AG1-011 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:44
Colonial Trail 230 kV
160.0 MW Capacity / 160.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-011 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the Dominion zone — Surry County, Virginia. The installed facilities will have a total capability of 160.0 MW with 160.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-011 |
| Project Name | Colonial Trail 230 kV |
| Developer Name | Urban Grid Solar Projects, LLC |
| State | Virginia |
| County | Surry |
| Transmission Owner | Dominion |
| MFO | 160.0 MW |
| MWE | 160.0 MW |
| MWC | 160.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-011 "Colonial Trial 230 kV" will interconnect with the Dominion transmission system.
Summer Peak Analysis
The Queue Project was evaluated as a 160.0 MW (Capacity 160.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 153.58 % | 155.28 % | 2442.12 | B | 3792.12 | 50.91 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P1-2: LN 211
CONTINGENCY 'DVP_P1-2: LN 211' OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 SET PRECONTRATING 797 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 END |
Single | AC | 140.59 % | 153.43 % | 449.32 | B | 689.38 | 59.76 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P1-2: LN 259
CONTINGENCY 'DVP_P1-2: LN 259' OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1 /*6BASIN 230.0 - 6CHESTF B 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1 230.0 - 6CHESTF B 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1 230.0 - 6CHESTF B 230.0 END |
Single | AC | 143.2 % | 151.58 % | 449.32 | B | 681.08 | 41.32 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P1-2: LN 228
CONTINGENCY 'DVP_P1-2: LN 228' OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1 /*6CHESTF A 230.0 - 6HOPEWLL 230.0 END |
Single | AC | 143.83 % | 149.56 % | 449.32 | B | 671.99 | 62.05 | |
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 135.7 % | 136.76 % | 2442.12 | B | 3339.87 | 42.29 | |
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 134.92 % | 136.33 % | 663.64 | B | 904.74 | 16.37 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P1-2: LN 208
CONTINGENCY 'DVP_P1-2: LN 208' OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1 /*6CHESTF A 230.0 - 6IRON208 230.0 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1 /*6IRON208 230.0 - 6SOUWEST 230.0 OPEN BUS 314309 /*6IRON208 230.0 END |
Single | AC | 128.26 % | 136.71 % | 449.32 | B | 614.27 | 42.89 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
Base Case | Single | AC | 118.65 % | 126.33 % | 449.32 | A | 567.6 | 37.88 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 574
CONTINGENCY 'DVP_P1-2: LN 574' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET POSTCONTRATING 2831 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 110.27 % | 111.08 % | 3220.44 | B | 3577.1 | 41.43 | |
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P1-2: LN 552
CONTINGENCY 'DVP_P1-2: LN 552' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET POSTCONTRATING 2078 BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 1905 BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Single | AC | 109.87 % | 110.62 % | 3220.44 | B | 3562.39 | 32.84 | |
| DVP |
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
314934 to 314916 ckt 1 |
DVP_P1-2: LN 581
CONTINGENCY 'DVP_P1-2: LN 581' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 109.64 % | 110.41 % | 3220.44 | B | 3555.56 | 32.34 | |
| DVP |
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1 |
DVP_P1-2: LN 581
CONTINGENCY 'DVP_P1-2: LN 581' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 114.15 % | 114.57 % | 2442.12 | B | 2797.84 | 27.21 | |
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P1-2: LN 581
CONTINGENCY 'DVP_P1-2: LN 581' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 106.09 % | 106.89 % | 3220.44 | B | 3442.2 | 33.53 | |
| DVP |
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
314911 to 314922 ckt 1 |
DVP_P1-2: LN 594
CONTINGENCY 'DVP_P1-2: LN 594' OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA 500.0 - 8SPOTSYL 500.0 END |
Single | AC | 111.35 % | 111.95 % | 2442.12 | B | 2734.03 | 25.47 | |
| DVP |
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
314918 to 314934 ckt 1 |
DVP_P1-2: LN 552
CONTINGENCY 'DVP_P1-2: LN 552' OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1 /*3CHANCE 115.0 - 8CHANCE 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET POSTCONTRATING 2078 BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET PRECONTRATING 1905 BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 END |
Single | AC | 104.36 % | 105.16 % | 3220.44 | B | 3386.65 | 32.91 | |
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Single | AC | 99.4 % | 100.16 % | 2442.12 | B | 2446.1 | 24.7 | |
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 217
CONTINGENCY 'DVP_P1-2: LN 217' OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1 /*6CHARCTY 230.0 - 6LAKESIDE 230.0 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1 /*6CHARCTY 230.0 - 6VARINA 230.0 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA 230.0 - 6CHESTF B 230.0 OPEN BUS 314225 /*6CHARCTY 230.0 OPEN BUS 314260 /*6VARINA 230.0 END |
Single | AC | 104.67 % | 107.53 % | 663.64 | B | 713.65 | 19.51 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
Base Case | Single | AC | 101.11 % | 109.84 % | 449.32 | A | 493.52 | 39.94 | |
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 185.12 % | 185.96 % | 1050.6 | C | 1953.71 | 34.52 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P4-2: 211T2124
CONTINGENCY 'DVP_P4-2: 211T2124' OPEN BRANCH FROM BUS 314269 TO BUS 314291 CKT 1 /*6PRGEORG 230.0 - 3PRGEORG 115.0 OPEN BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 OPEN BUS 314269 /*6PRGEORG 230.0 END |
Breaker | AC | 156.5 % | 166.73 % | 549.0 | C | 915.35 | 68.04 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 182.51 % | 189.56 % | 549.0 | C | 1040.71 | 38.75 | |
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P4-2: 57602
CONTINGENCY 'DVP_P4-2: 57602' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 155.59 % | 155.7 % | 3351.0 | C | 5217.61 | 50.89 | |
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P4-2: WT576
CONTINGENCY 'DVP_P4-2: WT576' OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2 /*6NO ANNA 230.0 - 8NO ANNA 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 155.59 % | 155.7 % | 3351.0 | C | 5217.57 | 50.89 | |
| DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 113.33 % | 113.49 % | 3637.0 | C | 4127.49 | 37.1 | |
| DVP |
6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer
314286 to 314284 ckt 1 |
DVP_P4-2: 208T287
CONTINGENCY 'DVP_P4-2: 208T287' OPEN BRANCH FROM BUS 314214 TO BUS 314286 CKT 1 /*6CHCKAHM 230.0 - 6CHESTF A 230.0 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1 /*6CHESTF A 230.0 - 6IRON208 230.0 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1 /*6IRON208 230.0 - 6SOUWEST 230.0 OPEN BUS 314309 /*6IRON208 230.0 END |
Breaker | AC | 110.93 % | 113.36 % | 284.8 | C | 322.84 | 8.08 | |
| DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 112.82 % | 112.96 % | 3637.0 | C | 4108.21 | 40.98 | |
| DVP |
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
314287 to 314260 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 101.59 % | 101.87 % | 1204.0 | C | 1226.49 | 16.38 | |
| DVP |
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
314260 to 314225 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 101.28 % | 101.57 % | 1204.0 | C | 1222.87 | 16.38 | |
| DVP |
AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line
935160 to 314303 ckt 1 |
DVP_P4-2: 240T2041
CONTINGENCY 'DVP_P4-2: 240T2041' OPEN BRANCH FROM BUS 314303 TO BUS 925330 CKT 2 /*6HOPEWLL 230.0 - AB2-190 TAP 230.0 OPEN BRANCH FROM BUS 942550 TO BUS 925330 CKT 2 /*AE2-270 TAP 230.0 - AB2-190 TAP 230.0 OPEN BUS 315077 /*1HOPHCF1 13.8 OPEN BUS 315078 /*1HOPHCF2 13.8 OPEN BUS 315079 /*1HOPHCF3 13.8 OPEN BUS 315080 /*1HOPHCF4 13.8 OPEN BUS 316132 /*AB2-190 C 230.0 OPEN BUS 925332 /*AB2-190 E 230.0 END |
Breaker | AC | 109.84 % | 119.58 % | 830.0 | C | 992.5 | 80.83 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P7-1: LN 212-240-D
CONTINGENCY 'DVP_P7-1: LN 212-240-D' OPEN BRANCH FROM BUS 313896 TO BUS 314538 CKT 1 /*6COLONIAL TR 230.0 - 6SURRY 230.0 OPEN BRANCH FROM BUS 961610 TO BUS 314538 CKT 2 /*AG1-000B TAP 230.0 - 6SURRY 230.0 END |
Tower | AC | 147.56 % | 159.59 % | 549.0 | C | 876.13 | 71.77 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P7-1: LN 212-240-C
CONTINGENCY 'DVP_P7-1: LN 212-240-C' OPEN BRANCH FROM BUS 313896 TO BUS 314538 CKT 1 /*6COLONIAL TR 230.0 - 6SURRY 230.0 OPEN BRANCH FROM BUS 961610 TO BUS 942550 CKT 2 /*AG1-000B TAP 230.0 - AE2-270 TAP 230.0 END |
Tower | AC | 140.87 % | 153.38 % | 549.0 | C | 842.07 | 71.77 | |
| DVP |
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
314269 to 314291 ckt 1 |
DVP_P7-1: LN 211-228
CONTINGENCY 'DVP_P7-1: LN 211-228' OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1 /*6CHESTF A 230.0 - 6HOPEWLL 230.0 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 END |
Tower | AC | 127.07 % | 137.33 % | 287.5 | C | 394.83 | 30.43 | |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961941 | AG1-037 C | Adder | 0.81 MW | 0.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962331 | AG1-082 C | Adder | 3.25 MW | 2.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962341 | AG1-083 C | Adder | 3.25 MW | 2.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | Adder | 8.25 MW | 7.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | Adder | 8.33 MW | 7.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963291 | AG1-178 C O2 | Adder | 95.92 MW | 81.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 O2 | Adder | 51.68 MW | 43.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | Adder | 9.65 MW | 8.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965291 | AG1-394 C | Adder | 3.31 MW | 2.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965691 | AG1-437 C O1 | Adder | 16.59 MW | 14.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965701 | AG1-438 C O1 | Adder | 16.59 MW | 14.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | Adder | 9.68 MW | 8.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | Adder | 9.68 MW | 8.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | Adder | 34.38 MW | 29.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966361 | AG1-505 C | Adder | 24.56 MW | 20.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966371 | AG1-506 C | Adder | 24.56 MW | 20.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966621 | AG1-532 C | Adder | 2.15 MW | 1.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 313506 | AB1-173 C OP | Adder | 10.6 MW | 9.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314572 | 3EMPORIA | Adder | 0.66 MW | 0.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926070 | AC1-086 C | Adder | 32.51 MW | 27.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934521 | AD1-076 C | Adder | 89.82 MW | 76.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942931 | AE2-313 C | Adder | 53.03 MW | 45.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943171 | AE2-346 C | Adder | 2.27 MW | 1.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | Adder | 19.19 MW | 16.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 960081 | AF2-299 C | Adder | 3.98 MW | 3.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315293 | 1DOMTR9 | Adder | 11.14 MW | 9.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315294 | 1DOMTR10 | Adder | 13.65 MW | 11.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316140 | AB2-099 C | Adder | 0.95 MW | 0.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923262 | AB1-132 C OP | Adder | 22.07 MW | 18.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 923991 | AB2-040 C O1 | Adder | 11.54 MW | 9.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940491 | AE2-034 C | Adder | 12.03 MW | 10.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | Adder | 58.73 MW | 49.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946281 | AF1-292 C | Adder | 2.36 MW | 2.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957521 | AF2-046 C | Adder | 27.28 MW | 23.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957531 | AF2-047 C | Adder | 28.58 MW | 24.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938771 | AE1-103 C | Adder | 4.93 MW | 4.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940481 | AE2-033 C | Adder | 25.59 MW | 21.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940641 | AE2-051 C O1 | Adder | 26.72 MW | 22.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | Adder | 21.42 MW | 18.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314229 | 6MT RD221 | 80/20 | 0.23 MW | 0.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314236 | 6NRTHEST | 80/20 | 0.35 MW | 0.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314241 | 6OLDCHRC | 80/20 | 1.6 MW | 1.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314250 | 6ROCKVILLE | 80/20 | 0.6 MW | 0.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314309 | 6IRON208 | 80/20 | 0.82 MW | 0.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 314421 | 6WINCHST | 80/20 | 0.25 MW | 0.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315060 | 1CHESTF5 | 80/20 | 114.17 MW | 114.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315061 | 1CHESTG7 | 80/20 | 7.26 MW | 7.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315062 | 1CHESTS7 | 80/20 | 3.33 MW | 3.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315063 | 1CHESTG8 | 80/20 | 7.14 MW | 7.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315064 | 1CHESTS8 | 80/20 | 3.68 MW | 3.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | 80/20 | 180.35 MW | 180.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315067 | 1DARBY 1 | 80/20 | 4.79 MW | 4.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315068 | 1DARBY 2 | 80/20 | 4.79 MW | 4.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315069 | 1DARBY 3 | 80/20 | 4.81 MW | 4.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315070 | 1DARBY 4 | 80/20 | 4.82 MW | 4.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315076 | 1HOPPOLC | 80/20 | 2.89 MW | 2.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315077 | 1HOPHCF1 | 80/20 | 4.52 MW | 4.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315078 | 1HOPHCF2 | 80/20 | 4.52 MW | 4.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315079 | 1HOPHCF3 | 80/20 | 4.52 MW | 4.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315080 | 1HOPHCF4 | 80/20 | 6.86 MW | 6.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | Adder | 18.29 MW | 15.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | Adder | 18.29 MW | 15.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315092 | 1YORKTN3 | 80/20 | 43.31 MW | 43.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 925863 | AC1-065 C | Adder | 10.45 MW | 8.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926754 | AC1-161 C | 80/20 | 53.78 MW | 53.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 926784 | AC1-164 C | 80/20 | 73.91 MW | 73.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927044 | AC1-191 C | Adder | 16.47 MW | 14.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 927225 | AC1-216 C | 80/20 | 2.97 MW | 2.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934014 | AD1-025 C | 80/20 | 29.98 MW | 29.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934061 | AD1-033 C | Adder | 13.12 MW | 11.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934141 | AD1-041 C | Adder | 8.93 MW | 7.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 934575 | AD1-082 C | Adder | 13.37 MW | 11.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 935164 | AD1-151 C | 80/20 | 28.68 MW | 28.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936151 | AD2-021 | 80/20 | 0.07 MW | 0.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936661 | AD2-085 C | Adder | 5.95 MW | 5.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 936761 | AD2-097 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 937221 | AD2-160 C O1 | Adder | 10.19 MW | 8.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942151 | AE2-227 C | 80/20 | 3.9 MW | 3.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942161 | AE2-228 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942341 | AE2-247 C | Adder | 2.58 MW | 2.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942371 | AE2-250 C O1 | Adder | 16.86 MW | 14.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942401 | AE2-253 C | Adder | 10.72 MW | 9.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | 80/20 | 47.76 MW | 47.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943431 | AF1-014 C | Adder | 2.17 MW | 1.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943461 | AF1-017 C | Adder | 2.33 MW | 1.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943471 | AF1-018 | Adder | 12.17 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943611 | AF1-032 C | Adder | 3.02 MW | 2.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 943621 | AF1-033 C | 80/20 | 4.19 MW | 4.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944631 | AF1-128 O1 | 80/20 | 71.44 MW | 71.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944871 | AF1-152 C | Adder | 9.08 MW | 7.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 945361 | AF1-201 C O1 | Adder | 28.2 MW | 23.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | 80/20 | 50.91 MW | 50.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966871 | AG1-558 C | Adder | 4.1 MW | 3.49 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315116 | 1SURRY 1 | 80/20 | 45.59 MW | 45.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315120 | 1GRAVEL4 | 80/20 | 4.69 MW | 4.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315122 | 1GRAVEL6 | 80/20 | 4.68 MW | 4.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315233 | 1SURRY 2 | 80/20 | 47.38 MW | 47.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316033 | AB2-134 C | 80/20 | 3.89 MW | 3.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316075 | AC2-137 C | 80/20 | 0.65 MW | 0.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316108 | AB2-160 C | Adder | 9.49 MW | 8.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316132 | AB2-190 C | 80/20 | 33.45 MW | 33.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932044 | AC2-012 C | Adder | 14.06 MW | 11.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 932591 | AC2-079 C O1 | Adder | 9.94 MW | 8.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 938535 | AE1-072 C | Adder | 30.49 MW | 25.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939195 | AE1-149 C | Adder | 18.56 MW | 15.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939414 | AE1-173_C1 | Adder | 50.54 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939415 | AE1-173_C2 | Adder | 43.32 MW | 36.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939416 | AE1-173_C3 | Adder | 50.54 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939431 | AE1-175 C | 80/20 | 4.36 MW | 4.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 939611 | AE1-191 C | Adder | 17.86 MW | 15.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940231 | AE2-005 C | Adder | 2.29 MW | 1.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940431 | AE2-027 C O1 | Adder | 22.71 MW | 19.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | Adder | 4.55 MW | 3.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940551 | AE2-041 | Adder | 12.17 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 6.19 MW | 5.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941101 | AE2-104 C O1 | Adder | 5.8 MW | 4.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 49.71 MW | 42.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 51.09 MW | 43.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 46.45 MW | 39.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946261 | AF1-291 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957491 | AF2-043 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957601 | AF2-054 C | Adder | 3.51 MW | 2.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 6.27 MW | 5.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957711 | AF2-065 C | 80/20 | 24.36 MW | 24.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962531 | AG1-102 C | Adder | 1.9 MW | 1.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962961 | AG1-145 C | 80/20 | 3.93 MW | 3.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963221 | AG1-171 C | 80/20 | 3.82 MW | 3.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963231 | AG1-172 C | 80/20 | 3.82 MW | 3.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963241 | AG1-173 C | 80/20 | 3.82 MW | 3.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963251 | AG1-174 C | 80/20 | 3.82 MW | 3.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 O1 | Adder | 39.83 MW | 33.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 12.55 MW | 10.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933294 | AC2-141 C | 80/20 | 53.78 MW | 53.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941501 | AE2-147 C | Adder | 27.24 MW | 23.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941581 | AE2-155 C | 80/20 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 31.37 MW | 26.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942001 | AE2-212 C | Adder | 3.75 MW | 3.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957831 | AF2-077 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957871 | AF2-081 C | Adder | 17.36 MW | 14.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | Adder | 5.92 MW | 5.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958161 | AF2-110 C | Adder | 2.39 MW | 2.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966611 | AG1-531 C | 80/20 | 10.35 MW | 10.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 83.97 MW | 71.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 83.97 MW | 71.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 83.97 MW | 71.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 933981 | AD1-022 C | Adder | 14.4 MW | 12.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961681 | AG1-008 C | Adder | 27.33 MW | 23.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962271 | AG1-075 C O1 | Adder | 29.1 MW | 24.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962571 | AG1-106 C | Adder | 9.04 MW | 7.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965281 | AG1-393 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 316083 | AB2-161 C | Adder | 5.87 MW | 4.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | 80/20 | 28.23 MW | 28.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.39 MW | 8.39 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.2 MW | 3.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 160.6 MW | 160.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.79 MW | 71.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.69 MW | 68.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.7 MW | 12.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.51 MW | 15.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.77 MW | 0.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.64 MW | 3.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.9 MW | 9.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.98 MW | 3.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.63 MW | 0.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.63 MW | 12.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.72 MW | 1.72 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 314507 | 3THOMPSN | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315076 | 1HOPPOLC | 80/20 | 4.96 MW | 4.96 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315077 | 1HOPHCF1 | 80/20 | 7.75 MW | 7.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315078 | 1HOPHCF2 | 80/20 | 7.75 MW | 7.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315079 | 1HOPHCF3 | 80/20 | 7.75 MW | 7.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315080 | 1HOPHCF4 | 80/20 | 11.76 MW | 11.76 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 926661 | AC1-147 C | 80/20 | 0.19 MW | 0.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 927225 | AC1-216 C | 80/20 | 3.49 MW | 3.49 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 934014 | AD1-025 C | 80/20 | 35.18 MW | 35.18 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 934575 | AD1-082 C | 80/20 | 5.13 MW | 5.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 935111 | AD1-144 C | 80/20 | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 935164 | AD1-151 C | 80/20 | 37.43 MW | 37.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 936661 | AD2-085 C | 80/20 | 1.79 MW | 1.79 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 942341 | AE2-247 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 942551 | AE2-270 | 80/20 | 58.44 MW | 58.44 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 943461 | AF1-017 C | 80/20 | 0.7 MW | 0.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 943621 | AF1-033 C | 80/20 | 2.73 MW | 2.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 961711 | AG1-011 | 80/20 | 59.76 MW | 59.76 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315098 | 1CHESPKA | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315099 | 1CHESPKB | 80/20 | 0.38 MW | 0.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315110 | 1ELIZAR3 | 80/20 | 1.64 MW | 1.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315116 | 1SURRY 1 | 80/20 | 33.26 MW | 33.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315117 | 1GRAVELC | 80/20 | 1.17 MW | 1.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315119 | 1GRAVEL3 | 80/20 | 3.38 MW | 3.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315120 | 1GRAVEL4 | 80/20 | 3.42 MW | 3.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315121 | 1GRAVEL5 | 80/20 | 3.38 MW | 3.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315122 | 1GRAVEL6 | 80/20 | 3.42 MW | 3.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315260 | 1GOSPORTA | 80/20 | 0.18 MW | 0.18 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315261 | 1GOSPORTB | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315262 | 1GOSPORTC | 80/20 | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 316033 | AB2-134 C | 80/20 | 4.57 MW | 4.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 316132 | AB2-190 C | 80/20 | 42.98 MW | 42.98 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 316258 | AE1-162 C | 80/20 | 0.36 MW | 0.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 932044 | AC2-012 C | 80/20 | 4.01 MW | 4.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 932591 | AC2-079 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 939195 | AE1-149 C | 80/20 | 7.55 MW | 7.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 940651 | AE2-052 | 80/20 | 2.52 MW | 2.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 957631 | AF2-057 | 80/20 | 1.79 MW | 1.79 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 957711 | AF2-065 C | 80/20 | 29.8 MW | 29.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 963221 | AG1-171 C | 80/20 | 4.48 MW | 4.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 963231 | AG1-172 C | 80/20 | 4.48 MW | 4.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 963241 | AG1-173 C | 80/20 | 4.48 MW | 4.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 963251 | AG1-174 C | 80/20 | 4.48 MW | 4.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 965001 | AG1-364 C O1 | 80/20 | 3.55 MW | 3.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941591 | AE2-156 O1 | 80/20 | 8.86 MW | 8.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 966611 | AG1-531 C | 80/20 | 4.77 MW | 4.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 316083 | AB2-161 C | 80/20 | 2.25 MW | 2.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 961611 | AG1-000B C | 80/20 | 23.38 MW | 23.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.84 MW | 0.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.01 MW | 14.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.97 MW | 0.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.01 MW | 3.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.28 MW | 1.28 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.83 MW | 0.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.67 MW | 0.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 966621 | AG1-532 C | 80/20 | 0.54 MW | 0.54 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 960081 | AF2-299 C | 80/20 | 0.99 MW | 0.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 946281 | AF1-292 C | 80/20 | 0.59 MW | 0.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 938771 | AE1-103 C | 80/20 | 1.13 MW | 1.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 940481 | AE2-033 C | 80/20 | 7.96 MW | 7.96 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 946011 | AF1-266 | 80/20 | 6.67 MW | 6.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 314314 | 3LOCKS | 80/20 | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 314435 | 6SAPONY | 80/20 | 0.21 MW | 0.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 314507 | 3THOMPSN | 80/20 | 0.13 MW | 0.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315065 | 1CHESTF6 | 80/20 | 109.91 MW | 109.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315076 | 1HOPPOLC | 80/20 | 3.43 MW | 3.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315077 | 1HOPHCF1 | 80/20 | 5.36 MW | 5.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315078 | 1HOPHCF2 | 80/20 | 5.36 MW | 5.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315079 | 1HOPHCF3 | 80/20 | 5.36 MW | 5.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315080 | 1HOPHCF4 | 80/20 | 8.13 MW | 8.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 926661 | AC1-147 C | 80/20 | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 927225 | AC1-216 C | 80/20 | 2.41 MW | 2.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 934014 | AD1-025 C | 80/20 | 24.33 MW | 24.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 934575 | AD1-082 C | 80/20 | 6.24 MW | 6.24 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 935111 | AD1-144 C | 80/20 | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 935164 | AD1-151 C | 80/20 | 25.88 MW | 25.88 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 936661 | AD2-085 C | 80/20 | 1.83 MW | 1.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 942161 | AE2-228 C | 80/20 | 2.22 MW | 2.22 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 942341 | AE2-247 C | 80/20 | 0.8 MW | 0.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 942371 | AE2-250 C O1 | 80/20 | 5.07 MW | 5.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 942551 | AE2-270 | 80/20 | 40.41 MW | 40.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 943461 | AF1-017 C | 80/20 | 0.72 MW | 0.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 943621 | AF1-033 C | 80/20 | 1.87 MW | 1.87 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 961711 | AG1-011 | 80/20 | 41.32 MW | 41.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315098 | 1CHESPKA | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315099 | 1CHESPKB | 80/20 | 0.28 MW | 0.28 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315116 | 1SURRY 1 | 80/20 | 23.0 MW | 23.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315117 | 1GRAVELC | 80/20 | 0.81 MW | 0.81 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315119 | 1GRAVEL3 | 80/20 | 2.34 MW | 2.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315120 | 1GRAVEL4 | 80/20 | 2.37 MW | 2.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315121 | 1GRAVEL5 | 80/20 | 2.34 MW | 2.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315122 | 1GRAVEL6 | 80/20 | 2.36 MW | 2.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315260 | 1GOSPORTA | 80/20 | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315261 | 1GOSPORTB | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 315262 | 1GOSPORTC | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316033 | AB2-134 C | 80/20 | 3.16 MW | 3.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316096 | AB2-100 C1 | 80/20 | 0.43 MW | 0.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316098 | AB2-100 C2 | 80/20 | 0.43 MW | 0.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316108 | AB2-160 C | 80/20 | 2.85 MW | 2.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316132 | AB2-190 C | 80/20 | 29.72 MW | 29.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316258 | AE1-162 C | 80/20 | 0.25 MW | 0.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 932044 | AC2-012 C | 80/20 | 2.98 MW | 2.98 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 932591 | AC2-079 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 939195 | AE1-149 C | 80/20 | 9.49 MW | 9.49 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 940541 | AE2-040 | 80/20 | 1.44 MW | 1.44 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 940651 | AE2-052 | 80/20 | 3.16 MW | 3.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 941101 | AE2-104 C O1 | 80/20 | 1.36 MW | 1.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 946261 | AF1-291 C | 80/20 | 2.25 MW | 2.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 957631 | AF2-057 | 80/20 | 1.33 MW | 1.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 957711 | AF2-065 C | 80/20 | 20.61 MW | 20.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 963221 | AG1-171 C | 80/20 | 3.1 MW | 3.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 963231 | AG1-172 C | 80/20 | 3.1 MW | 3.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 963241 | AG1-173 C | 80/20 | 3.1 MW | 3.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 963251 | AG1-174 C | 80/20 | 3.1 MW | 3.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 965001 | AG1-364 C O1 | 80/20 | 2.64 MW | 2.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 942001 | AE2-212 C | 80/20 | 1.93 MW | 1.93 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 958161 | AF2-110 C | 80/20 | 0.56 MW | 0.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 966611 | AG1-531 C | 80/20 | 3.11 MW | 3.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 962271 | AG1-075 C O1 | 80/20 | 8.75 MW | 8.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 965281 | AG1-393 C | 80/20 | 1.1 MW | 1.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 316083 | AB2-161 C | 80/20 | 2.74 MW | 2.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | 961611 | AG1-000B C | 80/20 | 16.17 MW | 16.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.1 MW | 1.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.26 MW | 0.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.92 MW | 18.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.87 MW | 3.87 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.36 MW | 5.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.67 MW | 1.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.34 MW | 1.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.65 MW | 0.65 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.08 MW | 1.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 259 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 314421 | 6WINCHST | 80/20 | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 314507 | 3THOMPSN | 80/20 | 0.18 MW | 0.18 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315076 | 1HOPPOLC | 80/20 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315077 | 1HOPHCF1 | 80/20 | 8.01 MW | 8.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315078 | 1HOPHCF2 | 80/20 | 8.01 MW | 8.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315079 | 1HOPHCF3 | 80/20 | 8.01 MW | 8.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315080 | 1HOPHCF4 | 80/20 | 12.15 MW | 12.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 926661 | AC1-147 C | 80/20 | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 927225 | AC1-216 C | 80/20 | 3.62 MW | 3.62 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 934014 | AD1-025 C | 80/20 | 36.53 MW | 36.53 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 935111 | AD1-144 C | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 935164 | AD1-151 C | 80/20 | 38.81 MW | 38.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 942551 | AE2-270 | 80/20 | 60.64 MW | 60.64 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 943621 | AF1-033 C | 80/20 | 2.9 MW | 2.9 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 961711 | AG1-011 | 80/20 | 62.05 MW | 62.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315098 | 1CHESPKA | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315099 | 1CHESPKB | 80/20 | 0.39 MW | 0.39 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315108 | 1ELIZAR1 | 80/20 | 1.66 MW | 1.66 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315110 | 1ELIZAR3 | 80/20 | 1.69 MW | 1.69 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315116 | 1SURRY 1 | 80/20 | 34.85 MW | 34.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315117 | 1GRAVELC | 80/20 | 1.22 MW | 1.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315119 | 1GRAVEL3 | 80/20 | 3.54 MW | 3.54 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315120 | 1GRAVEL4 | 80/20 | 3.58 MW | 3.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315121 | 1GRAVEL5 | 80/20 | 3.54 MW | 3.54 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315122 | 1GRAVEL6 | 80/20 | 3.58 MW | 3.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315260 | 1GOSPORTA | 80/20 | 0.19 MW | 0.19 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315261 | 1GOSPORTB | 80/20 | 0.24 MW | 0.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315262 | 1GOSPORTC | 80/20 | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 316033 | AB2-134 C | 80/20 | 4.74 MW | 4.74 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 316132 | AB2-190 C | 80/20 | 44.58 MW | 44.