AG1-147 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:48
Garner DP-Lancaster 115 kV
42.0 MW Capacity / 70.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-147 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Solar generating facility located in the Dominion zone — Lancaster County, Virginia. This project is an increase to the Interconnection Customer's original project, which will share the same point of interconnection. The AG1-147 queue position is a 70.0 MW uprate (42.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 100.0 MW.
| Project Information | |
|---|---|
| Queue Number | AG1-147 |
| Project Name | Garner DP-Lancaster 115 kV |
| Developer Name | Virginia Electric & Power Company |
| State | Virginia |
| County | Lancaster |
| Transmission Owner | Dominion |
| MFO | 100.0 MW |
| MWE | 70.0 MW |
| MWC | 42.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-147 "Garner DP-Lancaster 115 kV" will interconnect with the Dominion transmission system as an uprate to AG1-146, sharing the POI and Attachment Facilities.
Summer Peak Analysis
The Queue Project was evaluated as a 70.0 MW (Capacity 42.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
939240 to 314181 ckt 1 |
DVP_P1-2: LN 65-A
CONTINGENCY 'DVP_P1-2: LN 65-A' OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1 /*3OCRAN 115.0 - 3LANCAST 115.0 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1 /*3OCRAN 115.0 - 3WHIT STONE 115.0 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1 /*3RAPPAHNCK 115.0 - 3WHIT STONE 115.0 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1 /*3LANCAST 115.0 - 3LANCA_1 115.0 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1 /*AG1-146 TAP 115.0 - 3LANCAST 115.0 OPEN BUS 313813 /*3OCRAN 115.0 OPEN BUS 314178 /*3LANCAST 115.0 OPEN BUS 314191 /*3WHIT STONE 115.0 OPEN BUS 314400 /*3LANCA_1 115.0 END |
Single | AC | 102.27 % | 122.67 % | 203.98 | B | 250.21 | 42.0 | |
| DVP |
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1 |
DVP_P1-2: LN 2090-B
CONTINGENCY 'DVP_P1-2: LN 2090-B' OPEN BRANCH FROM BUS 965440 TO BUS 314197 CKT 1 /*AG1-412 TAP 230.0 - 6LDYSMITH CT 230.0 END |
Single | AC | 100.19 % | 101.59 % | 548.02 | B | 556.76 | 7.87 | |
| DVP |
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1 |
313837 6SUMMIT 230 965440 AG1-412 TAP 230 1
CONTINGENCY '313837 6SUMMIT 230 965440 AG1-412 TAP 230 1' /* Auto-generated /* 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 END |
Single | AC | 100.17 % | 101.57 % | 548.02 | B | 556.65 | 7.87 | |
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 188.29 % | 188.63 % | 1050.6 | C | 1981.77 | 14.11 | |
| DVP |
AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1 |
DVP_P4-2: 22452
CONTINGENCY 'DVP_P4-2: 22452' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2 /*3NORNECK 115.0 - 6NORNECK 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 END |
Breaker | AC | 116.39 % | 133.76 % | 249.0 | C | 333.05 | 45.99 | |
| DVP |
AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1 |
DVP_P4-2: H4T224
CONTINGENCY 'DVP_P4-2: H4T224' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1 /*3NORNECK 115.0 - 6NORNECK 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 END |
Breaker | AC | 115.39 % | 132.59 % | 249.0 | C | 330.16 | 45.3 | |
| DVP |
AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line
962970 to 314178 ckt 1 |
DVP_P4-2: 224T2129
CONTINGENCY 'DVP_P4-2: 224T2129' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314214 TO BUS 314388 CKT 2 /*6CHCKAHM 230.0 - 6LANEXA 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 END |
Breaker | AC | 112.76 % | 129.61 % | 249.0 | C | 322.72 | 43.44 | |
| DVP |
AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line
945360 to 314177 ckt 1 |
DVP_P4-2: 201632
CONTINGENCY 'DVP_P4-2: 201632' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314387 TO BUS 314388 CKT 2 /*3LANEXA 115.0 - 6LANEXA 230.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 314440 /*6LANEX_1 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Breaker | AC | 124.55 % | 132.92 % | 208.0 | C | 276.48 | 18.12 | |
| DVP |
AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line
945360 to 314177 ckt 1 |
DVP_P4-2: 2016T2024
CONTINGENCY 'DVP_P4-2: 2016T2024' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314214 TO BUS 314388 CKT 1 /*6CHCKAHM 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Breaker | AC | 124.09 % | 132.43 % | 208.0 | C | 275.45 | 17.99 | |
| DVP |
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1 |
DVP_P4-2: 224T2129
CONTINGENCY 'DVP_P4-2: 224T2129' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314214 TO BUS 314388 CKT 2 /*6CHCKAHM 230.0 - 6LANEXA 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 END |
Breaker | AC | 103.7 % | 107.39 % | 671.0 | C | 720.62 | 26.45 | |
| DVP |
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
314132 to 314163 ckt 1 |
DVP_P4-2: 22432
CONTINGENCY 'DVP_P4-2: 22432' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314387 TO BUS 314388 CKT 2 /*3LANEXA 115.0 - 6LANEXA 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 OPEN BUS 314440 /*6LANEX_1 230.0 END |
Breaker | AC | 103.66 % | 107.34 % | 671.0 | C | 720.24 | 26.36 | |
| DVP |
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1 |
DVP_P4-2: 224T2129
CONTINGENCY 'DVP_P4-2: 224T2129' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314214 TO BUS 314388 CKT 2 /*6CHCKAHM 230.0 - 6LANEXA 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 END |
Breaker | AC | 100.68 % | 104.37 % | 671.0 | C | 700.33 | 26.45 | |
| DVP |
6FINES-6FREDBRG 230.0 kV Ckt 1 line
314163 to 314137 ckt 1 |
DVP_P4-2: 22432
CONTINGENCY 'DVP_P4-2: 22432' OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1 /*6DUNNSVL 230.0 - 6NORNECK 230.0 OPEN BRANCH FROM BUS 314172 TO BUS 314388 CKT 1 /*6DUNNSVL 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 314387 TO BUS 314388 CKT 2 /*3LANEXA 115.0 - 6LANEXA 230.0 OPEN BUS 314172 /*6DUNNSVL 230.0 OPEN BUS 314440 /*6LANEX_1 230.0 END |
Breaker | AC | 100.63 % | 104.31 % | 671.0 | C | 699.95 | 26.36 | |
| DVP |
AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line
945360 to 314177 ckt 1 |
DVP_P7-1: LN 85-2016-B
CONTINGENCY 'DVP_P7-1: LN 85-2016-B' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1 /*3SHACKLE 115.0 - 3WEST PT 115.0 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1 /*3WEST PT 115.0 - 3LANEXA 115.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 934140 TO BUS 314184 CKT 1 /*AD1-041 TAP 115.0 - 3SHACKLE 115.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314184 /*3SHACKLE 115.0 OPEN BUS 314188 /*3WEST PT 115.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 925860 /*AC1-065 MAIN 115.0 OPEN BUS 925862 /*AC1-065 COL 34.5 OPEN BUS 925863 /*AC1-065 C 0.4 OPEN BUS 925864 /*AC1-065 TRE 13.8 OPEN BUS 925865 /*AC1-065 E 0.4 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Tower | AC | 148.56 % | 160.76 % | 208.0 | C | 334.38 | 26.79 | |
| DVP |
3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line
314174 to 313828 ckt 1 |
DVP_P7-1: LN 85-2016-B
CONTINGENCY 'DVP_P7-1: LN 85-2016-B' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1 /*3SHACKLE 115.0 - 3WEST PT 115.0 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1 /*3WEST PT 115.0 - 3LANEXA 115.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 934140 TO BUS 314184 CKT 1 /*AD1-041 TAP 115.0 - 3SHACKLE 115.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314184 /*3SHACKLE 115.0 OPEN BUS 314188 /*3WEST PT 115.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 925860 /*AC1-065 MAIN 115.0 OPEN BUS 925862 /*AC1-065 COL 34.5 OPEN BUS 925863 /*AC1-065 C 0.4 OPEN BUS 925864 /*AC1-065 TRE 13.8 OPEN BUS 925865 /*AC1-065 E 0.4 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Tower | AC | 94.09 % | 107.05 % | 208.0 | C | 222.67 | 26.79 | |
| DVP |
3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer
314177 to 314180 ckt 1 |
DVP_P7-1: LN 85-2016-B
CONTINGENCY 'DVP_P7-1: LN 85-2016-B' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1 /*3SHACKLE 115.0 - 3WEST PT 115.0 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1 /*3WEST PT 115.0 - 3LANEXA 115.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 934140 TO BUS 314184 CKT 1 /*AD1-041 TAP 115.0 - 3SHACKLE 115.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314184 /*3SHACKLE 115.0 OPEN BUS 314188 /*3WEST PT 115.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 925860 /*AC1-065 MAIN 115.0 OPEN BUS 925862 /*AC1-065 COL 34.5 OPEN BUS 925863 /*AC1-065 C 0.4 OPEN BUS 925864 /*AC1-065 TRE 13.8 OPEN BUS 925865 /*AC1-065 E 0.4 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Tower | AC | 99.71 % | 109.24 % | 285.7 | C | 312.11 | 26.79 | |
| DVP |
3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line
313828 to 945360 ckt 1 |
DVP_P7-1: LN 85-2016-B
CONTINGENCY 'DVP_P7-1: LN 85-2016-B' OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1 /*3HARMONY 115.0 - 6HARMONY 230.0 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1 /*6HARMONY 230.0 - 6PAPERMILL 230.0 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1 /*3SHACKLE 115.0 - 3WEST PT 115.0 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1 /*3WEST PT 115.0 - 3LANEXA 115.0 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1 /*6PAPERMILL 230.0 - 6CORRCTN 230.0 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1 /*6CORRCTN 230.0 - 6LANEXA 230.0 OPEN BRANCH FROM BUS 934140 TO BUS 314184 CKT 1 /*AD1-041 TAP 115.0 - 3SHACKLE 115.0 OPEN BUS 313846 /*6HARMONY_1 230.0 OPEN BUS 314176 /*6HARMONY 230.0 OPEN BUS 314184 /*3SHACKLE 115.0 OPEN BUS 314188 /*3WEST PT 115.0 OPEN BUS 314189 /*6PAPERMILL 230.0 OPEN BUS 314375 /*6CORRCTN 230.0 OPEN BUS 923842 /*AB2-024 E 230.0 OPEN BUS 925860 /*AC1-065 MAIN 115.0 OPEN BUS 925862 /*AC1-065 COL 34.5 OPEN BUS 925863 /*AC1-065 C 0.4 OPEN BUS 925864 /*AC1-065 TRE 13.8 OPEN BUS 925865 /*AC1-065 E 0.4 OPEN BUS 934391 /*AD1-063 C 230.0 OPEN BUS 934392 /*AD1-063 E 230.0 END |
Tower | AC | 92.37 % | 104.99 % | 208.0 | C | 218.37 | 26.79 | |
| Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 936591 | AD2-074 C | 80/20 | 32.68 MW | 32.68 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 943741 | AF1-042 C | 80/20 | 17.1 MW | 17.1 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 961951 | AG1-038 C | 80/20 | 18.9 MW | 18.9 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 966661 | AG1-536 C | 80/20 | 32.0 MW | 32.0 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 939245 | AE1-155 C | 80/20 | 76.2 MW | 76.2 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 962861 | AG1-135 C | 80/20 | 36.0 MW | 36.0 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 962971 | AG1-146 C | 80/20 | 18.0 MW | 18.0 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 962981 | AG1-147 C | 80/20 | 42.0 MW | 42.0 MW |
| AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65-A | 958261 | AF2-120 C | 80/20 | 37.2 MW | 37.2 MW |
| Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 314131 | 6ARNOLDS | 80/20 | 0.99 MW | 0.99 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 314184 | 3SHACKLE | 80/20 | 0.34 MW | 0.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 314190 | 6WESTMOR | 80/20 | 0.87 MW | 0.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 314243 | 3PROV 92 | 80/20 | 0.19 MW | 0.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 314375 | 6CORRCTN | 80/20 | 0.2 MW | 0.2 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 315033 | 1BIRCHWDA | 80/20 | 35.72 MW | 35.72 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 315034 | 1NORNECKC1 | 80/20 | 1.19 MW | 1.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 315035 | 1NORNECKC2 | 80/20 | 1.15 MW | 1.15 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 925863 | AC1-065 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 934141 | AD1-041 C | 80/20 | 3.18 MW | 3.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 934391 | AD1-063 C | 80/20 | 0.15 MW | 0.15 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 936581 | AD2-073 C | 80/20 | 4.51 MW | 4.51 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 936591 | AD2-074 C | 80/20 | 7.09 MW | 7.09 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 943431 | AF1-014 C | 80/20 | 0.72 MW | 0.72 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 943471 | AF1-018 | 80/20 | 3.88 MW | 3.88 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 943741 | AF1-042 C | 80/20 | 3.71 MW | 3.71 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 944491 | AF1-114 C | 80/20 | 21.12 MW | 21.12 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 945361 | AF1-201 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 945831 | AF1-248 | 80/20 | 0.1 MW | 0.1 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 961781 | AG1-019 | 80/20 | 62.13 MW | 62.13 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 961951 | AG1-038 C | 80/20 | 4.1 MW | 4.1 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 966661 | AG1-536 C | 80/20 | 7.42 MW | 7.42 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 316077 | AC2-138 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 316156 | AD2-030 C | 80/20 | 0.25 MW | 0.25 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 939245 | AE1-155 C | 80/20 | 17.67 MW | 17.67 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 939611 | AE1-191 C | 80/20 | 6.35 MW | 6.35 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 940231 | AE2-005 C | 80/20 | 0.76 MW | 0.76 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 940551 | AE2-041 | 80/20 | 3.88 MW | 3.88 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 957191 | AF2-013 | 80/20 | 62.13 MW | 62.13 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 957601 | AF2-054 C | 80/20 | 1.35 MW | 1.35 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 962531 | AG1-102 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 962861 | AG1-135 C | 80/20 | 8.11 MW | 8.11 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 962971 | AG1-146 C | 80/20 | 3.38 MW | 3.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 962981 | AG1-147 C | 80/20 | 7.87 MW | 7.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 963611 | AG1-210 C | 80/20 | 1.12 MW | 1.12 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 964211 | AG1-282 C | 80/20 | 3.06 MW | 3.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 957831 | AF2-077 C | 80/20 | 0.93 MW | 0.93 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 957971 | AF2-091 C | 80/20 | 7.18 MW | 7.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | 958261 | AF2-120 C | 80/20 | 8.63 MW | 8.63 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.64 MW | 0.64 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.19 MW | 0.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.73 MW | 11.73 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.38 MW | 3.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.02 MW | 4.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.97 MW | 0.97 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.96 MW | 0.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2090-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 314131 | 6ARNOLDS | 80/20 | 0.99 MW | 0.99 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 314184 | 3SHACKLE | 80/20 | 0.34 MW | 0.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 314190 | 6WESTMOR | 80/20 | 0.87 MW | 0.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 314243 | 3PROV 92 | 80/20 | 0.19 MW | 0.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 314375 | 6CORRCTN | 80/20 | 0.2 MW | 0.2 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 315033 | 1BIRCHWDA | 80/20 | 35.72 MW | 35.72 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 315034 | 1NORNECKC1 | 80/20 | 1.19 MW | 1.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 315035 | 1NORNECKC2 | 80/20 | 1.15 MW | 1.15 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 925863 | AC1-065 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 934141 | AD1-041 C | 80/20 | 3.18 MW | 3.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 934391 | AD1-063 C | 80/20 | 0.15 MW | 0.15 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 936581 | AD2-073 C | 80/20 | 4.51 MW | 4.51 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 936591 | AD2-074 C | 80/20 | 7.09 MW | 7.09 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 943431 | AF1-014 C | 80/20 | 0.72 MW | 0.72 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 943471 | AF1-018 | 80/20 | 3.88 MW | 3.88 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 943741 | AF1-042 C | 80/20 | 3.71 MW | 3.71 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 944491 | AF1-114 C | 80/20 | 21.12 MW | 21.12 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 945361 | AF1-201 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 945831 | AF1-248 | 80/20 | 0.1 MW | 0.1 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 961781 | AG1-019 | 80/20 | 62.13 MW | 62.13 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 961951 | AG1-038 C | 80/20 | 4.1 MW | 4.1 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 966661 | AG1-536 C | 80/20 | 7.42 MW | 7.42 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 316077 | AC2-138 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 316156 | AD2-030 C | 80/20 | 0.25 MW | 0.25 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 939245 | AE1-155 C | 80/20 | 17.67 MW | 17.67 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 939611 | AE1-191 C | 80/20 | 6.35 MW | 6.35 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 940231 | AE2-005 C | 80/20 | 0.76 MW | 0.76 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 940551 | AE2-041 | 80/20 | 3.88 MW | 3.88 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 957191 | AF2-013 | 80/20 | 62.13 MW | 62.13 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 957601 | AF2-054 C | 80/20 | 1.35 MW | 1.35 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 962531 | AG1-102 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 962861 | AG1-135 C | 80/20 | 8.11 MW | 8.11 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 962971 | AG1-146 C | 80/20 | 3.38 MW | 3.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 962981 | AG1-147 C | 80/20 | 7.87 MW | 7.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 963611 | AG1-210 C | 80/20 | 1.12 MW | 1.12 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 964211 | AG1-282 C | 80/20 | 3.06 MW | 3.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 957831 | AF2-077 C | 80/20 | 0.93 MW | 0.93 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 957971 | AF2-091 C | 80/20 | 7.18 MW | 7.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | 958261 | AF2-120 C | 80/20 | 8.63 MW | 8.63 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.64 MW | 0.64 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.19 MW | 0.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.73 MW | 11.73 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.38 MW | 3.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.02 MW | 4.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.97 MW | 0.97 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.96 MW | 0.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.53 MW | 0.53 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o 313837 6SUMMIT 230 965440 AG1-412 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 920042 | AA2-088 E OP | Adder | 9.08 MW | 7.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316097 | AB2-100 E1 | Adder | 2.54 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316099 | AB2-100 E2 | Adder | 2.54 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940491 | AE2-034 C | Adder | 6.24 MW | 5.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940492 | AE2-034 E | Adder | 2.67 MW | 2.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 14.82 MW | 12.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 7.46 MW | 6.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 5.47 MW | 4.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 25.56 MW | 21.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C | Adder | 2.66 MW | 2.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E | Adder | 3.67 MW | 3.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940481 | AE2-033 C | Adder | 15.16 MW | 12.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940482 | AE2-033 E | Adder | 10.22 MW | 8.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946011 | AF1-266 | Adder | 12.69 MW | 10.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 313717 | 6SLIGO L2192 | Adder | 2.01 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314177 | 3HAYES89 | Adder | 0.06 MW | 0.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314189 | 6PAPERMILL | Adder | 8.6 MW | 7.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314229 | 6MT RD221 | 50/50 | 0.24 MW | 0.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314236 | 6NRTHEST | 50/50 | 0.32 MW | 0.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314241 | 6OLDCHRC | 50/50 | 1.49 MW | 1.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314331 | 6POE | Adder | 2.58 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314466 | 6FENTRES | Adder | 2.04 MW | 1.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314525 | 6KINGFORK | Adder | 4.17 MW | 3.54 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314550 | 6HICKORY | Adder | 3.76 MW | 3.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314632 | 6AYDLETOLD | Adder | 2.01 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315051 | 1AA1-145 CT1 | 50/50 | 8.3 MW | 8.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315052 | 1AA1-145 CT2 | 50/50 | 8.3 MW | 8.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315060 | 1CHESTF5 | Adder | 90.49 MW | 76.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315065 | 1CHESTF6 | Adder | 142.59 MW | 121.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315067 | 1DARBY 1 | 50/50 | 4.27 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315068 | 1DARBY 2 | 50/50 | 4.27 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315069 | 1DARBY 3 | 50/50 | 4.29 MW | 4.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315070 | 1DARBY 4 | 50/50 | 4.29 MW | 4.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315073 | 1STONECA | Adder | 9.22 MW | 7.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315083 | 1SPRUNCA | Adder | 14.69 MW | 12.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315084 | 1SPRUNCB | Adder | 14.69 MW | 12.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | Adder | 5.86 MW | 4.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925863 | AC1-065 C | Adder | 7.82 MW | 6.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925865 | AC1-065 E | Adder | 12.57 MW | 10.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926412 | AC1-112 E | 50/50 | 1.9 MW | 1.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926472 | AC1-118 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 1.24 MW | 1.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926754 | AC1-161 C | Adder | 26.85 MW | 22.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926755 | AC1-161 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926784 | AC1-164 C | Adder | 57.34 MW | 48.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926785 | AC1-164 E | Adder | 25.76 MW | 21.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927044 | AC1-191 C | 50/50 | 17.5 MW | 17.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927045 | AC1-191 E | 50/50 | 8.71 MW | 8.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927226 | AC1-216 E | Adder | 9.3 MW | 7.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934014 | AD1-025 C | Adder | 20.32 MW | 17.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934015 | AD1-025 E | Adder | 12.04 MW | 10.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | Adder | 6.9 MW | 5.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | Adder | 4.6 MW | 3.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934141 | AD1-041 C | Adder | 6.64 MW | 5.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934142 | AD1-041 E | Adder | 4.43 MW | 3.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934392 | AD1-063 E | Adder | 1.36 MW | 1.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934575 | AD1-082 C | Adder | 8.77 MW | 7.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934576 | AD1-082 E | Adder | 5.0 MW | 4.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934781 | AD1-105 C | Adder | 11.58 MW | 9.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934782 | AD1-105 E | Adder | 7.72 MW | 6.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 0.91 MW | 0.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935164 | AD1-151 C | Adder | 19.95 MW | 16.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935165 | AD1-151 E | Adder | 13.3 MW | 11.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936581 | AD2-073 C | Adder | 2.25 MW | 1.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936582 | AD2-073 E | Adder | 1.12 MW | 0.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936591 | AD2-074 C | Adder | 6.39 MW | 5.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936592 | AD2-074 E | Adder | 10.42 MW | 8.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936661 | AD2-085 C | Adder | 3.46 MW | 2.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936662 | AD2-085 E | Adder | 5.65 MW | 4.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936761 | AD2-097 C | Adder | 2.79 MW | 2.