AG1-156 Transition Sort Retool Results -- Qualifies for Expedited Process
v1.00 released 2023-12-14 10:56
Jack Frost-Lake Harmony 69 kV
39.5 MW Capacity / 60.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Eligible for Expedited Process:
The AG1-156 project has been determined to meet the initial screen to be eligible for the Expedited Process according to the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304. Though your project initially screens as eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project from the Expedited Process into TC1. Please see "Expedited Process Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Next Steps for your project:
Refreshed Retool for Projects in Expedited Process:
After the initial sorting retool, PJM will conduct a refreshed analysis of the projects in the Expedited Process with the Transition Cycle #1 projects lifted from the study case model. After this refreshed analysis (including load flow, short circuit and stability analysis), retooled System Impact Study reports can be delivered to the Project Developers. Once the project's Facilities Study report is completed (and no conditions exist that would require the project to shift to TC1, see "Expedited Process Rules" below), the final GIA will be tendered along with the Facilities Study report.
Expedited Process Rules:
Though your project initially screens to be eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project into TC1 until the final GIA is tendered.
- If stability analysis or a sag study is completed during the expedited process, and it is determined that a project has an estimated Network Upgrade cost greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If it is determined during the Facilities Study that the cost of a Network Upgrade is now estimated to be greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
- If the interconnected Transmission Owner identifies the need for a Network Upgrade due to a violation of their criteria that is in excess of $5M, the project will be removed from the expedited process and shifted to Transition Cycle #1.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the PPL zone — Carbon County, Pennsylvania. The installed facilities will have a total capability of 60.0 MW with 39.5 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-156 |
| Project Name | Jack Frost-Lake Harmony 69 kV |
| Developer Name | Mora Solar, LLC |
| State | Pennsylvania |
| County | Carbon |
| Transmission Owner | PPL |
| MFO | 60.0 MW |
| MWE | 60.0 MW |
| MWC | 39.5 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-156 will interconnect on the PPL transmission system on the 69 kV line between Jack Frost - Harmony.
Summer Peak Analysis
The Queue Project was evaluated as a 60.0 MW (Capacity 39.5 MW) injection in the PPL area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| PL |
SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line
200022 to 200023 ckt 1 |
PL:03:P71:001017
CONTINGENCY 'PL:03:P71:001017' DISCONNECT BRANCH FROM BUS 200074 TO BUS 200098 CKT 1 /*LACKAWANNA 500.0 - LACHOP_T 500.0 DISCONNECT BRANCH FROM BUS 200091 TO BUS 200098 CKT 1 /*HOPATCONG 500.0 - LACHOP_T 500.0 DISCONNECT BRANCH FROM BUS 207919 TO BUS 211394 CKT 2 /*BLGR TR2 230.0 - BLGR 69.0 DISCONNECT BRANCH FROM BUS 208049 TO BUS 207919 CKT 1 /*PAUP 230.0 - BLGR TR2 230.0 END |
Tower | AC | 99.85 % | 100.38 % | 3112.0 | B | 3123.67 | 15.77 | |
| Details for SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 200038 | SUSQ 2 | 50/50 | 60.51 MW | 60.51 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 932691 | AC2-092 | 50/50 | 23.27 MW | 23.27 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 200083 | FRDM 11 | 50/50 | 31.32 MW | 31.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 200084 | FRDM 21 | 50/50 | 31.32 MW | 31.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 944411 | AF1-106 O1 | Adder | 2.68 MW | 2.28 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959471 | AF2-238 C | Adder | 1.56 MW | 1.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959472 | AF2-238 E | Adder | 1.04 MW | 0.88 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960031 | AF2-294 C | Adder | 1.52 MW | 1.29 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960032 | AF2-294 E | Adder | 1.02 MW | 0.86 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961141 | AF2-405 | Adder | 1.34 MW | 1.14 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961151 | AF2-406 | Adder | 10.04 MW | 8.54 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961211 | AF2-412 | Adder | 14.66 MW | 12.46 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961451 | AF2-436 | Adder | 0.26 MW | 0.23 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 200823 | 26MHP_X3-003 | Adder | 12.14 MW | 10.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 200894 | 26K02 | Adder | 7.0 MW | 5.95 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 203932 | AA2-133 GEN | Adder | 3.51 MW | 2.98 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 203999 | P-047 E | Adder | 10.06 MW | 8.55 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 294573 | P-028 E | Adder | 23.49 MW | 19.97 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941421 | AE2-139 C | Adder | 9.44 MW | 8.02 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941422 | AE2-139 E | Adder | 6.29 MW | 5.35 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208052 | LAEN G2 | 50/50 | 23.04 MW | 23.04 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208053 | LAEN G3 | 50/50 | 23.04 MW | 23.04 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208055 | LAEN G1 | 50/50 | 23.04 MW | 23.04 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 942281 | AE2-241 C | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 942282 | AE2-241 E | Adder | 2.25 MW | 1.91 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 942561 | AE2-271 C | Adder | 12.72 MW | 10.82 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 942562 | AE2-271 E | Adder | 8.48 MW | 7.21 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 943721 | AF1-040 C | Adder | 0.2 MW | 0.17 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 943722 | AF1-040 E | Adder | 3.84 MW | 3.27 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 945611 | AF1-226 C | Adder | 2.85 MW | 2.42 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 945612 | AF1-226 E | Adder | 3.93 MW | 3.34 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959421 | AF2-233 C | Adder | 2.43 MW | 2.06 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959422 | AF2-233 E | Adder | 1.62 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959431 | AF2-234 C | Adder | 4.85 MW | 4.13 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959432 | AF2-234 E | Adder | 3.24 MW | 2.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959922 | AF2-283 E | 50/50 | 0.58 MW | 0.58 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959932 | AF2-284 E | Adder | 0.42 MW | 0.35 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959942 | AF2-285 E | 50/50 | 0.56 MW | 0.56 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959982 | AF2-289 E | Adder | 0.62 MW | 0.53 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 959992 | AF2-290 E | Adder | 0.41 MW | 0.35 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960401 | AF2-331 C | Adder | 6.26 MW | 5.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960402 | AF2-331 E | Adder | 4.18 MW | 3.55 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960411 | AF2-332 C | Adder | 6.26 MW | 5.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960412 | AF2-332 E | Adder | 4.18 MW | 3.55 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960421 | AF2-333 C | Adder | 2.5 MW | 2.13 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960422 | AF2-333 E | Adder | 1.67 MW | 1.42 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960431 | AF2-334 C | Adder | 2.5 MW | 2.13 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 960432 | AF2-334 E | Adder | 1.67 MW | 1.42 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961261 | AF2-417 C | 50/50 | 3.34 MW | 3.34 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961262 | AF2-417 E | 50/50 | 2.23 MW | 2.23 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961301 | AF2-421 C | Adder | 2.3 MW | 1.96 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961302 | AF2-421 E | Adder | 1.54 MW | 1.3 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961331 | AF2-424 C | Adder | 2.06 MW | 1.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961332 | AF2-424 E | Adder | 1.37 MW | 1.17 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961341 | AF2-425 C | Adder | 2.06 MW | 1.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961342 | AF2-425 E | Adder | 1.37 MW | 1.17 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961362 | AF2-427 E | Adder | 0.62 MW | 0.53 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961412 | AF2-432 E | Adder | 0.39 MW | 0.33 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961421 | AF2-433 C O1 | Adder | 2.32 MW | 1.98 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961422 | AF2-433 E O1 | Adder | 1.55 MW | 1.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961431 | AF2-434 C O1 | Adder | 2.32 MW | 1.98 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961432 | AF2-434 E O1 | Adder | 1.55 MW | 1.32 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961531 | AF2-444 C | Adder | 2.03 MW | 1.72 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961532 | AF2-444 E | Adder | 1.37 MW | 1.17 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961541 | AF2-445AC | Adder | 1.85 MW | 1.58 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 961542 | AF2-445AE | Adder | 1.26 MW | 1.07 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 962061 | AG1-050 | Adder | 4.1 MW | 3.49 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 962151 | AG1-060 C | Adder | 4.42 MW | 3.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 962152 | AG1-060 E | Adder | 25.62 MW | 21.78 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964171 | AG1-278 C | Adder | 2.96 MW | 2.51 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964172 | AG1-278 E | Adder | 0.88 MW | 0.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208918 | SUSQ 1 | 50/50 | 39.48 MW | 39.48 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208944 | JENK CT | 50/50 | 1.25 MW | 1.25 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 208972 | BECR K09 | 50/50 | 0.15 MW | 0.15 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209003 | KSTN IPP | 50/50 | 0.24 MW | 0.24 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209006 | NEPC IPP | Adder | 4.61 MW | 3.92 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209009 | PEIP 2 | 50/50 | 2.15 MW | 2.15 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209010 | PEIP 1 | 50/50 | 1.31 MW | 1.31 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209022 | WHFR IPP | Adder | 6.76 MW | 5.