AG1-179 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:53
Brunswick-Gasburg 69 kV
33.66 MW Capacity / 50.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-179 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Sussex County, Virginia. The installed facilities will have a total capability of 50.0 MW with 33.66 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-179 |
| Project Name | Brunswick-Gasburg 69 kV |
| Developer Name | Merchant Solar, LLC |
| State | Virginia |
| County | Sussex |
| Transmission Owner | Dominion |
| MFO | 50.0 MW |
| MWE | 50.0 MW |
| MWC | 33.66 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-179 will interconnect with the Dominion transmission system. The POI will be a newly constructed 69 kV three breaker ring bus located on the line between the Brunswick substation and Gasburg substation.
Summer Peak Analysis
The Queue Project was evaluated as a 50.0 MW (Capacity 33.66 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 235-A
CONTINGENCY 'DVP_P1-2: LN 235-A' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Single | AC | 155.57 % | 157.66 % | 182.64 | B | 287.94 | 3.87 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 2201
CONTINGENCY 'DVP_P1-2: LN 2201' OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD 230.0 - 6CLUBHSE 230.0 END |
Single | AC | 150.53 % | 157.61 % | 182.64 | B | 287.86 | 12.96 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 254
CONTINGENCY 'DVP_P1-2: LN 254' OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD 230.0 - 6LAKEVEW 230.0 END |
Single | AC | 139.81 % | 146.74 % | 182.64 | B | 268.01 | 12.97 | |
| DVP |
2BRUNWICK-3BRUNWICK 69.0/115.0 kV Ckt 1 transformer
314782 to 314676 ckt 1 |
DVP_P1-2: LN 132-B
CONTINGENCY 'DVP_P1-2: LN 132-B' OPEN BRANCH FROM BUS 963300 TO BUS 314786 CKT 1 /*AG1-179 TAP 69.0 - 2GASBURG 69.0 OPEN BUS 314786 /*2GASBURG 69.0 END |
Single | AC | -0.48 % | 107.15 % | 31.4 | B | 33.64 | 33.66 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 98.48 % | 106.23 % | 182.64 | B | 194.02 | 14.2 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1' /* Auto-generated /* 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 END |
Single | AC | 98.47 % | 106.2 % | 182.64 | B | 193.97 | 14.2 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 98.46 % | 106.2 % | 182.64 | B | 193.96 | 14.2 | |
| DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 146.21 % | 147.57 % | 375.06 | B | 553.48 | 5.1 | |
| DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 146.18 % | 147.54 % | 375.06 | B | 553.36 | 5.1 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 123.25 % | 124.82 % | 678.68 | B | 847.14 | 10.85 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 124.9 % | 126.28 % | 678.68 | B | 857.05 | 10.85 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 121.73 % | 123.3 % | 678.68 | B | 836.83 | 10.85 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 123.38 % | 124.76 % | 678.68 | B | 846.69 | 10.85 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 111.77 % | 113.44 % | 678.68 | B | 769.87 | 10.85 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 110.25 % | 111.91 % | 678.68 | B | 759.52 | 10.85 | |
| DVP |
AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line
934330 to 313845 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 110.83 % | 112.29 % | 441.8 | B | 496.11 | 6.4 | |
| DVP |
AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line
934330 to 313845 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 110.81 % | 112.27 % | 441.8 | B | 496.01 | 6.4 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
Base Case | Single | AC | 100.29 % | 101.81 % | 678.68 | A | 690.98 | 10.29 | |
| DVP |
6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line
314579 to 934330 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 102.78 % | 104.23 % | 441.8 | B | 460.48 | 6.4 | |
| DVP |
6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line
314579 to 934330 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 102.76 % | 104.21 % | 441.8 | B | 460.39 | 6.4 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
Base Case | Single | AC | 104.06 % | 105.12 % | 678.68 | A | 713.41 | 10.3 | |
| DVP |
AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line
934330 to 313845 ckt 1 |
314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 99.07 % | 100.51 % | 441.8 | B | 444.07 | 6.4 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P1-2: LN 562-B-1
CONTINGENCY 'DVP_P1-2: LN 562-B-1' OPEN BRANCH FROM BUS 940640 TO BUS 314923 CKT 1 /*AE2-051 TAP 500.0 - 8SEPTA 500.0 END |
Single | AC | 99.97 % | 100.49 % | 559.3 | B | 562.05 | 2.9 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 152.67 % | 153.76 % | 221.4 | C | 340.42 | 3.09 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 314835 /*3CAROL_1 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 118.87 % | 120.28 % | 199.0 | B | 239.37 | 3.43 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P4-2: 3202
CONTINGENCY 'DVP_P4-2: 3202' OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1 /*3WELCOTAP 115.0 - 3REEDY C 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1 /*3WELCOTAP 115.0 - 3S BOSTN 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1 /*3WELCOTAP 115.0 - 3WELCO 115.0 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1 /*3SEDGE HILL 115.0 - 3SINAI 115.0 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1 /*3SINAI 115.0 - 3S BOSTN 115.0 OPEN BUS 313852 /*3WELCOTAP 115.0 OPEN BUS 314717 /*3SINAI 115.0 OPEN BUS 314718 /*3S BOSTN 115.0 OPEN BUS 314724 /*3WELCO 115.0 END |
Breaker | AC | 126.85 % | 127.98 % | 279.1 | C | 357.2 | 3.75 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 103.39 % | 104.69 % | 199.0 | B | 208.34 | 3.06 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 103.39 % | 104.69 % | 199.0 | B | 208.33 | 3.06 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 316085 CKT 1 /*3EMPORIA 115.0 - 3IVORY LANE 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 122.46 % | 123.5 % | 288.6 | C | 356.42 | 3.52 | |
| DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
DVP_P4-2: 23872
CONTINGENCY 'DVP_P4-2: 23872' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Breaker | AC | 148.15 % | 149.27 % | 459.0 | C | 685.13 | 5.11 | |
| DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
DVP_P4-2: 238T2002
CONTINGENCY 'DVP_P4-2: 238T2002' OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1 /*6CARSON 230.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1 /*3POE 115.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Breaker | AC | 147.6 % | 148.72 % | 459.0 | C | 682.62 | 5.1 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 14852
CONTINGENCY 'DVP_P4-2: 14852' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 END |
Breaker | AC | 111.33 % | 112.36 % | 288.6 | C | 324.27 | 3.52 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 93T140
CONTINGENCY 'DVP_P4-2: 93T140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Breaker | AC | 113.22 % | 114.03 % | 288.6 | C | 329.08 | 2.95 | |
| DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 126.65 % | 127.52 % | 541.0 | C | 689.88 | 6.08 | |
| DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 126.58 % | 127.44 % | 541.0 | C | 689.47 | 6.08 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90
CONTINGENCY 'DVP_P7-1: LN 22-90' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Tower | AC | 116.95 % | 118.26 % | 199.0 | B | 235.33 | 3.17 | |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961791 | AG1-021 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961891 | AG1-030 C | 80/20 | 37.77 MW | 37.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963171 | AG1-166 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963181 | AG1-167 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963191 | AG1-168 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963201 | AG1-169 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963211 | AG1-170 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963301 | AG1-179 C | 80/20 | 3.87 MW | 3.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963311 | AG1-180 | 80/20 | 1.89 MW | 1.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963321 | AG1-181 C O1 | 80/20 | 32.77 MW | 32.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963361 | AG1-185 O1 | 80/20 | 15.86 MW | 15.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964111 | AG1-272 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964121 | AG1-273 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964131 | AG1-274 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964241 | AG1-285 C O1 | 80/20 | 18.39 MW | 18.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964791 | AG1-342 C | 80/20 | 3.1 MW | 3.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965191 | AG1-384 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965591 | AG1-427 C | 80/20 | 17.61 MW | 17.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965601 | AG1-428 C O2 | 80/20 | 3.23 MW | 3.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965641 | AG1-432 C O1 | 80/20 | 73.68 MW | 73.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965721 | AG1-440 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965731 | AG1-441 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965771 | AG1-445 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965781 | AG1-446 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965831 | AG1-451 | 80/20 | 12.28 MW | 12.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313506 | AB1-173 C OP | 80/20 | 2.2 MW | 2.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314429 | 3JTRSVLE | 80/20 | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314704 | 3LAWRENC | 80/20 | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315158 | 1KERR 1 | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315159 | 1KERR 2 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315160 | 1KERR 3 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315161 | 1KERR 4 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315162 | 1KERR 5 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 927261 | AC1-222 C | 80/20 | 1.32 MW | 1.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 934311 | AD1-055 C | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 936265 | AD2-033 C | 80/20 | 24.79 MW | 24.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 942461 | AE2-259 C O1 | 80/20 | 36.84 MW | 36.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 943901 | AF1-058 C | 80/20 | 0.75 MW | 0.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958801 | AF2-171 C | 80/20 | 41.22 MW | 41.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 959311 | AF2-222 C | 80/20 | 36.05 MW | 36.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960061 | AF2-297 C | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315163 | 1KERR 6 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315164 | 1KERR 7 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315266 | 1PLYWOOD A | 80/20 | 0.63 MW | 0.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316118 | AC1-105 C | 80/20 | 3.19 MW | 3.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316129 | AC1-054 C | 80/20 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316131 | AB2-060 C | 80/20 | 2.02 MW | 2.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924301 | AB2-077 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924311 | AB2-078 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924321 | AB2-079 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 925611 | AC1-036 C | 80/20 | 0.5 MW | 0.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 938371 | AE1-056 C | 80/20 | 19.46 MW | 19.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 939181 | AE1-148 C | 80/20 | 7.77 MW | 7.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 940661 | AE2-053 O1 | 80/20 | 2.88 MW | 2.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946281 | AF1-292 C | 80/20 | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946301 | AF1-294 C | 80/20 | 11.32 MW | 11.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958211 | AF2-115 C | 80/20 | 6.9 MW | 6.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 962561 | AG1-105 C O1 | 80/20 | 7.36 MW | 7.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313527 | AB2-043 C | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.97 MW | 13.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.32 MW | 3.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.07 MW | 4.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.0 MW | 1.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961891 | AG1-030 C | 80/20 | 7.72 MW | 7.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963301 | AG1-179 C | 80/20 | 12.96 MW | 12.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963321 | AG1-181 C O1 | 80/20 | 10.66 MW | 10.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963361 | AG1-185 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964111 | AG1-272 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964121 | AG1-273 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964131 | AG1-274 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964241 | AG1-285 C O1 | 80/20 | 9.13 MW | 9.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964791 | AG1-342 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964801 | AG1-343 C | 80/20 | 2.87 MW | 2.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965191 | AG1-384 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965601 | AG1-428 C O2 | 80/20 | 10.82 MW | 10.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313506 | AB1-173 C OP | 80/20 | 14.92 MW | 14.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315136 | 1ROSEMG1 | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926070 | AC1-086 C | 80/20 | 10.02 MW | 10.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 927145 | AC1-208 C | 80/20 | 5.26 MW | 5.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 934331 | AD1-057 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 936265 | AD2-033 C | 80/20 | 8.32 MW | 8.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 944141 | AF1-082 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958801 | AF2-171 C | 80/20 | 7.02 MW | 7.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 959311 | AF2-222 C | 80/20 | 9.8 MW | 9.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923262 | AB1-132 C OP | 80/20 | 6.8 MW | 6.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923991 | AB2-040 C O1 | 80/20 | 16.25 MW | 16.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 957521 | AF2-046 C | 80/20 | 7.43 MW | 7.