AG1-098 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:49
Briery-Clover 230 kV
64.2 MW Capacity / 107.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-098 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Mecklenburg County, Virginia. The installed facilities will have a total capability of 107.0 MW with 64.2 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-098 |
| Project Name | Briery-Clover 230 kV |
| Developer Name | Virginia Electric & Power Company |
| State | Virginia |
| County | Mecklenburg |
| Transmission Owner | Dominion |
| MFO | 107.0 MW |
| MWE | 107.0 MW |
| MWC | 64.2 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-098 "Briery-Clover 230 kV" will interconnect with the Dominion transmission system. The primary POI will be a newly constructed 230 kV three breaker ring bus located on the line between the Briery substation and Clover substation.
Summer Peak Analysis
The Queue Project was evaluated as a 107.0 MW (Capacity 64.2 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 147.16 % | 151.96 % | 559.3 | B | 849.9 | 25.47 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 145.22 % | 149.92 % | 571.52 | B | 856.84 | 25.46 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 147.08 % | 151.82 % | 559.3 | B | 849.12 | 25.47 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 145.31 % | 150.03 % | 571.52 | B | 857.44 | 25.46 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 130.99 % | 135.14 % | 718.0 | B | 970.31 | 27.28 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 127.16 % | 131.58 % | 674.92 | B | 888.07 | 27.28 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 131.01 % | 135.18 % | 718.0 | B | 970.62 | 27.28 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 127.21 % | 131.63 % | 674.92 | B | 888.38 | 27.28 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 126.84 % | 128.61 % | 661.76 | B | 851.06 | 11.98 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 122.89 % | 124.65 % | 661.76 | B | 824.88 | 11.98 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 122.65 % | 124.41 % | 661.76 | B | 823.32 | 11.98 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 119.55 % | 121.31 % | 661.76 | B | 802.76 | 11.98 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 118.69 % | 120.46 % | 661.76 | B | 797.14 | 11.98 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 119.14 % | 121.02 % | 678.68 | B | 821.31 | 13.16 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 115.61 % | 117.38 % | 661.76 | B | 776.77 | 11.98 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 117.06 % | 118.93 % | 678.68 | B | 807.17 | 13.16 | |
| DVP |
AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line
935170 to 314697 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 115.88 % | 120.43 % | 814.98 | B | 981.48 | 34.69 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 114.94 % | 116.83 % | 678.68 | B | 792.87 | 13.16 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 112.86 % | 114.75 % | 678.68 | B | 778.76 | 13.16 | |
| DVP |
6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line
314690 to 935170 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 110.32 % | 114.83 % | 814.98 | B | 935.85 | 34.69 | |
| DVP |
AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line
934620 to 314268 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 119.32 % | 124.32 % | 571.52 | B | 710.51 | 29.22 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 118.29 % | 123.31 % | 571.52 | B | 704.72 | 29.22 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 118.25 % | 123.26 % | 571.52 | B | 704.47 | 29.22 | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 108.31 % | 110.46 % | 269.78 | B | 297.99 | 6.05 | |
| DVP |
AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line
962490 to 934620 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 112.72 % | 117.65 % | 571.52 | B | 672.38 | 29.22 | |
| DVP |
AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line
935170 to 314697 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 115.91 % | 120.53 % | 814.98 | B | 982.34 | 34.69 | |
| DVP |
AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line
934620 to 314268 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 119.32 % | 124.3 % | 571.52 | B | 710.37 | 29.22 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 118.3 % | 123.29 % | 571.52 | B | 704.64 | 29.22 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 118.25 % | 123.25 % | 571.52 | B | 704.39 | 29.22 | |
| DVP |
6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line
314690 to 935170 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 110.35 % | 114.93 % | 814.98 | B | 936.62 | 34.69 | |
| DVP |
AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line
962490 to 934620 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 112.72 % | 117.62 % | 571.52 | B | 672.22 | 29.22 | |
| DVP |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line
314940 to 941030 ckt 1 |
DVP_P1-2: LN 511-A
CONTINGENCY 'DVP_P1-2: LN 511-A' OPEN BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.84 % | 100.47 % | 4070.2 | B | 4089.25 | 20.69 | |
| DVP |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line
314940 to 941030 ckt 1 |
DVP_P1-2: LN 511-B
CONTINGENCY 'DVP_P1-2: LN 511-B' OPEN BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.79 % | 100.4 % | 4070.2 | B | 4086.56 | 20.69 | |
| DVP |
8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line
314936 to 942930 ckt 1 |
DVP_P1-2: LN 585-B
CONTINGENCY 'DVP_P1-2: LN 585-B' OPEN BRANCH FROM BUS 941030 TO BUS 314940 CKT 1 /*AE2-094 TAP 500.0 - 8ROGERS RD 500.0 END |
Single | AC | 99.8 % | 100.41 % | 4070.2 | B | 4086.73 | 23.12 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1' /* Auto-generated /* 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 END |
Single | AC | 99.22 % | 104.22 % | 571.52 | B | 595.67 | 29.22 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.22 % | 104.22 % | 571.52 | B | 595.66 | 29.22 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1' /* Auto-generated /* 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 END |
Single | AC | 99.17 % | 104.17 % | 571.52 | B | 595.38 | 29.22 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.16 % | 104.17 % | 571.52 | B | 595.37 | 29.22 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 165.71 % | 171.97 % | 684.0 | C | 1176.25 | 42.5 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 165.71 % | 171.96 % | 684.0 | C | 1176.23 | 42.5 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 165.65 % | 171.91 % | 684.0 | C | 1175.88 | 42.5 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 163.68 % | 169.81 % | 699.0 | C | 1186.96 | 42.49 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 163.68 % | 169.81 % | 699.0 | C | 1186.94 | 42.49 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 163.63 % | 169.76 % | 699.0 | C | 1186.59 | 42.49 | |
| DVP |
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
314902 to 314282 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 150.58 % | 151.69 % | 1039.7 | C | 1577.17 | 12.24 | |
| DVP |
AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line
934620 to 314268 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 122.62 % | 129.45 % | 699.0 | C | 904.88 | 48.74 | |
| DVP |
AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line
934620 to 314268 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 122.61 % | 129.45 % | 699.0 | C | 904.86 | 48.74 | |
| DVP |
AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line
934620 to 314268 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 122.61 % | 129.45 % | 699.0 | C | 904.84 | 48.74 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.8 % | 128.62 % | 699.0 | C | 899.09 | 48.74 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.79 % | 128.62 % | 699.0 | C | 899.06 | 48.74 | |
| DVP |
6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line
314268 to 313802 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.79 % | 128.62 % | 699.0 | C | 899.05 | 48.74 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.76 % | 128.6 % | 699.0 | C | 898.89 | 48.74 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.76 % | 128.59 % | 699.0 | C | 898.87 | 48.74 | |
| DVP |
6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line
313802 to 314692 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 121.76 % | 128.59 % | 699.0 | C | 898.86 | 48.74 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 111.22 % | 113.9 % | 809.0 | C | 921.47 | 22.18 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 111.22 % | 113.9 % | 809.0 | C | 921.47 | 22.18 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 111.2 % | 113.88 % | 809.0 | C | 921.31 | 22.18 | |
| DVP |
AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line
962490 to 934620 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 114.37 % | 121.04 % | 699.0 | C | 846.08 | 48.74 | |
| DVP |
AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line
962490 to 934620 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 114.37 % | 121.04 % | 699.0 | C | 846.08 | 48.74 | |
| DVP |
AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line
962490 to 934620 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 114.37 % | 121.04 % | 699.0 | C | 846.05 | 48.74 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.91 % | 103.71 % | 350.0 | C | 362.97 | 7.43 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.91 % | 103.7 % | 350.0 | C | 362.96 | 7.43 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.91 % | 103.7 % | 350.0 | C | 362.95 | 7.43 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.05 % | 102.84 % | 350.0 | C | 359.93 | 7.43 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.05 % | 102.84 % | 350.0 | C | 359.93 | 7.43 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 101.04 % | 102.83 % | 350.0 | C | 359.91 | 7.43 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 98.54 % | 100.06 % | 980.0 | C | 980.61 | 15.08 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 98.53 % | 100.05 % | 980.0 | C | 980.53 | 15.08 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 98.51 % | 100.03 % | 980.0 | C | 980.29 | 15.08 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 98.5 % | 100.02 % | 980.0 | C | 980.23 | 15.08 | |
| AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P4_#11112_05J.FERR 765_A1
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1' OPEN BRANCH FROM BUS 242511 TO BUS 242514 CKT 1 /*05BROADF 765.0 - 05J.FERR 765.0 OPEN BRANCH FROM BUS 242514 TO BUS 242520 CKT 1 /*05J.FERR 765.0 - 05J.FERR 500.0 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB /*05BROADF 138.0 - 05BROADX 138.0 END |
