VICT DP-3VICTRIA 115.0 kV Ckt 1 line
314725 to 314723 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 109.23 % | 111.31 % | 349.0 | C | 388.47 | 7.25 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 120.22 % | 121.2 % | 809.0 | C | 980.55 | 8.15 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 120.22 % | 121.2 % | 809.0 | C | 980.54 | 8.15 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 120.2 % | 121.19 % | 809.0 | C | 980.39 | 8.15 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 106.01 % | 106.87 % | 342.0 | C | 365.51 | 3.5 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 106.01 % | 106.87 % | 342.0 | C | 365.5 | 3.5 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 106.0 % | 106.87 % | 342.0 | C | 365.49 | 3.5 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90
CONTINGENCY 'DVP_P7-1: LN 22-90' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Tower | AC | 126.64 % | 130.4 % | 199.0 | B | 259.49 | 7.73 | |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961791 | AG1-021 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961891 | AG1-030 C | 80/20 | 37.77 MW | 37.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963171 | AG1-166 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963181 | AG1-167 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963191 | AG1-168 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963201 | AG1-169 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963211 | AG1-170 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963301 | AG1-179 C | 80/20 | 3.87 MW | 3.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963311 | AG1-180 | 80/20 | 1.89 MW | 1.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963321 | AG1-181 C O1 | 80/20 | 32.77 MW | 32.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963361 | AG1-185 O1 | 80/20 | 15.86 MW | 15.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964111 | AG1-272 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964121 | AG1-273 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964131 | AG1-274 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964241 | AG1-285 C O1 | 80/20 | 18.39 MW | 18.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964791 | AG1-342 C | 80/20 | 3.1 MW | 3.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965191 | AG1-384 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965591 | AG1-427 C | 80/20 | 17.61 MW | 17.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965601 | AG1-428 C O2 | 80/20 | 3.23 MW | 3.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965641 | AG1-432 C O1 | 80/20 | 73.68 MW | 73.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965721 | AG1-440 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965731 | AG1-441 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965771 | AG1-445 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965781 | AG1-446 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965831 | AG1-451 | 80/20 | 12.28 MW | 12.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313506 | AB1-173 C OP | 80/20 | 2.2 MW | 2.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314429 | 3JTRSVLE | 80/20 | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314704 | 3LAWRENC | 80/20 | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315158 | 1KERR 1 | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315159 | 1KERR 2 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315160 | 1KERR 3 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315161 | 1KERR 4 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315162 | 1KERR 5 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 927261 | AC1-222 C | 80/20 | 1.32 MW | 1.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 934311 | AD1-055 C | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 936265 | AD2-033 C | 80/20 | 24.79 MW | 24.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 942461 | AE2-259 C O1 | 80/20 | 36.84 MW | 36.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 943901 | AF1-058 C | 80/20 | 0.75 MW | 0.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958801 | AF2-171 C | 80/20 | 41.22 MW | 41.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 959311 | AF2-222 C | 80/20 | 36.05 MW | 36.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960061 | AF2-297 C | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315163 | 1KERR 6 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315164 | 1KERR 7 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315266 | 1PLYWOOD A | 80/20 | 0.63 MW | 0.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316118 | AC1-105 C | 80/20 | 3.19 MW | 3.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316129 | AC1-054 C | 80/20 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316131 | AB2-060 C | 80/20 | 2.02 MW | 2.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924301 | AB2-077 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924311 | AB2-078 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924321 | AB2-079 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 925611 | AC1-036 C | 80/20 | 0.5 MW | 0.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 938371 | AE1-056 C | 80/20 | 19.46 MW | 19.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 939181 | AE1-148 C | 80/20 | 7.77 MW | 7.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 940661 | AE2-053 O1 | 80/20 | 2.88 MW | 2.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946281 | AF1-292 C | 80/20 | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946301 | AF1-294 C | 80/20 | 11.32 MW | 11.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958211 | AF2-115 C | 80/20 | 6.9 MW | 6.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 962561 | AG1-105 C O1 | 80/20 | 7.36 MW | 7.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313527 | AB2-043 C | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.97 MW | 13.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.32 MW | 3.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.07 MW | 4.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.0 MW | 1.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 24.36 MW | 24.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963301 | AG1-179 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963311 | AG1-180 | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 46.99 MW | 46.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 22.74 MW | 22.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 34.86 MW | 34.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964791 | AG1-342 C | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 33.05 MW | 33.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965601 | AG1-428 C O2 | 80/20 | 1.42 MW | 1.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 55.78 MW | 55.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965721 | AG1-440 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965731 | AG1-441 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965771 | AG1-445 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965781 | AG1-446 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 9.3 MW | 9.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 14.45 MW | 14.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 27.89 MW | 27.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 41.84 MW | 41.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 46.48 MW | 46.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.94 MW | 0.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.68 MW | 0.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 18.04 MW | 18.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 3.42 MW | 3.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.27 MW | 1.27 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 4.57 MW | 4.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 962561 | AG1-105 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.37 MW | 0.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961891 | AG1-030 C | 80/20 | 7.72 MW | 7.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963301 | AG1-179 C | 80/20 | 12.96 MW | 12.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963321 | AG1-181 C O1 | 80/20 | 10.66 MW | 10.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963361 | AG1-185 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964111 | AG1-272 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964121 | AG1-273 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964131 | AG1-274 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964241 | AG1-285 C O1 | 80/20 | 9.13 MW | 9.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964791 | AG1-342 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964801 | AG1-343 C | 80/20 | 2.87 MW | 2.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965191 | AG1-384 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965601 | AG1-428 C O2 | 80/20 | 10.82 MW | 10.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313506 | AB1-173 C OP | 80/20 | 14.92 MW | 14.