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315608 | 3AA2-088SOLA | 80/20 | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316096 | AB2-100 C1 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316098 | AB2-100 C2 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961681 | AG1-008 C | 80/20 | 7.45 MW | 7.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.91 MW | 13.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.92 MW | 4.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.96 MW | 4.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.69 MW | 0.69 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961891 | AG1-030 C | 80/20 | 7.73 MW | 7.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963301 | AG1-179 C | 80/20 | 12.97 MW | 12.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963321 | AG1-181 C O1 | 80/20 | 10.68 MW | 10.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963361 | AG1-185 O1 | 80/20 | 5.17 MW | 5.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964791 | AG1-342 C | 80/20 | 1.95 MW | 1.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964801 | AG1-343 C | 80/20 | 2.88 MW | 2.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965601 | AG1-428 C O2 | 80/20 | 10.83 MW | 10.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313506 | AB1-173 C OP | 80/20 | 14.93 MW | 14.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926070 | AC1-086 C | 80/20 | 10.03 MW | 10.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 927145 | AC1-208 C | 80/20 | 5.27 MW | 5.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 934331 | AD1-057 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 936265 | AD2-033 C | 80/20 | 8.33 MW | 8.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 944141 | AF1-082 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958801 | AF2-171 C | 80/20 | 7.03 MW | 7.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 959311 | AF2-222 C | 80/20 | 9.81 MW | 9.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923262 | AB1-132 C OP | 80/20 | 6.81 MW | 6.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923991 | AB2-040 C O1 | 80/20 | 16.26 MW | 16.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 957521 | AF2-046 C | 80/20 | 7.44 MW | 7.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315608 | 3AA2-088SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961681 | AG1-008 C | 80/20 | 7.46 MW | 7.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.01 MW | 14.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.06 MW | 5.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.05 MW | 5.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.17 MW | 1.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.71 MW | 0.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 2BRUNWICK-3BRUNWICK 69.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 132-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 2BRUNWICK-3BRUNWICK 69.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 132-B | 963301 | AG1-179 C | 80/20 | 33.66 MW | 33.66 MW |
| 2BRUNWICK-3BRUNWICK 69.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 132-B | 963311 | AG1-180 | 80/20 | 16.4 MW | 16.4 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 961791 | AG1-021 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 961891 | AG1-030 C | 80/20 | 8.6 MW | 8.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963171 | AG1-166 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963181 | AG1-167 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963191 | AG1-168 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963201 | AG1-169 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963211 | AG1-170 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963301 | AG1-179 C | 80/20 | 14.2 MW | 14.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963311 | AG1-180 | 80/20 | 6.92 MW | 6.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963321 | AG1-181 C O1 | 80/20 | 11.55 MW | 11.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963361 | AG1-185 O1 | 80/20 | 5.59 MW | 5.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964111 | AG1-272 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964121 | AG1-273 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964131 | AG1-274 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964241 | AG1-285 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964791 | AG1-342 C | 80/20 | 2.17 MW | 2.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 966811 | AG1-552 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965191 | AG1-384 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965291 | AG1-394 C | 80/20 | 0.65 MW | 0.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965591 | AG1-427 C | 80/20 | 9.19 MW | 9.19 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965601 | AG1-428 C O2 | 80/20 | 11.86 MW | 11.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965641 | AG1-432 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965721 | AG1-440 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965731 | AG1-441 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965771 | AG1-445 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965781 | AG1-446 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 313506 | AB1-173 C OP | 80/20 | 15.44 MW | 15.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314429 | 3JTRSVLE | 80/20 | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314572 | 3EMPORIA | 80/20 | 1.34 MW | 1.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315126 | 1ROARAP2 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315158 | 1KERR 1 | 80/20 | 0.27 MW | 0.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 927145 | AC1-208 C | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 936265 | AD2-033 C | 80/20 | 9.0 MW | 9.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 958801 | AF2-171 C | 80/20 | 7.93 MW | 7.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 959311 | AF2-222 C | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 960081 | AF2-299 C | 80/20 | 8.93 MW | 8.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316118 | AC1-105 C | 80/20 | 2.34 MW | 2.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316129 | AC1-054 C | 80/20 | 4.75 MW | 4.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 923991 | AB2-040 C O1 | 80/20 | 16.82 MW | 16.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924301 | AB2-077 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924311 | AB2-078 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924321 | AB2-079 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 938371 | AE1-056 C | 80/20 | 3.09 MW | 3.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 939181 | AE1-148 C | 80/20 | 5.97 MW | 5.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 940661 | AE2-053 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 946281 | AF1-292 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 946301 | AF1-294 C | 80/20 | 2.15 MW | 2.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 958211 | AF2-115 C | 80/20 | 1.31 MW | 1.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315607 | 3AA1-063SOLA | 80/20 | 0.77 MW | 0.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315608 | 3AA2-088SOLA | 80/20 | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 962561 | AG1-105 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 313527 | AB2-043 C | 80/20 | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.41 MW | 0.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.23 MW | 3.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.99 MW | 2.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.67 MW | 0.67 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 961791 | AG1-021 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 961891 | AG1-030 C | 80/20 | 8.6 MW | 8.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963171 | AG1-166 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963181 | AG1-167 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963191 | AG1-168 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963201 | AG1-169 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963211 | AG1-170 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963301 | AG1-179 C | 80/20 | 14.2 MW | 14.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963311 | AG1-180 | 80/20 | 6.92 MW | 6.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963321 | AG1-181 C O1 | 80/20 | 11.55 MW | 11.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963361 | AG1-185 O1 | 80/20 | 5.59 MW | 5.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964111 | AG1-272 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964121 | AG1-273 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964131 | AG1-274 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964241 | AG1-285 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964791 | AG1-342 C | 80/20 | 2.17 MW | 2.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966811 | AG1-552 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965191 | AG1-384 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965291 | AG1-394 C | 80/20 | 0.65 MW | 0.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965591 | AG1-427 C | 80/20 | 9.19 MW | 9.19 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965601 | AG1-428 C O2 | 80/20 | 11.86 MW | 11.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965641 | AG1-432 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965721 | AG1-440 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965731 | AG1-441 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965771 | AG1-445 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965781 | AG1-446 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 313506 | AB1-173 C OP | 80/20 | 15.44 MW | 15.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314429 | 3JTRSVLE | 80/20 | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314572 | 3EMPORIA | 80/20 | 1.34 MW | 1.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315126 | 1ROARAP2 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315158 | 1KERR 1 | 80/20 | 0.27 MW | 0.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927145 | AC1-208 C | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936265 | AD2-033 C | 80/20 | 9.0 MW | 9.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958801 | AF2-171 C | 80/20 | 7.93 MW | 7.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 959311 | AF2-222 C | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 960081 | AF2-299 C | 80/20 | 8.93 MW | 8.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315266 | 1PLYWOOD A | 80/20 | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316118 | AC1-105 C | 80/20 | 2.34 MW | 2.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316129 | AC1-054 C | 80/20 | 4.75 MW | 4.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 923991 | AB2-040 C O1 | 80/20 | 16.82 MW | 16.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924301 | AB2-077 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924311 | AB2-078 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924321 | AB2-079 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 938371 | AE1-056 C | 80/20 | 3.09 MW | 3.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 939181 | AE1-148 C | 80/20 | 5.97 MW | 5.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 940661 | AE2-053 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 946281 | AF1-292 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 946301 | AF1-294 C | 80/20 | 2.15 MW | 2.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958211 | AF2-115 C | 80/20 | 1.31 MW | 1.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315607 | 3AA1-063SOLA | 80/20 | 0.77 MW | 0.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962561 | AG1-105 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 313527 | AB2-043 C | 80/20 | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.41 MW | 0.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.23 MW | 3.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.99 MW | 2.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.67 MW | 0.67 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 8.6 MW | 8.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 14.2 MW | 14.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 6.92 MW | 6.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 11.55 MW | 11.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 5.59 MW | 5.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 2.17 MW | 2.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965291 | AG1-394 C | 80/20 | 0.65 MW | 0.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 9.19 MW | 9.19 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 11.86 MW | 11.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 15.44 MW | 15.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 1.34 MW | 1.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.27 MW | 0.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 9.0 MW | 9.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 7.93 MW | 7.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 8.93 MW | 8.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 2.34 MW | 2.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.75 MW | 4.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 16.82 MW | 16.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 3.09 MW | 3.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 5.97 MW | 5.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 2.15 MW | 2.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 1.31 MW | 1.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.77 MW | 0.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 315608 | 3AA2-088SOLA | 80/20 | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.41 MW | 0.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.23 MW | 3.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.99 MW | 2.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.67 MW | 0.67 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961671 | AG1-007 C | 80/20 | 0.55 MW | 0.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 5.1 MW | 5.1 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 2.49 MW | 2.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 4.26 MW | 4.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965711 | AG1-439 C O1 | 80/20 | 10.52 MW | 10.52 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965761 | AG1-444 O1 | 80/20 | 5.61 MW | 5.61 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 1.88 MW | 1.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.46 MW | 0.