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 316258 | AE1-162 C | 80/20 | 0.38 MW | 0.38 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 932044 | AC2-012 C | 80/20 | 4.13 MW | 4.13 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 957631 | AF2-057 | 80/20 | 1.84 MW | 1.84 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 957711 | AF2-065 C | 80/20 | 30.93 MW | 30.93 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 963221 | AG1-171 C | 80/20 | 4.65 MW | 4.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 963231 | AG1-172 C | 80/20 | 4.65 MW | 4.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 963241 | AG1-173 C | 80/20 | 4.65 MW | 4.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 963251 | AG1-174 C | 80/20 | 4.65 MW | 4.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 965001 | AG1-364 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941591 | AE2-156 O1 | 80/20 | 9.13 MW | 9.13 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 966611 | AG1-531 C | 80/20 | 5.28 MW | 5.28 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 961611 | AG1-000B C | 80/20 | 24.43 MW | 24.43 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.45 MW | 0.45 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.84 MW | 6.84 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.26 MW | 0.26 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.68 MW | 0.68 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.09 MW | 0.09 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.16 MW | 0.16 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.69 MW | 0.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 2.75 MW | 2.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 2.75 MW | 2.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 7.0 MW | 5.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | Adder | 7.07 MW | 6.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | Adder | 81.81 MW | 69.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | Adder | 44.07 MW | 37.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | Adder | 8.16 MW | 6.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | Adder | 2.8 MW | 2.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | Adder | 14.12 MW | 12.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | Adder | 14.12 MW | 12.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | Adder | 8.24 MW | 7.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | Adder | 8.24 MW | 7.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | Adder | 29.17 MW | 24.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 20.75 MW | 17.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 20.75 MW | 17.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | Adder | 1.79 MW | 1.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | 8.84 MW | 7.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | Adder | 0.55 MW | 0.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | Adder | 27.29 MW | 23.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 76.6 MW | 65.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | Adder | 44.99 MW | 38.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 1.93 MW | 1.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | Adder | 16.3 MW | 13.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | Adder | 3.31 MW | 2.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 9.49 MW | 8.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 11.63 MW | 9.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.8 MW | 0.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | 18.53 MW | 15.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | 9.63 MW | 8.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 10.27 MW | 8.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | Adder | 49.89 MW | 42.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | Adder | 1.96 MW | 1.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 23.1 MW | 19.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 24.41 MW | 20.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | Adder | 4.19 MW | 3.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | Adder | 21.22 MW | 18.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | Adder | 22.83 MW | 19.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | Adder | 17.76 MW | 15.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314229 | 6MT RD221 | 80/20 | 0.19 MW | 0.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314241 | 6OLDCHRC | 80/20 | 1.36 MW | 1.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314421 | 6WINCHST | 80/20 | 0.21 MW | 0.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.51 MW | 0.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.52 MW | 0.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315060 | 1CHESTF5 | Adder | 92.66 MW | 78.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | Adder | 143.8 MW | 122.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315092 | 1YORKTN3 | 80/20 | 37.33 MW | 37.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925863 | AC1-065 C | Adder | 8.85 MW | 7.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.58 MW | 0.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 46.75 MW | 46.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926784 | AC1-164 C | 80/20 | 62.84 MW | 62.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927044 | AC1-191 C | Adder | 13.68 MW | 11.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | Adder | 24.9 MW | 21.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 11.3 MW | 11.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934141 | AD1-041 C | Adder | 7.57 MW | 6.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | 11.06 MW | 9.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | Adder | 23.7 MW | 20.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936151 | AD2-021 | 80/20 | 0.06 MW | 0.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | Adder | 5.03 MW | 4.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 8.77 MW | 7.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942151 | AE2-227 C | Adder | 3.03 MW | 2.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | Adder | 3.03 MW | 2.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | Adder | 2.18 MW | 1.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | Adder | 13.62 MW | 11.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 9.22 MW | 7.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | Adder | 39.59 MW | 33.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943431 | AF1-014 C | Adder | 1.83 MW | 1.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | Adder | 1.97 MW | 1.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943471 | AF1-018 | Adder | 10.34 MW | 8.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | Adder | 2.6 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 3.55 MW | 3.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944631 | AF1-128 O1 | Adder | 57.98 MW | 49.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 7.79 MW | 6.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945361 | AF1-201 C O1 | 80/20 | 24.2 MW | 24.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | Adder | 42.29 MW | 35.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966871 | AG1-558 C | Adder | 3.41 MW | 2.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.68 MW | 0.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 1.14 MW | 1.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 5.03 MW | 5.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 4.94 MW | 4.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 5.09 MW | 5.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 38.51 MW | 38.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 3.91 MW | 3.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 3.91 MW | 3.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 3.96 MW | 3.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 41.51 MW | 41.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.55 MW | 0.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.7 MW | 0.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.59 MW | 0.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316075 | AC2-137 C | 80/20 | 0.54 MW | 0.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | Adder | 7.67 MW | 6.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | Adder | 27.66 MW | 23.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.55 MW | 0.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 12.09 MW | 12.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | Adder | 8.34 MW | 7.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 26.22 MW | 22.28 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | Adder | 15.25 MW | 12.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | Adder | 43.27 MW | 36.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | Adder | 37.09 MW | 31.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | Adder | 43.27 MW | 36.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939431 | AE1-175 C | 80/20 | 3.75 MW | 3.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939611 | AE1-191 C | Adder | 15.14 MW | 12.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940231 | AE2-005 C | Adder | 1.94 MW | 1.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | Adder | 18.23 MW | 15.49 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | Adder | 3.77 MW | 3.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940551 | AE2-041 | Adder | 10.34 MW | 8.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | Adder | 5.08 MW | 4.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | Adder | 4.95 MW | 4.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 42.77 MW | 42.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 43.96 MW | 43.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 39.96 MW | 39.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | Adder | 3.03 MW | 2.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | Adder | 3.18 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957601 | AF2-054 C | Adder | 2.98 MW | 2.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 5.39 MW | 5.39 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | Adder | 20.19 MW | 17.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962531 | AG1-102 C | Adder | 1.63 MW | 1.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962961 | AG1-145 C | 80/20 | 3.38 MW | 3.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | Adder | 3.17 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | Adder | 3.17 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | Adder | 3.17 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | Adder | 3.17 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 34.29 MW | 34.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 10.79 MW | 10.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 46.75 MW | 46.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 23.37 MW | 19.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941581 | AE2-155 C | 80/20 | 0.17 MW | 0.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 26.98 MW | 26.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | Adder | 3.02 MW | 2.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957831 | AF2-077 C | Adder | 3.17 MW | 2.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 14.93 MW | 12.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | Adder | 2.04 MW | 1.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 8.83 MW | 8.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 72.43 MW | 72.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 72.43 MW | 72.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 72.43 MW | 72.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 12.27 MW | 10.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | Adder | 23.14 MW | 19.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | Adder | 23.51 MW | 19.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | Adder | 7.59 MW | 6.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | Adder | 2.88 MW | 2.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | 4.85 MW | 4.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | Adder | 23.75 MW | 20.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 7.12 MW | 7.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.77 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 136.96 MW | 136.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 63.0 MW | 63.0 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 59.61 MW | 59.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.77 MW | 10.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.41 MW | 13.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.66 MW | 0.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.19 MW | 3.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.64 MW | 8.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.46 MW | 3.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 10.92 MW | 10.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.51 MW | 1.51 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | Adder | 1.84 MW | 1.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 1.87 MW | 1.87 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 21.18 MW | 21.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | 80/20 | 2.34 MW | 2.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | 80/20 | 1.14 MW | 1.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 11.41 MW | 11.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | 80/20 | 2.42 MW | 2.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 0.82 MW | 0.7 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | 80/20 | 0.89 MW | 0.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | 80/20 | 1.96 MW | 1.96 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 3.79 MW | 3.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 3.79 MW | 3.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 7.72 MW | 7.72 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | Adder | 5.37 MW | 4.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | Adder | 5.37 MW | 4.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | 80/20 | 3.17 MW | 3.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.21 MW | 0.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.15 MW | 0.15 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.57 MW | 0.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.61 MW | 0.61 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.46 MW | 0.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.45 MW | 1.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | 80/20 | 9.57 MW | 9.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.39 MW | 2.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.8 MW | 0.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | 80/20 | 3.54 MW | 3.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 19.94 MW | 19.94 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.9 MW | 11.9 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.34 MW | 4.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 2.5 MW | 2.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.06 MW | 2.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.65 MW | 0.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 2.62 MW | 2.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.5 MW | 6.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.41 MW | 3.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 2.6 MW | 2.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.29 MW | 13.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.75 MW | 6.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 6.17 MW | 6.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 10.36 MW | 10.36 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.74 MW | 5.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 8.67 MW | 8.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.28 MW | 0.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | 80/20 | 144.18 MW | 144.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315076 | 1HOPPOLC | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315077 | 1HOPHCF1 | 80/20 | 1.84 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315078 | 1HOPHCF2 | 80/20 | 1.84 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315079 | 1HOPHCF3 | 80/20 | 1.84 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315080 | 1HOPHCF4 | 80/20 | 2.79 MW | 2.79 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927225 | AC1-216 C | 80/20 | 0.95 MW | 0.95 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | 80/20 | 9.64 MW | 9.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | Adder | 2.49 MW | 2.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | 80/20 | 5.52 MW | 5.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935164 | AD1-151 C | 80/20 | 9.82 MW | 9.82 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.71 MW | 1.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936761 | AD2-097 C | Adder | -2.89 MW | -2.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 1.95 MW | 1.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | 80/20 | 2.91 MW | 2.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.74 MW | 0.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 6.21 MW | 6.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 2.05 MW | 1.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | 80/20 | 15.73 MW | 15.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 1.83 MW | 1.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958501 | AF2-144 C | Adder | -0.62 MW | -0.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | 80/20 | 16.37 MW | 16.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.83 MW | 2.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.83 MW | 2.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.89 MW | 5.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 0.63 MW | 0.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 11.45 MW | 11.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315117 | 1GRAVELC | 80/20 | 0.4 MW | 0.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 1.16 MW | 1.16 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 1.16 MW | 1.16 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.45 MW | 1.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 3.65 MW | 3.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 3.65 MW | 3.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 3.65 MW | 3.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 6.34 MW | 6.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.61 MW | 0.61 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.45 MW | 0.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316033 | AB2-134 C | 80/20 | 1.25 MW | 1.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316087 | AB2-174 C | 80/20 | 0.57 MW | 0.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316096 | AB2-100 C1 | 80/20 | 0.55 MW | 0.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316098 | AB2-100 C2 | 80/20 | 0.55 MW | 0.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316108 | AB2-160 C | 80/20 | 3.5 MW | 3.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316132 | AB2-190 C | 80/20 | 11.34 MW | 11.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | Adder | 2.72 MW | 2.31 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 3.27 MW | 3.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | Adder | 5.89 MW | 5.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939195 | AE1-149 C | 80/20 | 8.31 MW | 8.31 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 10.5 MW | 10.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 9.0 MW | 9.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 10.5 MW | 10.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | 80/20 | 1.87 MW | 1.87 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 2.77 MW | 2.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 1.34 MW | 1.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | Adder | 9.51 MW | 8.09 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | Adder | 9.78 MW | 8.31 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | Adder | 8.88 MW | 7.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | 80/20 | 2.93 MW | 2.93 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | Adder | 1.21 MW | 1.03 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | 80/20 | 8.02 MW | 8.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | Adder | 7.55 MW | 6.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | Adder | 2.42 MW | 2.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 5.5 MW | 4.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | Adder | 6.05 MW | 5.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 2.52 MW | 2.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 3.34 MW | 2.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 0.55 MW | 0.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | Adder | 1.99 MW | 1.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 3.25 MW | 3.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | 80/20 | 6.77 MW | 6.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962271 | AG1-075 C O1 | 80/20 | 10.71 MW | 10.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | 80/20 | 1.43 MW | 1.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.59 MW | 0.59 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | 80/20 | 2.42 MW | 2.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | 80/20 | 7.53 MW | 7.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.69 MW | 1.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.86 MW | 29.86 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.07 MW | 8.07 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.56 MW | 2.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.3 MW | 2.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.23 MW | 1.23 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.45 MW | 0.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 314421 | 6WINCHST | 80/20 | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 314507 | 3THOMPSN | 80/20 | 0.13 MW | 0.13 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315060 | 1CHESTF5 | 80/20 | 67.95 MW | 67.95 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315061 | 1CHESTG7 | 80/20 | 4.32 MW | 4.32 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315062 | 1CHESTS7 | 80/20 | 1.98 MW | 1.98 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315063 | 1CHESTG8 | 80/20 | 4.25 MW | 4.25 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315064 | 1CHESTS8 | 80/20 | 2.19 MW | 2.19 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315076 | 1HOPPOLC | 80/20 | 3.49 MW | 3.49 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315077 | 1HOPHCF1 | 80/20 | 5.46 MW | 5.46 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315078 | 1HOPHCF2 | 80/20 | 5.46 MW | 5.46 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315079 | 1HOPHCF3 | 80/20 | 5.46 MW | 5.46 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315080 | 1HOPHCF4 | 80/20 | 8.29 MW | 8.29 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315092 | 1YORKTN3 | 80/20 | 9.58 MW | 9.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 926661 | AC1-147 C | 80/20 | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 926784 | AC1-164 C | 80/20 | 15.59 MW | 15.59 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 927225 | AC1-216 C | 80/20 | 2.5 MW | 2.5 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 934014 | AD1-025 C | 80/20 | 25.25 MW | 25.25 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 935111 | AD1-144 C | 80/20 | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 935164 | AD1-151 C | 80/20 | 26.71 MW | 26.71 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 936761 | AD2-097 C | Adder | -0.89 MW | -0.76 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 942551 | AE2-270 | 80/20 | 41.84 MW | 41.84 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 943621 | AF1-033 C | 80/20 | 2.09 MW | 2.09 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944631 | AF1-128 O1 | 80/20 | 42.52 MW | 42.52 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 945361 | AF1-201 C O1 | 80/20 | 6.13 MW | 6.13 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 961711 | AG1-011 | 80/20 | 42.89 MW | 42.89 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315098 | 1CHESPKA | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315099 | 1CHESPKB | 80/20 | 0.28 MW | 0.28 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315116 | 1SURRY 1 | 80/20 | 24.69 MW | 24.69 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315117 | 1GRAVELC | 80/20 | 0.86 MW | 0.86 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315119 | 1GRAVEL3 | 80/20 | 2.51 MW | 2.51 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315120 | 1GRAVEL4 | 80/20 | 2.54 MW | 2.54 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315121 | 1GRAVEL5 | 80/20 | 2.51 MW | 2.51 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315122 | 1GRAVEL6 | 80/20 | 2.54 MW | 2.54 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315261 | 1GOSPORTB | 80/20 | 0.17 MW | 0.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315262 | 1GOSPORTC | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 316033 | AB2-134 C | 80/20 | 3.28 MW | 3.28 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 316132 | AB2-190 C | 80/20 | 30.7 MW | 30.7 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 316258 | AE1-162 C | 80/20 | 0.27 MW | 0.27 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 932044 | AC2-012 C | 80/20 | 3.0 MW | 3.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 957631 | AF2-057 | 80/20 | 1.34 MW | 1.34 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 957711 | AF2-065 C | 80/20 | 21.34 MW | 21.34 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 963221 | AG1-171 C | 80/20 | 3.22 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 963231 | AG1-172 C | 80/20 | 3.22 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 963241 | AG1-173 C | 80/20 | 3.22 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 963251 | AG1-174 C | 80/20 | 3.22 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 966611 | AG1-531 C | 80/20 | 4.07 MW | 4.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 961611 | AG1-000B C | 80/20 | 17.18 MW | 17.18 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.24 MW | 0.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.44 MW | 0.44 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.08 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.39 MW | 0.39 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.2 MW | 0.2 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.59 MW | 0.59 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 5.92 MW | 5.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 4.95 MW | 4.95 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 314314 | 3LOCKS | 80/20 | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 314435 | 6SAPONY | 80/20 | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | 80/20 | 0.11 MW | 0.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315065 | 1CHESTF6 | 80/20 | 75.83 MW | 75.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315076 | 1HOPPOLC | 80/20 | 3.16 MW | 3.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315077 | 1HOPHCF1 | 80/20 | 4.94 MW | 4.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315078 | 1HOPHCF2 | 80/20 | 4.94 MW | 4.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315079 | 1HOPHCF3 | 80/20 | 4.94 MW | 4.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315080 | 1HOPHCF4 | 80/20 | 7.5 MW | 7.5 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 926661 | AC1-147 C | 80/20 | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 927225 | AC1-216 C | 80/20 | 2.21 MW | 2.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 934014 | AD1-025 C | 80/20 | 22.3 MW | 22.3 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 934575 | AD1-082 C | 80/20 | 5.07 MW | 5.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 935164 | AD1-151 C | 80/20 | 23.78 MW | 23.78 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 936661 | AD2-085 C | 80/20 | 1.51 MW | 1.51 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942161 | AE2-228 C | 80/20 | 1.54 MW | 1.54 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942341 | AE2-247 C | 80/20 | 0.66 MW | 0.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942371 | AE2-250 C O1 | 80/20 | 3.72 MW | 3.72 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 | 80/20 | 37.07 MW | 37.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 943461 | AF1-017 C | 80/20 | 0.59 MW | 0.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 943621 | AF1-033 C | 80/20 | 1.69 MW | 1.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 | 80/20 | 37.88 MW | 37.88 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315098 | 1CHESPKA | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315099 | 1CHESPKB | 80/20 | 0.24 MW | 0.24 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315116 | 1SURRY 1 | 80/20 | 20.82 MW | 20.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315117 | 1GRAVELC | 80/20 | 0.73 MW | 0.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315119 | 1GRAVEL3 | 80/20 | 2.12 MW | 2.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315120 | 1GRAVEL4 | 80/20 | 2.14 MW | 2.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315121 | 1GRAVEL5 | 80/20 | 2.12 MW | 2.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315122 | 1GRAVEL6 | 80/20 | 2.14 MW | 2.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315260 | 1GOSPORTA | 80/20 | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315262 | 1GOSPORTC | 80/20 | 0.13 MW | 0.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316033 | AB2-134 C | 80/20 | 2.9 MW | 2.9 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 0.32 MW | 0.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 0.32 MW | 0.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316108 | AB2-160 C | 80/20 | 2.1 MW | 2.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316132 | AB2-190 C | 80/20 | 27.29 MW | 27.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316258 | AE1-162 C | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 932044 | AC2-012 C | 80/20 | 2.57 MW | 2.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 932591 | AC2-079 C O1 | 80/20 | 2.93 MW | 2.93 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 939195 | AE1-149 C | 80/20 | 7.7 MW | 7.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 | 80/20 | 1.07 MW | 1.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940651 | AE2-052 | 80/20 | 2.56 MW | 2.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941101 | AE2-104 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 946261 | AF1-291 C | 80/20 | 1.56 MW | 1.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 957631 | AF2-057 | 80/20 | 1.15 MW | 1.15 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 957711 | AF2-065 C | 80/20 | 18.91 MW | 18.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 963221 | AG1-171 C | 80/20 | 2.84 MW | 2.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 963231 | AG1-172 C | 80/20 | 2.84 MW | 2.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 963241 | AG1-173 C | 80/20 | 2.84 MW | 2.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 963251 | AG1-174 C | 80/20 | 2.84 MW | 2.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942001 | AE2-212 C | 80/20 | 1.35 MW | 1.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 958161 | AF2-110 C | 80/20 | 0.47 MW | 0.47 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | 80/20 | 2.76 MW | 2.76 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 962271 | AG1-075 C O1 | 80/20 | 6.42 MW | 6.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 965281 | AG1-393 C | 80/20 | 0.81 MW | 0.81 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 316083 | AB2-161 C | 80/20 | 2.23 MW | 2.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | 80/20 | 14.69 MW | 14.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.88 MW | 0.88 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.21 MW | 0.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.09 MW | 15.09 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.96 MW | 2.96 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.21 MW | 4.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.34 MW | 1.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.06 MW | 1.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.5 MW | 0.5 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.85 MW | 0.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961671 | AG1-007 C | Adder | 1.37 MW | 1.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961941 | AG1-037 C | Adder | 0.75 MW | 0.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962331 | AG1-082 C | Adder | 3.02 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962341 | AG1-083 C | Adder | 3.02 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962491 | AG1-098 C O1 | Adder | 15.53 MW | 13.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963041 | AG1-153 C | 80/20 | 9.13 MW | 9.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963111 | AG1-160 C | 80/20 | 9.24 MW | 9.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963291 | AG1-178 C O2 | 80/20 | 104.2 MW | 104.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963301 | AG1-179 C | Adder | 8.11 MW | 6.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963311 | AG1-180 | Adder | 3.95 MW | 3.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963351 | AG1-184 O2 | 80/20 | 56.14 MW | 56.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964801 | AG1-343 C | Adder | 8.92 MW | 7.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966801 | AG1-551 C | Adder | 3.34 MW | 2.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966811 | AG1-552 C | Adder | 3.09 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965291 | AG1-394 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965601 | AG1-428 C O2 | Adder | 6.77 MW | 5.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965691 | AG1-437 C O1 | Adder | 15.29 MW | 12.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965701 | AG1-438 C O1 | Adder | 15.29 MW | 12.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965711 | AG1-439 C O1 | Adder | 34.53 MW | 29.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965721 | AG1-440 C | Adder | 10.16 MW | 8.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965731 | AG1-441 C | Adder | 10.16 MW | 8.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965741 | AG1-442 O1 | Adder | 8.92 MW | 7.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965751 | AG1-443 O1 | Adder | 8.92 MW | 7.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965761 | AG1-444 O1 | Adder | 18.42 MW | 15.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965771 | AG1-445 | Adder | 5.87 MW | 4.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965781 | AG1-446 | Adder | 5.87 MW | 4.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965811 | AG1-449 | 80/20 | 38.28 MW | 38.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966621 | AG1-532 C | Adder | 2.05 MW | 1.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313506 | AB1-173 C OP | Adder | 10.07 MW | 8.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314572 | 3EMPORIA | Adder | 0.63 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315131 | 1EDGECMA | Adder | 11.27 MW | 9.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315132 | 1EDGECMB | Adder | 11.27 MW | 9.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926070 | AC1-086 C | Adder | 30.8 MW | 26.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926201 | AC1-098 C | Adder | 9.0 MW | 7.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926211 | AC1-099 C | Adder | 3.02 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927024 | AC1-189 C | Adder | 12.38 MW | 10.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927145 | AC1-208 C | Adder | 13.16 MW | 11.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934331 | AD1-057 C O1 | Adder | 14.28 MW | 12.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934521 | AD1-076 C | Adder | 82.43 MW | 70.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934615 | AD1-087 C | Adder | 11.4 MW | 9.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934625 | AD1-088 C | Adder | 17.23 MW | 14.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935171 | AD1-152 C O1 | Adder | 11.76 MW | 9.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937481 | AD2-202 C O1 | Adder | 3.34 MW | 2.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942931 | AE2-313 C | 80/20 | 59.03 MW | 59.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943171 | AE2-346 C | Adder | 2.11 MW | 1.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944011 | AF1-069 C | 80/20 | 21.4 MW | 21.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944141 | AF1-082 | Adder | 4.06 MW | 3.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945811 | AF1-246 C O1 | 80/20 | 11.6 MW | 11.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960081 | AF2-299 C | Adder | 3.79 MW | 3.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315293 | 1DOMTR9 | Adder | 10.28 MW | 8.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315294 | 1DOMTR10 | Adder | 12.6 MW | 10.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316129 | AC1-054 C | Adder | 10.34 MW | 8.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316140 | AB2-099 C | Adder | 0.88 MW | 0.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923262 | AB1-132 C OP | Adder | 20.91 MW | 17.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923991 | AB2-040 C O1 | Adder | 10.97 MW | 9.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925591 | AC1-034 C | Adder | 9.64 MW | 8.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932631 | AC2-084 C | Adder | 12.83 MW | 10.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940491 | AE2-034 C | Adder | 10.97 MW | 9.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940571 | AE2-044 C | Adder | 6.31 MW | 5.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941031 | AE2-094 C | 80/20 | 65.5 MW | 65.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941791 | AE2-182 C | Adder | 2.8 MW | 2.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946281 | AF1-292 C | Adder | 2.25 MW | 1.