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315136 | 1ROSEMG1 | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926070 | AC1-086 C | 80/20 | 10.02 MW | 10.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 927145 | AC1-208 C | 80/20 | 5.26 MW | 5.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 934331 | AD1-057 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 936265 | AD2-033 C | 80/20 | 8.32 MW | 8.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 944141 | AF1-082 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958801 | AF2-171 C | 80/20 | 7.02 MW | 7.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 959311 | AF2-222 C | 80/20 | 9.8 MW | 9.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923262 | AB1-132 C OP | 80/20 | 6.8 MW | 6.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923991 | AB2-040 C O1 | 80/20 | 16.25 MW | 16.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 957521 | AF2-046 C | 80/20 | 7.43 MW | 7.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315608 | 3AA2-088SOLA | 80/20 | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316096 | AB2-100 C1 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316098 | AB2-100 C2 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961681 | AG1-008 C | 80/20 | 7.45 MW | 7.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.91 MW | 13.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.92 MW | 4.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.96 MW | 4.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.69 MW | 0.69 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 1.88 MW | 1.88 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 0.92 MW | 0.92 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 31.57 MW | 31.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 15.27 MW | 15.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 12.75 MW | 12.75 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.43 MW | 1.43 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 12.41 MW | 12.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 1.57 MW | 1.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 100.11 MW | 100.11 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 16.68 MW | 16.68 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 4.15 MW | 4.15 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 50.05 MW | 50.05 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 49.79 MW | 49.79 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 37.78 MW | 37.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.51 MW | 0.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 24.51 MW | 24.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.78 MW | 3.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.51 MW | 4.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.2 MW | 1.2 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.38 MW | 1.38 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -6.03 MW | -5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961891 | AG1-030 C | 80/20 | 7.73 MW | 7.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963301 | AG1-179 C | 80/20 | 12.97 MW | 12.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963321 | AG1-181 C O1 | 80/20 | 10.68 MW | 10.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963361 | AG1-185 O1 | 80/20 | 5.17 MW | 5.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964791 | AG1-342 C | 80/20 | 1.95 MW | 1.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964801 | AG1-343 C | 80/20 | 2.88 MW | 2.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965601 | AG1-428 C O2 | 80/20 | 10.83 MW | 10.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313506 | AB1-173 C OP | 80/20 | 14.93 MW | 14.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926070 | AC1-086 C | 80/20 | 10.03 MW | 10.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 927145 | AC1-208 C | 80/20 | 5.27 MW | 5.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 934331 | AD1-057 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 936265 | AD2-033 C | 80/20 | 8.33 MW | 8.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 944141 | AF1-082 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958801 | AF2-171 C | 80/20 | 7.03 MW | 7.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 959311 | AF2-222 C | 80/20 | 9.81 MW | 9.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923262 | AB1-132 C OP | 80/20 | 6.81 MW | 6.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923991 | AB2-040 C O1 | 80/20 | 16.26 MW | 16.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 957521 | AF2-046 C | 80/20 | 7.44 MW | 7.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315608 | 3AA2-088SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961681 | AG1-008 C | 80/20 | 7.46 MW | 7.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.01 MW | 14.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.06 MW | 5.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.05 MW | 5.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.17 MW | 1.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.71 MW | 0.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 963301 | AG1-179 C | 80/20 | 1.88 MW | 1.88 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 963311 | AG1-180 | 80/20 | 0.92 MW | 0.92 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 963321 | AG1-181 C O1 | 80/20 | 31.57 MW | 31.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 963361 | AG1-185 O1 | 80/20 | 15.27 MW | 15.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 964111 | AG1-272 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 964121 | AG1-273 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 964131 | AG1-274 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 964241 | AG1-285 C O1 | 80/20 | 12.75 MW | 12.75 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 964791 | AG1-342 C | 80/20 | 1.43 MW | 1.43 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965191 | AG1-384 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965591 | AG1-427 C | 80/20 | 12.41 MW | 12.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965601 | AG1-428 C O2 | 80/20 | 1.57 MW | 1.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965641 | AG1-432 C O1 | 80/20 | 100.11 MW | 100.11 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965831 | AG1-451 | 80/20 | 16.68 MW | 16.68 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315159 | 1KERR 2 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315160 | 1KERR 3 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315161 | 1KERR 4 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315162 | 1KERR 5 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 936265 | AD2-033 C | 80/20 | 4.15 MW | 4.15 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 942461 | AE2-259 C O1 | 80/20 | 50.05 MW | 50.05 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 958801 | AF2-171 C | 80/20 | 49.79 MW | 49.79 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 959311 | AF2-222 C | 80/20 | 37.78 MW | 37.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315163 | 1KERR 6 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 315164 | 1KERR 7 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 924301 | AB2-077 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 924311 | AB2-078 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 924321 | AB2-079 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 925611 | AC1-036 C | 80/20 | 0.51 MW | 0.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 938371 | AE1-056 C | 80/20 | 24.51 MW | 24.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 939181 | AE1-148 C | 80/20 | 3.78 MW | 3.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 962561 | AG1-105 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 313527 | AB2-043 C | 80/20 | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.51 MW | 4.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.2 MW | 1.2 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.38 MW | 1.38 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961891 | AG1-030 C | 80/20 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963301 | AG1-179 C | 80/20 | 3.09 MW | 3.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963311 | AG1-180 | 80/20 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 28.69 MW | 28.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964241 | AG1-285 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964791 | AG1-342 C | 80/20 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965721 | AG1-440 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965731 | AG1-441 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315159 | 1KERR 2 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315160 | 1KERR 3 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315161 | 1KERR 4 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315162 | 1KERR 5 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 936265 | AD2-033 C | 80/20 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 31.82 MW | 31.