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.1 MW | 0.1 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.32 MW | 0.32 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 6.49 MW | 6.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 4.03 MW | 4.03 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 3.04 MW | 3.04 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 67.5 MW | 67.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 19.73 MW | 19.73 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | Adder | -0.97 MW | -0.83 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.49 MW | 3.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315601 | 1CONETOE2SOL | 80/20 | 0.63 MW | 0.63 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316020 | AB2-059 C OP | 80/20 | 1.35 MW | 1.35 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | Adder | -3.61 MW | -3.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 1.15 MW | 1.15 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 45.84 MW | 45.84 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 5.13 MW | 5.13 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 3.36 MW | 3.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.07 MW | 2.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 38.46 MW | 38.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 32.19 MW | 32.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 0.77 MW | 0.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C | 80/20 | 7.36 MW | 7.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 18.77 MW | 18.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.08 MW | 1.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.43 MW | 18.43 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.11 MW | 6.11 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.33 MW | 6.33 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.19 MW | 1.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961671 | AG1-007 C | 80/20 | 0.55 MW | 0.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 5.1 MW | 5.1 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 2.49 MW | 2.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 4.26 MW | 4.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965711 | AG1-439 C O1 | 80/20 | 10.52 MW | 10.52 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965761 | AG1-444 O1 | 80/20 | 5.61 MW | 5.61 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 1.88 MW | 1.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.46 MW | 0.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.1 MW | 0.1 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.32 MW | 0.32 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 6.49 MW | 6.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 4.03 MW | 4.03 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 3.04 MW | 3.04 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 67.5 MW | 67.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 19.73 MW | 19.73 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | Adder | -0.97 MW | -0.83 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.49 MW | 3.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.63 MW | 0.63 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.35 MW | 1.35 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | Adder | -3.61 MW | -3.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.15 MW | 1.15 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 45.84 MW | 45.84 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 5.13 MW | 5.13 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 3.36 MW | 3.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.07 MW | 2.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 38.46 MW | 38.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 32.19 MW | 32.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.77 MW | 0.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C | 80/20 | 7.36 MW | 7.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 18.77 MW | 18.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.08 MW | 1.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.43 MW | 18.43 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.11 MW | 6.11 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.33 MW | 6.33 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.19 MW | 1.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 4.73 MW | 4.73 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 37.04 MW | 37.04 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 4.74 MW | 4.74 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 37.04 MW | 37.04 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.29 MW | 10.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.55 MW | 10.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.27 MW | 5.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.5 MW | 20.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.07 MW | 7.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.07 MW | 7.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.93 MW | 10.93 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.19 MW | 39.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.58 MW | 10.58 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.24 MW | 8.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.34 MW | 8.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.44 MW | 1.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.61 MW | 26.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.47 MW | 6.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.51 MW | 9.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.14 MW | 63.14 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.85 MW | 52.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314435 | 6SAPONY | 80/20 | 1.74 MW | 1.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 | 80/20 | 11.6 MW | 11.6 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965281 | AG1-393 C | 80/20 | 8.87 MW | 8.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.99 MW | 1.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.12 MW | 33.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.81 MW | 10.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.27 MW | 11.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.64 MW | 2.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| Details for 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 4.73 MW | 4.73 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 4.74 MW | 4.74 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.3 MW | 10.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.56 MW | 10.56 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.28 MW | 5.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.51 MW | 20.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.08 MW | 7.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.08 MW | 7.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.94 MW | 10.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.2 MW | 39.2 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.02 MW | 7.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.59 MW | 10.59 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.25 MW | 8.25 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.28 MW | 1.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.35 MW | 8.35 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.45 MW | 1.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.62 MW | 26.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.48 MW | 6.48 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.52 MW | 9.52 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.15 MW | 63.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.86 MW | 52.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.19 MW | 33.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.91 MW | 10.91 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.33 MW | 11.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.65 MW | 2.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.13 MW | 2.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| Details for AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 4.73 MW | 4.73 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 37.04 MW | 37.04 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314563 6CLUBHSE 230 940480 AE2-033 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 963041 | AG1-153 C | 80/20 | 1.59 MW | 1.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 963111 | AG1-160 C | 80/20 | 1.61 MW | 1.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 963301 | AG1-179 C | 80/20 | 2.9 MW | 2.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 963311 | AG1-180 | 80/20 | 1.41 MW | 1.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 966811 | AG1-552 C | 80/20 | 0.89 MW | 0.89 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965601 | AG1-428 C O2 | 80/20 | 2.42 MW | 2.42 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965811 | AG1-449 | 80/20 | 6.66 MW | 6.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 966361 | AG1-505 C | 80/20 | 4.69 MW | 4.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 966371 | AG1-506 C | 80/20 | 4.69 MW | 4.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 966621 | AG1-532 C | 80/20 | 0.87 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 313506 | AB1-173 C OP | 80/20 | 3.7 MW | 3.7 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 313719 | 3CHESTNUT | 80/20 | 0.43 MW | 0.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 314572 | 3EMPORIA | 80/20 | 0.26 MW | 0.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 314623 | 3WITAKRS | 80/20 | 0.08 MW | 0.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 314704 | 3LAWRENC | 80/20 | 0.17 MW | 0.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315126 | 1ROARAP2 | 80/20 | 0.61 MW | 0.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315128 | 1ROARAP4 | 80/20 | 0.58 MW | 0.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315131 | 1EDGECMA | 80/20 | 2.69 MW | 2.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315132 | 1EDGECMB | 80/20 | 2.69 MW | 2.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315136 | 1ROSEMG1 | 80/20 | 1.07 MW | 1.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315137 | 1ROSEMS1 | 80/20 | 0.66 MW | 0.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315138 | 1ROSEMG2 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315139 | 1GASTONA | 80/20 | 1.61 MW | 1.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315158 | 1KERR 1 | 80/20 | 0.13 MW | 0.13 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315159 | 1KERR 2 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315160 | 1KERR 3 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315161 | 1KERR 4 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315162 | 1KERR 5 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 926070 | AC1-086 C | 80/20 | 10.63 MW | 10.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 926201 | AC1-098 C | 80/20 | 2.09 MW | 2.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 926211 | AC1-099 C | 80/20 | 0.7 MW | 0.7 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 927145 | AC1-208 C | 80/20 | 3.29 MW | 3.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 934331 | AD1-057 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 942931 | AE2-313 C | 80/20 | 10.28 MW | 10.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 944011 | AF1-069 C | 80/20 | 3.74 MW | 3.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 944141 | AF1-082 | 80/20 | 0.96 MW | 0.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 960081 | AF2-299 C | 80/20 | 1.62 MW | 1.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315163 | 1KERR 6 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315164 | 1KERR 7 | 80/20 | 0.37 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315606 | 3AA2-053SOLA | 80/20 | 0.62 MW | 0.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316020 | AB2-059 C OP | 80/20 | 0.6 MW | 0.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316129 | AC1-054 C | 80/20 | 2.69 MW | 2.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 922922 | AB1-081 C OP | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 923262 | AB1-132 C OP | 80/20 | 7.22 MW | 7.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 923991 | AB2-040 C O1 | 80/20 | 4.03 MW | 4.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 924301 | AB2-077 C O1 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 924311 | AB2-078 C O1 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 924321 | AB2-079 C O1 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 925591 | AC1-034 C | 80/20 | 2.29 MW | 2.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 932631 | AC2-084 C | 80/20 | 2.98 MW | 2.98 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 939181 | AE1-148 C | 80/20 | 2.8 MW | 2.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 940571 | AE2-044 C | 80/20 | 1.5 MW | 1.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 940661 | AE2-053 O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 941031 | AE2-094 C | 80/20 | 11.44 MW | 11.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 946281 | AF1-292 C | 80/20 | 0.96 MW | 0.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 940481 | AE2-033 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 940641 | AE2-051 C O1 | 80/20 | 5.15 MW | 5.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 946011 | AF1-266 | 80/20 | 12.82 MW | 12.82 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 314435 | 6SAPONY | 80/20 | 0.42 MW | 0.42 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 936761 | AD2-097 C | Adder | -0.79 MW | -0.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.45 MW | 2.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.45 MW | 2.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.45 MW | 2.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.09 MW | 5.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315141 | 1GASTONB | 80/20 | 1.61 MW | 1.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315241 | 1Z1-086 GT1 | 80/20 | 3.15 MW | 3.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315242 | 1Z1-086 GT2 | 80/20 | 3.15 MW | 3.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315243 | 1Z1-086 GT3 | 80/20 | 3.15 MW | 3.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315244 | 1Z1-086 ST | 80/20 | 5.48 MW | 5.48 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 315607 | 3AA1-063SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316087 | AB2-174 C | 80/20 | 0.69 MW | 0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316096 | AB2-100 C1 | 80/20 | 0.74 MW | 0.