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936762 | AD2-097 E | Adder | 13.93 MW | 11.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | Adder | 5.35 MW | 4.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942151 | AE2-227 C | Adder | 3.24 MW | 2.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942152 | AE2-227 E | Adder | 2.16 MW | 1.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942161 | AE2-228 C | Adder | 2.95 MW | 2.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942162 | AE2-228 E | Adder | 1.97 MW | 1.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942191 | AE2-231 C O1 | Adder | 4.15 MW | 3.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942192 | AE2-231 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942341 | AE2-247 C | Adder | 1.5 MW | 1.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942342 | AE2-247 E | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942371 | AE2-250 C O1 | Adder | 12.48 MW | 10.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942372 | AE2-250 E O1 | Adder | 6.58 MW | 5.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | Adder | 5.63 MW | 4.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | Adder | 2.53 MW | 2.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942551 | AE2-270 | Adder | 32.7 MW | 27.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943431 | AF1-014 C | Adder | 1.62 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943432 | AF1-014 E | Adder | 2.86 MW | 2.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943461 | AF1-017 C | Adder | 1.36 MW | 1.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943462 | AF1-017 E | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943471 | AF1-018 | Adder | 9.09 MW | 7.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 1.61 MW | 1.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 0.86 MW | 0.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943621 | AF1-033 C | Adder | 2.58 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943622 | AF1-033 E | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943741 | AF1-042 C | Adder | 3.34 MW | 2.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943742 | AF1-042 E | Adder | 5.45 MW | 4.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944631 | AF1-128 O1 | Adder | 56.62 MW | 48.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 4.78 MW | 4.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 3.19 MW | 2.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945361 | AF1-201 C O1 | Adder | 17.99 MW | 15.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945362 | AF1-201 E O1 | Adder | 11.99 MW | 10.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960091 | AF2-300 C | Adder | 1.88 MW | 1.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960092 | AF2-300 E | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961711 | AG1-011 | Adder | 34.52 MW | 29.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961951 | AG1-038 C | Adder | 3.7 MW | 3.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961952 | AG1-038 E | Adder | 5.1 MW | 4.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966661 | AG1-536 C | Adder | 6.16 MW | 5.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966662 | AG1-536 E | Adder | 8.28 MW | 7.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966871 | AG1-558 C | 50/50 | 4.36 MW | 4.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966872 | AG1-558 E | 50/50 | 2.19 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966881 | AG1-559 C | Adder | 2.09 MW | 1.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966882 | AG1-559 E | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316076 | AC2-137 E | Adder | 2.02 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316078 | AC2-138 E | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316108 | AB2-160 C | Adder | 7.02 MW | 5.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316109 | AB2-160 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316132 | AB2-190 C | Adder | 23.18 MW | 19.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316157 | AD2-030 E | Adder | 1.45 MW | 1.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 1.99 MW | 1.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | Adder | 1.74 MW | 1.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 1.13 MW | 0.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923842 | AB2-024 E | Adder | 1.45 MW | 1.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923852 | AB2-025 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924814 | AB2-134 E | Adder | 15.23 MW | 12.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 930122 | AB1-027 E | 50/50 | 1.87 MW | 1.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932044 | AC2-012 C | Adder | 7.49 MW | 6.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932046 | AC2-012 E | Adder | 12.22 MW | 10.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932591 | AC2-079 C O1 | Adder | 6.02 MW | 5.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932592 | AC2-079 E O1 | Adder | 9.83 MW | 8.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938535 | AE1-072 C | Adder | 16.02 MW | 13.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938536 | AE1-072 E | Adder | 8.35 MW | 7.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938552 | AE1-074 E | Adder | 1.56 MW | 1.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939195 | AE1-149 C | Adder | 12.55 MW | 10.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939196 | AE1-149 E | Adder | 8.37 MW | 7.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939245 | AE1-155 C | Adder | 14.66 MW | 12.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939312 | AE1-162 E | Adder | 1.48 MW | 1.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939414 | AE1-173_C1 | Adder | 24.48 MW | 20.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939415 | AE1-173_C2 | Adder | 20.98 MW | 17.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939416 | AE1-173_C3 | Adder | 24.48 MW | 20.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939423 | AE1-173_E1 | Adder | 6.95 MW | 5.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939431 | AE1-175 C | Adder | 2.84 MW | 2.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939432 | AE1-175 E | Adder | 1.41 MW | 1.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939611 | AE1-191 C | Adder | 13.29 MW | 11.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939612 | AE1-191 E | Adder | 8.86 MW | 7.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940231 | AE2-005 C | Adder | 1.71 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940232 | AE2-005 E | Adder | 2.79 MW | 2.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940431 | AE2-027 C O1 | Adder | 17.63 MW | 14.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940432 | AE2-027 E O1 | Adder | 11.75 MW | 9.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940541 | AE2-040 | Adder | 2.71 MW | 2.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940551 | AE2-041 | Adder | 9.09 MW | 7.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940651 | AE2-052 | Adder | 4.18 MW | 3.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 3.18 MW | 2.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 5.06 MW | 4.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | Adder | 26.28 MW | 22.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | Adder | 106.03 MW | 90.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | Adder | 27.0 MW | 22.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | Adder | 105.3 MW | 89.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | Adder | 24.53 MW | 20.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | Adder | 107.64 MW | 91.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946261 | AF1-291 C | Adder | 2.95 MW | 2.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946262 | AF1-291 E | Adder | 1.97 MW | 1.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957411 | AF2-035 C | Adder | 7.54 MW | 6.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957412 | AF2-035 E | Adder | 5.02 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 1.97 MW | 1.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 1.32 MW | 1.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957601 | AF2-054 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957602 | AF2-054 E | Adder | 1.72 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 3.34 MW | 2.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957711 | AF2-065 C | Adder | 16.67 MW | 14.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957712 | AF2-065 E | Adder | 16.02 MW | 13.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962531 | AG1-102 C | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962532 | AG1-102 E | Adder | 2.62 MW | 2.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962851 | AG1-134 C | Adder | 15.64 MW | 13.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962852 | AG1-134 E | Adder | 10.43 MW | 8.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962861 | AG1-135 C | Adder | 6.98 MW | 5.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962862 | AG1-135 E | Adder | 4.65 MW | 3.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962961 | AG1-145 C | Adder | 2.57 MW | 2.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962962 | AG1-145 E | Adder | 1.71 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962971 | AG1-146 C | Adder | 3.63 MW | 3.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962972 | AG1-146 E | Adder | 2.42 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962981 | AG1-147 C | Adder | 8.46 MW | 7.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962982 | AG1-147 E | Adder | 5.64 MW | 4.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963221 | AG1-171 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963222 | AG1-171 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963231 | AG1-172 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963232 | AG1-172 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963241 | AG1-173 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963242 | AG1-173 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963251 | AG1-174 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963252 | AG1-174 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963611 | AG1-210 C | Adder | 0.73 MW | 0.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963612 | AG1-210 E | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963621 | AG1-213 C | Adder | 0.63 MW | 0.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963622 | AG1-213 E | Adder | 0.94 MW | 0.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964211 | AG1-282 C | Adder | 2.29 MW | 1.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964212 | AG1-282 E | Adder | 1.53 MW | 1.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964951 | AG1-359 O1 | Adder | 20.92 MW | 17.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965001 | AG1-364 C O1 | Adder | 6.68 MW | 5.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965002 | AG1-364 E O1 | Adder | 10.01 MW | 8.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 41.58 MW | 35.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 0.96 MW | 0.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925332 | AB2-190 E | Adder | 9.93 MW | 8.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | Adder | 1.06 MW | 0.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933294 | AC2-141 C | Adder | 26.85 MW | 22.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933295 | AC2-141 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 14.34 MW | 12.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 9.56 MW | 8.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941581 | AE2-155 C | 50/50 | 0.19 MW | 0.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941582 | AE2-155 E | 50/50 | 0.47 MW | 0.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | Adder | 16.69 MW | 14.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942001 | AE2-212 C | Adder | 2.8 MW | 2.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942002 | AE2-212 E | Adder | 1.87 MW | 1.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957831 | AF2-077 C | Adder | 2.45 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957832 | AF2-077 E | Adder | 1.63 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | Adder | 9.12 MW | 7.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | Adder | 3.91 MW | 3.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957911 | AF2-085 | Adder | 3.81 MW | 3.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 1.31 MW | 1.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 2.05 MW | 1.