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315163 | 1KERR 6 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315164 | 1KERR 7 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316118 | AC1-105 C | 80/20 | 1.97 MW | 1.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316129 | AC1-054 C | 80/20 | 3.16 MW | 3.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316131 | AB2-060 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924301 | AB2-077 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924311 | AB2-078 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924321 | AB2-079 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 939181 | AE1-148 C | 80/20 | 6.24 MW | 6.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 940661 | AE2-053 O1 | 80/20 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 6.19 MW | 6.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 962561 | AG1-105 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 313527 | AB2-043 C | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.01 MW | 1.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 24.59 MW | 24.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 1.17 MW | 1.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 21.16 MW | 21.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 10.24 MW | 10.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 11.73 MW | 11.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.83 MW | 1.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 11.24 MW | 11.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 48.39 MW | 48.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965831 | AG1-451 | 80/20 | 8.06 MW | 8.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.82 MW | 0.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 15.99 MW | 15.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 24.2 MW | 24.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 26.89 MW | 26.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 23.37 MW | 23.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.28 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 12.73 MW | 12.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 4.82 MW | 4.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.79 MW | 1.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 7.39 MW | 7.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 4.5 MW | 4.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.42 MW | 4.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.74 MW | 5.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.5 MW | 1.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.75 MW | 1.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.23 MW | 0.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 7.79 MW | 7.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 14.09 MW | 14.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 6.87 MW | 6.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.18 MW | 5.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964801 | AG1-343 C | 80/20 | 1.86 MW | 1.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966811 | AG1-552 C | 80/20 | 1.38 MW | 1.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965291 | AG1-394 C | 80/20 | 0.66 MW | 0.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.63 MW | 8.63 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 11.77 MW | 11.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 4.51 MW | 4.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 4.51 MW | 4.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 2.61 MW | 2.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 2.61 MW | 2.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 15.41 MW | 15.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314572 | 3EMPORIA | 80/20 | 1.33 MW | 1.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 927145 | AC1-208 C | 80/20 | 3.01 MW | 3.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.36 MW | 8.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 7.1 MW | 7.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 9.86 MW | 9.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 960081 | AF2-299 C | 80/20 | 8.92 MW | 8.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315266 | 1PLYWOOD A | 80/20 | 0.4 MW | 0.4 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.6 MW | 4.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 16.79 MW | 16.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 2.72 MW | 2.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 5.65 MW | 5.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.09 MW | 2.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946281 | AF1-292 C | 80/20 | 5.29 MW | 5.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 1.93 MW | 1.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 0.76 MW | 0.76 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.34 MW | 0.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.53 MW | 4.53 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.32 MW | 0.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.38 MW | 2.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.26 MW | 2.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961791 | AG1-021 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961891 | AG1-030 C | 80/20 | 9.77 MW | 9.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962491 | AG1-098 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963171 | AG1-166 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963181 | AG1-167 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963191 | AG1-168 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963201 | AG1-169 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963211 | AG1-170 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963321 | AG1-181 C O1 | 80/20 | 9.04 MW | 9.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 O1 | 80/20 | 4.37 MW | 4.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964241 | AG1-285 C O1 | 80/20 | 5.52 MW | 5.52 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965591 | AG1-427 C | 80/20 | 5.27 MW | 5.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965641 | AG1-432 C O1 | 80/20 | 17.69 MW | 17.69 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.95 MW | 2.95 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315153 | 1CLOVER1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315154 | 1CLOVER2 | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934615 | AD1-087 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934625 | AD1-088 C | 80/20 | 6.81 MW | 6.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 936265 | AD2-033 C | 80/20 | 6.87 MW | 6.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 937481 | AD2-202 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 942461 | AE2-259 C O1 | 80/20 | 8.85 MW | 8.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958801 | AF2-171 C | 80/20 | 10.46 MW | 10.46 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 316131 | AB2-060 C | 80/20 | 0.63 MW | 0.63 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924301 | AB2-077 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924311 | AB2-078 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924321 | AB2-079 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925611 | AC1-036 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938371 | AE1-056 C | 80/20 | 4.85 MW | 4.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 939181 | AE1-148 C | 80/20 | 2.81 MW | 2.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941791 | AE2-182 C | 80/20 | 1.11 MW | 1.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946301 | AF1-294 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958211 | AF2-115 C | 80/20 | 1.75 MW | 1.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 933501 | AC2-165 C | 80/20 | 9.02 MW | 9.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314333 | 6POWHATN | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314677 | 6BUCKING | 80/20 | 0.49 MW | 0.49 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315191 | 1BEARGRDN G1 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315192 | 1BEARGRDN G2 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315193 | 1BEARGRDN S1 | 80/20 | 10.93 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938561 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962561 | AG1-105 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.79 MW | 0.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.19 MW | 0.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 55.97 MW | 55.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 27.08 MW | 27.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 41.52 MW | 41.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 27.68 MW | 27.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 39.37 MW | 39.