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316098 | AB2-100 C2 | 80/20 | 0.74 MW | 0.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 316132 | AB2-190 C | Adder | -6.51 MW | -5.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 940541 | AE2-040 | 80/20 | 2.8 MW | 2.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 960331 | AF2-324 C | 80/20 | 2.63 MW | 2.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 962571 | AG1-106 C | 80/20 | 2.96 MW | 2.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 965281 | AG1-393 C | 80/20 | 2.14 MW | 2.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | 313527 | AB2-043 C | 80/20 | 0.16 MW | 0.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.52 MW | 1.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.45 MW | 0.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.26 MW | 27.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.28 MW | 9.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.61 MW | 9.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.31 MW | 2.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.25 MW | 2.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.32 MW | 1.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.81 MW | 1.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 562-B-1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961791 | AG1-021 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961792 | AG1-021 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961891 | AG1-030 C | 50/50 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961892 | AG1-030 E | 50/50 | 22.44 MW | 22.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963171 | AG1-166 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963172 | AG1-166 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963181 | AG1-167 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963182 | AG1-167 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963191 | AG1-168 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963192 | AG1-168 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963201 | AG1-169 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963202 | AG1-169 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963211 | AG1-170 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963212 | AG1-170 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963301 | AG1-179 C | Adder | 3.09 MW | 2.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963311 | AG1-180 | Adder | 1.5 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963321 | AG1-181 C O1 | 50/50 | 28.68 MW | 28.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963361 | AG1-185 O1 | 50/50 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964111 | AG1-272 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964112 | AG1-272 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964121 | AG1-273 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964122 | AG1-273 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964131 | AG1-274 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964132 | AG1-274 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964241 | AG1-285 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964242 | AG1-285 E O1 | 50/50 | 10.46 MW | 10.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964791 | AG1-342 C | Adder | 2.21 MW | 1.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964792 | AG1-342 E | Adder | 1.74 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965191 | AG1-384 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965192 | AG1-384 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965591 | AG1-427 C | 50/50 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965592 | AG1-427 E | 50/50 | 10.05 MW | 10.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965601 | AG1-428 C O2 | Adder | 2.58 MW | 2.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965602 | AG1-428 E O2 | Adder | 1.72 MW | 1.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965641 | AG1-432 C O1 | 50/50 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965642 | AG1-432 E O1 | 50/50 | 44.61 MW | 44.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965721 | AG1-440 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965722 | AG1-440 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965731 | AG1-441 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965732 | AG1-441 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965771 | AG1-445 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965781 | AG1-446 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965831 | AG1-451 | 50/50 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313853 | 3PONTONDP | 50/50 | 1.65 MW | 1.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314429 | 3JTRSVLE | 50/50 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314713 | 3PAMPLIN | 50/50 | 4.39 MW | 4.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315159 | 1KERR 2 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315160 | 1KERR 3 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315161 | 1KERR 4 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315162 | 1KERR 5 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936265 | AD2-033 C | 50/50 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936266 | AD2-033 E | 50/50 | 14.44 MW | 14.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942461 | AE2-259 C O1 | 50/50 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942462 | AE2-259 E O1 | 50/50 | 22.31 MW | 22.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958801 | AF2-171 C | 50/50 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958802 | AF2-171 E | 50/50 | 24.61 MW | 24.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959311 | AF2-222 C | 50/50 | 31.81 MW | 31.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959312 | AF2-222 E | 50/50 | 21.32 MW | 21.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315163 | 1KERR 6 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 316131 | AB2-060 C | 50/50 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924162 | AB2-060 E OP | 50/50 | 4.68 MW | 4.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925611 | AC1-036 C | 50/50 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925612 | AC1-036 E | 50/50 | 2.81 MW | 2.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938371 | AE1-056 C | 50/50 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938372 | AE1-056 E | 50/50 | 9.57 MW | 9.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939181 | AE1-148 C | 50/50 | 6.23 MW | 6.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939182 | AE1-148 E | 50/50 | 4.16 MW | 4.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 940661 | AE2-053 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946301 | AF1-294 C | 50/50 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946302 | AF1-294 E | 50/50 | 6.76 MW | 6.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958211 | AF2-115 C | 50/50 | 6.18 MW | 6.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958212 | AF2-115 E | 50/50 | 4.12 MW | 4.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962561 | AG1-105 C O1 | 50/50 | 5.47 MW | 5.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962562 | AG1-105 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313527 | AB2-043 C | 50/50 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924022 | AB2-043 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961791 | AG1-021 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961792 | AG1-021 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961891 | AG1-030 C | 50/50 | 11.84 MW | 11.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961892 | AG1-030 E | 50/50 | 7.89 MW | 7.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963171 | AG1-166 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963172 | AG1-166 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963181 | AG1-167 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963182 | AG1-167 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963191 | AG1-168 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963192 | AG1-168 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963201 | AG1-169 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963202 | AG1-169 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963211 | AG1-170 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963212 | AG1-170 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963301 | AG1-179 C | Adder | 3.43 MW | 2.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963311 | AG1-180 | Adder | 1.67 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963321 | AG1-181 C O1 | 50/50 | 16.16 MW | 16.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963361 | AG1-185 O1 | 50/50 | 7.82 MW | 7.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964111 | AG1-272 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964121 | AG1-273 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964131 | AG1-274 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964241 | AG1-285 C O1 | 50/50 | 13.75 MW | 13.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964242 | AG1-285 E O1 | 50/50 | 9.16 MW | 9.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964791 | AG1-342 C | Adder | 2.86 MW | 2.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964792 | AG1-342 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965191 | AG1-384 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965591 | AG1-427 C | 50/50 | 12.98 MW | 12.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965592 | AG1-427 E | 50/50 | 8.67 MW | 8.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965601 | AG1-428 C O2 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965602 | AG1-428 E O2 | Adder | 1.91 MW | 1.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965641 | AG1-432 C O1 | Adder | 8.86 MW | 7.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965642 | AG1-432 E O1 | Adder | 5.91 MW | 5.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965721 | AG1-440 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965722 | AG1-440 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965731 | AG1-441 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965732 | AG1-441 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965771 | AG1-445 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965781 | AG1-446 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965831 | AG1-451 | Adder | 1.48 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313853 | 3PONTONDP | Adder | 0.48 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 314713 | 3PAMPLIN | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925785 | AC1-054 E | 50/50 | 7.3 MW | 7.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926274 | AC1-105 E | Adder | 1.4 MW | 1.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936265 | AD2-033 C | 50/50 | 12.62 MW | 12.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936266 | AD2-033 E | 50/50 | 8.41 MW | 8.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.43 MW | 3.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 2.95 MW | 2.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.81 MW | 10.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.21 MW | 7.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 14.91 MW | 14.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 9.99 MW | 9.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316118 | AC1-105 C | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316129 | AC1-054 C | 50/50 | 15.84 MW | 15.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316131 | AB2-060 C | 50/50 | 1.77 MW | 1.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.9 MW | 4.9 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.43 MW | 1.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.16 MW | 3.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.27 MW | 1.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C | 50/50 | 17.48 MW | 17.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E | 50/50 | 11.65 MW | 11.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.47 MW | 6.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.96 MW | 1.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962561 | AG1-105 C O1 | 50/50 | 6.82 MW | 6.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962562 | AG1-105 E O1 | 50/50 | 4.55 MW | 4.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313527 | AB2-043 C | 50/50 | 0.63 MW | 0.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.44 MW | 0.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.06 MW | 0.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.81 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.24 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.47 MW | 0.47 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961791 | AG1-021 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961891 | AG1-030 C | Adder | 12.01 MW | 10.21 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961892 | AG1-030 E | Adder | 8.0 MW | 6.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963171 | AG1-166 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963181 | AG1-167 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963191 | AG1-168 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963201 | AG1-169 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963211 | AG1-170 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963301 | AG1-179 C | Adder | 3.75 MW | 3.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963311 | AG1-180 | Adder | 1.83 MW | 1.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963321 | AG1-181 C O1 | 50/50 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963361 | AG1-185 O1 | 50/50 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964111 | AG1-272 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964112 | AG1-272 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964121 | AG1-273 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964122 | AG1-273 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964131 | AG1-274 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964132 | AG1-274 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964241 | AG1-285 C O1 | 50/50 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964242 | AG1-285 E O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964791 | AG1-342 C | 50/50 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964792 | AG1-342 E | 50/50 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966691 | AG1-539 C | 50/50 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966692 | AG1-539 E | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966761 | AG1-547 C | Adder | 4.41 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966762 | AG1-547 E | Adder | 2.37 MW | 2.