AG1-121 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:44
Kewanee-Streator 138 kV
51.9 MW Capacity / 294.7 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-121 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Wind generating facility located in the ComEd zone — Bureau County, Illinois. The installed facilities will have a total capability of 294.7 MW with 51.9 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-121 |
| Project Name | Kewanee-Streator 138 kV |
| Developer Name | Leeward Renewable Energy Development, LLC |
| State | Illinois |
| County | Bureau |
| Transmission Owner | ComEd |
| MFO | 294.7 MW |
| MWE | 294.7 MW |
| MWC | 51.9 MW |
| Fuel Type | Wind |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-121 will interconnect on the ComEd transmission system tapping the Kewanee to Streator 138 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 294.7 MW (Capacity 51.9 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 140.23 % | 143.01 % | 179.0 | B | 255.99 | 5.09 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P1-2_138-L6101___-S-B
CONTINGENCY 'COMED_P1-2_138-L6101___-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 140.47 % | 143.1 % | 179.0 | B | 256.16 | 4.85 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 166.2 % | 166.64 % | 1466.0 | B | 2442.97 | 23.94 | |
| AMIL/CE |
HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line
271655 to 348918 ckt 1 |
COMED_P4_074-38-L6101__
CONTINGENCY 'COMED_P4_074-38-L6101__' DISCONNECT BUS 271835 /*KEWANEE ;23 138.0 DISCONNECT BUS 271839 /*KEWANEE ;22 138.0 DISCONNECT BUS 271845 /*KEWANEE ;21 138.0 TRIP BRANCH FROM BUS 965670 TO BUS 271835 CKT 1 /*AG1-435 TAP 138.0 - KEWANEE ;23 138.0 END |
Breaker | AC | 40.34 % | 117.24 % | 305.0 | B | 357.59 | 246.44 | |
| AMIL/CE |
HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line
271655 to 348918 ckt 1 |
COMED_P4_074-38-L94301_
CONTINGENCY 'COMED_P4_074-38-L94301_' DISCONNECT BUS 271835 /*KEWANEE ;23 138.0 DISCONNECT BUS 271839 /*KEWANEE ;22 138.0 DISCONNECT BUS 271845 /*KEWANEE ;21 138.0 REMOVE UNIT W1 FROM BUS 274877 /*BISHOP HL;1U 0.7 REMOVE UNIT W2 FROM BUS 274878 /*BISHOP HL;2U 0.7 TRIP BRANCH FROM BUS 271134 TO BUS 271845 CKT 1 /*BISHOP HL; 138.0 - KEWANEE ;21 138.0 TRIP BRANCH FROM BUS 271134 TO BUS 274452 CKT 1 /*BISHOP HL; 138.0 - BISHOP HL; 1 34.5 TRIP BRANCH FROM BUS 271134 TO BUS 274453 CKT 1 /*BISHOP HL; 138.0 - BISHOP HL; 2 34.5 TRIP BRANCH FROM BUS 274422 TO BUS 274877 CKT 1 /*BISHOP HL;1H 34.5 - BISHOP HL;1U 0.7 TRIP BRANCH FROM BUS 274423 TO BUS 274878 CKT 1 /*BISHOP HL;2H 34.5 - BISHOP HL;2U 0.7 TRIP BRANCH FROM BUS 274452 TO BUS 274422 CKT 1 /*BISHOP HL; 1 34.5 - BISHOP HL;1H 34.5 TRIP BRANCH FROM BUS 274453 TO BUS 274423 CKT 1 /*BISHOP HL; 2 34.5 - BISHOP HL;2H 34.5 END |
Breaker | AC | 40.34 % | 117.24 % | 305.0 | B | 357.59 | 246.44 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3130_05EUGENE 345_B2
CONTINGENCY 'AEP_P4_#3130_05EUGENE 345_B2' OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 154.21 % | 154.54 % | 1466.0 | B | 2265.63 | 24.37 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-L11614_
CONTINGENCY 'COMED_P4_116-45-L11614_' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1 /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1 /*BLUE ISL ;RT 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1 /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0 END |
Breaker | AC | 111.57 % | 112.52 % | 2083.0 | STE | 2343.86 | 23.02 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P4_074-38-L15508_
CONTINGENCY 'COMED_P4_074-38-L15508_' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 MOVE 100 PERCENT LOAD FROM BUS 271331 TO BUS 271330 /*DIXON ;8R 138.0 - DIXON ;7B 138.0 TRIP BRANCH FROM BUS 271331 TO BUS 271333 CKT 1 /*DIXON ;8R 138.0 - DIXON ; R 138.0 TRIP BRANCH FROM BUS 272097 TO BUS 271331 CKT 1 /*NELSON ;RT 138.0 - DIXON ;8R 138.0 TRIP BRANCH FROM BUS 272097 TO BUS 272095 CKT 1 /*NELSON ;RT 138.0 - NELSON ; R 138.0 TRIP BRANCH FROM BUS 272505 TO BUS 272097 CKT 1 /*SCHAUFF R; R 138.0 - NELSON ;RT 138.0 END |
Breaker | AC | 104.98 % | 115.34 % | 265.0 | ALDR | 305.64 | 30.12 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P4_074-38-L7413__
CONTINGENCY 'COMED_P4_074-38-L7413__' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 END |
Breaker | AC | 104.5 % | 114.77 % | 265.0 | ALDR | 304.14 | 29.9 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-TR82___
CONTINGENCY 'COMED_P4_116-45-TR82___' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 271565 TO BUS 275324 CKT 1 /*GOODINGS ;2R 345.0 - GOODINGS ; R 138.0 - GOODINGS ;2C 34.5 END |
Breaker | AC | 108.03 % | 108.98 % | 2083.0 | STE | 2270.03 | 22.92 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P4_001-38-TR81___
CONTINGENCY 'COMED_P4_001-38-TR81___' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 TRIP BRANCH FROM BUS 270802 TO BUS 270803 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; R 345.0 TRIP BRANCH FROM BUS 270802 TO BUS 271908 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; B 138.0 END |
Breaker | AC | 109.4 % | 124.37 % | 223.0 | B | 277.34 | 35.14 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_116-45-L0303__
CONTINGENCY 'COMED_P4_116-45-L0303__' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Breaker | AC | 106.31 % | 107.26 % | 2083.0 | STE | 2234.25 | 22.93 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_112-45-BT4-5__
CONTINGENCY 'COMED_P4_112-45-BT4-5__' TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1 /*PONTIAC ; B 345.0 - LORETTO ; B 345.0 END |
Breaker | AC | 103.02 % | 104.41 % | 2083.0 | STE | 2174.76 | 27.08 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_076-45-BT4-5__
CONTINGENCY 'COMED_P4_076-45-BT4-5__' TRIP BRANCH FROM BUS 270664 TO BUS 275162 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 270664 TO BUS 275181 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;4M 138.0 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270674 TO BUS 270664 CKT 1 /*BURNHAM ; B 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 275162 TO BUS 271100 CKT 1 /*BLUE ISL ;3M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275181 TO BUS 271100 CKT 1 /*BLUE ISL ;4M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275262 TO BUS 275162 CKT 1 /*BLUE ISLA;3C 34.5 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 275281 TO BUS 275181 CKT 1 /*BLUE ISLA;4C 34.5 - BLUE ISL ;4M 138.0 END |
Breaker | AC | 102.11 % | 103.2 % | 2083.0 | STE | 2149.71 | 26.19 | |
| CE |
PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275207 to 270630 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 115.55 % | 115.93 % | 1469.0 | STE | 1703.05 | 20.16 | |
| CE |
PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line
270846 to 275207 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 115.4 % | 115.79 % | 1469.0 | STE | 1700.94 | 20.16 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 114.32 % | 114.6 % | 1469.0 | STE | 1683.52 | 19.2 | |
| CE |
PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line
270847 to 275208 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 113.91 % | 114.19 % | 1469.0 | STE | 1677.43 | 19.2 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 101.78 % | 103.1 % | 1656.0 | B | 1707.3 | 25.15 | |
| AMIL/CE |
KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line
271835 to 348962 ckt 1 |
COMED_P4_187-38-BT5-6__
CONTINGENCY 'COMED_P4_187-38-BT5-6__' DISCONNECT BUS 272719 /*WALNUT RG; 138.0 DISCONNECT BUS 274399 /*WALNUT RG; 34.5 DISCONNECT BUS 293513 /*O-009 C1 0.7 DISCONNECT BUS 293514 /*O-009 C2 0.6 DISCONNECT BUS 293515 /*O-009 C3 0.6 MOVE 100 PERCENT LOAD FROM BUS 272110 TO BUS 272111 /*NORMANDY ; B 138.0 - NORMANDY ; R 138.0 REMOVE UNIT W1 FROM BUS 293513 /*O-009 C1 0.7 REMOVE UNIT W1 FROM BUS 293514 /*O-009 C2 0.6 REMOVE UNIT W1 FROM BUS 293515 /*O-009 C3 0.6 TRIP BRANCH FROM BUS 271836 TO BUS 272110 CKT 1 /*KEWANEE ;11 138.0 - NORMANDY ; B 138.0 TRIP BRANCH FROM BUS 272110 TO BUS 272505 CKT 1 /*NORMANDY ; B 138.0 - SCHAUFF R; R 138.0 TRIP BRANCH FROM BUS 272505 TO BUS 272719 CKT 1 /*SCHAUFF R; R 138.0 - WALNUT RG; 138.0 END |
Breaker | AC | 81.31 % | 100.05 % | 223.0 | B | 223.11 | 43.14 | |
| AMIL/CE |
HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line
271655 to 348918 ckt 1 |
COMED_P2-2_074_KE-138___2
CONTINGENCY 'COMED_P2-2_074_KE-138___2' DISCONNECT BUS 271835 /*KEWANEE ;23 138.0 DISCONNECT BUS 271839 /*KEWANEE ;22 138.0 DISCONNECT BUS 271845 /*KEWANEE ;21 138.0 END |
Bus | AC | 40.34 % | 117.24 % | 305.0 | B | 357.57 | 246.44 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 117.6 % | 129.8 % | 265.0 | ALDR | 343.97 | 35.14 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P2-2_#286_05EUGENE 345_2
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Bus | AC | 156.7 % | 156.81 % | 1466.0 | B | 2298.83 | 24.25 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P2-2_074_KE-138___1
CONTINGENCY 'COMED_P2-2_074_KE-138___1' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 END |
Bus | AC | 104.51 % | 114.78 % | 265.0 | ALDR | 304.16 | 29.9 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P2-2_116_GG-345R__2
CONTINGENCY 'COMED_P2-2_116_GG-345R__2' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 END |
Bus | AC | 108.03 % | 108.98 % | 2083.0 | STE | 2270.09 | 22.92 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 109.42 % | 124.38 % | 223.0 | B | 277.37 | 35.14 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 149.11 % | 176.09 % | 214.0 | B | 376.83 | 57.74 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 149.11 % | 176.09 % | 214.0 | B | 376.83 | 57.74 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 145.99 % | 169.77 % | 449.0 | B | 762.26 | 106.78 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 145.99 % | 169.77 % | 449.0 | B | 762.25 | 106.78 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 138.48 % | 141.33 % | 2033.0 | ALDR | 2873.23 | 54.28 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 152.54 % | 156.25 % | 1479.0 | B | 2311.01 | 54.28 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 127.28 % | 129.93 % | 2033.0 | ALDR | 2641.46 | 54.34 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 137.78 % | 141.77 % | 1479.0 | B | 2096.76 | 54.34 | |
| CE |
TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line
272607 to 272269 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 101.3 % | 119.63 % | 315.0 | ALDR | 376.83 | 57.74 | |
| CE |
TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line
272607 to 272269 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 101.3 % | 119.63 % | 315.0 | ALDR | 376.83 | 57.74 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A' TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 END |
Tower | AC | 112.22 % | 123.37 % | 265.0 | ALDR | 326.92 | 32.25 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B' TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 TRIP BRANCH FROM BUS 965670 TO BUS 271835 CKT 1 /*AG1-435 TAP 138.0 - KEWANEE ;23 138.0 END |
Tower | AC | 101.13 % | 117.18 % | 265.0 | ALDR | 310.53 | 46.63 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A' TRIP BRANCH FROM BUS 271241 TO BUS 946540 CKT 1 /*CRESCENT ; R 138.0 - AF1-318 TAP 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 END |
Tower | AC | 92.72 % | 116.93 % | 449.0 | B | 525.03 | 106.78 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C' TRIP BRANCH FROM BUS 271241 TO BUS 946540 CKT 1 /*CRESCENT ; R 138.0 - AF1-318 TAP 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 END |
Tower | AC | 92.73 % | 116.93 % | 449.0 | B | 525.02 | 106.78 | |
| AMIL/CE |
KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line
271835 to 348962 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 94.95 % | 116.14 % | 223.0 | B | 258.98 | 47.25 | |
| AMIL/CE |
KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line
271835 to 348962 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 94.95 % | 116.14 % | 223.0 | B | 258.98 | 47.25 | |
| AMIL/CE |
AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line
934053 to 349637 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 95.15 % | 114.68 % | 189.0 | B | 216.75 | 36.91 | |
| AMIL/CE |
AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line
934053 to 349637 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 95.15 % | 114.68 % | 189.0 | B | 216.74 | 36.91 | |
| CE |
KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line
271837 to 934053 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 90.2 % | 109.73 % | 189.0 | C | 207.39 | 36.91 | |
| CE |
KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line
271837 to 934053 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 90.2 % | 109.73 % | 189.0 | C | 207.39 | 36.91 | |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 961651 | AG1-005 C O1 | 80/20 | 113.84 MW | 113.84 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965671 | AG1-435 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927201 | AC1-214 C O1 | 80/20 | 1.11 MW | 1.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 934051 | AD1-031 C O1 | 80/20 | 2.6 MW | 2.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274848 | CAMPGROVE;RU | 80/20 | 0.37 MW | 0.37 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274849 | CRESCENT ;1U | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274851 | PROVIDENC;RU | 80/20 | 0.6 MW | 0.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274877 | BISHOP HL;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274878 | BISHOP HL;2U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925581 | AC1-033 C | 80/20 | 1.29 MW | 1.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946541 | AF1-318 C O1 | 80/20 | 36.33 MW | 36.33 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957751 | AF2-069 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957761 | AF2-070 C | 80/20 | 1.07 MW | 1.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 958341 | AF2-128 C O1 | 80/20 | 10.62 MW | 10.62 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.58 MW | 4.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.0 MW | 1.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 961651 | AG1-005 C O1 | 80/20 | 112.47 MW | 112.47 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962721 | AG1-121 C O1 | 80/20 | 4.85 MW | 4.85 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 965671 | AG1-435 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 927201 | AC1-214 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 934051 | AD1-031 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274848 | CAMPGROVE;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274849 | CRESCENT ;1U | 80/20 | 0.58 MW | 0.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274851 | PROVIDENC;RU | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274877 | BISHOP HL;1U | 80/20 | 0.32 MW | 0.32 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274878 | BISHOP HL;2U | 80/20 | 0.32 MW | 0.32 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 925581 | AC1-033 C | 80/20 | 1.23 MW | 1.23 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 946541 | AF1-318 C O1 | 80/20 | 35.87 MW | 35.87 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 957751 | AF2-069 C | 80/20 | 0.74 MW | 0.74 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 957761 | AF2-070 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 958341 | AF2-128 C O1 | 80/20 | 10.49 MW | 10.49 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.3 MW | 4.3 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.01 MW | 1.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961651 | AG1-005 C O1 | Adder | 12.31 MW | 10.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961652 | AG1-005 E O1 | Adder | 8.21 MW | 6.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C O1 | Adder | 4.22 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E O1 | Adder | 19.72 MW | 16.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964581 | AG1-321 C O1 | Adder | 11.78 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964582 | AG1-321 E O1 | Adder | 6.86 MW | 5.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 18.91 MW | 16.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 3.81 MW | 3.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965091 | AG1-374 C | 50/50 | 21.96 MW | 21.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 14.64 MW | 14.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C | 50/50 | 7.26 MW | 7.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E | 50/50 | 33.99 MW | 33.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 | 50/50 | 13.75 MW | 13.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C O1 | Adder | 2.87 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E O1 | Adder | 13.45 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965931 | AG1-462 C O1 | Adder | 12.24 MW | 10.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965932 | AG1-462 E O1 | Adder | 8.16 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 C | Adder | 11.31 MW | 9.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.79 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.29 MW | 4.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 4.96 MW | 4.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 5.71 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C | 50/50 | 22.42 MW | 22.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E | 50/50 | 14.95 MW | 14.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C | 50/50 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E | 50/50 | 7.42 MW | 7.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.04 MW | 31.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.7 MW | 20.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 20.29 MW | 17.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958911 | AF2-182 C | Adder | 12.64 MW | 10.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958912 | AF2-182 E | Adder | 8.43 MW | 7.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.25 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.37 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959341 | AF2-225 C | 50/50 | 7.12 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959342 | AF2-225 E | 50/50 | 9.83 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.38 MW | 1.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 2.47 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.52 MW | 2.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 11.79 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.86 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 1.17 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.11 MW | 5.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.11 MW | 2.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.54 MW | 5.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.58 MW | 3.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.29 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 4.86 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293777 | CAYUG;1U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293778 | CAYUG;2U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 39.32 MW | 39.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 19.65 MW | 19.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 24.56 MW | 24.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.91 MW | 3.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 23.69 MW | 23.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.21 MW | 6.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930761 | AB1-122 CT1 | Adder | 39.4 MW | 33.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 7.94 MW | 6.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.04 MW | 13.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | 50/50 | 9.49 MW | 9.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 6.77 MW | 6.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 31.68 MW | 31.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946151 | AF1-280 C O1 | Adder | 9.62 MW | 8.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946152 | AF1-280 E O1 | Adder | 4.42 MW | 3.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 13.76 MW | 11.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 4.33 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957381 | AF2-032 C | 50/50 | 2.33 MW | 2.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.58 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.24 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 1.15 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 5.38 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 10.49 MW | 8.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 3.19 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 279.8 MW | 279.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.99 MW | 13.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.84 MW | 31.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 18.15 MW | 18.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 40.39 MW | 40.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.21 MW | 32.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 9.11 MW | 9.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 5.26 MW | 5.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 28.46 MW | 28.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.27 MW | 14.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 C | External Queue | 33.84 MW | 33.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954821 | J955 | External Queue | 112.27 MW | 112.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 16.19 MW | 16.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956451 | J1139 | External Queue | 20.56 MW | 20.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.99 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990071 | J1204 | External Queue | 65.14 MW | 65.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 107.73 MW | 107.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990672 | J1360 E | External Queue | 35.45 MW | 35.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991196 | J1626 | External Queue | 27.49 MW | 27.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991266 | J1714 | External Queue | 18.33 MW | 18.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 C | External Queue | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991262 | J1713 E | External Queue | 16.55 MW | 16.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.68 MW | 2.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.49 MW | 16.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.32 MW | 68.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 74.8 MW | 74.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.26 MW | 13.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.26 MW | 15.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.99 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.32 MW | 8.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 962721 | AG1-121 C O1 | 50/50 | 43.4 MW | 43.4 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 962722 | AG1-121 E O1 | 50/50 | 203.04 MW | 203.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 965671 | AG1-435 C O1 | 50/50 | 29.43 MW | 29.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 965672 | AG1-435 E O1 | 50/50 | 137.81 MW | 137.81 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 926821 | AC1-168 C O1 | 50/50 | 7.54 MW | 7.54 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 926822 | AC1-168 E O1 | 50/50 | 50.62 MW | 50.62 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 276173 | Z2-081 | 50/50 | 0.85 MW | 0.85 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 293061 | N-015 E | Adder | 9.67 MW | 8.22 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 294392 | P-010 E | Adder | 12.28 MW | 10.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | 925581 | AC1-033 C | Adder | -0.85 MW | -0.72 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.05 MW | 0.05 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.11 MW | 0.11 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.52 MW | 0.52 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.87 MW | 0.87 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L6101__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| Details for HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 962721 | AG1-121 C O1 | 50/50 | 43.4 MW | 43.4 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 962722 | AG1-121 E O1 | 50/50 | 203.04 MW | 203.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 965671 | AG1-435 C O1 | 50/50 | 29.43 MW | 29.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 965672 | AG1-435 E O1 | 50/50 | 137.81 MW | 137.81 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 926821 | AC1-168 C O1 | 50/50 | 7.54 MW | 7.54 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 926822 | AC1-168 E O1 | 50/50 | 50.62 MW | 50.62 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 276173 | Z2-081 | 50/50 | 0.85 MW | 0.85 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 293061 | N-015 E | Adder | 9.67 MW | 8.22 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 294392 | P-010 E | Adder | 12.28 MW | 10.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | 925581 | AC1-033 C | Adder | -0.85 MW | -0.72 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.05 MW | 0.05 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.11 MW | 0.11 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.52 MW | 0.52 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.87 MW | 0.87 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L94301_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961651 | AG1-005 C O1 | Adder | 12.53 MW | 10.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961652 | AG1-005 E O1 | Adder | 8.35 MW | 7.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962721 | AG1-121 C O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962722 | AG1-121 E O1 | Adder | 20.08 MW | 17.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963831 | AG1-236 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963832 | AG1-236 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964581 | AG1-321 C O1 | Adder | 11.86 MW | 10.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964582 | AG1-321 E O1 | Adder | 6.91 MW | 5.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966821 | AG1-553 C O1 | Adder | 19.16 MW | 16.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965091 | AG1-374 C | 50/50 | 21.61 MW | 21.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965092 | AG1-374 E | 50/50 | 14.4 MW | 14.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965331 | AG1-398 | 50/50 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965341 | AG1-399 C | 50/50 | 7.08 MW | 7.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965342 | AG1-399 E | 50/50 | 33.15 MW | 33.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965351 | AG1-400 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965371 | AG1-402 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965391 | AG1-404 | 50/50 | 13.41 MW | 13.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965671 | AG1-435 C O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965672 | AG1-435 E O1 | Adder | 13.68 MW | 11.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965911 | AG1-460 C | 50/50 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965912 | AG1-460 E | 50/50 | 3.0 MW | 3.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965931 | AG1-462 C O1 | Adder | 12.4 MW | 10.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965932 | AG1-462 E O1 | Adder | 8.27 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290261 | S-027 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290265 | S-028 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 295111 | SUBLETTE E | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 919581 | AA2-030 C | Adder | 11.63 MW | 9.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925771 | AC1-053 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925772 | AC1-053 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926821 | AC1-168 C O1 | Adder | 0.81 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926822 | AC1-168 E O1 | Adder | 5.42 MW | 4.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 927202 | AC1-214 E O1 | Adder | 5.04 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934051 | AD1-031 C O1 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934052 | AD1-031 E O1 | Adder | 3.62 MW | 3.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 935141 | AD1-148 | 50/50 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936511 | AD2-066 C O1 | Adder | 4.85 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936512 | AD2-066 E O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936771 | AD2-100 C | 50/50 | 21.54 MW | 21.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936772 | AD2-100 E | 50/50 | 14.36 MW | 14.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936971 | AD2-131 C | 50/50 | 1.42 MW | 1.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936972 | AD2-131 E | 50/50 | 7.13 MW | 7.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937311 | AD2-172 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937312 | AD2-172 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942111 | AE2-223 C | 50/50 | 2.18 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942112 | AE2-223 E | 50/50 | 14.59 MW | 14.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942481 | AE2-261 C | 50/50 | 29.87 MW | 29.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942482 | AE2-261 E | 50/50 | 19.91 MW | 19.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945871 | AF1-252 O1 | 50/50 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945881 | AF1-253 | 50/50 | 7.95 MW | 7.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946542 | AF1-318 E O1 | Adder | 20.64 MW | 17.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958911 | AF2-182 C | Adder | 13.04 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958912 | AF2-182 E | Adder | 8.69 MW | 7.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958921 | AF2-183 C | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958922 | AF2-183 E | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959101 | AF2-201 C O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959102 | AF2-201 E O1 | Adder | 10.24 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959341 | AF2-225 C | 50/50 | 7.04 MW | 7.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959342 | AF2-225 E | 50/50 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959611 | AF2-252 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959612 | AF2-252 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960141 | AF2-305 | 50/50 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960261 | AF2-317 | 50/50 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960611 | AF2-352 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960612 | AF2-352 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961011 | AF2-392 C O1 | Adder | 2.59 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961012 | AF2-392 E O1 | Adder | 12.14 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961021 | AF2-393 O1 | Adder | 4.42 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961031 | AF2-394 O1 | Adder | 2.95 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274650 | KINCAID ;1U | 50/50 | 15.61 MW | 15.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274651 | KINCAID ;2U | 50/50 | 15.6 MW | 15.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274853 | TWINGROVE;U1 | 50/50 | 0.71 MW | 0.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274854 | TWINGROVE;U2 | 50/50 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274859 | EASYR;U1 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274860 | EASYR;U2 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274880 | RADFORD R;1U | 50/50 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276615 | W2-048 GEN | 50/50 | 7.85 MW | 7.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276621 | X2-022 GEN | 50/50 | 28.17 MW | 28.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293516 | O-009 E1 | Adder | 6.27 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293517 | O-009 E2 | Adder | 3.18 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293518 | O-009 E3 | Adder | 3.51 MW | 2.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293715 | O-029 E | Adder | 6.7 MW | 5.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293716 | O-029 E | Adder | 3.67 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293717 | O-029 E | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293771 | O-035 E | Adder | 4.94 MW | 4.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293777 | CAYUG;1U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293778 | CAYUG;2U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293798 | W4-005 E | 50/50 | 38.12 MW | 38.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294401 | BSHIL;1U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294410 | BSHIL;2U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294763 | P-046 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 916211 | Z1-072 E | Adder | 3.74 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 917502 | Z2-087 E | 50/50 | 19.45 MW | 19.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924042 | AB2-047 E O1 | 50/50 | 24.32 MW | 24.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924261 | AB2-070 C O1 | 50/50 | 3.79 MW | 3.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924262 | AB2-070 E O1 | 50/50 | 22.98 MW | 22.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925582 | AC1-033 E | Adder | 7.32 MW | 6.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 930761 | AB1-122 CT1 | Adder | 41.0 MW | 34.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938861 | AE1-114 C O1 | Adder | 2.41 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938862 | AE1-114 E O1 | Adder | 8.22 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939401 | AE1-172 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939402 | AE1-172 E O1 | Adder | 16.51 MW | 14.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939741 | AE1-205 C O1 | 50/50 | 9.39 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939742 | AE1-205 E O1 | 50/50 | 12.97 MW | 12.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940501 | AE2-035 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940502 | AE2-035 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941731 | AE2-173 O1 | 50/50 | 5.59 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944221 | AF1-090 C O1 | 50/50 | 6.48 MW | 6.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944222 | AF1-090 E O1 | 50/50 | 30.33 MW | 30.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946151 | AF1-280 C O1 | Adder | 9.92 MW | 8.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946152 | AF1-280 E O1 | Adder | 4.56 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946162 | AF1-281 E O1 | Adder | 1.23 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946322 | AF1-296 E O1 | Adder | 13.97 MW | 11.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946501 | AF1-314 C | Adder | 2.58 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946502 | AF1-314 E | Adder | 12.12 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946541 | AF1-318 C O1 | Adder | 4.41 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957381 | AF2-032 C | 50/50 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957382 | AF2-032 E | 50/50 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957762 | AF2-070 E | Adder | 1.26 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958341 | AF2-128 C O1 | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958342 | AF2-128 E O1 | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990901 | L-005 E | Adder | 10.63 MW | 9.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934101 | AD2-000 1 | Adder | 3.32 MW | 2.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944202 | AF1-088 FTWR | 50/50 | 309.06 MW | 309.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942602 | AE2-276 BAT | 50/50 | 15.45 MW | 15.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941343 | AE2-130 BAT | 50/50 | 34.8 MW | 34.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953401 | J811 | External Queue | 17.16 MW | 17.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953641 | J813 | External Queue | 37.62 MW | 37.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953651 | J815 | External Queue | 30.66 MW | 30.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953881 | J848 C | External Queue | 4.99 MW | 4.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953882 | J848 E | External Queue | 27.02 MW | 27.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954411 | J912 | External Queue | 13.54 MW | 13.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954681 | J949 C | External Queue | 31.51 MW | 31.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954821 | J955 | External Queue | 84.37 MW | 84.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 956451 | J1139 | External Queue | 19.36 MW | 19.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990056 | J1201 | External Queue | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990071 | J1204 | External Queue | 61.78 MW | 61.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990271 | J1263 | External Queue | 101.39 MW | 101.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990672 | J1360 E | External Queue | 33.75 MW | 33.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991196 | J1626 | External Queue | 26.01 MW | 26.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991266 | J1714 | External Queue | 17.34 MW | 17.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991261 | J1713 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991262 | J1713 E | External Queue | 15.68 MW | 15.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.8 MW | 3.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.57 MW | 13.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.43 MW | 71.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.74 MW | 67.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.36 MW | 12.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.6 MW | 1.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.01 MW | 15.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.1 MW | 5.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.1 MW | 2.1 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961651 | AG1-005 C O1 | Adder | 11.21 MW | 9.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961652 | AG1-005 E O1 | Adder | 7.48 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962691 | AG1-118 C O1 | Adder | 13.13 MW | 11.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962692 | AG1-118 E O1 | Adder | 8.75 MW | 7.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962701 | AG1-119 C | Adder | 14.19 MW | 12.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962702 | AG1-119 E | Adder | 9.46 MW | 8.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962711 | AG1-120 C O1 | Adder | 5.33 MW | 4.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962712 | AG1-120 E O1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962721 | AG1-121 C O1 | Adder | 4.06 MW | 3.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962722 | AG1-121 E O1 | Adder | 18.97 MW | 16.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966821 | AG1-553 C O1 | Adder | 18.17 MW | 15.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965141 | AG1-379 C | Adder | 20.91 MW | 17.