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 26.3 MW | 26.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 66.44 MW | 66.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 44.29 MW | 44.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 11.07 MW | 11.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 5.39 MW | 5.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 43.19 MW | 43.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 28.79 MW | 28.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 22.15 MW | 22.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 55.37 MW | 55.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 37.09 MW | 37.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 5.13 MW | 5.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 14.17 MW | 14.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.81 MW | 0.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 5.15 MW | 5.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 21.48 MW | 21.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 11.74 MW | 11.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 13.62 MW | 13.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 9.08 MW | 9.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 8.3 MW | 8.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 5.54 MW | 5.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 45.08 MW | 45.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 21.81 MW | 21.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 33.45 MW | 33.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 22.3 MW | 22.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 31.71 MW | 31.71 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 21.18 MW | 21.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 53.51 MW | 53.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 35.67 MW | 35.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.92 MW | 8.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.34 MW | 4.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 34.78 MW | 34.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 23.19 MW | 23.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 17.84 MW | 17.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 44.59 MW | 44.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 29.88 MW | 29.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 4.13 MW | 4.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 11.42 MW | 11.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.65 MW | 0.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 17.3 MW | 17.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.97 MW | 10.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 7.31 MW | 7.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.69 MW | 6.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.46 MW | 4.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961791 | AG1-021 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961792 | AG1-021 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961891 | AG1-030 C | 50/50 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961892 | AG1-030 E | 50/50 | 22.44 MW | 22.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963171 | AG1-166 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963172 | AG1-166 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963181 | AG1-167 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963182 | AG1-167 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963191 | AG1-168 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963192 | AG1-168 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963201 | AG1-169 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963202 | AG1-169 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963211 | AG1-170 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963212 | AG1-170 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963301 | AG1-179 C | Adder | 3.09 MW | 2.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963311 | AG1-180 | Adder | 1.5 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963321 | AG1-181 C O1 | 50/50 | 28.68 MW | 28.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963361 | AG1-185 O1 | 50/50 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964111 | AG1-272 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964112 | AG1-272 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964121 | AG1-273 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964122 | AG1-273 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964131 | AG1-274 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964132 | AG1-274 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964241 | AG1-285 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964242 | AG1-285 E O1 | 50/50 | 10.46 MW | 10.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964791 | AG1-342 C | Adder | 2.21 MW | 1.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964792 | AG1-342 E | Adder | 1.74 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965191 | AG1-384 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965192 | AG1-384 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965591 | AG1-427 C | 50/50 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965592 | AG1-427 E | 50/50 | 10.05 MW | 10.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965601 | AG1-428 C O2 | Adder | 2.58 MW | 2.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965602 | AG1-428 E O2 | Adder | 1.72 MW | 1.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965641 | AG1-432 C O1 | 50/50 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965642 | AG1-432 E O1 | 50/50 | 44.61 MW | 44.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965721 | AG1-440 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965722 | AG1-440 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965731 | AG1-441 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965732 | AG1-441 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965771 | AG1-445 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965781 | AG1-446 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965831 | AG1-451 | 50/50 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313853 | 3PONTONDP | 50/50 | 1.65 MW | 1.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314429 | 3JTRSVLE | 50/50 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314713 | 3PAMPLIN | 50/50 | 4.39 MW | 4.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315159 | 1KERR 2 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315160 | 1KERR 3 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315161 | 1KERR 4 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315162 | 1KERR 5 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936265 | AD2-033 C | 50/50 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936266 | AD2-033 E | 50/50 | 14.44 MW | 14.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942461 | AE2-259 C O1 | 50/50 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942462 | AE2-259 E O1 | 50/50 | 22.31 MW | 22.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958801 | AF2-171 C | 50/50 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958802 | AF2-171 E | 50/50 | 24.61 MW | 24.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959311 | AF2-222 C | 50/50 | 31.81 MW | 31.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959312 | AF2-222 E | 50/50 | 21.32 MW | 21.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315163 | 1KERR 6 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 316131 | AB2-060 C | 50/50 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924162 | AB2-060 E OP | 50/50 | 4.68 MW | 4.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925611 | AC1-036 C | 50/50 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925612 | AC1-036 E | 50/50 | 2.81 MW | 2.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938371 | AE1-056 C | 50/50 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938372 | AE1-056 E | 50/50 | 9.57 MW | 9.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939181 | AE1-148 C | 50/50 | 6.23 MW | 6.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939182 | AE1-148 E | 50/50 | 4.16 MW | 4.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 940661 | AE2-053 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946301 | AF1-294 C | 50/50 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946302 | AF1-294 E | 50/50 | 6.76 MW | 6.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958211 | AF2-115 C | 50/50 | 6.18 MW | 6.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958212 | AF2-115 E | 50/50 | 4.12 MW | 4.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962561 | AG1-105 C O1 | 50/50 | 5.47 MW | 5.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962562 | AG1-105 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313527 | AB2-043 C | 50/50 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924022 | AB2-043 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961791 | AG1-021 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961792 | AG1-021 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961891 | AG1-030 C | 50/50 | 11.84 MW | 11.