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965191 | AG1-384 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965192 | AG1-384 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965591 | AG1-427 C | 50/50 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965592 | AG1-427 E | 50/50 | 9.52 MW | 9.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965601 | AG1-428 C O2 | Adder | 3.13 MW | 2.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965602 | AG1-428 E O2 | Adder | 2.08 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965721 | AG1-440 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965731 | AG1-441 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965771 | AG1-445 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965781 | AG1-446 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 314713 | 3PAMPLIN | Adder | 0.99 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315156 | 1HALLBR1 | 50/50 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315159 | 1KERR 2 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315161 | 1KERR 4 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315162 | 1KERR 5 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925785 | AC1-054 E | Adder | 2.15 MW | 1.82 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926023 | AC1-080 C | 50/50 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926274 | AC1-105 E | 50/50 | 8.2 MW | 8.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926646 | AC1-145 E | Adder | 2.31 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927261 | AC1-222 C | 50/50 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927262 | AC1-222 E | 50/50 | 11.51 MW | 11.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934311 | AD1-055 C | 50/50 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934312 | AD1-055 E | 50/50 | 2.16 MW | 2.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936265 | AD2-033 C | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936266 | AD2-033 E | 50/50 | 9.0 MW | 9.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942671 | AE2-283 C | Adder | 5.37 MW | 4.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942672 | AE2-283 E | Adder | 2.82 MW | 2.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942751 | AE2-291 C | 50/50 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942752 | AE2-291 E | 50/50 | 12.81 MW | 12.81 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942761 | AE2-292 C O1 | 50/50 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942762 | AE2-292 E O1 | 50/50 | 15.96 MW | 15.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958801 | AF2-171 C | Adder | 10.66 MW | 9.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958802 | AF2-171 E | Adder | 7.1 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959311 | AF2-222 C | 50/50 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959312 | AF2-222 E | 50/50 | 10.48 MW | 10.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960061 | AF2-297 C | 50/50 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960062 | AF2-297 E | 50/50 | 18.23 MW | 18.23 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961121 | AF2-403 | Adder | 1.08 MW | 0.92 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315164 | 1KERR 7 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315266 | 1PLYWOOD A | 50/50 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316118 | AC1-105 C | 50/50 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316129 | AC1-054 C | Adder | 4.66 MW | 3.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316131 | AB2-060 C | 50/50 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924162 | AB2-060 E OP | 50/50 | 5.43 MW | 5.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924301 | AB2-077 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924302 | AB2-077 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924311 | AB2-078 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924312 | AB2-078 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924321 | AB2-079 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924322 | AB2-079 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925612 | AC1-036 E | 50/50 | 1.51 MW | 1.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925661 | AC1-042 C | Adder | 2.16 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925662 | AC1-042 E | Adder | 3.53 MW | 3.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938371 | AE1-056 C | Adder | 3.93 MW | 3.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938372 | AE1-056 E | Adder | 2.15 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939181 | AE1-148 C | 50/50 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939182 | AE1-148 E | 50/50 | 6.04 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 940661 | AE2-053 O1 | 50/50 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941801 | AE2-185 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941802 | AE2-185 E | Adder | 3.26 MW | 2.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941821 | AE2-187 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941822 | AE2-187 E | Adder | 2.17 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946301 | AF1-294 C | Adder | 2.89 MW | 2.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946302 | AF1-294 E | Adder | 1.93 MW | 1.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958211 | AF2-115 C | Adder | 1.76 MW | 1.5 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962561 | AG1-105 C O1 | 50/50 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962562 | AG1-105 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313527 | AB2-043 C | 50/50 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924022 | AB2-043 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316123 | AC1-075 C | 50/50 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925997 | AC1-075 E | 50/50 | 8.22 MW | 8.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926024 | AC1-080 E | 50/50 | 2.73 MW | 2.73 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961891 | AG1-030 C | Adder | 6.32 MW | 5.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961892 | AG1-030 E | Adder | 4.21 MW | 3.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962561 | AG1-105 C O1 | Adder | 3.79 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962562 | AG1-105 E O1 | Adder | 2.53 MW | 2.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 961671 | AG1-007 C | Adder | 0.55 MW | 0.47 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 961672 | AG1-007 E | Adder | 0.31 MW | 0.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 963301 | AG1-179 C | 50/50 | 5.11 MW | 5.11 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 963311 | AG1-180 | 50/50 | 2.49 MW | 2.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 965601 | AG1-428 C O2 | 50/50 | 4.26 MW | 4.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 965602 | AG1-428 E O2 | 50/50 | 2.84 MW | 2.84 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 966621 | AG1-532 C | 50/50 | 1.89 MW | 1.89 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 966622 | AG1-532 E | 50/50 | 1.26 MW | 1.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 314541 | 3WATKINS | Adder | -0.34 MW | -0.29 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 314572 | 3EMPORIA | 50/50 | 0.46 MW | 0.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 314704 | 3LAWRENC | 50/50 | 0.32 MW | 0.32 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315131 | 1EDGECMA | 50/50 | 7.55 MW | 7.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315132 | 1EDGECMB | 50/50 | 7.55 MW | 7.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315136 | 1ROSEMG1 | 50/50 | 6.5 MW | 6.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315137 | 1ROSEMS1 | 50/50 | 4.03 MW | 4.03 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315138 | 1ROSEMG2 | 50/50 | 3.04 MW | 3.04 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315139 | 1GASTONA | 50/50 | 10.23 MW | 10.23 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 926070 | AC1-086 C | 50/50 | 67.52 MW | 67.52 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 926071 | AC1-086 E | 50/50 | 30.73 MW | 30.73 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 934331 | AD1-057 C O1 | 50/50 | 19.74 MW | 19.74 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 934332 | AD1-057 E O1 | 50/50 | 10.55 MW | 10.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 943171 | AE2-346 C | Adder | -0.97 MW | -0.82 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 944141 | AF1-082 | 50/50 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 960081 | AF2-299 C | 50/50 | 3.49 MW | 3.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 960082 | AF2-299 E | 50/50 | 2.33 MW | 2.33 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316020 | AB2-059 C OP | 50/50 | 1.35 MW | 1.35 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316088 | AB2-174 E | 50/50 | 4.08 MW | 4.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316097 | AB2-100 E1 | 50/50 | 7.34 MW | 7.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316099 | AB2-100 E2 | 50/50 | 7.34 MW | 7.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316129 | AC1-054 C | Adder | -3.6 MW | -3.06 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 922922 | AB1-081 C OP | 50/50 | 1.15 MW | 1.15 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 922923 | AB1-081 E OP | 50/50 | 2.88 MW | 2.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 923262 | AB1-132 C OP | 50/50 | 45.85 MW | 45.85 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 923263 | AB1-132 E OP | 50/50 | 19.65 MW | 19.65 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 924152 | AB2-059 E OP | 50/50 | 4.09 MW | 4.09 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 925591 | AC1-034 C | 50/50 | 5.14 MW | 5.14 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 925592 | AC1-034 E | 50/50 | 3.88 MW | 3.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 940571 | AE2-044 C | 50/50 | 3.37 MW | 3.37 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 940572 | AE2-044 E | 50/50 | 1.44 MW | 1.44 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 946281 | AF1-292 C | 50/50 | 2.07 MW | 2.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 946282 | AF1-292 E | 50/50 | 1.4 MW | 1.4 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 940481 | AE2-033 C | 50/50 | 38.47 MW | 38.47 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 940482 | AE2-033 E | 50/50 | 25.93 MW | 25.93 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 946011 | AF1-266 | 50/50 | 32.2 MW | 32.2 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 315141 | 1GASTONB | 50/50 | 10.23 MW | 10.23 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316087 | AB2-174 C | 50/50 | 0.77 MW | 0.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316096 | AB2-100 C1 | 50/50 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 316098 | AB2-100 C2 | 50/50 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 960331 | AF2-324 C | 50/50 | 7.37 MW | 7.37 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 960332 | AF2-324 E | 50/50 | 3.96 MW | 3.96 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 962572 | AG1-106 E | 50/50 | 8.52 MW | 8.52 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 962571 | AG1-106 C | 50/50 | 18.78 MW | 18.78 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 964803 | AG1-343 BAT | 50/50 | 1.37 MW | 1.37 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 965752 | AG1-443 BAT | 50/50 | 3.5 MW | 3.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | 965742 | AG1-442 BAT | 50/50 | 3.5 MW | 3.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.62 MW | 18.62 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.18 MW | 6.18 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.4 MW | 6.4 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.66 MW | 1.66 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.5 MW | 1.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.88 MW | 0.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.4 MW | 2.4 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.2 MW | 1.2 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 23872 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 961671 | AG1-007 C | Adder | 0.55 MW | 0.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 961672 | AG1-007 E | Adder | 0.31 MW | 0.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 963301 | AG1-179 C | 50/50 | 5.1 MW | 5.1 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 963311 | AG1-180 | 50/50 | 2.49 MW | 2.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 965601 | AG1-428 C O2 | 50/50 | 4.26 MW | 4.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 965602 | AG1-428 E O2 | 50/50 | 2.83 MW | 2.83 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 966621 | AG1-532 C | 50/50 | 1.88 MW | 1.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 966622 | AG1-532 E | 50/50 | 1.26 MW | 1.26 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 314541 | 3WATKINS | Adder | -0.34 MW | -0.29 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 314572 | 3EMPORIA | 50/50 | 0.46 MW | 0.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 314704 | 3LAWRENC | 50/50 | 0.32 MW | 0.32 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315131 | 1EDGECMA | 50/50 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315132 | 1EDGECMB | 50/50 | 7.54 MW | 7.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315136 | 1ROSEMG1 | 50/50 | 6.49 MW | 6.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315137 | 1ROSEMS1 | 50/50 | 4.03 MW | 4.03 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315138 | 1ROSEMG2 | 50/50 | 3.04 MW | 3.04 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315139 | 1GASTONA | 50/50 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 926070 | AC1-086 C | 50/50 | 67.5 MW | 67.5 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 926071 | AC1-086 E | 50/50 | 30.72 MW | 30.72 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 934331 | AD1-057 C O1 | 50/50 | 19.73 MW | 19.73 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 934332 | AD1-057 E O1 | 50/50 | 10.55 MW | 10.55 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 943171 | AE2-346 C | Adder | -0.97 MW | -0.83 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 944141 | AF1-082 | 50/50 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 960081 | AF2-299 C | 50/50 | 3.49 MW | 3.