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965142 | AG1-379 E | Adder | 9.57 MW | 8.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965551 | AG1-423 C O1 | Adder | 9.46 MW | 8.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965552 | AG1-423 E O1 | Adder | 6.31 MW | 5.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965662 | AG1-434 E O1 | Adder | 13.14 MW | 11.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965671 | AG1-435 C O1 | Adder | 2.81 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965672 | AG1-435 E O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965931 | AG1-462 C O1 | Adder | 11.76 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 965932 | AG1-462 E O1 | Adder | 7.84 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290021 | O50 E | Adder | 24.38 MW | 20.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 295109 | WESTBROOK E | Adder | 3.48 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 919581 | AA2-030 C | Adder | 12.27 MW | 10.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 920272 | AA2-123 E | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 926331 | AC1-110 1 | Adder | 1.17 MW | 0.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 926341 | AC1-110 2 | Adder | 1.17 MW | 0.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927091 | AC1-204 GEN1 | 50/50 | 19.31 MW | 19.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927093 | AC1-204 GEN2 | 50/50 | 19.42 MW | 19.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927202 | AC1-214 E O1 | Adder | 4.8 MW | 4.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927451 | AC1-142A 1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 927461 | AC1-142A 2 | Adder | 3.7 MW | 3.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934051 | AD1-031 C O1 | Adder | 2.2 MW | 1.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934052 | AD1-031 E O1 | Adder | 3.58 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936511 | AD2-066 C O1 | Adder | 6.33 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 936512 | AD2-066 E O1 | Adder | 4.22 MW | 3.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937002 | AD2-134 E | Adder | 6.29 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937312 | AD2-172 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937401 | AD2-194 1 | Adder | 12.19 MW | 10.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 937411 | AD2-194 2 | 50/50 | 12.26 MW | 12.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942421 | AE2-255 C O1 | Adder | 3.81 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942422 | AE2-255 E O1 | Adder | 11.43 MW | 9.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942991 | AE2-321 C | Adder | 5.3 MW | 4.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 942992 | AE2-321 E | Adder | 2.61 MW | 2.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 943801 | AF1-048 C | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 943802 | AF1-048 E | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946542 | AF1-318 E O1 | Adder | 18.68 MW | 15.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958911 | AF2-182 C | Adder | 14.08 MW | 11.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958912 | AF2-182 E | Adder | 9.39 MW | 7.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958922 | AF2-183 E | Adder | 3.75 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959081 | AF2-199 C | Adder | 4.81 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959101 | AF2-201 C O1 | Adder | 4.01 MW | 3.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959102 | AF2-201 E O1 | Adder | 11.51 MW | 9.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959351 | AF2-226 C | 50/50 | 5.92 MW | 5.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 959352 | AF2-226 E | 50/50 | 8.88 MW | 8.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960281 | AF2-319 C | 50/50 | 5.92 MW | 5.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960282 | AF2-319 E | 50/50 | 8.88 MW | 8.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960581 | AF2-349 C | Adder | 14.2 MW | 12.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960582 | AF2-349 E | Adder | 9.47 MW | 8.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960721 | AF2-363 C O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960751 | AF2-366 C | Adder | 4.15 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961011 | AF2-392 C O1 | Adder | 2.74 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274728 | ELWOOD EC;5P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274730 | ELWOOD EC;6P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274731 | ELWOOD EC;2P | 50/50 | 5.19 MW | 5.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274732 | ELWOOD EC;7P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274734 | ELWOOD EC;8P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274736 | ELWOOD EC;9P | 50/50 | 5.22 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274859 | EASYR;U1 E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274860 | EASYR;U2 E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 274862 | TOP CROP ;2U | 50/50 | 1.77 MW | 1.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 276170 | Z1-108 E | Adder | 1.6 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 276591 | L-013 2 | Adder | 2.24 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293516 | O-009 E1 | Adder | 6.49 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293517 | O-009 E2 | Adder | 3.3 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293644 | O22 E1 | 50/50 | 24.17 MW | 24.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293645 | O22 E2 | 50/50 | 46.91 MW | 46.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293715 | O-029 E | Adder | 6.94 MW | 5.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293717 | O-029 E | Adder | 3.5 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 293771 | O-035 E | Adder | 4.71 MW | 4.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294401 | BSHIL;1U E | Adder | 6.59 MW | 5.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294410 | BSHIL;2U E | Adder | 6.59 MW | 5.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 294763 | P-046 E | Adder | 6.24 MW | 5.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915011 | Y3-013 1 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915021 | Y3-013 2 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 915031 | Y3-013 3 | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 916211 | Z1-072 E | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 925582 | AC1-033 E | Adder | 7.22 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930482 | AB1-089 CT | Adder | 24.07 MW | 20.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930483 | AB1-089 ST | Adder | 19.13 MW | 16.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930761 | AB1-122 CT1 | Adder | 69.01 MW | 58.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 930771 | AB1-122 CT2 | Adder | 92.77 MW | 78.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938511 | AE1-070 1 | 50/50 | 14.41 MW | 14.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938521 | AE1-070 2 | Adder | 13.11 MW | 11.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938851 | AE1-113 C O1 | Adder | 10.06 MW | 8.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938852 | AE1-113 E O1 | Adder | 35.66 MW | 30.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 938862 | AE1-114 E O1 | Adder | 9.04 MW | 7.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 36.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 940502 | AE2-035 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946151 | AF1-280 C O1 | Adder | 10.72 MW | 9.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946161 | AF1-281 C O1 | Adder | 0.23 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946322 | AF1-296 E O1 | Adder | 13.4 MW | 11.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946501 | AF1-314 C | Adder | 2.9 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946502 | AF1-314 E | Adder | 13.64 MW | 11.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946541 | AF1-318 C O1 | Adder | 3.99 MW | 3.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946662 | AF1-330 E | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957331 | AF2-027 C | Adder | 1.64 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957332 | AF2-027 E | Adder | 2.46 MW | 2.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957401 | AF2-034 C | Adder | 1.86 MW | 1.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957402 | AF2-034 E | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957471 | AF2-041 C | Adder | 14.44 MW | 12.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957472 | AF2-041 E | Adder | 7.22 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 957762 | AF2-070 E | Adder | 1.2 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958341 | AF2-128 C O1 | Adder | 1.05 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958342 | AF2-128 E O1 | Adder | 4.9 MW | 4.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 990901 | L-005 E | Adder | 10.47 MW | 8.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934101 | AD2-000 1 | Adder | 5.58 MW | 4.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 934111 | AD2-000 2 | Adder | 7.5 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 290108 | LEEDK;1U E | Adder | 14.61 MW | 12.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 958023 | AF2-096 BAT | Adder | 8.68 MW | 7.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 964362 | AG1-298 BAT | Adder | 57.7 MW | 49.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 954981 | J974 C | External Queue | 3.04 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | 954982 | J974 E | External Queue | 16.43 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.01 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.26 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.5 MW | 41.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.4 MW | 15.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.15 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.7 MW | 9.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.49 MW | 2.49 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 961651 | AG1-005 C O1 | 50/50 | 32.19 MW | 32.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 961652 | AG1-005 E O1 | 50/50 | 21.46 MW | 21.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 962721 | AG1-121 C O1 | 50/50 | 5.3 MW | 5.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 962722 | AG1-121 E O1 | 50/50 | 24.82 MW | 24.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 965671 | AG1-435 C O1 | Adder | 3.05 MW | 2.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 965672 | AG1-435 E O1 | Adder | 14.28 MW | 12.14 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 926821 | AC1-168 C O1 | 50/50 | 1.31 MW | 1.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 926822 | AC1-168 E O1 | 50/50 | 8.78 MW | 8.78 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 927202 | AC1-214 E O1 | 50/50 | 12.96 MW | 12.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 936511 | AD2-066 C O1 | 50/50 | 44.55 MW | 44.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 936512 | AD2-066 E O1 | 50/50 | 29.7 MW | 29.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 946542 | AF1-318 E O1 | 50/50 | 53.04 MW | 53.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 293771 | O-035 E | 50/50 | 12.7 MW | 12.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 294401 | BSHIL;1U E | Adder | 4.89 MW | 4.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 294410 | BSHIL;2U E | Adder | 4.89 MW | 4.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 916211 | Z1-072 E | 50/50 | 9.61 MW | 9.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 946541 | AF1-318 C O1 | 50/50 | 11.33 MW | 11.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957761 | AF2-070 C | 50/50 | 0.67 MW | 0.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 958342 | AF2-128 E O1 | 50/50 | 14.06 MW | 14.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 990901 | L-005 E | Adder | 6.61 MW | 5.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 953201 | J715 C | External Queue | 3.32 MW | 3.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 953202 | J715 E | External Queue | 17.95 MW | 17.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 990051 | J1200 | External Queue | 3.5 MW | 3.5 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 991302 | J1755 E | External Queue | 13.93 MW | 13.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.69 MW | 1.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.69 MW | 2.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 961651 | AG1-005 C O1 | 50/50 | 32.15 MW | 32.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 961652 | AG1-005 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 962721 | AG1-121 C O1 | 50/50 | 5.27 MW | 5.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 962722 | AG1-121 E O1 | 50/50 | 24.64 MW | 24.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 965671 | AG1-435 C O1 | Adder | 3.02 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 965672 | AG1-435 E O1 | Adder | 14.13 MW | 12.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 926821 | AC1-168 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 926822 | AC1-168 E O1 | 50/50 | 8.76 MW | 8.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 927202 | AC1-214 E O1 | 50/50 | 12.95 MW | 12.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 936511 | AD2-066 C O1 | 50/50 | 44.54 MW | 44.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 936512 | AD2-066 E O1 | 50/50 | 29.69 MW | 29.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 946542 | AF1-318 E O1 | 50/50 | 52.97 MW | 52.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 293771 | O-035 E | 50/50 | 12.69 MW | 12.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 294401 | BSHIL;1U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 294410 | BSHIL;2U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 916211 | Z1-072 E | 50/50 | 9.6 MW | 9.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 946541 | AF1-318 C O1 | 50/50 | 11.31 MW | 11.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957761 | AF2-070 C | 50/50 | 0.66 MW | 0.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 958342 | AF2-128 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 990901 | L-005 E | Adder | 6.49 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 953201 | J715 C | External Queue | 3.31 MW | 3.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 953202 | J715 E | External Queue | 17.92 MW | 17.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 990051 | J1200 | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 991302 | J1755 E | External Queue | 13.9 MW | 13.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.71 MW | 1.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.46 MW | 0.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962701 | AG1-119 C | Adder | 14.23 MW | 12.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962702 | AG1-119 E | Adder | 9.48 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962722 | AG1-121 E O1 | Adder | 18.88 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966821 | AG1-553 C O1 | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965672 | AG1-435 E O1 | Adder | 13.08 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290021 | O50 E | Adder | 24.43 MW | 20.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 943801 | AF1-048 C | Adder | 2.48 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946542 | AF1-318 E O1 | Adder | 18.59 MW | 15.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958912 | AF2-182 E | Adder | 9.39 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960581 | AF2-349 C | Adder | 14.25 MW | 12.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274729 | ELWOOD EC;1P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293644 | O22 E1 | 50/50 | 24.24 MW | 24.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930482 | AB1-089 CT | Adder | 24.12 MW | 20.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930761 | AB1-122 CT1 | Adder | 68.76 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 930771 | AB1-122 CT2 | Adder | 93.21 MW | 79.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938511 | AE1-070 1 | 50/50 | 14.44 MW | 14.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 938862 | AE1-114 E O1 | Adder | 9.05 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 35.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946322 | AF1-296 E O1 | Adder | 13.39 MW | 11.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946502 | AF1-314 E | Adder | 13.66 MW | 11.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957471 | AF2-041 C | Adder | 14.45 MW | 12.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958342 | AF2-128 E O1 | Adder | 4.87 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 964362 | AG1-298 BAT | Adder | 42.67 MW | 36.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.03 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.34 MW | 42.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.14 MW | 15.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962701 | AG1-119 C | Adder | 14.23 MW | 12.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962702 | AG1-119 E | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962722 | AG1-121 E O1 | Adder | 18.89 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966821 | AG1-553 C O1 | Adder | 18.16 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965672 | AG1-435 E O1 | Adder | 13.09 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290021 | O50 E | Adder | 24.43 MW | 20.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 943801 | AF1-048 C | Adder | 2.49 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946542 | AF1-318 E O1 | Adder | 18.6 MW | 15.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958492 | AF2-143 E | Adder | 8.44 MW | 7.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958912 | AF2-182 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958921 | AF2-183 C | Adder | 2.51 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959091 | AF2-200 C O1 | Adder | 9.64 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960581 | AF2-349 C | Adder | 14.25 MW | 12.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 960752 | AF2-366 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961012 | AF2-392 E O1 | Adder | 12.86 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274735 | ELWOOD EC;4P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293644 | O22 E1 | 50/50 | 24.25 MW | 24.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930482 | AB1-089 CT | Adder | 24.13 MW | 20.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930761 | AB1-122 CT1 | Adder | 68.77 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 930771 | AB1-122 CT2 | Adder | 93.22 MW | 79.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938511 | AE1-070 1 | 50/50 | 14.45 MW | 14.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 938862 | AE1-114 E O1 | Adder | 9.06 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 36.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 941131 | AE2-107 C | Adder | 3.95 MW | 3.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946322 | AF1-296 E O1 | Adder | 13.4 MW | 11.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946502 | AF1-314 E | Adder | 13.67 MW | 11.62 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957471 | AF2-041 C | Adder | 14.45 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958342 | AF2-128 E O1 | Adder | 4.88 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 964362 | AG1-298 BAT | Adder | 42.66 MW | 36.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.02 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.37 MW | 42.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.16 MW | 15.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.75 MW | 6.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 13.25 MW | 11.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.83 MW | 7.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.0 MW | 14.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.33 MW | 9.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962701 | AG1-119 C | Adder | 18.64 MW | 15.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.42 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 6.95 MW | 5.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.63 MW | 3.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.77 MW | 4.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 22.31 MW | 18.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.4 MW | 4.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964581 | AG1-321 C O1 | Adder | 11.37 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964582 | AG1-321 E O1 | Adder | 6.62 MW | 5.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.74 MW | 19.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.58 MW | 3.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.02 MW | 0.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.38 MW | 19.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.24 MW | 8.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.43 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.58 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 16.76 MW | 14.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 15.47 MW | 13.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.72 MW | 12.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.81 MW | 8.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.58 MW | 0.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.1 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290021 | O50 E | Adder | 26.1 MW | 22.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.37 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.48 MW | 3.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.6 MW | 13.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.11 MW | 1.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.22 MW | 18.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.67 MW | 4.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.37 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.47 MW | 1.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.31 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.59 MW | 2.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.22 MW | 3.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.78 MW | 0.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.52 MW | 0.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.01 MW | 9.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.24 MW | 6.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.82 MW | 4.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.02 MW | 1.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.09 MW | 6.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937312 | AD2-172 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.36 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.5 MW | 11.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942111 | AE2-223 C | Adder | 1.51 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942112 | AE2-223 E | Adder | 10.12 MW | 8.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.24 MW | 10.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.62 MW | 0.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.83 MW | 3.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.07 MW | 6.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.48 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.03 MW | 6.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943122 | AE2-341 E | Adder | 3.94 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.64 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.2 MW | 1.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 22.06 MW | 18.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.02 MW | 6.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.05 MW | 15.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.03 MW | 10.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.21 MW | 2.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.81 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.15 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.29 MW | 10.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.2 MW | 6.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.23 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.02 MW | 12.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959341 | AF2-225 C | Adder | 4.88 MW | 4.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959342 | AF2-225 E | Adder | 6.74 MW | 5.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.37 MW | 2.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960581 | AF2-349 C | Adder | 18.9 MW | 16.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.6 MW | 10.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.77 MW | 4.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.18 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.38 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.32 MW | 13.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.94 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.96 MW | 3.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.12 MW | 1.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.14 MW | 2.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.16 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276591 | L-013 2 | Adder | 2.95 MW | 2.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.09 MW | 6.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.11 MW | 3.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.52 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.21 MW | 29.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 56.7 MW | 56.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293715 | O-029 E | Adder | 8.65 MW | 7.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293716 | O-029 E | Adder | 4.74 MW | 4.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293717 | O-029 E | Adder | 4.36 MW | 3.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293771 | O-035 E | Adder | 5.56 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294763 | P-046 E | Adder | 8.14 MW | 6.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.2 MW | 3.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.35 MW | 3.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 917502 | Z2-087 E | Adder | 13.49 MW | 11.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 16.86 MW | 14.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.27 MW | 1.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.52 MW | 7.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 31.55 MW | 26.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.08 MW | 21.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 73.53 MW | 62.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 101.92 MW | 86.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.52 MW | 13.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.21 MW | 10.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.77 MW | 9.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.17 MW | 32.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.42 MW | 2.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.67 MW | 9.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.36 MW | 3.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 26.81 MW | 22.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939741 | AE1-205 C O1 | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939742 | AE1-205 E O1 | Adder | 8.99 MW | 7.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940502 | AE2-035 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.09 MW | 4.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941731 | AE2-173 O1 | Adder | 3.88 MW | 3.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.74 MW | 11.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.32 MW | 5.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.7 MW | 1.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.6 MW | 3.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.83 MW | 14.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.79 MW | 3.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946502 | AF1-314 E | Adder | 17.79 MW | 15.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.71 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.73 MW | 1.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.38 MW | 0.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.91 MW | 1.62 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.3 MW | 1.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.21 MW | 2.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.88 MW | 1.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.44 MW | 15.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.22 MW | 7.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.67 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.29 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.41 MW | 1.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.24 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.78 MW | 4.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 990901 | L-005 E | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.24 MW | 7.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 18.85 MW | 16.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954981 | J974 C | External Queue | 3.02 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954982 | J974 E | External Queue | 10.86 MW | 10.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.3 MW | 0.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.02 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.43 MW | 57.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.2 MW | 21.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.27 MW | 1.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.22 MW | 4.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.32 MW | 12.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.69 MW | 0.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.14 MW | 8.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.36 MW | 0.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.89 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.43 MW | 3.43 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 12.71 MW | 10.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.47 MW | 7.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.56 MW | 14.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.71 MW | 9.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962701 | AG1-119 C | Adder | 19.08 MW | 16.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.14 MW | 6.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.76 MW | 4.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.61 MW | 3.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 21.58 MW | 18.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.57 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.71 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.49 MW | 19.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.42 MW | 19.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.26 MW | 8.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.64 MW | 3.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 17.03 MW | 14.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.19 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 14.96 MW | 12.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.56 MW | 12.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.7 MW | 8.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.4 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290021 | O50 E | Adder | 26.14 MW | 22.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.68 MW | 13.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.42 MW | 18.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.46 MW | 4.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.49 MW | 4.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.52 MW | 4.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.82 MW | 0.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.34 MW | 1.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.53 MW | 0.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.39 MW | 2.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.17 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.28 MW | 6.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.86 MW | 4.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937312 | AD2-172 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.49 MW | 9.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.63 MW | 11.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.89 MW | 3.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.24 MW | 6.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.57 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943122 | AE2-341 E | Adder | 4.16 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.64 MW | 4.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.79 MW | 2.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 21.19 MW | 18.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.13 MW | 6.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.42 MW | 4.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.2 MW | 15.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.13 MW | 10.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.24 MW | 2.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.85 MW | 4.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.27 MW | 5.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.54 MW | 10.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.36 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.31 MW | 4.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.24 MW | 12.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960581 | AF2-349 C | Adder | 19.33 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.89 MW | 10.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.9 MW | 4.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.27 MW | 2.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.7 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.5 MW | 2.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.4 MW | 13.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.97 MW | 5.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.98 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.13 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.15 MW | 2.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.22 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276591 | L-013 2 | Adder | 3.05 MW | 2.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.05 MW | 6.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.09 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.5 MW | 3.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.41 MW | 29.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 57.09 MW | 57.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293715 | O-029 E | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293716 | O-029 E | Adder | 4.72 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293717 | O-029 E | Adder | 4.33 MW | 3.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293771 | O-035 E | Adder | 5.36 MW | 4.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294763 | P-046 E | Adder | 8.26 MW | 7.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.05 MW | 3.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.45 MW | 3.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.23 MW | 1.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.23 MW | 7.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 32.18 MW | 27.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.58 MW | 21.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 71.38 MW | 60.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 103.64 MW | 88.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.67 MW | 13.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.35 MW | 10.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.78 MW | 9.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.24 MW | 32.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.46 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.81 MW | 10.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.43 MW | 3.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 27.2 MW | 23.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940502 | AE2-035 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.24 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.85 MW | 11.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.72 MW | 1.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.69 MW | 14.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.84 MW | 3.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946502 | AF1-314 E | Adder | 18.05 MW | 15.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.78 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.37 MW | 2.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.25 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.91 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.81 MW | 15.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 990901 | L-005 E | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.77 MW | 4.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.38 MW | 7.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.41 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 7.3 MW | 6.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953151 | J831 | External Queue | 3.03 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953491 | J947 | External Queue | 15.9 MW | 15.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954141 | J878 | External Queue | 15.94 MW | 15.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954981 | J974 C | External Queue | 2.94 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954982 | J974 E | External Queue | 15.91 MW | 15.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 991321 | J1778 | External Queue | 7.97 MW | 7.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.4 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.54 MW | 57.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.5 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.51 MW | 3.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 11.83 MW | 11.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.53 MW | 8.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.5 MW | 3.5 MW |