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961892 | AG1-030 E | 50/50 | 7.89 MW | 7.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963171 | AG1-166 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963172 | AG1-166 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963181 | AG1-167 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963182 | AG1-167 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963191 | AG1-168 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963192 | AG1-168 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963201 | AG1-169 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963202 | AG1-169 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963211 | AG1-170 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963212 | AG1-170 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963301 | AG1-179 C | Adder | 3.43 MW | 2.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963311 | AG1-180 | Adder | 1.67 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963321 | AG1-181 C O1 | 50/50 | 16.16 MW | 16.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963361 | AG1-185 O1 | 50/50 | 7.82 MW | 7.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964111 | AG1-272 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964121 | AG1-273 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964131 | AG1-274 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964241 | AG1-285 C O1 | 50/50 | 13.75 MW | 13.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964242 | AG1-285 E O1 | 50/50 | 9.16 MW | 9.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964791 | AG1-342 C | Adder | 2.86 MW | 2.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964792 | AG1-342 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965191 | AG1-384 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965591 | AG1-427 C | 50/50 | 12.98 MW | 12.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965592 | AG1-427 E | 50/50 | 8.67 MW | 8.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965601 | AG1-428 C O2 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965602 | AG1-428 E O2 | Adder | 1.91 MW | 1.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965641 | AG1-432 C O1 | Adder | 8.86 MW | 7.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965642 | AG1-432 E O1 | Adder | 5.91 MW | 5.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965721 | AG1-440 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965722 | AG1-440 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965731 | AG1-441 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965732 | AG1-441 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965771 | AG1-445 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965781 | AG1-446 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965831 | AG1-451 | Adder | 1.48 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313853 | 3PONTONDP | Adder | 0.48 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 314713 | 3PAMPLIN | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925785 | AC1-054 E | 50/50 | 7.3 MW | 7.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926274 | AC1-105 E | Adder | 1.4 MW | 1.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936265 | AD2-033 C | 50/50 | 12.62 MW | 12.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936266 | AD2-033 E | 50/50 | 8.41 MW | 8.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.43 MW | 3.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 2.95 MW | 2.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.81 MW | 10.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.21 MW | 7.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 14.91 MW | 14.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 9.99 MW | 9.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316118 | AC1-105 C | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316129 | AC1-054 C | 50/50 | 15.84 MW | 15.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316131 | AB2-060 C | 50/50 | 1.77 MW | 1.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.9 MW | 4.9 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.43 MW | 1.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.16 MW | 3.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.27 MW | 1.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C | 50/50 | 17.48 MW | 17.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E | 50/50 | 11.65 MW | 11.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.47 MW | 6.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.96 MW | 1.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962561 | AG1-105 C O1 | 50/50 | 6.82 MW | 6.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962562 | AG1-105 E O1 | 50/50 | 4.55 MW | 4.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313527 | AB2-043 C | 50/50 | 0.63 MW | 0.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.44 MW | 0.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.06 MW | 0.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.81 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.24 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.47 MW | 0.47 MW |
| Details for 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.34 MW | 71.34 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.56 MW | 47.56 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 14.97 MW | 14.97 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.24 MW | 7.24 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.18 MW | 62.18 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.46 MW | 41.46 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.36 MW | 10.36 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 69.6 MW | 69.6 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 46.4 MW | 46.4 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.09 MW | 31.09 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.73 MW | 20.73 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.7 MW | 28.7 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.14 MW | 19.14 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.45 MW | 19.45 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.03 MW | 13.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 9.18 MW | 9.18 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 25.35 MW | 25.35 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.54 MW | 14.54 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.94 MW | 7.94 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.35 MW | 12.35 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.04 MW | 0.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.03 MW | 0.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.07 MW | 0.07 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.23 MW | 0.23 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.09 MW | 0.09 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 86.08 MW | 86.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 41.65 MW | 41.65 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961791 | AG1-021 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961891 | AG1-030 C | Adder | 12.01 MW | 10.21 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961892 | AG1-030 E | Adder | 8.0 MW | 6.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963171 | AG1-166 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963181 | AG1-167 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963191 | AG1-168 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963201 | AG1-169 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963211 | AG1-170 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963301 | AG1-179 C | Adder | 3.75 MW | 3.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963311 | AG1-180 | Adder | 1.83 MW | 1.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963321 | AG1-181 C O1 | 50/50 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963361 | AG1-185 O1 | 50/50 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964111 | AG1-272 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964112 | AG1-272 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964121 | AG1-273 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964122 | AG1-273 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964131 | AG1-274 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964132 | AG1-274 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964241 | AG1-285 C O1 | 50/50 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964242 | AG1-285 E O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964791 | AG1-342 C | 50/50 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964792 | AG1-342 E | 50/50 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966691 | AG1-539 C | 50/50 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966692 | AG1-539 E | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966761 | AG1-547 C | Adder | 4.41 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966762 | AG1-547 E | Adder | 2.37 MW | 2.