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 960082 | AF2-299 E | 50/50 | 2.33 MW | 2.33 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316020 | AB2-059 C OP | 50/50 | 1.35 MW | 1.35 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316088 | AB2-174 E | 50/50 | 4.08 MW | 4.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316097 | AB2-100 E1 | 50/50 | 7.34 MW | 7.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316099 | AB2-100 E2 | 50/50 | 7.34 MW | 7.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316129 | AC1-054 C | Adder | -3.61 MW | -3.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 922922 | AB1-081 C OP | 50/50 | 1.15 MW | 1.15 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 922923 | AB1-081 E OP | 50/50 | 2.88 MW | 2.88 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 923262 | AB1-132 C OP | 50/50 | 45.84 MW | 45.84 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 923263 | AB1-132 E OP | 50/50 | 19.64 MW | 19.64 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 924152 | AB2-059 E OP | 50/50 | 4.08 MW | 4.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 925591 | AC1-034 C | 50/50 | 5.13 MW | 5.13 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 925592 | AC1-034 E | 50/50 | 3.87 MW | 3.87 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 940571 | AE2-044 C | 50/50 | 3.36 MW | 3.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 940572 | AE2-044 E | 50/50 | 1.44 MW | 1.44 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 946281 | AF1-292 C | 50/50 | 2.07 MW | 2.07 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 946282 | AF1-292 E | 50/50 | 1.4 MW | 1.4 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 940481 | AE2-033 C | 50/50 | 38.46 MW | 38.46 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 940482 | AE2-033 E | 50/50 | 25.93 MW | 25.93 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 946011 | AF1-266 | 50/50 | 32.19 MW | 32.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 315141 | 1GASTONB | 50/50 | 10.22 MW | 10.22 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316087 | AB2-174 C | 50/50 | 0.77 MW | 0.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316096 | AB2-100 C1 | 50/50 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 316098 | AB2-100 C2 | 50/50 | 2.54 MW | 2.54 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 960331 | AF2-324 C | 50/50 | 7.36 MW | 7.36 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 960332 | AF2-324 E | 50/50 | 3.95 MW | 3.95 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 962572 | AG1-106 E | 50/50 | 8.51 MW | 8.51 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 962571 | AG1-106 C | 50/50 | 18.77 MW | 18.77 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 964803 | AG1-343 BAT | 50/50 | 1.37 MW | 1.37 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 965752 | AG1-443 BAT | 50/50 | 3.51 MW | 3.51 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | 965742 | AG1-442 BAT | 50/50 | 3.51 MW | 3.51 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.48 MW | 18.48 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.13 MW | 6.13 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.35 MW | 6.35 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.37 MW | 0.37 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.49 MW | 1.49 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.38 MW | 2.38 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.19 MW | 1.19 MW |
| 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 238T2002 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961891 | AG1-030 C | Adder | 5.6 MW | 4.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961892 | AG1-030 E | Adder | 3.74 MW | 3.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961941 | AG1-037 C | Adder | 0.32 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961942 | AG1-037 E | Adder | 0.22 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962331 | AG1-082 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962332 | AG1-082 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962341 | AG1-083 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962342 | AG1-083 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963301 | AG1-179 C | Adder | 2.95 MW | 2.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963311 | AG1-180 | Adder | 1.44 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963321 | AG1-181 C O1 | Adder | 7.68 MW | 6.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963361 | AG1-185 O1 | Adder | 3.72 MW | 3.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964111 | AG1-272 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964112 | AG1-272 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964121 | AG1-273 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964122 | AG1-273 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964131 | AG1-274 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964132 | AG1-274 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964241 | AG1-285 C O1 | Adder | 6.55 MW | 5.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964242 | AG1-285 E O1 | Adder | 4.37 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964801 | AG1-343 C | 50/50 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964802 | AG1-343 E | 50/50 | 7.66 MW | 7.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966811 | AG1-552 C | 50/50 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966812 | AG1-552 E | 50/50 | 2.2 MW | 2.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965191 | AG1-384 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965192 | AG1-384 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965291 | AG1-394 C | 50/50 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965292 | AG1-394 E | 50/50 | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965591 | AG1-427 C | Adder | 6.18 MW | 5.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965592 | AG1-427 E | Adder | 4.13 MW | 3.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965602 | AG1-428 E O2 | Adder | 1.64 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965721 | AG1-440 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965722 | AG1-440 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965731 | AG1-441 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965732 | AG1-441 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965771 | AG1-445 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965781 | AG1-446 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 313506 | AB1-173 C OP | 50/50 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314572 | 3EMPORIA | Adder | 0.31 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315126 | 1ROARAP2 | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315128 | 1ROARAP4 | 50/50 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315159 | 1KERR 2 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315160 | 1KERR 3 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315161 | 1KERR 4 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315162 | 1KERR 5 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 918492 | AA1-063AE OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919692 | AA2-053 E OP | 50/50 | 7.76 MW | 7.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919702 | AA2-057 E OP | Adder | 2.0 MW | 1.7 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920042 | AA2-088 E OP | 50/50 | 18.01 MW | 18.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920592 | AA2-165 E | Adder | 0.28 MW | 0.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925785 | AC1-054 E | 50/50 | 5.44 MW | 5.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926201 | AC1-098 C | Adder | 5.16 MW | 4.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926202 | AC1-098 E | Adder | 3.08 MW | 2.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926211 | AC1-099 C | Adder | 1.73 MW | 1.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926212 | AC1-099 E | Adder | 1.02 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927145 | AC1-208 C | 50/50 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927146 | AC1-208 E | 50/50 | 4.49 MW | 4.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936265 | AD2-033 C | Adder | 6.0 MW | 5.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936266 | AD2-033 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943171 | AE2-346 C | Adder | 0.9 MW | 0.77 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943172 | AE2-346 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959311 | AF2-222 C | Adder | 7.08 MW | 6.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959312 | AF2-222 E | Adder | 4.74 MW | 4.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960081 | AF2-299 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315163 | 1KERR 6 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315164 | 1KERR 7 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315606 | 3AA2-053SOLA | 50/50 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316088 | AB2-174 E | 50/50 | 7.19 MW | 7.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316129 | AC1-054 C | 50/50 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316140 | AB2-099 C | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316141 | AB2-099 E | Adder | 0.16 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 900672 | V4-068 E | 50/50 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 917332 | Z2-043 E | Adder | 0.6 MW | 0.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923573 | AB1-173 E OP | 50/50 | 4.34 MW | 4.34 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923991 | AB2-040 C O1 | 50/50 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923992 | AB2-040 E O1 | 50/50 | 8.15 MW | 8.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924162 | AB2-060 E OP | Adder | 2.34 MW | 1.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924301 | AB2-077 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924302 | AB2-077 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924311 | AB2-078 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924312 | AB2-078 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924321 | AB2-079 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924322 | AB2-079 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925612 | AC1-036 E | Adder | 0.68 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932631 | AC2-084 C | Adder | 7.36 MW | 6.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932632 | AC2-084 E | Adder | 3.62 MW | 3.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939181 | AE1-148 C | Adder | 7.6 MW | 6.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939182 | AE1-148 E | Adder | 5.06 MW | 4.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 940661 | AE2-053 O1 | Adder | 2.81 MW | 2.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946281 | AF1-292 C | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957521 | AF2-046 C | 50/50 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957522 | AF2-046 E | 50/50 | 10.06 MW | 10.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314589 | 3MURPHYS | 50/50 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315608 | 3AA2-088SOLA | 50/50 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316087 | AB2-174 C | 50/50 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962561 | AG1-105 C O1 | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962562 | AG1-105 E O1 | Adder | 2.24 MW | 1.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961681 | AG1-008 C | 50/50 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961682 | AG1-008 E | 50/50 | 10.02 MW | 10.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924022 | AB2-043 E O1 | Adder | 1.57 MW | 1.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961671 | AG1-007 C | Adder | 0.56 MW | 0.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961672 | AG1-007 E | Adder | 0.32 MW | 0.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961941 | AG1-037 C | 50/50 | 0.32 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961942 | AG1-037 E | 50/50 | 0.21 MW | 0.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962331 | AG1-082 C | 50/50 | 1.27 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962332 | AG1-082 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962341 | AG1-083 C | 50/50 | 1.27 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962342 | AG1-083 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963301 | AG1-179 C | 50/50 | 6.08 MW | 6.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963311 | AG1-180 | 50/50 | 2.96 MW | 2.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964241 | AG1-285 C O1 | Adder | 5.82 MW | 4.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964242 | AG1-285 E O1 | Adder | 3.88 MW | 3.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964801 | AG1-343 C | 50/50 | 4.02 MW | 4.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964802 | AG1-343 E | 50/50 | 3.16 MW | 3.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966801 | AG1-551 C | Adder | 1.13 MW | 0.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966802 | AG1-551 E | Adder | 0.49 MW | 0.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966811 | AG1-552 C | 50/50 | 1.94 MW | 1.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966812 | AG1-552 E | 50/50 | 0.83 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965291 | AG1-394 C | 50/50 | 1.39 MW | 1.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965292 | AG1-394 E | 50/50 | 0.92 MW | 0.92 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965591 | AG1-427 C | Adder | 5.5 MW | 4.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965592 | AG1-427 E | Adder | 3.67 MW | 3.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965601 | AG1-428 C O2 | 50/50 | 5.08 MW | 5.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965602 | AG1-428 E O2 | 50/50 | 3.38 MW | 3.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965691 | AG1-437 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965692 | AG1-437 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965701 | AG1-438 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965702 | AG1-438 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965711 | AG1-439 C O1 | Adder | 13.64 MW | 11.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965712 | AG1-439 E O1 | Adder | 9.1 MW | 7.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965721 | AG1-440 C | 50/50 | 4.51 MW | 4.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965722 | AG1-440 E | 50/50 | 3.01 MW | 3.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965731 | AG1-441 C | 50/50 | 4.51 MW | 4.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965732 | AG1-441 E | 50/50 | 3.01 MW | 3.