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958261 | AF2-120 C | Adder | 7.16 MW | 6.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958262 | AF2-120 E | Adder | 4.77 MW | 4.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966611 | AG1-531 C | Adder | 6.29 MW | 5.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966612 | AG1-531 E | Adder | 4.19 MW | 3.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962271 | AG1-075 C O1 | Adder | 21.53 MW | 18.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962272 | AG1-075 E O1 | Adder | 13.12 MW | 11.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965281 | AG1-393 C | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965282 | AG1-393 E | Adder | 1.38 MW | 1.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939246 | AE1-155 E | Adder | 9.78 MW | 8.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315043 | 1FOUR RIVERA | 50/50 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315045 | 1FOUR RIVERC | 50/50 | 6.45 MW | 6.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315048 | 1FOUR RIVERF | 50/50 | 6.45 MW | 6.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 920692 | AA2-178 E | Adder | 3.56 MW | 3.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316083 | AB2-161 C | Adder | 3.85 MW | 3.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316084 | AB2-161 E | Adder | 6.28 MW | 5.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961611 | AG1-000B C | Adder | 17.82 MW | 15.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.25 MW | 3.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 53.98 MW | 53.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.91 MW | 2.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.9 MW | 10.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.93 MW | 4.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.13 MW | 2.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.07 MW | 3.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.97 MW | 0.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.05 MW | 1.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 13.58 MW | 13.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.45 MW | 2.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.09 MW | 0.09 MW |
| Details for AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 314190 | 6WESTMOR | 50/50 | 0.46 MW | 0.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 315034 | 1NORNECKC1 | 50/50 | 1.69 MW | 1.69 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 315035 | 1NORNECKC2 | 50/50 | 1.63 MW | 1.63 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 926472 | AC1-118 E | 50/50 | 1.38 MW | 1.38 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 934141 | AD1-041 C | Adder | -3.43 MW | -2.92 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 936581 | AD2-073 C | 50/50 | 2.95 MW | 2.95 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 936582 | AD2-073 E | 50/50 | 1.46 MW | 1.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 936591 | AD2-074 C | 50/50 | 18.81 MW | 18.81 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 936592 | AD2-074 E | 50/50 | 30.69 MW | 30.69 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 943741 | AF1-042 C | 50/50 | 9.84 MW | 9.84 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 943742 | AF1-042 E | 50/50 | 16.06 MW | 16.06 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 944491 | AF1-114 C | 50/50 | 6.63 MW | 6.63 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 944492 | AF1-114 E | 50/50 | 9.15 MW | 9.15 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 945831 | AF1-248 | 50/50 | 0.14 MW | 0.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 961781 | AG1-019 | 50/50 | 11.2 MW | 11.2 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 961951 | AG1-038 C | 50/50 | 10.88 MW | 10.88 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 961952 | AG1-038 E | 50/50 | 15.02 MW | 15.02 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 966661 | AG1-536 C | 50/50 | 17.09 MW | 17.09 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 966662 | AG1-536 E | 50/50 | 22.97 MW | 22.97 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 316077 | AC2-138 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 316078 | AC2-138 E | 50/50 | 2.39 MW | 2.39 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 939245 | AE1-155 C | 50/50 | 40.7 MW | 40.7 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 939611 | AE1-191 C | Adder | -6.87 MW | -5.84 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 957191 | AF2-013 | 50/50 | 11.2 MW | 11.2 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962861 | AG1-135 C | 50/50 | 19.88 MW | 19.88 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962862 | AG1-135 E | 50/50 | 13.26 MW | 13.26 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962971 | AG1-146 C | 50/50 | 11.83 MW | 11.83 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962972 | AG1-146 E | 50/50 | 7.88 MW | 7.88 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962981 | AG1-147 C | 50/50 | 27.59 MW | 27.59 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 962982 | AG1-147 E | 50/50 | 18.39 MW | 18.39 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 963611 | AG1-210 C | 50/50 | 1.59 MW | 1.59 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 963612 | AG1-210 E | 50/50 | 2.39 MW | 2.39 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 957971 | AF2-091 C | 50/50 | 2.25 MW | 2.25 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 957972 | AF2-091 E | 50/50 | 3.11 MW | 3.11 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 958261 | AF2-120 C | 50/50 | 19.87 MW | 19.87 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 958262 | AF2-120 E | 50/50 | 13.24 MW | 13.24 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | 939246 | AE1-155 E | 50/50 | 27.13 MW | 27.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.15 MW | 0.15 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.38 MW | 0.38 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.13 MW | 0.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.18 MW | 0.18 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.46 MW | 0.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.43 MW | 0.43 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.26 MW | 0.26 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.42 MW | 0.42 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 22452 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.16 MW | 1.16 MW |
| Details for AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 314190 | 6WESTMOR | 50/50 | 0.47 MW | 0.47 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 315034 | 1NORNECKC1 | 50/50 | 1.62 MW | 1.62 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 315035 | 1NORNECKC2 | 50/50 | 1.56 MW | 1.56 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 926472 | AC1-118 E | 50/50 | 1.42 MW | 1.42 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 934141 | AD1-041 C | Adder | -3.53 MW | -3.0 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 936581 | AD2-073 C | 50/50 | 3.04 MW | 3.04 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 936582 | AD2-073 E | 50/50 | 1.5 MW | 1.5 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 936591 | AD2-074 C | 50/50 | 18.41 MW | 18.41 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 936592 | AD2-074 E | 50/50 | 30.05 MW | 30.05 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 943741 | AF1-042 C | 50/50 | 9.64 MW | 9.64 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 943742 | AF1-042 E | 50/50 | 15.72 MW | 15.72 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 944491 | AF1-114 C | 50/50 | 6.82 MW | 6.82 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 944492 | AF1-114 E | 50/50 | 9.41 MW | 9.41 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 945831 | AF1-248 | 50/50 | 0.14 MW | 0.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 961781 | AG1-019 | 50/50 | 11.52 MW | 11.52 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 961951 | AG1-038 C | 50/50 | 10.65 MW | 10.65 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 961952 | AG1-038 E | 50/50 | 14.71 MW | 14.71 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 966661 | AG1-536 C | 50/50 | 16.66 MW | 16.66 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 966662 | AG1-536 E | 50/50 | 22.39 MW | 22.39 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 316077 | AC2-138 C | 50/50 | 0.41 MW | 0.41 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 316078 | AC2-138 E | 50/50 | 2.29 MW | 2.29 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 939245 | AE1-155 C | 50/50 | 39.68 MW | 39.68 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 939611 | AE1-191 C | Adder | -7.07 MW | -6.01 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 957191 | AF2-013 | 50/50 | 11.52 MW | 11.52 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962861 | AG1-135 C | 50/50 | 19.42 MW | 19.42 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962862 | AG1-135 E | 50/50 | 12.95 MW | 12.95 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962971 | AG1-146 C | 50/50 | 11.65 MW | 11.65 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962972 | AG1-146 E | 50/50 | 7.77 MW | 7.77 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962981 | AG1-147 C | 50/50 | 27.18 MW | 27.18 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962982 | AG1-147 E | 50/50 | 18.12 MW | 18.12 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 963611 | AG1-210 C | 50/50 | 1.52 MW | 1.52 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 963612 | AG1-210 E | 50/50 | 2.29 MW | 2.29 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 957971 | AF2-091 C | 50/50 | 2.32 MW | 2.32 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 957972 | AF2-091 E | 50/50 | 3.2 MW | 3.2 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 958261 | AF2-120 C | 50/50 | 19.37 MW | 19.37 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 958262 | AF2-120 E | 50/50 | 12.91 MW | 12.91 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 939246 | AE1-155 E | 50/50 | 26.45 MW | 26.45 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | 962533 | AG1-102 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.15 MW | 0.15 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.39 MW | 0.39 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.13 MW | 0.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.19 MW | 0.19 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.47 MW | 0.47 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.45 MW | 0.45 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.43 MW | 0.43 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: H4T224 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.2 MW | 1.2 MW |
| Details for AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314131 | 6ARNOLDS | 50/50 | 0.15 MW | 0.15 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314190 | 6WESTMOR | 50/50 | 0.5 MW | 0.5 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315034 | 1NORNECKC1 | 50/50 | 1.43 MW | 1.43 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315035 | 1NORNECKC2 | 50/50 | 1.38 MW | 1.38 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 926472 | AC1-118 E | 50/50 | 1.51 MW | 1.51 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 934141 | AD1-041 C | Adder | -3.88 MW | -3.3 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936581 | AD2-073 C | 50/50 | 3.23 MW | 3.23 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936582 | AD2-073 E | 50/50 | 1.6 MW | 1.6 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936591 | AD2-074 C | 50/50 | 17.37 MW | 17.37 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936592 | AD2-074 E | 50/50 | 28.34 MW | 28.34 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943741 | AF1-042 C | 50/50 | 9.09 MW | 9.09 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943742 | AF1-042 E | 50/50 | 14.83 MW | 14.83 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944491 | AF1-114 C | 50/50 | 7.26 MW | 7.26 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944492 | AF1-114 E | 50/50 | 10.02 MW | 10.02 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 945831 | AF1-248 | 50/50 | 0.12 MW | 0.12 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961781 | AG1-019 | 50/50 | 12.27 MW | 12.27 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961951 | AG1-038 C | 50/50 | 10.05 MW | 10.05 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961952 | AG1-038 E | 50/50 | 13.87 MW | 13.87 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966661 | AG1-536 C | 50/50 | 15.55 MW | 15.55 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966662 | AG1-536 E | 50/50 | 20.9 MW | 20.9 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316077 | AC2-138 C | 50/50 | 0.36 MW | 0.36 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316078 | AC2-138 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939245 | AE1-155 C | 50/50 | 37.04 MW | 37.04 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939611 | AE1-191 C | Adder | -7.77 MW | -6.6 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957191 | AF2-013 | 50/50 | 12.27 MW | 12.27 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962861 | AG1-135 C | 50/50 | 18.21 MW | 18.21 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962862 | AG1-135 E | 50/50 | 12.14 MW | 12.