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957481 | AF2-042 C | 80/20 | 82.88 MW | 82.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957521 | AF2-046 C | Adder | 25.27 MW | 21.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957531 | AF2-047 C | Adder | 26.07 MW | 22.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957861 | AF2-080 C | Adder | 11.24 MW | 9.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938771 | AE1-103 C | Adder | 4.46 MW | 3.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940481 | AE2-033 C | 80/20 | 24.36 MW | 24.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940641 | AE2-051 C O1 | 80/20 | 28.75 MW | 28.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946011 | AF1-266 | 80/20 | 20.39 MW | 20.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933501 | AC2-165 C | Adder | 14.15 MW | 12.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 313526 | AB2-022 C | 80/20 | 0.61 MW | 0.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314435 | 6SAPONY | 80/20 | 0.65 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314491 | 3PENDLTN | 80/20 | 0.53 MW | 0.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314507 | 3THOMPSN | 80/20 | 0.53 MW | 0.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314638 | 6ELIZ CT | 80/20 | 0.35 MW | 0.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314639 | 6TANGLEW | 80/20 | 0.65 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314643 | 3O INLET | 80/20 | 0.71 MW | 0.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315060 | 1CHESTF5 | Adder | 84.08 MW | 71.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315065 | 1CHESTF6 | Adder | 144.13 MW | 122.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315083 | 1SPRUNCA | Adder | 15.45 MW | 13.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315084 | 1SPRUNCB | Adder | 15.45 MW | 13.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926661 | AC1-147 C | 80/20 | 0.6 MW | 0.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926754 | AC1-161 C | 80/20 | 47.63 MW | 47.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926784 | AC1-164 C | Adder | 50.3 MW | 42.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934014 | AD1-025 C | Adder | 24.39 MW | 20.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934061 | AD1-033 C | 80/20 | 11.71 MW | 11.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934575 | AD1-082 C | 80/20 | 11.62 MW | 11.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935111 | AD1-144 C | 80/20 | 0.45 MW | 0.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935164 | AD1-151 C | Adder | 23.14 MW | 19.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936661 | AD2-085 C | 80/20 | 5.27 MW | 5.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936761 | AD2-097 C | Adder | 2.93 MW | 2.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937221 | AD2-160 C O1 | 80/20 | 9.11 MW | 9.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942151 | AE2-227 C | Adder | 2.91 MW | 2.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942161 | AE2-228 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942341 | AE2-247 C | 80/20 | 2.28 MW | 2.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942371 | AE2-250 C O1 | Adder | 14.04 MW | 11.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942401 | AE2-253 C | 80/20 | 9.58 MW | 9.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942551 | AE2-270 | Adder | 38.74 MW | 32.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943461 | AF1-017 C | 80/20 | 2.06 MW | 2.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943611 | AF1-032 C | 80/20 | 2.7 MW | 2.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943621 | AF1-033 C | Adder | 3.48 MW | 2.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944631 | AF1-128 O1 | Adder | 52.61 MW | 44.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944871 | AF1-152 C | 80/20 | 8.16 MW | 8.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945361 | AF1-201 C O1 | Adder | 21.89 MW | 18.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958501 | AF2-144 C | Adder | 2.7 MW | 2.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961711 | AG1-011 | Adder | 41.43 MW | 35.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315098 | 1CHESPKA | 80/20 | 0.71 MW | 0.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315099 | 1CHESPKB | 80/20 | 1.17 MW | 1.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.04 MW | 14.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.04 MW | 14.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.04 MW | 14.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315105 | 1BRUNSWICKS1 | 80/20 | 29.17 MW | 29.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315108 | 1ELIZAR1 | 80/20 | 5.19 MW | 5.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315109 | 1ELIZAR2 | 80/20 | 5.11 MW | 5.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315110 | 1ELIZAR3 | 80/20 | 5.26 MW | 5.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315233 | 1SURRY 2 | 80/20 | 38.85 MW | 38.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315241 | 1Z1-086 GT1 | 80/20 | 18.05 MW | 18.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315242 | 1Z1-086 GT2 | 80/20 | 18.05 MW | 18.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315243 | 1Z1-086 GT3 | 80/20 | 18.05 MW | 18.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315244 | 1Z1-086 ST | 80/20 | 31.37 MW | 31.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315260 | 1GOSPORTA | 80/20 | 0.56 MW | 0.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315261 | 1GOSPORTB | 80/20 | 0.72 MW | 0.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315262 | 1GOSPORTC | 80/20 | 0.61 MW | 0.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315603 | 6AA1-139SOLA | 80/20 | 3.71 MW | 3.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315605 | 6W1-029WIND | 80/20 | 1.81 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315611 | 6Z1-036WIND | 80/20 | 1.12 MW | 1.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316108 | AB2-160 C | Adder | 7.91 MW | 6.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316132 | AB2-190 C | Adder | 27.03 MW | 22.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316258 | AE1-162 C | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932044 | AC2-012 C | 80/20 | 12.48 MW | 12.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932591 | AC2-079 C O1 | 80/20 | 8.74 MW | 8.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938535 | AE1-072 C | 80/20 | 27.27 MW | 27.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938551 | AE1-074 C | 80/20 | 0.66 MW | 0.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939195 | AE1-149 C | 80/20 | 16.04 MW | 16.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939414 | AE1-173_C1 | 80/20 | 51.97 MW | 51.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939415 | AE1-173_C2 | 80/20 | 44.54 MW | 44.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939416 | AE1-173_C3 | 80/20 | 51.97 MW | 51.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939431 | AE1-175 C | Adder | 3.28 MW | 2.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940431 | AE2-027 C O1 | Adder | 18.18 MW | 15.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940541 | AE2-040 | 80/20 | 4.33 MW | 4.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940651 | AE2-052 | 80/20 | 5.35 MW | 5.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941101 | AE2-104 C O1 | 80/20 | 5.17 MW | 5.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941281 | AE2-122 C O1 | 80/20 | 44.26 MW | 44.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941291 | AE2-123 C O1 | 80/20 | 45.49 MW | 45.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941301 | AE2-124 C O1 | 80/20 | 41.37 MW | 41.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946261 | AF1-291 C | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957491 | AF2-043 C | 80/20 | 3.31 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957631 | AF2-057 | 80/20 | 5.57 MW | 5.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957711 | AF2-065 C | Adder | 19.76 MW | 16.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962531 | AG1-102 C | Adder | 1.46 MW | 1.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962961 | AG1-145 C | Adder | 2.96 MW | 2.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963221 | AG1-171 C | Adder | 3.11 MW | 2.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963231 | AG1-172 C | Adder | 3.11 MW | 2.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963241 | AG1-173 C | Adder | 3.11 MW | 2.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 963251 | AG1-174 C | Adder | 3.11 MW | 2.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 964951 | AG1-359 O1 | 80/20 | 35.55 MW | 35.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965001 | AG1-364 C O1 | 80/20 | 11.14 MW | 11.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933294 | AC2-141 C | 80/20 | 47.63 MW | 47.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941501 | AE2-147 C | 80/20 | 24.48 MW | 24.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941591 | AE2-156 O1 | 80/20 | 27.85 MW | 27.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942001 | AE2-212 C | Adder | 3.14 MW | 2.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957831 | AF2-077 C | Adder | 2.84 MW | 2.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957871 | AF2-081 C | 80/20 | 15.52 MW | 15.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957911 | AF2-085 | 80/20 | 6.61 MW | 6.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958161 | AF2-110 C | 80/20 | 2.13 MW | 2.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 966611 | AG1-531 C | Adder | 8.46 MW | 7.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944581 | AF1-123 C O1 | 80/20 | 75.16 MW | 75.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944591 | AF1-124 C O1 | 80/20 | 75.16 MW | 75.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944601 | AF1-125 C O1 | 80/20 | 75.16 MW | 75.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933981 | AD1-022 C | Adder | 13.25 MW | 11.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960331 | AF2-324 C | Adder | 11.0 MW | 9.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961681 | AG1-008 C | Adder | 25.32 MW | 21.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962271 | AG1-075 C O1 | Adder | 24.24 MW | 20.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 962571 | AG1-106 C | Adder | 8.56 MW | 7.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 965281 | AG1-393 C | 80/20 | 3.31 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 316083 | AB2-161 C | 80/20 | 5.1 MW | 5.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 961611 | AG1-000B C | Adder | 23.45 MW | 19.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.27 MW | 8.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.78 MW | 2.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 153.85 MW | 153.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.72 MW | 57.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 59.09 MW | 59.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.52 MW | 12.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.66 MW | 13.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.74 MW | 0.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.92 MW | 2.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.22 MW | 8.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.16 MW | 3.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.51 MW | 0.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.07 MW | 11.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.39 MW | 1.39 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961941 | AG1-037 C | Adder | 0.54 MW | 0.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962331 | AG1-082 C | Adder | 2.17 MW | 1.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962341 | AG1-083 C | Adder | 2.17 MW | 1.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963041 | AG1-153 C | Adder | 6.02 MW | 5.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963111 | AG1-160 C | Adder | 6.09 MW | 5.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963291 | AG1-178 C O2 | 80/20 | 69.42 MW | 69.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963351 | AG1-184 O2 | 80/20 | 37.4 MW | 37.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964801 | AG1-343 C | Adder | 6.46 MW | 5.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965291 | AG1-394 C | Adder | 2.22 MW | 1.89 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965691 | AG1-437 C O1 | Adder | 11.05 MW | 9.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965701 | AG1-438 C O1 | Adder | 11.05 MW | 9.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965741 | AG1-442 O1 | Adder | 6.44 MW | 5.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965751 | AG1-443 O1 | Adder | 6.44 MW | 5.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965811 | AG1-449 | 80/20 | 25.21 MW | 25.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966361 | AG1-505 C | Adder | 17.96 MW | 15.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966371 | AG1-506 C | Adder | 17.96 MW | 15.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966621 | AG1-532 C | Adder | 1.47 MW | 1.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314572 | 3EMPORIA | Adder | 0.45 MW | 0.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934521 | AD1-076 C | Adder | 59.7 MW | 50.75 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942931 | AE2-313 C | 80/20 | 38.89 MW | 38.89 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943171 | AE2-346 C | Adder | 1.52 MW | 1.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944011 | AF1-069 C | 80/20 | 14.07 MW | 14.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 945811 | AF1-246 C O1 | Adder | 7.8 MW | 6.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 960081 | AF2-299 C | Adder | 2.72 MW | 2.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315293 | 1DOMTR9 | Adder | 7.42 MW | 6.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315294 | 1DOMTR10 | Adder | 9.09 MW | 7.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316140 | AB2-099 C | Adder | 0.63 MW | 0.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940491 | AE2-034 C | Adder | 7.97 MW | 6.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941031 | AE2-094 C | 80/20 | 43.08 MW | 43.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946281 | AF1-292 C | Adder | 1.62 MW | 1.37 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957481 | AF2-042 C | Adder | 55.7 MW | 47.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957521 | AF2-046 C | Adder | 18.27 MW | 15.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957531 | AF2-047 C | Adder | 18.95 MW | 16.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938771 | AE1-103 C | Adder | 3.27 MW | 2.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940481 | AE2-033 C | Adder | 17.59 MW | 14.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940641 | AE2-051 C O1 | 80/20 | 19.23 MW | 19.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946011 | AF1-266 | Adder | 14.72 MW | 12.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933501 | AC2-165 C | Adder | 10.51 MW | 8.94 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314236 | 6NRTHEST | 80/20 | 0.22 MW | 0.22 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314250 | 6ROCKVILLE | 80/20 | 0.4 MW | 0.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314309 | 6IRON208 | 80/20 | 0.53 MW | 0.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314314 | 3LOCKS | 80/20 | 0.35 MW | 0.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314507 | 3THOMPSN | 80/20 | 0.4 MW | 0.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315060 | 1CHESTF5 | Adder | 71.77 MW | 61.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315065 | 1CHESTF6 | 80/20 | 117.48 MW | 117.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315077 | 1HOPHCF1 | 80/20 | 2.91 MW | 2.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315078 | 1HOPHCF2 | 80/20 | 2.91 MW | 2.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315079 | 1HOPHCF3 | 80/20 | 2.91 MW | 2.91 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315080 | 1HOPHCF4 | 80/20 | 4.41 MW | 4.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315083 | 1SPRUNCA | 80/20 | 12.29 MW | 12.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315084 | 1SPRUNCB | 80/20 | 12.29 MW | 12.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 925863 | AC1-065 C | Adder | 6.83 MW | 5.8 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926001 | AC1-076 C | 80/20 | 6.08 MW | 6.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926661 | AC1-147 C | 80/20 | 0.44 MW | 0.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926737 | AC1-158 C1 | 80/20 | 15.74 MW | 15.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926738 | AC1-158 C2 | 80/20 | 15.74 MW | 15.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926754 | AC1-161 C | 80/20 | 35.01 MW | 35.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926784 | AC1-164 C | Adder | 44.73 MW | 38.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 927044 | AC1-191 C | Adder | 10.51 MW | 8.93 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934014 | AD1-025 C | Adder | 19.34 MW | 16.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934061 | AD1-033 C | Adder | 8.62 MW | 7.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934141 | AD1-041 C | Adder | 5.88 MW | 4.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934575 | AD1-082 C | Adder | 8.86 MW | 7.54 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 935164 | AD1-151 C | Adder | 18.48 MW | 15.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936591 | AD2-074 C | Adder | 5.94 MW | 5.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936661 | AD2-085 C | Adder | 3.93 MW | 3.34 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936761 | AD2-097 C | 80/20 | 2.33 MW | 2.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 937221 | AD2-160 C O1 | Adder | 6.7 MW | 5.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942151 | AE2-227 C | 80/20 | 2.48 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942161 | AE2-228 C | 80/20 | 2.48 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942191 | AE2-231 C O1 | Adder | 5.16 MW | 4.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942341 | AE2-247 C | Adder | 1.7 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942371 | AE2-250 C O1 | 80/20 | 11.12 MW | 11.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942401 | AE2-253 C | Adder | 7.04 MW | 5.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942551 | AE2-270 | Adder | 30.8 MW | 26.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943431 | AF1-014 C | Adder | 1.42 MW | 1.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943461 | AF1-017 C | Adder | 1.54 MW | 1.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943471 | AF1-018 | Adder | 7.88 MW | 6.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943611 | AF1-032 C | Adder | 1.99 MW | 1.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943621 | AF1-033 C | Adder | 2.7 MW | 2.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943741 | AF1-042 C | Adder | 3.11 MW | 2.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944631 | AF1-128 O1 | Adder | 44.91 MW | 38.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944871 | AF1-152 C | Adder | 5.99 MW | 5.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 945361 | AF1-201 C O1 | Adder | 18.1 MW | 15.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 958501 | AF2-144 C | Adder | 1.97 MW | 1.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 960091 | AF2-300 C | Adder | 2.35 MW | 2.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961711 | AG1-011 | Adder | 32.84 MW | 27.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961951 | AG1-038 C | Adder | 3.43 MW | 2.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966871 | AG1-558 C | Adder | 2.62 MW | 2.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966881 | AG1-559 C | Adder | 2.6 MW | 2.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315098 | 1CHESPKA | 80/20 | 0.52 MW | 0.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315099 | 1CHESPKB | 80/20 | 0.87 MW | 0.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315108 | 1ELIZAR1 | 80/20 | 3.84 MW | 3.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315109 | 1ELIZAR2 | 80/20 | 3.77 MW | 3.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315110 | 1ELIZAR3 | 80/20 | 3.88 MW | 3.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315225 | 1N ANNA1 | 80/20 | 58.74 MW | 58.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315226 | 1N ANNA2 | 80/20 | 58.74 MW | 58.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315233 | 1SURRY 2 | 80/20 | 29.69 MW | 29.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315260 | 1GOSPORTA | 80/20 | 0.42 MW | 0.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315261 | 1GOSPORTB | 80/20 | 0.53 MW | 0.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315262 | 1GOSPORTC | 80/20 | 0.45 MW | 0.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316108 | AB2-160 C | 80/20 | 6.26 MW | 6.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316132 | AB2-190 C | Adder | 21.56 MW | 18.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 925021 | AB2-158 C | 80/20 | 2.17 MW | 2.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 932044 | AC2-012 C | 80/20 | 9.22 MW | 9.22 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 932591 | AC2-079 C O1 | Adder | 6.57 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938535 | AE1-072 C | Adder | 20.05 MW | 17.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938551 | AE1-074 C | 80/20 | 0.49 MW | 0.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939195 | AE1-149 C | Adder | 12.31 MW | 10.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939261 | AE1-157 C O1 | Adder | 15.09 MW | 12.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939414 | AE1-173_C1 | 80/20 | 35.55 MW | 35.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939415 | AE1-173_C2 | 80/20 | 30.47 MW | 30.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939416 | AE1-173_C3 | 80/20 | 35.55 MW | 35.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939431 | AE1-175 C | Adder | 2.71 MW | 2.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939611 | AE1-191 C | Adder | 11.75 MW | 9.99 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940231 | AE2-005 C | Adder | 1.49 MW | 1.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940431 | AE2-027 C O1 | 80/20 | 14.81 MW | 14.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940541 | AE2-040 | Adder | 3.13 MW | 2.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940551 | AE2-041 | Adder | 7.88 MW | 6.69 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940651 | AE2-052 | Adder | 4.1 MW | 3.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941101 | AE2-104 C O1 | Adder | 3.82 MW | 3.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941281 | AE2-122 C O1 | Adder | 32.64 MW | 27.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941291 | AE2-123 C O1 | Adder | 33.54 MW | 28.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941301 | AE2-124 C O1 | Adder | 30.5 MW | 25.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941381 | AE2-134 | 80/20 | 4.19 MW | 4.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946261 | AF1-291 C | 80/20 | 2.48 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946371 | AF1-301 C | 80/20 | 14.93 MW | 14.93 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957411 | AF2-035 C | Adder | 9.39 MW | 7.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957431 | AF2-037 C | 80/20 | 14.44 MW | 14.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957491 | AF2-043 C | Adder | 2.44 MW | 2.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957601 | AF2-054 C | Adder | 2.33 MW | 1.98 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957631 | AF2-057 | 80/20 | 4.12 MW | 4.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957691 | AF2-063 C | 80/20 | 23.04 MW | 23.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957711 | AF2-065 C | Adder | 15.71 MW | 13.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962531 | AG1-102 C | Adder | 1.23 MW | 1.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962841 | AG1-133 C O1 | 80/20 | 24.46 MW | 24.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962861 | AG1-135 C | Adder | 6.5 MW | 5.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962961 | AG1-145 C | Adder | 2.44 MW | 2.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962971 | AG1-146 C | Adder | 3.34 MW | 2.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962981 | AG1-147 C | Adder | 7.79 MW | 6.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963051 | AG1-154 C | Adder | 3.82 MW | 3.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963221 | AG1-171 C | Adder | 2.46 MW | 2.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963231 | AG1-172 C | Adder | 2.46 MW | 2.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963241 | AG1-173 C | Adder | 2.46 MW | 2.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963251 | AG1-174 C | Adder | 2.46 MW | 2.09 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963621 | AG1-213 C | Adder | 0.78 MW | 0.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964271 | AG1-288 C | 80/20 | 32.65 MW | 32.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964281 | AG1-289 | 80/20 | 18.05 MW | 18.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964421 | AG1-305 C O2 | 80/20 | 18.12 MW | 18.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964951 | AG1-359 O1 | Adder | 26.17 MW | 22.24 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965001 | AG1-364 C O1 | 80/20 | 8.23 MW | 8.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933294 | AC2-141 C | 80/20 | 35.01 MW | 35.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941501 | AE2-147 C | Adder | 17.96 MW | 15.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941591 | AE2-156 O1 | 80/20 | 20.58 MW | 20.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942001 | AE2-212 C | 80/20 | 2.48 MW | 2.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957831 | AF2-077 C | Adder | 2.4 MW | 2.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957871 | AF2-081 C | Adder | 11.41 MW | 9.7 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957911 | AF2-085 | 80/20 | 4.52 MW | 4.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 958161 | AF2-110 C | Adder | 1.58 MW | 1.34 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966611 | AG1-531 C | Adder | 6.63 MW | 5.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944581 | AF1-123 C O1 | 80/20 | 55.17 MW | 55.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944591 | AF1-124 C O1 | 80/20 | 55.17 MW | 55.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944601 | AF1-125 C O1 | 80/20 | 55.17 MW | 55.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933981 | AD1-022 C | Adder | 9.58 MW | 8.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961681 | AG1-008 C | Adder | 18.3 MW | 15.56 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962271 | AG1-075 C O1 | 80/20 | 19.19 MW | 19.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965281 | AG1-393 C | Adder | 2.39 MW | 2.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316083 | AB2-161 C | Adder | 3.89 MW | 3.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961611 | AG1-000B C | Adder | 18.25 MW | 15.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.58 MW | 5.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.66 MW | 1.66 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 102.49 MW | 102.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 26.65 MW | 26.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.12 MW | 34.12 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.46 MW | 8.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.27 MW | 8.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.58 MW | 0.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.48 MW | 1.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.32 MW | 4.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.88 MW | 2.88 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.27 MW | 0.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.76 MW | 6.76 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.67 MW | 0.67 MW |
| Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961941 | AG1-037 C | Adder | 0.54 MW | 0.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962331 | AG1-082 C | Adder | 2.14 MW | 1.82 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962341 | AG1-083 C | Adder | 2.14 MW | 1.82 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963041 | AG1-153 C | Adder | 5.93 MW | 5.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963111 | AG1-160 C | Adder | 6.0 MW | 5.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963291 | AG1-178 C O2 | 80/20 | 68.4 MW | 68.4 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963351 | AG1-184 O2 | 80/20 | 36.85 MW | 36.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964801 | AG1-343 C | Adder | 6.36 MW | 5.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965291 | AG1-394 C | Adder | 2.18 MW | 1.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965691 | AG1-437 C O1 | Adder | 10.88 MW | 9.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965701 | AG1-438 C O1 | Adder | 10.88 MW | 9.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965741 | AG1-442 O1 | Adder | 6.35 MW | 5.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965751 | AG1-443 O1 | Adder | 6.35 MW | 5.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965811 | AG1-449 | 80/20 | 24.84 MW | 24.84 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966361 | AG1-505 C | Adder | 17.69 MW | 15.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966371 | AG1-506 C | Adder | 17.69 MW | 15.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966621 | AG1-532 C | Adder | 1.45 MW | 1.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 313506 | AB1-173 C OP | Adder | 7.11 MW | 6.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314572 | 3EMPORIA | Adder | 0.44 MW | 0.38 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934521 | AD1-076 C | Adder | 58.78 MW | 49.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942931 | AE2-313 C | 80/20 | 38.31 MW | 38.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943171 | AE2-346 C | Adder | 1.5 MW | 1.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944011 | AF1-069 C | 80/20 | 13.87 MW | 13.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 945811 | AF1-246 C O1 | Adder | 7.68 MW | 6.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 960081 | AF2-299 C | Adder | 2.68 MW | 2.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315293 | 1DOMTR9 | Adder | 7.3 MW | 6.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315294 | 1DOMTR10 | Adder | 8.95 MW | 7.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316140 | AB2-099 C | Adder | 0.62 MW | 0.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 923991 | AB2-040 C O1 | Adder | 7.74 MW | 6.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940491 | AE2-034 C | Adder | 7.85 MW | 6.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941031 | AE2-094 C | 80/20 | 42.44 MW | 42.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946281 | AF1-292 C | Adder | 1.59 MW | 1.35 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957481 | AF2-042 C | Adder | 54.83 MW | 46.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957521 | AF2-046 C | Adder | 17.98 MW | 15.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957531 | AF2-047 C | Adder | 18.66 MW | 15.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938771 | AE1-103 C | Adder | 3.22 MW | 2.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940481 | AE2-033 C | Adder | 17.32 MW | 14.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940641 | AE2-051 C O1 | 80/20 | 18.95 MW | 18.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946011 | AF1-266 | Adder | 14.5 MW | 12.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933501 | AC2-165 C | Adder | 10.32 MW | 8.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314236 | 6NRTHEST | 80/20 | 0.21 MW | 0.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314250 | 6ROCKVILLE | 80/20 | 0.39 MW | 0.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314309 | 6IRON208 | 80/20 | 0.52 MW | 0.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314314 | 3LOCKS | 80/20 | 0.34 MW | 0.34 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314507 | 3THOMPSN | 80/20 | 0.39 MW | 0.39 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315060 | 1CHESTF5 | Adder | 70.64 MW | 60.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315065 | 1CHESTF6 | 80/20 | 115.65 MW | 115.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315077 | 1HOPHCF1 | 80/20 | 2.86 MW | 2.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315078 | 1HOPHCF2 | 80/20 | 2.86 MW | 2.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315079 | 1HOPHCF3 | 80/20 | 2.86 MW | 2.86 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315080 | 1HOPHCF4 | 80/20 | 4.34 MW | 4.34 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315083 | 1SPRUNCA | 80/20 | 12.1 MW | 12.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315084 | 1SPRUNCB | 80/20 | 12.1 MW | 12.1 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 925863 | AC1-065 C | Adder | 6.72 MW | 5.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926001 | AC1-076 C | Adder | 4.26 MW | 3.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926661 | AC1-147 C | 80/20 | 0.43 MW | 0.43 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926737 | AC1-158 C1 | 80/20 | 15.62 MW | 15.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926738 | AC1-158 C2 | 80/20 | 15.62 MW | 15.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926754 | AC1-161 C | 80/20 | 34.48 MW | 34.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926784 | AC1-164 C | Adder | 44.02 MW | 37.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 927044 | AC1-191 C | Adder | 10.34 MW | 8.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934014 | AD1-025 C | Adder | 19.04 MW | 16.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934061 | AD1-033 C | Adder | 8.49 MW | 7.21 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934141 | AD1-041 C | Adder | 5.78 MW | 4.92 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934575 | AD1-082 C | Adder | 8.73 MW | 7.42 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 935164 | AD1-151 C | Adder | 18.2 MW | 15.47 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936591 | AD2-074 C | Adder | 5.84 MW | 4.97 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936661 | AD2-085 C | Adder | 3.87 MW | 3.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936761 | AD2-097 C | 80/20 | 2.3 MW | 2.3 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 937221 | AD2-160 C O1 | Adder | 6.6 MW | 5.61 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942151 | AE2-227 C | 80/20 | 2.44 MW | 2.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942161 | AE2-228 C | 80/20 | 2.44 MW | 2.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942191 | AE2-231 C O1 | Adder | 5.08 MW | 4.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942341 | AE2-247 C | Adder | 1.68 MW | 1.43 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942371 | AE2-250 C O1 | 80/20 | 10.95 MW | 10.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942401 | AE2-253 C | Adder | 6.94 MW | 5.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942551 | AE2-270 | Adder | 30.32 MW | 25.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943431 | AF1-014 C | Adder | 1.39 MW | 1.18 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943461 | AF1-017 C | Adder | 1.52 MW | 1.29 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943471 | AF1-018 | Adder | 7.75 MW | 6.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943611 | AF1-032 C | Adder | 1.96 MW | 1.67 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943621 | AF1-033 C | Adder | 2.66 MW | 2.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943741 | AF1-042 C | Adder | 3.06 MW | 2.6 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944631 | AF1-128 O1 | Adder | 44.2 MW | 37.57 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944871 | AF1-152 C | Adder | 5.9 MW | 5.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 945361 | AF1-201 C O1 | Adder | 17.82 MW | 15.15 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958501 | AF2-144 C | Adder | 1.93 MW | 1.64 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 960091 | AF2-300 C | Adder | 2.31 MW | 1.96 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961711 | AG1-011 | Adder | 32.34 MW | 27.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961951 | AG1-038 C | Adder | 3.38 MW | 2.87 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966661 | AG1-536 C | Adder | 5.66 MW | 4.81 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966871 | AG1-558 C | Adder | 2.58 MW | 2.19 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966881 | AG1-559 C | Adder | 2.56 MW | 2.17 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315098 | 1CHESPKA | 80/20 | 0.51 MW | 0.51 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315099 | 1CHESPKB | 80/20 | 0.85 MW | 0.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315108 | 1ELIZAR1 | 80/20 | 3.78 MW | 3.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315109 | 1ELIZAR2 | 80/20 | 3.71 MW | 3.71 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315110 | 1ELIZAR3 | 80/20 | 3.83 MW | 3.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315225 | 1N ANNA1 | 80/20 | 58.06 MW | 58.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315226 | 1N ANNA2 | 80/20 | 58.06 MW | 58.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315233 | 1SURRY 2 | 80/20 | 29.23 MW | 29.