Breaker | AC | 135.89 % | 137.06 % | 402.0 | B | 550.97 | 5.67 | |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -6.03 MW | -5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 60.29 MW | 60.29 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 60.29 MW | 60.29 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 35.11 MW | 35.11 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 60.29 MW | 60.29 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 60.29 MW | 60.29 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | Adder | -12.89 MW | -10.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 29.3 MW | 29.3 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 29.3 MW | 29.3 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 29.3 MW | 29.3 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 29.3 MW | 29.3 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 29.3 MW | 29.3 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 29.3 MW | 29.3 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961791 | AG1-021 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961891 | AG1-030 C | 80/20 | 9.77 MW | 9.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962491 | AG1-098 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963171 | AG1-166 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963181 | AG1-167 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963191 | AG1-168 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963201 | AG1-169 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963211 | AG1-170 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963321 | AG1-181 C O1 | 80/20 | 9.04 MW | 9.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 O1 | 80/20 | 4.37 MW | 4.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964241 | AG1-285 C O1 | 80/20 | 5.52 MW | 5.52 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965591 | AG1-427 C | 80/20 | 5.27 MW | 5.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965641 | AG1-432 C O1 | 80/20 | 17.69 MW | 17.69 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.95 MW | 2.95 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315153 | 1CLOVER1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315154 | 1CLOVER2 | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934615 | AD1-087 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934625 | AD1-088 C | 80/20 | 6.81 MW | 6.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 936265 | AD2-033 C | 80/20 | 6.87 MW | 6.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 937481 | AD2-202 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 942461 | AE2-259 C O1 | 80/20 | 8.85 MW | 8.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958801 | AF2-171 C | 80/20 | 10.46 MW | 10.46 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 316131 | AB2-060 C | 80/20 | 0.63 MW | 0.63 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924301 | AB2-077 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924311 | AB2-078 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924321 | AB2-079 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925611 | AC1-036 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938371 | AE1-056 C | 80/20 | 4.85 MW | 4.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 939181 | AE1-148 C | 80/20 | 2.81 MW | 2.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941791 | AE2-182 C | 80/20 | 1.11 MW | 1.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946301 | AF1-294 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958211 | AF2-115 C | 80/20 | 1.75 MW | 1.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 933501 | AC2-165 C | 80/20 | 9.02 MW | 9.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314333 | 6POWHATN | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314677 | 6BUCKING | 80/20 | 0.49 MW | 0.49 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315191 | 1BEARGRDN G1 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315192 | 1BEARGRDN G2 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315193 | 1BEARGRDN S1 | 80/20 | 10.93 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938561 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962561 | AG1-105 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.79 MW | 0.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.19 MW | 0.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 29.3 MW | 29.3 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 29.3 MW | 29.3 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 35.11 MW | 35.11 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | Adder | -12.89 MW | -10.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 13.68 MW | 13.68 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 97.68 MW | 97.68 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961791 | AG1-021 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961891 | AG1-030 C | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962491 | AG1-098 C O1 | 80/20 | 20.69 MW | 20.69 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963041 | AG1-153 C | 80/20 | 17.6 MW | 17.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963111 | AG1-160 C | 80/20 | 18.44 MW | 18.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963171 | AG1-166 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963181 | AG1-167 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963191 | AG1-168 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963201 | AG1-169 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963211 | AG1-170 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963321 | AG1-181 C O1 | 80/20 | 15.44 MW | 15.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 963361 | AG1-185 O1 | 80/20 | 7.47 MW | 7.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964111 | AG1-272 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964121 | AG1-273 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964131 | AG1-274 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964241 | AG1-285 C O1 | 80/20 | 11.41 MW | 11.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 964791 | AG1-342 C | 80/20 | 5.47 MW | 5.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966691 | AG1-539 C | 80/20 | 5.64 MW | 5.64 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966761 | AG1-547 C | 80/20 | 3.77 MW | 3.77 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965191 | AG1-384 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965591 | AG1-427 C | 80/20 | 10.81 MW | 10.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965641 | AG1-432 C O1 | 80/20 | 18.63 MW | 18.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965721 | AG1-440 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965731 | AG1-441 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965811 | AG1-449 | 80/20 | 68.22 MW | 68.22 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 965831 | AG1-451 | 80/20 | 3.1 MW | 3.1 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966361 | AG1-505 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 966371 | AG1-506 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 247284 | 05LEESVG | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 314429 | 3JTRSVLE | 80/20 | 0.42 MW | 0.42 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315153 | 1CLOVER1 | 80/20 | 30.43 MW | 30.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315154 | 1CLOVER2 | 80/20 | 30.14 MW | 30.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315158 | 1KERR 1 | 80/20 | 0.35 MW | 0.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315159 | 1KERR 2 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315160 | 1KERR 3 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315161 | 1KERR 4 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315162 | 1KERR 5 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926023 | AC1-080 C | 80/20 | 0.43 MW | 0.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926051 | AC1-083 C O1 | 80/20 | 4.86 MW | 4.86 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926645 | AC1-145 C | 80/20 | 0.38 MW | 0.38 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927251 | AC1-221 C | 80/20 | 3.73 MW | 3.73 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 927261 | AC1-222 C | 80/20 | 5.71 MW | 5.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 933941 | AD1-017 C | 80/20 | 0.97 MW | 0.97 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934311 | AD1-055 C | 80/20 | 3.96 MW | 3.96 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934341 | AD1-058 C | 80/20 | 9.36 MW | 9.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934615 | AD1-087 C | 80/20 | 17.65 MW | 17.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934625 | AD1-088 C | 80/20 | 22.84 MW | 22.84 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934991 | AD1-131 C | 80/20 | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 935171 | AD1-152 C O1 | 80/20 | 17.29 MW | 17.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936161 | AD2-022 C O1 | 80/20 | 12.6 MW | 12.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936171 | AD2-023 C O1 | 80/20 | 7.35 MW | 7.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 936265 | AD2-033 C | 80/20 | 11.91 MW | 11.91 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937481 | AD2-202 C O1 | 80/20 | 5.17 MW | 5.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942461 | AE2-259 C O1 | 80/20 | 9.31 MW | 9.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942671 | AE2-283 C | 80/20 | 4.59 MW | 4.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942751 | AE2-291 C | 80/20 | 10.79 MW | 10.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942761 | AE2-292 C O1 | 80/20 | 13.43 MW | 13.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942931 | AE2-313 C | 80/20 | 105.35 MW | 105.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943811 | AF1-049 C | 80/20 | 9.05 MW | 9.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943901 | AF1-058 C | 80/20 | 3.16 MW | 3.16 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 944141 | AF1-082 | 80/20 | 1.87 MW | 1.87 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 945811 | AF1-246 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958801 | AF2-171 C | 80/20 | 13.85 MW | 13.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 959311 | AF2-222 C | 80/20 | 15.31 MW | 15.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 960061 | AF2-297 C | 80/20 | 12.65 MW | 12.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 961121 | AF2-403 | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315163 | 1KERR 6 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315164 | 1KERR 7 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315266 | 1PLYWOOD A | 80/20 | 1.88 MW | 1.88 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316020 | AB2-059 C OP | 80/20 | 1.17 MW | 1.