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965741 | AG1-442 O1 | Adder | 2.87 MW | 2.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965751 | AG1-443 O1 | Adder | 2.87 MW | 2.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965761 | AG1-444 O1 | Adder | 7.28 MW | 6.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965771 | AG1-445 | 50/50 | 2.61 MW | 2.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965781 | AG1-446 | 50/50 | 2.61 MW | 2.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966621 | AG1-532 C | 50/50 | 1.95 MW | 1.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966622 | AG1-532 E | 50/50 | 1.3 MW | 1.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313506 | AB1-173 C OP | 50/50 | 8.18 MW | 8.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313719 | 3CHESTNUT | 50/50 | 0.84 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.4 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.57 MW | 0.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314582 | 3KELFORD | 50/50 | 0.25 MW | 0.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314623 | 3WITAKRS | 50/50 | 0.15 MW | 0.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.36 MW | 0.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315126 | 1ROARAP2 | 50/50 | 1.32 MW | 1.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315128 | 1ROARAP4 | 50/50 | 1.26 MW | 1.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.93 MW | 4.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.93 MW | 4.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.33 MW | 2.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.44 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.09 MW | 1.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.55 MW | 3.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | 50/50 | 3.33 MW | 3.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | 50/50 | 3.26 MW | 3.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | 50/50 | 2.32 MW | 2.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | 50/50 | 7.02 MW | 7.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920591 | AA2-165 C | 50/50 | 0.11 MW | 0.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | 50/50 | 0.32 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925785 | AC1-054 E | 50/50 | 2.42 MW | 2.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926070 | AC1-086 C | 50/50 | 23.43 MW | 23.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 E | 50/50 | 10.66 MW | 10.66 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | 50/50 | 4.33 MW | 4.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | 50/50 | 2.58 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | 50/50 | 1.45 MW | 1.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927024 | AC1-189 C | Adder | 4.72 MW | 4.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927025 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927145 | AC1-208 C | 50/50 | 6.76 MW | 6.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927146 | AC1-208 E | 50/50 | 3.0 MW | 3.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | 50/50 | 8.4 MW | 8.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | 50/50 | 0.89 MW | 0.89 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | 50/50 | 0.38 MW | 0.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.77 MW | 1.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.61 MW | 3.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315606 | 3AA2-053SOLA | 50/50 | 1.35 MW | 1.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316088 | AB2-174 E | 50/50 | 8.07 MW | 8.07 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316097 | AB2-100 E1 | 50/50 | 4.87 MW | 4.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316099 | AB2-100 E2 | 50/50 | 4.87 MW | 4.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316129 | AC1-054 C | 50/50 | 5.26 MW | 5.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316140 | AB2-099 C | 50/50 | 0.37 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316141 | AB2-099 E | 50/50 | 0.16 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | 50/50 | 0.2 MW | 0.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | 50/50 | 0.69 MW | 0.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | 50/50 | 0.37 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 15.91 MW | 15.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.82 MW | 6.82 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 3.89 MW | 3.89 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.29 MW | 7.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.34 MW | 2.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.08 MW | 1.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.7 MW | 2.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | 50/50 | 6.18 MW | 6.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | 50/50 | 3.04 MW | 3.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.62 MW | 0.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C | Adder | 4.77 MW | 4.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E | Adder | 3.18 MW | 2.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.75 MW | 2.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.14 MW | 2.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.44 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | 50/50 | 11.06 MW | 11.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | 50/50 | 5.57 MW | 5.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.29 MW | 3.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 3.26 MW | 2.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C | Adder | 1.5 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E | Adder | 2.06 MW | 1.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.53 MW | 35.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 23.95 MW | 23.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 29.74 MW | 29.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314331 | 6POE | 50/50 | 7.0 MW | 7.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 0.97 MW | 0.97 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934575 | AD1-082 C | 50/50 | 11.71 MW | 11.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934576 | AD1-082 E | 50/50 | 6.68 MW | 6.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | 50/50 | 2.54 MW | 2.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | 50/50 | 4.14 MW | 4.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | 50/50 | 1.11 MW | 1.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | 50/50 | 1.0 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | 50/50 | 1.64 MW | 1.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315115 | 1S HAMPT1 | 50/50 | 0.91 MW | 0.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.55 MW | 3.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315607 | 3AA1-063SOLA | 50/50 | 1.2 MW | 1.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315608 | 3AA2-088SOLA | 50/50 | 0.73 MW | 0.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316087 | AB2-174 C | 50/50 | 1.52 MW | 1.52 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316096 | AB2-100 C1 | 50/50 | 1.68 MW | 1.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316098 | AB2-100 C2 | 50/50 | 1.68 MW | 1.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.57 MW | 2.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | 50/50 | 5.71 MW | 5.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | 50/50 | 9.32 MW | 9.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939195 | AE1-149 C | 50/50 | 18.6 MW | 18.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939196 | AE1-149 E | 50/50 | 12.4 MW | 12.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 | 50/50 | 6.51 MW | 6.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.2 MW | 6.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 4.0 MW | 3.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.18 MW | 1.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C | Adder | 4.82 MW | 4.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E | Adder | 2.58 MW | 2.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962572 | AG1-106 E | 50/50 | 2.96 MW | 2.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961681 | AG1-008 C | 50/50 | 11.09 MW | 11.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961682 | AG1-008 E | 50/50 | 5.54 MW | 5.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962571 | AG1-106 C | 50/50 | 6.51 MW | 6.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965281 | AG1-393 C | 50/50 | 4.98 MW | 4.98 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965282 | AG1-393 E | 50/50 | 3.32 MW | 3.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.27 MW | 1.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.39 MW | 1.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316083 | AB2-161 C | 50/50 | 5.14 MW | 5.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316084 | AB2-161 E | 50/50 | 8.38 MW | 8.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.59 MW | 1.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.04 MW | 27.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.64 MW | 8.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.41 MW | 2.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.63 MW | 0.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.15 MW | 2.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.0 MW | 4.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.73 MW | 1.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961671 | AG1-007 C | Adder | 0.56 MW | 0.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961672 | AG1-007 E | Adder | 0.32 MW | 0.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961941 | AG1-037 C | 50/50 | 0.32 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961942 | AG1-037 E | 50/50 | 0.21 MW | 0.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962331 | AG1-082 C | 50/50 | 1.27 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962332 | AG1-082 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962341 | AG1-083 C | 50/50 | 1.27 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962342 | AG1-083 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963301 | AG1-179 C | 50/50 | 6.08 MW | 6.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963311 | AG1-180 | 50/50 | 2.96 MW | 2.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964241 | AG1-285 C O1 | Adder | 5.82 MW | 4.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964242 | AG1-285 E O1 | Adder | 3.88 MW | 3.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964801 | AG1-343 C | 50/50 | 4.02 MW | 4.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964802 | AG1-343 E | 50/50 | 3.16 MW | 3.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966801 | AG1-551 C | Adder | 1.13 MW | 0.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966802 | AG1-551 E | Adder | 0.49 MW | 0.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966811 | AG1-552 C | 50/50 | 1.94 MW | 1.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966812 | AG1-552 E | 50/50 | 0.83 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965291 | AG1-394 C | 50/50 | 1.39 MW | 1.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965292 | AG1-394 E | 50/50 | 0.92 MW | 0.92 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965591 | AG1-427 C | Adder | 5.5 MW | 4.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965592 | AG1-427 E | Adder | 3.67 MW | 3.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965601 | AG1-428 C O2 | 50/50 | 5.08 MW | 5.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965602 | AG1-428 E O2 | 50/50 | 3.38 MW | 3.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965691 | AG1-437 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965692 | AG1-437 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965701 | AG1-438 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965702 | AG1-438 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965711 | AG1-439 C O1 | Adder | 13.64 MW | 11.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965712 | AG1-439 E O1 | Adder | 9.1 MW | 7.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965721 | AG1-440 C | 50/50 | 4.51 MW | 4.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965722 | AG1-440 E | 50/50 | 3.01 MW | 3.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965731 | AG1-441 C | 50/50 | 4.51 MW | 4.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965732 | AG1-441 E | 50/50 | 3.01 MW | 3.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965741 | AG1-442 O1 | Adder | 2.87 MW | 2.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965751 | AG1-443 O1 | Adder | 2.87 MW | 2.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965761 | AG1-444 O1 | Adder | 7.28 MW | 6.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965771 | AG1-445 | 50/50 | 2.61 MW | 2.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965781 | AG1-446 | 50/50 | 2.61 MW | 2.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966621 | AG1-532 C | 50/50 | 1.95 MW | 1.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966622 | AG1-532 E | 50/50 | 1.3 MW | 1.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313506 | AB1-173 C OP | 50/50 | 8.18 MW | 8.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313719 | 3CHESTNUT | 50/50 | 0.84 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.4 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.57 MW | 0.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314582 | 3KELFORD | 50/50 | 0.25 MW | 0.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314623 | 3WITAKRS | 50/50 | 0.15 MW | 0.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.36 MW | 0.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315126 | 1ROARAP2 | 50/50 | 1.32 MW | 1.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315128 | 1ROARAP4 | 50/50 | 1.26 MW | 1.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.93 MW | 4.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.93 MW | 4.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.33 MW | 2.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.44 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.09 MW | 1.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.55 MW | 3.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | 50/50 | 3.33 MW | 3.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | 50/50 | 3.26 MW | 3.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | 50/50 | 2.32 MW | 2.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | 50/50 | 7.02 MW | 7.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920591 | AA2-165 C | 50/50 | 0.11 MW | 0.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | 50/50 | 0.32 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925785 | AC1-054 E | 50/50 | 2.42 MW | 2.