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962971 | AG1-146 C | 50/50 | 11.17 MW | 11.17 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962972 | AG1-146 E | 50/50 | 7.45 MW | 7.45 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962981 | AG1-147 C | 50/50 | 26.06 MW | 26.06 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962982 | AG1-147 E | 50/50 | 17.38 MW | 17.38 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963611 | AG1-210 C | 50/50 | 1.35 MW | 1.35 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963612 | AG1-210 E | 50/50 | 2.02 MW | 2.02 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957971 | AF2-091 C | 50/50 | 2.47 MW | 2.47 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957972 | AF2-091 E | 50/50 | 3.41 MW | 3.41 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958261 | AF2-120 C | 50/50 | 18.08 MW | 18.08 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958262 | AF2-120 E | 50/50 | 12.05 MW | 12.05 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939246 | AE1-155 E | 50/50 | 24.69 MW | 24.69 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 940552 | AE2-041 BAT | Adder | 4.07 MW | 3.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943472 | AF1-018 BAT | Adder | 4.07 MW | 3.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962533 | AG1-102 BAT | Adder | 1.92 MW | 1.63 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.16 MW | 0.16 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.25 MW | 0.25 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.15 MW | 0.15 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.21 MW | 0.21 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.14 MW | 0.14 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.5 MW | 0.5 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.49 MW | 0.49 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.08 MW | 0.08 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.29 MW | 0.29 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
| AG1-146 TAP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.3 MW | 1.3 MW |
| Details for AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 314184 | 3SHACKLE | 50/50 | 0.88 MW | 0.88 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 925863 | AC1-065 C | 50/50 | 9.01 MW | 9.01 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 925865 | AC1-065 E | 50/50 | 14.47 MW | 14.47 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 934141 | AD1-041 C | 50/50 | 9.42 MW | 9.42 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 934142 | AD1-041 E | 50/50 | 6.28 MW | 6.28 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 936591 | AD2-074 C | 50/50 | 6.82 MW | 6.82 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 936592 | AD2-074 E | 50/50 | 11.13 MW | 11.13 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 943431 | AF1-014 C | 50/50 | 1.87 MW | 1.87 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 943432 | AF1-014 E | 50/50 | 3.29 MW | 3.29 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 943741 | AF1-042 C | 50/50 | 3.57 MW | 3.57 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 943742 | AF1-042 E | 50/50 | 5.82 MW | 5.82 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 945361 | AF1-201 C O1 | 50/50 | 70.65 MW | 70.65 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 945362 | AF1-201 E O1 | 50/50 | 47.1 MW | 47.1 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 961951 | AG1-038 C | 50/50 | 3.94 MW | 3.94 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 961952 | AG1-038 E | 50/50 | 5.45 MW | 5.45 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 966661 | AG1-536 C | 50/50 | 5.86 MW | 5.86 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 966662 | AG1-536 E | 50/50 | 7.88 MW | 7.88 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 316078 | AC2-138 E | Adder | 0.6 MW | 0.51 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 316156 | AD2-030 C | 50/50 | 0.86 MW | 0.86 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 316157 | AD2-030 E | 50/50 | 2.58 MW | 2.58 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 939245 | AE1-155 C | 50/50 | 13.96 MW | 13.96 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 939611 | AE1-191 C | 50/50 | 18.84 MW | 18.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 939612 | AE1-191 E | 50/50 | 12.56 MW | 12.56 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 940231 | AE2-005 C | 50/50 | 1.97 MW | 1.97 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 940232 | AE2-005 E | 50/50 | 3.22 MW | 3.22 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 957601 | AF2-054 C | 50/50 | 4.6 MW | 4.6 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 957602 | AF2-054 E | 50/50 | 3.06 MW | 3.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962531 | AG1-102 C | 50/50 | 4.25 MW | 4.25 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962532 | AG1-102 E | 50/50 | 8.87 MW | 8.87 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962861 | AG1-135 C | 50/50 | 7.0 MW | 7.0 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962862 | AG1-135 E | 50/50 | 4.67 MW | 4.67 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962971 | AG1-146 C | 50/50 | 4.66 MW | 4.66 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962972 | AG1-146 E | 50/50 | 3.11 MW | 3.11 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962981 | AG1-147 C | 50/50 | 10.87 MW | 10.87 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 962982 | AG1-147 E | 50/50 | 7.25 MW | 7.25 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 963611 | AG1-210 C | Adder | 0.4 MW | 0.34 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 963612 | AG1-210 E | Adder | 0.6 MW | 0.51 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 957831 | AF2-077 C | 50/50 | 8.29 MW | 8.29 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 957832 | AF2-077 E | 50/50 | 5.53 MW | 5.53 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 958261 | AF2-120 C | 50/50 | 6.81 MW | 6.81 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 958262 | AF2-120 E | 50/50 | 4.54 MW | 4.54 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | 939246 | AE1-155 E | 50/50 | 9.3 MW | 9.3 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.19 MW | 0.19 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.08 MW | 0.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.17 MW | 0.17 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 201632 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 314184 | 3SHACKLE | 50/50 | 0.84 MW | 0.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 315034 | 1NORNECKC1 | 50/50 | 0.44 MW | 0.44 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 315035 | 1NORNECKC2 | 50/50 | 0.42 MW | 0.42 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 925863 | AC1-065 C | 50/50 | 8.58 MW | 8.58 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 925865 | AC1-065 E | 50/50 | 13.79 MW | 13.79 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 934141 | AD1-041 C | 50/50 | 9.13 MW | 9.13 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 934142 | AD1-041 E | 50/50 | 6.09 MW | 6.09 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 936591 | AD2-074 C | 50/50 | 6.82 MW | 6.82 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 936592 | AD2-074 E | 50/50 | 11.12 MW | 11.12 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 943431 | AF1-014 C | 50/50 | 1.78 MW | 1.78 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 943432 | AF1-014 E | 50/50 | 3.14 MW | 3.14 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 943741 | AF1-042 C | 50/50 | 3.57 MW | 3.57 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 943742 | AF1-042 E | 50/50 | 5.82 MW | 5.82 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 945361 | AF1-201 C O1 | 50/50 | 70.54 MW | 70.54 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 945362 | AF1-201 E O1 | 50/50 | 47.03 MW | 47.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 945831 | AF1-248 | 50/50 | 0.04 MW | 0.04 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 961951 | AG1-038 C | 50/50 | 3.94 MW | 3.94 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 961952 | AG1-038 E | 50/50 | 5.44 MW | 5.44 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 966661 | AG1-536 C | 50/50 | 5.88 MW | 5.88 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 966662 | AG1-536 E | 50/50 | 7.9 MW | 7.9 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 316077 | AC2-138 C | 50/50 | 0.11 MW | 0.11 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 316078 | AC2-138 E | 50/50 | 0.62 MW | 0.62 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 316156 | AD2-030 C | 50/50 | 0.84 MW | 0.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 316157 | AD2-030 E | 50/50 | 2.54 MW | 2.54 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 939245 | AE1-155 C | 50/50 | 14.01 MW | 14.01 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 939611 | AE1-191 C | 50/50 | 18.27 MW | 18.27 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 939612 | AE1-191 E | 50/50 | 12.18 MW | 12.18 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 940231 | AE2-005 C | 50/50 | 1.88 MW | 1.88 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 940232 | AE2-005 E | 50/50 | 3.06 MW | 3.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 957601 | AF2-054 C | 50/50 | 4.52 MW | 4.52 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 957602 | AF2-054 E | 50/50 | 3.02 MW | 3.02 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962531 | AG1-102 C | 50/50 | 4.24 MW | 4.24 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962532 | AG1-102 E | 50/50 | 8.84 MW | 8.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962861 | AG1-135 C | 50/50 | 7.01 MW | 7.01 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962862 | AG1-135 E | 50/50 | 4.67 MW | 4.67 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962971 | AG1-146 C | 50/50 | 4.63 MW | 4.63 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962972 | AG1-146 E | 50/50 | 3.08 MW | 3.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962981 | AG1-147 C | 50/50 | 10.79 MW | 10.79 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 962982 | AG1-147 E | 50/50 | 7.2 MW | 7.2 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 963611 | AG1-210 C | 50/50 | 0.41 MW | 0.41 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 963612 | AG1-210 E | 50/50 | 0.62 MW | 0.62 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 957831 | AF2-077 C | 50/50 | 8.26 MW | 8.26 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 957832 | AF2-077 E | 50/50 | 5.51 MW | 5.51 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 958261 | AF2-120 C | 50/50 | 6.84 MW | 6.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 958262 | AF2-120 E | 50/50 | 4.56 MW | 4.56 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | 939246 | AE1-155 E | 50/50 | 9.34 MW | 9.34 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.19 MW | 0.19 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.08 MW | 0.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.17 MW | 0.17 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P4-2: 2016T2024 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314131 | 6ARNOLDS | 50/50 | 1.33 MW | 1.33 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314184 | 3SHACKLE | 50/50 | 0.37 MW | 0.37 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314190 | 6WESTMOR | 50/50 | 1.75 MW | 1.75 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315033 | 1BIRCHWDA | 50/50 | 45.43 MW | 45.43 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315034 | 1NORNECKC1 | 50/50 | 2.8 MW | 2.8 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315035 | 1NORNECKC2 | 50/50 | 2.7 MW | 2.7 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 925863 | AC1-065 C | 50/50 | 3.75 MW | 3.75 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 925865 | AC1-065 E | 50/50 | 6.02 MW | 6.