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316118 | AC1-105 C | 80/20 | 8.29 MW | 8.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316131 | AB2-060 C | 80/20 | 1.41 MW | 1.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 922922 | AB1-081 C OP | 80/20 | 0.99 MW | 0.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924301 | AB2-077 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924311 | AB2-078 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 924321 | AB2-079 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925591 | AC1-034 C | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925611 | AC1-036 C | 80/20 | 0.22 MW | 0.22 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 925661 | AC1-042 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932761 | AC2-100 C | 80/20 | 8.59 MW | 8.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938371 | AE1-056 C | 80/20 | 5.99 MW | 5.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 939181 | AE1-148 C | 80/20 | 7.56 MW | 7.56 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940081 | AE1-250 C | 80/20 | 13.17 MW | 13.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940571 | AE2-044 C | 80/20 | 2.9 MW | 2.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940661 | AE2-053 O1 | 80/20 | 2.8 MW | 2.8 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941431 | AE2-140 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941791 | AE2-182 C | 80/20 | 3.71 MW | 3.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941801 | AE2-185 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 941821 | AE2-187 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 946301 | AF1-294 C | 80/20 | 3.79 MW | 3.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957481 | AF2-042 C | 80/20 | 136.39 MW | 136.39 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 958211 | AF2-115 C | 80/20 | 2.31 MW | 2.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 926754 | AC1-161 C | Adder | -31.93 MW | -27.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 934061 | AD1-033 C | Adder | -7.2 MW | -6.12 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 937221 | AD2-160 C O1 | Adder | -5.42 MW | -4.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 942401 | AE2-253 C | Adder | -5.7 MW | -4.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943611 | AF1-032 C | Adder | -1.56 MW | -1.32 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 943621 | AF1-033 C | Adder | -2.13 MW | -1.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315102 | 1BRUNSWICKG1 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315103 | 1BRUNSWICKG2 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315104 | 1BRUNSWICKG3 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315105 | 1BRUNSWICKS1 | 80/20 | 56.26 MW | 56.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315241 | 1Z1-086 GT1 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315242 | 1Z1-086 GT2 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315243 | 1Z1-086 GT3 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 315244 | 1Z1-086 ST | 80/20 | 62.59 MW | 62.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 932044 | AC2-012 C | Adder | -7.78 MW | -6.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 938741 | AE1-100 C O1 | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 939431 | AE1-175 C | Adder | -2.09 MW | -1.78 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 940601 | AE2-047 C O1 | 80/20 | 4.11 MW | 4.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 957491 | AF2-043 C | Adder | -1.91 MW | -1.62 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962961 | AG1-145 C | Adder | -1.89 MW | -1.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 962561 | AG1-105 C O1 | 80/20 | 11.17 MW | 11.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 313527 | AB2-043 C | 80/20 | 0.49 MW | 0.49 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | 316123 | AC1-075 C | 80/20 | 1.29 MW | 1.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.63 MW | 9.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 180.98 MW | 180.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.2 MW | 62.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.2 MW | 65.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 14.58 MW | 14.58 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.29 MW | 15.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.82 MW | 0.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.05 MW | 3.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.9 MW | 8.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.07 MW | 2.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.3 MW | 12.3 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.49 MW | 1.49 MW |
| Details for 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 961791 | AG1-021 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 961891 | AG1-030 C | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 962491 | AG1-098 C O1 | 80/20 | 20.69 MW | 20.69 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963041 | AG1-153 C | 80/20 | 17.6 MW | 17.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963111 | AG1-160 C | 80/20 | 18.44 MW | 18.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963171 | AG1-166 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963181 | AG1-167 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963191 | AG1-168 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963201 | AG1-169 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963211 | AG1-170 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963321 | AG1-181 C O1 | 80/20 | 15.44 MW | 15.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 963361 | AG1-185 O1 | 80/20 | 7.47 MW | 7.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 964111 | AG1-272 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 964121 | AG1-273 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 964131 | AG1-274 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 964241 | AG1-285 C O1 | 80/20 | 11.41 MW | 11.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 964791 | AG1-342 C | 80/20 | 5.47 MW | 5.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 966691 | AG1-539 C | 80/20 | 5.64 MW | 5.64 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 966761 | AG1-547 C | 80/20 | 3.77 MW | 3.77 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965191 | AG1-384 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965591 | AG1-427 C | 80/20 | 10.81 MW | 10.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965641 | AG1-432 C O1 | 80/20 | 18.63 MW | 18.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965721 | AG1-440 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965731 | AG1-441 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 965831 | AG1-451 | 80/20 | 3.1 MW | 3.1 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 966361 | AG1-505 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 966371 | AG1-506 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 247284 | 05LEESVG | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 314429 | 3JTRSVLE | 80/20 | 0.42 MW | 0.42 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315153 | 1CLOVER1 | 80/20 | 30.43 MW | 30.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315154 | 1CLOVER2 | 80/20 | 30.14 MW | 30.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315158 | 1KERR 1 | 80/20 | 0.35 MW | 0.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315159 | 1KERR 2 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315160 | 1KERR 3 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315161 | 1KERR 4 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315162 | 1KERR 5 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 926023 | AC1-080 C | 80/20 | 0.43 MW | 0.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 926051 | AC1-083 C O1 | 80/20 | 4.86 MW | 4.86 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 926645 | AC1-145 C | 80/20 | 0.38 MW | 0.38 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 927251 | AC1-221 C | 80/20 | 3.73 MW | 3.73 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 927261 | AC1-222 C | 80/20 | 5.71 MW | 5.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 933941 | AD1-017 C | 80/20 | 0.97 MW | 0.97 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934311 | AD1-055 C | 80/20 | 3.96 MW | 3.96 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934341 | AD1-058 C | 80/20 | 9.36 MW | 9.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934615 | AD1-087 C | 80/20 | 17.65 MW | 17.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934625 | AD1-088 C | 80/20 | 22.84 MW | 22.84 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934991 | AD1-131 C | 80/20 | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 935171 | AD1-152 C O1 | 80/20 | 17.29 MW | 17.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 936161 | AD2-022 C O1 | 80/20 | 12.6 MW | 12.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 936171 | AD2-023 C O1 | 80/20 | 7.35 MW | 7.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 936265 | AD2-033 C | 80/20 | 11.91 MW | 11.91 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 937481 | AD2-202 C O1 | 80/20 | 5.17 MW | 5.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942461 | AE2-259 C O1 | 80/20 | 9.31 MW | 9.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942671 | AE2-283 C | 80/20 | 4.59 MW | 4.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942751 | AE2-291 C | 80/20 | 10.79 MW | 10.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942761 | AE2-292 C O1 | 80/20 | 13.43 MW | 13.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942931 | AE2-313 C | 80/20 | 105.35 MW | 105.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 943811 | AF1-049 C | 80/20 | 9.05 MW | 9.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 943901 | AF1-058 C | 80/20 | 3.16 MW | 3.16 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 944141 | AF1-082 | 80/20 | 1.87 MW | 1.87 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 945811 | AF1-246 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 958801 | AF2-171 C | 80/20 | 13.85 MW | 13.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 959311 | AF2-222 C | 80/20 | 15.31 MW | 15.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 960061 | AF2-297 C | 80/20 | 12.65 MW | 12.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 961121 | AF2-403 | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315163 | 1KERR 6 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315164 | 1KERR 7 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315266 | 1PLYWOOD A | 80/20 | 1.88 MW | 1.88 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316020 | AB2-059 C OP | 80/20 | 1.17 MW | 1.