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965191 | AG1-384 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965192 | AG1-384 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965591 | AG1-427 C | 50/50 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965592 | AG1-427 E | 50/50 | 9.52 MW | 9.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965601 | AG1-428 C O2 | Adder | 3.13 MW | 2.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965602 | AG1-428 E O2 | Adder | 2.08 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965721 | AG1-440 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965731 | AG1-441 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965771 | AG1-445 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965781 | AG1-446 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 314713 | 3PAMPLIN | Adder | 0.99 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315156 | 1HALLBR1 | 50/50 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315159 | 1KERR 2 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315161 | 1KERR 4 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315162 | 1KERR 5 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925785 | AC1-054 E | Adder | 2.15 MW | 1.82 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926023 | AC1-080 C | 50/50 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926274 | AC1-105 E | 50/50 | 8.2 MW | 8.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926646 | AC1-145 E | Adder | 2.31 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927261 | AC1-222 C | 50/50 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927262 | AC1-222 E | 50/50 | 11.51 MW | 11.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934311 | AD1-055 C | 50/50 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934312 | AD1-055 E | 50/50 | 2.16 MW | 2.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936265 | AD2-033 C | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936266 | AD2-033 E | 50/50 | 9.0 MW | 9.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942671 | AE2-283 C | Adder | 5.37 MW | 4.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942672 | AE2-283 E | Adder | 2.82 MW | 2.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942751 | AE2-291 C | 50/50 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942752 | AE2-291 E | 50/50 | 12.81 MW | 12.81 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942761 | AE2-292 C O1 | 50/50 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942762 | AE2-292 E O1 | 50/50 | 15.96 MW | 15.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958801 | AF2-171 C | Adder | 10.66 MW | 9.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958802 | AF2-171 E | Adder | 7.1 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959311 | AF2-222 C | 50/50 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959312 | AF2-222 E | 50/50 | 10.48 MW | 10.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960061 | AF2-297 C | 50/50 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960062 | AF2-297 E | 50/50 | 18.23 MW | 18.23 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961121 | AF2-403 | Adder | 1.08 MW | 0.92 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315164 | 1KERR 7 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315266 | 1PLYWOOD A | 50/50 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316118 | AC1-105 C | 50/50 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316129 | AC1-054 C | Adder | 4.66 MW | 3.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316131 | AB2-060 C | 50/50 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924162 | AB2-060 E OP | 50/50 | 5.43 MW | 5.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924301 | AB2-077 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924302 | AB2-077 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924311 | AB2-078 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924312 | AB2-078 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924321 | AB2-079 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924322 | AB2-079 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925612 | AC1-036 E | 50/50 | 1.51 MW | 1.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925661 | AC1-042 C | Adder | 2.16 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925662 | AC1-042 E | Adder | 3.53 MW | 3.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938371 | AE1-056 C | Adder | 3.93 MW | 3.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938372 | AE1-056 E | Adder | 2.15 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939181 | AE1-148 C | 50/50 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939182 | AE1-148 E | 50/50 | 6.04 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 940661 | AE2-053 O1 | 50/50 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941801 | AE2-185 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941802 | AE2-185 E | Adder | 3.26 MW | 2.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941821 | AE2-187 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941822 | AE2-187 E | Adder | 2.17 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946301 | AF1-294 C | Adder | 2.89 MW | 2.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946302 | AF1-294 E | Adder | 1.93 MW | 1.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958211 | AF2-115 C | Adder | 1.76 MW | 1.5 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962561 | AG1-105 C O1 | 50/50 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962562 | AG1-105 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313527 | AB2-043 C | 50/50 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924022 | AB2-043 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316123 | AC1-075 C | 50/50 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925997 | AC1-075 E | 50/50 | 8.22 MW | 8.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926024 | AC1-080 E | 50/50 | 2.73 MW | 2.73 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961891 | AG1-030 C | Adder | 6.32 MW | 5.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961892 | AG1-030 E | Adder | 4.21 MW | 3.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962561 | AG1-105 C O1 | Adder | 3.79 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962562 | AG1-105 E O1 | Adder | 2.53 MW | 2.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | 50/50 | 12.87 MW | 12.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | 50/50 | 26.91 MW | 26.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 69.62 MW | 69.62 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 46.41 MW | 46.41 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.93 MW | 0.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961891 | AG1-030 C | Adder | 5.6 MW | 4.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961892 | AG1-030 E | Adder | 3.74 MW | 3.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961941 | AG1-037 C | Adder | 0.32 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961942 | AG1-037 E | Adder | 0.22 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962331 | AG1-082 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962332 | AG1-082 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962341 | AG1-083 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962342 | AG1-083 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963301 | AG1-179 C | Adder | 2.95 MW | 2.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963311 | AG1-180 | Adder | 1.44 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963321 | AG1-181 C O1 | Adder | 7.68 MW | 6.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963361 | AG1-185 O1 | Adder | 3.72 MW | 3.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964111 | AG1-272 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964112 | AG1-272 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964121 | AG1-273 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964122 | AG1-273 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964131 | AG1-274 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964132 | AG1-274 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964241 | AG1-285 C O1 | Adder | 6.55 MW | 5.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964242 | AG1-285 E O1 | Adder | 4.37 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964801 | AG1-343 C | 50/50 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964802 | AG1-343 E | 50/50 | 7.66 MW | 7.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966811 | AG1-552 C | 50/50 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966812 | AG1-552 E | 50/50 | 2.2 MW | 2.