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315260 | 1GOSPORTA | 80/20 | 0.41 MW | 0.41 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315261 | 1GOSPORTB | 80/20 | 0.52 MW | 0.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315262 | 1GOSPORTC | 80/20 | 0.45 MW | 0.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316108 | AB2-160 C | 80/20 | 6.16 MW | 6.16 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316132 | AB2-190 C | Adder | 21.23 MW | 18.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932044 | AC2-012 C | 80/20 | 9.08 MW | 9.08 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932591 | AC2-079 C O1 | Adder | 6.47 MW | 5.5 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938535 | AE1-072 C | Adder | 19.74 MW | 16.78 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938551 | AE1-074 C | 80/20 | 0.49 MW | 0.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939195 | AE1-149 C | Adder | 12.12 MW | 10.31 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939245 | AE1-155 C | Adder | 13.48 MW | 11.46 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939261 | AE1-157 C O1 | Adder | 14.85 MW | 12.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939414 | AE1-173_C1 | 80/20 | 35.01 MW | 35.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939415 | AE1-173_C2 | 80/20 | 30.01 MW | 30.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939416 | AE1-173_C3 | 80/20 | 35.01 MW | 35.01 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939431 | AE1-175 C | Adder | 2.67 MW | 2.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939611 | AE1-191 C | Adder | 11.57 MW | 9.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940231 | AE2-005 C | Adder | 1.47 MW | 1.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940431 | AE2-027 C O1 | 80/20 | 14.58 MW | 14.58 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940541 | AE2-040 | Adder | 3.08 MW | 2.62 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940551 | AE2-041 | Adder | 7.75 MW | 6.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940651 | AE2-052 | Adder | 4.04 MW | 3.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941101 | AE2-104 C O1 | Adder | 3.76 MW | 3.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941281 | AE2-122 C O1 | Adder | 32.14 MW | 27.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941291 | AE2-123 C O1 | Adder | 33.03 MW | 28.07 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941301 | AE2-124 C O1 | Adder | 30.03 MW | 25.53 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941381 | AE2-134 | Adder | 2.93 MW | 2.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946261 | AF1-291 C | 80/20 | 2.44 MW | 2.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946371 | AF1-301 C | 80/20 | 14.48 MW | 14.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957411 | AF2-035 C | Adder | 9.24 MW | 7.85 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957431 | AF2-037 C | 80/20 | 14.11 MW | 14.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957491 | AF2-043 C | Adder | 2.4 MW | 2.04 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957601 | AF2-054 C | Adder | 2.29 MW | 1.95 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957631 | AF2-057 | 80/20 | 4.05 MW | 4.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957691 | AF2-063 C | 80/20 | 22.52 MW | 22.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957711 | AF2-065 C | Adder | 15.46 MW | 13.14 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962531 | AG1-102 C | Adder | 1.21 MW | 1.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962841 | AG1-133 C O1 | 80/20 | 24.14 MW | 24.14 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962861 | AG1-135 C | Adder | 6.4 MW | 5.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962961 | AG1-145 C | Adder | 2.41 MW | 2.05 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962971 | AG1-146 C | Adder | 3.29 MW | 2.79 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962981 | AG1-147 C | Adder | 7.67 MW | 6.52 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963051 | AG1-154 C | Adder | 3.76 MW | 3.2 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963221 | AG1-171 C | Adder | 2.42 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963231 | AG1-172 C | Adder | 2.42 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963241 | AG1-173 C | Adder | 2.42 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963251 | AG1-174 C | Adder | 2.42 MW | 2.06 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963621 | AG1-213 C | Adder | 0.77 MW | 0.65 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964271 | AG1-288 C | 80/20 | 23.03 MW | 23.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964281 | AG1-289 | 80/20 | 12.74 MW | 12.74 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964421 | AG1-305 C O2 | 80/20 | 17.72 MW | 17.72 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964951 | AG1-359 O1 | Adder | 25.77 MW | 21.9 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965001 | AG1-364 C O1 | 80/20 | 8.11 MW | 8.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933294 | AC2-141 C | 80/20 | 34.48 MW | 34.48 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941501 | AE2-147 C | Adder | 17.68 MW | 15.03 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941591 | AE2-156 O1 | 80/20 | 20.27 MW | 20.27 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942001 | AE2-212 C | 80/20 | 2.44 MW | 2.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957831 | AF2-077 C | Adder | 2.36 MW | 2.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957871 | AF2-081 C | Adder | 11.24 MW | 9.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957911 | AF2-085 | 80/20 | 4.45 MW | 4.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958161 | AF2-110 C | Adder | 1.55 MW | 1.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958261 | AF2-120 C | Adder | 6.58 MW | 5.59 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966611 | AG1-531 C | Adder | 6.53 MW | 5.55 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944581 | AF1-123 C O1 | 80/20 | 54.33 MW | 54.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944591 | AF1-124 C O1 | 80/20 | 54.33 MW | 54.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944601 | AF1-125 C O1 | 80/20 | 54.33 MW | 54.33 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933981 | AD1-022 C | Adder | 9.44 MW | 8.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961681 | AG1-008 C | Adder | 18.02 MW | 15.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962271 | AG1-075 C O1 | 80/20 | 18.89 MW | 18.89 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965281 | AG1-393 C | Adder | 2.35 MW | 2.0 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316083 | AB2-161 C | Adder | 3.83 MW | 3.25 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961611 | AG1-000B C | Adder | 17.97 MW | 15.28 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.49 MW | 5.49 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.63 MW | 1.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 100.77 MW | 100.77 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 26.02 MW | 26.02 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 33.44 MW | 33.44 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.32 MW | 8.32 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.11 MW | 8.11 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.57 MW | 0.57 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.45 MW | 1.45 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.23 MW | 4.23 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.83 MW | 2.83 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.26 MW | 0.26 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.63 MW | 6.63 MW |
| 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.66 MW | 0.66 MW |
| Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963291 | AG1-178 C O2 | Adder | 51.82 MW | 44.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963351 | AG1-184 O2 | Adder | 27.92 MW | 23.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940641 | AE2-051 C O1 | Adder | 14.4 MW | 12.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314229 | 6MT RD221 | 80/20 | 0.12 MW | 0.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314236 | 6NRTHEST | 80/20 | 0.19 MW | 0.19 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314241 | 6OLDCHRC | 80/20 | 0.86 MW | 0.86 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314250 | 6ROCKVILLE | 80/20 | 0.33 MW | 0.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314309 | 6IRON208 | 80/20 | 0.45 MW | 0.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315037 | 1LDYSMT1 | 80/20 | 5.47 MW | 5.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315038 | 1LDYSMT2 | 80/20 | 5.47 MW | 5.47 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315039 | 1LDYSMT3 | 80/20 | 5.27 MW | 5.27 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315040 | 1LDYSMT4 | 80/20 | 5.28 MW | 5.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315041 | 1LDYSMT5 | 80/20 | 5.3 MW | 5.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315051 | 1AA1-145 CT1 | 80/20 | 5.44 MW | 5.44 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315052 | 1AA1-145 CT2 | 80/20 | 5.44 MW | 5.44 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315060 | 1CHESTF5 | 80/20 | 61.32 MW | 61.32 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315061 | 1CHESTG7 | 80/20 | 3.9 MW | 3.9 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315062 | 1CHESTS7 | 80/20 | 1.79 MW | 1.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315063 | 1CHESTG8 | 80/20 | 3.84 MW | 3.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315064 | 1CHESTS8 | 80/20 | 1.98 MW | 1.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315065 | 1CHESTF6 | Adder | 98.13 MW | 83.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315067 | 1DARBY 1 | 80/20 | 2.6 MW | 2.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315068 | 1DARBY 2 | 80/20 | 2.6 MW | 2.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315069 | 1DARBY 3 | 80/20 | 2.61 MW | 2.61 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315070 | 1DARBY 4 | 80/20 | 2.62 MW | 2.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315083 | 1SPRUNCA | Adder | 10.08 MW | 8.56 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315084 | 1SPRUNCB | Adder | 10.08 MW | 8.56 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 925863 | AC1-065 C | Adder | 5.81 MW | 4.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926754 | AC1-161 C | Adder | 28.09 MW | 23.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926784 | AC1-164 C | 80/20 | 39.04 MW | 39.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 927044 | AC1-191 C | Adder | 9.34 MW | 7.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934014 | AD1-025 C | Adder | 16.02 MW | 13.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934061 | AD1-033 C | Adder | 6.91 MW | 5.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934141 | AD1-041 C | Adder | 4.99 MW | 4.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934575 | AD1-082 C | Adder | 7.2 MW | 6.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 935164 | AD1-151 C | Adder | 15.35 MW | 13.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936151 | AD2-021 | 80/20 | 0.04 MW | 0.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936661 | AD2-085 C | Adder | 3.17 MW | 2.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936761 | AD2-097 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 937221 | AD2-160 C O1 | Adder | 5.37 MW | 4.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942151 | AE2-227 C | 80/20 | 2.11 MW | 2.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942161 | AE2-228 C | Adder | 2.06 MW | 1.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942191 | AE2-231 C O1 | 80/20 | 5.04 MW | 5.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942341 | AE2-247 C | Adder | 1.37 MW | 1.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942371 | AE2-250 C O1 | Adder | 9.16 MW | 7.78 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942401 | AE2-253 C | Adder | 5.65 MW | 4.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942551 | AE2-270 | Adder | 25.54 MW | 21.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943431 | AF1-014 C | Adder | 1.2 MW | 1.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943461 | AF1-017 C | Adder | 1.24 MW | 1.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943471 | AF1-018 | Adder | 6.72 MW | 5.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943611 | AF1-032 C | Adder | 1.6 MW | 1.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943621 | AF1-033 C | Adder | 2.22 MW | 1.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944631 | AF1-128 O1 | Adder | 38.37 MW | 32.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944871 | AF1-152 C | Adder | 4.8 MW | 4.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 945361 | AF1-201 C O1 | Adder | 15.14 MW | 12.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 960091 | AF2-300 C | 80/20 | 2.29 MW | 2.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961711 | AG1-011 | Adder | 27.21 MW | 23.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966871 | AG1-558 C | Adder | 2.33 MW | 1.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966881 | AG1-559 C | 80/20 | 2.54 MW | 2.54 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315225 | 1N ANNA1 | 80/20 | 28.57 MW | 28.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315226 | 1N ANNA2 | 80/20 | 28.57 MW | 28.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316075 | AC2-137 C | 80/20 | 0.34 MW | 0.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316108 | AB2-160 C | Adder | 5.16 MW | 4.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316132 | AB2-190 C | Adder | 17.9 MW | 15.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932044 | AC2-012 C | Adder | 7.41 MW | 6.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932591 | AC2-079 C O1 | Adder | 5.31 MW | 4.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938535 | AE1-072 C | Adder | 16.08 MW | 13.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939195 | AE1-149 C | Adder | 10.02 MW | 8.51 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939261 | AE1-157 C O1 | 80/20 | 14.94 MW | 14.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939414 | AE1-173_C1 | Adder | 27.08 MW | 23.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939415 | AE1-173_C2 | Adder | 23.21 MW | 19.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939416 | AE1-173_C3 | Adder | 27.08 MW | 23.01 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939431 | AE1-175 C | Adder | 2.29 MW | 1.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939611 | AE1-191 C | Adder | 9.98 MW | 8.48 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940231 | AE2-005 C | Adder | 1.27 MW | 1.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940431 | AE2-027 C O1 | Adder | 12.35 MW | 10.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940541 | AE2-040 | Adder | 2.47 MW | 2.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940551 | AE2-041 | Adder | 6.72 MW | 5.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940651 | AE2-052 | Adder | 3.34 MW | 2.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941101 | AE2-104 C O1 | Adder | 3.07 MW | 2.61 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941281 | AE2-122 C O1 | Adder | 26.19 MW | 22.26 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941291 | AE2-123 C O1 | Adder | 26.92 MW | 22.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941301 | AE2-124 C O1 | Adder | 24.47 MW | 20.8 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946261 | AF1-291 C | Adder | 2.06 MW | 1.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957411 | AF2-035 C | 80/20 | 9.17 MW | 9.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957491 | AF2-043 C | Adder | 1.96 MW | 1.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957601 | AF2-054 C | Adder | 1.97 MW | 1.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957631 | AF2-057 | Adder | 3.3 MW | 2.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957711 | AF2-065 C | Adder | 13.02 MW | 11.07 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962531 | AG1-102 C | Adder | 1.03 MW | 0.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962841 | AG1-133 C O1 | 80/20 | 16.36 MW | 16.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962961 | AG1-145 C | Adder | 2.07 MW | 1.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963051 | AG1-154 C | 80/20 | 3.87 MW | 3.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963221 | AG1-171 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963231 | AG1-172 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963241 | AG1-173 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963251 | AG1-174 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963621 | AG1-213 C | 80/20 | 0.76 MW | 0.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964951 | AG1-359 O1 | Adder | 20.98 MW | 17.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965001 | AG1-364 C O1 | Adder | 6.61 MW | 5.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965441 | AG1-412 C | Adder | 13.33 MW | 11.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933294 | AC2-141 C | Adder | 28.09 MW | 23.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941501 | AE2-147 C | Adder | 14.41 MW | 12.25 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941581 | AE2-155 C | 80/20 | 0.11 MW | 0.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941591 | AE2-156 O1 | Adder | 16.53 MW | 14.05 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942001 | AE2-212 C | Adder | 2.04 MW | 1.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957831 | AF2-077 C | Adder | 2.01 MW | 1.71 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957871 | AF2-081 C | Adder | 9.15 MW | 7.78 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957911 | AF2-085 | Adder | 3.35 MW | 2.85 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958161 | AF2-110 C | Adder | 1.27 MW | 1.08 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966611 | AG1-531 C | Adder | 5.47 MW | 4.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944581 | AF1-123 C O1 | Adder | 44.17 MW | 37.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944591 | AF1-124 C O1 | Adder | 44.17 MW | 37.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944601 | AF1-125 C O1 | Adder | 44.17 MW | 37.55 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962271 | AG1-075 C O1 | Adder | 15.8 MW | 13.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965281 | AG1-393 C | Adder | 1.89 MW | 1.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315043 | 1FOUR RIVERA | 80/20 | 3.46 MW | 3.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315044 | 1FOUR RIVERB | 80/20 | 3.46 MW | 3.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315045 | 1FOUR RIVERC | 80/20 | 4.22 MW | 4.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315046 | 1FOUR RIVERD | 80/20 | 3.46 MW | 3.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315047 | 1FOUR RIVERE | 80/20 | 3.46 MW | 3.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315048 | 1FOUR RIVERF | 80/20 | 4.22 MW | 4.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316083 | AB2-161 C | Adder | 3.16 MW | 2.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961611 | AG1-000B C | Adder | 15.0 MW | 12.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.64 MW | 4.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.84 MW | 1.84 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 89.46 MW | 89.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.5 MW | 42.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 39.62 MW | 39.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 7.02 MW | 7.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.87 MW | 8.87 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.42 MW | 0.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.14 MW | 2.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.79 MW | 5.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.9 MW | 2.9 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.37 MW | 0.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.22 MW | 7.22 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.02 MW | 1.02 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961941 | AG1-037 C | Adder | 0.55 MW | 0.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962331 | AG1-082 C | Adder | 2.22 MW | 1.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962341 | AG1-083 C | Adder | 2.22 MW | 1.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963041 | AG1-153 C | Adder | 6.15 MW | 5.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963111 | AG1-160 C | Adder | 6.22 MW | 5.29 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963291 | AG1-178 C O2 | 80/20 | 70.9 MW | 70.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963351 | AG1-184 O2 | 80/20 | 38.2 MW | 38.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964801 | AG1-343 C | Adder | 6.59 MW | 5.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965291 | AG1-394 C | Adder | 2.26 MW | 1.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965691 | AG1-437 C O1 | Adder | 11.28 MW | 9.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965701 | AG1-438 C O1 | Adder | 11.28 MW | 9.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965741 | AG1-442 O1 | Adder | 6.58 MW | 5.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965751 | AG1-443 O1 | Adder | 6.58 MW | 5.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965811 | AG1-449 | 80/20 | 25.74 MW | 25.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966361 | AG1-505 C | Adder | 18.32 MW | 15.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966371 | AG1-506 C | Adder | 18.32 MW | 15.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966621 | AG1-532 C | Adder | 1.5 MW | 1.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 313506 | AB1-173 C OP | Adder | 7.36 MW | 6.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314572 | 3EMPORIA | Adder | 0.46 MW | 0.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926070 | AC1-086 C | Adder | 22.48 MW | 19.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934521 | AD1-076 C | Adder | 60.94 MW | 51.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942931 | AE2-313 C | 80/20 | 39.7 MW | 39.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943171 | AE2-346 C | Adder | 1.55 MW | 1.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944011 | AF1-069 C | 80/20 | 14.37 MW | 14.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 945811 | AF1-246 C O1 | Adder | 7.94 MW | 6.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 960081 | AF2-299 C | Adder | 2.78 MW | 2.36 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315293 | 1DOMTR9 | Adder | 7.57 MW | 6.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315294 | 1DOMTR10 | Adder | 9.28 MW | 7.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316140 | AB2-099 C | Adder | 0.65 MW | 0.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 923262 | AB1-132 C OP | Adder | 15.26 MW | 12.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 923991 | AB2-040 C O1 | Adder | 8.02 MW | 6.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940491 | AE2-034 C | Adder | 8.14 MW | 6.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941031 | AE2-094 C | 80/20 | 43.99 MW | 43.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946281 | AF1-292 C | Adder | 1.65 MW | 1.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957481 | AF2-042 C | Adder | 56.7 MW | 48.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957521 | AF2-046 C | Adder | 18.64 MW | 15.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957531 | AF2-047 C | Adder | 19.34 MW | 16.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938771 | AE1-103 C | Adder | 3.34 MW | 2.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940481 | AE2-033 C | Adder | 17.95 MW | 15.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940641 | AE2-051 C O1 | 80/20 | 19.64 MW | 19.64 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946011 | AF1-266 | Adder | 15.03 MW | 12.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933501 | AC2-165 C | Adder | 10.54 MW | 8.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314236 | 6NRTHEST | 80/20 | 0.22 MW | 0.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314250 | 6ROCKVILLE | 80/20 | 0.41 MW | 0.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314309 | 6IRON208 | 80/20 | 0.54 MW | 0.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314314 | 3LOCKS | 80/20 | 0.36 MW | 0.36 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 314507 | 3THOMPSN | 80/20 | 0.4 MW | 0.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315060 | 1CHESTF5 | Adder | 73.25 MW | 62.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315065 | 1CHESTF6 | 80/20 | 119.9 MW | 119.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315077 | 1HOPHCF1 | 80/20 | 2.97 MW | 2.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315078 | 1HOPHCF2 | 80/20 | 2.97 MW | 2.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315079 | 1HOPHCF3 | 80/20 | 2.97 MW | 2.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315080 | 1HOPHCF4 | 80/20 | 4.5 MW | 4.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315083 | 1SPRUNCA | 80/20 | 12.54 MW | 12.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315084 | 1SPRUNCB | 80/20 | 12.54 MW | 12.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 925863 | AC1-065 C | Adder | 6.97 MW | 5.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926001 | AC1-076 C | Adder | -5.37 MW | -4.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926661 | AC1-147 C | 80/20 | 0.45 MW | 0.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926754 | AC1-161 C | 80/20 | 35.75 MW | 35.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 926784 | AC1-164 C | Adder | 45.66 MW | 38.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 927044 | AC1-191 C | Adder | 10.73 MW | 9.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934014 | AD1-025 C | Adder | 19.74 MW | 16.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934061 | AD1-033 C | Adder | 8.8 MW | 7.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934141 | AD1-041 C | Adder | 6.0 MW | 5.1 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 934575 | AD1-082 C | Adder | 9.05 MW | 7.69 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 935164 | AD1-151 C | Adder | 18.87 MW | 16.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936591 | AD2-074 C | Adder | 6.07 MW | 5.16 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936661 | AD2-085 C | Adder | 4.01 MW | 3.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 936761 | AD2-097 C | 80/20 | 2.38 MW | 2.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 937221 | AD2-160 C O1 | Adder | 6.84 MW | 5.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942151 | AE2-227 C | 80/20 | 2.53 MW | 2.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942161 | AE2-228 C | 80/20 | 2.53 MW | 2.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942191 | AE2-231 C O1 | Adder | 5.29 MW | 4.49 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942341 | AE2-247 C | Adder | 1.74 MW | 1.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942371 | AE2-250 C O1 | 80/20 | 11.35 MW | 11.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942401 | AE2-253 C | Adder | 7.19 MW | 6.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942551 | AE2-270 | Adder | 31.44 MW | 26.72 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943431 | AF1-014 C | Adder | 1.45 MW | 1.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943461 | AF1-017 C | Adder | 1.57 MW | 1.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943471 | AF1-018 | Adder | 8.04 MW | 6.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943611 | AF1-032 C | Adder | 2.03 MW | 1.73 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943621 | AF1-033 C | Adder | 2.76 MW | 2.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 943741 | AF1-042 C | Adder | 3.18 MW | 2.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944631 | AF1-128 O1 | Adder | 45.83 MW | 38.96 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944871 | AF1-152 C | Adder | 6.11 MW | 5.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 945361 | AF1-201 C O1 | Adder | 18.49 MW | 15.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958501 | AF2-144 C | Adder | 1.98 MW | 1.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 960091 | AF2-300 C | Adder | 2.4 MW | 2.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961711 | AG1-011 | Adder | 33.53 MW | 28.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961951 | AG1-038 C | Adder | 3.51 MW | 2.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966661 | AG1-536 C | Adder | 5.88 MW | 5.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966871 | AG1-558 C | Adder | 2.67 MW | 2.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966881 | AG1-559 C | Adder | 2.66 MW | 2.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315098 | 1CHESPKA | 80/20 | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315099 | 1CHESPKB | 80/20 | 0.88 MW | 0.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315108 | 1ELIZAR1 | 80/20 | 3.92 MW | 3.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315109 | 1ELIZAR2 | 80/20 | 3.85 MW | 3.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315110 | 1ELIZAR3 | 80/20 | 3.97 MW | 3.97 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315225 | 1N ANNA1 | 80/20 | 60.3 MW | 60.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315226 | 1N ANNA2 | 80/20 | 60.3 MW | 60.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315233 | 1SURRY 2 | 80/20 | 30.31 MW | 30.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315260 | 1GOSPORTA | 80/20 | 0.42 MW | 0.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315261 | 1GOSPORTB | 80/20 | 0.54 MW | 0.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 315262 | 1GOSPORTC | 80/20 | 0.46 MW | 0.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316108 | AB2-160 C | 80/20 | 6.39 MW | 6.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316132 | AB2-190 C | Adder | 22.01 MW | 18.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932044 | AC2-012 C | 80/20 | 9.42 MW | 9.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 932591 | AC2-079 C O1 | Adder | 6.71 MW | 5.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938535 | AE1-072 C | Adder | 20.47 MW | 17.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 938551 | AE1-074 C | 80/20 | 0.5 MW | 0.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939195 | AE1-149 C | Adder | 12.57 MW | 10.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939245 | AE1-155 C | Adder | 14.01 MW | 11.91 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939261 | AE1-157 C O1 | Adder | 15.46 MW | 13.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939414 | AE1-173_C1 | 80/20 | 36.3 MW | 36.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939415 | AE1-173_C2 | 80/20 | 31.11 MW | 31.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939416 | AE1-173_C3 | 80/20 | 36.3 MW | 36.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939431 | AE1-175 C | Adder | 2.77 MW | 2.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 939611 | AE1-191 C | Adder | 12.0 MW | 10.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940231 | AE2-005 C | Adder | 1.53 MW | 1.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940431 | AE2-027 C O1 | 80/20 | 15.12 MW | 15.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940541 | AE2-040 | Adder | 3.19 MW | 2.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940551 | AE2-041 | Adder | 8.04 MW | 6.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 940651 | AE2-052 | Adder | 4.19 MW | 3.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941101 | AE2-104 C O1 | Adder | 3.9 MW | 3.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941281 | AE2-122 C O1 | Adder | 33.32 MW | 28.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941291 | AE2-123 C O1 | Adder | 34.25 MW | 29.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941301 | AE2-124 C O1 | Adder | 31.14 MW | 26.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941381 | AE2-134 | Adder | -3.7 MW | -3.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946261 | AF1-291 C | 80/20 | 2.53 MW | 2.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 946371 | AF1-301 C | Adder | 13.65 MW | 11.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957411 | AF2-035 C | Adder | 9.61 MW | 8.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957431 | AF2-037 C | 80/20 | 13.86 MW | 13.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957491 | AF2-043 C | Adder | 2.49 MW | 2.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957601 | AF2-054 C | Adder | 2.38 MW | 2.02 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957631 | AF2-057 | 80/20 | 4.2 MW | 4.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957691 | AF2-063 C | 80/20 | 22.11 MW | 22.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957711 | AF2-065 C | Adder | 16.03 MW | 13.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962531 | AG1-102 C | Adder | 1.26 MW | 1.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962841 | AG1-133 C O1 | 80/20 | 25.09 MW | 25.09 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962861 | AG1-135 C | Adder | 6.65 MW | 5.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962961 | AG1-145 C | Adder | 2.5 MW | 2.12 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962971 | AG1-146 C | Adder | 3.41 MW | 2.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962981 | AG1-147 C | Adder | 7.96 MW | 6.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963051 | AG1-154 C | Adder | 3.92 MW | 3.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963221 | AG1-171 C | Adder | 2.51 MW | 2.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963231 | AG1-172 C | Adder | 2.51 MW | 2.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963241 | AG1-173 C | Adder | 2.51 MW | 2.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963251 | AG1-174 C | Adder | 2.51 MW | 2.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 963621 | AG1-213 C | Adder | 0.8 MW | 0.68 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964211 | AG1-282 C | Adder | 2.17 MW | 1.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964421 | AG1-305 C O2 | 80/20 | 17.39 MW | 17.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 964951 | AG1-359 O1 | Adder | 26.72 MW | 22.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965001 | AG1-364 C O1 | 80/20 | 8.4 MW | 8.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933294 | AC2-141 C | 80/20 | 35.75 MW | 35.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941501 | AE2-147 C | Adder | 18.34 MW | 15.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 941591 | AE2-156 O1 | 80/20 | 21.01 MW | 21.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 942001 | AE2-212 C | 80/20 | 2.53 MW | 2.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957831 | AF2-077 C | Adder | 2.45 MW | 2.08 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957871 | AF2-081 C | Adder | 11.65 MW | 9.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 957911 | AF2-085 | 80/20 | 4.6 MW | 4.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958161 | AF2-110 C | Adder | 1.61 MW | 1.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 958261 | AF2-120 C | Adder | 6.84 MW | 5.82 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 966611 | AG1-531 C | Adder | 6.77 MW | 5.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944581 | AF1-123 C O1 | 80/20 | 56.33 MW | 56.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944591 | AF1-124 C O1 | 80/20 | 56.33 MW | 56.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 944601 | AF1-125 C O1 | 80/20 | 56.33 MW | 56.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 933981 | AD1-022 C | Adder | 9.78 MW | 8.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961681 | AG1-008 C | Adder | 18.68 MW | 15.87 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962271 | AG1-075 C O1 | 80/20 | 19.59 MW | 19.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 962571 | AG1-106 C | Adder | 6.25 MW | 5.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 965281 | AG1-393 C | Adder | 2.44 MW | 2.07 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 316083 | AB2-161 C | Adder | 3.97 MW | 3.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | 961611 | AG1-000B C | Adder | 18.63 MW | 15.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.7 MW | 5.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.73 MW | 1.73 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 104.86 MW | 104.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 28.9 MW | 28.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.63 MW | 35.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.63 MW | 8.63 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.57 MW | 8.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.58 MW | 0.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.58 MW | 1.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.58 MW | 4.58 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.77 MW | 2.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.28 MW | 0.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.0 MW | 7.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.72 MW | 0.72 MW |
| Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963291 | AG1-178 C O2 | Adder | 50.69 MW | 43.09 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963351 | AG1-184 O2 | Adder | 27.31 MW | 23.21 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 965811 | AG1-449 | Adder | 18.4 MW | 15.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944011 | AF1-069 C | Adder | 10.26 MW | 8.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941031 | AE2-094 C | Adder | 31.39 MW | 26.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 940641 | AE2-051 C O1 | Adder | 14.07 MW | 11.96 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 314229 | 6MT RD221 | 80/20 | 0.11 MW | 0.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 314236 | 6NRTHEST | 80/20 | 0.17 MW | 0.17 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 314241 | 6OLDCHRC | 80/20 | 0.79 MW | 0.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 314250 | 6ROCKVILLE | 80/20 | 0.31 MW | 0.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 314309 | 6IRON208 | 80/20 | 0.41 MW | 0.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315037 | 1LDYSMT1 | 80/20 | 4.6 MW | 4.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315038 | 1LDYSMT2 | 80/20 | 4.6 MW | 4.6 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315039 | 1LDYSMT3 | 80/20 | 4.43 MW | 4.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315040 | 1LDYSMT4 | 80/20 | 4.43 MW | 4.43 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315041 | 1LDYSMT5 | 80/20 | 4.45 MW | 4.45 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315051 | 1AA1-145 CT1 | 80/20 | 4.82 MW | 4.82 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315052 | 1AA1-145 CT2 | 80/20 | 4.82 MW | 4.82 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315060 | 1CHESTF5 | Adder | 56.64 MW | 48.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315065 | 1CHESTF6 | Adder | 91.54 MW | 77.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315067 | 1DARBY 1 | 80/20 | 2.39 MW | 2.39 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315068 | 1DARBY 2 | 80/20 | 2.39 MW | 2.39 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315069 | 1DARBY 3 | 80/20 | 2.4 MW | 2.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315070 | 1DARBY 4 | 80/20 | 2.4 MW | 2.4 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315083 | 1SPRUNCA | 80/20 | 9.46 MW | 9.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315084 | 1SPRUNCB | 80/20 | 9.46 MW | 9.46 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 925863 | AC1-065 C | Adder | 5.33 MW | 4.53 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 926737 | AC1-158 C1 | 80/20 | 6.04 MW | 6.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 926738 | AC1-158 C2 | 80/20 | 6.04 MW | 6.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 926754 | AC1-161 C | Adder | 26.68 MW | 22.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 926784 | AC1-164 C | Adder | 35.74 MW | 30.38 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 927044 | AC1-191 C | Adder | 8.43 MW | 7.16 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 934014 | AD1-025 C | Adder | 15.0 MW | 12.75 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 934061 | AD1-033 C | Adder | 6.57 MW | 5.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 934141 | AD1-041 C | Adder | 4.58 MW | 3.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 934575 | AD1-082 C | Adder | 6.8 MW | 5.78 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 935164 | AD1-151 C | Adder | 14.36 MW | 12.2 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 936661 | AD2-085 C | Adder | 3.01 MW | 2.56 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 936761 | AD2-097 C | 80/20 | 1.79 MW | 1.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 937221 | AD2-160 C O1 | Adder | 5.11 MW | 4.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942151 | AE2-227 C | 80/20 | 1.96 MW | 1.96 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942161 | AE2-228 C | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942191 | AE2-231 C O1 | 80/20 | 4.34 MW | 4.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942341 | AE2-247 C | Adder | 1.3 MW | 1.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942371 | AE2-250 C O1 | Adder | 8.59 MW | 7.3 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942401 | AE2-253 C | Adder | 5.37 MW | 4.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942551 | AE2-270 | Adder | 23.9 MW | 20.31 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 943431 | AF1-014 C | Adder | 1.1 MW | 0.94 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 943461 | AF1-017 C | Adder | 1.18 MW | 1.0 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 943471 | AF1-018 | Adder | 6.16 MW | 5.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 943611 | AF1-032 C | Adder | 1.52 MW | 1.29 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 943621 | AF1-033 C | Adder | 2.09 MW | 1.77 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944631 | AF1-128 O1 | Adder | 35.44 MW | 30.12 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944871 | AF1-152 C | Adder | 4.57 MW | 3.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 945361 | AF1-201 C O1 | Adder | 14.06 MW | 11.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 960091 | AF2-300 C | 80/20 | 1.97 MW | 1.97 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 961711 | AG1-011 | Adder | 25.47 MW | 21.65 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 966871 | AG1-558 C | Adder | 2.1 MW | 1.78 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 966881 | AG1-559 C | 80/20 | 2.19 MW | 2.19 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315225 | 1N ANNA1 | 80/20 | 33.49 MW | 33.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315226 | 1N ANNA2 | 80/20 | 33.5 MW | 33.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 316108 | AB2-160 C | Adder | 4.84 MW | 4.11 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 316132 | AB2-190 C | Adder | 16.74 MW | 14.23 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 932044 | AC2-012 C | Adder | 7.04 MW | 5.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 932591 | AC2-079 C O1 | Adder | 5.03 MW | 4.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 938535 | AE1-072 C | Adder | 15.29 MW | 12.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 938551 | AE1-074 C | 80/20 | 0.37 MW | 0.37 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939195 | AE1-149 C | Adder | 9.45 MW | 8.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939261 | AE1-157 C O1 | 80/20 | 12.74 MW | 12.74 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939414 | AE1-173_C1 | Adder | 26.26 MW | 22.32 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939415 | AE1-173_C2 | Adder | 22.51 MW | 19.14 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939416 | AE1-173_C3 | Adder | 26.26 MW | 22.32 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939431 | AE1-175 C | Adder | 2.13 MW | 1.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 939611 | AE1-191 C | Adder | 9.15 MW | 7.78 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 940231 | AE2-005 C | Adder | 1.17 MW | 0.99 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 940431 | AE2-027 C O1 | Adder | 11.52 MW | 9.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 940551 | AE2-041 | Adder | 6.16 MW | 5.24 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 940651 | AE2-052 | Adder | 3.15 MW | 2.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941101 | AE2-104 C O1 | Adder | 2.92 MW | 2.48 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941281 | AE2-122 C O1 | Adder | 24.88 MW | 21.15 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941291 | AE2-123 C O1 | Adder | 25.57 MW | 21.73 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941301 | AE2-124 C O1 | Adder | 23.25 MW | 19.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 946261 | AF1-291 C | Adder | 1.93 MW | 1.64 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957411 | AF2-035 C | 80/20 | 7.89 MW | 7.89 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957431 | AF2-037 C | Adder | 9.08 MW | 7.72 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957491 | AF2-043 C | Adder | 1.86 MW | 1.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957601 | AF2-054 C | Adder | 1.81 MW | 1.54 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957631 | AF2-057 | Adder | 3.14 MW | 2.67 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957691 | AF2-063 C | Adder | 14.5 MW | 12.32 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957711 | AF2-065 C | Adder | 12.19 MW | 10.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 962531 | AG1-102 C | Adder | 0.96 MW | 0.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 962841 | AG1-133 C O1 | 80/20 | 16.57 MW | 16.57 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 962961 | AG1-145 C | Adder | 1.92 MW | 1.63 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963051 | AG1-154 C | Adder | 3.25 MW | 2.77 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963221 | AG1-171 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963231 | AG1-172 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963241 | AG1-173 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963251 | AG1-174 C | Adder | 1.91 MW | 1.62 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 963621 | AG1-213 C | 80/20 | 0.66 MW | 0.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 964271 | AG1-288 C | Adder | 14.64 MW | 12.44 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 964281 | AG1-289 | Adder | 8.09 MW | 6.88 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 964421 | AG1-305 C O2 | Adder | 11.4 MW | 9.69 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 964951 | AG1-359 O1 | Adder | 19.94 MW | 16.95 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 965001 | AG1-364 C O1 | Adder | 6.28 MW | 5.33 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 933294 | AC2-141 C | Adder | 26.68 MW | 22.68 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941501 | AE2-147 C | Adder | 13.71 MW | 11.66 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941581 | AE2-155 C | 80/20 | 0.1 MW | 0.1 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 941591 | AE2-156 O1 | Adder | 15.69 MW | 13.34 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 942001 | AE2-212 C | Adder | 1.91 MW | 1.63 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957831 | AF2-077 C | Adder | 1.86 MW | 1.58 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957871 | AF2-081 C | Adder | 8.7 MW | 7.39 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 957911 | AF2-085 | 80/20 | 3.28 MW | 3.28 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 958161 | AF2-110 C | Adder | 1.2 MW | 1.02 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 966611 | AG1-531 C | Adder | 5.13 MW | 4.36 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944581 | AF1-123 C O1 | Adder | 42.0 MW | 35.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944591 | AF1-124 C O1 | Adder | 42.0 MW | 35.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 944601 | AF1-125 C O1 | Adder | 42.0 MW | 35.7 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 962271 | AG1-075 C O1 | Adder | 14.83 MW | 12.61 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315043 | 1FOUR RIVERA | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315044 | 1FOUR RIVERB | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315045 | 1FOUR RIVERC | 80/20 | 3.74 MW | 3.74 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315046 | 1FOUR RIVERD | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315047 | 1FOUR RIVERE | 80/20 | 3.06 MW | 3.06 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 315048 | 1FOUR RIVERF | 80/20 | 3.74 MW | 3.74 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 316083 | AB2-161 C | Adder | 2.98 MW | 2.54 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | 961611 | AG1-000B C | Adder | 14.1 MW | 11.98 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.49 MW | 4.49 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.76 MW | 1.76 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 86.39 MW | 86.39 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 40.42 MW | 40.42 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 37.9 MW | 37.9 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 6.79 MW | 6.79 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.5 MW | 8.5 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.41 MW | 0.41 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.04 MW | 2.04 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.52 MW | 5.52 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.81 MW | 2.81 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.35 MW | 0.35 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.92 MW | 6.92 MW |
| 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.97 MW | 0.97 MW |
| Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961941 | AG1-037 C | Adder | 0.55 MW | 0.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962331 | AG1-082 C | Adder | 2.18 MW | 1.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962341 | AG1-083 C | Adder | 2.18 MW | 1.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963041 | AG1-153 C | Adder | 6.06 MW | 5.15 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963111 | AG1-160 C | Adder | 6.13 MW | 5.21 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963291 | AG1-178 C O2 | 80/20 | 69.88 MW | 69.88 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963351 | AG1-184 O2 | 80/20 | 37.65 MW | 37.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964801 | AG1-343 C | Adder | 6.49 MW | 5.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965291 | AG1-394 C | Adder | 2.23 MW | 1.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965691 | AG1-437 C O1 | Adder | 11.09 MW | 9.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965701 | AG1-438 C O1 | Adder | 11.09 MW | 9.43 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965741 | AG1-442 O1 | Adder | 6.47 MW | 5.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965751 | AG1-443 O1 | Adder | 6.47 MW | 5.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965811 | AG1-449 | 80/20 | 25.38 MW | 25.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966361 | AG1-505 C | Adder | 18.06 MW | 15.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966371 | AG1-506 C | Adder | 18.06 MW | 15.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966621 | AG1-532 C | Adder | 1.48 MW | 1.25 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 313506 | AB1-173 C OP | Adder | 7.25 MW | 6.16 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314572 | 3EMPORIA | Adder | 0.45 MW | 0.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926070 | AC1-086 C | Adder | 22.12 MW | 18.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934521 | AD1-076 C | Adder | 59.94 MW | 50.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934615 | AD1-087 C | Adder | 7.76 MW | 6.6 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 937481 | AD2-202 C O1 | Adder | 2.27 MW | 1.93 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942931 | AE2-313 C | 80/20 | 39.14 MW | 39.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943171 | AE2-346 C | Adder | 1.53 MW | 1.3 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944011 | AF1-069 C | 80/20 | 14.17 MW | 14.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 945811 | AF1-246 C O1 | Adder | 7.83 MW | 6.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 960081 | AF2-299 C | Adder | 2.73 MW | 2.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315293 | 1DOMTR9 | Adder | 7.45 MW | 6.33 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315294 | 1DOMTR10 | Adder | 9.13 MW | 7.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316140 | AB2-099 C | Adder | 0.64 MW | 0.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 923262 | AB1-132 C OP | Adder | 15.02 MW | 12.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 923991 | AB2-040 C O1 | Adder | 7.9 MW | 6.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940491 | AE2-034 C | Adder | 8.01 MW | 6.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941031 | AE2-094 C | 80/20 | 43.37 MW | 43.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946281 | AF1-292 C | Adder | 1.62 MW | 1.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957481 | AF2-042 C | Adder | 55.93 MW | 47.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957521 | AF2-046 C | Adder | 18.34 MW | 15.59 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957531 | AF2-047 C | Adder | 19.02 MW | 16.17 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938771 | AE1-103 C | Adder | 3.28 MW | 2.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940481 | AE2-033 C | Adder | 17.66 MW | 15.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940641 | AE2-051 C O1 | 80/20 | 19.35 MW | 19.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946011 | AF1-266 | Adder | 14.78 MW | 12.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933501 | AC2-165 C | Adder | 10.42 MW | 8.86 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314236 | 6NRTHEST | 80/20 | 0.22 MW | 0.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314250 | 6ROCKVILLE | 80/20 | 0.4 MW | 0.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314309 | 6IRON208 | 80/20 | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314314 | 3LOCKS | 80/20 | 0.35 MW | 0.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314491 | 3PENDLTN | 80/20 | 0.39 MW | 0.39 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 314507 | 3THOMPSN | 80/20 | 0.4 MW | 0.4 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315060 | 1CHESTF5 | Adder | 71.81 MW | 61.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315065 | 1CHESTF6 | 80/20 | 117.66 MW | 117.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315077 | 1HOPHCF1 | 80/20 | 2.91 MW | 2.91 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315078 | 1HOPHCF2 | 80/20 | 2.91 MW | 2.91 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315079 | 1HOPHCF3 | 80/20 | 2.91 MW | 2.91 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315080 | 1HOPHCF4 | 80/20 | 4.42 MW | 4.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315083 | 1SPRUNCA | 80/20 | 12.31 MW | 12.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315084 | 1SPRUNCB | 80/20 | 12.31 MW | 12.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 925863 | AC1-065 C | Adder | 6.83 MW | 5.81 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926661 | AC1-147 C | 80/20 | 0.44 MW | 0.44 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926754 | AC1-161 C | 80/20 | 35.14 MW | 35.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 926784 | AC1-164 C | Adder | 44.72 MW | 38.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 927044 | AC1-191 C | Adder | 10.49 MW | 8.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934014 | AD1-025 C | Adder | 19.38 MW | 16.47 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934061 | AD1-033 C | 80/20 | 8.65 MW | 8.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934141 | AD1-041 C | Adder | 5.88 MW | 5.0 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 934575 | AD1-082 C | Adder | 8.89 MW | 7.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 935164 | AD1-151 C | Adder | 18.52 MW | 15.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936591 | AD2-074 C | Adder | 5.94 MW | 5.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936661 | AD2-085 C | Adder | 3.95 MW | 3.35 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 936761 | AD2-097 C | 80/20 | 2.34 MW | 2.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 937221 | AD2-160 C O1 | Adder | 6.72 MW | 5.71 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942151 | AE2-227 C | 80/20 | 2.48 MW | 2.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942161 | AE2-228 C | 80/20 | 2.48 MW | 2.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942191 | AE2-231 C O1 | Adder | 5.14 MW | 4.37 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942341 | AE2-247 C | Adder | 1.71 MW | 1.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942371 | AE2-250 C O1 | 80/20 | 11.14 MW | 11.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942401 | AE2-253 C | Adder | 7.07 MW | 6.01 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942551 | AE2-270 | Adder | 30.86 MW | 26.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943431 | AF1-014 C | Adder | 1.42 MW | 1.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943461 | AF1-017 C | Adder | 1.55 MW | 1.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943471 | AF1-018 | Adder | 7.88 MW | 6.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943611 | AF1-032 C | Adder | 2.0 MW | 1.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943621 | AF1-033 C | Adder | 2.71 MW | 2.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 943741 | AF1-042 C | Adder | 3.11 MW | 2.64 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944631 | AF1-128 O1 | Adder | 44.93 MW | 38.19 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944871 | AF1-152 C | Adder | 6.01 MW | 5.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 945361 | AF1-201 C O1 | Adder | 18.14 MW | 15.41 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 958501 | AF2-144 C | Adder | 1.96 MW | 1.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 960091 | AF2-300 C | Adder | 2.34 MW | 1.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961711 | AG1-011 | Adder | 32.91 MW | 27.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961951 | AG1-038 C | Adder | 3.44 MW | 2.92 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966661 | AG1-536 C | Adder | 5.76 MW | 4.89 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966871 | AG1-558 C | Adder | 2.61 MW | 2.22 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966881 | AG1-559 C | Adder | 2.59 MW | 2.2 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315098 | 1CHESPKA | 80/20 | 0.52 MW | 0.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315099 | 1CHESPKB | 80/20 | 0.87 MW | 0.87 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315108 | 1ELIZAR1 | 80/20 | 3.85 MW | 3.85 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315109 | 1ELIZAR2 | 80/20 | 3.78 MW | 3.78 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315110 | 1ELIZAR3 | 80/20 | 3.9 MW | 3.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315225 | 1N ANNA1 | 80/20 | 59.99 MW | 59.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315226 | 1N ANNA2 | 80/20 | 59.99 MW | 59.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315233 | 1SURRY 2 | 80/20 | 29.77 MW | 29.77 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315260 | 1GOSPORTA | 80/20 | 0.42 MW | 0.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315261 | 1GOSPORTB | 80/20 | 0.53 MW | 0.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 315262 | 1GOSPORTC | 80/20 | 0.45 MW | 0.45 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316108 | AB2-160 C | 80/20 | 6.27 MW | 6.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316132 | AB2-190 C | Adder | 21.6 MW | 18.36 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316258 | AE1-162 C | 80/20 | 0.42 MW | 0.42 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 932044 | AC2-012 C | 80/20 | 9.26 MW | 9.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 932591 | AC2-079 C O1 | Adder | 6.59 MW | 5.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938535 | AE1-072 C | Adder | 20.12 MW | 17.11 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 938551 | AE1-074 C | 80/20 | 0.49 MW | 0.49 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939195 | AE1-149 C | Adder | 12.35 MW | 10.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939245 | AE1-155 C | Adder | 13.71 MW | 11.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939261 | AE1-157 C O1 | Adder | 15.01 MW | 12.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939414 | AE1-173_C1 | 80/20 | 35.75 MW | 35.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939415 | AE1-173_C2 | 80/20 | 30.64 MW | 30.64 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939416 | AE1-173_C3 | 80/20 | 35.75 MW | 35.75 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939431 | AE1-175 C | Adder | 2.71 MW | 2.31 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 939611 | AE1-191 C | Adder | 11.76 MW | 9.99 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940231 | AE2-005 C | Adder | 1.5 MW | 1.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940431 | AE2-027 C O1 | 80/20 | 14.84 MW | 14.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940541 | AE2-040 | Adder | 3.14 MW | 2.67 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940551 | AE2-041 | Adder | 7.88 MW | 6.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 940651 | AE2-052 | Adder | 4.12 MW | 3.5 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941101 | AE2-104 C O1 | Adder | 3.84 MW | 3.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941281 | AE2-122 C O1 | 80/20 | 32.76 MW | 32.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941291 | AE2-123 C O1 | 80/20 | 33.66 MW | 33.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941301 | AE2-124 C O1 | 80/20 | 30.61 MW | 30.61 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946261 | AF1-291 C | 80/20 | 2.48 MW | 2.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 946371 | AF1-301 C | Adder | 13.87 MW | 11.79 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957411 | AF2-035 C | Adder | 9.34 MW | 7.94 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957431 | AF2-037 C | 80/20 | 13.95 MW | 13.95 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957491 | AF2-043 C | Adder | 2.45 MW | 2.08 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957601 | AF2-054 C | Adder | 2.33 MW | 1.98 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957631 | AF2-057 | 80/20 | 4.13 MW | 4.13 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957691 | AF2-063 C | 80/20 | 22.27 MW | 22.27 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957711 | AF2-065 C | Adder | 15.74 MW | 13.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962531 | AG1-102 C | Adder | 1.23 MW | 1.05 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962841 | AG1-133 C O1 | 80/20 | 24.76 MW | 24.76 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962861 | AG1-135 C | Adder | 6.51 MW | 5.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962961 | AG1-145 C | Adder | 2.45 MW | 2.08 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962971 | AG1-146 C | Adder | 3.34 MW | 2.84 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962981 | AG1-147 C | Adder | 7.79 MW | 6.62 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963051 | AG1-154 C | Adder | 3.8 MW | 3.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963221 | AG1-171 C | Adder | 2.47 MW | 2.1 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963231 | AG1-172 C | Adder | 2.47 MW | 2.1 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963241 | AG1-173 C | Adder | 2.47 MW | 2.1 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963251 | AG1-174 C | Adder | 2.47 MW | 2.1 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 963621 | AG1-213 C | Adder | 0.78 MW | 0.66 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964211 | AG1-282 C | Adder | 2.12 MW | 1.8 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964421 | AG1-305 C O2 | 80/20 | 17.52 MW | 17.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 964951 | AG1-359 O1 | 80/20 | 26.26 MW | 26.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965001 | AG1-364 C O1 | 80/20 | 8.26 MW | 8.26 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933294 | AC2-141 C | 80/20 | 35.14 MW | 35.14 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941501 | AE2-147 C | Adder | 18.03 MW | 15.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 941591 | AE2-156 O1 | 80/20 | 20.65 MW | 20.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 942001 | AE2-212 C | 80/20 | 2.48 MW | 2.48 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957831 | AF2-077 C | Adder | 2.4 MW | 2.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957871 | AF2-081 C | Adder | 11.45 MW | 9.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 957911 | AF2-085 | 80/20 | 4.54 MW | 4.54 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 958161 | AF2-110 C | Adder | 1.58 MW | 1.34 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 958261 | AF2-120 C | Adder | 6.69 MW | 5.69 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 966611 | AG1-531 C | Adder | 6.65 MW | 5.65 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944581 | AF1-123 C O1 | 80/20 | 55.38 MW | 55.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944591 | AF1-124 C O1 | 80/20 | 55.38 MW | 55.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 944601 | AF1-125 C O1 | 80/20 | 55.38 MW | 55.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 933981 | AD1-022 C | Adder | 9.62 MW | 8.18 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961681 | AG1-008 C | Adder | 18.37 MW | 15.62 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962271 | AG1-075 C O1 | 80/20 | 19.23 MW | 19.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 962571 | AG1-106 C | Adder | 6.15 MW | 5.23 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 965281 | AG1-393 C | Adder | 2.4 MW | 2.04 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 316083 | AB2-161 C | Adder | 3.9 MW | 3.32 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | 961611 | AG1-000B C | Adder | 18.3 MW | 15.55 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.62 MW | 5.62 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.7 MW | 1.7 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 103.38 MW | 103.38 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 28.53 MW | 28.53 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.15 MW | 35.15 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.51 MW | 8.51 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.46 MW | 8.46 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.57 MW | 0.57 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.56 MW | 1.56 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.52 MW | 4.52 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.74 MW | 2.74 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.28 MW | 0.28 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.9 MW | 6.9 MW |
| 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.71 MW | 0.71 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961671 | AG1-007 C | Adder | 1.07 MW | 0.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961941 | AG1-037 C | Adder | 0.64 MW | 0.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962331 | AG1-082 C | Adder | 2.55 MW | 2.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962341 | AG1-083 C | Adder | 2.55 MW | 2.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962491 | AG1-098 C O1 | Adder | 9.67 MW | 8.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963041 | AG1-153 C | 80/20 | 7.01 MW | 7.01 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963111 | AG1-160 C | 80/20 | 7.12 MW | 7.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963291 | AG1-178 C O2 | 80/20 | 85.77 MW | 85.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963301 | AG1-179 C | Adder | 5.43 MW | 4.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963311 | AG1-180 | Adder | 2.64 MW | 2.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963351 | AG1-184 O2 | 80/20 | 46.21 MW | 46.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964801 | AG1-343 C | Adder | 7.48 MW | 6.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966801 | AG1-551 C | Adder | 2.8 MW | 2.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966811 | AG1-552 C | Adder | 2.33 MW | 1.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965291 | AG1-394 C | Adder | 2.57 MW | 2.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965601 | AG1-428 C O2 | Adder | 4.53 MW | 3.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965691 | AG1-437 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965701 | AG1-438 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965711 | AG1-439 C O1 | Adder | 27.25 MW | 23.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965721 | AG1-440 C | Adder | 7.06 MW | 6.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965731 | AG1-441 C | Adder | 7.06 MW | 6.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965741 | AG1-442 O1 | 80/20 | 7.95 MW | 7.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965751 | AG1-443 O1 | 80/20 | 7.95 MW | 7.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965761 | AG1-444 O1 | Adder | 14.53 MW | 12.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965771 | AG1-445 | Adder | 4.08 MW | 3.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965781 | AG1-446 | Adder | 4.08 MW | 3.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965811 | AG1-449 | 80/20 | 29.54 MW | 29.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966361 | AG1-505 C | 80/20 | 20.6 MW | 20.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966371 | AG1-506 C | 80/20 | 20.6 MW | 20.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966621 | AG1-532 C | Adder | 1.41 MW | 1.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313506 | AB1-173 C OP | Adder | 7.21 MW | 6.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | Adder | 0.44 MW | 0.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 8.54 MW | 7.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 8.54 MW | 7.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926070 | AC1-086 C | Adder | 22.89 MW | 19.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | Adder | 7.1 MW | 6.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | Adder | 2.38 MW | 2.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927024 | AC1-189 C | Adder | 9.89 MW | 8.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927145 | AC1-208 C | Adder | 10.14 MW | 8.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | Adder | 10.72 MW | 9.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | 80/20 | 75.19 MW | 75.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934615 | AD1-087 C | Adder | 8.02 MW | 6.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934625 | AD1-088 C | Adder | 10.68 MW | 9.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 8.21 MW | 6.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 2.35 MW | 2.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 45.53 MW | 45.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 1.78 MW | 1.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 16.59 MW | 16.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 3.08 MW | 2.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 8.43 MW | 7.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | Adder | 2.6 MW | 2.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315293 | 1DOMTR9 | Adder | 9.18 MW | 7.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 11.25 MW | 9.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316129 | AC1-054 C | Adder | 7.4 MW | 6.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316140 | AB2-099 C | Adder | 0.74 MW | 0.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | Adder | 15.54 MW | 13.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | Adder | 7.85 MW | 6.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 7.3 MW | 6.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | Adder | 10.12 MW | 8.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C | Adder | 8.07 MW | 6.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | 80/20 | 10.28 MW | 10.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 4.78 MW | 4.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 2.99 MW | 2.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 50.76 MW | 50.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941791 | AE2-182 C | Adder | 1.74 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | Adder | 1.54 MW | 1.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 60.22 MW | 51.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 21.27 MW | 18.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | 80/20 | 24.43 MW | 24.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 8.98 MW | 7.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C | 80/20 | 4.01 MW | 4.01 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | Adder | 15.24 MW | 12.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 24.42 MW | 24.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | Adder | 12.76 MW | 10.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 313526 | AB2-022 C | 80/20 | 0.62 MW | 0.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314421 | 6WINCHST | 80/20 | 0.18 MW | 0.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314491 | 3PENDLTN | 80/20 | 0.55 MW | 0.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314507 | 3THOMPSN | 80/20 | 0.55 MW | 0.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314638 | 6ELIZ CT | 80/20 | 0.36 MW | 0.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314639 | 6TANGLEW | 80/20 | 0.66 MW | 0.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314643 | 3O INLET | 80/20 | 0.73 MW | 0.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315092 | 1YORKTN3 | 80/20 | 32.53 MW | 32.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | 80/20 | 0.62 MW | 0.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926754 | AC1-161 C | 80/20 | 57.15 MW | 57.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934014 | AD1-025 C | Adder | 14.54 MW | 12.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | 80/20 | 12.29 MW | 12.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934575 | AD1-082 C | Adder | 7.03 MW | 5.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | 80/20 | 0.44 MW | 0.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 4.42 MW | 4.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | 80/20 | 9.48 MW | 9.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 1.91 MW | 1.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | 80/20 | 9.98 MW | 9.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | Adder | 22.2 MW | 18.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 1.73 MW | 1.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | 80/20 | 2.72 MW | 2.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | Adder | 2.84 MW | 2.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | 80/20 | 8.14 MW | 8.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945361 | AF1-201 C O1 | Adder | 17.29 MW | 14.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961711 | AG1-011 | Adder | 24.7 MW | 21.