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316118 | AC1-105 C | 80/20 | 8.29 MW | 8.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316131 | AB2-060 C | 80/20 | 1.41 MW | 1.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 922922 | AB1-081 C OP | 80/20 | 0.99 MW | 0.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 924301 | AB2-077 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 924311 | AB2-078 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 924321 | AB2-079 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 925591 | AC1-034 C | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 925611 | AC1-036 C | 80/20 | 0.22 MW | 0.22 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 925661 | AC1-042 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 932761 | AC2-100 C | 80/20 | 8.59 MW | 8.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 938371 | AE1-056 C | 80/20 | 5.99 MW | 5.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 939181 | AE1-148 C | 80/20 | 7.56 MW | 7.56 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 940081 | AE1-250 C | 80/20 | 13.17 MW | 13.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 940571 | AE2-044 C | 80/20 | 2.9 MW | 2.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 940661 | AE2-053 O1 | 80/20 | 2.8 MW | 2.8 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 941431 | AE2-140 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 941791 | AE2-182 C | 80/20 | 3.71 MW | 3.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 941801 | AE2-185 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 941821 | AE2-187 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 946301 | AF1-294 C | 80/20 | 3.79 MW | 3.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 957481 | AF2-042 C | 80/20 | 136.39 MW | 136.39 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 958211 | AF2-115 C | 80/20 | 2.31 MW | 2.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 926754 | AC1-161 C | Adder | -31.93 MW | -27.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934061 | AD1-033 C | Adder | -7.2 MW | -6.12 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 934575 | AD1-082 C | Adder | -6.69 MW | -5.69 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 937221 | AD2-160 C O1 | Adder | -5.42 MW | -4.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 942401 | AE2-253 C | Adder | -5.7 MW | -4.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 943611 | AF1-032 C | Adder | -1.56 MW | -1.32 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 943621 | AF1-033 C | Adder | -2.13 MW | -1.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315102 | 1BRUNSWICKG1 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315103 | 1BRUNSWICKG2 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315104 | 1BRUNSWICKG3 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315105 | 1BRUNSWICKS1 | 80/20 | 56.26 MW | 56.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315241 | 1Z1-086 GT1 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315242 | 1Z1-086 GT2 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315243 | 1Z1-086 GT3 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 315244 | 1Z1-086 ST | 80/20 | 62.59 MW | 62.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316132 | AB2-190 C | Adder | -16.2 MW | -13.77 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 932044 | AC2-012 C | Adder | -7.78 MW | -6.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 938741 | AE1-100 C O1 | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 939431 | AE1-175 C | Adder | -2.09 MW | -1.78 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 940601 | AE2-047 C O1 | 80/20 | 4.11 MW | 4.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 957491 | AF2-043 C | Adder | -1.91 MW | -1.62 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 962961 | AG1-145 C | Adder | -1.89 MW | -1.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 962561 | AG1-105 C O1 | 80/20 | 11.17 MW | 11.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 313527 | AB2-043 C | 80/20 | 0.49 MW | 0.49 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316083 | AB2-161 C | Adder | -2.94 MW | -2.5 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | 316123 | AC1-075 C | 80/20 | 1.29 MW | 1.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.63 MW | 9.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 180.98 MW | 180.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.2 MW | 62.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.2 MW | 65.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 14.58 MW | 14.58 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.29 MW | 15.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.82 MW | 0.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.05 MW | 3.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.9 MW | 8.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.07 MW | 2.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.3 MW | 12.3 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.49 MW | 1.49 MW |
| Details for 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961791 | AG1-021 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961891 | AG1-030 C | 80/20 | 15.36 MW | 15.36 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962491 | AG1-098 C O1 | 80/20 | 23.12 MW | 23.12 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963041 | AG1-153 C | 80/20 | 17.62 MW | 17.62 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963111 | AG1-160 C | 80/20 | 17.62 MW | 17.62 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963171 | AG1-166 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963181 | AG1-167 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963191 | AG1-168 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963201 | AG1-169 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963211 | AG1-170 C | 80/20 | 2.06 MW | 2.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963321 | AG1-181 C O1 | 80/20 | 17.07 MW | 17.07 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 963361 | AG1-185 O1 | 80/20 | 8.26 MW | 8.26 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964111 | AG1-272 C | 80/20 | 2.61 MW | 2.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964121 | AG1-273 C | 80/20 | 2.61 MW | 2.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964131 | AG1-274 C | 80/20 | 2.61 MW | 2.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964241 | AG1-285 C O1 | 80/20 | 12.55 MW | 12.55 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 964791 | AG1-342 C | 80/20 | 6.0 MW | 6.0 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966691 | AG1-539 C | 80/20 | 6.13 MW | 6.13 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966761 | AG1-547 C | 80/20 | 4.06 MW | 4.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965191 | AG1-384 C | 80/20 | 2.61 MW | 2.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965591 | AG1-427 C | 80/20 | 11.9 MW | 11.9 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965641 | AG1-432 C O1 | 80/20 | 20.93 MW | 20.93 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965721 | AG1-440 C | 80/20 | 5.69 MW | 5.69 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965731 | AG1-441 C | 80/20 | 5.69 MW | 5.69 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965771 | AG1-445 | 80/20 | 3.29 MW | 3.29 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965781 | AG1-446 | 80/20 | 3.29 MW | 3.29 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 965831 | AG1-451 | 80/20 | 3.49 MW | 3.49 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966361 | AG1-505 C | 80/20 | 54.28 MW | 54.28 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 966371 | AG1-506 C | 80/20 | 54.28 MW | 54.28 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 246844 | 05SMG2 | 80/20 | 3.59 MW | 3.59 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 247284 | 05LEESVG | 80/20 | 0.99 MW | 0.99 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 314429 | 3JTRSVLE | 80/20 | 0.47 MW | 0.47 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315153 | 1CLOVER1 | 80/20 | 33.93 MW | 33.93 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315154 | 1CLOVER2 | 80/20 | 33.61 MW | 33.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315156 | 1HALLBR1 | 80/20 | 1.2 MW | 1.2 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315158 | 1KERR 1 | 80/20 | 0.38 MW | 0.38 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315159 | 1KERR 2 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315160 | 1KERR 3 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315161 | 1KERR 4 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315162 | 1KERR 5 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926023 | AC1-080 C | 80/20 | 0.47 MW | 0.47 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926051 | AC1-083 C O1 | 80/20 | 5.12 MW | 5.12 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926645 | AC1-145 C | 80/20 | 0.4 MW | 0.4 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 927251 | AC1-221 C | 80/20 | 3.96 MW | 3.96 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 927261 | AC1-222 C | 80/20 | 6.24 MW | 6.24 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 933941 | AD1-017 C | 80/20 | 1.02 MW | 1.02 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934311 | AD1-055 C | 80/20 | 4.33 MW | 4.33 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934341 | AD1-058 C | 80/20 | 9.94 MW | 9.94 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934615 | AD1-087 C | 80/20 | 19.68 MW | 19.68 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934625 | AD1-088 C | 80/20 | 25.52 MW | 25.52 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934991 | AD1-131 C | 80/20 | 3.26 MW | 3.26 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 935171 | AD1-152 C O1 | 80/20 | 19.14 MW | 19.14 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936161 | AD2-022 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936171 | AD2-023 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 936265 | AD2-033 C | 80/20 | 13.16 MW | 13.16 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 937481 | AD2-202 C O1 | 80/20 | 5.76 MW | 5.76 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942461 | AE2-259 C O1 | 80/20 | 10.46 MW | 10.46 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942671 | AE2-283 C | 80/20 | 4.94 MW | 4.94 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942751 | AE2-291 C | 80/20 | 11.73 MW | 11.73 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942761 | AE2-292 C O1 | 80/20 | 14.61 MW | 14.61 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943811 | AF1-049 C | 80/20 | 9.46 MW | 9.46 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943901 | AF1-058 C | 80/20 | 3.46 MW | 3.46 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 945811 | AF1-246 C O1 | 80/20 | 21.36 MW | 21.36 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 958801 | AF2-171 C | 80/20 | 15.43 MW | 15.43 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 959311 | AF2-222 C | 80/20 | 16.95 MW | 16.95 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 960061 | AF2-297 C | 80/20 | 13.84 MW | 13.84 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 961121 | AF2-403 | 80/20 | 1.0 MW | 1.0 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315163 | 1KERR 6 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315164 | 1KERR 7 | 80/20 | 1.06 MW | 1.06 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315266 | 1PLYWOOD A | 80/20 | 2.05 MW | 2.05 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316118 | AC1-105 C | 80/20 | 9.08 MW | 9.08 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316131 | AB2-060 C | 80/20 | 1.55 MW | 1.55 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924301 | AB2-077 C O1 | 80/20 | 2.03 MW | 2.03 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924311 | AB2-078 C O1 | 80/20 | 2.03 MW | 2.03 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 924321 | AB2-079 C O1 | 80/20 | 2.03 MW | 2.03 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 925611 | AC1-036 C | 80/20 | 0.25 MW | 0.25 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 925661 | AC1-042 C | 80/20 | 1.99 MW | 1.99 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 932761 | AC2-100 C | 80/20 | 9.12 MW | 9.12 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 938371 | AE1-056 C | 80/20 | 6.68 MW | 6.68 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 939181 | AE1-148 C | 80/20 | 8.21 MW | 8.21 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940081 | AE1-250 C | 80/20 | 13.82 MW | 13.82 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940661 | AE2-053 O1 | 80/20 | 3.04 MW | 3.04 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941431 | AE2-140 C O1 | 80/20 | 14.45 MW | 14.45 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941791 | AE2-182 C | 80/20 | 4.15 MW | 4.15 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941801 | AE2-185 C | 80/20 | 4.49 MW | 4.49 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 941821 | AE2-187 C | 80/20 | 4.49 MW | 4.49 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 946301 | AF1-294 C | 80/20 | 4.22 MW | 4.22 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 957481 | AF2-042 C | 80/20 | 152.55 MW | 152.55 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 958211 | AF2-115 C | 80/20 | 2.57 MW | 2.57 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 926754 | AC1-161 C | Adder | -33.24 MW | -28.25 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934061 | AD1-033 C | Adder | -7.49 MW | -6.37 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 934575 | AD1-082 C | Adder | -6.96 MW | -5.91 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 937221 | AD2-160 C O1 | Adder | -5.64 MW | -4.8 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 942401 | AE2-253 C | Adder | -5.94 MW | -5.05 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943611 | AF1-032 C | Adder | -1.62 MW | -1.38 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 943621 | AF1-033 C | Adder | -2.22 MW | -1.89 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315102 | 1BRUNSWICKG1 | 80/20 | 27.11 MW | 27.11 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315103 | 1BRUNSWICKG2 | 80/20 | 27.11 MW | 27.11 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315104 | 1BRUNSWICKG3 | 80/20 | 27.11 MW | 27.11 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315105 | 1BRUNSWICKS1 | 80/20 | 56.32 MW | 56.32 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315241 | 1Z1-086 GT1 | 80/20 | 34.42 MW | 34.42 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315242 | 1Z1-086 GT2 | 80/20 | 34.42 MW | 34.42 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315243 | 1Z1-086 GT3 | 80/20 | 34.42 MW | 34.42 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 315244 | 1Z1-086 ST | 80/20 | 59.82 MW | 59.82 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316132 | AB2-190 C | Adder | -16.83 MW | -14.31 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 932044 | AC2-012 C | Adder | -8.1 MW | -6.88 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 938741 | AE1-100 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 939431 | AE1-175 C | Adder | -2.17 MW | -1.85 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 940601 | AE2-047 C O1 | 80/20 | 4.29 MW | 4.29 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 957491 | AF2-043 C | Adder | -1.99 MW | -1.69 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962961 | AG1-145 C | Adder | -1.96 MW | -1.67 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 962561 | AG1-105 C O1 | 80/20 | 12.24 MW | 12.24 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 313527 | AB2-043 C | 80/20 | 0.54 MW | 0.54 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316083 | AB2-161 C | Adder | -3.05 MW | -2.6 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | 316123 | AC1-075 C | 80/20 | 1.41 MW | 1.41 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.93 MW | 9.93 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.18 MW | 3.18 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 186.51 MW | 186.51 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.82 MW | 64.82 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.55 MW | 67.55 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 15.03 MW | 15.03 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.82 MW | 15.82 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.85 MW | 0.85 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.18 MW | 3.18 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.25 MW | 9.25 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.13 MW | 2.13 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.57 MW | 0.57 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.73 MW | 12.73 MW |
| 8RAWLINGS-AE2-313 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.55 MW | 1.55 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 962491 | AG1-098 C O1 | 80/20 | 29.22 MW | 29.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964791 | AG1-342 C | 80/20 | 2.13 MW | 2.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 966691 | AG1-539 C | 80/20 | 2.7 MW | 2.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315153 | 1CLOVER1 | 80/20 | 24.48 MW | 24.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315154 | 1CLOVER2 | 80/20 | 24.25 MW | 24.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 926023 | AC1-080 C | 80/20 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927251 | AC1-221 C | 80/20 | 1.5 MW | 1.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 927261 | AC1-222 C | 80/20 | 3.13 MW | 3.13 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934311 | AD1-055 C | 80/20 | 2.17 MW | 2.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934341 | AD1-058 C | 80/20 | 3.77 MW | 3.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934615 | AD1-087 C | 80/20 | 14.18 MW | 14.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934625 | AD1-088 C | 80/20 | 32.77 MW | 32.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 934991 | AD1-131 C | 80/20 | 1.24 MW | 1.24 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 935171 | AD1-152 C O1 | 80/20 | 12.67 MW | 12.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936161 | AD2-022 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936171 | AD2-023 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 937481 | AD2-202 C O1 | 80/20 | 4.15 MW | 4.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942751 | AE2-291 C | 80/20 | 5.17 MW | 5.17 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 942761 | AE2-292 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 943901 | AF1-058 C | 80/20 | 1.76 MW | 1.76 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 960061 | AF2-297 C | 80/20 | 7.05 MW | 7.05 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 316118 | AC1-105 C | 80/20 | 4.0 MW | 4.0 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 932761 | AC2-100 C | 80/20 | 3.46 MW | 3.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 941791 | AE2-182 C | 80/20 | 5.32 MW | 5.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 933501 | AC2-165 C | Adder | -4.29 MW | -3.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958501 | AF2-144 C | Adder | -0.66 MW | -0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 962561 | AG1-105 C O1 | 80/20 | 3.83 MW | 3.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 316123 | AC1-075 C | 80/20 | 0.65 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.86 MW | 1.86 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.7 MW | 32.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.1 MW | 10.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.84 MW | 10.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.82 MW | 2.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.56 MW | 2.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.06 MW | 2.06 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | 50/50 | 7.35 MW | 7.35 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | 50/50 | 4.9 MW | 4.9 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | 50/50 | 6.27 MW | 6.27 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | 50/50 | 9.4 MW | 9.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 6.41 MW | 6.41 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 9.62 MW | 9.62 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | 50/50 | 68.22 MW | 68.22 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | 50/50 | 36.75 MW | 36.75 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 26.9 MW | 26.9 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | 50/50 | 18.32 MW | 18.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | 50/50 | 12.21 MW | 12.21 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | 50/50 | 18.32 MW | 18.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | 50/50 | 12.21 MW | 12.21 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | -4.75 MW | -4.04 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315153 | 1CLOVER1 | 50/50 | 11.06 MW | 11.06 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315154 | 1CLOVER2 | 50/50 | 10.96 MW | 10.96 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 1.19 MW | 1.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 1.19 MW | 1.