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 926472 | AC1-118 E | 50/50 | 5.28 MW | 5.28 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 934141 | AD1-041 C | 50/50 | 3.83 MW | 3.83 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 934142 | AD1-041 E | 50/50 | 2.56 MW | 2.56 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936581 | AD2-073 C | 50/50 | 10.07 MW | 10.07 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936582 | AD2-073 E | 50/50 | 4.99 MW | 4.99 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936591 | AD2-074 C | 50/50 | 15.26 MW | 15.26 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936592 | AD2-074 E | 50/50 | 24.89 MW | 24.89 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943431 | AF1-014 C | 50/50 | 0.78 MW | 0.78 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943432 | AF1-014 E | 50/50 | 1.37 MW | 1.37 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943741 | AF1-042 C | 50/50 | 7.98 MW | 7.98 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943742 | AF1-042 E | 50/50 | 13.03 MW | 13.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944491 | AF1-114 C | 50/50 | 34.67 MW | 34.67 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944492 | AF1-114 E | 50/50 | 47.88 MW | 47.88 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 945831 | AF1-248 | 50/50 | 0.24 MW | 0.24 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961781 | AG1-019 | 50/50 | 87.58 MW | 87.58 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961951 | AG1-038 C | 50/50 | 8.82 MW | 8.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961952 | AG1-038 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966661 | AG1-536 C | 50/50 | 16.4 MW | 16.4 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966662 | AG1-536 E | 50/50 | 22.03 MW | 22.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316077 | AC2-138 C | 50/50 | 0.71 MW | 0.71 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316078 | AC2-138 E | 50/50 | 3.97 MW | 3.97 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316156 | AD2-030 C | 50/50 | 0.34 MW | 0.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316157 | AD2-030 E | 50/50 | 1.03 MW | 1.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939245 | AE1-155 C | 50/50 | 39.04 MW | 39.04 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939611 | AE1-191 C | 50/50 | 7.67 MW | 7.67 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939612 | AE1-191 E | 50/50 | 5.11 MW | 5.11 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 940231 | AE2-005 C | 50/50 | 0.82 MW | 0.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 940232 | AE2-005 E | 50/50 | 1.34 MW | 1.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957191 | AF2-013 | 50/50 | 87.58 MW | 87.58 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957601 | AF2-054 C | 50/50 | 1.83 MW | 1.83 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957602 | AF2-054 E | 50/50 | 1.22 MW | 1.22 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962861 | AG1-135 C | 50/50 | 17.73 MW | 17.73 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962862 | AG1-135 E | 50/50 | 11.82 MW | 11.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962971 | AG1-146 C | 50/50 | 6.8 MW | 6.8 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962972 | AG1-146 E | 50/50 | 4.53 MW | 4.53 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962981 | AG1-147 C | 50/50 | 15.87 MW | 15.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962982 | AG1-147 E | 50/50 | 10.58 MW | 10.58 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963611 | AG1-210 C | 50/50 | 2.64 MW | 2.64 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963612 | AG1-210 E | 50/50 | 3.97 MW | 3.97 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957971 | AF2-091 C | 50/50 | 11.79 MW | 11.79 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957972 | AF2-091 E | 50/50 | 16.28 MW | 16.28 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958261 | AF2-120 C | 50/50 | 19.06 MW | 19.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958262 | AF2-120 E | 50/50 | 12.71 MW | 12.71 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939246 | AE1-155 E | 50/50 | 26.03 MW | 26.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.0 MW | 3.0 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.4 MW | 0.4 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.42 MW | 2.42 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.12 MW | 0.12 MW |
| Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314131 | 6ARNOLDS | 50/50 | 1.33 MW | 1.33 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314184 | 3SHACKLE | 50/50 | 0.37 MW | 0.37 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314190 | 6WESTMOR | 50/50 | 1.75 MW | 1.75 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315033 | 1BIRCHWDA | 50/50 | 45.42 MW | 45.42 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315034 | 1NORNECKC1 | 50/50 | 2.8 MW | 2.8 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315035 | 1NORNECKC2 | 50/50 | 2.7 MW | 2.7 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 925863 | AC1-065 C | 50/50 | 3.77 MW | 3.77 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 925865 | AC1-065 E | 50/50 | 6.05 MW | 6.05 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 926472 | AC1-118 E | 50/50 | 5.28 MW | 5.28 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 934141 | AD1-041 C | 50/50 | 3.82 MW | 3.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 934142 | AD1-041 E | 50/50 | 2.55 MW | 2.55 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936581 | AD2-073 C | 50/50 | 10.06 MW | 10.06 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936582 | AD2-073 E | 50/50 | 4.99 MW | 4.99 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936591 | AD2-074 C | 50/50 | 15.22 MW | 15.22 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936592 | AD2-074 E | 50/50 | 24.84 MW | 24.84 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943431 | AF1-014 C | 50/50 | 0.78 MW | 0.78 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943432 | AF1-014 E | 50/50 | 1.38 MW | 1.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943741 | AF1-042 C | 50/50 | 7.96 MW | 7.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943742 | AF1-042 E | 50/50 | 13.0 MW | 13.0 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 944491 | AF1-114 C | 50/50 | 34.66 MW | 34.66 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 944492 | AF1-114 E | 50/50 | 47.87 MW | 47.87 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 945831 | AF1-248 | 50/50 | 0.24 MW | 0.24 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961781 | AG1-019 | 50/50 | 87.56 MW | 87.56 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961951 | AG1-038 C | 50/50 | 8.8 MW | 8.8 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961952 | AG1-038 E | 50/50 | 12.16 MW | 12.16 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 966661 | AG1-536 C | 50/50 | 16.36 MW | 16.36 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 966662 | AG1-536 E | 50/50 | 21.99 MW | 21.99 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316077 | AC2-138 C | 50/50 | 0.71 MW | 0.71 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316078 | AC2-138 E | 50/50 | 3.96 MW | 3.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316156 | AD2-030 C | 50/50 | 0.34 MW | 0.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316157 | AD2-030 E | 50/50 | 1.02 MW | 1.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939245 | AE1-155 C | 50/50 | 38.97 MW | 38.97 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939611 | AE1-191 C | 50/50 | 7.64 MW | 7.64 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939612 | AE1-191 E | 50/50 | 5.09 MW | 5.09 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 940231 | AE2-005 C | 50/50 | 0.82 MW | 0.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 940232 | AE2-005 E | 50/50 | 1.34 MW | 1.34 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957191 | AF2-013 | 50/50 | 87.56 MW | 87.56 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957601 | AF2-054 C | 50/50 | 1.81 MW | 1.81 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957602 | AF2-054 E | 50/50 | 1.21 MW | 1.21 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962861 | AG1-135 C | 50/50 | 17.69 MW | 17.69 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962862 | AG1-135 E | 50/50 | 11.79 MW | 11.79 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962971 | AG1-146 C | 50/50 | 6.78 MW | 6.78 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962972 | AG1-146 E | 50/50 | 4.52 MW | 4.52 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962981 | AG1-147 C | 50/50 | 15.82 MW | 15.82 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962982 | AG1-147 E | 50/50 | 10.54 MW | 10.54 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 963611 | AG1-210 C | 50/50 | 2.64 MW | 2.64 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 963612 | AG1-210 E | 50/50 | 3.96 MW | 3.96 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957971 | AF2-091 C | 50/50 | 11.79 MW | 11.79 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957972 | AF2-091 E | 50/50 | 16.27 MW | 16.27 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 958261 | AF2-120 C | 50/50 | 19.02 MW | 19.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 958262 | AF2-120 E | 50/50 | 12.68 MW | 12.68 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939246 | AE1-155 E | 50/50 | 25.98 MW | 25.98 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.93 MW | 2.93 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.38 MW | 0.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.41 MW | 2.41 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314131 | 6ARNOLDS | 50/50 | 1.33 MW | 1.33 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314184 | 3SHACKLE | 50/50 | 0.37 MW | 0.37 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 314190 | 6WESTMOR | 50/50 | 1.75 MW | 1.75 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315033 | 1BIRCHWDA | 50/50 | 45.43 MW | 45.43 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315034 | 1NORNECKC1 | 50/50 | 2.8 MW | 2.8 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 315035 | 1NORNECKC2 | 50/50 | 2.7 MW | 2.7 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 925863 | AC1-065 C | 50/50 | 3.75 MW | 3.75 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 925865 | AC1-065 E | 50/50 | 6.02 MW | 6.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 926472 | AC1-118 E | 50/50 | 5.28 MW | 5.28 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 934141 | AD1-041 C | 50/50 | 3.83 MW | 3.83 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 934142 | AD1-041 E | 50/50 | 2.56 MW | 2.56 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936581 | AD2-073 C | 50/50 | 10.07 MW | 10.07 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936582 | AD2-073 E | 50/50 | 4.99 MW | 4.99 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936591 | AD2-074 C | 50/50 | 15.26 MW | 15.26 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 936592 | AD2-074 E | 50/50 | 24.89 MW | 24.89 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943431 | AF1-014 C | 50/50 | 0.78 MW | 0.78 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943432 | AF1-014 E | 50/50 | 1.37 MW | 1.37 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943741 | AF1-042 C | 50/50 | 7.98 MW | 7.98 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 943742 | AF1-042 E | 50/50 | 13.03 MW | 13.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944491 | AF1-114 C | 50/50 | 34.67 MW | 34.67 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 944492 | AF1-114 E | 50/50 | 47.88 MW | 47.88 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 945831 | AF1-248 | 50/50 | 0.24 MW | 0.24 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961781 | AG1-019 | 50/50 | 87.58 MW | 87.58 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961951 | AG1-038 C | 50/50 | 8.82 MW | 8.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 961952 | AG1-038 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966661 | AG1-536 C | 50/50 | 16.4 MW | 16.4 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 966662 | AG1-536 E | 50/50 | 22.03 MW | 22.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316077 | AC2-138 C | 50/50 | 0.71 MW | 0.71 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316078 | AC2-138 E | 50/50 | 3.97 MW | 3.97 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316156 | AD2-030 C | 50/50 | 0.34 MW | 0.34 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 316157 | AD2-030 E | 50/50 | 1.03 MW | 1.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939245 | AE1-155 C | 50/50 | 39.04 MW | 39.04 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939611 | AE1-191 C | 50/50 | 7.67 MW | 7.67 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939612 | AE1-191 E | 50/50 | 5.11 MW | 5.11 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 940231 | AE2-005 C | 50/50 | 0.82 MW | 0.