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315098 | 1CHESPKA | 80/20 | 0.73 MW | 0.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315099 | 1CHESPKB | 80/20 | 1.21 MW | 1.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 10.79 MW | 10.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 10.79 MW | 10.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 10.79 MW | 10.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 22.42 MW | 22.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315108 | 1ELIZAR1 | 80/20 | 5.41 MW | 5.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315109 | 1ELIZAR2 | 80/20 | 5.32 MW | 5.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315110 | 1ELIZAR3 | 80/20 | 5.48 MW | 5.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315115 | 1S HAMPT1 | 80/20 | 2.06 MW | 2.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315233 | 1SURRY 2 | 80/20 | 54.03 MW | 54.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315241 | 1Z1-086 GT1 | 80/20 | 13.91 MW | 13.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315242 | 1Z1-086 GT2 | 80/20 | 13.91 MW | 13.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315243 | 1Z1-086 GT3 | 80/20 | 13.91 MW | 13.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315244 | 1Z1-086 ST | 80/20 | 24.18 MW | 24.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315260 | 1GOSPORTA | 80/20 | 0.58 MW | 0.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315261 | 1GOSPORTB | 80/20 | 0.75 MW | 0.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315262 | 1GOSPORTC | 80/20 | 0.63 MW | 0.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315603 | 6AA1-139SOLA | 80/20 | 3.86 MW | 3.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315605 | 6W1-029WIND | 80/20 | 1.8 MW | 1.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315611 | 6Z1-036WIND | 80/20 | 1.09 MW | 1.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316258 | AE1-162 C | 80/20 | 0.49 MW | 0.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932044 | AC2-012 C | 80/20 | 12.94 MW | 12.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | Adder | 6.67 MW | 5.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938535 | AE1-072 C | 80/20 | 28.21 MW | 28.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939414 | AE1-173_C1 | 80/20 | 46.57 MW | 46.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939415 | AE1-173_C2 | 80/20 | 39.92 MW | 39.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939416 | AE1-173_C3 | 80/20 | 46.57 MW | 46.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939431 | AE1-175 C | Adder | 2.21 MW | 1.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 | Adder | 2.68 MW | 2.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | 80/20 | 4.87 MW | 4.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | 80/20 | 46.19 MW | 46.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | 80/20 | 47.47 MW | 47.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | 80/20 | 43.2 MW | 43.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | 80/20 | 3.33 MW | 3.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | 80/20 | 5.77 MW | 5.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | Adder | 11.32 MW | 9.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962531 | AG1-102 C | Adder | 1.03 MW | 0.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962961 | AG1-145 C | Adder | 1.99 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963221 | AG1-171 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963231 | AG1-172 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963241 | AG1-173 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 963251 | AG1-174 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 964951 | AG1-359 O1 | 80/20 | 37.34 MW | 37.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965001 | AG1-364 C O1 | 80/20 | 11.57 MW | 11.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933294 | AC2-141 C | 80/20 | 57.15 MW | 57.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | 80/20 | 24.42 MW | 24.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | 80/20 | 28.93 MW | 28.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957831 | AF2-077 C | Adder | 2.0 MW | 1.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | 80/20 | 16.11 MW | 16.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | 80/20 | 2.01 MW | 2.01 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 966611 | AG1-531 C | 80/20 | 7.32 MW | 7.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | 80/20 | 80.97 MW | 80.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | 80/20 | 80.97 MW | 80.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | 80/20 | 80.97 MW | 80.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | 80/20 | 11.93 MW | 11.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C | Adder | 8.34 MW | 7.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961681 | AG1-008 C | Adder | 21.31 MW | 18.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 962571 | AG1-106 C | Adder | 6.36 MW | 5.41 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 965281 | AG1-393 C | Adder | 2.05 MW | 1.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315614 | AA2-178 C | 80/20 | 2.33 MW | 2.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 316083 | AB2-161 C | Adder | 3.09 MW | 2.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 961611 | AG1-000B C | Adder | 17.64 MW | 15.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 5.82 MW | 5.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.5 MW | 1.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 102.45 MW | 102.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.75 MW | 24.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.15 MW | 31.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.81 MW | 8.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.64 MW | 7.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.49 MW | 0.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.26 MW | 1.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.92 MW | 3.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.61 MW | 1.61 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.23 MW | 0.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.14 MW | 6.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.61 MW | 0.61 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 961941 | AG1-037 C | 80/20 | 0.19 MW | 0.19 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 962331 | AG1-082 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 962341 | AG1-083 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963301 | AG1-179 C | 80/20 | 2.4 MW | 2.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963311 | AG1-180 | 80/20 | 1.17 MW | 1.17 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 964801 | AG1-343 C | 80/20 | 2.38 MW | 2.38 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 966811 | AG1-552 C | 80/20 | 0.89 MW | 0.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965291 | AG1-394 C | 80/20 | 0.82 MW | 0.82 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965601 | AG1-428 C O2 | 80/20 | 2.01 MW | 2.01 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965691 | AG1-437 C O1 | 80/20 | 3.56 MW | 3.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965701 | AG1-438 C O1 | 80/20 | 3.56 MW | 3.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965741 | AG1-442 O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965751 | AG1-443 O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 966621 | AG1-532 C | 80/20 | 0.73 MW | 0.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 313506 | AB1-173 C OP | 80/20 | 3.29 MW | 3.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 313719 | 3CHESTNUT | 80/20 | 0.44 MW | 0.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314572 | 3EMPORIA | 80/20 | 0.22 MW | 0.22 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315126 | 1ROARAP2 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315128 | 1ROARAP4 | 80/20 | 0.57 MW | 0.57 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315136 | 1ROSEMG1 | 80/20 | 0.99 MW | 0.99 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315139 | 1GASTONA | 80/20 | 1.49 MW | 1.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 926070 | AC1-086 C | 80/20 | 9.82 MW | 9.82 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 926201 | AC1-098 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 926211 | AC1-099 C | 80/20 | 0.77 MW | 0.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 927145 | AC1-208 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 934331 | AD1-057 C O1 | 80/20 | 3.93 MW | 3.93 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 934521 | AD1-076 C | 80/20 | 18.52 MW | 18.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 943171 | AE2-346 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 960081 | AF2-299 C | 80/20 | 1.35 MW | 1.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315606 | 3AA2-053SOLA | 80/20 | 0.64 MW | 0.64 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316129 | AC1-054 C | 80/20 | 2.53 MW | 2.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316140 | AB2-099 C | 80/20 | 0.22 MW | 0.22 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 923262 | AB1-132 C OP | 80/20 | 6.67 MW | 6.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 923991 | AB2-040 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 932631 | AC2-084 C | 80/20 | 3.28 MW | 3.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 940491 | AE2-034 C | 80/20 | 2.39 MW | 2.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 946281 | AF1-292 C | 80/20 | 0.8 MW | 0.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 957521 | AF2-046 C | 80/20 | 6.59 MW | 6.59 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 957531 | AF2-047 C | 80/20 | 5.68 MW | 5.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 938771 | AE1-103 C | 80/20 | 1.16 MW | 1.16 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 940481 | AE2-033 C | 80/20 | 11.61 MW | 11.61 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 946011 | AF1-266 | 80/20 | 9.72 MW | 9.72 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314314 | 3LOCKS | 80/20 | 0.25 MW | 0.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314435 | 6SAPONY | 80/20 | 0.32 MW | 0.32 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315065 | 1CHESTF6 | 80/20 | 187.55 MW | 187.55 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315076 | 1HOPPOLC | 80/20 | 1.49 MW | 1.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315077 | 1HOPHCF1 | 80/20 | 2.33 MW | 2.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315078 | 1HOPHCF2 | 80/20 | 2.33 MW | 2.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315079 | 1HOPHCF3 | 80/20 | 2.33 MW | 2.33 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315080 | 1HOPHCF4 | 80/20 | 3.53 MW | 3.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 927225 | AC1-216 C | 80/20 | 1.14 MW | 1.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 934014 | AD1-025 C | 80/20 | 11.49 MW | 11.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 934575 | AD1-082 C | 80/20 | 6.58 MW | 6.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 935111 | AD1-144 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 935164 | AD1-151 C | 80/20 | 11.91 MW | 11.91 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 936661 | AD2-085 C | 80/20 | 1.84 MW | 1.84 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 936761 | AD2-097 C | Adder | -2.63 MW | -2.24 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 942161 | AE2-228 C | 80/20 | 3.77 MW | 3.77 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 942341 | AE2-247 C | 80/20 | 0.8 MW | 0.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 942371 | AE2-250 C O1 | 80/20 | 7.92 MW | 7.92 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 942551 | AE2-270 | 80/20 | 18.88 MW | 18.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 943461 | AF1-017 C | 80/20 | 0.72 MW | 0.72 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 943621 | AF1-033 C | 80/20 | 1.06 MW | 1.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 961711 | AG1-011 | 80/20 | 19.51 MW | 19.51 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315115 | 1S HAMPT1 | 80/20 | 0.62 MW | 0.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315116 | 1SURRY 1 | 80/20 | 12.53 MW | 12.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315117 | 1GRAVELC | 80/20 | 0.44 MW | 0.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315119 | 1GRAVEL3 | 80/20 | 1.27 MW | 1.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315120 | 1GRAVEL4 | 80/20 | 1.29 MW | 1.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315121 | 1GRAVEL5 | 80/20 | 1.27 MW | 1.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315122 | 1GRAVEL6 | 80/20 | 1.29 MW | 1.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315141 | 1GASTONB | 80/20 | 1.49 MW | 1.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315607 | 3AA1-063SOLA | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315608 | 3AA2-088SOLA | 80/20 | 0.44 MW | 0.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316033 | AB2-134 C | 80/20 | 1.49 MW | 1.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316087 | AB2-174 C | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316096 | AB2-100 C1 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316098 | AB2-100 C2 | 80/20 | 0.6 MW | 0.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316108 | AB2-160 C | 80/20 | 4.46 MW | 4.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316132 | AB2-190 C | 80/20 | 13.73 MW | 13.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316258 | AE1-162 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 932591 | AC2-079 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 938221 | AE1-035 C | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 939195 | AE1-149 C | 80/20 | 10.09 MW | 10.09 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 940431 | AE2-027 C O1 | 80/20 | 5.66 MW | 5.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 940541 | AE2-040 | 80/20 | 2.11 MW | 2.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 940651 | AE2-052 | 80/20 | 3.36 MW | 3.36 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 941101 | AE2-104 C O1 | 80/20 | 1.32 MW | 1.32 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 946261 | AF1-291 C | 80/20 | 3.8 MW | 3.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 957711 | AF2-065 C | 80/20 | 9.63 MW | 9.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963221 | AG1-171 C | 80/20 | 1.46 MW | 1.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963231 | AG1-172 C | 80/20 | 1.46 MW | 1.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963241 | AG1-173 C | 80/20 | 1.46 MW | 1.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 963251 | AG1-174 C | 80/20 | 1.46 MW | 1.46 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 942001 | AE2-212 C | 80/20 | 3.22 MW | 3.22 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 958161 | AF2-110 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 966611 | AG1-531 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 933981 | AD1-022 C | 80/20 | 3.04 MW | 3.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 961681 | AG1-008 C | 80/20 | 6.6 MW | 6.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 962271 | AG1-075 C O1 | 80/20 | 13.67 MW | 13.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 962571 | AG1-106 C | 80/20 | 2.73 MW | 2.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 965281 | AG1-393 C | 80/20 | 1.61 MW | 1.61 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315602 | 1HOLLOMANSOL | 80/20 | 0.56 MW | 0.56 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 315614 | AA2-178 C | 80/20 | 0.54 MW | 0.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 316083 | AB2-161 C | 80/20 | 2.89 MW | 2.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | 961611 | AG1-000B C | 80/20 | 8.44 MW | 8.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.35 MW | 1.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 23.39 MW | 23.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.63 MW | 5.63 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.04 MW | 7.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.05 MW | 2.05 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.73 MW | 1.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.11 MW | 0.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.28 MW | 0.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.89 MW | 0.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.39 MW | 1.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 314309 | 6IRON208 | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 314421 | 6WINCHST | 80/20 | 0.06 MW | 0.06 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 314507 | 3THOMPSN | 80/20 | 0.11 MW | 0.11 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315060 | 1CHESTF5 | 80/20 | 50.99 MW | 50.99 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315061 | 1CHESTG7 | 80/20 | 3.24 MW | 3.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315062 | 1CHESTS7 | 80/20 | 1.49 MW | 1.49 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315063 | 1CHESTG8 | 80/20 | 3.19 MW | 3.19 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315064 | 1CHESTS8 | 80/20 | 1.64 MW | 1.64 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315076 | 1HOPPOLC | 80/20 | 3.28 MW | 3.28 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315077 | 1HOPHCF1 | 80/20 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315078 | 1HOPHCF2 | 80/20 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315079 | 1HOPHCF3 | 80/20 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315080 | 1HOPHCF4 | 80/20 | 7.78 MW | 7.78 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315092 | 1YORKTN3 | 80/20 | 8.14 MW | 8.14 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 926661 | AC1-147 C | 80/20 | 0.13 MW | 0.13 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 927225 | AC1-216 C | 80/20 | 2.33 MW | 2.33 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 934014 | AD1-025 C | 80/20 | 23.52 MW | 23.52 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 935111 | AD1-144 C | 80/20 | 0.11 MW | 0.11 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 935164 | AD1-151 C | 80/20 | 24.93 MW | 24.93 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 936761 | AD2-097 C | Adder | -0.87 MW | -0.74 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 942151 | AE2-227 C | 80/20 | 1.07 MW | 1.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 | 80/20 | 39.0 MW | 39.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 943621 | AF1-033 C | 80/20 | 1.91 MW | 1.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 944631 | AF1-128 O1 | 80/20 | 31.9 MW | 31.9 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 | 80/20 | 39.94 MW | 39.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315098 | 1CHESPKA | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315099 | 1CHESPKB | 80/20 | 0.25 MW | 0.25 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315116 | 1SURRY 1 | 80/20 | 22.7 MW | 22.7 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315117 | 1GRAVELC | 80/20 | 0.8 MW | 0.8 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315119 | 1GRAVEL3 | 80/20 | 2.31 MW | 2.31 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315120 | 1GRAVEL4 | 80/20 | 2.33 MW | 2.33 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315121 | 1GRAVEL5 | 80/20 | 2.31 MW | 2.31 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315122 | 1GRAVEL6 | 80/20 | 2.33 MW | 2.33 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 315261 | 1GOSPORTB | 80/20 | 0.15 MW | 0.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 316033 | AB2-134 C | 80/20 | 3.05 MW | 3.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 316132 | AB2-190 C | 80/20 | 28.64 MW | 28.64 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 316258 | AE1-162 C | 80/20 | 0.24 MW | 0.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 932044 | AC2-012 C | 80/20 | 2.63 MW | 2.63 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 957631 | AF2-057 | 80/20 | 1.17 MW | 1.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 957711 | AF2-065 C | 80/20 | 19.89 MW | 19.89 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 963221 | AG1-171 C | 80/20 | 3.0 MW | 3.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 963231 | AG1-172 C | 80/20 | 3.0 MW | 3.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 963241 | AG1-173 C | 80/20 | 3.0 MW | 3.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 963251 | AG1-174 C | 80/20 | 3.0 MW | 3.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 966611 | AG1-531 C | 80/20 | 3.67 MW | 3.67 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | 80/20 | 15.85 MW | 15.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.26 MW | 0.26 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.11 MW | 0.11 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.45 MW | 0.45 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.5 MW | 0.5 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.1 MW | 0.1 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.65 MW | 0.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 920042 | AA2-088 E OP | Adder | 9.08 MW | 7.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316097 | AB2-100 E1 | Adder | 2.54 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316099 | AB2-100 E2 | Adder | 2.54 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940491 | AE2-034 C | Adder | 6.24 MW | 5.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940492 | AE2-034 E | Adder | 2.67 MW | 2.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 14.82 MW | 12.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 7.46 MW | 6.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 5.47 MW | 4.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 25.56 MW | 21.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C | Adder | 2.66 MW | 2.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E | Adder | 3.67 MW | 3.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940481 | AE2-033 C | Adder | 15.16 MW | 12.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940482 | AE2-033 E | Adder | 10.22 MW | 8.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946011 | AF1-266 | Adder | 12.69 MW | 10.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 313717 | 6SLIGO L2192 | Adder | 2.01 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314177 | 3HAYES89 | Adder | 0.06 MW | 0.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314189 | 6PAPERMILL | Adder | 8.6 MW | 7.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314229 | 6MT RD221 | 50/50 | 0.24 MW | 0.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314236 | 6NRTHEST | 50/50 | 0.32 MW | 0.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314241 | 6OLDCHRC | 50/50 | 1.49 MW | 1.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314331 | 6POE | Adder | 2.58 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314466 | 6FENTRES | Adder | 2.04 MW | 1.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314525 | 6KINGFORK | Adder | 4.17 MW | 3.54 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314550 | 6HICKORY | Adder | 3.76 MW | 3.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314632 | 6AYDLETOLD | Adder | 2.01 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315051 | 1AA1-145 CT1 | 50/50 | 8.3 MW | 8.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315052 | 1AA1-145 CT2 | 50/50 | 8.3 MW | 8.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315060 | 1CHESTF5 | Adder | 90.49 MW | 76.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315065 | 1CHESTF6 | Adder | 142.59 MW | 121.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315067 | 1DARBY 1 | 50/50 | 4.27 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315068 | 1DARBY 2 | 50/50 | 4.27 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315069 | 1DARBY 3 | 50/50 | 4.29 MW | 4.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315070 | 1DARBY 4 | 50/50 | 4.29 MW | 4.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315073 | 1STONECA | Adder | 9.22 MW | 7.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315083 | 1SPRUNCA | Adder | 14.69 MW | 12.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315084 | 1SPRUNCB | Adder | 14.69 MW | 12.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | Adder | 5.86 MW | 4.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925863 | AC1-065 C | Adder | 7.82 MW | 6.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925865 | AC1-065 E | Adder | 12.57 MW | 10.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926412 | AC1-112 E | 50/50 | 1.9 MW | 1.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926472 | AC1-118 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 1.24 MW | 1.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926754 | AC1-161 C | Adder | 26.85 MW | 22.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926755 | AC1-161 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926784 | AC1-164 C | Adder | 57.34 MW | 48.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926785 | AC1-164 E | Adder | 25.76 MW | 21.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927044 | AC1-191 C | 50/50 | 17.5 MW | 17.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927045 | AC1-191 E | 50/50 | 8.71 MW | 8.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927226 | AC1-216 E | Adder | 9.3 MW | 7.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934014 | AD1-025 C | Adder | 20.32 MW | 17.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934015 | AD1-025 E | Adder | 12.04 MW | 10.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | Adder | 6.9 MW | 5.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | Adder | 4.6 MW | 3.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934141 | AD1-041 C | Adder | 6.64 MW | 5.65 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934142 | AD1-041 E | Adder | 4.43 MW | 3.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934392 | AD1-063 E | Adder | 1.36 MW | 1.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934575 | AD1-082 C | Adder | 8.77 MW | 7.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934576 | AD1-082 E | Adder | 5.0 MW | 4.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934781 | AD1-105 C | Adder | 11.58 MW | 9.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934782 | AD1-105 E | Adder | 7.72 MW | 6.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 0.91 MW | 0.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935164 | AD1-151 C | Adder | 19.95 MW | 16.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935165 | AD1-151 E | Adder | 13.3 MW | 11.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936581 | AD2-073 C | Adder | 2.25 MW | 1.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936582 | AD2-073 E | Adder | 1.12 MW | 0.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936591 | AD2-074 C | Adder | 6.39 MW | 5.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936592 | AD2-074 E | Adder | 10.42 MW | 8.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936661 | AD2-085 C | Adder | 3.46 MW | 2.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936662 | AD2-085 E | Adder | 5.65 MW | 4.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936761 | AD2-097 C | Adder | 2.79 MW | 2.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936762 | AD2-097 E | Adder | 13.93 MW | 11.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | Adder | 5.35 MW | 4.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | Adder | 2.81 MW | 2.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942151 | AE2-227 C | Adder | 3.24 MW | 2.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942152 | AE2-227 E | Adder | 2.16 MW | 1.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942161 | AE2-228 C | Adder | 2.95 MW | 2.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942162 | AE2-228 E | Adder | 1.97 MW | 1.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942191 | AE2-231 C O1 | Adder | 4.15 MW | 3.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942192 | AE2-231 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942341 | AE2-247 C | Adder | 1.5 MW | 1.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942342 | AE2-247 E | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942371 | AE2-250 C O1 | Adder | 12.48 MW | 10.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942372 | AE2-250 E O1 | Adder | 6.58 MW | 5.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | Adder | 5.63 MW | 4.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | Adder | 2.53 MW | 2.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942551 | AE2-270 | Adder | 32.7 MW | 27.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943431 | AF1-014 C | Adder | 1.62 MW | 1.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943432 | AF1-014 E | Adder | 2.86 MW | 2.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943461 | AF1-017 C | Adder | 1.36 MW | 1.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943462 | AF1-017 E | Adder | 2.22 MW | 1.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943471 | AF1-018 | Adder | 9.09 MW | 7.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 1.61 MW | 1.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 0.86 MW | 0.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943621 | AF1-033 C | Adder | 2.58 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943622 | AF1-033 E | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943741 | AF1-042 C | Adder | 3.34 MW | 2.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943742 | AF1-042 E | Adder | 5.45 MW | 4.64 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944631 | AF1-128 O1 | Adder | 56.62 MW | 48.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 4.78 MW | 4.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 3.19 MW | 2.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945361 | AF1-201 C O1 | Adder | 17.99 MW | 15.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945362 | AF1-201 E O1 | Adder | 11.99 MW | 10.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960091 | AF2-300 C | Adder | 1.88 MW | 1.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960092 | AF2-300 E | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961711 | AG1-011 | Adder | 34.52 MW | 29.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961951 | AG1-038 C | Adder | 3.7 MW | 3.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961952 | AG1-038 E | Adder | 5.1 MW | 4.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966661 | AG1-536 C | Adder | 6.16 MW | 5.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966662 | AG1-536 E | Adder | 8.28 MW | 7.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966871 | AG1-558 C | 50/50 | 4.36 MW | 4.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966872 | AG1-558 E | 50/50 | 2.19 MW | 2.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966881 | AG1-559 C | Adder | 2.09 MW | 1.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966882 | AG1-559 E | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316076 | AC2-137 E | Adder | 2.02 MW | 1.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316078 | AC2-138 E | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316108 | AB2-160 C | Adder | 7.02 MW | 5.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316109 | AB2-160 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316132 | AB2-190 C | Adder | 23.18 MW | 19.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316157 | AD2-030 E | Adder | 1.45 MW | 1.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 1.99 MW | 1.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | Adder | 1.74 MW | 1.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 1.13 MW | 0.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923842 | AB2-024 E | Adder | 1.45 MW | 1.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923852 | AB2-025 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924814 | AB2-134 E | Adder | 15.23 MW | 12.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 930122 | AB1-027 E | 50/50 | 1.87 MW | 1.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932044 | AC2-012 C | Adder | 7.49 MW | 6.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932046 | AC2-012 E | Adder | 12.22 MW | 10.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932591 | AC2-079 C O1 | Adder | 6.02 MW | 5.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932592 | AC2-079 E O1 | Adder | 9.83 MW | 8.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938535 | AE1-072 C | Adder | 16.02 MW | 13.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938536 | AE1-072 E | Adder | 8.35 MW | 7.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938552 | AE1-074 E | Adder | 1.56 MW | 1.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939195 | AE1-149 C | Adder | 12.55 MW | 10.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939196 | AE1-149 E | Adder | 8.37 MW | 7.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939245 | AE1-155 C | Adder | 14.66 MW | 12.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939312 | AE1-162 E | Adder | 1.48 MW | 1.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939414 | AE1-173_C1 | Adder | 24.48 MW | 20.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939415 | AE1-173_C2 | Adder | 20.98 MW | 17.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939416 | AE1-173_C3 | Adder | 24.48 MW | 20.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939423 | AE1-173_E1 | Adder | 6.95 MW | 5.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939431 | AE1-175 C | Adder | 2.84 MW | 2.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939432 | AE1-175 E | Adder | 1.41 MW | 1.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939611 | AE1-191 C | Adder | 13.29 MW | 11.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939612 | AE1-191 E | Adder | 8.86 MW | 7.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940231 | AE2-005 C | Adder | 1.71 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940232 | AE2-005 E | Adder | 2.79 MW | 2.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940431 | AE2-027 C O1 | Adder | 17.63 MW | 14.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940432 | AE2-027 E O1 | Adder | 11.75 MW | 9.99 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940541 | AE2-040 | Adder | 2.71 MW | 2.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940551 | AE2-041 | Adder | 9.09 MW | 7.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940651 | AE2-052 | Adder | 4.18 MW | 3.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 3.18 MW | 2.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 5.06 MW | 4.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | Adder | 26.28 MW | 22.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | Adder | 106.03 MW | 90.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | Adder | 27.0 MW | 22.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | Adder | 105.3 MW | 89.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | Adder | 24.53 MW | 20.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | Adder | 107.64 MW | 91.49 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946261 | AF1-291 C | Adder | 2.95 MW | 2.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946262 | AF1-291 E | Adder | 1.97 MW | 1.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957411 | AF2-035 C | Adder | 7.54 MW | 6.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957412 | AF2-035 E | Adder | 5.02 MW | 4.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 1.97 MW | 1.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 1.32 MW | 1.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957601 | AF2-054 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957602 | AF2-054 E | Adder | 1.72 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 3.34 MW | 2.84 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957711 | AF2-065 C | Adder | 16.67 MW | 14.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957712 | AF2-065 E | Adder | 16.02 MW | 13.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962531 | AG1-102 C | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962532 | AG1-102 E | Adder | 2.62 MW | 2.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962851 | AG1-134 C | Adder | 15.64 MW | 13.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962852 | AG1-134 E | Adder | 10.43 MW | 8.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962861 | AG1-135 C | Adder | 6.98 MW | 5.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962862 | AG1-135 E | Adder | 4.65 MW | 3.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962961 | AG1-145 C | Adder | 2.57 MW | 2.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962962 | AG1-145 E | Adder | 1.71 MW | 1.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962971 | AG1-146 C | Adder | 3.63 MW | 3.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962972 | AG1-146 E | Adder | 2.42 MW | 2.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962981 | AG1-147 C | Adder | 8.46 MW | 7.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962982 | AG1-147 E | Adder | 5.64 MW | 4.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963221 | AG1-171 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963222 | AG1-171 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963231 | AG1-172 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963232 | AG1-172 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963241 | AG1-173 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963242 | AG1-173 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963251 | AG1-174 C | Adder | 2.59 MW | 2.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963252 | AG1-174 E | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963611 | AG1-210 C | Adder | 0.73 MW | 0.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963612 | AG1-210 E | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963621 | AG1-213 C | Adder | 0.63 MW | 0.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 963622 | AG1-213 E | Adder | 0.94 MW | 0.