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.76 MW | 1.5 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.68 MW | 1.43 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.22 MW | 1.04 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.32 MW | 0.27 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.99 MW | 2.54 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.76 MW | 0.65 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | 50/50 | 6.41 MW | 6.41 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | 50/50 | 3.01 MW | 3.01 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | 50/50 | 8.1 MW | 8.1 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | 50/50 | 3.81 MW | 3.81 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.98 MW | 0.83 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.65 MW | 0.56 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | 50/50 | 6.1 MW | 6.1 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | 50/50 | 1.88 MW | 1.88 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | 50/50 | 0.88 MW | 0.88 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 41.44 MW | 41.44 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 27.62 MW | 27.62 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.98 MW | 0.83 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.65 MW | 0.55 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 15.16 MW | 15.16 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 5.89 MW | 5.89 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | 50/50 | 7.07 MW | 7.07 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | 50/50 | 9.77 MW | 9.77 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.91 MW | 3.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.61 MW | 2.21 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | -8.8 MW | -7.48 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | -5.17 MW | -4.39 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.75 MW | 2.34 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.34 MW | 1.14 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 46.41 MW | 46.41 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 20.79 MW | 20.79 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | 50/50 | 1.32 MW | 1.32 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | 50/50 | 0.61 MW | 0.61 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | 50/50 | 50.52 MW | 50.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | 50/50 | 33.68 MW | 33.68 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -4.25 MW | -3.61 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | Adder | -7.31 MW | -6.22 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -1.09 MW | -0.92 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -5.43 MW | -4.62 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315102 | 1BRUNSWICKG1 | 50/50 | 9.64 MW | 9.64 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 9.64 MW | 9.64 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 9.64 MW | 9.64 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 20.03 MW | 20.03 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 12.52 MW | 12.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 12.52 MW | 12.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 12.52 MW | 12.52 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 21.77 MW | 21.77 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 316132 | AB2-190 C | Adder | -7.63 MW | -6.49 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | 50/50 | 27.4 MW | 27.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | 50/50 | 23.48 MW | 23.48 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | 50/50 | 27.4 MW | 27.4 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | 50/50 | 18.26 MW | 18.26 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | 50/50 | 15.65 MW | 15.65 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | 50/50 | 18.26 MW | 18.26 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | Adder | -3.21 MW | -2.73 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 963312 | AG1-180 BAT | Adder | 3.26 MW | 2.77 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 946012 | AF1-266 BAT | 50/50 | 23.74 MW | 23.74 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 940542 | AE2-040 BAT | 50/50 | 5.25 MW | 5.25 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | 940652 | AE2-052 BAT | 50/50 | 4.02 MW | 4.02 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.94 MW | 2.94 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.94 MW | 0.94 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 55.95 MW | 55.95 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 18.77 MW | 18.77 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 19.99 MW | 19.99 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.45 MW | 4.45 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.49 MW | 1.49 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.71 MW | 4.71 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.92 MW | 0.92 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.71 MW | 2.71 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.45 MW | 9.45 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.17 MW | 0.17 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.79 MW | 3.79 MW |
| 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.45 MW | 0.45 MW |
| Details for AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AD1-088 TAP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6BRIERY-6PRINCE EDW 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 32.79 MW | 32.79 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 15.43 MW | 15.43 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 5.33 MW | 5.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.48 MW | 2.48 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6PRINCE EDW-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 29.25 MW | 29.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | Adder | 2.15 MW | 1.82 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | Adder | 1.69 MW | 1.43 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 2.72 MW | 2.31 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 3.65 MW | 3.1 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 29.35 MW | 29.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 19.57 MW | 19.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | -0.54 MW | -0.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 24.52 MW | 24.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 24.29 MW | 24.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.22 MW | 0.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.92 MW | 1.92 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | 50/50 | 1.52 MW | 1.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.99 MW | 2.99 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.18 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.56 MW | 0.56 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | 50/50 | 3.81 MW | 3.81 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | 50/50 | 0.97 MW | 0.97 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 14.2 MW | 14.2 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.66 MW | 6.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | 50/50 | 0.83 MW | 0.83 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.7 MW | 12.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.47 MW | 8.47 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.95 MW | 1.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 5.2 MW | 4.42 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 3.46 MW | 2.94 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 6.47 MW | 5.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 4.31 MW | 3.67 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.77 MW | 1.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.18 MW | 1.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 13.7 MW | 13.7 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 18.91 MW | 18.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.08 MW | 7.08 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 4.72 MW | 4.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.95 MW | 0.95 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.02 MW | 4.02 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | 50/50 | 3.5 MW | 3.5 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | 50/50 | 1.71 MW | 1.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 97.84 MW | 97.84 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 65.22 MW | 65.22 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | Adder | -4.31 MW | -3.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | Adder | -0.67 MW | -0.57 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | Adder | 3.85 MW | 3.27 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | Adder | 2.57 MW | 2.18 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 0.66 MW | 0.66 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 2.19 MW | 2.19 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 0.72 MW | 0.72 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963362 | AG1-185 BAT | Adder | 6.78 MW | 5.77 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964133 | AG1-274 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964113 | AG1-272 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965193 | AG1-384 BAT | Adder | 0.75 MW | 0.64 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964123 | AG1-273 BAT | Adder | 1.75 MW | 1.49 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965832 | AG1-451 BAT | 50/50 | 4.35 MW | 4.35 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 3.87 MW | 3.29 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 9.16 MW | 7.78 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 5.46 MW | 5.46 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958503 | AF2-144 BAT | Adder | 0.77 MW | 0.65 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.91 MW | 1.91 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.58 MW | 33.58 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.39 MW | 10.39 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.15 MW | 11.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.89 MW | 2.89 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.71 MW | 0.71 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.51 MW | 1.51 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.52 MW | 4.52 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| AG1-098 TAP-AD1-088 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961671 | AG1-007 C | Adder | 0.43 MW | 0.