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 940232 | AE2-005 E | 50/50 | 1.34 MW | 1.34 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957191 | AF2-013 | 50/50 | 87.58 MW | 87.58 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957601 | AF2-054 C | 50/50 | 1.83 MW | 1.83 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957602 | AF2-054 E | 50/50 | 1.22 MW | 1.22 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962861 | AG1-135 C | 50/50 | 17.73 MW | 17.73 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962862 | AG1-135 E | 50/50 | 11.82 MW | 11.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962971 | AG1-146 C | 50/50 | 6.8 MW | 6.8 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962972 | AG1-146 E | 50/50 | 4.53 MW | 4.53 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962981 | AG1-147 C | 50/50 | 15.87 MW | 15.87 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 962982 | AG1-147 E | 50/50 | 10.58 MW | 10.58 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963611 | AG1-210 C | 50/50 | 2.64 MW | 2.64 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 963612 | AG1-210 E | 50/50 | 3.97 MW | 3.97 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957971 | AF2-091 C | 50/50 | 11.79 MW | 11.79 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 957972 | AF2-091 E | 50/50 | 16.28 MW | 16.28 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958261 | AF2-120 C | 50/50 | 19.06 MW | 19.06 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 958262 | AF2-120 E | 50/50 | 12.71 MW | 12.71 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | 939246 | AE1-155 E | 50/50 | 26.03 MW | 26.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.0 MW | 3.0 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.4 MW | 0.4 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.42 MW | 2.42 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 224T2129 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.12 MW | 0.12 MW |
| Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314131 | 6ARNOLDS | 50/50 | 1.33 MW | 1.33 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314184 | 3SHACKLE | 50/50 | 0.37 MW | 0.37 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 314190 | 6WESTMOR | 50/50 | 1.75 MW | 1.75 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315033 | 1BIRCHWDA | 50/50 | 45.42 MW | 45.42 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315034 | 1NORNECKC1 | 50/50 | 2.8 MW | 2.8 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 315035 | 1NORNECKC2 | 50/50 | 2.7 MW | 2.7 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 925863 | AC1-065 C | 50/50 | 3.77 MW | 3.77 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 925865 | AC1-065 E | 50/50 | 6.05 MW | 6.05 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 926472 | AC1-118 E | 50/50 | 5.28 MW | 5.28 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 934141 | AD1-041 C | 50/50 | 3.82 MW | 3.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 934142 | AD1-041 E | 50/50 | 2.55 MW | 2.55 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936581 | AD2-073 C | 50/50 | 10.06 MW | 10.06 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936582 | AD2-073 E | 50/50 | 4.99 MW | 4.99 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936591 | AD2-074 C | 50/50 | 15.22 MW | 15.22 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 936592 | AD2-074 E | 50/50 | 24.84 MW | 24.84 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943431 | AF1-014 C | 50/50 | 0.78 MW | 0.78 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943432 | AF1-014 E | 50/50 | 1.38 MW | 1.38 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943741 | AF1-042 C | 50/50 | 7.96 MW | 7.96 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 943742 | AF1-042 E | 50/50 | 13.0 MW | 13.0 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 944491 | AF1-114 C | 50/50 | 34.66 MW | 34.66 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 944492 | AF1-114 E | 50/50 | 47.87 MW | 47.87 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 945831 | AF1-248 | 50/50 | 0.24 MW | 0.24 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961781 | AG1-019 | 50/50 | 87.56 MW | 87.56 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961951 | AG1-038 C | 50/50 | 8.8 MW | 8.8 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 961952 | AG1-038 E | 50/50 | 12.16 MW | 12.16 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 966661 | AG1-536 C | 50/50 | 16.36 MW | 16.36 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 966662 | AG1-536 E | 50/50 | 21.99 MW | 21.99 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316077 | AC2-138 C | 50/50 | 0.71 MW | 0.71 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316078 | AC2-138 E | 50/50 | 3.96 MW | 3.96 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316156 | AD2-030 C | 50/50 | 0.34 MW | 0.34 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 316157 | AD2-030 E | 50/50 | 1.02 MW | 1.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939245 | AE1-155 C | 50/50 | 38.97 MW | 38.97 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939611 | AE1-191 C | 50/50 | 7.64 MW | 7.64 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939612 | AE1-191 E | 50/50 | 5.09 MW | 5.09 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 940231 | AE2-005 C | 50/50 | 0.82 MW | 0.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 940232 | AE2-005 E | 50/50 | 1.34 MW | 1.34 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957191 | AF2-013 | 50/50 | 87.56 MW | 87.56 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957601 | AF2-054 C | 50/50 | 1.81 MW | 1.81 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957602 | AF2-054 E | 50/50 | 1.21 MW | 1.21 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962861 | AG1-135 C | 50/50 | 17.69 MW | 17.69 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962862 | AG1-135 E | 50/50 | 11.79 MW | 11.79 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962971 | AG1-146 C | 50/50 | 6.78 MW | 6.78 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962972 | AG1-146 E | 50/50 | 4.52 MW | 4.52 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962981 | AG1-147 C | 50/50 | 15.82 MW | 15.82 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 962982 | AG1-147 E | 50/50 | 10.54 MW | 10.54 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 963611 | AG1-210 C | 50/50 | 2.64 MW | 2.64 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 963612 | AG1-210 E | 50/50 | 3.96 MW | 3.96 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957971 | AF2-091 C | 50/50 | 11.79 MW | 11.79 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 957972 | AF2-091 E | 50/50 | 16.27 MW | 16.27 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 958261 | AF2-120 C | 50/50 | 19.02 MW | 19.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 958262 | AF2-120 E | 50/50 | 12.68 MW | 12.68 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | 939246 | AE1-155 E | 50/50 | 25.98 MW | 25.98 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.93 MW | 2.93 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.38 MW | 0.38 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.27 MW | 0.27 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.41 MW | 2.41 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 22432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| Details for AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315034 | 1NORNECKC1 | 50/50 | 0.6 MW | 0.6 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315035 | 1NORNECKC2 | 50/50 | 0.58 MW | 0.58 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934141 | AD1-041 C | 50/50 | 17.22 MW | 17.22 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934142 | AD1-041 E | 50/50 | 11.48 MW | 11.48 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936591 | AD2-074 C | 50/50 | 10.03 MW | 10.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936592 | AD2-074 E | 50/50 | 16.36 MW | 16.36 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943741 | AF1-042 C | 50/50 | 5.25 MW | 5.25 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943742 | AF1-042 E | 50/50 | 8.56 MW | 8.56 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945361 | AF1-201 C O1 | 50/50 | 76.51 MW | 76.51 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945362 | AF1-201 E O1 | 50/50 | 51.01 MW | 51.01 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945831 | AF1-248 | 50/50 | 0.05 MW | 0.05 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961951 | AG1-038 C | 50/50 | 5.8 MW | 5.8 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961952 | AG1-038 E | 50/50 | 8.01 MW | 8.01 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966661 | AG1-536 C | 50/50 | 8.57 MW | 8.57 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966662 | AG1-536 E | 50/50 | 11.52 MW | 11.52 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316077 | AC2-138 C | 50/50 | 0.15 MW | 0.15 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316078 | AC2-138 E | 50/50 | 0.85 MW | 0.85 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316156 | AD2-030 C | 50/50 | 1.28 MW | 1.28 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316157 | AD2-030 E | 50/50 | 3.85 MW | 3.85 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939245 | AE1-155 C | 50/50 | 20.42 MW | 20.42 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939611 | AE1-191 C | 50/50 | 34.44 MW | 34.44 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939612 | AE1-191 E | 50/50 | 22.96 MW | 22.96 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957601 | AF2-054 C | 50/50 | 6.85 MW | 6.85 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957602 | AF2-054 E | 50/50 | 4.57 MW | 4.57 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962531 | AG1-102 C | 50/50 | 4.83 MW | 4.83 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962532 | AG1-102 E | 50/50 | 10.08 MW | 10.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962861 | AG1-135 C | 50/50 | 10.26 MW | 10.26 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962862 | AG1-135 E | 50/50 | 6.84 MW | 6.84 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962971 | AG1-146 C | 50/50 | 6.89 MW | 6.89 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962972 | AG1-146 E | 50/50 | 4.59 MW | 4.59 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962981 | AG1-147 C | 50/50 | 16.07 MW | 16.07 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962982 | AG1-147 E | 50/50 | 10.72 MW | 10.72 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963611 | AG1-210 C | 50/50 | 0.56 MW | 0.56 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963612 | AG1-210 E | 50/50 | 0.85 MW | 0.85 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957831 | AF2-077 C | 50/50 | 9.42 MW | 9.42 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957832 | AF2-077 E | 50/50 | 6.28 MW | 6.28 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958261 | AF2-120 C | 50/50 | 9.97 MW | 9.97 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958262 | AF2-120 E | 50/50 | 6.64 MW | 6.64 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939246 | AE1-155 E | 50/50 | 13.61 MW | 13.61 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.18 MW | 0.18 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.09 MW | 0.09 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.18 MW | 0.18 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF1-201 TAP-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315034 | 1NORNECKC1 | 50/50 | 0.6 MW | 0.6 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315035 | 1NORNECKC2 | 50/50 | 0.58 MW | 0.58 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 926472 | AC1-118 E | Adder | 0.42 MW | 0.36 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934141 | AD1-041 C | 50/50 | 17.22 MW | 17.22 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934142 | AD1-041 E | 50/50 | 11.48 MW | 11.48 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936581 | AD2-073 C | Adder | 0.9 MW | 0.77 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936582 | AD2-073 E | Adder | 0.45 MW | 0.38 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936591 | AD2-074 C | 50/50 | 10.03 MW | 10.03 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936592 | AD2-074 E | 50/50 | 16.36 MW | 16.36 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943741 | AF1-042 C | 50/50 | 5.25 MW | 5.25 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943742 | AF1-042 E | 50/50 | 8.56 MW | 8.56 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945831 | AF1-248 | 50/50 | 0.05 MW | 0.05 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961951 | AG1-038 C | 50/50 | 5.8 MW | 5.8 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961952 | AG1-038 E | 50/50 | 8.01 MW | 8.01 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966661 | AG1-536 C | 50/50 | 8.57 MW | 8.57 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966662 | AG1-536 E | 50/50 | 11.52 MW | 11.52 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316077 | AC2-138 C | 50/50 | 0.15 MW | 0.15 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316078 | AC2-138 E | 50/50 | 0.85 MW | 0.85 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316156 | AD2-030 C | 50/50 | 1.28 MW | 1.28 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316157 | AD2-030 E | 50/50 | 3.85 MW | 3.85 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939245 | AE1-155 C | 50/50 | 20.42 MW | 20.42 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939611 | AE1-191 C | 50/50 | 34.44 MW | 34.44 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939612 | AE1-191 E | 50/50 | 22.96 MW | 22.96 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957601 | AF2-054 C | 50/50 | 6.85 MW | 6.85 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957602 | AF2-054 E | 50/50 | 4.57 MW | 4.57 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962861 | AG1-135 C | 50/50 | 10.26 MW | 10.26 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962862 | AG1-135 E | 50/50 | 6.84 MW | 6.84 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962971 | AG1-146 C | 50/50 | 6.89 MW | 6.89 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962972 | AG1-146 E | 50/50 | 4.59 MW | 4.59 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962981 | AG1-147 C | 50/50 | 16.07 MW | 16.07 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962982 | AG1-147 E | 50/50 | 10.72 MW | 10.72 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963611 | AG1-210 C | 50/50 | 0.56 MW | 0.56 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963612 | AG1-210 E | 50/50 | 0.85 MW | 0.85 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958261 | AF2-120 C | 50/50 | 9.97 MW | 9.97 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958262 | AF2-120 E | 50/50 | 6.64 MW | 6.64 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939246 | AE1-155 E | 50/50 | 13.61 MW | 13.61 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962533 | AG1-102 BAT | 50/50 | 4.08 MW | 4.08 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945363 | AF1-201 BAT | 50/50 | 3.0 MW | 3.0 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.18 MW | 0.18 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.09 MW | 0.09 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.18 MW | 0.18 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 3HARMONY-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 314177 | 3HAYES89 | 50/50 | 0.27 MW | 0.27 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 315034 | 1NORNECKC1 | 50/50 | 0.6 MW | 0.6 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 315035 | 1NORNECKC2 | 50/50 | 0.58 MW | 0.58 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 934141 | AD1-041 C | 50/50 | 17.22 MW | 17.22 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 934142 | AD1-041 E | 50/50 | 11.48 MW | 11.48 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 936591 | AD2-074 C | 50/50 | 10.03 MW | 10.03 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 936592 | AD2-074 E | 50/50 | 16.36 MW | 16.36 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 943741 | AF1-042 C | 50/50 | 5.25 MW | 5.25 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 943742 | AF1-042 E | 50/50 | 8.56 MW | 8.56 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 945361 | AF1-201 C O1 | 50/50 | 76.51 MW | 76.51 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 945362 | AF1-201 E O1 | 50/50 | 51.01 MW | 51.01 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 945831 | AF1-248 | 50/50 | 0.05 MW | 0.05 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 961951 | AG1-038 C | 50/50 | 5.8 MW | 5.8 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 961952 | AG1-038 E | 50/50 | 8.01 MW | 8.01 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 966661 | AG1-536 C | 50/50 | 8.57 MW | 8.57 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 966662 | AG1-536 E | 50/50 | 11.52 MW | 11.52 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 316077 | AC2-138 C | 50/50 | 0.15 MW | 0.15 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 316078 | AC2-138 E | 50/50 | 0.85 MW | 0.85 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 316156 | AD2-030 C | 50/50 | 1.28 MW | 1.28 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 316157 | AD2-030 E | 50/50 | 3.85 MW | 3.85 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 939245 | AE1-155 C | 50/50 | 20.42 MW | 20.42 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 939611 | AE1-191 C | 50/50 | 34.44 MW | 34.44 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 939612 | AE1-191 E | 50/50 | 22.96 MW | 22.96 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 957601 | AF2-054 C | 50/50 | 6.85 MW | 6.85 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 957602 | AF2-054 E | 50/50 | 4.57 MW | 4.57 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962531 | AG1-102 C | 50/50 | 4.83 MW | 4.83 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962532 | AG1-102 E | 50/50 | 10.08 MW | 10.08 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962861 | AG1-135 C | 50/50 | 10.26 MW | 10.26 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962862 | AG1-135 E | 50/50 | 6.84 MW | 6.84 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962971 | AG1-146 C | 50/50 | 6.89 MW | 6.89 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962972 | AG1-146 E | 50/50 | 4.59 MW | 4.59 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962981 | AG1-147 C | 50/50 | 16.07 MW | 16.07 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 962982 | AG1-147 E | 50/50 | 10.72 MW | 10.72 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 963611 | AG1-210 C | 50/50 | 0.56 MW | 0.56 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 963612 | AG1-210 E | 50/50 | 0.85 MW | 0.85 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 957831 | AF2-077 C | 50/50 | 9.42 MW | 9.42 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 957832 | AF2-077 E | 50/50 | 6.28 MW | 6.28 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 958261 | AF2-120 C | 50/50 | 9.97 MW | 9.97 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 958262 | AF2-120 E | 50/50 | 6.64 MW | 6.64 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | 939246 | AE1-155 E | 50/50 | 13.61 MW | 13.61 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.18 MW | 0.18 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.09 MW | 0.09 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.18 MW | 0.18 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 3HAYES89-6HAYES 115.0/230.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 85-2016-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315034 | 1NORNECKC1 | 50/50 | 0.6 MW | 0.6 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 315035 | 1NORNECKC2 | 50/50 | 0.58 MW | 0.58 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934141 | AD1-041 C | 50/50 | 17.22 MW | 17.22 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 934142 | AD1-041 E | 50/50 | 11.48 MW | 11.48 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936591 | AD2-074 C | 50/50 | 10.03 MW | 10.03 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 936592 | AD2-074 E | 50/50 | 16.36 MW | 16.36 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943741 | AF1-042 C | 50/50 | 5.25 MW | 5.25 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 943742 | AF1-042 E | 50/50 | 8.56 MW | 8.56 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945831 | AF1-248 | 50/50 | 0.05 MW | 0.05 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961951 | AG1-038 C | 50/50 | 5.8 MW | 5.8 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 961952 | AG1-038 E | 50/50 | 8.01 MW | 8.01 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966661 | AG1-536 C | 50/50 | 8.57 MW | 8.57 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 966662 | AG1-536 E | 50/50 | 11.52 MW | 11.52 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316077 | AC2-138 C | 50/50 | 0.15 MW | 0.15 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316078 | AC2-138 E | 50/50 | 0.85 MW | 0.85 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316156 | AD2-030 C | 50/50 | 1.28 MW | 1.28 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 316157 | AD2-030 E | 50/50 | 3.85 MW | 3.85 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939245 | AE1-155 C | 50/50 | 20.42 MW | 20.42 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939611 | AE1-191 C | 50/50 | 34.44 MW | 34.44 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939612 | AE1-191 E | 50/50 | 22.96 MW | 22.96 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957601 | AF2-054 C | 50/50 | 6.85 MW | 6.85 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957602 | AF2-054 E | 50/50 | 4.57 MW | 4.57 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962531 | AG1-102 C | 50/50 | 4.83 MW | 4.83 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962532 | AG1-102 E | 50/50 | 10.08 MW | 10.08 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962861 | AG1-135 C | 50/50 | 10.26 MW | 10.26 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962862 | AG1-135 E | 50/50 | 6.84 MW | 6.84 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962971 | AG1-146 C | 50/50 | 6.89 MW | 6.89 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962972 | AG1-146 E | 50/50 | 4.59 MW | 4.59 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962981 | AG1-147 C | 50/50 | 16.07 MW | 16.07 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 962982 | AG1-147 E | 50/50 | 10.72 MW | 10.72 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963611 | AG1-210 C | 50/50 | 0.56 MW | 0.56 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 963612 | AG1-210 E | 50/50 | 0.85 MW | 0.85 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957831 | AF2-077 C | 50/50 | 9.42 MW | 9.42 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 957832 | AF2-077 E | 50/50 | 6.28 MW | 6.28 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958261 | AF2-120 C | 50/50 | 9.97 MW | 9.97 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 958262 | AF2-120 E | 50/50 | 6.64 MW | 6.64 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 939246 | AE1-155 E | 50/50 | 13.61 MW | 13.61 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | 945363 | AF1-201 BAT | 50/50 | 3.0 MW | 3.0 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.18 MW | 0.18 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.09 MW | 0.09 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.2 MW | 0.2 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.18 MW | 0.18 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 3WHITEMARSH-AF1-201 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 85-2016-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7697 | Hayes Substation : Transformer Addition | $6,000,000 | |
| n7614 | Reconductor 1.4 miles of 115 kV Line 89 from Hayes to AF1-201 Tap with 768.2 ACSS 250 C. Replace Line Switch at Hayes terminal. | $1,040,000 | |
| n7555 | Reconductor 5.9 miles of 115 kV Line 65 from AG1-146 Tap to Lancaster with 768.2 ACSS 250 C. replace Line Switch at Lancaster terminal. | $4,100,000 | |
| n7613 | Reconductor 10.06 miles of 138 kV line 65 from AE1-155 Tap to Northern Neck with 768 ACSS 250 C. Replace Line Switch and wave trap at Northern neck terminal | $6,386,000 | |
| n7696 | Reconductor 5.63 miles of 115 kV Line 89 from Harmony Village to White Marsh with 636 ACSR 150 C. | $3,378,000 | |
| n7695 | Reconductor 5.59 miles of 115 kV line 89 from White Marsh to AF1-201 Tap with 636 ACSR 150 C | $3,354,000 | |
| n7576 | Rebuild 4.87 mi miles of 230 kV Line 2083 from Birchwood to Fines with 2-636 ACSR (24/7) 150 C. | $12,175,000 | |
| n8149 | Add Additional 500/230 kV Transformer at Elmont Substation | $22,000,000 | |
| n7575 | Rebuild 7.24 mi miles of 230 kV Line 2083 from Fredericksburg to Fines with 2-636 ACSR (24/7) 150 C. | $18,100,000 | |
Attachments
Download all tables in report
| Uprate Chain | |||||
|---|---|---|---|---|---|
| Project | Project Status | MFO | MWE | MWC | Disposition |
| AG1-146 | Active | 30.0 | 30.0 | 18.0 | Transition Cycle 1 |
| AG1-147 | Active | 100.0 | 70.0 | 42.0 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-147 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.