| Details for PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962722 | AG1-121 E O1 | Adder | 20.72 MW | 17.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.19 MW | 3.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.04 MW | 10.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946501 | AF1-314 C | Adder | 3.03 MW | 2.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946502 | AF1-314 E | Adder | 14.26 MW | 12.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 961651 | AG1-005 C O1 | 50/50 | 15.7 MW | 15.7 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 961652 | AG1-005 E O1 | 50/50 | 10.47 MW | 10.47 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 962721 | AG1-121 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 962722 | AG1-121 E O1 | 50/50 | 35.54 MW | 35.54 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 965671 | AG1-435 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 965672 | AG1-435 E O1 | 50/50 | 26.62 MW | 26.62 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.97 MW | 0.83 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 6.53 MW | 5.55 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 927201 | AC1-214 C O1 | 50/50 | 0.5 MW | 0.5 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 927202 | AC1-214 E O1 | 50/50 | 9.37 MW | 9.37 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 934051 | AD1-031 C O1 | 50/50 | 4.88 MW | 4.88 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 934052 | AD1-031 E O1 | 50/50 | 7.97 MW | 7.97 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 946542 | AF1-318 E O1 | 50/50 | 28.0 MW | 28.0 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 274848 | CAMPGROVE;RU | 50/50 | 0.71 MW | 0.71 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 274849 | CRESCENT ;1U | 50/50 | 0.26 MW | 0.26 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 274851 | PROVIDENC;RU | 50/50 | 0.27 MW | 0.27 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 274877 | BISHOP HL;1U | 50/50 | 0.63 MW | 0.63 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 274878 | BISHOP HL;2U | 50/50 | 0.63 MW | 0.63 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 293771 | O-035 E | 50/50 | 9.18 MW | 9.18 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 294401 | BSHIL;1U E | 50/50 | 14.84 MW | 14.84 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 294410 | BSHIL;2U E | 50/50 | 14.84 MW | 14.84 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 916211 | Z1-072 E | 50/50 | 6.95 MW | 6.95 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 925581 | AC1-033 C | 50/50 | 2.42 MW | 2.42 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 925582 | AC1-033 E | 50/50 | 16.23 MW | 16.23 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 946541 | AF1-318 C O1 | 50/50 | 5.98 MW | 5.98 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 957751 | AF2-069 C | 50/50 | 0.34 MW | 0.34 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 957752 | AF2-069 E | 50/50 | 1.1 MW | 1.1 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 957761 | AF2-070 C | 50/50 | 0.48 MW | 0.48 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 957762 | AF2-070 E | 50/50 | 2.33 MW | 2.33 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 958341 | AF2-128 C O1 | 50/50 | 1.46 MW | 1.46 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 958342 | AF2-128 E O1 | 50/50 | 6.86 MW | 6.86 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 990901 | L-005 E | 50/50 | 19.79 MW | 19.79 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 962013 | AG1-044 BAT | Adder | 0.06 MW | 0.05 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 961022 | AF2-393 BAT | Adder | 4.79 MW | 4.07 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 961032 | AF2-394 BAT | Adder | 3.19 MW | 2.71 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 953201 | J715 C | External Queue | 1.56 MW | 1.56 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 953202 | J715 E | External Queue | 8.43 MW | 8.43 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 990051 | J1200 | External Queue | 2.67 MW | 2.67 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 991301 | J1755 C | External Queue | 3.44 MW | 3.44 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | 991302 | J1755 E | External Queue | 18.61 MW | 18.61 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.13 MW | 0.13 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.81 MW | 0.81 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.62 MW | 0.62 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.17 MW | 0.17 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.26 MW | 0.26 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P4_187-38-BT5-6__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.69 MW | 0.69 MW |
| Details for HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 962721 | AG1-121 C O1 | 50/50 | 43.4 MW | 43.4 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 962722 | AG1-121 E O1 | 50/50 | 203.04 MW | 203.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 965671 | AG1-435 C O1 | 50/50 | 29.43 MW | 29.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 965672 | AG1-435 E O1 | 50/50 | 137.81 MW | 137.81 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 926821 | AC1-168 C O1 | 50/50 | 7.54 MW | 7.54 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 926822 | AC1-168 E O1 | 50/50 | 50.62 MW | 50.62 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 276173 | Z2-081 | 50/50 | 0.85 MW | 0.85 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 293061 | N-015 E | Adder | 9.67 MW | 8.22 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 294392 | P-010 E | Adder | 12.28 MW | 10.43 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 925581 | AC1-033 C | Adder | -0.85 MW | -0.72 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.49 MW | 0.49 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.05 MW | 0.05 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.11 MW | 0.11 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.52 MW | 0.52 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.87 MW | 0.87 MW |
| HENNEEPIN; T-4HENNEPIN S 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 936511 | AD2-066 C O1 | 50/50 | 44.34 MW | 44.34 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 936512 | AD2-066 E O1 | 50/50 | 29.56 MW | 29.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961651 | AG1-005 C O1 | Adder | 12.46 MW | 10.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961652 | AG1-005 E O1 | Adder | 8.31 MW | 7.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962721 | AG1-121 C O1 | Adder | 4.27 MW | 3.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962722 | AG1-121 E O1 | Adder | 19.98 MW | 16.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963831 | AG1-236 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963832 | AG1-236 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964581 | AG1-321 C O1 | Adder | 11.85 MW | 10.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964582 | AG1-321 E O1 | Adder | 6.9 MW | 5.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966821 | AG1-553 C O1 | Adder | 19.15 MW | 16.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965061 | AG1-371 | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965081 | AG1-373 | Adder | 0.66 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965091 | AG1-374 C | 50/50 | 21.84 MW | 21.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965092 | AG1-374 E | 50/50 | 14.56 MW | 14.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965331 | AG1-398 | 50/50 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965341 | AG1-399 C | 50/50 | 7.19 MW | 7.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965342 | AG1-399 E | 50/50 | 33.66 MW | 33.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965351 | AG1-400 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965371 | AG1-402 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965391 | AG1-404 | 50/50 | 13.62 MW | 13.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965661 | AG1-434 C O1 | Adder | 2.4 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965662 | AG1-434 E O1 | Adder | 11.22 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965671 | AG1-435 C O1 | Adder | 2.91 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965672 | AG1-435 E O1 | Adder | 13.62 MW | 11.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965911 | AG1-460 C | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965912 | AG1-460 E | 50/50 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965931 | AG1-462 C O1 | Adder | 12.39 MW | 10.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965932 | AG1-462 E O1 | Adder | 8.26 MW | 7.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 272364 | ESS H440N ;R | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290051 | GSG-6; E | Adder | 5.74 MW | 4.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290261 | S-027 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290265 | S-028 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295109 | WESTBROOK E | Adder | 3.07 MW | 2.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295111 | SUBLETTE E | Adder | 1.64 MW | 1.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 919581 | AA2-030 C | Adder | 11.53 MW | 9.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925771 | AC1-053 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925772 | AC1-053 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 927202 | AC1-214 E O1 | Adder | 5.02 MW | 4.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933911 | AD1-013 C | Adder | 1.01 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933912 | AD1-013 E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934051 | AD1-031 C O1 | Adder | 2.21 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934052 | AD1-031 E O1 | Adder | 3.61 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 935141 | AD1-148 | 50/50 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936771 | AD2-100 C | 50/50 | 22.11 MW | 22.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936772 | AD2-100 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936971 | AD2-131 C | 50/50 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936972 | AD2-131 E | 50/50 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937001 | AD2-134 C | Adder | 1.39 MW | 1.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937002 | AD2-134 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937311 | AD2-172 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937312 | AD2-172 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942111 | AE2-223 C | 50/50 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942112 | AE2-223 E | 50/50 | 14.69 MW | 14.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942481 | AE2-261 C | 50/50 | 30.63 MW | 30.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942482 | AE2-261 E | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945871 | AF1-252 O1 | 50/50 | 11.82 MW | 11.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945881 | AF1-253 | 50/50 | 8.19 MW | 8.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946542 | AF1-318 E O1 | Adder | 20.54 MW | 17.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958911 | AF2-182 C | Adder | 12.9 MW | 10.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958912 | AF2-182 E | Adder | 8.6 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958922 | AF2-183 E | Adder | 3.44 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959081 | AF2-199 C | Adder | 3.98 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959082 | AF2-199 E | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959091 | AF2-200 C O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959092 | AF2-200 E O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959101 | AF2-201 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959102 | AF2-201 E O1 | Adder | 10.09 MW | 8.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959341 | AF2-225 C | 50/50 | 7.09 MW | 7.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959342 | AF2-225 E | 50/50 | 9.79 MW | 9.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959611 | AF2-252 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959612 | AF2-252 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960141 | AF2-305 | 50/50 | 1.37 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960261 | AF2-317 | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960611 | AF2-352 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960612 | AF2-352 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961012 | AF2-392 E O1 | Adder | 12.02 MW | 10.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274650 | KINCAID ;1U | 50/50 | 16.0 MW | 16.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274651 | KINCAID ;2U | 50/50 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274859 | EASYR;U1 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274860 | EASYR;U2 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274880 | RADFORD R;1U | 50/50 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276615 | W2-048 GEN | 50/50 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276621 | X2-022 GEN | 50/50 | 28.76 MW | 28.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293516 | O-009 E1 | Adder | 6.22 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293517 | O-009 E2 | Adder | 3.16 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293518 | O-009 E3 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293715 | O-029 E | Adder | 6.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293716 | O-029 E | Adder | 3.65 MW | 3.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293717 | O-029 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293771 | O-035 E | Adder | 4.92 MW | 4.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293777 | CAYUG;1U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293778 | CAYUG;2U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293798 | W4-005 E | 50/50 | 38.82 MW | 38.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294401 | BSHIL;1U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294410 | BSHIL;2U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294763 | P-046 E | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916211 | Z1-072 E | Adder | 3.73 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916221 | Z1-073 E | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 917502 | Z2-087 E | 50/50 | 19.59 MW | 19.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924042 | AB2-047 E O1 | 50/50 | 24.48 MW | 24.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924261 | AB2-070 C O1 | 50/50 | 3.86 MW | 3.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924262 | AB2-070 E O1 | 50/50 | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925582 | AC1-033 E | Adder | 7.3 MW | 6.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930482 | AB1-089 CT | Adder | 20.14 MW | 17.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930483 | AB1-089 ST | Adder | 16.01 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930761 | AB1-122 CT1 | Adder | 40.35 MW | 34.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938861 | AE1-114 C O1 | Adder | 2.38 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938862 | AE1-114 E O1 | Adder | 8.12 MW | 6.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939401 | AE1-172 C O1 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939402 | AE1-172 E O1 | Adder | 16.31 MW | 13.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939741 | AE1-205 C O1 | 50/50 | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939742 | AE1-205 E O1 | 50/50 | 13.06 MW | 13.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940501 | AE2-035 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940502 | AE2-035 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941731 | AE2-173 O1 | 50/50 | 5.63 MW | 5.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944221 | AF1-090 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944222 | AF1-090 E O1 | 50/50 | 31.22 MW | 31.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946151 | AF1-280 C O1 | Adder | 9.82 MW | 8.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946152 | AF1-280 E O1 | Adder | 4.52 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946322 | AF1-296 E O1 | Adder | 13.95 MW | 11.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946501 | AF1-314 C | Adder | 2.54 MW | 2.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946502 | AF1-314 E | Adder | 11.95 MW | 10.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946541 | AF1-318 C O1 | Adder | 4.39 MW | 3.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946671 | AF1-331 | Adder | 1.31 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957381 | AF2-032 C | 50/50 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957382 | AF2-032 E | 50/50 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957471 | AF2-041 C | Adder | 11.94 MW | 10.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957472 | AF2-041 E | Adder | 5.97 MW | 5.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957762 | AF2-070 E | Adder | 1.25 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958341 | AF2-128 C O1 | Adder | 1.16 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958342 | AF2-128 E O1 | Adder | 5.44 MW | 4.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990901 | L-005 E | Adder | 10.6 MW | 9.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934101 | AD2-000 1 | Adder | 3.26 MW | 2.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944202 | AF1-088 FTWR | 50/50 | 260.6 MW | 260.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942602 | AE2-276 BAT | 50/50 | 13.03 MW | 13.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941343 | AE2-130 BAT | 50/50 | 29.76 MW | 29.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953401 | J811 | External Queue | 18.24 MW | 18.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953641 | J813 | External Queue | 40.35 MW | 40.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953881 | J848 C | External Queue | 5.27 MW | 5.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953882 | J848 E | External Queue | 28.49 MW | 28.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954411 | J912 | External Queue | 14.3 MW | 14.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954681 | J949 C | External Queue | 32.68 MW | 32.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 956451 | J1139 | External Queue | 20.06 MW | 20.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990056 | J1201 | External Queue | 7.03 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990071 | J1204 | External Queue | 65.85 MW | 65.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990271 | J1263 | External Queue | 106.84 MW | 106.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991196 | J1626 | External Queue | 27.64 MW | 27.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991266 | J1714 | External Queue | 18.43 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991261 | J1713 C | External Queue | 3.03 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991262 | J1713 E | External Queue | 3.46 MW | 3.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.0 MW | 15.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 69.74 MW | 69.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.94 MW | 68.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.87 MW | 12.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.25 MW | 15.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.06 MW | 2.06 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 961651 | AG1-005 C O1 | 50/50 | 32.15 MW | 32.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 961652 | AG1-005 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 962721 | AG1-121 C O1 | 50/50 | 5.27 MW | 5.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 962722 | AG1-121 E O1 | 50/50 | 24.64 MW | 24.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 965671 | AG1-435 C O1 | Adder | 3.02 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 965672 | AG1-435 E O1 | Adder | 14.13 MW | 12.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 926821 | AC1-168 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 926822 | AC1-168 E O1 | 50/50 | 8.76 MW | 8.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 927202 | AC1-214 E O1 | 50/50 | 12.95 MW | 12.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 936511 | AD2-066 C O1 | 50/50 | 44.54 MW | 44.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 936512 | AD2-066 E O1 | 50/50 | 29.69 MW | 29.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 946542 | AF1-318 E O1 | 50/50 | 52.97 MW | 52.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 293771 | O-035 E | 50/50 | 12.69 MW | 12.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 294401 | BSHIL;1U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 294410 | BSHIL;2U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 916211 | Z1-072 E | 50/50 | 9.6 MW | 9.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 946541 | AF1-318 C O1 | 50/50 | 11.31 MW | 11.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957761 | AF2-070 C | 50/50 | 0.66 MW | 0.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 958342 | AF2-128 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 990901 | L-005 E | Adder | 6.49 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 953201 | J715 C | External Queue | 3.31 MW | 3.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 953202 | J715 E | External Queue | 17.92 MW | 17.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 990051 | J1200 | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 991302 | J1755 E | External Queue | 13.9 MW | 13.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.71 MW | 1.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.46 MW | 0.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961651 | AG1-005 C O1 | Adder | 11.16 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961652 | AG1-005 E O1 | Adder | 7.44 MW | 6.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962691 | AG1-118 C O1 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962692 | AG1-118 E O1 | Adder | 8.76 MW | 7.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962701 | AG1-119 C | Adder | 14.23 MW | 12.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962702 | AG1-119 E | Adder | 9.48 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962711 | AG1-120 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962712 | AG1-120 E O1 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962721 | AG1-121 C O1 | Adder | 4.04 MW | 3.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962722 | AG1-121 E O1 | Adder | 18.88 MW | 16.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962781 | AG1-127 C | Adder | 4.17 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 962782 | AG1-127 E | Adder | 2.77 MW | 2.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966821 | AG1-553 C O1 | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966822 | AG1-553 E O1 | Adder | 3.66 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965061 | AG1-371 | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965081 | AG1-373 | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965141 | AG1-379 C | Adder | 20.95 MW | 17.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965142 | AG1-379 E | Adder | 9.59 MW | 8.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965551 | AG1-423 C O1 | Adder | 9.49 MW | 8.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965552 | AG1-423 E O1 | Adder | 6.32 MW | 5.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965661 | AG1-434 C O1 | Adder | 2.81 MW | 2.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965662 | AG1-434 E O1 | Adder | 13.15 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965671 | AG1-435 C O1 | Adder | 2.8 MW | 2.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965672 | AG1-435 E O1 | Adder | 13.08 MW | 11.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965931 | AG1-462 C O1 | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 965932 | AG1-462 E O1 | Adder | 7.83 MW | 6.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966441 | AG1-513 C | Adder | 0.3 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 966442 | AG1-513 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 272364 | ESS H440N ;R | Adder | 1.63 MW | 1.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290021 | O50 E | Adder | 24.43 MW | 20.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290051 | GSG-6; E | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 295109 | WESTBROOK E | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 918052 | AA1-018 E OP | Adder | 18.15 MW | 15.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 919581 | AA2-030 C | Adder | 12.28 MW | 10.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 920272 | AA2-123 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 926331 | AC1-110 1 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 926341 | AC1-110 2 | Adder | 1.17 MW | 1.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927091 | AC1-204 GEN1 | 50/50 | 19.36 MW | 19.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927093 | AC1-204 GEN2 | 50/50 | 19.47 MW | 19.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927202 | AC1-214 E O1 | Adder | 4.78 MW | 4.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927451 | AC1-142A 1 | Adder | 3.72 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 927461 | AC1-142A 2 | Adder | 3.74 MW | 3.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933911 | AD1-013 C | Adder | 1.14 MW | 0.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933912 | AD1-013 E | Adder | 1.83 MW | 1.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933931 | AD1-016 C | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 933932 | AD1-016 E | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934432 | AD1-067 E | Adder | 0.34 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934971 | AD1-129 C | Adder | 0.59 MW | 0.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934972 | AD1-129 E | Adder | 0.39 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936291 | AD2-038 C O1 | Adder | 3.71 MW | 3.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936292 | AD2-038 E O1 | Adder | 17.39 MW | 14.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936511 | AD2-066 C O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 936512 | AD2-066 E O1 | Adder | 4.24 MW | 3.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937001 | AD2-134 C | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937002 | AD2-134 E | Adder | 6.3 MW | 5.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937311 | AD2-172 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937312 | AD2-172 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937401 | AD2-194 1 | Adder | 12.23 MW | 10.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 937411 | AD2-194 2 | 50/50 | 12.29 MW | 12.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942421 | AE2-255 C O1 | Adder | 3.82 MW | 3.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942422 | AE2-255 E O1 | Adder | 11.45 MW | 9.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942652 | AE2-281 E O1 | Adder | 6.05 MW | 5.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942991 | AE2-321 C | Adder | 5.32 MW | 4.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 942992 | AE2-321 E | Adder | 2.62 MW | 2.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 943801 | AF1-048 C | Adder | 2.48 MW | 2.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 943802 | AF1-048 E | Adder | 1.66 MW | 1.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946542 | AF1-318 E O1 | Adder | 18.59 MW | 15.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958481 | AF2-142 C | Adder | 12.52 MW | 10.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958482 | AF2-142 E | Adder | 8.35 MW | 7.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958491 | AF2-143 C | Adder | 12.66 MW | 10.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958492 | AF2-143 E | Adder | 8.44 MW | 7.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958911 | AF2-182 C | Adder | 14.09 MW | 11.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958912 | AF2-182 E | Adder | 9.39 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958921 | AF2-183 C | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958922 | AF2-183 E | Adder | 3.76 MW | 3.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959081 | AF2-199 C | Adder | 4.82 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959082 | AF2-199 E | Adder | 2.41 MW | 2.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959091 | AF2-200 C O1 | Adder | 9.63 MW | 8.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959092 | AF2-200 E O1 | Adder | 6.42 MW | 5.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959101 | AF2-201 C O1 | Adder | 4.02 MW | 3.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959102 | AF2-201 E O1 | Adder | 11.54 MW | 9.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959351 | AF2-226 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 959352 | AF2-226 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960281 | AF2-319 C | 50/50 | 5.94 MW | 5.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960282 | AF2-319 E | 50/50 | 8.91 MW | 8.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960581 | AF2-349 C | Adder | 14.25 MW | 12.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960582 | AF2-349 E | Adder | 9.5 MW | 8.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960721 | AF2-363 C O1 | Adder | 3.67 MW | 3.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960722 | AF2-363 E O1 | Adder | 2.44 MW | 2.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960751 | AF2-366 C | Adder | 4.16 MW | 3.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 960752 | AF2-366 E | Adder | 2.77 MW | 2.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961011 | AF2-392 C O1 | Adder | 2.75 MW | 2.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961012 | AF2-392 E O1 | Adder | 12.85 MW | 10.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961021 | AF2-393 O1 | Adder | 4.68 MW | 3.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 961031 | AF2-394 O1 | Adder | 3.12 MW | 2.65 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274728 | ELWOOD EC;5P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274729 | ELWOOD EC;1P | 50/50 | 5.21 MW | 5.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274730 | ELWOOD EC;6P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274732 | ELWOOD EC;7P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274734 | ELWOOD EC;8P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274736 | ELWOOD EC;9P | 50/50 | 5.23 MW | 5.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274859 | EASYR;U1 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274860 | EASYR;U2 E | Adder | 7.52 MW | 6.39 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274861 | TOP CROP ;1U | 50/50 | 0.93 MW | 0.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 274862 | TOP CROP ;2U | 50/50 | 1.78 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 276170 | Z1-108 E | Adder | 1.61 MW | 1.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 276591 | L-013 2 | Adder | 2.25 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293516 | O-009 E1 | Adder | 6.48 MW | 5.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293517 | O-009 E2 | Adder | 3.29 MW | 2.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293518 | O-009 E3 | Adder | 3.63 MW | 3.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293644 | O22 E1 | 50/50 | 24.24 MW | 24.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293645 | O22 E2 | 50/50 | 47.06 MW | 47.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293715 | O-029 E | Adder | 6.93 MW | 5.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293716 | O-029 E | Adder | 3.8 MW | 3.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293717 | O-029 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 293771 | O-035 E | Adder | 4.69 MW | 3.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294401 | BSHIL;1U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294410 | BSHIL;2U E | Adder | 6.56 MW | 5.58 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 294763 | P-046 E | Adder | 6.25 MW | 5.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 916211 | Z1-072 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 916221 | Z1-073 E | Adder | 3.38 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 925582 | AC1-033 E | Adder | 7.2 MW | 6.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930482 | AB1-089 CT | Adder | 24.12 MW | 20.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930483 | AB1-089 ST | Adder | 19.18 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930761 | AB1-122 CT1 | Adder | 68.76 MW | 58.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 930771 | AB1-122 CT2 | Adder | 93.21 MW | 79.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938511 | AE1-070 1 | 50/50 | 14.44 MW | 14.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938521 | AE1-070 2 | Adder | 13.14 MW | 11.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938851 | AE1-113 C O1 | Adder | 10.08 MW | 8.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938852 | AE1-113 E O1 | Adder | 35.73 MW | 30.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938861 | AE1-114 C O1 | Adder | 2.65 MW | 2.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 938862 | AE1-114 E O1 | Adder | 9.05 MW | 7.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939051 | AE1-134 1 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939061 | AE1-134 2 | Adder | 0.95 MW | 0.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939321 | AE1-163 C O1 | Adder | 6.89 MW | 5.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 939322 | AE1-163 E O1 | Adder | 42.35 MW | 35.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 940501 | AE2-035 C | Adder | 1.64 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 940502 | AE2-035 E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 941131 | AE2-107 C | Adder | 3.95 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 941132 | AE2-107 E | Adder | 2.63 MW | 2.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946151 | AF1-280 C O1 | Adder | 10.73 MW | 9.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946152 | AF1-280 E O1 | Adder | 4.93 MW | 4.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946161 | AF1-281 C O1 | Adder | 0.24 MW | 0.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946162 | AF1-281 E O1 | Adder | 1.33 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946321 | AF1-296 C O1 | Adder | 2.86 MW | 2.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946322 | AF1-296 E O1 | Adder | 13.39 MW | 11.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946501 | AF1-314 C | Adder | 2.91 MW | 2.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946502 | AF1-314 E | Adder | 13.66 MW | 11.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946541 | AF1-318 C O1 | Adder | 3.97 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946661 | AF1-330 C | Adder | 1.3 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946662 | AF1-330 E | Adder | 0.29 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 946671 | AF1-331 | Adder | 1.48 MW | 1.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957401 | AF2-034 C | Adder | 1.87 MW | 1.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957402 | AF2-034 E | Adder | 1.59 MW | 1.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957471 | AF2-041 C | Adder | 14.45 MW | 12.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957472 | AF2-041 E | Adder | 7.23 MW | 6.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957751 | AF2-069 C | Adder | 0.17 MW | 0.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 957762 | AF2-070 E | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958341 | AF2-128 C O1 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958342 | AF2-128 E O1 | Adder | 4.87 MW | 4.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 990901 | L-005 E | Adder | 10.43 MW | 8.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934101 | AD2-000 1 | Adder | 5.56 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 934111 | AD2-000 2 | Adder | 7.54 MW | 6.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 290108 | LEEDK;1U E | Adder | 14.62 MW | 12.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 958023 | AF2-096 BAT | Adder | 8.72 MW | 7.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 964362 | AG1-298 BAT | Adder | 42.67 MW | 36.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 954981 | J974 C | External Queue | 3.01 MW | 3.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | 954982 | J974 E | External Queue | 16.3 MW | 16.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.29 MW | 0.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.03 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.34 MW | 42.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.14 MW | 15.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.05 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.11 MW | 3.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.57 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.35 MW | 0.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.51 MW | 2.51 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 54.42 MW | 54.42 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 36.28 MW | 36.28 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 89.68 MW | 89.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 19.16 MW | 19.16 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 5.08 MW | 5.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 23.77 MW | 23.77 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 54.42 MW | 54.42 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 36.28 MW | 36.28 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 89.68 MW | 89.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 19.16 MW | 19.16 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 5.08 MW | 5.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 23.77 MW | 23.77 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | 50/50 | 395.01 MW | 395.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934101 | AD2-000 1 | 50/50 | 31.94 MW | 31.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | Adder | -179.99 MW | -152.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | 50/50 | 395.13 MW | 395.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934101 | AD2-000 1 | 50/50 | 31.95 MW | 31.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965911 | AG1-460 C | Adder | 0.84 MW | 0.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965912 | AG1-460 E | Adder | 1.26 MW | 1.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942481 | AE2-261 C | Adder | 12.56 MW | 10.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942482 | AE2-261 E | Adder | 8.38 MW | 7.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | Adder | -179.87 MW | -152.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957381 | AF2-032 C | Adder | 0.96 MW | 0.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957382 | AF2-032 E | Adder | 0.45 MW | 0.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951031 | J344 C | External Queue | 2.36 MW | 2.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951032 | J344 E | External Queue | 7.09 MW | 7.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951841 | J555 C | External Queue | 1.61 MW | 1.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951842 | J555 E | External Queue | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954721 | J750 C | External Queue | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954722 | J750 E | External Queue | 9.84 MW | 9.84 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991191 | J1610 | External Queue | 7.16 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 961651 | AG1-005 C O1 | 50/50 | 33.38 MW | 33.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 961652 | AG1-005 E O1 | 50/50 | 22.26 MW | 22.26 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 962721 | AG1-121 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 962722 | AG1-121 E O1 | 50/50 | 26.57 MW | 26.