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961672 | AG1-007 E | Adder | 0.24 MW | 0.21 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961791 | AG1-021 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961792 | AG1-021 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961891 | AG1-030 C | Adder | 4.85 MW | 4.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961892 | AG1-030 E | Adder | 3.24 MW | 2.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961941 | AG1-037 C | Adder | 0.17 MW | 0.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961942 | AG1-037 E | Adder | 0.11 MW | 0.1 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962331 | AG1-082 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962332 | AG1-082 E | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962341 | AG1-083 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962342 | AG1-083 E | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962491 | AG1-098 C O1 | Adder | 3.4 MW | 2.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962492 | AG1-098 E O1 | Adder | 2.27 MW | 1.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963171 | AG1-166 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963172 | AG1-166 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963181 | AG1-167 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963182 | AG1-167 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963191 | AG1-168 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963192 | AG1-168 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963201 | AG1-169 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963202 | AG1-169 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963211 | AG1-170 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963212 | AG1-170 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963301 | AG1-179 C | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963311 | AG1-180 | Adder | 0.96 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963321 | AG1-181 C O1 | Adder | 5.91 MW | 5.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963361 | AG1-185 O1 | Adder | 2.86 MW | 2.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964111 | AG1-272 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964112 | AG1-272 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964121 | AG1-273 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964122 | AG1-273 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964131 | AG1-274 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964132 | AG1-274 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964241 | AG1-285 C O1 | Adder | 4.66 MW | 3.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964242 | AG1-285 E O1 | Adder | 3.11 MW | 2.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964791 | AG1-342 C | Adder | 1.72 MW | 1.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964792 | AG1-342 E | Adder | 1.36 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964801 | AG1-343 C | Adder | 1.87 MW | 1.59 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964802 | AG1-343 E | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966801 | AG1-551 C | Adder | 0.88 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966802 | AG1-551 E | Adder | 0.38 MW | 0.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966811 | AG1-552 C | Adder | 0.76 MW | 0.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966812 | AG1-552 E | Adder | 0.32 MW | 0.28 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965191 | AG1-384 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965192 | AG1-384 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965291 | AG1-394 C | Adder | 0.64 MW | 0.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965292 | AG1-394 E | Adder | 0.43 MW | 0.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965591 | AG1-427 C | Adder | 4.41 MW | 3.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965592 | AG1-427 E | Adder | 2.95 MW | 2.5 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965601 | AG1-428 C O2 | Adder | 1.64 MW | 1.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965602 | AG1-428 E O2 | Adder | 1.09 MW | 0.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965691 | AG1-437 C O1 | Adder | 3.22 MW | 2.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965692 | AG1-437 E O1 | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965701 | AG1-438 C O1 | Adder | 3.22 MW | 2.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965702 | AG1-438 E O1 | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965711 | AG1-439 C O1 | Adder | 10.5 MW | 8.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965712 | AG1-439 E O1 | Adder | 7.0 MW | 5.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965721 | AG1-440 C | Adder | 3.12 MW | 2.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965722 | AG1-440 E | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965731 | AG1-441 C | Adder | 3.12 MW | 2.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965732 | AG1-441 E | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965741 | AG1-442 O1 | Adder | 1.88 MW | 1.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965751 | AG1-443 O1 | Adder | 1.88 MW | 1.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965761 | AG1-444 O1 | Adder | 5.6 MW | 4.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965771 | AG1-445 | Adder | 1.8 MW | 1.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965781 | AG1-446 | Adder | 1.8 MW | 1.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966621 | AG1-532 C | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966622 | AG1-532 E | Adder | 0.3 MW | 0.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 313506 | AB1-173 C OP | Adder | 2.31 MW | 1.97 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 313853 | 3PONTONDP | Adder | 0.21 MW | 0.18 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 314572 | 3EMPORIA | Adder | 0.14 MW | 0.12 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 314594 | 6PLYMOTH | Adder | 0.03 MW | 0.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315131 | 1EDGECMA | Adder | 3.72 MW | 3.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315132 | 1EDGECMB | Adder | 3.72 MW | 3.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917512 | Z2-088 E OP1 | Adder | 3.47 MW | 2.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918492 | AA1-063AE OP | Adder | 1.38 MW | 1.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918532 | AA1-067 E | Adder | 0.3 MW | 0.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919692 | AA2-053 E OP | Adder | 1.34 MW | 1.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919702 | AA2-057 E OP | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 920042 | AA2-088 E OP | Adder | 3.26 MW | 2.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 920592 | AA2-165 E | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925785 | AC1-054 E | Adder | 1.36 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926051 | AC1-083 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926052 | AC1-083 E O1 | 50/50 | 6.79 MW | 6.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926070 | AC1-086 C | Adder | 7.28 MW | 6.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926071 | AC1-086 E | Adder | 3.31 MW | 2.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926274 | AC1-105 E | Adder | 1.16 MW | 0.98 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927024 | AC1-189 C | Adder | 3.66 MW | 3.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927025 | AC1-189 E | Adder | 1.82 MW | 1.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927145 | AC1-208 C | Adder | 3.64 MW | 3.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927146 | AC1-208 E | Adder | 1.61 MW | 1.37 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927251 | AC1-221 C | 50/50 | 1.61 MW | 1.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927252 | AC1-221 E | 50/50 | 1.61 MW | 1.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927261 | AC1-222 C | Adder | 1.53 MW | 1.3 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927262 | AC1-222 E | Adder | 1.46 MW | 1.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933941 | AD1-017 C | 50/50 | 0.83 MW | 0.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933942 | AD1-017 E | 50/50 | 1.36 MW | 1.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934311 | AD1-055 C | Adder | 1.06 MW | 0.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934312 | AD1-055 E | Adder | 0.27 MW | 0.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934331 | AD1-057 C O1 | Adder | 4.1 MW | 3.48 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934332 | AD1-057 E O1 | Adder | 2.19 MW | 1.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934341 | AD1-058 C | 50/50 | 4.03 MW | 4.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934342 | AD1-058 E | 50/50 | 1.02 MW | 1.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934521 | AD1-076 C | Adder | 16.75 MW | 14.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934522 | AD1-076 E | Adder | 8.53 MW | 7.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934615 | AD1-087 C | Adder | 2.63 MW | 2.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934616 | AD1-087 E | Adder | 1.23 MW | 1.05 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934625 | AD1-088 C | Adder | 3.77 MW | 3.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934626 | AD1-088 E | Adder | 1.77 MW | 1.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934991 | AD1-131 C | 50/50 | 1.32 MW | 1.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934992 | AD1-131 E | 50/50 | 0.88 MW | 0.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935171 | AD1-152 C O1 | Adder | 3.35 MW | 2.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935172 | AD1-152 E O1 | Adder | 2.23 MW | 1.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936161 | AD2-022 C O1 | 50/50 | 10.83 MW | 10.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936162 | AD2-022 E O1 | 50/50 | 6.5 MW | 6.5 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936171 | AD2-023 C O1 | 50/50 | 6.32 MW | 6.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936172 | AD2-023 E O1 | 50/50 | 3.43 MW | 3.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936265 | AD2-033 C | Adder | 4.58 MW | 3.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936266 | AD2-033 E | Adder | 3.05 MW | 2.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937481 | AD2-202 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937482 | AD2-202 E O1 | Adder | 0.36 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943172 | AE2-346 E | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943901 | AF1-058 C | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943902 | AF1-058 E | Adder | 0.57 MW | 0.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 944141 | AF1-082 | Adder | 1.34 MW | 1.