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964211 | AG1-282 C | Adder | 2.29 MW | 1.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964212 | AG1-282 E | Adder | 1.53 MW | 1.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 964951 | AG1-359 O1 | Adder | 20.92 MW | 17.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965001 | AG1-364 C O1 | Adder | 6.68 MW | 5.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965002 | AG1-364 E O1 | Adder | 10.01 MW | 8.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 41.58 MW | 35.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 0.96 MW | 0.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925332 | AB2-190 E | Adder | 9.93 MW | 8.44 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | Adder | 1.06 MW | 0.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933294 | AC2-141 C | Adder | 26.85 MW | 22.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933295 | AC2-141 E | Adder | 11.46 MW | 9.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 14.34 MW | 12.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 9.56 MW | 8.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941581 | AE2-155 C | 50/50 | 0.19 MW | 0.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941582 | AE2-155 E | 50/50 | 0.47 MW | 0.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | Adder | 16.69 MW | 14.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942001 | AE2-212 C | Adder | 2.8 MW | 2.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942002 | AE2-212 E | Adder | 1.87 MW | 1.59 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957831 | AF2-077 C | Adder | 2.45 MW | 2.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957832 | AF2-077 E | Adder | 1.63 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | Adder | 9.12 MW | 7.75 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | Adder | 3.91 MW | 3.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957911 | AF2-085 | Adder | 3.81 MW | 3.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 1.31 MW | 1.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 2.05 MW | 1.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958261 | AF2-120 C | Adder | 7.16 MW | 6.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958262 | AF2-120 E | Adder | 4.77 MW | 4.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966611 | AG1-531 C | Adder | 6.29 MW | 5.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 966612 | AG1-531 E | Adder | 4.19 MW | 3.56 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | Adder | 43.55 MW | 37.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | Adder | 99.72 MW | 84.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962271 | AG1-075 C O1 | Adder | 21.53 MW | 18.3 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 962272 | AG1-075 E O1 | Adder | 13.12 MW | 11.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965281 | AG1-393 C | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 965282 | AG1-393 E | Adder | 1.38 MW | 1.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939246 | AE1-155 E | Adder | 9.78 MW | 8.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315043 | 1FOUR RIVERA | 50/50 | 5.27 MW | 5.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315045 | 1FOUR RIVERC | 50/50 | 6.45 MW | 6.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315048 | 1FOUR RIVERF | 50/50 | 6.45 MW | 6.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 920692 | AA2-178 E | Adder | 3.56 MW | 3.03 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316083 | AB2-161 C | Adder | 3.85 MW | 3.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 316084 | AB2-161 E | Adder | 6.28 MW | 5.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 961611 | AG1-000B C | Adder | 17.82 MW | 15.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.25 MW | 3.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 53.98 MW | 53.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.91 MW | 2.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.9 MW | 10.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.93 MW | 4.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.13 MW | 2.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.07 MW | 3.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.97 MW | 0.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.05 MW | 1.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 13.58 MW | 13.58 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.45 MW | 2.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.09 MW | 0.09 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 314525 | 6KINGFORK | Adder | 2.52 MW | 2.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315073 | 1STONECA | 50/50 | 24.05 MW | 24.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315076 | 1HOPPOLC | 50/50 | 5.66 MW | 5.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315077 | 1HOPHCF1 | 50/50 | 8.85 MW | 8.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315078 | 1HOPHCF2 | 50/50 | 8.85 MW | 8.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315079 | 1HOPHCF3 | 50/50 | 8.85 MW | 8.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315080 | 1HOPHCF4 | 50/50 | 13.44 MW | 13.44 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 927225 | AC1-216 C | 50/50 | 3.97 MW | 3.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 927226 | AC1-216 E | 50/50 | 18.33 MW | 18.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 934014 | AD1-025 C | 50/50 | 40.06 MW | 40.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 934015 | AD1-025 E | 50/50 | 23.73 MW | 23.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 935112 | AD1-144 E | Adder | 0.55 MW | 0.47 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 935164 | AD1-151 C | 50/50 | 42.67 MW | 42.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 935165 | AD1-151 E | 50/50 | 28.45 MW | 28.45 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 942551 | AE2-270 | 50/50 | 66.57 MW | 66.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 943621 | AF1-033 C | Adder | 3.1 MW | 2.63 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 943622 | AF1-033 E | Adder | 1.6 MW | 1.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 961711 | AG1-011 | 50/50 | 68.04 MW | 68.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315116 | 1SURRY 1 | 50/50 | 37.62 MW | 37.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315119 | 1GRAVEL3 | 50/50 | 3.82 MW | 3.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315120 | 1GRAVEL4 | 50/50 | 3.87 MW | 3.87 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315122 | 1GRAVEL6 | 50/50 | 3.87 MW | 3.87 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 316033 | AB2-134 C | 50/50 | 5.2 MW | 5.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 316132 | AB2-190 C | 50/50 | 48.99 MW | 48.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 924814 | AB2-134 E | 50/50 | 30.02 MW | 30.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 939312 | AE1-162 E | Adder | 1.59 MW | 1.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 957711 | AF2-065 C | 50/50 | 33.95 MW | 33.95 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 957712 | AF2-065 E | 50/50 | 32.62 MW | 32.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963221 | AG1-171 C | 50/50 | 5.1 MW | 5.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963222 | AG1-171 E | 50/50 | 3.4 MW | 3.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963231 | AG1-172 C | 50/50 | 5.1 MW | 5.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963232 | AG1-172 E | 50/50 | 3.4 MW | 3.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963241 | AG1-173 C | 50/50 | 5.1 MW | 5.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963242 | AG1-173 E | 50/50 | 3.4 MW | 3.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963251 | AG1-174 C | 50/50 | 5.1 MW | 5.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 963252 | AG1-174 E | 50/50 | 3.4 MW | 3.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 925332 | AB2-190 E | 50/50 | 21.0 MW | 21.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 966611 | AG1-531 C | Adder | 5.46 MW | 4.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 966612 | AG1-531 E | Adder | 3.64 MW | 3.09 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 961611 | AG1-000B C | 50/50 | 26.5 MW | 26.5 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.69 MW | 0.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.02 MW | 0.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.1 MW | 0.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.12 MW | 11.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.74 MW | 1.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.04 MW | 1.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.55 MW | 0.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.09 MW | 0.09 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.73 MW | 4.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.44 MW | 0.44 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314466 | 6FENTRES | Adder | 0.82 MW | 0.69 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314525 | 6KINGFORK | Adder | 1.82 MW | 1.55 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314550 | 6HICKORY | Adder | 1.49 MW | 1.27 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315060 | 1CHESTF5 | Adder | 46.39 MW | 39.43 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315073 | 1STONECA | 50/50 | 13.17 MW | 13.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315076 | 1HOPPOLC | 50/50 | 3.1 MW | 3.1 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315077 | 1HOPHCF1 | 50/50 | 4.85 MW | 4.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315078 | 1HOPHCF2 | 50/50 | 4.85 MW | 4.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315079 | 1HOPHCF3 | 50/50 | 4.85 MW | 4.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315080 | 1HOPHCF4 | 50/50 | 7.36 MW | 7.36 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | Adder | 0.55 MW | 0.47 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927225 | AC1-216 C | 50/50 | 2.26 MW | 2.26 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927226 | AC1-216 E | 50/50 | 10.44 MW | 10.44 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934014 | AD1-025 C | 50/50 | 22.81 MW | 22.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934015 | AD1-025 E | 50/50 | 13.51 MW | 13.51 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | Adder | 2.78 MW | 2.36 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | Adder | 1.85 MW | 1.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935112 | AD1-144 E | Adder | 0.4 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935164 | AD1-151 C | 50/50 | 24.0 MW | 24.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935165 | AD1-151 E | 50/50 | 16.0 MW | 16.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936761 | AD2-097 C | Adder | -1.08 MW | -0.92 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936762 | AD2-097 E | Adder | -5.39 MW | -4.58 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | Adder | 2.08 MW | 1.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | Adder | 1.09 MW | 0.93 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942151 | AE2-227 C | Adder | 0.91 MW | 0.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942152 | AE2-227 E | Adder | 0.6 MW | 0.51 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | Adder | 2.19 MW | 1.86 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | Adder | 0.98 MW | 0.84 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942551 | AE2-270 | 50/50 | 37.72 MW | 37.72 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943621 | AF1-033 C | Adder | 1.95 MW | 1.66 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943622 | AF1-033 E | Adder | 1.01 MW | 0.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944631 | AF1-128 O1 | Adder | 29.03 MW | 24.67 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961711 | AG1-011 | 50/50 | 38.75 MW | 38.75 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315116 | 1SURRY 1 | 50/50 | 23.02 MW | 23.02 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315119 | 1GRAVEL3 | 50/50 | 2.34 MW | 2.34 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315120 | 1GRAVEL4 | 50/50 | 2.37 MW | 2.37 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315122 | 1GRAVEL6 | 50/50 | 2.37 MW | 2.37 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316033 | AB2-134 C | 50/50 | 2.96 MW | 2.96 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316132 | AB2-190 C | 50/50 | 27.61 MW | 27.61 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | Adder | 0.73 MW | 0.62 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 924814 | AB2-134 E | 50/50 | 17.1 MW | 17.1 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932044 | AC2-012 C | Adder | 3.33 MW | 2.83 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932046 | AC2-012 E | Adder | 5.43 MW | 4.62 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939312 | AE1-162 E | Adder | 1.02 MW | 0.87 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | Adder | 10.98 MW | 9.33 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | Adder | 44.31 MW | 37.66 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | Adder | 11.28 MW | 9.59 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | Adder | 44.0 MW | 37.4 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | Adder | 10.18 MW | 8.66 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | Adder | 44.69 MW | 37.98 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | Adder | 1.49 MW | 1.26 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957711 | AF2-065 C | 50/50 | 19.24 MW | 19.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957712 | AF2-065 E | 50/50 | 18.48 MW | 18.48 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963221 | AG1-171 C | 50/50 | 2.91 MW | 2.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963222 | AG1-171 E | 50/50 | 1.94 MW | 1.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963231 | AG1-172 C | 50/50 | 2.91 MW | 2.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963232 | AG1-172 E | 50/50 | 1.94 MW | 1.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963241 | AG1-173 C | 50/50 | 2.91 MW | 2.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963242 | AG1-173 E | 50/50 | 1.94 MW | 1.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963251 | AG1-174 C | 50/50 | 2.91 MW | 2.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963252 | AG1-174 E | 50/50 | 1.94 MW | 1.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964951 | AG1-359 O1 | Adder | 8.38 MW | 7.12 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965001 | AG1-364 C O1 | Adder | 2.96 MW | 2.52 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965002 | AG1-364 E O1 | Adder | 4.44 MW | 3.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925332 | AB2-190 E | 50/50 | 11.83 MW | 11.83 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | Adder | 0.45 MW | 0.38 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | Adder | 7.39 MW | 6.28 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966611 | AG1-531 C | Adder | 3.83 MW | 3.25 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966612 | AG1-531 E | Adder | 2.55 MW | 2.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961611 | AG1-000B C | 50/50 | 15.86 MW | 15.86 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 946012 | AF1-266 BAT | Adder | 11.03 MW | 9.37 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940542 | AE2-040 BAT | Adder | 2.45 MW | 2.08 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.46 MW | 0.46 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.15 MW | 8.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.35 MW | 1.35 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.7 MW | 0.7 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.6 MW | 0.6 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.85 MW | 3.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963291 | AG1-178 C O2 | Adder | 95.91 MW | 81.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963351 | AG1-184 O2 | Adder | 51.67 MW | 43.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314541 | 3WATKINS | Adder | 1.15 MW | 0.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940491 | AE2-034 C | Adder | 3.3 MW | 2.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957531 | AF2-047 C | Adder | 28.57 MW | 24.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957532 | AF2-047 E | Adder | 14.37 MW | 12.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314539 | 3UNCAMP | Adder | 10.17 MW | 8.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 916042 | Z1-036 E | Adder | 48.83 MW | 41.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 938771 | AE1-103 C | Adder | 4.93 MW | 4.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 938772 | AE1-103 E | Adder | 6.8 MW | 5.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940481 | AE2-033 C | Adder | 25.59 MW | 21.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940482 | AE2-033 E | Adder | 17.25 MW | 14.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940641 | AE2-051 C O1 | Adder | 26.72 MW | 22.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940642 | AE2-051 E O1 | Adder | 17.81 MW | 15.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 946011 | AF1-266 | Adder | 21.42 MW | 18.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 313717 | 6SLIGO L2192 | Adder | 3.82 MW | 3.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314177 | 3HAYES89 | Adder | 0.1 MW | 0.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314189 | 6PAPERMILL | Adder | 11.44 MW | 9.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314229 | 6MT RD221 | 50/50 | 0.23 MW | 0.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314236 | 6NRTHEST | 50/50 | 0.35 MW | 0.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314241 | 6OLDCHRC | 50/50 | 1.6 MW | 1.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314331 | 6POE | Adder | 3.76 MW | 3.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314466 | 6FENTRES | Adder | 3.87 MW | 3.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314525 | 6KINGFORK | Adder | 7.56 MW | 6.42 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314550 | 6HICKORY | Adder | 7.15 MW | 6.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 314632 | 6AYDLETOLD | Adder | 3.83 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315060 | 1CHESTF5 | 50/50 | 114.11 MW | 114.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315061 | 1CHESTG7 | 50/50 | 7.26 MW | 7.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315062 | 1CHESTS7 | 50/50 | 3.33 MW | 3.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315063 | 1CHESTG8 | 50/50 | 7.14 MW | 7.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315064 | 1CHESTS8 | 50/50 | 3.68 MW | 3.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315065 | 1CHESTF6 | Adder | 180.27 MW | 153.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315067 | 1DARBY 1 | 50/50 | 4.78 MW | 4.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315068 | 1DARBY 2 | 50/50 | 4.79 MW | 4.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315069 | 1DARBY 3 | 50/50 | 4.81 MW | 4.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315070 | 1DARBY 4 | 50/50 | 4.81 MW | 4.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315073 | 1STONECA | Adder | 12.28 MW | 10.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315083 | 1SPRUNCA | Adder | 18.28 MW | 15.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315084 | 1SPRUNCB | Adder | 18.28 MW | 15.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 919152 | AA1-139 E | Adder | 11.15 MW | 9.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 925863 | AC1-065 C | Adder | 10.44 MW | 8.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 925865 | AC1-065 E | Adder | 16.78 MW | 14.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926412 | AC1-112 E | 50/50 | 2.05 MW | 2.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926662 | AC1-147 E | Adder | 2.32 MW | 1.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926754 | AC1-161 C | Adder | 53.76 MW | 45.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926755 | AC1-161 E | Adder | 22.95 MW | 19.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926784 | AC1-164 C | 50/50 | 73.86 MW | 73.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 926785 | AC1-164 E | 50/50 | 33.18 MW | 33.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 927044 | AC1-191 C | Adder | 16.46 MW | 13.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 927045 | AC1-191 E | Adder | 8.2 MW | 6.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 927226 | AC1-216 E | Adder | 13.71 MW | 11.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934014 | AD1-025 C | Adder | 29.96 MW | 25.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934015 | AD1-025 E | Adder | 17.75 MW | 15.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934061 | AD1-033 C | Adder | 13.12 MW | 11.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934062 | AD1-033 E | Adder | 8.75 MW | 7.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934141 | AD1-041 C | Adder | 8.93 MW | 7.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934142 | AD1-041 E | Adder | 5.95 MW | 5.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934392 | AD1-063 E | Adder | 1.82 MW | 1.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934575 | AD1-082 C | Adder | 13.37 MW | 11.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 934576 | AD1-082 E | Adder | 7.62 MW | 6.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 935112 | AD1-144 E | Adder | 1.65 MW | 1.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 935164 | AD1-151 C | Adder | 28.66 MW | 24.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 935165 | AD1-151 E | Adder | 19.11 MW | 16.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 936151 | AD2-021 | 50/50 | 0.07 MW | 0.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 936661 | AD2-085 C | Adder | 5.95 MW | 5.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 936662 | AD2-085 E | Adder | 9.71 MW | 8.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 936761 | AD2-097 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 936762 | AD2-097 E | Adder | 17.34 MW | 14.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 937221 | AD2-160 C O1 | Adder | 10.19 MW | 8.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 937222 | AD2-160 E O1 | Adder | 5.34 MW | 4.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942151 | AE2-227 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942152 | AE2-227 E | Adder | 2.6 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942161 | AE2-228 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942162 | AE2-228 E | Adder | 2.52 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942341 | AE2-247 C | Adder | 2.58 MW | 2.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942342 | AE2-247 E | Adder | 3.56 MW | 3.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942371 | AE2-250 C O1 | Adder | 16.85 MW | 14.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942372 | AE2-250 E O1 | Adder | 8.89 MW | 7.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942401 | AE2-253 C | Adder | 10.71 MW | 9.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942402 | AE2-253 E | Adder | 4.81 MW | 4.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942551 | AE2-270 | Adder | 47.74 MW | 40.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943431 | AF1-014 C | Adder | 2.16 MW | 1.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943432 | AF1-014 E | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943461 | AF1-017 C | Adder | 2.33 MW | 1.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943462 | AF1-017 E | Adder | 3.81 MW | 3.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943471 | AF1-018 | Adder | 12.16 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943611 | AF1-032 C | Adder | 3.02 MW | 2.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943612 | AF1-032 E | Adder | 1.6 MW | 1.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943621 | AF1-033 C | Adder | 4.19 MW | 3.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 943622 | AF1-033 E | Adder | 2.16 MW | 1.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944631 | AF1-128 O1 | Adder | 71.4 MW | 60.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944871 | AF1-152 C | Adder | 9.08 MW | 7.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944872 | AF1-152 E | Adder | 6.05 MW | 5.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 945361 | AF1-201 C O1 | Adder | 28.18 MW | 23.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 945362 | AF1-201 E O1 | Adder | 18.79 MW | 15.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 961711 | AG1-011 | Adder | 50.89 MW | 43.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 966871 | AG1-558 C | Adder | 4.1 MW | 3.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 966872 | AG1-558 E | Adder | 2.06 MW | 1.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 315233 | 1SURRY 2 | 50/50 | 47.37 MW | 47.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316075 | AC2-137 C | 50/50 | 0.65 MW | 0.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316076 | AC2-137 E | 50/50 | 2.46 MW | 2.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316108 | AB2-160 C | Adder | 9.49 MW | 8.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316109 | AB2-160 E | Adder | 15.48 MW | 13.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316132 | AB2-190 C | Adder | 33.44 MW | 28.42 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316157 | AD2-030 E | Adder | 1.97 MW | 1.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 913392 | Y1-086 E | Adder | 3.79 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 916192 | Z1-068 E | Adder | 3.28 MW | 2.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 923832 | AB2-022 E | Adder | 2.14 MW | 1.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 923842 | AB2-024 E | Adder | 1.92 MW | 1.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 923852 | AB2-025 E | Adder | 1.8 MW | 1.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 924814 | AB2-134 E | Adder | 22.46 MW | 19.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 930122 | AB1-027 E | 50/50 | 2.02 MW | 2.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 932044 | AC2-012 C | Adder | 14.06 MW | 11.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 932046 | AC2-012 E | Adder | 22.94 MW | 19.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 932591 | AC2-079 C O1 | Adder | 9.94 MW | 8.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 932592 | AC2-079 E O1 | Adder | 16.21 MW | 13.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 938535 | AE1-072 C | Adder | 30.48 MW | 25.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 938536 | AE1-072 E | Adder | 15.89 MW | 13.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 938552 | AE1-074 E | Adder | 2.07 MW | 1.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939195 | AE1-149 C | Adder | 18.55 MW | 15.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939196 | AE1-149 E | Adder | 12.37 MW | 10.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939312 | AE1-162 E | Adder | 2.52 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939414 | AE1-173_C1 | Adder | 50.53 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939415 | AE1-173_C2 | Adder | 43.31 MW | 36.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939416 | AE1-173_C3 | Adder | 50.53 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939423 | AE1-173_E1 | Adder | 33.68 MW | 28.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939424 | AE1-173_E2 | Adder | 28.87 MW | 24.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939425 | AE1-173_E3 | Adder | 33.68 MW | 28.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939431 | AE1-175 C | 50/50 | 4.36 MW | 4.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939432 | AE1-175 E | 50/50 | 2.16 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939611 | AE1-191 C | Adder | 17.85 MW | 15.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 939612 | AE1-191 E | Adder | 11.9 MW | 10.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940231 | AE2-005 C | Adder | 2.29 MW | 1.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940232 | AE2-005 E | Adder | 3.73 MW | 3.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940431 | AE2-027 C O1 | Adder | 22.7 MW | 19.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940432 | AE2-027 E O1 | Adder | 15.14 MW | 12.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940541 | AE2-040 | Adder | 4.54 MW | 3.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940551 | AE2-041 | Adder | 12.16 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 940651 | AE2-052 | Adder | 6.18 MW | 5.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941101 | AE2-104 C O1 | Adder | 5.8 MW | 4.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941102 | AE2-104 E O1 | Adder | 9.21 MW | 7.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941281 | AE2-122 C O1 | Adder | 49.7 MW | 42.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941282 | AE2-122 E O1 | Adder | 200.54 MW | 170.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941291 | AE2-123 C O1 | Adder | 51.07 MW | 43.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941292 | AE2-123 E O1 | Adder | 199.17 MW | 169.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941301 | AE2-124 C O1 | Adder | 46.43 MW | 39.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941302 | AE2-124 E O1 | Adder | 203.74 MW | 173.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 946261 | AF1-291 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 946262 | AF1-291 E | Adder | 2.53 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957491 | AF2-043 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957492 | AF2-043 E | Adder | 2.47 MW | 2.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957601 | AF2-054 C | Adder | 3.5 MW | 2.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957602 | AF2-054 E | Adder | 2.34 MW | 1.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957631 | AF2-057 | Adder | 6.27 MW | 5.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957711 | AF2-065 C | Adder | 24.35 MW | 20.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957712 | AF2-065 E | Adder | 23.39 MW | 19.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962531 | AG1-102 C | Adder | 1.9 MW | 1.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962532 | AG1-102 E | Adder | 3.96 MW | 3.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962961 | AG1-145 C | 50/50 | 3.93 MW | 3.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962962 | AG1-145 E | 50/50 | 2.62 MW | 2.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963221 | AG1-171 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963222 | AG1-171 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963231 | AG1-172 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963232 | AG1-172 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963241 | AG1-173 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963242 | AG1-173 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963251 | AG1-174 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 963252 | AG1-174 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 964951 | AG1-359 O1 | Adder | 39.82 MW | 33.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 965001 | AG1-364 C O1 | Adder | 12.54 MW | 10.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 965002 | AG1-364 E O1 | Adder | 18.82 MW | 15.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 901082 | W1-029 E | Adder | 78.98 MW | 67.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 917122 | Z2-027 E | Adder | 1.83 MW | 1.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 925332 | AB2-190 E | Adder | 14.33 MW | 12.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 925522 | AC1-027 E | Adder | 2.0 MW | 1.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 933294 | AC2-141 C | Adder | 53.76 MW | 45.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 933295 | AC2-141 E | Adder | 22.95 MW | 19.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941501 | AE2-147 C | Adder | 27.23 MW | 23.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941502 | AE2-147 E | Adder | 18.16 MW | 15.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941581 | AE2-155 C | 50/50 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941582 | AE2-155 E | 50/50 | 0.5 MW | 0.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 941591 | AE2-156 O1 | Adder | 31.36 MW | 26.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942001 | AE2-212 C | Adder | 3.75 MW | 3.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 942002 | AE2-212 E | Adder | 2.5 MW | 2.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957831 | AF2-077 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957832 | AF2-077 E | Adder | 2.47 MW | 2.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957871 | AF2-081 C | Adder | 17.35 MW | 14.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957872 | AF2-081 E | Adder | 7.44 MW | 6.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 957911 | AF2-085 | Adder | 5.92 MW | 5.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 958161 | AF2-110 C | Adder | 2.39 MW | 2.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 958162 | AF2-110 E | Adder | 3.74 MW | 3.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 966611 | AG1-531 C | Adder | 10.35 MW | 8.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 966612 | AG1-531 E | Adder | 6.9 MW | 5.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944581 | AF1-123 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944582 | AF1-123 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944591 | AF1-124 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944592 | AF1-124 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944601 | AF1-125 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 944602 | AF1-125 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962271 | AG1-075 C O1 | Adder | 29.08 MW | 24.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 962272 | AG1-075 E O1 | Adder | 17.72 MW | 15.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 965281 | AG1-393 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 965282 | AG1-393 E | Adder | 2.32 MW | 1.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316083 | AB2-161 C | Adder | 5.86 MW | 4.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 316084 | AB2-161 E | Adder | 9.57 MW | 8.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | 961611 | AG1-000B C | Adder | 28.22 MW | 23.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.4 MW | 8.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.21 MW | 3.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 160.72 MW | 160.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.92 MW | 71.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.79 MW | 68.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.7 MW | 12.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 8.87 MW | 8.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.53 MW | 15.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.77 MW | 0.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.64 MW | 3.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.92 MW | 9.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.99 MW | 3.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 56.38 MW | 56.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.63 MW | 0.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.64 MW | 12.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.72 MW | 1.72 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963291 | AG1-178 C O2 | Adder | 95.91 MW | 81.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963351 | AG1-184 O2 | Adder | 51.67 MW | 43.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314541 | 3WATKINS | Adder | 1.15 MW | 0.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940491 | AE2-034 C | Adder | 3.3 MW | 2.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957531 | AF2-047 C | Adder | 28.57 MW | 24.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957532 | AF2-047 E | Adder | 14.37 MW | 12.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314539 | 3UNCAMP | Adder | 10.17 MW | 8.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 916042 | Z1-036 E | Adder | 48.83 MW | 41.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 938771 | AE1-103 C | Adder | 4.93 MW | 4.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 938772 | AE1-103 E | Adder | 6.8 MW | 5.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940481 | AE2-033 C | Adder | 25.59 MW | 21.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940482 | AE2-033 E | Adder | 17.25 MW | 14.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940641 | AE2-051 C O1 | Adder | 26.72 MW | 22.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940642 | AE2-051 E O1 | Adder | 17.81 MW | 15.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 946011 | AF1-266 | Adder | 21.42 MW | 18.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 313717 | 6SLIGO L2192 | Adder | 3.82 MW | 3.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314177 | 3HAYES89 | Adder | 0.1 MW | 0.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314189 | 6PAPERMILL | Adder | 11.44 MW | 9.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314229 | 6MT RD221 | 50/50 | 0.23 MW | 0.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314236 | 6NRTHEST | 50/50 | 0.35 MW | 0.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314241 | 6OLDCHRC | 50/50 | 1.6 MW | 1.6 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314331 | 6POE | Adder | 3.76 MW | 3.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314466 | 6FENTRES | Adder | 3.87 MW | 3.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314525 | 6KINGFORK | Adder | 7.56 MW | 6.42 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314550 | 6HICKORY | Adder | 7.15 MW | 6.08 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 314632 | 6AYDLETOLD | Adder | 3.83 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315060 | 1CHESTF5 | 50/50 | 114.11 MW | 114.