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965191 | AG1-384 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965192 | AG1-384 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965291 | AG1-394 C | 50/50 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965292 | AG1-394 E | 50/50 | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965591 | AG1-427 C | Adder | 6.18 MW | 5.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965592 | AG1-427 E | Adder | 4.13 MW | 3.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965602 | AG1-428 E O2 | Adder | 1.64 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965721 | AG1-440 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965722 | AG1-440 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965731 | AG1-441 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965732 | AG1-441 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965771 | AG1-445 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965781 | AG1-446 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 313506 | AB1-173 C OP | 50/50 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314572 | 3EMPORIA | Adder | 0.31 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315126 | 1ROARAP2 | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315128 | 1ROARAP4 | 50/50 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315159 | 1KERR 2 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315160 | 1KERR 3 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315161 | 1KERR 4 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315162 | 1KERR 5 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 918492 | AA1-063AE OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919692 | AA2-053 E OP | 50/50 | 7.76 MW | 7.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919702 | AA2-057 E OP | Adder | 2.0 MW | 1.7 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920042 | AA2-088 E OP | 50/50 | 18.01 MW | 18.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920592 | AA2-165 E | Adder | 0.28 MW | 0.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925785 | AC1-054 E | 50/50 | 5.44 MW | 5.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926201 | AC1-098 C | Adder | 5.16 MW | 4.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926202 | AC1-098 E | Adder | 3.08 MW | 2.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926211 | AC1-099 C | Adder | 1.73 MW | 1.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926212 | AC1-099 E | Adder | 1.02 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927145 | AC1-208 C | 50/50 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927146 | AC1-208 E | 50/50 | 4.49 MW | 4.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936265 | AD2-033 C | Adder | 6.0 MW | 5.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936266 | AD2-033 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943171 | AE2-346 C | Adder | 0.9 MW | 0.77 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943172 | AE2-346 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959311 | AF2-222 C | Adder | 7.08 MW | 6.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959312 | AF2-222 E | Adder | 4.74 MW | 4.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960081 | AF2-299 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315163 | 1KERR 6 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315164 | 1KERR 7 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315606 | 3AA2-053SOLA | 50/50 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316088 | AB2-174 E | 50/50 | 7.19 MW | 7.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316129 | AC1-054 C | 50/50 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316140 | AB2-099 C | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316141 | AB2-099 E | Adder | 0.16 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 900672 | V4-068 E | 50/50 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 917332 | Z2-043 E | Adder | 0.6 MW | 0.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923573 | AB1-173 E OP | 50/50 | 4.34 MW | 4.34 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923991 | AB2-040 C O1 | 50/50 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923992 | AB2-040 E O1 | 50/50 | 8.15 MW | 8.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924162 | AB2-060 E OP | Adder | 2.34 MW | 1.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924301 | AB2-077 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924302 | AB2-077 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924311 | AB2-078 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924312 | AB2-078 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924321 | AB2-079 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924322 | AB2-079 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925612 | AC1-036 E | Adder | 0.68 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932631 | AC2-084 C | Adder | 7.36 MW | 6.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932632 | AC2-084 E | Adder | 3.62 MW | 3.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939181 | AE1-148 C | Adder | 7.6 MW | 6.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939182 | AE1-148 E | Adder | 5.06 MW | 4.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 940661 | AE2-053 O1 | Adder | 2.81 MW | 2.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946281 | AF1-292 C | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957521 | AF2-046 C | 50/50 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957522 | AF2-046 E | 50/50 | 10.06 MW | 10.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314589 | 3MURPHYS | 50/50 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315608 | 3AA2-088SOLA | 50/50 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316087 | AB2-174 C | 50/50 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962561 | AG1-105 C O1 | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962562 | AG1-105 E O1 | Adder | 2.24 MW | 1.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961681 | AG1-008 C | 50/50 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961682 | AG1-008 E | 50/50 | 10.02 MW | 10.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924022 | AB2-043 E O1 | Adder | 1.57 MW | 1.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961791 | AG1-021 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961891 | AG1-030 C | 50/50 | 11.7 MW | 11.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961892 | AG1-030 E | 50/50 | 7.8 MW | 7.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963171 | AG1-166 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963181 | AG1-167 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963191 | AG1-168 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963201 | AG1-169 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963211 | AG1-170 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963301 | AG1-179 C | Adder | 3.17 MW | 2.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963311 | AG1-180 | Adder | 1.55 MW | 1.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963321 | AG1-181 C O1 | 50/50 | 15.97 MW | 15.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963361 | AG1-185 O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964111 | AG1-272 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964121 | AG1-273 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964131 | AG1-274 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964241 | AG1-285 C O1 | 50/50 | 13.59 MW | 13.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964242 | AG1-285 E O1 | 50/50 | 9.06 MW | 9.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964791 | AG1-342 C | Adder | 2.83 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964792 | AG1-342 E | Adder | 2.22 MW | 1.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965191 | AG1-384 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965591 | AG1-427 C | 50/50 | 12.83 MW | 12.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965592 | AG1-427 E | 50/50 | 8.57 MW | 8.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965601 | AG1-428 C O2 | Adder | 2.65 MW | 2.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965602 | AG1-428 E O2 | Adder | 1.76 MW | 1.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965641 | AG1-432 C O1 | Adder | 8.76 MW | 7.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965642 | AG1-432 E O1 | Adder | 5.84 MW | 4.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965721 | AG1-440 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965722 | AG1-440 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965731 | AG1-441 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965732 | AG1-441 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965771 | AG1-445 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965781 | AG1-446 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965831 | AG1-451 | Adder | 1.46 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 314713 | 3PAMPLIN | Adder | 1.03 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315159 | 1KERR 2 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315160 | 1KERR 3 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315161 | 1KERR 4 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315162 | 1KERR 5 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 926274 | AC1-105 E | Adder | 1.38 MW | 1.