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 945811 | AF1-246 C O1 | Adder | 2.36 MW | 2.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 945812 | AF1-246 E O1 | Adder | 3.26 MW | 2.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958801 | AF2-171 C | Adder | 4.69 MW | 3.99 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958802 | AF2-171 E | Adder | 3.13 MW | 2.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 959311 | AF2-222 C | Adder | 5.67 MW | 4.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 959312 | AF2-222 E | Adder | 3.8 MW | 3.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960061 | AF2-297 C | Adder | 3.44 MW | 2.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960062 | AF2-297 E | Adder | 2.29 MW | 1.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960081 | AF2-299 C | Adder | 0.83 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960082 | AF2-299 E | Adder | 0.55 MW | 0.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 244012 | 05PINNACLE | Adder | -2.07 MW | -1.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 244165 | 05FRIES | Adder | -0.27 MW | -0.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315293 | 1DOMTR9 | Adder | 2.25 MW | 1.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315294 | 1DOMTR10 | Adder | 2.76 MW | 2.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316088 | AB2-174 E | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316097 | AB2-100 E1 | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316099 | AB2-100 E2 | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316118 | AC1-105 C | Adder | 2.42 MW | 2.05 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316129 | AC1-054 C | Adder | 2.95 MW | 2.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316140 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316141 | AB2-099 E | Adder | 0.08 MW | 0.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 900672 | V4-068 E | Adder | 0.1 MW | 0.08 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917332 | Z2-043 E | Adder | 0.38 MW | 0.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917342 | Z2-044 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 922923 | AB1-081 E OP | Adder | 1.78 MW | 1.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923262 | AB1-132 C OP | Adder | 4.94 MW | 4.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923263 | AB1-132 E OP | Adder | 2.12 MW | 1.8 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923573 | AB1-173 E OP | Adder | 1.1 MW | 0.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923991 | AB2-040 C O1 | Adder | 2.52 MW | 2.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923992 | AB2-040 E O1 | Adder | 2.06 MW | 1.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924152 | AB2-059 E OP | Adder | 2.53 MW | 2.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924162 | AB2-060 E OP | Adder | 1.62 MW | 1.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924301 | AB2-077 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924302 | AB2-077 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924311 | AB2-078 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924312 | AB2-078 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924321 | AB2-079 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924322 | AB2-079 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925122 | AB2-169 E | Adder | 2.06 MW | 1.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925591 | AC1-034 C | Adder | 3.18 MW | 2.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925592 | AC1-034 E | Adder | 2.4 MW | 2.04 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925612 | AC1-036 E | Adder | 0.54 MW | 0.46 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932761 | AC2-100 C | 50/50 | 3.7 MW | 3.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932762 | AC2-100 E | 50/50 | 1.81 MW | 1.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939181 | AE1-148 C | Adder | 3.76 MW | 3.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939182 | AE1-148 E | Adder | 2.51 MW | 2.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940081 | AE1-250 C | 50/50 | 14.53 MW | 14.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940082 | AE1-250 E | 50/50 | 9.69 MW | 9.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940571 | AE2-044 C | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940572 | AE2-044 E | Adder | 0.89 MW | 0.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940661 | AE2-053 O1 | Adder | 1.39 MW | 1.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941791 | AE2-182 C | Adder | 0.61 MW | 0.52 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941792 | AE2-182 E | Adder | 0.28 MW | 0.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946281 | AF1-292 C | Adder | 0.49 MW | 0.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946282 | AF1-292 E | Adder | 0.33 MW | 0.28 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946301 | AF1-294 C | Adder | 1.28 MW | 1.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946302 | AF1-294 E | Adder | 0.85 MW | 0.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957481 | AF2-042 C | Adder | 16.85 MW | 14.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957482 | AF2-042 E | Adder | 11.23 MW | 9.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957521 | AF2-046 C | Adder | 5.44 MW | 4.63 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957522 | AF2-046 E | Adder | 2.74 MW | 2.33 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957861 | AF2-080 C | Adder | 3.32 MW | 2.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957862 | AF2-080 E | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958211 | AF2-115 C | Adder | 0.78 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958212 | AF2-115 E | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 938741 | AE1-100 C O1 | Adder | -10.74 MW | -9.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933981 | AD1-022 C | Adder | 2.75 MW | 2.34 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933982 | AD1-022 E | Adder | 1.5 MW | 1.27 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960331 | AF2-324 C | Adder | 3.63 MW | 3.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960332 | AF2-324 E | Adder | 1.95 MW | 1.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962561 | AG1-105 C O1 | Adder | 3.66 MW | 3.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962562 | AG1-105 E O1 | Adder | 2.44 MW | 2.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962572 | AG1-106 E | Adder | 0.92 MW | 0.78 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961681 | AG1-008 C | Adder | 5.46 MW | 4.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961682 | AG1-008 E | Adder | 2.73 MW | 2.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962571 | AG1-106 C | Adder | 2.02 MW | 1.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918512 | AA1-065 E OP | Adder | 1.33 MW | 1.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924022 | AB2-043 E O1 | Adder | 1.08 MW | 0.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937493 | AD2-205 BAT | Adder | 0.25 MW | 0.21 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943033 | AE2-326 BAT | Adder | 3.48 MW | 2.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.96 MW | 3.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.17 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.29 MW | 1.29 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.4 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 70.03 MW | 70.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.4 MW | 6.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 6.02 MW | 6.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.66 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.31 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.62 MW | 2.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.37 MW | 0.37 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.43 MW | 0.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.75 MW | 1.75 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6124 | PJM Network Upgrade n6124. Increasing the Danville East Danville 138 kV ci [...] e line. | $8,249,851 | |
| n7754.1 | AEPA0021g : Replace 5 Sub cond 2000 AAC 91 Str at Danville2 138kV station | $0 | |
| n7754.2 | AEPA0021h : Replace 3 Sub cond 2000 AAC 91 Str at East Danville 138kV station | $0 | |
| s2143.2 | Replace 2000A non-oil breaker on the 05EDAN 1-05DANVL2 138 kV line | $0 | |
| n7754.3 | The Danville - East Danville 138 kV Circuit will require higher capacity conductor to obtain a rating higher than the 482 MVA achieved by the initial rebuild to 1272 ACSR by AD1-152 . | $456,572 | |
| (TBD) | Temporary Bremo transformer #7 to remain in service. Ratings are 290/290/332 MVA. | $0 | |
| n7016 | Reconductor 3.9 miles of 115 kV Line 31 from Grit DP to Otter River with 768.2 ACSS 250 | $2,340,000 | |
| n7015 | Reconductor 8.5 miles of 115 kV Line 31 from Grit to AE2-291 Tap with 768.2 ACSS 250 C. | $5,100,000 | |
| n8244 | Rebuild 230 kV Line #2068 | $25,450,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n6219 | Rebuild 15.51 miles of 230 kV Line 298 from Buckingham to Bremo with 2-636 ACSR. | $23,265,000 | |
| n6245 | Rebuild 12.76 miles of 230 kV Line 298 from Buckingham to Farmville with 2-768.2 ACSS 250 C. Replace Line Lead, Line Switch, Relay (CT), Wave trap at Farmville terminal | $19,710,000 | |
| b3694.7 | Energize in-service spare 500-230 kV Carson Tx#1 | $1,000,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n8453 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with 2-636 ACSR. | $7,500,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n8156 | Rebuild 12.1 miles of 230 kV Line 2028 from Mount Eagle to AF2-397 Tap with 2-636 ACSR. | $18,150,000 | |
| n6449 | For DEV portion, rebuild 2 miles of 230 kV Line 296 from AC1-221 Tap to Persons DEP with 2-636 ACSR. | $3,000,000 | |
| (TBD) | Reconductor 5 miles with double 795 ACSS-TW per phase, replace disconnect switches | $22,500,000 | |
| n7181 | Rebuild 5.7 miles of 230 kV Line 235 from Briery to Prince EDW with 2-636 ACSR. | $8,550,000 | |
| n7180 | Rebuild 7.2 miles of 230 kV Line 235 from Prince EDW to Farmville with 2-636 ACSR. | $10,800,000 | |
| n6215 | Rebuild 2 miles of the AC1-221 Tap – Sedge Hill 230 kV line#33. | $3,000,000 | |
| n6539 | Build new 500 kV Line from Rawlings to Morrisville Substation 110 miles | $400,000,000 | |
| n8262 | Rebuild 500 kV Line #511 from Rawlings to AE2-313 Tap. | $19,220,000 | |
| n7020 | Rebuild 5.8 miles of 230 kV line 235 from AD1-088 Tap to Briery with 2-636 ACSR. | $8,700,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-098 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.