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 209029 | WAYM IPP | 50/50 | 0.44 MW | 0.44 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 211374 | AVOC | 50/50 | 0.81 MW | 0.81 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 211375 | BEAC | Adder | 3.84 MW | 3.26 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 234304 | HUN GEN3 | 50/50 | 1.29 MW | 1.29 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 234305 | HUN GEN4 | 50/50 | 1.95 MW | 1.95 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 234311 | HUN GEN5 | 50/50 | 2.16 MW | 2.16 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 234312 | HUN GEN6 | 50/50 | 2.14 MW | 2.14 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 923673 | AB1-182 E | 50/50 | 5.26 MW | 5.26 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 938393 | AE1-058_GEN2 | Adder | 35.18 MW | 29.9 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 939891 | AE1-225 C O1 | Adder | 1.9 MW | 1.62 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 939892 | AE1-225 E O1 | Adder | 2.1 MW | 1.79 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940561 | AE2-042 C | Adder | 9.6 MW | 8.16 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940562 | AE2-042 E | Adder | 4.76 MW | 4.05 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940592 | AE2-046 E | Adder | 4.99 MW | 4.24 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940721 | AE2-059 C | Adder | 1.72 MW | 1.47 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940722 | AE2-059 E | Adder | 2.38 MW | 2.02 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940941 | AE2-084 C | Adder | 1.72 MW | 1.47 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 940942 | AE2-084 E | Adder | 2.38 MW | 2.02 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941161 | AE2-110 C | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941162 | AE2-110 E | Adder | 2.25 MW | 1.91 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941371 | AE2-133 C | Adder | 1.7 MW | 1.44 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 941372 | AE2-133 E | Adder | 2.35 MW | 1.99 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946691 | AF1-333 C O1 | Adder | 2.44 MW | 2.08 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946692 | AF1-333 E O1 | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946731 | AF1-337 C | Adder | 2.44 MW | 2.08 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946732 | AF1-337 E | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946741 | AF1-338 C | Adder | 2.44 MW | 2.08 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946742 | AF1-338 E | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946751 | AF1-339 C O1 | Adder | 2.44 MW | 2.08 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946752 | AF1-339 E O1 | Adder | 1.63 MW | 1.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946761 | AF1-271AC | Adder | 2.06 MW | 1.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 946762 | AF1-271AE | Adder | 1.38 MW | 1.17 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957621 | AF2-056 C | Adder | 5.19 MW | 4.41 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957622 | AF2-056 E | Adder | 2.67 MW | 2.27 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963071 | AG1-156 C | 50/50 | 10.38 MW | 10.38 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963072 | AG1-156 E | 50/50 | 5.39 MW | 5.39 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963151 | AG1-164 C | Adder | 2.3 MW | 1.96 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963152 | AG1-164 E | Adder | 1.54 MW | 1.3 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963161 | AG1-165 C | Adder | 2.3 MW | 1.96 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 963162 | AG1-165 E | Adder | 1.54 MW | 1.3 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964051 | AG1-259 C | Adder | 1.36 MW | 1.15 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964052 | AG1-259 E | Adder | 1.86 MW | 1.58 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964061 | AG1-260 C | Adder | 1.36 MW | 1.15 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964062 | AG1-260 E | Adder | 1.86 MW | 1.58 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964161 | AG1-277 C | Adder | 6.14 MW | 5.22 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964162 | AG1-277 E | Adder | 1.54 MW | 1.3 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964181 | AG1-279 C | Adder | 2.96 MW | 2.51 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 964182 | AG1-279 E | Adder | 0.88 MW | 0.75 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957881 | AF2-082 C | Adder | 6.68 MW | 5.67 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957882 | AF2-082 E | Adder | 4.45 MW | 3.78 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957921 | AF2-086 C | Adder | 2.29 MW | 1.94 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 957922 | AF2-086 E | Adder | 1.51 MW | 1.28 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 958461 | AF2-140 | Adder | 6.23 MW | 5.29 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 938392 | AE1-058_GEN1 | Adder | 35.18 MW | 29.9 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | 938402 | AE1-059-G1 | 50/50 | 56.06 MW | 56.06 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.24 MW | 0.24 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.08 MW | 5.08 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.71 MW | 1.71 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 9.23 MW | 9.23 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.15 MW | 0.15 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.43 MW | 0.43 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.43 MW | 1.43 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 56.35 MW | 56.35 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.16 MW | 0.16 MW |
| SUSQUEHANNA-WESCOSVILLE 500.0 kV Ckt 1 line l/o PL:03:P71:001017 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| (TBD) | Non 500 kV Violation. | $0 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-156 is eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A). See next steps for your project in the "Introduction" section above.