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936265 | AD2-033 C | 50/50 | 12.47 MW | 12.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936266 | AD2-033 E | 50/50 | 8.31 MW | 8.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942461 | AE2-259 C O1 | Adder | 4.38 MW | 3.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942462 | AE2-259 E O1 | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958801 | AF2-171 C | 50/50 | 10.69 MW | 10.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958802 | AF2-171 E | 50/50 | 7.13 MW | 7.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959311 | AF2-222 C | 50/50 | 14.73 MW | 14.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959312 | AF2-222 E | 50/50 | 9.87 MW | 9.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315163 | 1KERR 6 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315164 | 1KERR 7 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316118 | AC1-105 C | Adder | 2.89 MW | 2.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316131 | AB2-060 C | 50/50 | 1.75 MW | 1.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924162 | AB2-060 E OP | 50/50 | 4.84 MW | 4.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924301 | AB2-077 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924302 | AB2-077 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924311 | AB2-078 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924312 | AB2-078 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924321 | AB2-079 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924322 | AB2-079 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925611 | AC1-036 C | 50/50 | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925612 | AC1-036 E | 50/50 | 1.42 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938371 | AE1-056 C | Adder | 4.11 MW | 3.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938372 | AE1-056 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939181 | AE1-148 C | 50/50 | 17.39 MW | 17.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939182 | AE1-148 E | 50/50 | 11.59 MW | 11.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 940661 | AE2-053 O1 | 50/50 | 6.44 MW | 6.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946301 | AF1-294 C | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946302 | AF1-294 E | Adder | 1.94 MW | 1.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958211 | AF2-115 C | Adder | 1.77 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962561 | AG1-105 C O1 | 50/50 | 6.74 MW | 6.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962562 | AG1-105 E O1 | 50/50 | 4.5 MW | 4.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.34 MW | 1.34 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
Light Load Analysis
The Queue Project was evaluated as a 0.0 MW (Capacity 48.91 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 125.19 % | 128.19 % | 269.78 | B | 345.83 | 7.98 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 119.6 % | 121.08 % | 678.68 | B | 821.75 | 14.26 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 118.56 % | 120.05 % | 678.68 | B | 814.76 | 14.26 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 105.01 % | 106.53 % | 661.76 | B | 704.97 | 13.04 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 101.49 % | 102.73 % | 661.76 | B | 679.83 | 14.08 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 105.02 % | 106.53 % | 661.76 | B | 704.97 | 13.04 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 102.95 % | 104.46 % | 661.76 | B | 691.27 | 13.04 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 99.27 % | 100.5 % | 661.76 | B | 665.07 | 14.08 | |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.03 MW | 1.03 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941281 | AE2-122 C O1 | Adder | 3.34 MW | 2.84 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941282 | AE2-122 E O1 | Adder | 13.48 MW | 11.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941291 | AE2-123 C O1 | Adder | 3.43 MW | 2.92 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941292 | AE2-123 E O1 | Adder | 13.38 MW | 11.38 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941301 | AE2-124 C O1 | Adder | 3.12 MW | 2.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941302 | AE2-124 E O1 | Adder | 13.69 MW | 11.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.09 MW | 1.09 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958502 | AF2-144 E | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964112 | AG1-272 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964122 | AG1-273 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964132 | AG1-274 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 0.18 MW | 0.18 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964792 | AG1-342 E | 80/20 | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965192 | AG1-384 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.94 MW | 2.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944581 | AF1-123 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944582 | AF1-123 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944591 | AF1-124 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944592 | AF1-124 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944601 | AF1-125 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944602 | AF1-125 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 C | 80/20 | 4.34 MW | 4.34 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963362 | AG1-185 E | 80/20 | 3.64 MW | 3.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946293 | AF1-293 BAT | 80/20 | 27.71 MW | 27.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961063 | AF2-397 BAT | 80/20 | 8.65 MW | 8.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965583 | AG1-426 BAT | 80/20 | 14.15 MW | 14.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966253 | AG1-494 BAT | 80/20 | 3.94 MW | 3.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966673 | AG1-537 BAT | 80/20 | 4.39 MW | 4.39 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | 80/20 | 1.14 MW | 1.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961063 | AF2-397 BAT | 80/20 | 25.66 MW | 25.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 1.14 MW | 0.97 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961062 | AF2-397 E | 80/20 | 26.99 MW | 26.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n8245 | Reconductor 115 kV Line #31 | $700,000 | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n7543 | Rebuild 115 kV Line 1045 | $3,445,000 | |
| n7675 | Reconductor 115 kV Line#98 from AD2-033 Tap to Butcher Creek. | $19,220,000 | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n7766 | Rebuild 115 kV Line #1012 From AD2-063 Tap-AG1-181 Tap-Central-Twitty's Creek-AF2-222 Tap-Madsonav | $24,835,000 | |
| n7821 | Wreck and rebuild 115 kV line #1012 from Chase City to AG1-285 Tap | $13,400,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n7819 | Wreck and rebuild 115 kV line #84 from Willis to Farmville to a double circuit. | $20,050,000 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n7667 | Rebuild 115 kV Line #33 from Mt. Laurel -AC1-105 Tap -Sedge Hill. | $16,590,000 | |
| n7826 | Rebuild 115 kV line #84 from Willis Mountain to Pamplin. | $20,730,000 | |
| n7687 | Add additional 230/115 kV transformer at Sedge Hill substation. | $6,000,000 | |
| n7662 | Rebuild 115 kV Line #1034 from AG1-030 Tap to Victoria DP | $9,115,000 | |
| n7688 | Rebuild 115 kV Line #1034 | $3,830,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n7570 | Wreck and Rebuild 230 kV Line #298 From Buckingham to Bremo | $47,675,000 | |
| n6245 | Rebuild 12.76 miles of 230 kV Line 298 from Buckingham to Farmville with 2-768.2 ACSS 250 C. Replace Line Lead, Line Switch, Relay (CT), Wave trap at Farmville terminal | $19,710,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
| (TBD) | Reconductor 5 miles with double 795 ACSS-TW per phase, replace disconnect switches | $22,500,000 | |
| n7083 | For DEV portion, rebuild 2 miles of 230 kV Line 296 from AC1-221 Tap to Persons DEP with 2-795 ACSR. | $3,000,000 | |
| n6215 | Rebuild 2 miles of the AC1-221 Tap – Sedge Hill 230 kV line#33. | $3,000,000 | |
| n7823 | Wreck and rebuild 115 kV line#1012 from AG1-427 Tap to AG1-285 Tap | $3,150,000 | |
Attachments
Download all tables in report
| Uprate Chain | |||||
|---|---|---|---|---|---|
| Project | Project Status | MFO | MWE | MWC | Disposition |
| AG1-181 | Active | 150.0 | 150.0 | 101.09 | Transition Cycle 1 |
| AG1-185 | Active | 150.0 | 0.0 | 48.91 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-185 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.