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 965671 | AG1-435 C O1 | Adder | 3.23 MW | 2.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 965672 | AG1-435 E O1 | Adder | 15.13 MW | 12.86 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 926821 | AC1-168 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 926822 | AC1-168 E O1 | 50/50 | 10.67 MW | 10.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 927201 | AC1-214 C O1 | 50/50 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 927202 | AC1-214 E O1 | 50/50 | 13.44 MW | 13.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 934051 | AD1-031 C O1 | Adder | 1.66 MW | 1.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 934052 | AD1-031 E O1 | Adder | 2.71 MW | 2.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 936511 | AD2-066 C O1 | 50/50 | 44.77 MW | 44.77 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 936512 | AD2-066 E O1 | 50/50 | 29.85 MW | 29.85 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 946542 | AF1-318 E O1 | 50/50 | 55.01 MW | 55.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 274849 | CRESCENT ;1U | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 274851 | PROVIDENC;RU | 50/50 | 0.39 MW | 0.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 293771 | O-035 E | 50/50 | 13.18 MW | 13.18 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 294401 | BSHIL;1U E | Adder | 5.03 MW | 4.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 294410 | BSHIL;2U E | Adder | 5.03 MW | 4.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 916211 | Z1-072 E | 50/50 | 9.97 MW | 9.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 925581 | AC1-033 C | Adder | 0.82 MW | 0.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 925582 | AC1-033 E | Adder | 5.51 MW | 4.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 946541 | AF1-318 C O1 | 50/50 | 11.75 MW | 11.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957751 | AF2-069 C | 50/50 | 0.49 MW | 0.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957752 | AF2-069 E | 50/50 | 1.58 MW | 1.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957761 | AF2-070 C | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957762 | AF2-070 E | 50/50 | 3.35 MW | 3.35 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 958341 | AF2-128 C O1 | 50/50 | 3.11 MW | 3.11 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 958342 | AF2-128 E O1 | 50/50 | 14.58 MW | 14.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 990901 | L-005 E | Adder | 6.85 MW | 5.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 953201 | J715 C | External Queue | 3.44 MW | 3.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 953202 | J715 E | External Queue | 18.58 MW | 18.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 990051 | J1200 | External Queue | 3.76 MW | 3.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 991301 | J1755 C | External Queue | 2.48 MW | 2.48 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 991302 | J1755 E | External Queue | 13.42 MW | 13.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.18 MW | 1.18 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.33 MW | 2.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.96 MW | 2.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.52 MW | 0.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.94 MW | 0.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.32 MW | 0.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.19 MW | 0.19 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 33.78 MW | 33.78 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 22.52 MW | 22.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 8.21 MW | 8.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 38.42 MW | 38.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 26.07 MW | 26.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.45 MW | 1.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.73 MW | 0.73 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 13.6 MW | 13.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 936511 | AD2-066 C O1 | 50/50 | 44.9 MW | 44.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 936512 | AD2-066 E O1 | 50/50 | 29.93 MW | 29.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 55.66 MW | 55.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.4 MW | 0.4 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 293771 | O-035 E | 50/50 | 13.33 MW | 13.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 916211 | Z1-072 E | 50/50 | 10.09 MW | 10.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 11.89 MW | 11.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957751 | AF2-069 C | 50/50 | 0.49 MW | 0.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957752 | AF2-069 E | 50/50 | 1.6 MW | 1.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957761 | AF2-070 C | 50/50 | 0.7 MW | 0.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957762 | AF2-070 E | 50/50 | 3.39 MW | 3.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 3.15 MW | 3.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 14.75 MW | 14.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 953201 | J715 C | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 953202 | J715 E | External Queue | 18.87 MW | 18.87 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 990051 | J1200 | External Queue | 3.83 MW | 3.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 991301 | J1755 C | External Queue | 2.27 MW | 2.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 991302 | J1755 E | External Queue | 12.27 MW | 12.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.02 MW | 1.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.23 MW | 1.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.46 MW | 2.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.65 MW | 0.65 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.2 MW | 0.2 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 23.76 MW | 23.76 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 15.84 MW | 15.84 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 8.32 MW | 8.32 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 38.93 MW | 38.93 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 26.42 MW | 26.42 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.51 MW | 0.51 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 9.57 MW | 9.57 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 4.18 MW | 4.18 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 6.83 MW | 6.83 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 39.16 MW | 39.16 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.61 MW | 0.61 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.27 MW | 0.27 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.28 MW | 0.28 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.54 MW | 0.54 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.54 MW | 0.54 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 9.38 MW | 9.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 12.74 MW | 12.74 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 12.74 MW | 12.74 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 7.1 MW | 7.1 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.08 MW | 2.08 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 13.91 MW | 13.91 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.36 MW | 8.36 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.35 MW | 0.35 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.49 MW | 0.49 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.38 MW | 2.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 10.38 MW | 10.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 16.98 MW | 16.98 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962013 | AG1-044 BAT | Adder | 0.04 MW | 0.04 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 953202 | J715 E | External Queue | 4.47 MW | 4.47 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.59 MW | 1.59 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 2.61 MW | 2.61 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 14.11 MW | 14.11 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.71 MW | 0.71 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.82 MW | 0.82 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 23.76 MW | 23.76 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 15.84 MW | 15.84 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 8.32 MW | 8.32 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 38.93 MW | 38.93 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 26.42 MW | 26.42 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.51 MW | 0.51 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 9.57 MW | 9.57 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 4.18 MW | 4.18 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 6.83 MW | 6.83 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 39.16 MW | 39.16 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 0.61 MW | 0.61 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.27 MW | 0.27 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.28 MW | 0.28 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.54 MW | 0.54 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.54 MW | 0.54 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 9.38 MW | 9.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 12.74 MW | 12.74 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 12.74 MW | 12.74 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 7.1 MW | 7.1 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.08 MW | 2.08 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 13.91 MW | 13.91 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 8.36 MW | 8.36 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.35 MW | 0.35 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.49 MW | 0.49 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.38 MW | 2.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 10.38 MW | 10.38 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 16.98 MW | 16.98 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962013 | AG1-044 BAT | Adder | 0.04 MW | 0.04 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 953202 | J715 E | External Queue | 4.47 MW | 4.47 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.59 MW | 1.59 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 2.61 MW | 2.61 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 14.11 MW | 14.11 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.71 MW | 0.71 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.82 MW | 0.82 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;23-4KEEMIN 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.5 MW | 0.5 MW |
| Details for AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 18.88 MW | 18.88 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 12.59 MW | 12.59 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 6.5 MW | 6.5 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 30.41 MW | 30.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 4.41 MW | 4.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 20.64 MW | 20.64 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 7.6 MW | 7.6 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 3.57 MW | 3.57 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 5.82 MW | 5.82 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 31.12 MW | 31.12 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.45 MW | 0.45 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.43 MW | 0.43 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.43 MW | 0.43 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 7.45 MW | 7.45 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 10.04 MW | 10.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 10.04 MW | 10.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 5.64 MW | 5.64 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 1.65 MW | 1.65 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 11.05 MW | 11.05 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 6.65 MW | 6.65 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 1.9 MW | 1.9 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 1.76 MW | 1.76 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 8.25 MW | 8.25 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 12.61 MW | 12.61 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 1.79 MW | 1.79 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 9.7 MW | 9.7 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.3 MW | 0.3 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.85 MW | 3.85 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.11 MW | 0.11 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.22 MW | 0.22 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 18.88 MW | 18.88 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 12.59 MW | 12.59 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 6.5 MW | 6.5 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 30.41 MW | 30.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 4.41 MW | 4.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 20.64 MW | 20.64 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 7.6 MW | 7.6 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 3.57 MW | 3.57 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 5.82 MW | 5.82 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 31.12 MW | 31.12 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 0.45 MW | 0.45 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.43 MW | 0.43 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.43 MW | 0.43 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 7.45 MW | 7.45 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 10.04 MW | 10.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 10.04 MW | 10.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 5.64 MW | 5.64 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 1.65 MW | 1.65 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 11.05 MW | 11.05 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 6.65 MW | 6.65 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 1.9 MW | 1.9 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 1.76 MW | 1.76 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 8.25 MW | 8.25 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 12.61 MW | 12.61 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 1.79 MW | 1.79 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 9.7 MW | 9.7 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.3 MW | 0.3 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.85 MW | 3.85 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.11 MW | 0.11 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.22 MW | 0.22 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| AD1-031 TAP-4EDWARDS3 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 18.88 MW | 18.88 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 12.59 MW | 12.59 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 6.5 MW | 6.5 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 30.41 MW | 30.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 4.41 MW | 4.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 20.64 MW | 20.64 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 7.6 MW | 7.6 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 31.12 MW | 31.12 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.45 MW | 0.45 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.43 MW | 0.43 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.43 MW | 0.43 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 7.45 MW | 7.45 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 10.04 MW | 10.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 10.04 MW | 10.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 5.64 MW | 5.64 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 1.65 MW | 1.65 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 11.05 MW | 11.05 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 6.65 MW | 6.65 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 1.9 MW | 1.9 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 1.76 MW | 1.76 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 8.25 MW | 8.25 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 12.61 MW | 12.61 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 1.79 MW | 1.79 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 9.7 MW | 9.7 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.3 MW | 0.3 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.85 MW | 3.85 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.11 MW | 0.11 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.22 MW | 0.22 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 18.88 MW | 18.88 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 12.59 MW | 12.59 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 6.5 MW | 6.5 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 30.41 MW | 30.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 4.41 MW | 4.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 20.64 MW | 20.64 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 7.6 MW | 7.6 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 31.12 MW | 31.12 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 0.45 MW | 0.45 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.43 MW | 0.43 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.43 MW | 0.43 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 7.45 MW | 7.45 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 10.04 MW | 10.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 10.04 MW | 10.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 5.64 MW | 5.64 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 1.65 MW | 1.65 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 11.05 MW | 11.05 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 6.65 MW | 6.65 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 1.9 MW | 1.9 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 1.76 MW | 1.76 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 8.25 MW | 8.25 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 12.61 MW | 12.61 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 1.79 MW | 1.79 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 9.7 MW | 9.7 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.3 MW | 0.3 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.85 MW | 3.85 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.11 MW | 0.11 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.14 MW | 0.14 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.22 MW | 0.22 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;12-AD1-031 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
Light Load Analysis
The Queue Project was evaluated as a 294.7 MW (Capacity 51.9 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line
965670 to 271835 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 0.83 % | 113.25 % | 201.0 | B | 227.63 | 235.76 | |
| CE |
AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line
965670 to 271835 ckt 1 |
COMED_P1-2_138-L6101___-S-B
CONTINGENCY 'COMED_P1-2_138-L6101___-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | -0.83 % | 112.54 % | 201.0 | B | 226.21 | 235.76 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
COMED_P2-2_074_KE-138___2
CONTINGENCY 'COMED_P2-2_074_KE-138___2' DISCONNECT BUS 271835 /*KEWANEE ;23 138.0 DISCONNECT BUS 271839 /*KEWANEE ;22 138.0 DISCONNECT BUS 271845 /*KEWANEE ;21 138.0 END |
Bus | AC | -1.08 % | 109.01 % | 208.0 | C | 226.74 | 235.76 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
COMED_P1-2_138-L98105_R-S-D
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-D' TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Single | AC | 79.72 % | 132.37 % | 201.0 | B | 266.06 | 109.52 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
COMED_P1-2_138-L98105_R-S-B
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-B' TRIP BRANCH FROM BUS 946540 TO BUS 958340 CKT 1 /*AF1-318 TAP 138.0 - AF2-128 TAP 138.0 END |
Single | AC | 76.15 % | 128.94 % | 201.0 | B | 259.17 | 109.52 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1
CONTINGENCY 'EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1' OPEN BRANCH FROM BUS 348919 TO BUS 348921 CKT 1 /*4LTV STL NTP 138.0 - 4BUREAU 138.0 END |
Single | AC | 64.89 % | 116.29 % | 201.0 | B | 233.74 | 106.84 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552
CONTINGENCY 'EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552' OPEN BRANCH FROM BUS 348918 TO BUS 348919 CKT 1 /*4HENNEPIN S 138.0 - 4LTV STL NTP 138.0 OPEN BRANCH FROM BUS 348919 TO BUS 348921 CKT 1 /*4LTV STL NTP 138.0 - 4BUREAU 138.0 OPEN BRANCH FROM BUS 348919 TO BUS 349448 CKT 1 /*4LTV STL NTP 138.0 - 1LTV STL 13.8 END |
Single | AC | 64.89 % | 116.28 % | 201.0 | B | 233.72 | 106.83 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
COMED_P1-2_138-L98105_R-S-A
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-A' TRIP BRANCH FROM BUS 271241 TO BUS 946540 CKT 1 /*CRESCENT ; R 138.0 - AF1-318 TAP 138.0 END |
Single | AC | 63.19 % | 115.92 % | 201.0 | B | 233.0 | 109.52 | |
| CE |
AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line
962720 to 271655 ckt 1 |
Base Case | Single | AC | 46.72 % | 102.14 % | 190.0 | A | 194.07 | 109.02 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 156.59 % | 166.24 % | 229.0 | B | 380.69 | 23.22 | |
| CE |
AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line
946540 to 958340 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 173.45 % | 185.57 % | 180.0 | STE | 334.02 | 23.22 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 131.52 % | 133.6 % | 971.0 | B | 1297.26 | 20.21 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 131.52 % | 133.6 % | 971.0 | B | 1297.26 | 20.21 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 113.17 % | 114.1 % | 971.0 | B | 1107.91 | 20.1 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 134.79 % | 136.74 % | 1409.0 | B | 1926.67 | 29.19 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 134.79 % | 136.74 % | 1409.0 | B | 1926.67 | 29.19 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 131.53 % | 133.61 % | 971.0 | STE | 1297.35 | 20.21 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 131.53 % | 133.61 % | 971.0 | STE | 1297.35 | 20.21 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 113.18 % | 113.83 % | 971.0 | STE | 1105.29 | 20.1 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 123.16 % | 124.83 % | 1483.0 | STE | 1851.16 | 25.58 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 123.16 % | 124.83 % | 1483.0 | STE | 1851.16 | 25.58 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
Base Case | Single | DC | 108.24 % | 109.75 % | 1091.0 | A | 1197.37 | 16.44 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 130.33 % | 132.1 % | 1399.0 | B | 1848.08 | 25.58 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 130.33 % | 132.1 % | 1399.0 | B | 1848.08 | 25.58 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
Base Case | Single | DC | 107.97 % | 109.47 % | 1091.0 | A | 1194.32 | 16.44 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 110.43 % | 112.08 % | 1441.0 | B | 1615.07 | 23.81 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 110.43 % | 112.08 % | 1441.0 | B | 1615.07 | 23.81 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | AC | 95.88 % | 116.28 % | 214.0 | B | 248.84 | 45.47 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | AC | 96.44 % | 116.5 % | 214.0 | B | 249.31 | 45.47 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S
CONTINGENCY 'COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S' MOVE 100 PERCENT LOAD FROM BUS 272110 TO BUS 272111 /*NORMANDY ; B 138.0 - NORMANDY ; R 138.0 TRIP BRANCH FROM BUS 271835 TO BUS 348962 CKT 1 /*KEWANEE ;23 138.0 - 4KEEMIN 138.0 TRIP BRANCH FROM BUS 271836 TO BUS 272110 CKT 1 /*KEWANEE ;11 138.0 - NORMANDY ; B 138.0 TRIP BRANCH FROM BUS 272110 TO BUS 272505 CKT 1 /*NORMANDY ; B 138.0 - SCHAUFF R; R 138.0 END |
Tower | AC | 89.39 % | 108.0 % | 214.0 | B | 231.12 | 40.77 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S
CONTINGENCY 'COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S' MOVE 100 PERCENT LOAD FROM BUS 272111 TO BUS 272110 /*NORMANDY ; R 138.0 - NORMANDY ; B 138.0 TRIP BRANCH FROM BUS 271836 TO BUS 272110 CKT 1 /*KEWANEE ;11 138.0 - NORMANDY ; B 138.0 TRIP BRANCH FROM BUS 272110 TO BUS 272505 CKT 1 /*NORMANDY ; B 138.0 - SCHAUFF R; R 138.0 TRIP BRANCH FROM BUS 272505 TO BUS 272111 CKT 1 /*SCHAUFF R; R 138.0 - NORMANDY ; R 138.0 TRIP BRANCH FROM BUS 348962 TO BUS 272111 CKT 1 /*4KEEMIN 138.0 - NORMANDY ; R 138.0 END |
Tower | AC | 88.43 % | 107.02 % | 214.0 | B | 229.02 | 40.77 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z
CONTINGENCY 'EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z' OPEN BRANCH FROM BUS 348923 TO BUS 348974 CKT Z /*4KEWANEE N 138.0 - 4KEWANEE S 138.0 END |
Single | AC | 86.84 % | 103.62 % | 214.0 | B | 221.75 | 36.06 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P1-2_138-L98105_R-S-D
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-D' TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Single | AC | 91.6 % | 104.6 % | 214.0 | B | 223.84 | 29.62 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
Base Case | Single | AC | 85.66 % | 101.36 % | 184.0 | A | 186.5 | 29.4 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B
CONTINGENCY 'COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B' TRIP BRANCH FROM BUS 271977 TO BUS 271844 CKT 1 /*MARSEILLE; T 138.0 - KICKAPOO ; B 138.0 TRIP BRANCH FROM BUS 271977 TO BUS 348931 CKT 1 /*MARSEILLE; T 138.0 - 4MARSEILLES 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 271977 CKT 1 /*STREATOR ; 138.0 - MARSEILLE; T 138.0 TRIP BRANCH FROM BUS 936510 TO BUS 348935 CKT 1 /*AD2-066 TAP 138.0 - 4CORBIN 138.0 END |
Tower | AC | 84.81 % | 101.18 % | 214.0 | B | 216.53 | 35.68 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P1-2_138-L7423___-SA
CONTINGENCY 'COMED_P1-2_138-L7423___-SA' TRIP BRANCH FROM BUS 271837 TO BUS 934053 CKT 1 /*KEWANEE ;12 138.0 - AD1-031 TAP 138.0 END |
Single | AC | 85.25 % | 100.65 % | 214.0 | B | 215.39 | 33.49 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P1-2_138-L98105_R-S-B
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-B' TRIP BRANCH FROM BUS 946540 TO BUS 958340 CKT 1 /*AF1-318 TAP 138.0 - AF2-128 TAP 138.0 END |
Single | AC | 87.56 % | 101.07 % | 214.0 | B | 216.29 | 29.62 | |
| CE |
MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line
271987 to 271187 ckt 1 |
Base Case | Single | AC | 105.0 % | 115.97 % | 173.0 | A | 200.63 | 20.75 | |
| CE |
MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line
271987 to 271187 ckt 1 |
COMED_P1-2_138-L0112__B-S
CONTINGENCY 'COMED_P1-2_138-L0112__B-S' TRIP BRANCH FROM BUS 271844 TO BUS 271908 CKT 1 /*KICKAPOO ; B 138.0 - LASCO STA; B 138.0 END |
Single | AC | 102.73 % | 113.06 % | 223.0 | STE | 252.12 | 25.14 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 107.32 % | 108.99 % | 1091.0 | B | 1189.08 | 18.26 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 107.32 % | 108.99 % | 1091.0 | B | 1189.08 | 18.26 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 106.3 % | 107.57 % | 1466.0 | B | 1576.98 | 19.57 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P1-2_#286_1687
CONTINGENCY 'AEP_P1-2_#286_1687' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Single | DC | 99.17 % | 100.51 % | 1466.0 | B | 1473.48 | 19.7 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P1-2_138-L0112__B-S
CONTINGENCY 'COMED_P1-2_138-L0112__B-S' TRIP BRANCH FROM BUS 271844 TO BUS 271908 CKT 1 /*KICKAPOO ; B 138.0 - LASCO STA; B 138.0 END |
Single | AC | 102.57 % | 113.13 % | 253.0 | B | 286.22 | 28.7 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P4_001-38-TR81___
CONTINGENCY 'COMED_P4_001-38-TR81___' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 TRIP BRANCH FROM BUS 270802 TO BUS 270803 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; R 345.0 TRIP BRANCH FROM BUS 270802 TO BUS 271908 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; B 138.0 END |
Breaker | AC | 101.01 % | 111.53 % | 253.0 | B | 282.17 | 28.59 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 101.01 % | 111.53 % | 253.0 | B | 282.17 | 28.59 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
Base Case | Single | AC | 94.38 % | 104.36 % | 213.0 | A | 222.29 | 23.08 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P1-2_138-L0112__B-S
CONTINGENCY 'COMED_P1-2_138-L0112__B-S' TRIP BRANCH FROM BUS 271844 TO BUS 271908 CKT 1 /*KICKAPOO ; B 138.0 - LASCO STA; B 138.0 END |
Single | AC | 116.21 % | 128.2 % | 223.0 | STE | 285.89 | 28.7 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 96.3 % | 106.36 % | 265.0 | ALDR | 281.84 | 28.59 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P4_001-38-TR81___
CONTINGENCY 'COMED_P4_001-38-TR81___' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 TRIP BRANCH FROM BUS 270802 TO BUS 270803 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; R 345.0 TRIP BRANCH FROM BUS 270802 TO BUS 271908 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; B 138.0 END |
Breaker | AC | 96.3 % | 106.36 % | 265.0 | ALDR | 281.84 | 28.59 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
Base Case | Single | AC | 94.18 % | 104.18 % | 213.0 | A | 221.9 | 23.08 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P1-2_138-L7413__R-S
CONTINGENCY 'COMED_P1-2_138-L7413__R-S' TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 END |
Single | AC | 97.93 % | 107.41 % | 223.0 | STE | 239.52 | 22.76 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P1-2_345-L15502_B-R-A
CONTINGENCY 'COMED_P1-2_345-L15502_B-R-A' TRIP BRANCH FROM BUS 270828 TO BUS 965660 CKT 1 /*NELSON ; B 345.0 - AG1-434 TAP 345.0 END |
Single | AC | 96.07 % | 105.72 % | 223.0 | STE | 235.75 | 23.34 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P1-2_345-L15502_B-R-B
CONTINGENCY 'COMED_P1-2_345-L15502_B-R-B' TRIP BRANCH FROM BUS 965660 TO BUS 957470 CKT 1 /*AG1-434 TAP 345.0 - AF2-041 TAP 345.0 END |
Single | AC | 96.07 % | 105.7 % | 223.0 | STE | 235.72 | 23.34 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
Base Case | Single | DC | 102.35 % | 103.81 % | 3555.0 | A | 3690.45 | 55.22 | |
| CE |
AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line
962720 to 965670 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 0.31 % | 114.38 % | 201.0 | B | 229.9 | 235.76 | |
| CE |
AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line
962720 to 965670 ckt 1 |
COMED_P1-2_138-L6101___-S-B
CONTINGENCY 'COMED_P1-2_138-L6101___-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | -0.31 % | 114.33 % | 201.0 | B | 229.8 | 235.76 | |
| Details for AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C | 80/20 | 41.52 MW | 41.52 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962722 | AG1-121 E | 80/20 | 194.24 MW | 194.24 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965671 | AG1-435 C | 80/20 | 28.16 MW | 28.16 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965672 | AG1-435 E | 80/20 | 131.84 MW | 131.84 MW |
| Details for AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962721 | AG1-121 C | 80/20 | 41.52 MW | 41.52 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962722 | AG1-121 E | 80/20 | 194.24 MW | 194.24 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 965671 | AG1-435 C | 80/20 | 28.16 MW | 28.16 MW |
| AG1-435 TAP-KEWANEE ;23 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 965672 | AG1-435 E | 80/20 | 131.84 MW | 131.84 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 962721 | AG1-121 C | 50/50 | 41.52 MW | 41.52 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 962722 | AG1-121 E | 50/50 | 194.24 MW | 194.24 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 965671 | AG1-435 C | 50/50 | 28.16 MW | 28.16 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___2 | 965672 | AG1-435 E | 50/50 | 131.84 MW | 131.84 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 80/20 | 1.05 MW | 1.05 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 80/20 | 0.48 MW | 0.48 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 80/20 | 0.49 MW | 0.49 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293771 | O-035 E | 80/20 | 2.82 MW | 2.82 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 294401 | BSHIL;1U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 294410 | BSHIL;2U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 916211 | Z1-072 E | 80/20 | 4.27 MW | 4.27 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 925581 | AC1-033 C | 80/20 | 1.25 MW | 1.25 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 925582 | AC1-033 E | 80/20 | 8.36 MW | 8.36 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 80/20 | 2.88 MW | 2.88 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 80/20 | 5.03 MW | 5.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 80/20 | 23.56 MW | 23.56 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957751 | AF2-069 C | 80/20 | 0.21 MW | 0.21 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957752 | AF2-069 E | 80/20 | 0.68 MW | 0.68 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957761 | AF2-070 C | 80/20 | 0.29 MW | 0.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957762 | AF2-070 E | 80/20 | 1.44 MW | 1.44 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 80/20 | 1.33 MW | 1.33 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 80/20 | 6.24 MW | 6.24 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 962721 | AG1-121 C | 80/20 | 19.29 MW | 19.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 962722 | AG1-121 E | 80/20 | 90.23 MW | 90.23 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 965671 | AG1-435 C | 80/20 | 9.41 MW | 9.41 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 965672 | AG1-435 E | 80/20 | 44.06 MW | 44.06 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 80/20 | 1.05 MW | 1.05 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 80/20 | 0.48 MW | 0.48 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 80/20 | 0.49 MW | 0.49 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293771 | O-035 E | 80/20 | 2.82 MW | 2.82 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 294401 | BSHIL;1U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 294410 | BSHIL;2U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 916211 | Z1-072 E | 80/20 | 4.27 MW | 4.27 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 925581 | AC1-033 C | 80/20 | 1.25 MW | 1.25 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 925582 | AC1-033 E | 80/20 | 8.36 MW | 8.36 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 80/20 | 2.88 MW | 2.88 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 80/20 | 5.03 MW | 5.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 80/20 | 23.56 MW | 23.56 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957751 | AF2-069 C | 80/20 | 0.21 MW | 0.21 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957752 | AF2-069 E | 80/20 | 0.68 MW | 0.68 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957761 | AF2-070 C | 80/20 | 0.29 MW | 0.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957762 | AF2-070 E | 80/20 | 1.44 MW | 1.44 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 962721 | AG1-121 C | 80/20 | 19.29 MW | 19.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 962722 | AG1-121 E | 80/20 | 90.23 MW | 90.23 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 965671 | AG1-435 C | 80/20 | 9.41 MW | 9.41 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 965672 | AG1-435 E | 80/20 | 44.06 MW | 44.06 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 274848 | CAMPGROVE;RU | 80/20 | 1.14 MW | 1.14 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 274877 | BISHOP HL;1U | 80/20 | 1.03 MW | 1.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 274878 | BISHOP HL;2U | 80/20 | 1.03 MW | 1.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 294401 | BSHIL;1U E | 80/20 | 4.13 MW | 4.13 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 294410 | BSHIL;2U E | 80/20 | 4.13 MW | 4.13 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 925581 | AC1-033 C | 80/20 | 1.35 MW | 1.35 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 925582 | AC1-033 E | 80/20 | 9.02 MW | 9.02 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 962721 | AG1-121 C | 80/20 | 18.82 MW | 18.82 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 962722 | AG1-121 E | 80/20 | 88.02 MW | 88.02 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 965671 | AG1-435 C | 80/20 | 9.31 MW | 9.31 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 965672 | AG1-435 E | 80/20 | 43.6 MW | 43.6 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_348919 4LTV STL NTP 138 348921 4BUREAU 138 1 | 991301 | J1755 | External Queue | 16.16 MW | 16.16 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 274848 | CAMPGROVE;RU | 80/20 | 1.14 MW | 1.14 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 274877 | BISHOP HL;1U | 80/20 | 1.03 MW | 1.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 274878 | BISHOP HL;2U | 80/20 | 1.03 MW | 1.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 294401 | BSHIL;1U E | 80/20 | 4.13 MW | 4.13 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 294410 | BSHIL;2U E | 80/20 | 4.13 MW | 4.13 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 925581 | AC1-033 C | 80/20 | 1.35 MW | 1.35 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 925582 | AC1-033 E | 80/20 | 9.02 MW | 9.02 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 962721 | AG1-121 C | 80/20 | 18.81 MW | 18.81 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 962722 | AG1-121 E | 80/20 | 88.02 MW | 88.02 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 965671 | AG1-435 C | 80/20 | 9.31 MW | 9.31 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 965672 | AG1-435 E | 80/20 | 43.59 MW | 43.59 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o EXT_P12:138:AMIL::HENNEPIN:BUREAU:1552 | 991301 | J1755 | External Queue | 16.16 MW | 16.16 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 274848 | CAMPGROVE;RU | 80/20 | 1.05 MW | 1.05 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 274849 | CRESCENT ;1U | 80/20 | 0.48 MW | 0.48 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 274851 | PROVIDENC;RU | 80/20 | 0.49 MW | 0.49 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 274877 | BISHOP HL;1U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 274878 | BISHOP HL;2U | 80/20 | 0.96 MW | 0.96 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 293771 | O-035 E | 80/20 | 2.82 MW | 2.82 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 294401 | BSHIL;1U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 294410 | BSHIL;2U E | 80/20 | 3.83 MW | 3.83 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 916211 | Z1-072 E | 80/20 | 4.27 MW | 4.27 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 925581 | AC1-033 C | 80/20 | 1.25 MW | 1.25 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 925582 | AC1-033 E | 80/20 | 8.36 MW | 8.36 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 927201 | AC1-214 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 927202 | AC1-214 E O1 | 80/20 | 2.88 MW | 2.88 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 957751 | AF2-069 C | 80/20 | 0.21 MW | 0.21 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 957752 | AF2-069 E | 80/20 | 0.68 MW | 0.68 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 957761 | AF2-070 C | 80/20 | 0.29 MW | 0.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 957762 | AF2-070 E | 80/20 | 1.44 MW | 1.44 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 962721 | AG1-121 C | 80/20 | 19.29 MW | 19.29 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 962722 | AG1-121 E | 80/20 | 90.23 MW | 90.23 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 965671 | AG1-435 C | 80/20 | 9.41 MW | 9.41 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-A | 965672 | AG1-435 E | 80/20 | 44.06 MW | 44.06 MW |