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926070 | AC1-086 C | 50/50 | 23.43 MW | 23.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 E | 50/50 | 10.66 MW | 10.66 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | 50/50 | 4.33 MW | 4.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | 50/50 | 2.58 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | 50/50 | 1.45 MW | 1.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927024 | AC1-189 C | Adder | 4.72 MW | 4.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927025 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927145 | AC1-208 C | 50/50 | 6.76 MW | 6.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927146 | AC1-208 E | 50/50 | 3.0 MW | 3.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | 50/50 | 8.4 MW | 8.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | 50/50 | 0.89 MW | 0.89 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | 50/50 | 0.38 MW | 0.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.77 MW | 1.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.61 MW | 3.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.4 MW | 2.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315606 | 3AA2-053SOLA | 50/50 | 1.35 MW | 1.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316088 | AB2-174 E | 50/50 | 8.07 MW | 8.07 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316097 | AB2-100 E1 | 50/50 | 4.87 MW | 4.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316099 | AB2-100 E2 | 50/50 | 4.87 MW | 4.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316129 | AC1-054 C | 50/50 | 5.26 MW | 5.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316140 | AB2-099 C | 50/50 | 0.37 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316141 | AB2-099 E | 50/50 | 0.16 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | 50/50 | 0.2 MW | 0.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | 50/50 | 0.69 MW | 0.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | 50/50 | 0.37 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 15.91 MW | 15.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.82 MW | 6.82 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 3.89 MW | 3.89 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.29 MW | 7.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.34 MW | 2.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.08 MW | 1.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.7 MW | 2.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | 50/50 | 6.18 MW | 6.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | 50/50 | 3.04 MW | 3.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.62 MW | 0.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C | Adder | 4.77 MW | 4.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E | Adder | 3.18 MW | 2.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.75 MW | 2.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.14 MW | 2.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.44 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | 50/50 | 11.06 MW | 11.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | 50/50 | 5.57 MW | 5.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.29 MW | 3.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 3.26 MW | 2.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C | Adder | 1.5 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E | Adder | 2.06 MW | 1.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.53 MW | 35.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 23.95 MW | 23.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 29.74 MW | 29.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314331 | 6POE | 50/50 | 7.0 MW | 7.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 0.97 MW | 0.97 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934575 | AD1-082 C | 50/50 | 11.71 MW | 11.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934576 | AD1-082 E | 50/50 | 6.68 MW | 6.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | 50/50 | 2.54 MW | 2.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | 50/50 | 4.14 MW | 4.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | 50/50 | 1.11 MW | 1.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | 50/50 | 1.53 MW | 1.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | 50/50 | 1.0 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | 50/50 | 1.64 MW | 1.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315115 | 1S HAMPT1 | 50/50 | 0.91 MW | 0.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.55 MW | 3.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315607 | 3AA1-063SOLA | 50/50 | 1.2 MW | 1.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315608 | 3AA2-088SOLA | 50/50 | 0.73 MW | 0.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316087 | AB2-174 C | 50/50 | 1.52 MW | 1.52 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316096 | AB2-100 C1 | 50/50 | 1.68 MW | 1.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316098 | AB2-100 C2 | 50/50 | 1.68 MW | 1.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.57 MW | 2.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | 50/50 | 5.71 MW | 5.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | 50/50 | 9.32 MW | 9.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939195 | AE1-149 C | 50/50 | 18.6 MW | 18.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939196 | AE1-149 E | 50/50 | 12.4 MW | 12.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 | 50/50 | 6.51 MW | 6.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.2 MW | 6.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 4.0 MW | 3.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.18 MW | 1.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C | Adder | 4.82 MW | 4.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E | Adder | 2.58 MW | 2.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962572 | AG1-106 E | 50/50 | 2.96 MW | 2.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961681 | AG1-008 C | 50/50 | 11.09 MW | 11.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961682 | AG1-008 E | 50/50 | 5.54 MW | 5.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962571 | AG1-106 C | 50/50 | 6.51 MW | 6.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965281 | AG1-393 C | 50/50 | 4.98 MW | 4.98 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965282 | AG1-393 E | 50/50 | 3.32 MW | 3.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.27 MW | 1.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.39 MW | 1.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316083 | AB2-161 C | 50/50 | 5.14 MW | 5.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316084 | AB2-161 E | 50/50 | 8.38 MW | 8.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.59 MW | 1.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.04 MW | 27.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.64 MW | 8.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.41 MW | 2.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.63 MW | 0.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.15 MW | 2.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.0 MW | 4.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.73 MW | 1.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961791 | AG1-021 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961891 | AG1-030 C | 50/50 | 11.7 MW | 11.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961892 | AG1-030 E | 50/50 | 7.8 MW | 7.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963171 | AG1-166 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963181 | AG1-167 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963191 | AG1-168 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963201 | AG1-169 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963211 | AG1-170 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963301 | AG1-179 C | Adder | 3.17 MW | 2.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963311 | AG1-180 | Adder | 1.55 MW | 1.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963321 | AG1-181 C O1 | 50/50 | 15.97 MW | 15.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963361 | AG1-185 O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964111 | AG1-272 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964121 | AG1-273 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964131 | AG1-274 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964241 | AG1-285 C O1 | 50/50 | 13.59 MW | 13.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964242 | AG1-285 E O1 | 50/50 | 9.06 MW | 9.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964791 | AG1-342 C | Adder | 2.83 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964792 | AG1-342 E | Adder | 2.22 MW | 1.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965191 | AG1-384 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965591 | AG1-427 C | 50/50 | 12.83 MW | 12.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965592 | AG1-427 E | 50/50 | 8.57 MW | 8.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965601 | AG1-428 C O2 | Adder | 2.65 MW | 2.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965602 | AG1-428 E O2 | Adder | 1.76 MW | 1.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965641 | AG1-432 C O1 | Adder | 8.76 MW | 7.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965642 | AG1-432 E O1 | Adder | 5.84 MW | 4.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965721 | AG1-440 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965722 | AG1-440 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965731 | AG1-441 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965732 | AG1-441 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965771 | AG1-445 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965781 | AG1-446 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965831 | AG1-451 | Adder | 1.46 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 314713 | 3PAMPLIN | Adder | 1.03 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315159 | 1KERR 2 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315160 | 1KERR 3 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315161 | 1KERR 4 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315162 | 1KERR 5 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 926274 | AC1-105 E | Adder | 1.38 MW | 1.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936265 | AD2-033 C | 50/50 | 12.47 MW | 12.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936266 | AD2-033 E | 50/50 | 8.31 MW | 8.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942461 | AE2-259 C O1 | Adder | 4.38 MW | 3.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942462 | AE2-259 E O1 | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958801 | AF2-171 C | 50/50 | 10.69 MW | 10.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958802 | AF2-171 E | 50/50 | 7.13 MW | 7.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959311 | AF2-222 C | 50/50 | 14.73 MW | 14.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959312 | AF2-222 E | 50/50 | 9.87 MW | 9.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315163 | 1KERR 6 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315164 | 1KERR 7 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316118 | AC1-105 C | Adder | 2.89 MW | 2.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316131 | AB2-060 C | 50/50 | 1.75 MW | 1.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924162 | AB2-060 E OP | 50/50 | 4.84 MW | 4.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924301 | AB2-077 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924302 | AB2-077 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924311 | AB2-078 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924312 | AB2-078 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924321 | AB2-079 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924322 | AB2-079 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925611 | AC1-036 C | 50/50 | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925612 | AC1-036 E | 50/50 | 1.42 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938371 | AE1-056 C | Adder | 4.11 MW | 3.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938372 | AE1-056 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939181 | AE1-148 C | 50/50 | 17.39 MW | 17.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939182 | AE1-148 E | 50/50 | 11.59 MW | 11.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 940661 | AE2-053 O1 | 50/50 | 6.44 MW | 6.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946301 | AF1-294 C | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946302 | AF1-294 E | Adder | 1.94 MW | 1.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958211 | AF2-115 C | Adder | 1.77 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962561 | AG1-105 C O1 | 50/50 | 6.74 MW | 6.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962562 | AG1-105 E O1 | 50/50 | 4.5 MW | 4.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.34 MW | 1.34 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7660 | Brunswick Substation: 115/69 kV Transformer Addition | $7,000,000 | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n7687 | Add additional 230/115 kV transformer at Sedge Hill substation. | $6,000,000 | |
| b3691 | Reconductor approximately 1.4 miles of 230 kV line #2141 from Lakeview-Carolina to achieve a summer rating of 1047 MVA. | $1,190,000 | |
| b3694.8 | Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. | $15,365,000 | |
| n6221 | Rebuild 11.79 miles of 230 kV Line 238 from Sapony to Carson with 2-795 150C ACSR. | $17,685,000 | |
| n6872 | Rebuild 14.28 miles of 230 kV Line 238 from Clubhouse to AE2-033 Tap with 2-795 150C ACSR. | $21,420,000 | |
| n6179 | Rebuild 12.3 miles of 230 kV Line 2003 from Poe to Harrowgate with 2-636 ACSR. | $30,750,000 | |
| s2824 | Rebuild 230 kV Line #2056 from Hornertown to Hathaway. | $49,100,000 | |
| n6452 | Rebuild 2.47 miles of 230 kV Line 238 from AE2-033 TAP to Sapony with 2-795 150C ACSR. | $3,705,000 | |
| n6178 | Rebuild 4.5 miles of 230 kV Line 2003 from Harrowgate to Tyler with 2-636 ACSR. | $11,250,000 | |
Attachments
Download all tables in report
| Uprate Chain | |||||
|---|---|---|---|---|---|
| Project | Project Status | MFO | MWE | MWC | Disposition |
| AG1-179 | Active | 50.0 | 50.0 | 33.66 | Transition Cycle 1 |
| AG1-180 | Active | 50.0 | 0.0 | 16.4 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-179 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.