| Details for AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.79 MW | 0.79 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.79 MW | 0.79 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 3.17 MW | 3.17 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 3.17 MW | 3.17 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 1.03 MW | 1.03 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 6.9 MW | 6.9 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 19.2 MW | 19.2 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 89.82 MW | 89.82 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 9.15 MW | 9.15 MW |
| AG1-121 TAP-HENNEEPIN; T 138.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 42.86 MW | 42.86 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274849 | CRESCENT ;1U | 80/20 | 1.38 MW | 1.38 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274851 | PROVIDENC;RU | 80/20 | 1.42 MW | 1.42 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274877 | BISHOP HL;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274878 | BISHOP HL;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 293771 | O-035 E | 80/20 | 8.17 MW | 8.17 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 294401 | BSHIL;1U E | 80/20 | 3.16 MW | 3.16 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 294410 | BSHIL;2U E | 80/20 | 3.16 MW | 3.16 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 916211 | Z1-072 E | 80/20 | 12.36 MW | 12.36 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925582 | AC1-033 E | 80/20 | 6.95 MW | 6.95 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927201 | AC1-214 C O1 | 80/20 | 2.62 MW | 2.62 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927202 | AC1-214 E O1 | 80/20 | 8.34 MW | 8.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946541 | AF1-318 C O1 | 80/20 | 29.07 MW | 29.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946542 | AF1-318 E O1 | 80/20 | 136.11 MW | 136.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957751 | AF2-069 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957752 | AF2-069 E | 80/20 | 1.96 MW | 1.96 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957761 | AF2-070 C | 80/20 | 0.86 MW | 0.86 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957762 | AF2-070 E | 80/20 | 4.15 MW | 4.15 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 958341 | AF2-128 C O1 | 80/20 | 8.5 MW | 8.5 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 958342 | AF2-128 E O1 | 80/20 | 39.78 MW | 39.78 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C | 80/20 | 4.09 MW | 4.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962722 | AG1-121 E | 80/20 | 19.13 MW | 19.13 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965671 | AG1-435 C | 80/20 | 2.77 MW | 2.77 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965672 | AG1-435 E | 80/20 | 12.99 MW | 12.99 MW |
| Details for AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274849 | CRESCENT ;1U | 80/20 | 1.38 MW | 1.38 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274851 | PROVIDENC;RU | 80/20 | 1.42 MW | 1.42 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274877 | BISHOP HL;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274878 | BISHOP HL;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 293771 | O-035 E | 80/20 | 8.17 MW | 8.17 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 294401 | BSHIL;1U E | 80/20 | 3.16 MW | 3.16 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 294410 | BSHIL;2U E | 80/20 | 3.16 MW | 3.16 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 916211 | Z1-072 E | 80/20 | 12.36 MW | 12.36 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925582 | AC1-033 E | 80/20 | 6.95 MW | 6.95 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927201 | AC1-214 C O1 | 80/20 | 2.62 MW | 2.62 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927202 | AC1-214 E O1 | 80/20 | 8.34 MW | 8.34 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946541 | AF1-318 C O1 | 80/20 | 29.07 MW | 29.07 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946542 | AF1-318 E O1 | 80/20 | 136.11 MW | 136.11 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957751 | AF2-069 C | 80/20 | 0.61 MW | 0.61 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957752 | AF2-069 E | 80/20 | 1.96 MW | 1.96 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957761 | AF2-070 C | 80/20 | 0.86 MW | 0.86 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957762 | AF2-070 E | 80/20 | 4.15 MW | 4.15 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C | 80/20 | 4.09 MW | 4.09 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962722 | AG1-121 E | 80/20 | 19.13 MW | 19.13 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965671 | AG1-435 C | 80/20 | 2.77 MW | 2.77 MW |
| AF1-318 TAP-AF2-128 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965672 | AG1-435 E | 80/20 | 12.99 MW | 12.99 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965791 | AG1-447 | 80/20 | 46.86 MW | 46.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965791 | AG1-447 | 80/20 | 46.86 MW | 46.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274658 | DRESDEN ;2U | 50/50 | 92.19 MW | 92.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274659 | DRESDEN ;3U | Adder | 89.08 MW | 75.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274847 | GR RIDGE ;BU | 50/50 | 1.13 MW | 1.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274871 | GR RIDGE ;2U | 50/50 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274888 | KELLY CRK;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274891 | OTTER CRK;1U | 50/50 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | 50/50 | 5.83 MW | 5.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | 50/50 | 4.95 MW | 4.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293799 | PILOT HIL;1E | 50/50 | 6.58 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | 50/50 | 6.29 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | 50/50 | 6.31 MW | 6.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.27 MW | 1.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | 50/50 | 12.22 MW | 12.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | 50/50 | 57.03 MW | 57.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | 50/50 | 2.83 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | 50/50 | 13.84 MW | 13.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 6.39 MW | 5.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C O1 | Adder | 5.04 MW | 4.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 8.43 MW | 7.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | 50/50 | 4.01 MW | 4.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | 50/50 | 24.61 MW | 24.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 3.26 MW | 2.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 15.28 MW | 12.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | 50/50 | 0.57 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | 50/50 | 3.52 MW | 3.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.02 MW | 2.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946161 | AF1-281 C O1 | Adder | 0.27 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946162 | AF1-281 E O1 | Adder | 1.52 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 2.74 MW | 2.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 12.86 MW | 10.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946541 | AF1-318 C O1 | Adder | 3.62 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946542 | AF1-318 E O1 | Adder | 16.95 MW | 14.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 1.98 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 2.97 MW | 2.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | 50/50 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | 50/50 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | 50/50 | 4.17 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | 50/50 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | 50/50 | 8.02 MW | 8.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | 50/50 | 0.0 MW | 0.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958342 | AF2-128 E O1 | Adder | 4.5 MW | 3.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958921 | AF2-183 C | Adder | 2.86 MW | 2.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958922 | AF2-183 E | Adder | 4.29 MW | 3.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 3.78 MW | 3.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 10.86 MW | 9.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | 50/50 | 4.25 MW | 4.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | 50/50 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961011 | AF2-392 C O1 | Adder | 2.5 MW | 2.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961012 | AF2-392 E O1 | Adder | 11.69 MW | 9.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961021 | AF2-393 O1 | Adder | 5.32 MW | 4.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961031 | AF2-394 O1 | Adder | 3.55 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 6.86 MW | 5.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 10.29 MW | 8.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962721 | AG1-121 C | Adder | 3.54 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962722 | AG1-121 E | Adder | 16.56 MW | 14.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 964361 | AG1-298 O1 | Adder | 23.75 MW | 20.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965661 | AG1-434 C | Adder | 2.6 MW | 2.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965662 | AG1-434 E | Adder | 12.16 MW | 10.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965791 | AG1-447 | 50/50 | 46.73 MW | 46.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966091 | AG1-478 C | 50/50 | 0.41 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966092 | AG1-478 E | 50/50 | 0.62 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966431 | AG1-512 C | 50/50 | 3.6 MW | 3.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966432 | AG1-512 E | 50/50 | 5.39 MW | 5.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966441 | AG1-513 C | 50/50 | 0.4 MW | 0.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966442 | AG1-513 E | 50/50 | 0.61 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 919221 | AA1-146 | Adder | 13.83 MW | 11.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965061 | AG1-371 C | Adder | 2.81 MW | 2.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965062 | AG1-371 E | Adder | 4.21 MW | 3.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965081 | AG1-373 C | Adder | 0.94 MW | 0.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965082 | AG1-373 E | Adder | 1.4 MW | 1.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | 50/50 | 208.43 MW | 208.43 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 93.0 MW | 93.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 89.8 MW | 89.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.51 MW | 0.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.0 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.34 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.79 MW | 0.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.02 MW | 1.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.47 MW | 1.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 5.89 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.47 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.87 MW | 0.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.56 MW | 1.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 4.43 MW | 4.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 6.16 MW | 6.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.33 MW | 3.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 7.74 MW | 7.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 4.42 MW | 4.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.0 MW | 5.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.81 MW | 0.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.46 MW | 0.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.11 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.04 MW | 6.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.69 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.55 MW | 1.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.02 MW | 2.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.83 MW | 6.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 6.64 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 6.34 MW | 6.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.7 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.96 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.01 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.12 MW | 0.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.93 MW | 0.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.05 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.95 MW | 1.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 5.12 MW | 5.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 6.36 MW | 6.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 7.02 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.93 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.87 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 12.33 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 57.54 MW | 57.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.08 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 13.98 MW | 13.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 6.44 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 18.01 MW | 18.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 24.8 MW | 24.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 15.38 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.68 MW | 3.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.15 MW | 1.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 7.69 MW | 7.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.77 MW | 5.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.04 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.03 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 11.65 MW | 11.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.76 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 12.96 MW | 12.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 17.04 MW | 17.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.0 MW | 2.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.62 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.1 MW | 8.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.53 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.88 MW | 2.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 4.32 MW | 4.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 10.94 MW | 10.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 2.86 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 4.28 MW | 4.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.26 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.4 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.09 MW | 2.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 11.76 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 5.35 MW | 5.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.57 MW | 3.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.96 MW | 6.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.56 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 16.65 MW | 16.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.14 MW | 1.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 7.64 MW | 7.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 43.13 MW | 43.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 5.23 MW | 5.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 12.34 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 9.36 MW | 9.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 6.24 MW | 6.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.62 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 12.24 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.4 MW | 2.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 11.24 MW | 11.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.62 MW | 3.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 5.42 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 6.8 MW | 6.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 5.44 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 8.15 MW | 8.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 13.91 MW | 13.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.83 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 4.24 MW | 4.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 210.26 MW | 210.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965792 | AG1-447 BAT | 80/20 | 8.14 MW | 8.14 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274658 | DRESDEN ;2U | 50/50 | 92.19 MW | 92.19 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274659 | DRESDEN ;3U | Adder | 89.08 MW | 75.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274847 | GR RIDGE ;BU | 50/50 | 1.13 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274871 | GR RIDGE ;2U | 50/50 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274888 | KELLY CRK;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274891 | OTTER CRK;1U | 50/50 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | 50/50 | 5.83 MW | 5.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.32 MW | 1.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | 50/50 | 4.95 MW | 4.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293799 | PILOT HIL;1E | 50/50 | 6.58 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | 50/50 | 6.29 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | 50/50 | 6.31 MW | 6.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.27 MW | 1.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | 50/50 | 12.22 MW | 12.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | 50/50 | 57.03 MW | 57.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | 50/50 | 2.83 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | 50/50 | 13.84 MW | 13.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 6.39 MW | 5.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C O1 | Adder | 5.04 MW | 4.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 8.43 MW | 7.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | 50/50 | 4.01 MW | 4.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | 50/50 | 24.61 MW | 24.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 3.26 MW | 2.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 15.28 MW | 12.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | 50/50 | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | 50/50 | 3.52 MW | 3.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.02 MW | 2.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946161 | AF1-281 C O1 | Adder | 0.27 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946162 | AF1-281 E O1 | Adder | 1.52 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 2.74 MW | 2.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 12.86 MW | 10.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946541 | AF1-318 C O1 | Adder | 3.62 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946542 | AF1-318 E O1 | Adder | 16.95 MW | 14.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 1.98 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 2.97 MW | 2.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | 50/50 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | 50/50 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | 50/50 | 4.17 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | 50/50 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | 50/50 | 8.02 MW | 8.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | 50/50 | 0.0 MW | 0.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958342 | AF2-128 E O1 | Adder | 4.5 MW | 3.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958921 | AF2-183 C | Adder | 2.86 MW | 2.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958922 | AF2-183 E | Adder | 4.29 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 3.78 MW | 3.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 10.86 MW | 9.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | 50/50 | 4.25 MW | 4.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | 50/50 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961011 | AF2-392 C O1 | Adder | 2.5 MW | 2.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961012 | AF2-392 E O1 | Adder | 11.69 MW | 9.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961021 | AF2-393 O1 | Adder | 5.32 MW | 4.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961031 | AF2-394 O1 | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 6.86 MW | 5.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 10.29 MW | 8.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962721 | AG1-121 C | Adder | 3.54 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962722 | AG1-121 E | Adder | 16.56 MW | 14.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 964361 | AG1-298 O1 | Adder | 34.76 MW | 29.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965661 | AG1-434 C | Adder | 2.6 MW | 2.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965662 | AG1-434 E | Adder | 12.16 MW | 10.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966091 | AG1-478 C | 50/50 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966092 | AG1-478 E | 50/50 | 0.62 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966431 | AG1-512 C | 50/50 | 3.6 MW | 3.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966432 | AG1-512 E | 50/50 | 5.39 MW | 5.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966441 | AG1-513 C | 50/50 | 0.4 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966442 | AG1-513 E | 50/50 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 919221 | AA1-146 | Adder | 13.83 MW | 11.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965061 | AG1-371 C | Adder | 2.81 MW | 2.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965062 | AG1-371 E | Adder | 4.21 MW | 3.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965081 | AG1-373 C | Adder | 0.94 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965082 | AG1-373 E | Adder | 1.4 MW | 1.19 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | 50/50 | 208.43 MW | 208.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965792 | AG1-447 BAT | 50/50 | 8.28 MW | 8.28 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 80.75 MW | 80.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 69.94 MW | 69.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.4 MW | 0.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.76 MW | 0.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.58 MW | 0.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 2.8 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 2.8 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.33 MW | 1.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.68 MW | 0.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 4.17 MW | 4.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 5.31 MW | 5.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 2.64 MW | 2.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 6.12 MW | 6.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 3.37 MW | 3.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 3.37 MW | 3.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 4.07 MW | 4.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.65 MW | 0.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.33 MW | 0.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 3.42 MW | 3.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 6.63 MW | 6.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 1.64 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 3.61 MW | 3.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 3.61 MW | 3.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 4.69 MW | 4.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 5.17 MW | 5.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 2.39 MW | 2.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.21 MW | 0.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 1.59 MW | 1.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 2.48 MW | 2.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 1.55 MW | 1.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 3.91 MW | 3.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 4.89 MW | 4.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 1.67 MW | 1.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 9.73 MW | 9.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 45.4 MW | 45.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 9.88 MW | 9.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.28 MW | 1.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 5.11 MW | 5.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 4.38 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 15.53 MW | 15.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 6.83 MW | 6.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 3.05 MW | 3.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 18.71 MW | 18.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 11.72 MW | 11.72 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 2.81 MW | 2.81 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 0.88 MW | 0.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 5.87 MW | 5.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 4.98 MW | 4.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 2.67 MW | 2.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 2.45 MW | 2.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 1.23 MW | 1.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 9.4 MW | 9.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 2.22 MW | 2.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 10.43 MW | 10.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 13.82 MW | 13.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 2.45 MW | 2.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 0.37 MW | 0.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 2.98 MW | 2.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 8.26 MW | 8.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 3.67 MW | 3.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.32 MW | 2.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 8.8 MW | 8.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 3.14 MW | 3.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 3.14 MW | 3.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.29 MW | 3.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 1.6 MW | 1.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 9.46 MW | 9.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.31 MW | 4.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 13.55 MW | 13.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 3.99 MW | 3.99 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 2.1 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 9.84 MW | 9.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 1.95 MW | 1.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 9.15 MW | 9.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 0.49 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 1.01 MW | 1.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 1.52 MW | 1.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 11.2 MW | 11.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 2.27 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 3.41 MW | 3.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 0.76 MW | 0.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 1.14 MW | 1.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 151.26 MW | 151.26 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 121.1 MW | 121.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 112.32 MW | 112.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.45 MW | 1.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.64 MW | 0.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.24 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.91 MW | 0.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.41 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.98 MW | 0.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.26 MW | 1.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.93 MW | 1.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.5 MW | 5.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.98 MW | 7.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.2 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.77 MW | 9.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.49 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 6.35 MW | 6.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.85 MW | 1.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.04 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.76 MW | 4.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.24 MW | 9.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.14 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.55 MW | 2.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.88 MW | 5.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.46 MW | 8.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.06 MW | 8.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.75 MW | 3.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.54 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.15 MW | 0.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.17 MW | 1.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.86 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.36 MW | 6.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.01 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.71 MW | 8.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.12 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 7.51 MW | 7.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 6.17 MW | 6.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.38 MW | 15.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.78 MW | 71.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.58 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 15.6 MW | 15.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.03 MW | 2.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 8.13 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 23.34 MW | 23.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.74 MW | 10.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.54 MW | 28.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.08 MW | 19.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.43 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.54 MW | 9.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.49 MW | 2.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 7.48 MW | 7.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.57 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 944222 | AF1-090 E O1 | 80/20 | 6.67 MW | 6.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.94 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 14.76 MW | 14.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.49 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 16.4 MW | 16.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 21.49 MW | 21.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 4.7 MW | 4.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.65 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.47 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 13.85 MW | 13.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.37 MW | 5.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.41 MW | 1.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.73 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.6 MW | 2.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 14.89 MW | 14.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.78 MW | 6.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 9.95 MW | 9.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 21.07 MW | 21.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.48 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 32.61 MW | 32.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.41 MW | 0.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.31 MW | 15.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.61 MW | 11.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.74 MW | 7.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.32 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.04 MW | 3.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 14.23 MW | 14.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965911 | AG1-460 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965912 | AG1-460 E | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.5 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.75 MW | 0.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.41 MW | 2.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 4.42 MW | 4.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.89 MW | 6.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 10.33 MW | 10.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 17.63 MW | 17.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.59 MW | 3.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.38 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.2 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.79 MW | 1.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 264.83 MW | 264.83 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 80.75 MW | 80.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 69.94 MW | 69.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 0.93 MW | 0.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.71 MW | 0.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.4 MW | 0.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.74 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.76 MW | 0.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.58 MW | 0.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 2.8 MW | 2.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 2.8 MW | 2.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 0.35 MW | 0.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.33 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.68 MW | 0.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 4.17 MW | 4.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.7 MW | 0.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 5.31 MW | 5.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 2.64 MW | 2.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 6.12 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 3.37 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 3.37 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 4.07 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.65 MW | 0.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.33 MW | 0.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.37 MW | 0.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 3.42 MW | 3.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 6.63 MW | 6.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 1.64 MW | 1.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 3.61 MW | 3.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 3.61 MW | 3.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 4.69 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 5.17 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 2.39 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.21 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 1.59 MW | 1.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 0.74 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 2.48 MW | 2.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 1.55 MW | 1.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 3.91 MW | 3.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 4.57 MW | 4.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 4.89 MW | 4.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 1.67 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.14 MW | 0.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 9.73 MW | 9.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 45.4 MW | 45.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 9.88 MW | 9.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.28 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 5.11 MW | 5.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 4.38 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 15.53 MW | 15.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 6.83 MW | 6.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 3.05 MW | 3.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 18.71 MW | 18.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 11.72 MW | 11.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 2.81 MW | 2.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 0.88 MW | 0.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 5.87 MW | 5.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 4.98 MW | 4.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 2.67 MW | 2.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 2.45 MW | 2.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 1.23 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 9.4 MW | 9.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 2.22 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 10.43 MW | 10.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 2.95 MW | 2.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 13.82 MW | 13.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 2.45 MW | 2.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 0.37 MW | 0.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 2.98 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 8.26 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 3.67 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.32 MW | 2.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 3.48 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 8.8 MW | 8.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 3.14 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 3.14 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.29 MW | 3.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 1.6 MW | 1.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 9.46 MW | 9.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.31 MW | 4.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 13.55 MW | 13.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 3.99 MW | 3.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 2.1 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 9.84 MW | 9.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 1.95 MW | 1.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 9.15 MW | 9.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 0.49 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 1.01 MW | 1.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 0.48 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 11.2 MW | 11.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 2.27 MW | 2.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 3.41 MW | 3.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 0.76 MW | 0.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 1.14 MW | 1.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 151.26 MW | 151.26 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 109.06 MW | 109.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 106.54 MW | 106.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.32 MW | 1.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.6 MW | 0.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.18 MW | 1.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.22 MW | 1.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.99 MW | 0.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.55 MW | 1.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.84 MW | 1.84 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.8 MW | 1.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.24 MW | 1.24 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.05 MW | 1.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 8.03 MW | 8.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 1.88 MW | 1.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 5.35 MW | 5.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 7.22 MW | 7.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.94 MW | 3.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 9.18 MW | 9.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 5.79 MW | 5.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.96 MW | 0.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.54 MW | 0.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 3.4 MW | 3.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.73 MW | 1.73 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.9 MW | 1.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.61 MW | 3.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 7.0 MW | 7.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 3.64 MW | 3.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.83 MW | 1.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 8.28 MW | 8.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 9.05 MW | 9.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 7.35 MW | 7.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 3.51 MW | 3.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.14 MW | 0.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.09 MW | 1.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.31 MW | 2.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 6.25 MW | 6.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 7.37 MW | 7.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 7.81 MW | 7.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 8.5 MW | 8.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 6.99 MW | 6.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 5.72 MW | 5.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.21 MW | 0.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 15.27 MW | 15.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 71.26 MW | 71.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 2.52 MW | 2.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 3.9 MW | 3.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 19.05 MW | 19.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.91 MW | 1.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 7.63 MW | 7.63 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 21.11 MW | 21.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 10.04 MW | 10.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 4.69 MW | 4.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 28.83 MW | 28.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 19.14 MW | 19.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 4.49 MW | 4.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 9.38 MW | 9.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 6.77 MW | 6.77 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.4 MW | 2.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.81 MW | 1.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 13.78 MW | 13.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.26 MW | 3.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 15.33 MW | 15.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 4.29 MW | 4.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 20.08 MW | 20.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.36 MW | 2.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 3.54 MW | 3.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.18 MW | 0.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.57 MW | 0.57 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.25 MW | 0.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.21 MW | 1.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 5.74 MW | 5.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 9.02 MW | 9.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 5.33 MW | 5.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 3.41 MW | 3.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 5.11 MW | 5.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 12.94 MW | 12.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.5 MW | 0.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 5.09 MW | 5.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 1.15 MW | 1.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.72 MW | 1.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 13.91 MW | 13.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 6.33 MW | 6.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 4.22 MW | 4.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 7.83 MW | 7.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 4.19 MW | 4.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 19.62 MW | 19.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 144.54 MW | 144.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 6.38 MW | 6.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 3.2 MW | 3.2 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 15.0 MW | 15.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 7.59 MW | 7.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.1 MW | 3.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 14.49 MW | 14.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.83 MW | 2.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 13.25 MW | 13.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.78 MW | 0.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 2.69 MW | 2.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 14.56 MW | 14.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 9.64 MW | 9.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 16.46 MW | 16.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 3.35 MW | 3.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 5.02 MW | 5.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.12 MW | 1.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.67 MW | 1.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 251.18 MW | 251.18 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 109.06 MW | 109.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 106.54 MW | 106.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.32 MW | 1.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.6 MW | 0.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.18 MW | 1.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.22 MW | 1.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.99 MW | 0.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.55 MW | 1.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.84 MW | 1.84 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.8 MW | 0.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.8 MW | 1.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.24 MW | 1.24 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 2.01 MW | 2.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.05 MW | 1.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 8.03 MW | 8.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 1.88 MW | 1.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 5.35 MW | 5.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 7.22 MW | 7.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.94 MW | 3.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 9.18 MW | 9.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 5.39 MW | 5.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 5.79 MW | 5.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.96 MW | 0.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.54 MW | 0.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 3.4 MW | 3.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.73 MW | 1.73 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.9 MW | 1.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.61 MW | 3.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 7.0 MW | 7.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 3.64 MW | 3.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.83 MW | 1.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 5.86 MW | 5.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 8.28 MW | 8.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 9.05 MW | 9.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 7.35 MW | 7.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.19 MW | 3.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 3.51 MW | 3.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.38 MW | 2.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.14 MW | 0.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.09 MW | 1.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.31 MW | 2.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 6.25 MW | 6.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 7.37 MW | 7.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 7.81 MW | 7.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 8.5 MW | 8.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 6.99 MW | 6.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 5.72 MW | 5.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.05 MW | 0.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.21 MW | 0.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 15.27 MW | 15.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 71.26 MW | 71.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 2.52 MW | 2.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 3.9 MW | 3.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 19.05 MW | 19.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.91 MW | 1.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 7.63 MW | 7.63 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 5.96 MW | 5.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 21.11 MW | 21.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 10.04 MW | 10.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 4.69 MW | 4.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 28.83 MW | 28.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 19.14 MW | 19.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 4.49 MW | 4.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.4 MW | 1.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 9.38 MW | 9.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 6.77 MW | 6.77 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.12 MW | 4.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.4 MW | 2.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.81 MW | 1.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 13.78 MW | 13.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.26 MW | 3.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 15.33 MW | 15.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 4.29 MW | 4.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 20.08 MW | 20.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.36 MW | 2.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 3.54 MW | 3.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.18 MW | 0.18 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.57 MW | 0.57 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.25 MW | 0.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.21 MW | 1.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 5.74 MW | 5.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 9.02 MW | 9.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 5.33 MW | 5.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 3.41 MW | 3.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 5.11 MW | 5.11 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 12.94 MW | 12.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.5 MW | 0.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.21 MW | 2.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 3.31 MW | 3.31 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 5.09 MW | 5.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 1.15 MW | 1.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.72 MW | 1.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.7 MW | 1.7 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 2.55 MW | 2.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 13.91 MW | 13.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 6.33 MW | 6.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 4.22 MW | 4.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 7.83 MW | 7.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.06 MW | 0.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 4.19 MW | 4.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 19.62 MW | 19.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 9.25 MW | 9.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 144.54 MW | 144.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 6.38 MW | 6.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.4 MW | 0.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 3.2 MW | 3.2 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 15.0 MW | 15.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 11.38 MW | 11.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 7.59 MW | 7.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.1 MW | 3.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 14.49 MW | 14.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.83 MW | 2.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 13.25 MW | 13.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.78 MW | 0.78 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 2.69 MW | 2.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.48 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.72 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 14.56 MW | 14.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 9.64 MW | 9.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 16.46 MW | 16.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 3.35 MW | 3.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 5.02 MW | 5.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.12 MW | 1.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.67 MW | 1.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 251.18 MW | 251.18 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 3.32 MW | 3.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.77 MW | 0.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.79 MW | 0.79 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 1.54 MW | 1.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 1.54 MW | 1.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 4.54 MW | 4.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 6.16 MW | 6.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 6.16 MW | 6.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 6.88 MW | 6.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.01 MW | 2.01 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 13.46 MW | 13.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 1.46 MW | 1.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 4.63 MW | 4.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.92 MW | 37.92 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.09 MW | 1.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.48 MW | 0.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.31 MW | 2.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.15 MW | 2.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 10.05 MW | 10.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C | 50/50 | 8.01 MW | 8.01 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E | 50/50 | 37.46 MW | 37.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C | 50/50 | 5.43 MW | 5.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E | 50/50 | 25.43 MW | 25.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.36 MW | 1.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 | External Queue | 18.04 MW | 18.04 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 3.32 MW | 3.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.77 MW | 0.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.79 MW | 0.79 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 1.54 MW | 1.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 1.54 MW | 1.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 4.54 MW | 4.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 6.16 MW | 6.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 6.16 MW | 6.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 6.88 MW | 6.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.01 MW | 2.01 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 13.46 MW | 13.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 1.46 MW | 1.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 4.63 MW | 4.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 37.92 MW | 37.92 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.09 MW | 1.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.48 MW | 0.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.31 MW | 2.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.15 MW | 2.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 10.05 MW | 10.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C | 50/50 | 8.01 MW | 8.01 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E | 50/50 | 37.46 MW | 37.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C | 50/50 | 5.43 MW | 5.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E | 50/50 | 25.43 MW | 25.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.36 MW | 1.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 | External Queue | 18.04 MW | 18.04 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 274848 | CAMPGROVE;RU | 50/50 | 3.62 MW | 3.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 274849 | CRESCENT ;1U | 50/50 | 0.74 MW | 0.74 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 274851 | PROVIDENC;RU | 50/50 | 0.77 MW | 0.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 274877 | BISHOP HL;1U | 50/50 | 1.8 MW | 1.8 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 274878 | BISHOP HL;2U | 50/50 | 1.8 MW | 1.8 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 293771 | O-035 E | 50/50 | 4.4 MW | 4.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 294401 | BSHIL;1U E | 50/50 | 7.22 MW | 7.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 294410 | BSHIL;2U E | 50/50 | 7.22 MW | 7.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 916211 | Z1-072 E | 50/50 | 6.65 MW | 6.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 925581 | AC1-033 C | 50/50 | 2.36 MW | 2.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 925582 | AC1-033 E | 50/50 | 15.79 MW | 15.79 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 926821 | AC1-168 C O1 | 50/50 | 0.88 MW | 0.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 926822 | AC1-168 E O1 | 50/50 | 5.9 MW | 5.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 927201 | AC1-214 C O1 | 50/50 | 1.41 MW | 1.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 927202 | AC1-214 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 946541 | AF1-318 C O1 | 50/50 | 5.52 MW | 5.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 946542 | AF1-318 E O1 | 50/50 | 25.84 MW | 25.84 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 957751 | AF2-069 C | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 957752 | AF2-069 E | 50/50 | 1.05 MW | 1.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 957761 | AF2-070 C | 50/50 | 0.46 MW | 0.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 957762 | AF2-070 E | 50/50 | 2.23 MW | 2.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 958341 | AF2-128 C O1 | 50/50 | 1.34 MW | 1.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 958342 | AF2-128 E O1 | 50/50 | 6.26 MW | 6.26 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 962721 | AG1-121 C | 50/50 | 7.18 MW | 7.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 962722 | AG1-121 E | 50/50 | 33.59 MW | 33.59 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 965671 | AG1-435 C | 50/50 | 5.44 MW | 5.44 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 965672 | AG1-435 E | 50/50 | 25.45 MW | 25.45 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 990051 | J1200 | External Queue | 2.85 MW | 2.85 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L7411__R-S_+_138-L7405__R-S | 991301 | J1755 | External Queue | 25.12 MW | 25.12 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 274848 | CAMPGROVE;RU | 50/50 | 3.62 MW | 3.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 274849 | CRESCENT ;1U | 50/50 | 0.74 MW | 0.74 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 274851 | PROVIDENC;RU | 50/50 | 0.77 MW | 0.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 274877 | BISHOP HL;1U | 50/50 | 1.8 MW | 1.8 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 274878 | BISHOP HL;2U | 50/50 | 1.8 MW | 1.8 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 293771 | O-035 E | 50/50 | 4.4 MW | 4.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 294401 | BSHIL;1U E | 50/50 | 7.22 MW | 7.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 294410 | BSHIL;2U E | 50/50 | 7.22 MW | 7.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 916211 | Z1-072 E | 50/50 | 6.65 MW | 6.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 925581 | AC1-033 C | 50/50 | 2.36 MW | 2.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 925582 | AC1-033 E | 50/50 | 15.79 MW | 15.79 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 926821 | AC1-168 C O1 | 50/50 | 0.88 MW | 0.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 926822 | AC1-168 E O1 | 50/50 | 5.9 MW | 5.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 927201 | AC1-214 C O1 | 50/50 | 1.41 MW | 1.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 927202 | AC1-214 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 946541 | AF1-318 C O1 | 50/50 | 5.52 MW | 5.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 946542 | AF1-318 E O1 | 50/50 | 25.84 MW | 25.84 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 957751 | AF2-069 C | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 957752 | AF2-069 E | 50/50 | 1.05 MW | 1.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 957761 | AF2-070 C | 50/50 | 0.46 MW | 0.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 957762 | AF2-070 E | 50/50 | 2.23 MW | 2.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 958341 | AF2-128 C O1 | 50/50 | 1.34 MW | 1.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 958342 | AF2-128 E O1 | 50/50 | 6.26 MW | 6.26 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 962721 | AG1-121 C | 50/50 | 7.18 MW | 7.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 962722 | AG1-121 E | 50/50 | 33.59 MW | 33.59 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 965671 | AG1-435 C | 50/50 | 5.44 MW | 5.44 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 965672 | AG1-435 E | 50/50 | 25.45 MW | 25.45 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 990051 | J1200 | External Queue | 2.85 MW | 2.85 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L18706_R-S_+_138-L7405__R-S | 991301 | J1755 | External Queue | 25.12 MW | 25.12 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 274848 | CAMPGROVE;RU | 80/20 | 3.39 MW | 3.39 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 274849 | CRESCENT ;1U | 80/20 | 0.66 MW | 0.66 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 274851 | PROVIDENC;RU | 80/20 | 0.68 MW | 0.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 274877 | BISHOP HL;1U | 80/20 | 1.61 MW | 1.61 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 274878 | BISHOP HL;2U | 80/20 | 1.61 MW | 1.61 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 276156 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 276157 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 276158 | O-029 C | 80/20 | 0.68 MW | 0.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293513 | O-009 C1 | 80/20 | 0.64 MW | 0.64 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293514 | O-009 C2 | 80/20 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293515 | O-009 C3 | 80/20 | 0.36 MW | 0.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293516 | O-009 E1 | 80/20 | 2.27 MW | 2.27 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293517 | O-009 E2 | 80/20 | 1.16 MW | 1.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293518 | O-009 E3 | 80/20 | 1.27 MW | 1.27 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293715 | O-029 E | 80/20 | 2.43 MW | 2.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293716 | O-029 E | 80/20 | 1.33 MW | 1.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293717 | O-029 E | 80/20 | 1.23 MW | 1.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 293771 | O-035 E | 80/20 | 3.9 MW | 3.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 294401 | BSHIL;1U E | 80/20 | 6.43 MW | 6.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 294410 | BSHIL;2U E | 80/20 | 6.43 MW | 6.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 916211 | Z1-072 E | 80/20 | 5.9 MW | 5.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 925581 | AC1-033 C | 80/20 | 2.1 MW | 2.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 925582 | AC1-033 E | 80/20 | 14.05 MW | 14.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 926821 | AC1-168 C O1 | 80/20 | 0.77 MW | 0.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 926822 | AC1-168 E O1 | 80/20 | 5.16 MW | 5.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 927201 | AC1-214 C O1 | 80/20 | 1.25 MW | 1.25 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 927202 | AC1-214 E O1 | 80/20 | 3.98 MW | 3.98 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 946541 | AF1-318 C O1 | 80/20 | 4.86 MW | 4.86 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 946542 | AF1-318 E O1 | 80/20 | 22.73 MW | 22.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 957751 | AF2-069 C | 80/20 | 0.29 MW | 0.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 957752 | AF2-069 E | 80/20 | 0.94 MW | 0.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 957761 | AF2-070 C | 80/20 | 0.41 MW | 0.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 957762 | AF2-070 E | 80/20 | 1.98 MW | 1.98 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 958341 | AF2-128 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 958342 | AF2-128 E O1 | 80/20 | 5.49 MW | 5.49 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 962721 | AG1-121 C | 80/20 | 6.35 MW | 6.35 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 962722 | AG1-121 E | 80/20 | 29.71 MW | 29.71 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 965671 | AG1-435 C | 80/20 | 4.82 MW | 4.82 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 965672 | AG1-435 E | 80/20 | 22.57 MW | 22.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 990051 | J1200 | External Queue | 2.48 MW | 2.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o EXT_348923 4KEWANEE N 138 348974 4KEWANEE S 138 Z | 991301 | J1755 | External Queue | 22.22 MW | 22.22 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 80/20 | 3.15 MW | 3.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 80/20 | 0.69 MW | 0.69 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 80/20 | 0.71 MW | 0.71 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 80/20 | 1.39 MW | 1.39 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 80/20 | 1.39 MW | 1.39 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276156 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293515 | O-009 C3 | 80/20 | 0.32 MW | 0.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293516 | O-009 E1 | 80/20 | 2.05 MW | 2.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293517 | O-009 E2 | 80/20 | 1.04 MW | 1.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293518 | O-009 E3 | 80/20 | 1.15 MW | 1.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293715 | O-029 E | 80/20 | 2.19 MW | 2.19 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293716 | O-029 E | 80/20 | 1.2 MW | 1.2 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293717 | O-029 E | 80/20 | 1.1 MW | 1.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293771 | O-035 E | 80/20 | 4.09 MW | 4.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 294401 | BSHIL;1U E | 80/20 | 5.55 MW | 5.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 294410 | BSHIL;2U E | 80/20 | 5.55 MW | 5.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 916211 | Z1-072 E | 80/20 | 6.2 MW | 6.2 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 925581 | AC1-033 C | 80/20 | 1.81 MW | 1.81 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 925582 | AC1-033 E | 80/20 | 12.13 MW | 12.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 926821 | AC1-168 C O1 | 80/20 | 0.57 MW | 0.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 926822 | AC1-168 E O1 | 80/20 | 3.81 MW | 3.81 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 80/20 | 4.18 MW | 4.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 80/20 | 7.3 MW | 7.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 80/20 | 34.17 MW | 34.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957751 | AF2-069 C | 80/20 | 0.3 MW | 0.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957752 | AF2-069 E | 80/20 | 0.98 MW | 0.98 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957761 | AF2-070 C | 80/20 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957762 | AF2-070 E | 80/20 | 2.08 MW | 2.08 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 80/20 | 1.94 MW | 1.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 80/20 | 9.06 MW | 9.06 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 962721 | AG1-121 C | 80/20 | 5.22 MW | 5.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 962722 | AG1-121 E | 80/20 | 24.4 MW | 24.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 965671 | AG1-435 C | 80/20 | 4.05 MW | 4.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 965672 | AG1-435 E | 80/20 | 18.96 MW | 18.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.78 MW | 1.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 991301 | J1755 | External Queue | 17.96 MW | 17.96 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 3.07 MW | 3.07 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.54 MW | 0.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.55 MW | 0.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 1.32 MW | 1.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 1.32 MW | 1.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.58 MW | 0.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 1.94 MW | 1.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 0.99 MW | 0.99 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.09 MW | 1.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.08 MW | 2.08 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.14 MW | 1.14 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.05 MW | 1.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 3.18 MW | 3.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 5.26 MW | 5.26 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 5.26 MW | 5.26 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 4.81 MW | 4.81 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 1.72 MW | 1.72 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 11.5 MW | 11.5 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.62 MW | 0.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 4.17 MW | 4.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 1.02 MW | 1.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 3.25 MW | 3.25 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 3.94 MW | 3.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 18.43 MW | 18.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.24 MW | 0.24 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.76 MW | 0.76 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 1.62 MW | 1.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.95 MW | 0.95 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 4.44 MW | 4.44 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 5.18 MW | 5.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 24.22 MW | 24.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 3.94 MW | 3.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 18.44 MW | 18.44 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 1.97 MW | 1.97 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 | External Queue | 17.89 MW | 17.89 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 3.23 MW | 3.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.64 MW | 0.64 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.66 MW | 0.66 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 1.46 MW | 1.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 1.46 MW | 1.46 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 293771 | O-035 E | 50/50 | 3.77 MW | 3.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 294401 | BSHIL;1U E | 50/50 | 5.83 MW | 5.83 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 294410 | BSHIL;2U E | 50/50 | 5.83 MW | 5.83 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 916211 | Z1-072 E | 50/50 | 5.71 MW | 5.71 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 925581 | AC1-033 C | 50/50 | 1.9 MW | 1.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 925582 | AC1-033 E | 50/50 | 12.74 MW | 12.74 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 0.98 MW | 0.98 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 6.59 MW | 6.59 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 1.21 MW | 1.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 3.85 MW | 3.85 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 5.43 MW | 5.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 25.4 MW | 25.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 957752 | AF2-069 E | 50/50 | 0.91 MW | 0.91 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 957761 | AF2-070 C | 50/50 | 0.4 MW | 0.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 957762 | AF2-070 E | 50/50 | 1.92 MW | 1.92 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 1.37 MW | 1.37 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 6.4 MW | 6.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 962721 | AG1-121 C | 50/50 | 6.29 MW | 6.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 962722 | AG1-121 E | 50/50 | 29.4 MW | 29.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 965671 | AG1-435 C | 50/50 | 4.59 MW | 4.59 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 965672 | AG1-435 E | 50/50 | 21.51 MW | 21.51 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 990051 | J1200 | External Queue | 2.8 MW | 2.8 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6102___-S_+_138-L7713__R-S-B | 991301 | J1755 | External Queue | 21.64 MW | 21.64 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 274848 | CAMPGROVE;RU | 80/20 | 3.26 MW | 3.26 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 274849 | CRESCENT ;1U | 80/20 | 0.61 MW | 0.61 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 274851 | PROVIDENC;RU | 80/20 | 0.63 MW | 0.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 274877 | BISHOP HL;1U | 80/20 | 1.5 MW | 1.5 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 274878 | BISHOP HL;2U | 80/20 | 1.5 MW | 1.5 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 276156 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 276157 | O-029 C | 80/20 | 0.36 MW | 0.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 276158 | O-029 C | 80/20 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293513 | O-009 C1 | 80/20 | 0.62 MW | 0.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293514 | O-009 C2 | 80/20 | 0.32 MW | 0.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293515 | O-009 C3 | 80/20 | 0.35 MW | 0.35 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293516 | O-009 E1 | 80/20 | 2.21 MW | 2.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293517 | O-009 E2 | 80/20 | 1.12 MW | 1.12 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293518 | O-009 E3 | 80/20 | 1.24 MW | 1.24 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293715 | O-029 E | 80/20 | 2.36 MW | 2.36 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293716 | O-029 E | 80/20 | 1.3 MW | 1.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293717 | O-029 E | 80/20 | 1.19 MW | 1.19 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 293771 | O-035 E | 80/20 | 3.63 MW | 3.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 294401 | BSHIL;1U E | 80/20 | 6.02 MW | 6.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 294410 | BSHIL;2U E | 80/20 | 6.02 MW | 6.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 916211 | Z1-072 E | 80/20 | 5.5 MW | 5.5 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 925581 | AC1-033 C | 80/20 | 1.97 MW | 1.97 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 925582 | AC1-033 E | 80/20 | 13.16 MW | 13.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 926821 | AC1-168 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 926822 | AC1-168 E O1 | 80/20 | 4.72 MW | 4.72 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 927201 | AC1-214 C O1 | 80/20 | 1.17 MW | 1.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 927202 | AC1-214 E O1 | 80/20 | 3.71 MW | 3.71 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 946541 | AF1-318 C O1 | 80/20 | 4.48 MW | 4.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 946542 | AF1-318 E O1 | 80/20 | 20.99 MW | 20.99 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 957751 | AF2-069 C | 80/20 | 0.27 MW | 0.27 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 957752 | AF2-069 E | 80/20 | 0.87 MW | 0.87 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 957761 | AF2-070 C | 80/20 | 0.38 MW | 0.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 957762 | AF2-070 E | 80/20 | 1.85 MW | 1.85 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 958341 | AF2-128 C O1 | 80/20 | 1.08 MW | 1.08 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 958342 | AF2-128 E O1 | 80/20 | 5.05 MW | 5.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 962721 | AG1-121 C | 80/20 | 5.9 MW | 5.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 962722 | AG1-121 E | 80/20 | 27.6 MW | 27.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 965671 | AG1-435 C | 80/20 | 4.49 MW | 4.49 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 965672 | AG1-435 E | 80/20 | 21.04 MW | 21.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 990051 | J1200 | External Queue | 2.23 MW | 2.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7423___-SA | 991301 | J1755 | External Queue | 20.4 MW | 20.4 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 80/20 | 3.15 MW | 3.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 80/20 | 0.69 MW | 0.69 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 80/20 | 0.71 MW | 0.71 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 80/20 | 1.39 MW | 1.39 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 80/20 | 1.39 MW | 1.39 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 276156 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293515 | O-009 C3 | 80/20 | 0.32 MW | 0.32 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293516 | O-009 E1 | 80/20 | 2.05 MW | 2.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293517 | O-009 E2 | 80/20 | 1.04 MW | 1.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293518 | O-009 E3 | 80/20 | 1.15 MW | 1.15 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293715 | O-029 E | 80/20 | 2.19 MW | 2.19 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293716 | O-029 E | 80/20 | 1.2 MW | 1.2 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293717 | O-029 E | 80/20 | 1.1 MW | 1.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 293771 | O-035 E | 80/20 | 4.09 MW | 4.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 294401 | BSHIL;1U E | 80/20 | 5.55 MW | 5.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 294410 | BSHIL;2U E | 80/20 | 5.55 MW | 5.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 916211 | Z1-072 E | 80/20 | 6.2 MW | 6.2 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 925581 | AC1-033 C | 80/20 | 1.81 MW | 1.81 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 925582 | AC1-033 E | 80/20 | 12.13 MW | 12.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 926821 | AC1-168 C O1 | 80/20 | 0.57 MW | 0.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 926822 | AC1-168 E O1 | 80/20 | 3.81 MW | 3.81 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 80/20 | 4.18 MW | 4.18 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 80/20 | 7.3 MW | 7.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 80/20 | 34.17 MW | 34.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957751 | AF2-069 C | 80/20 | 0.3 MW | 0.3 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957752 | AF2-069 E | 80/20 | 0.98 MW | 0.98 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957761 | AF2-070 C | 80/20 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 957762 | AF2-070 E | 80/20 | 2.08 MW | 2.08 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 80/20 | 3.1 MW | 3.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 962721 | AG1-121 C | 80/20 | 5.22 MW | 5.22 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 962722 | AG1-121 E | 80/20 | 24.4 MW | 24.4 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 965671 | AG1-435 C | 80/20 | 4.05 MW | 4.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 965672 | AG1-435 E | 80/20 | 18.96 MW | 18.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.78 MW | 1.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-B | 991301 | J1755 | External Queue | 17.96 MW | 17.96 MW |
| Details for MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.56 MW | 0.56 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.39 MW | 0.39 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.4 MW | 0.4 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.49 MW | 0.49 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.49 MW | 0.49 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 2.29 MW | 2.29 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 1.96 MW | 1.96 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 1.96 MW | 1.96 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 3.46 MW | 3.46 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.64 MW | 0.64 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.3 MW | 4.3 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 5.71 MW | 5.71 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.17 MW | 6.17 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 28.87 MW | 28.87 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.17 MW | 0.17 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.55 MW | 0.55 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.24 MW | 0.24 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 1.16 MW | 1.16 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 8.18 MW | 8.18 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 3.65 MW | 3.65 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 17.09 MW | 17.09 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 2.19 MW | 2.19 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 10.27 MW | 10.27 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 966093 | AG1-478 BAT | 80/20 | 0.52 MW | 0.52 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 2.77 MW | 2.77 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 | External Queue | 12.74 MW | 12.74 MW |
| Details for MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274847 | GR RIDGE ;BU | 80/20 | 1.67 MW | 1.67 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274848 | CAMPGROVE;RU | 80/20 | 0.67 MW | 0.67 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274849 | CRESCENT ;1U | 80/20 | 0.45 MW | 0.45 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274851 | PROVIDENC;RU | 80/20 | 0.46 MW | 0.46 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274871 | GR RIDGE ;2U | 80/20 | 0.62 MW | 0.62 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274877 | BISHOP HL;1U | 80/20 | 0.58 MW | 0.58 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274878 | BISHOP HL;2U | 80/20 | 0.58 MW | 0.58 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293061 | N-015 E | 80/20 | 7.33 MW | 7.33 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293771 | O-035 E | 80/20 | 2.65 MW | 2.65 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294392 | P-010 E | 80/20 | 9.3 MW | 9.3 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294401 | BSHIL;1U E | 80/20 | 2.34 MW | 2.34 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294410 | BSHIL;2U E | 80/20 | 2.34 MW | 2.34 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 916211 | Z1-072 E | 80/20 | 4.01 MW | 4.01 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925581 | AC1-033 C | 80/20 | 0.77 MW | 0.77 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925582 | AC1-033 E | 80/20 | 5.13 MW | 5.13 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926821 | AC1-168 C O1 | 80/20 | 1.16 MW | 1.16 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926822 | AC1-168 E O1 | 80/20 | 7.77 MW | 7.77 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927201 | AC1-214 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927202 | AC1-214 E O1 | 80/20 | 2.7 MW | 2.7 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946541 | AF1-318 C O1 | 80/20 | 7.01 MW | 7.01 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946542 | AF1-318 E O1 | 80/20 | 32.83 MW | 32.83 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957751 | AF2-069 C | 80/20 | 0.2 MW | 0.2 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957752 | AF2-069 E | 80/20 | 0.64 MW | 0.64 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957761 | AF2-070 C | 80/20 | 0.28 MW | 0.28 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957762 | AF2-070 E | 80/20 | 1.35 MW | 1.35 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958341 | AF2-128 C O1 | 80/20 | 1.98 MW | 1.98 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958342 | AF2-128 E O1 | 80/20 | 9.29 MW | 9.29 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962721 | AG1-121 C | 80/20 | 4.43 MW | 4.43 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962722 | AG1-121 E | 80/20 | 20.71 MW | 20.71 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965671 | AG1-435 C | 80/20 | 2.64 MW | 2.64 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965672 | AG1-435 E | 80/20 | 12.38 MW | 12.38 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 966093 | AG1-478 BAT | 80/20 | 0.52 MW | 0.52 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 990051 | J1200 | External Queue | 3.35 MW | 3.35 MW |
| MAZON ; R-CHANNAHON; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 991301 | J1755 | External Queue | 15.34 MW | 15.34 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 85.91 MW | 85.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 80.36 MW | 80.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.46 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.32 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 0.9 MW | 0.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 0.75 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.5 MW | 0.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 3.15 MW | 3.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.74 MW | 0.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.38 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 1.42 MW | 1.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 0.92 MW | 0.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 1.24 MW | 1.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 0.77 MW | 0.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.76 MW | 0.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 4.96 MW | 4.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.43 MW | 0.43 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 5.67 MW | 5.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 3.0 MW | 3.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 6.98 MW | 6.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 3.97 MW | 3.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 4.5 MW | 4.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 0.73 MW | 0.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.41 MW | 0.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 1.32 MW | 1.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 1.46 MW | 1.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 6.4 MW | 6.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 1.4 MW | 1.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 1.82 MW | 1.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 4.25 MW | 4.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 6.13 MW | 6.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 5.72 MW | 5.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 2.45 MW | 2.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 2.68 MW | 2.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 1.81 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 0.84 MW | 0.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 2.76 MW | 2.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 1.76 MW | 1.76 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 4.59 MW | 4.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 5.08 MW | 5.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 0.86 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 5.74 MW | 5.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 6.3 MW | 6.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 0.8 MW | 0.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 5.36 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 4.4 MW | 4.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 1.86 MW | 1.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 11.08 MW | 11.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 51.73 MW | 51.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 11.78 MW | 11.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 1.45 MW | 1.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 5.81 MW | 5.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 4.67 MW | 4.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 7.67 MW | 7.67 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 3.35 MW | 3.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 20.56 MW | 20.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 13.8 MW | 13.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 3.3 MW | 3.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.03 MW | 1.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 5.31 MW | 5.31 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.48 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 2.94 MW | 2.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 2.75 MW | 2.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 1.83 MW | 1.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 1.38 MW | 1.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 2.49 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 11.71 MW | 11.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 15.35 MW | 15.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 1.8 MW | 1.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 2.71 MW | 2.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 0.78 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.39 MW | 0.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.58 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.44 MW | 0.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.19 MW | 0.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 0.93 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 8.0 MW | 8.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 2.6 MW | 2.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 3.91 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 3.44 MW | 3.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 9.89 MW | 9.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.02 MW | 2.02 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 3.03 MW | 3.03 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 0.71 MW | 0.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 1.25 MW | 1.25 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 1.88 MW | 1.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 10.64 MW | 10.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 4.84 MW | 4.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 3.23 MW | 3.23 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 8.91 MW | 8.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 3.21 MW | 3.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 15.04 MW | 15.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 34.53 MW | 34.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 4.69 MW | 4.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.29 MW | 0.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 11.07 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 8.4 MW | 8.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 5.6 MW | 5.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 2.37 MW | 2.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 11.09 MW | 11.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 2.17 MW | 2.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 10.16 MW | 10.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.36 MW | 0.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 1.12 MW | 1.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 1.68 MW | 1.68 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.37 MW | 0.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.55 MW | 0.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 5.26 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 7.38 MW | 7.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 12.59 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 2.56 MW | 2.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 3.84 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 0.85 MW | 0.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 1.28 MW | 1.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 189.4 MW | 189.4 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274658 | DRESDEN ;2U | Adder | 48.02 MW | 40.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274659 | DRESDEN ;3U | Adder | 52.33 MW | 44.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 1.73 MW | 1.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 2.74 MW | 2.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276170 | Z1-108 E | Adder | 1.34 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 4.6 MW | 4.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 7.64 MW | 7.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 7.64 MW | 7.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 18.35 MW | 18.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.0 MW | 2.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 7.75 MW | 7.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 920272 | AA2-123 E | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 1.45 MW | 1.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 18.89 MW | 18.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 5.91 MW | 5.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 21.19 MW | 21.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.64 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934721 | AD1-100 C | Adder | 6.39 MW | 5.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934722 | AD1-100 E | Adder | 29.8 MW | 25.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 6.16 MW | 6.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937001 | AD2-134 C | Adder | 1.06 MW | 0.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937002 | AD2-134 E | Adder | 4.25 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938851 | AE1-113 C O1 | Adder | 3.47 MW | 2.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938852 | AE1-113 E O1 | Adder | 12.29 MW | 10.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 1.85 MW | 1.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 6.3 MW | 5.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939321 | AE1-163 C O1 | Adder | 2.51 MW | 2.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939322 | AE1-163 E O1 | Adder | 15.4 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 2.67 MW | 2.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 12.51 MW | 10.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.57 MW | 5.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 11.62 MW | 11.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942421 | AE2-255 C O1 | Adder | 1.31 MW | 1.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942422 | AE2-255 E O1 | Adder | 3.94 MW | 3.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942651 | AE2-281 C O1 | Adder | 0.36 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942652 | AE2-281 E O1 | Adder | 2.2 MW | 1.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 943801 | AF1-048 C | Adder | 1.87 MW | 1.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 943802 | AF1-048 E | Adder | 1.24 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 5.41 MW | 5.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 25.32 MW | 25.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.98 MW | 11.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.36 MW | 2.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 11.05 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946501 | AF1-314 C | Adder | 1.96 MW | 1.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946502 | AF1-314 E | Adder | 9.22 MW | 7.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 16.48 MW | 14.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957331 | AF2-027 C | Adder | 1.13 MW | 0.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957332 | AF2-027 E | Adder | 1.69 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957401 | AF2-034 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957402 | AF2-034 E | Adder | 0.31 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.01 MW | 0.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 0.93 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 4.36 MW | 3.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.23 MW | 1.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959101 | AF2-201 C O1 | Adder | 2.71 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959102 | AF2-201 E O1 | Adder | 7.78 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959351 | AF2-226 C | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959352 | AF2-226 E | Adder | 1.75 MW | 1.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 1.97 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960281 | AF2-319 C | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960282 | AF2-319 E | Adder | 1.75 MW | 1.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960381 | AF2-329 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 9.4 MW | 7.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.28 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.85 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C | Adder | 3.45 MW | 2.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E | Adder | 16.12 MW | 13.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 21.19 MW | 21.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 9.04 MW | 9.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C O1 | 50/50 | 5.76 MW | 5.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E O1 | 50/50 | 26.99 MW | 26.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 O1 | 50/50 | 20.47 MW | 20.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 O1 | 50/50 | 20.47 MW | 20.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 O1 | 50/50 | 13.65 MW | 13.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965661 | AG1-434 C | Adder | 1.85 MW | 1.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965662 | AG1-434 E | Adder | 8.66 MW | 7.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C | Adder | 2.35 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E | Adder | 11.0 MW | 9.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.11 MW | 3.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966091 | AG1-478 C | Adder | 0.2 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966092 | AG1-478 E | Adder | 0.31 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966441 | AG1-513 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966442 | AG1-513 E | Adder | 0.32 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919221 | AA1-146 | Adder | 11.27 MW | 9.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965061 | AG1-371 C | Adder | 1.91 MW | 1.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965062 | AG1-371 E | Adder | 2.86 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965081 | AG1-373 C | Adder | 0.64 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965082 | AG1-373 E | Adder | 0.95 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 32.07 MW | 32.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 14.04 MW | 14.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 280.83 MW | 280.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945351 | AF1-200 FTIR | Adder | 112.21 MW | 95.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.89 MW | 6.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 106.62 MW | 106.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990351 | J1289 C | External Queue | 2.01 MW | 2.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.02 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 15.8 MW | 15.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955711 | J1055 C | External Queue | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955712 | J1055 E | External Queue | 6.51 MW | 6.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956281 | J1115 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956282 | J1115 E | External Queue | 15.71 MW | 15.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991236 | J1676 | External Queue | 24.78 MW | 24.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 | External Queue | 19.26 MW | 19.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991276 | J1725 | External Queue | 5.14 MW | 5.14 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274658 | DRESDEN ;2U | 80/20 | 49.8 MW | 49.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274659 | DRESDEN ;3U | 80/20 | 53.84 MW | 53.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274847 | GR RIDGE ;BU | 80/20 | 0.61 MW | 0.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274848 | CAMPGROVE;RU | 80/20 | 0.91 MW | 0.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274850 | MENDOTA H;RU | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274853 | TWINGROVE;U1 | 80/20 | 1.66 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274854 | TWINGROVE;U2 | 80/20 | 1.71 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274855 | GSG-6 ;RU | 80/20 | 0.56 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274856 | ECOGROVE ;U1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274857 | BIG SKY ;U1 | 80/20 | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274858 | BIG SKY ;U2 | 80/20 | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274859 | EASYR;U1 E | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274860 | EASYR;U2 E | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274861 | TOP CROP ;1U | 80/20 | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274862 | TOP CROP ;2U | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274863 | CAYUGA RI;1U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274864 | CAYUGA RI;2U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274871 | GR RIDGE ;2U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274872 | LEE DEKAL;1U | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274879 | MINONK ;1U | 80/20 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274880 | RADFORD R;1U | 80/20 | 2.7 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274889 | BRIGHTSTK;1U | 80/20 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274891 | OTTER CRK;1U | 80/20 | 0.54 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276156 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276157 | O-029 C | 80/20 | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276158 | O-029 C | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276615 | W2-048 GEN | 80/20 | 4.54 MW | 4.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276621 | X2-022 GEN | 80/20 | 12.91 MW | 12.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290021 | O50 E | 80/20 | 4.29 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290051 | GSG-6; E | 80/20 | 2.25 MW | 2.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290108 | LEEDK;1U E | 80/20 | 4.93 MW | 4.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290261 | S-027 E | 80/20 | 7.58 MW | 7.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290265 | S-028 E | 80/20 | 7.58 MW | 7.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293061 | N-015 E | 80/20 | 2.66 MW | 2.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293513 | O-009 C1 | 80/20 | 0.7 MW | 0.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293514 | O-009 C2 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293515 | O-009 C3 | 80/20 | 0.39 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293516 | O-009 E1 | 80/20 | 2.49 MW | 2.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293517 | O-009 E2 | 80/20 | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293518 | O-009 E3 | 80/20 | 1.39 MW | 1.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293644 | O22 E1 | 80/20 | 1.97 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293645 | O22 E2 | 80/20 | 3.81 MW | 3.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293715 | O-029 E | 80/20 | 2.66 MW | 2.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293716 | O-029 E | 80/20 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293717 | O-029 E | 80/20 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293771 | O-035 E | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293777 | CAYUG;1U E | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293778 | CAYUG;2U E | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293798 | W4-005 E | 80/20 | 18.07 MW | 18.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294392 | P-010 E | 80/20 | 3.38 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294401 | BSHIL;1U E | 80/20 | 2.71 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294410 | BSHIL;2U E | 80/20 | 2.71 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294763 | P-046 E | 80/20 | 2.15 MW | 2.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295108 | WESTBROOK C | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295109 | WESTBROOK E | 80/20 | 1.36 MW | 1.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295111 | SUBLETTE E | 80/20 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 916211 | Z1-072 E | 80/20 | 3.02 MW | 3.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 916221 | Z1-073 E | 80/20 | 1.32 MW | 1.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 917502 | Z2-087 E | 80/20 | 7.7 MW | 7.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 918052 | AA1-018 E OP | 80/20 | 3.58 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924041 | AB2-047 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924042 | AB2-047 E O1 | 80/20 | 9.63 MW | 9.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924261 | AB2-070 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924262 | AB2-070 E O1 | 80/20 | 18.61 MW | 18.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925582 | AC1-033 E | 80/20 | 5.95 MW | 5.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925771 | AC1-053 C | 80/20 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925772 | AC1-053 E | 80/20 | 20.88 MW | 20.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 926821 | AC1-168 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 926822 | AC1-168 E O1 | 80/20 | 4.34 MW | 4.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 927201 | AC1-214 C O1 | 80/20 | 0.64 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 927202 | AC1-214 E O1 | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934432 | AD1-067 E | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934721 | AD1-100 C | 80/20 | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934722 | AD1-100 E | 80/20 | 30.89 MW | 30.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 935141 | AD1-148 | 80/20 | 6.07 MW | 6.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 937001 | AD2-134 C | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 937002 | AD2-134 E | 80/20 | 4.35 MW | 4.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938851 | AE1-113 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938852 | AE1-113 E O1 | 80/20 | 12.55 MW | 12.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938861 | AE1-114 C O1 | 80/20 | 1.88 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938862 | AE1-114 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939321 | AE1-163 C O1 | 80/20 | 2.57 MW | 2.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939322 | AE1-163 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939401 | AE1-172 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939402 | AE1-172 E O1 | 80/20 | 12.67 MW | 12.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 941731 | AE2-173 O1 | 80/20 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942111 | AE2-223 C | 80/20 | 1.73 MW | 1.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942112 | AE2-223 E | 80/20 | 11.55 MW | 11.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942421 | AE2-255 C O1 | 80/20 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942422 | AE2-255 E O1 | 80/20 | 4.02 MW | 4.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942651 | AE2-281 C O1 | 80/20 | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942652 | AE2-281 E O1 | 80/20 | 2.25 MW | 2.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 943801 | AF1-048 C | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 943802 | AF1-048 E | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944221 | AF1-090 C O1 | 80/20 | 5.32 MW | 5.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944222 | AF1-090 E O1 | 80/20 | 24.9 MW | 24.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 945871 | AF1-252 O1 | 80/20 | 11.79 MW | 11.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 945881 | AF1-253 | 80/20 | 8.16 MW | 8.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946161 | AF1-281 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946162 | AF1-281 E O1 | 80/20 | 1.21 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946321 | AF1-296 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946322 | AF1-296 E O1 | 80/20 | 11.14 MW | 11.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946501 | AF1-314 C | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946502 | AF1-314 E | 80/20 | 9.4 MW | 9.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946541 | AF1-318 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946542 | AF1-318 E O1 | 80/20 | 16.59 MW | 16.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957331 | AF2-027 C | 80/20 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957332 | AF2-027 E | 80/20 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957401 | AF2-034 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957402 | AF2-034 E | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957762 | AF2-070 E | 80/20 | 1.02 MW | 1.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958341 | AF2-128 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958342 | AF2-128 E O1 | 80/20 | 4.39 MW | 4.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958921 | AF2-183 C | 80/20 | 2.27 MW | 2.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958922 | AF2-183 E | 80/20 | 3.4 MW | 3.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959101 | AF2-201 C O1 | 80/20 | 2.76 MW | 2.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959102 | AF2-201 E O1 | 80/20 | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959351 | AF2-226 C | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959352 | AF2-226 E | 80/20 | 1.81 MW | 1.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959611 | AF2-252 C | 80/20 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959612 | AF2-252 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960141 | AF2-305 | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960261 | AF2-317 | 80/20 | 1.94 MW | 1.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960281 | AF2-319 C | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960282 | AF2-319 E | 80/20 | 1.81 MW | 1.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960381 | AF2-329 | 80/20 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960611 | AF2-352 C | 80/20 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960612 | AF2-352 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961011 | AF2-392 C O1 | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961012 | AF2-392 E O1 | 80/20 | 9.54 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961021 | AF2-393 O1 | 80/20 | 4.34 MW | 4.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961031 | AF2-394 O1 | 80/20 | 2.89 MW | 2.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962721 | AG1-121 C | 80/20 | 3.47 MW | 3.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962722 | AG1-121 E | 80/20 | 16.23 MW | 16.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 963831 | AG1-236 C | 80/20 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 963832 | AG1-236 E | 80/20 | 20.88 MW | 20.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965092 | AG1-374 E | 80/20 | 8.97 MW | 8.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965331 | AG1-398 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965341 | AG1-399 C O1 | 80/20 | 5.69 MW | 5.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965342 | AG1-399 E O1 | 80/20 | 26.65 MW | 26.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965351 | AG1-400 O1 | 80/20 | 20.22 MW | 20.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965371 | AG1-402 O1 | 80/20 | 20.22 MW | 20.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965391 | AG1-404 O1 | 80/20 | 13.48 MW | 13.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965661 | AG1-434 C | 80/20 | 1.89 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965662 | AG1-434 E | 80/20 | 8.83 MW | 8.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965671 | AG1-435 C | 80/20 | 2.37 MW | 2.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965672 | AG1-435 E | 80/20 | 11.08 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965911 | AG1-460 C | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965912 | AG1-460 E | 80/20 | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966091 | AG1-478 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966092 | AG1-478 E | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966441 | AG1-513 C | 80/20 | 0.22 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966442 | AG1-513 E | 80/20 | 0.33 MW | 0.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966821 | AG1-553 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966822 | AG1-553 E O1 | 80/20 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 919221 | AA1-146 | 80/20 | 11.43 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957382 | AF2-032 E | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965061 | AG1-371 C | 80/20 | 1.95 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965062 | AG1-371 E | 80/20 | 2.93 MW | 2.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965081 | AG1-373 C | 80/20 | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965082 | AG1-373 E | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 941343 | AE2-130 BAT | 80/20 | 30.06 MW | 30.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942602 | AE2-276 BAT | 80/20 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944202 | AF1-088 FTWR | 80/20 | 261.98 MW | 261.98 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274847 | GR RIDGE ;BU | 80/20 | 1.91 MW | 1.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274848 | CAMPGROVE;RU | 80/20 | 0.76 MW | 0.76 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274849 | CRESCENT ;1U | 80/20 | 0.51 MW | 0.51 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274851 | PROVIDENC;RU | 80/20 | 0.53 MW | 0.53 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274871 | GR RIDGE ;2U | 80/20 | 0.71 MW | 0.71 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274877 | BISHOP HL;1U | 80/20 | 0.67 MW | 0.67 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274878 | BISHOP HL;2U | 80/20 | 0.67 MW | 0.67 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293061 | N-015 E | 80/20 | 8.35 MW | 8.35 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293771 | O-035 E | 80/20 | 3.02 MW | 3.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294392 | P-010 E | 80/20 | 10.6 MW | 10.6 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294401 | BSHIL;1U E | 80/20 | 2.68 MW | 2.68 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294410 | BSHIL;2U E | 80/20 | 2.68 MW | 2.68 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 916211 | Z1-072 E | 80/20 | 4.58 MW | 4.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925582 | AC1-033 E | 80/20 | 5.87 MW | 5.87 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926821 | AC1-168 C O1 | 80/20 | 1.32 MW | 1.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926822 | AC1-168 E O1 | 80/20 | 8.86 MW | 8.86 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927201 | AC1-214 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927202 | AC1-214 E O1 | 80/20 | 3.08 MW | 3.08 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946541 | AF1-318 C O1 | 80/20 | 7.99 MW | 7.99 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946542 | AF1-318 E O1 | 80/20 | 37.4 MW | 37.4 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957751 | AF2-069 C | 80/20 | 0.23 MW | 0.23 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957752 | AF2-069 E | 80/20 | 0.72 MW | 0.72 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957761 | AF2-070 C | 80/20 | 0.32 MW | 0.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957762 | AF2-070 E | 80/20 | 1.54 MW | 1.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958341 | AF2-128 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958342 | AF2-128 E O1 | 80/20 | 10.58 MW | 10.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962721 | AG1-121 C | 80/20 | 5.05 MW | 5.05 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962722 | AG1-121 E | 80/20 | 23.64 MW | 23.64 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965671 | AG1-435 C | 80/20 | 3.02 MW | 3.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965672 | AG1-435 E | 80/20 | 14.14 MW | 14.14 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 990051 | J1200 | External Queue | 3.81 MW | 3.81 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 991301 | J1755 | External Queue | 17.47 MW | 17.47 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274847 | GR RIDGE ;BU | 50/50 | 1.9 MW | 1.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274849 | CRESCENT ;1U | 50/50 | 0.51 MW | 0.51 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274851 | PROVIDENC;RU | 50/50 | 0.52 MW | 0.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274871 | GR RIDGE ;2U | 50/50 | 0.71 MW | 0.71 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293061 | N-015 E | 50/50 | 8.32 MW | 8.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293771 | O-035 E | 50/50 | 3.01 MW | 3.01 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294392 | P-010 E | 50/50 | 10.57 MW | 10.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 916211 | Z1-072 E | 50/50 | 4.56 MW | 4.56 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925581 | AC1-033 C | Adder | 0.87 MW | 0.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925582 | AC1-033 E | Adder | 5.84 MW | 4.97 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926821 | AC1-168 C O1 | 50/50 | 1.32 MW | 1.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926822 | AC1-168 E O1 | 50/50 | 8.83 MW | 8.83 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927201 | AC1-214 C O1 | 50/50 | 0.97 MW | 0.97 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927202 | AC1-214 E O1 | 50/50 | 3.07 MW | 3.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946541 | AF1-318 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946542 | AF1-318 E O1 | 50/50 | 37.28 MW | 37.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957751 | AF2-069 C | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957752 | AF2-069 E | 50/50 | 0.72 MW | 0.72 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957761 | AF2-070 C | 50/50 | 0.32 MW | 0.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957762 | AF2-070 E | 50/50 | 1.53 MW | 1.53 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958341 | AF2-128 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958342 | AF2-128 E O1 | 50/50 | 10.54 MW | 10.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962721 | AG1-121 C | 50/50 | 5.03 MW | 5.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962722 | AG1-121 E | 50/50 | 23.55 MW | 23.55 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965671 | AG1-435 C | 50/50 | 3.01 MW | 3.01 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965672 | AG1-435 E | 50/50 | 14.09 MW | 14.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990051 | J1200 | External Queue | 3.8 MW | 3.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991301 | J1755 | External Queue | 17.42 MW | 17.42 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 1.9 MW | 1.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.51 MW | 0.51 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.52 MW | 0.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.71 MW | 0.71 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 8.32 MW | 8.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 3.01 MW | 3.01 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 10.57 MW | 10.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 4.56 MW | 4.56 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 0.87 MW | 0.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 5.84 MW | 4.97 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.32 MW | 1.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 8.83 MW | 8.83 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.97 MW | 0.97 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 3.07 MW | 3.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 37.28 MW | 37.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.72 MW | 0.72 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.32 MW | 0.32 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.53 MW | 1.53 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 10.54 MW | 10.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C | 50/50 | 5.03 MW | 5.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E | 50/50 | 23.55 MW | 23.55 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C | 50/50 | 3.01 MW | 3.01 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E | 50/50 | 14.09 MW | 14.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.8 MW | 3.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 | External Queue | 17.42 MW | 17.42 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.63 MW | 0.63 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.45 MW | 0.45 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 2.56 MW | 2.56 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.19 MW | 2.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.19 MW | 2.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 3.88 MW | 3.88 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.81 MW | 4.81 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 6.22 MW | 6.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 2.61 MW | 2.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.91 MW | 6.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 32.33 MW | 32.33 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.96 MW | 1.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 9.17 MW | 9.17 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 4.06 MW | 4.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 19.01 MW | 19.01 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 2.44 MW | 2.44 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 11.44 MW | 11.44 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 3.07 MW | 3.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 | External Queue | 14.14 MW | 14.14 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274847 | GR RIDGE ;BU | 80/20 | 1.91 MW | 1.91 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274848 | CAMPGROVE;RU | 80/20 | 0.76 MW | 0.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274849 | CRESCENT ;1U | 80/20 | 0.51 MW | 0.51 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274851 | PROVIDENC;RU | 80/20 | 0.53 MW | 0.53 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274871 | GR RIDGE ;2U | 80/20 | 0.71 MW | 0.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274877 | BISHOP HL;1U | 80/20 | 0.67 MW | 0.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 274878 | BISHOP HL;2U | 80/20 | 0.67 MW | 0.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293061 | N-015 E | 80/20 | 8.35 MW | 8.35 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 293771 | O-035 E | 80/20 | 3.02 MW | 3.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294392 | P-010 E | 80/20 | 10.6 MW | 10.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294401 | BSHIL;1U E | 80/20 | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 294410 | BSHIL;2U E | 80/20 | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 916211 | Z1-072 E | 80/20 | 4.58 MW | 4.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 925582 | AC1-033 E | 80/20 | 5.87 MW | 5.87 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926821 | AC1-168 C O1 | 80/20 | 1.32 MW | 1.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 926822 | AC1-168 E O1 | 80/20 | 8.86 MW | 8.86 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927201 | AC1-214 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 927202 | AC1-214 E O1 | 80/20 | 3.08 MW | 3.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946541 | AF1-318 C O1 | 80/20 | 7.99 MW | 7.99 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 946542 | AF1-318 E O1 | 80/20 | 37.4 MW | 37.4 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957751 | AF2-069 C | 80/20 | 0.23 MW | 0.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957752 | AF2-069 E | 80/20 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957761 | AF2-070 C | 80/20 | 0.32 MW | 0.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 957762 | AF2-070 E | 80/20 | 1.54 MW | 1.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958341 | AF2-128 C O1 | 80/20 | 2.26 MW | 2.26 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 958342 | AF2-128 E O1 | 80/20 | 10.58 MW | 10.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962721 | AG1-121 C | 80/20 | 5.05 MW | 5.05 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 962722 | AG1-121 E | 80/20 | 23.64 MW | 23.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965671 | AG1-435 C | 80/20 | 3.02 MW | 3.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 965672 | AG1-435 E | 80/20 | 14.14 MW | 14.14 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 990051 | J1200 | External Queue | 3.81 MW | 3.81 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L0112__B-S | 991301 | J1755 | External Queue | 17.47 MW | 17.47 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 1.9 MW | 1.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.51 MW | 0.51 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.52 MW | 0.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.71 MW | 0.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 8.32 MW | 8.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 3.01 MW | 3.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 10.57 MW | 10.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 4.56 MW | 4.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 0.87 MW | 0.74 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 5.84 MW | 4.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.32 MW | 1.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 8.83 MW | 8.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.97 MW | 0.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 3.07 MW | 3.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 37.28 MW | 37.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.22 MW | 0.22 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.32 MW | 0.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.53 MW | 1.53 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 10.54 MW | 10.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C | 50/50 | 5.03 MW | 5.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E | 50/50 | 23.55 MW | 23.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C | 50/50 | 3.01 MW | 3.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E | 50/50 | 14.09 MW | 14.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.8 MW | 3.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 | External Queue | 17.42 MW | 17.42 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274847 | GR RIDGE ;BU | 50/50 | 1.9 MW | 1.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274849 | CRESCENT ;1U | 50/50 | 0.51 MW | 0.51 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274851 | PROVIDENC;RU | 50/50 | 0.52 MW | 0.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274871 | GR RIDGE ;2U | 50/50 | 0.71 MW | 0.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293061 | N-015 E | 50/50 | 8.32 MW | 8.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293771 | O-035 E | 50/50 | 3.01 MW | 3.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294392 | P-010 E | 50/50 | 10.57 MW | 10.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 916211 | Z1-072 E | 50/50 | 4.56 MW | 4.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925581 | AC1-033 C | Adder | 0.87 MW | 0.74 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925582 | AC1-033 E | Adder | 5.84 MW | 4.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926821 | AC1-168 C O1 | 50/50 | 1.32 MW | 1.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926822 | AC1-168 E O1 | 50/50 | 8.83 MW | 8.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927201 | AC1-214 C O1 | 50/50 | 0.97 MW | 0.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927202 | AC1-214 E O1 | 50/50 | 3.07 MW | 3.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946541 | AF1-318 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946542 | AF1-318 E O1 | 50/50 | 37.28 MW | 37.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957751 | AF2-069 C | 50/50 | 0.22 MW | 0.22 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957752 | AF2-069 E | 50/50 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957761 | AF2-070 C | 50/50 | 0.32 MW | 0.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957762 | AF2-070 E | 50/50 | 1.53 MW | 1.53 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958341 | AF2-128 C O1 | 50/50 | 2.25 MW | 2.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958342 | AF2-128 E O1 | 50/50 | 10.54 MW | 10.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962721 | AG1-121 C | 50/50 | 5.03 MW | 5.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962722 | AG1-121 E | 50/50 | 23.55 MW | 23.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965671 | AG1-435 C | 50/50 | 3.01 MW | 3.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965672 | AG1-435 E | 50/50 | 14.09 MW | 14.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990051 | J1200 | External Queue | 3.8 MW | 3.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991301 | J1755 | External Queue | 17.42 MW | 17.42 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.63 MW | 0.63 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.43 MW | 0.43 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.45 MW | 0.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 2.56 MW | 2.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.19 MW | 2.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.19 MW | 2.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 3.88 MW | 3.88 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.81 MW | 4.81 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 6.22 MW | 6.22 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.82 MW | 0.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 2.61 MW | 2.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.91 MW | 6.91 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 32.33 MW | 32.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.61 MW | 0.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 1.3 MW | 1.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.96 MW | 1.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 9.17 MW | 9.17 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 4.06 MW | 4.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 19.01 MW | 19.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 2.44 MW | 2.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 11.44 MW | 11.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 3.07 MW | 3.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 | External Queue | 14.14 MW | 14.14 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 274849 | CRESCENT ;1U | 80/20 | 0.84 MW | 0.84 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 274851 | PROVIDENC;RU | 80/20 | 0.86 MW | 0.86 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 274877 | BISHOP HL;1U | 80/20 | 0.45 MW | 0.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 274878 | BISHOP HL;2U | 80/20 | 0.45 MW | 0.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 293771 | O-035 E | 80/20 | 4.95 MW | 4.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 294401 | BSHIL;1U E | 80/20 | 1.8 MW | 1.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 294410 | BSHIL;2U E | 80/20 | 1.8 MW | 1.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 916211 | Z1-072 E | 80/20 | 7.5 MW | 7.5 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 925581 | AC1-033 C | 80/20 | 0.59 MW | 0.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 925582 | AC1-033 E | 80/20 | 3.95 MW | 3.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 926821 | AC1-168 C O1 | 80/20 | 1.0 MW | 1.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 926822 | AC1-168 E O1 | 80/20 | 6.69 MW | 6.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 927201 | AC1-214 C O1 | 80/20 | 1.59 MW | 1.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 927202 | AC1-214 E O1 | 80/20 | 5.05 MW | 5.05 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 946541 | AF1-318 C O1 | 80/20 | 8.83 MW | 8.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 946542 | AF1-318 E O1 | 80/20 | 41.35 MW | 41.35 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 957751 | AF2-069 C | 80/20 | 0.37 MW | 0.37 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 957752 | AF2-069 E | 80/20 | 1.19 MW | 1.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 957761 | AF2-070 C | 80/20 | 0.52 MW | 0.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 957762 | AF2-070 E | 80/20 | 2.52 MW | 2.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 958341 | AF2-128 C O1 | 80/20 | 2.34 MW | 2.34 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 958342 | AF2-128 E O1 | 80/20 | 10.96 MW | 10.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 962721 | AG1-121 C | 80/20 | 4.01 MW | 4.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 962722 | AG1-121 E | 80/20 | 18.75 MW | 18.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 965671 | AG1-435 C | 80/20 | 2.29 MW | 2.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 965672 | AG1-435 E | 80/20 | 10.72 MW | 10.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 990051 | J1200 | External Queue | 3.32 MW | 3.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L7413__R-S | 991301 | J1755 | External Queue | 14.05 MW | 14.05 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 274848 | CAMPGROVE;RU | 80/20 | 0.64 MW | 0.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 274849 | CRESCENT ;1U | 80/20 | 0.44 MW | 0.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 274851 | PROVIDENC;RU | 80/20 | 0.45 MW | 0.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 274877 | BISHOP HL;1U | 80/20 | 0.56 MW | 0.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 274878 | BISHOP HL;2U | 80/20 | 0.56 MW | 0.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 293771 | O-035 E | 80/20 | 2.59 MW | 2.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 294401 | BSHIL;1U E | 80/20 | 2.24 MW | 2.24 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 294410 | BSHIL;2U E | 80/20 | 2.24 MW | 2.24 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 916211 | Z1-072 E | 80/20 | 3.92 MW | 3.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 925581 | AC1-033 C | 80/20 | 0.73 MW | 0.73 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 925582 | AC1-033 E | 80/20 | 4.92 MW | 4.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 926821 | AC1-168 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 926822 | AC1-168 E O1 | 80/20 | 6.25 MW | 6.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 927201 | AC1-214 C O1 | 80/20 | 0.83 MW | 0.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 927202 | AC1-214 E O1 | 80/20 | 2.64 MW | 2.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 946541 | AF1-318 C O1 | 80/20 | 6.94 MW | 6.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 946542 | AF1-318 E O1 | 80/20 | 32.49 MW | 32.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 957752 | AF2-069 E | 80/20 | 0.62 MW | 0.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 957762 | AF2-070 E | 80/20 | 1.32 MW | 1.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 958341 | AF2-128 C O1 | 80/20 | 1.97 MW | 1.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 958342 | AF2-128 E O1 | 80/20 | 9.21 MW | 9.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 962721 | AG1-121 C | 80/20 | 4.11 MW | 4.11 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 962722 | AG1-121 E | 80/20 | 19.23 MW | 19.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 965671 | AG1-435 C | 80/20 | 2.48 MW | 2.48 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 965672 | AG1-435 E | 80/20 | 11.61 MW | 11.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 990051 | J1200 | External Queue | 3.07 MW | 3.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-A | 991301 | J1755 | External Queue | 14.22 MW | 14.22 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274848 | CAMPGROVE;RU | 80/20 | 0.64 MW | 0.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274849 | CRESCENT ;1U | 80/20 | 0.44 MW | 0.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274851 | PROVIDENC;RU | 80/20 | 0.45 MW | 0.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274877 | BISHOP HL;1U | 80/20 | 0.56 MW | 0.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274878 | BISHOP HL;2U | 80/20 | 0.56 MW | 0.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 293771 | O-035 E | 80/20 | 2.59 MW | 2.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 294401 | BSHIL;1U E | 80/20 | 2.24 MW | 2.24 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 294410 | BSHIL;2U E | 80/20 | 2.24 MW | 2.24 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 916211 | Z1-072 E | 80/20 | 3.92 MW | 3.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 925581 | AC1-033 C | 80/20 | 0.73 MW | 0.73 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 925582 | AC1-033 E | 80/20 | 4.92 MW | 4.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 926821 | AC1-168 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 926822 | AC1-168 E O1 | 80/20 | 6.25 MW | 6.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927201 | AC1-214 C O1 | 80/20 | 0.83 MW | 0.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927202 | AC1-214 E O1 | 80/20 | 2.64 MW | 2.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946541 | AF1-318 C O1 | 80/20 | 6.94 MW | 6.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946542 | AF1-318 E O1 | 80/20 | 32.49 MW | 32.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957752 | AF2-069 E | 80/20 | 0.62 MW | 0.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957761 | AF2-070 C | 80/20 | 0.27 MW | 0.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957762 | AF2-070 E | 80/20 | 1.32 MW | 1.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 958341 | AF2-128 C O1 | 80/20 | 1.97 MW | 1.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 958342 | AF2-128 E O1 | 80/20 | 9.21 MW | 9.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 962721 | AG1-121 C | 80/20 | 4.11 MW | 4.11 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 962722 | AG1-121 E | 80/20 | 19.23 MW | 19.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 965671 | AG1-435 C | 80/20 | 2.48 MW | 2.48 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 965672 | AG1-435 E | 80/20 | 11.61 MW | 11.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 990051 | J1200 | External Queue | 3.07 MW | 3.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 991301 | J1755 | External Queue | 14.22 MW | 14.22 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274658 | DRESDEN ;2U | 80/20 | 243.95 MW | 243.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274659 | DRESDEN ;3U | 80/20 | 256.29 MW | 256.29 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 3.15 MW | 3.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 2.37 MW | 2.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.93 MW | 0.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 1.43 MW | 1.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.96 MW | 0.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 2.81 MW | 2.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 2.89 MW | 2.89 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 2.36 MW | 2.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 2.0 MW | 2.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 1.54 MW | 1.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 1.54 MW | 1.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 1.83 MW | 1.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 3.5 MW | 3.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 2.28 MW | 2.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 2.28 MW | 2.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 1.17 MW | 1.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 4.41 MW | 4.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 1.85 MW | 1.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 1.85 MW | 1.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 2.97 MW | 2.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 3.65 MW | 3.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 3.65 MW | 3.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 2.5 MW | 2.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 2.2 MW | 2.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 14.59 MW | 14.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 1.22 MW | 1.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 1.32 MW | 1.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 2.41 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 4.51 MW | 4.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 12.84 MW | 12.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 16.14 MW | 16.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 9.44 MW | 9.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 22.05 MW | 22.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 12.8 MW | 12.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 12.8 MW | 12.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 13.78 MW | 13.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 2.25 MW | 2.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 1.14 MW | 1.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 1.26 MW | 1.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 8.01 MW | 8.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 4.07 MW | 4.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 4.48 MW | 4.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 8.13 MW | 8.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 15.79 MW | 15.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 8.56 MW | 8.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 4.69 MW | 4.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 4.31 MW | 4.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 5.51 MW | 5.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 13.69 MW | 13.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 13.69 MW | 13.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 19.85 MW | 19.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 16.44 MW | 16.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 17.5 MW | 17.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 7.41 MW | 7.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 7.41 MW | 7.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 8.27 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.77 MW | 0.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 5.69 MW | 5.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.32 MW | 0.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 2.59 MW | 2.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 8.34 MW | 8.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 5.52 MW | 5.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 14.82 MW | 14.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 918052 | AA1-018 E OP | 80/20 | 14.75 MW | 14.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 18.52 MW | 18.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.43 MW | 2.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 16.24 MW | 16.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.31 MW | 3.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 22.17 MW | 22.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.98 MW | 1.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 13.3 MW | 13.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 1.77 MW | 1.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 5.62 MW | 5.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.12 MW | 0.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.5 MW | 0.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 34.17 MW | 34.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 159.48 MW | 159.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 6.04 MW | 6.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 7.09 MW | 7.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 34.6 MW | 34.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 4.57 MW | 4.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 18.25 MW | 18.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 13.31 MW | 13.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 47.21 MW | 47.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 6.94 MW | 6.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 23.69 MW | 23.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 9.68 MW | 9.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 59.45 MW | 59.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 9.48 MW | 9.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 44.49 MW | 44.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 10.64 MW | 10.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 3.32 MW | 3.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 22.23 MW | 22.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 5.04 MW | 5.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 15.13 MW | 15.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 8.49 MW | 8.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 8.48 MW | 8.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 5.65 MW | 5.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 4.27 MW | 4.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 6.93 MW | 6.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 32.42 MW | 32.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 7.69 MW | 7.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 36.14 MW | 36.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 9.91 MW | 9.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 46.4 MW | 46.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 5.43 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 8.14 MW | 8.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957371 | AF2-031 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957372 | AF2-031 E O1 | 80/20 | 2.54 MW | 2.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 1.08 MW | 1.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 1.62 MW | 1.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.41 MW | 0.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 1.32 MW | 1.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.58 MW | 0.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 2.8 MW | 2.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 10.42 MW | 10.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 20.27 MW | 20.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 12.32 MW | 12.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 8.05 MW | 8.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 12.07 MW | 12.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 30.51 MW | 30.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 4.98 MW | 4.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 7.47 MW | 7.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 6.06 MW | 6.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.19 MW | 1.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 1.93 MW | 1.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 4.98 MW | 4.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 7.47 MW | 7.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 12.58 MW | 12.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 3.13 MW | 3.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 4.04 MW | 4.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 6.06 MW | 6.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 7.02 MW | 7.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 32.86 MW | 32.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 14.96 MW | 14.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 9.97 MW | 9.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961501 | AF2-441 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961502 | AF2-441 E O1 | 80/20 | 27.35 MW | 27.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.14 MW | 0.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 9.72 MW | 9.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 45.49 MW | 45.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.31 MW | 3.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 22.17 MW | 22.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 964361 | AG1-298 O1 | 80/20 | 112.0 MW | 112.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 15.15 MW | 15.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.95 MW | 0.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 7.64 MW | 7.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 35.79 MW | 35.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 27.14 MW | 27.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 27.14 MW | 27.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 18.1 MW | 18.1 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 7.35 MW | 7.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 34.42 MW | 34.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 6.57 MW | 6.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 30.74 MW | 30.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 1.06 MW | 1.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 1.59 MW | 1.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966431 | AG1-512 C | 80/20 | 3.56 MW | 3.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966432 | AG1-512 E | 80/20 | 5.35 MW | 5.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966441 | AG1-513 C | 80/20 | 1.16 MW | 1.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966442 | AG1-513 E | 80/20 | 1.74 MW | 1.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966651 | AG1-535 O1 | 80/20 | 17.93 MW | 17.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 15.12 MW | 15.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 22.68 MW | 22.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 38.88 MW | 38.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 7.97 MW | 7.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 11.95 MW | 11.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 2.66 MW | 2.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 3.98 MW | 3.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 686.73 MW | 686.73 MW |
| Details for AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C | 80/20 | 41.52 MW | 41.52 MW |
| AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962722 | AG1-121 E | 80/20 | 194.24 MW | 194.24 MW |
| Details for AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962721 | AG1-121 C | 80/20 | 41.52 MW | 41.52 MW |
| AG1-121 TAP-AG1-435 TAP 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962722 | AG1-121 E | 80/20 | 194.24 MW | 194.24 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| n5252 | Mitigate the sag on L11215 | $9,000,000 | |
| n6860 | Wilton Upgrade exisiting Current Transformers | $1,000,000 | |
| n6600 | Replace Dumont Circuit Breaker B1 | $3,000,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
| n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
| n7925.4 | Replace three 2-2000 AAC 91 Str | $300,000 | |
| n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
| b3775.9 | Upgrade existing terminal equipment (substation conductor) at Green Acres on the St. John to Green Acres 345 kV lin | $0 | |
| n5912.3 | The existing SLD/ALDR rating are 1767/2032 MVA. Reconductor the line and replace the 345kV BT 10-11 & BT 9-10 CB disconnect switches at TSS 177 along with upgrading the L17703 MOD. | $18,400,000 | |
| n5912 | Re-conductor of the line along with station conductor upgrade at Burnham | $1,000,000 | |
| (TBD) | Upgrade 0.6 miles of line to bundled conductor and additional susbtation upgrades required. | $5,000,000 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| n6992 | Re-conductor a portion of the Corbin 138 kV line. | $7,200,000 | |
| n7093 | 4Corbin-AD2-066 138 kV Line - Mitigate Sag and Reconductor | $22,400,000 | |
| (TBD) | MISO review required. | $0 | |
| (TBD) | MISO review required. | $0 | |
| n8375 | AB1-122 - Tazewell 345 kV Line Sag Mitigation | $39,900,000 | |
| b3775.5 | Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker. | $0 | |
| n7945 | Channahon - Mazon 138 kV line conductor and circuit breaker upgrades | $5,200,000 | |
| n5324 | Re-conductor the line segment - Dresden - AB1-122 345 kV line | $4,000,000 | |
| n5324.1 | Dresden - AB1-122 345 kV line - Re-conductor the line segment and upgrade relay package. | $5,000,000 | |
| b3775.4 | Rebuild 345 kV double circuit extending from Crete to E. Frankfort. | $0 | |
| n6279 | TSS 116 Replace 345 kV Circuit Breaker | $3,200,000 | |
| n8389 | TSS 116 Replace Station Conductor | $1,000,000 | |
| (TBD) | MISO (AMIL) Review required | $0 | |
| n8401 | Re-conductor the line, upgrade a line trap and install new station bus at TSS 74 Kewanee. | $16,500,000 | |
| n8378 | Kewanee 138 kV - Re-conductor the line segment. | $2,500,000 | |
| n8400 | Mitigate Sag Kewanee - AD1-031 - Edwards 138 kV line | $20,800,000 | |
| (TBD) | MISO review required on its limiting equipment. | $500,000 | |
| (TBD) | MISO review required | $0 | |
| n8399 | Kewanee - 4 Kemin 138 kV line Mitigate Sag | $2,800,000 | |
| n8400.1 | Re-conductor the line - Kewanee - AG1-435 138 kV line | $7,800,000 | |
| s2768 | Mazon Circuit Breaker Replacement | $2,500,000 | |
| b3677 | Mazon - Lasalle 138 kV line rebuild | $42,060,000 | |
| n8373 | Plano - Install 3rd Auto Transformer at TSS 167 Plano. | $20,000,000 | |
| n6752.1 | Re-conductor the line, replace station conductor and a line trap ComEd L1404 138 kV line. | $5,800,000 | |
| n6270 | Disconnect Switch Upgrade on Toulon - Powerton 138 kV line | $600,000 | |
| n8377 | Powerton - Toulon 138 kV line Reconductor and upgrades | $32,000,000 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-121 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.