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315061 | 1CHESTG7 | 50/50 | 7.26 MW | 7.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315062 | 1CHESTS7 | 50/50 | 3.33 MW | 3.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315063 | 1CHESTG8 | 50/50 | 7.14 MW | 7.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315064 | 1CHESTS8 | 50/50 | 3.68 MW | 3.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315065 | 1CHESTF6 | Adder | 180.27 MW | 153.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315067 | 1DARBY 1 | 50/50 | 4.78 MW | 4.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315068 | 1DARBY 2 | 50/50 | 4.79 MW | 4.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315069 | 1DARBY 3 | 50/50 | 4.81 MW | 4.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315070 | 1DARBY 4 | 50/50 | 4.81 MW | 4.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315073 | 1STONECA | Adder | 12.28 MW | 10.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315083 | 1SPRUNCA | Adder | 18.28 MW | 15.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315084 | 1SPRUNCB | Adder | 18.28 MW | 15.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 919152 | AA1-139 E | Adder | 11.15 MW | 9.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 925863 | AC1-065 C | Adder | 10.44 MW | 8.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 925865 | AC1-065 E | Adder | 16.78 MW | 14.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926412 | AC1-112 E | 50/50 | 2.05 MW | 2.05 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926662 | AC1-147 E | Adder | 2.32 MW | 1.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926754 | AC1-161 C | Adder | 53.77 MW | 45.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926755 | AC1-161 E | Adder | 22.95 MW | 19.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926784 | AC1-164 C | 50/50 | 73.86 MW | 73.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 926785 | AC1-164 E | 50/50 | 33.18 MW | 33.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 927044 | AC1-191 C | Adder | 16.46 MW | 13.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 927045 | AC1-191 E | Adder | 8.2 MW | 6.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 927226 | AC1-216 E | Adder | 13.71 MW | 11.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934014 | AD1-025 C | Adder | 29.96 MW | 25.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934015 | AD1-025 E | Adder | 17.75 MW | 15.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934061 | AD1-033 C | Adder | 13.12 MW | 11.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934062 | AD1-033 E | Adder | 8.75 MW | 7.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934141 | AD1-041 C | Adder | 8.93 MW | 7.59 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934142 | AD1-041 E | Adder | 5.95 MW | 5.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934392 | AD1-063 E | Adder | 1.82 MW | 1.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934575 | AD1-082 C | Adder | 13.37 MW | 11.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 934576 | AD1-082 E | Adder | 7.62 MW | 6.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 935112 | AD1-144 E | Adder | 1.65 MW | 1.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 935164 | AD1-151 C | Adder | 28.66 MW | 24.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 935165 | AD1-151 E | Adder | 19.11 MW | 16.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 936151 | AD2-021 | 50/50 | 0.07 MW | 0.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 936661 | AD2-085 C | Adder | 5.95 MW | 5.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 936662 | AD2-085 E | Adder | 9.71 MW | 8.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 936761 | AD2-097 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 936762 | AD2-097 E | Adder | 17.34 MW | 14.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 937221 | AD2-160 C O1 | Adder | 10.19 MW | 8.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 937222 | AD2-160 E O1 | Adder | 5.34 MW | 4.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942151 | AE2-227 C | Adder | 3.89 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942152 | AE2-227 E | Adder | 2.6 MW | 2.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942161 | AE2-228 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942162 | AE2-228 E | Adder | 2.52 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942341 | AE2-247 C | Adder | 2.58 MW | 2.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942342 | AE2-247 E | Adder | 3.56 MW | 3.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942371 | AE2-250 C O1 | Adder | 16.85 MW | 14.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942372 | AE2-250 E O1 | Adder | 8.89 MW | 7.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942401 | AE2-253 C | Adder | 10.71 MW | 9.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942402 | AE2-253 E | Adder | 4.81 MW | 4.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942551 | AE2-270 | Adder | 47.74 MW | 40.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943431 | AF1-014 C | Adder | 2.16 MW | 1.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943432 | AF1-014 E | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943461 | AF1-017 C | Adder | 2.33 MW | 1.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943462 | AF1-017 E | Adder | 3.81 MW | 3.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943471 | AF1-018 | Adder | 12.16 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943611 | AF1-032 C | Adder | 3.02 MW | 2.57 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943612 | AF1-032 E | Adder | 1.6 MW | 1.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943621 | AF1-033 C | Adder | 4.19 MW | 3.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 943622 | AF1-033 E | Adder | 2.16 MW | 1.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944631 | AF1-128 O1 | Adder | 71.4 MW | 60.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944871 | AF1-152 C | Adder | 9.08 MW | 7.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944872 | AF1-152 E | Adder | 6.05 MW | 5.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 945361 | AF1-201 C O1 | Adder | 28.18 MW | 23.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 945362 | AF1-201 E O1 | Adder | 18.79 MW | 15.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 961711 | AG1-011 | Adder | 50.89 MW | 43.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 966871 | AG1-558 C | Adder | 4.1 MW | 3.48 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 966872 | AG1-558 E | Adder | 2.06 MW | 1.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 315233 | 1SURRY 2 | 50/50 | 47.37 MW | 47.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316075 | AC2-137 C | 50/50 | 0.65 MW | 0.65 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316076 | AC2-137 E | 50/50 | 2.46 MW | 2.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316108 | AB2-160 C | Adder | 9.49 MW | 8.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316109 | AB2-160 E | Adder | 15.48 MW | 13.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316132 | AB2-190 C | Adder | 33.44 MW | 28.42 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316157 | AD2-030 E | Adder | 1.97 MW | 1.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 913392 | Y1-086 E | Adder | 3.79 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 916192 | Z1-068 E | Adder | 3.28 MW | 2.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 923832 | AB2-022 E | Adder | 2.14 MW | 1.82 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 923842 | AB2-024 E | Adder | 1.92 MW | 1.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 923852 | AB2-025 E | Adder | 1.8 MW | 1.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 924814 | AB2-134 E | Adder | 22.46 MW | 19.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 930122 | AB1-027 E | 50/50 | 2.02 MW | 2.02 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 932044 | AC2-012 C | Adder | 14.06 MW | 11.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 932046 | AC2-012 E | Adder | 22.94 MW | 19.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 932591 | AC2-079 C O1 | Adder | 9.94 MW | 8.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 932592 | AC2-079 E O1 | Adder | 16.21 MW | 13.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 938535 | AE1-072 C | Adder | 30.48 MW | 25.91 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 938536 | AE1-072 E | Adder | 15.89 MW | 13.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 938552 | AE1-074 E | Adder | 2.07 MW | 1.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939195 | AE1-149 C | Adder | 18.55 MW | 15.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939196 | AE1-149 E | Adder | 12.37 MW | 10.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939312 | AE1-162 E | Adder | 2.52 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939414 | AE1-173_C1 | Adder | 50.53 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939415 | AE1-173_C2 | Adder | 43.31 MW | 36.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939416 | AE1-173_C3 | Adder | 50.53 MW | 42.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939423 | AE1-173_E1 | Adder | 33.68 MW | 28.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939424 | AE1-173_E2 | Adder | 28.87 MW | 24.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939425 | AE1-173_E3 | Adder | 33.68 MW | 28.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939431 | AE1-175 C | 50/50 | 4.36 MW | 4.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939432 | AE1-175 E | 50/50 | 2.16 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939611 | AE1-191 C | Adder | 17.85 MW | 15.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 939612 | AE1-191 E | Adder | 11.9 MW | 10.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940231 | AE2-005 C | Adder | 2.29 MW | 1.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940232 | AE2-005 E | Adder | 3.73 MW | 3.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940431 | AE2-027 C O1 | Adder | 22.7 MW | 19.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940432 | AE2-027 E O1 | Adder | 15.14 MW | 12.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940541 | AE2-040 | Adder | 4.54 MW | 3.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940551 | AE2-041 | Adder | 12.16 MW | 10.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 940651 | AE2-052 | Adder | 6.18 MW | 5.26 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941101 | AE2-104 C O1 | Adder | 5.8 MW | 4.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941102 | AE2-104 E O1 | Adder | 9.21 MW | 7.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941281 | AE2-122 C O1 | Adder | 49.7 MW | 42.24 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941282 | AE2-122 E O1 | Adder | 200.54 MW | 170.46 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941291 | AE2-123 C O1 | Adder | 51.07 MW | 43.41 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941292 | AE2-123 E O1 | Adder | 199.17 MW | 169.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941301 | AE2-124 C O1 | Adder | 46.43 MW | 39.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941302 | AE2-124 E O1 | Adder | 203.74 MW | 173.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 946261 | AF1-291 C | Adder | 3.79 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 946262 | AF1-291 E | Adder | 2.53 MW | 2.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957491 | AF2-043 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957492 | AF2-043 E | Adder | 2.47 MW | 2.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957601 | AF2-054 C | Adder | 3.5 MW | 2.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957602 | AF2-054 E | Adder | 2.34 MW | 1.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957631 | AF2-057 | Adder | 6.27 MW | 5.33 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957711 | AF2-065 C | Adder | 24.35 MW | 20.69 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957712 | AF2-065 E | Adder | 23.39 MW | 19.88 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962531 | AG1-102 C | Adder | 1.9 MW | 1.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962532 | AG1-102 E | Adder | 3.96 MW | 3.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962961 | AG1-145 C | 50/50 | 3.93 MW | 3.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962962 | AG1-145 E | 50/50 | 2.62 MW | 2.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963221 | AG1-171 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963222 | AG1-171 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963231 | AG1-172 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963232 | AG1-172 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963241 | AG1-173 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963242 | AG1-173 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963251 | AG1-174 C | Adder | 3.82 MW | 3.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 963252 | AG1-174 E | Adder | 2.54 MW | 2.16 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 964951 | AG1-359 O1 | Adder | 39.82 MW | 33.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 965001 | AG1-364 C O1 | Adder | 12.54 MW | 10.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 965002 | AG1-364 E O1 | Adder | 18.82 MW | 15.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 901082 | W1-029 E | Adder | 78.98 MW | 67.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 917122 | Z2-027 E | Adder | 1.83 MW | 1.55 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 925332 | AB2-190 E | Adder | 14.33 MW | 12.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 925522 | AC1-027 E | Adder | 2.0 MW | 1.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 933294 | AC2-141 C | Adder | 53.77 MW | 45.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 933295 | AC2-141 E | Adder | 22.95 MW | 19.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941501 | AE2-147 C | Adder | 27.23 MW | 23.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941502 | AE2-147 E | Adder | 18.16 MW | 15.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941581 | AE2-155 C | 50/50 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941582 | AE2-155 E | 50/50 | 0.5 MW | 0.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 941591 | AE2-156 O1 | Adder | 31.36 MW | 26.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942001 | AE2-212 C | Adder | 3.75 MW | 3.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 942002 | AE2-212 E | Adder | 2.5 MW | 2.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957831 | AF2-077 C | Adder | 3.7 MW | 3.15 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957832 | AF2-077 E | Adder | 2.47 MW | 2.1 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957871 | AF2-081 C | Adder | 17.35 MW | 14.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957872 | AF2-081 E | Adder | 7.44 MW | 6.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 957911 | AF2-085 | Adder | 5.92 MW | 5.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 958161 | AF2-110 C | Adder | 2.39 MW | 2.03 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 958162 | AF2-110 E | Adder | 3.74 MW | 3.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 966611 | AG1-531 C | Adder | 10.35 MW | 8.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 966612 | AG1-531 E | Adder | 6.9 MW | 5.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944581 | AF1-123 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944582 | AF1-123 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944591 | AF1-124 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944592 | AF1-124 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944601 | AF1-125 C O1 | Adder | 83.94 MW | 71.35 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 944602 | AF1-125 E O1 | Adder | 192.21 MW | 163.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962271 | AG1-075 C O1 | Adder | 29.08 MW | 24.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 962272 | AG1-075 E O1 | Adder | 17.73 MW | 15.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 965281 | AG1-393 C | Adder | 3.47 MW | 2.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 965282 | AG1-393 E | Adder | 2.32 MW | 1.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316083 | AB2-161 C | Adder | 5.86 MW | 4.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 316084 | AB2-161 E | Adder | 9.57 MW | 8.13 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | 961611 | AG1-000B C | Adder | 28.22 MW | 23.98 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 8.4 MW | 8.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.21 MW | 3.21 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 160.72 MW | 160.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.92 MW | 71.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.79 MW | 68.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.7 MW | 12.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 8.87 MW | 8.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.53 MW | 15.53 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.77 MW | 0.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.64 MW | 3.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.92 MW | 9.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.99 MW | 3.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 56.38 MW | 56.38 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.63 MW | 0.63 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.64 MW | 12.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.72 MW | 1.72 MW |
| Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963041 | AG1-153 C | Adder | 8.09 MW | 6.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963042 | AG1-153 E | Adder | 12.13 MW | 10.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963111 | AG1-160 C | Adder | 8.21 MW | 6.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963112 | AG1-160 E | Adder | 12.32 MW | 10.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963291 | AG1-178 C O2 | Adder | 97.7 MW | 83.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 963351 | AG1-184 O2 | Adder | 52.64 MW | 44.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964801 | AG1-343 C | Adder | 8.12 MW | 6.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964802 | AG1-343 E | Adder | 6.38 MW | 5.42 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965291 | AG1-394 C | Adder | 2.79 MW | 2.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965292 | AG1-394 E | Adder | 1.86 MW | 1.58 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965691 | AG1-437 C O1 | Adder | 14.78 MW | 12.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965692 | AG1-437 E O1 | Adder | 9.86 MW | 8.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965701 | AG1-438 C O1 | Adder | 14.78 MW | 12.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965702 | AG1-438 E O1 | Adder | 9.86 MW | 8.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965741 | AG1-442 O1 | Adder | 8.62 MW | 7.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965751 | AG1-443 O1 | Adder | 8.62 MW | 7.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965811 | AG1-449 | Adder | 34.09 MW | 28.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966361 | AG1-505 C | Adder | 23.76 MW | 20.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966362 | AG1-505 E | Adder | 15.84 MW | 13.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966371 | AG1-506 C | Adder | 23.76 MW | 20.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966372 | AG1-506 E | Adder | 15.84 MW | 13.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314541 | 3WATKINS | Adder | 1.0 MW | 0.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314594 | 6PLYMOTH | Adder | 0.14 MW | 0.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920042 | AA2-088 E OP | Adder | 14.55 MW | 12.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934521 | AD1-076 C | Adder | 81.74 MW | 69.48 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934522 | AD1-076 E | Adder | 41.62 MW | 35.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942931 | AE2-313 C | Adder | 52.55 MW | 44.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942932 | AE2-313 E | Adder | 35.04 MW | 29.78 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944011 | AF1-069 C | Adder | 19.14 MW | 16.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944012 | AF1-069 E | Adder | 7.44 MW | 6.32 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315293 | 1DOMTR9 | Adder | 9.98 MW | 8.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315294 | 1DOMTR10 | Adder | 12.24 MW | 10.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925122 | AB2-169 E | Adder | 8.15 MW | 6.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938222 | AE1-035 E | Adder | 1.56 MW | 1.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940491 | AE2-034 C | Adder | 11.19 MW | 9.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940492 | AE2-034 E | Adder | 4.8 MW | 4.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941031 | AE2-094 C | Adder | 58.58 MW | 49.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941032 | AE2-094 E | Adder | 26.24 MW | 22.3 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957531 | AF2-047 C | Adder | 26.59 MW | 22.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957532 | AF2-047 E | Adder | 13.37 MW | 11.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314539 | 3UNCAMP | Adder | 9.01 MW | 7.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916042 | Z1-036 E | Adder | 47.03 MW | 39.97 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938771 | AE1-103 C | Adder | 4.41 MW | 3.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938772 | AE1-103 E | Adder | 6.09 MW | 5.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940641 | AE2-051 C O1 | Adder | 27.52 MW | 23.39 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940642 | AE2-051 E O1 | Adder | 18.34 MW | 15.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 313717 | 6SLIGO L2192 | Adder | 3.84 MW | 3.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314177 | 3HAYES89 | Adder | 0.09 MW | 0.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314189 | 6PAPERMILL | Adder | 9.62 MW | 8.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314466 | 6FENTRES | 50/50 | 3.94 MW | 3.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314491 | 3PENDLTN | 50/50 | 0.6 MW | 0.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314525 | 6KINGFORK | Adder | 7.32 MW | 6.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314550 | 6HICKORY | 50/50 | 7.25 MW | 7.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314632 | 6AYDLETOLD | Adder | 3.84 MW | 3.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315092 | 1YORKTN3 | 50/50 | 42.87 MW | 42.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 919152 | AA1-139 E | Adder | 11.24 MW | 9.56 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925863 | AC1-065 C | Adder | 8.69 MW | 7.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925865 | AC1-065 E | Adder | 13.96 MW | 11.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | Adder | 2.34 MW | 1.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926754 | AC1-161 C | 50/50 | 58.97 MW | 58.97 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926755 | AC1-161 E | 50/50 | 25.17 MW | 25.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926784 | AC1-164 C | Adder | 58.68 MW | 49.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926785 | AC1-164 E | Adder | 26.36 MW | 22.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | 50/50 | 13.33 MW | 13.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | 50/50 | 8.89 MW | 8.89 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934141 | AD1-041 C | Adder | 7.57 MW | 6.43 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934142 | AD1-041 E | Adder | 5.04 MW | 4.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934392 | AD1-063 E | Adder | 1.55 MW | 1.32 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935112 | AD1-144 E | Adder | 1.6 MW | 1.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936661 | AD2-085 C | Adder | 5.01 MW | 4.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936662 | AD2-085 E | Adder | 8.17 MW | 6.95 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | Adder | 10.29 MW | 8.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | Adder | 5.4 MW | 4.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942341 | AE2-247 C | Adder | 2.17 MW | 1.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942342 | AE2-247 E | Adder | 2.99 MW | 2.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | Adder | 10.83 MW | 9.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | Adder | 4.86 MW | 4.13 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943431 | AF1-014 C | Adder | 1.8 MW | 1.53 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943432 | AF1-014 E | Adder | 3.18 MW | 2.7 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943461 | AF1-017 C | Adder | 1.96 MW | 1.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943462 | AF1-017 E | Adder | 3.2 MW | 2.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943471 | AF1-018 | Adder | 10.34 MW | 8.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943611 | AF1-032 C | Adder | 2.99 MW | 2.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943612 | AF1-032 E | Adder | 1.59 MW | 1.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943621 | AF1-033 C | Adder | 3.67 MW | 3.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943622 | AF1-033 E | Adder | 1.89 MW | 1.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944871 | AF1-152 C | Adder | 8.89 MW | 7.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944872 | AF1-152 E | Adder | 5.92 MW | 5.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945361 | AF1-201 C O1 | Adder | 26.89 MW | 22.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945362 | AF1-201 E O1 | Adder | 17.93 MW | 15.24 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961711 | AG1-011 | Adder | 28.42 MW | 24.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315099 | 1CHESPKB | 50/50 | 1.33 MW | 1.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315108 | 1ELIZAR1 | 50/50 | 5.91 MW | 5.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315109 | 1ELIZAR2 | 50/50 | 5.81 MW | 5.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315110 | 1ELIZAR3 | 50/50 | 5.99 MW | 5.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315233 | 1SURRY 2 | 50/50 | 53.85 MW | 53.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 316157 | AD2-030 E | Adder | 1.71 MW | 1.45 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 913392 | Y1-086 E | Adder | 3.77 MW | 3.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | 50/50 | 3.32 MW | 3.32 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923832 | AB2-022 E | Adder | 2.13 MW | 1.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923842 | AB2-024 E | Adder | 1.62 MW | 1.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932044 | AC2-012 C | Adder | 14.17 MW | 12.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932046 | AC2-012 E | Adder | 23.11 MW | 19.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932591 | AC2-079 C O1 | Adder | 7.71 MW | 6.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932592 | AC2-079 E O1 | Adder | 12.58 MW | 10.69 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938535 | AE1-072 C | Adder | 30.63 MW | 26.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938536 | AE1-072 E | Adder | 15.97 MW | 13.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939312 | AE1-162 E | Adder | 2.31 MW | 1.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939414 | AE1-173_C1 | Adder | 51.91 MW | 44.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939415 | AE1-173_C2 | Adder | 44.49 MW | 37.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939416 | AE1-173_C3 | Adder | 51.91 MW | 44.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939423 | AE1-173_E1 | Adder | 34.6 MW | 29.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939424 | AE1-173_E2 | Adder | 29.66 MW | 25.21 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939425 | AE1-173_E3 | Adder | 34.6 MW | 29.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939431 | AE1-175 C | Adder | 4.08 MW | 3.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939432 | AE1-175 E | Adder | 2.03 MW | 1.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939611 | AE1-191 C | Adder | 15.13 MW | 12.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939612 | AE1-191 E | Adder | 10.09 MW | 8.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940231 | AE2-005 C | Adder | 1.9 MW | 1.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940232 | AE2-005 E | Adder | 3.1 MW | 2.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940551 | AE2-041 | Adder | 10.34 MW | 8.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941101 | AE2-104 C O1 | Adder | 5.4 MW | 4.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941102 | AE2-104 E O1 | Adder | 8.59 MW | 7.3 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | 50/50 | 50.31 MW | 50.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | 50/50 | 203.0 MW | 203.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | 50/50 | 51.7 MW | 51.7 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | 50/50 | 201.61 MW | 201.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | 50/50 | 47.02 MW | 47.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | 50/50 | 206.33 MW | 206.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957491 | AF2-043 C | Adder | 3.66 MW | 3.11 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957492 | AF2-043 E | Adder | 2.44 MW | 2.07 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957601 | AF2-054 C | Adder | 3.04 MW | 2.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957602 | AF2-054 E | Adder | 2.03 MW | 1.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | Adder | 6.32 MW | 5.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962531 | AG1-102 C | Adder | 1.78 MW | 1.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962532 | AG1-102 E | Adder | 3.7 MW | 3.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962961 | AG1-145 C | Adder | 3.69 MW | 3.13 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 962962 | AG1-145 E | Adder | 2.46 MW | 2.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 964951 | AG1-359 O1 | 50/50 | 40.49 MW | 40.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965001 | AG1-364 C O1 | 50/50 | 12.66 MW | 12.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 965002 | AG1-364 E O1 | 50/50 | 18.98 MW | 18.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 901082 | W1-029 E | Adder | 77.31 MW | 65.71 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917122 | Z2-027 E | Adder | 1.8 MW | 1.53 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | 50/50 | 2.02 MW | 2.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933294 | AC2-141 C | 50/50 | 58.97 MW | 58.97 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933295 | AC2-141 E | 50/50 | 25.17 MW | 25.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941501 | AE2-147 C | Adder | 26.66 MW | 22.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941502 | AE2-147 E | Adder | 17.77 MW | 15.11 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | 50/50 | 31.65 MW | 31.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957831 | AF2-077 C | Adder | 3.46 MW | 2.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957832 | AF2-077 E | Adder | 2.31 MW | 1.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957871 | AF2-081 C | Adder | 17.49 MW | 14.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957872 | AF2-081 E | Adder | 7.49 MW | 6.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958161 | AF2-110 C | Adder | 2.23 MW | 1.89 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958162 | AF2-110 E | Adder | 3.48 MW | 2.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966611 | AG1-531 C | Adder | 9.51 MW | 8.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 966612 | AG1-531 E | Adder | 6.34 MW | 5.39 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944581 | AF1-123 C O1 | 50/50 | 86.88 MW | 86.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944582 | AF1-123 E O1 | 50/50 | 198.92 MW | 198.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944591 | AF1-124 C O1 | 50/50 | 86.88 MW | 86.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944592 | AF1-124 E O1 | 50/50 | 198.92 MW | 198.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944601 | AF1-125 C O1 | 50/50 | 86.88 MW | 86.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944602 | AF1-125 E O1 | 50/50 | 198.92 MW | 198.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933981 | AD1-022 C | Adder | 12.96 MW | 11.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933982 | AD1-022 E | Adder | 7.05 MW | 6.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918512 | AA1-065 E OP | Adder | 5.68 MW | 4.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920692 | AA2-178 E | Adder | 6.39 MW | 5.43 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 961611 | AG1-000B C | Adder | 23.37 MW | 19.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.49 MW | 6.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.61 MW | 1.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 113.77 MW | 113.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.59 MW | 24.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 33.06 MW | 33.06 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.84 MW | 9.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 3.94 MW | 3.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.22 MW | 8.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.56 MW | 0.56 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.27 MW | 1.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.04 MW | 4.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.87 MW | 1.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 25.15 MW | 25.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.24 MW | 0.24 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.61 MW | 6.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.61 MW | 0.61 MW |
| Details for 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315060 | 1CHESTF5 | 50/50 | 58.45 MW | 58.45 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315061 | 1CHESTG7 | 50/50 | 3.72 MW | 3.72 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315062 | 1CHESTS7 | 50/50 | 1.71 MW | 1.71 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315063 | 1CHESTG8 | 50/50 | 3.66 MW | 3.66 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315064 | 1CHESTS8 | 50/50 | 1.88 MW | 1.88 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 315073 | 1STONECA | Adder | 2.73 MW | 2.32 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 927226 | AC1-216 E | Adder | 2.18 MW | 1.85 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 934014 | AD1-025 C | Adder | 4.76 MW | 4.04 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 934015 | AD1-025 E | Adder | 2.82 MW | 2.4 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 935164 | AD1-151 C | Adder | 4.99 MW | 4.25 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 935165 | AD1-151 E | Adder | 3.33 MW | 2.83 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 942551 | AE2-270 | Adder | 7.86 MW | 6.68 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 944631 | AF1-128 O1 | 50/50 | 36.57 MW | 36.57 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 961711 | AG1-011 | Adder | 8.08 MW | 6.87 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 316132 | AB2-190 C | Adder | 5.75 MW | 4.88 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 924814 | AB2-134 E | Adder | 3.57 MW | 3.03 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 957711 | AF2-065 C | Adder | 4.01 MW | 3.41 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 957712 | AF2-065 E | Adder | 3.85 MW | 3.27 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963221 | AG1-171 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963222 | AG1-171 E | Adder | 0.4 MW | 0.34 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963231 | AG1-172 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963232 | AG1-172 E | Adder | 0.4 MW | 0.34 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963241 | AG1-173 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963242 | AG1-173 E | Adder | 0.4 MW | 0.34 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963251 | AG1-174 C | Adder | 0.61 MW | 0.52 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 963252 | AG1-174 E | Adder | 0.4 MW | 0.34 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | 925332 | AB2-190 E | Adder | 2.46 MW | 2.09 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.11 MW | 0.11 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.72 MW | 1.72 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.12 MW | 0.12 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.17 MW | 0.17 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.97 MW | 0.97 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.0 MW | 0.0 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| 6CHESTF A-3CHESTFLD 230.0/115.0 kV Ckt 1 transformer l/o DVP_P4-2: 208T287 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.05 MW | 0.05 MW |
| Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963041 | AG1-153 C | Adder | 7.81 MW | 6.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963042 | AG1-153 E | Adder | 11.71 MW | 9.95 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963111 | AG1-160 C | Adder | 7.92 MW | 6.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963112 | AG1-160 E | Adder | 11.88 MW | 10.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963291 | AG1-178 C O2 | Adder | 94.53 MW | 80.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963351 | AG1-184 O2 | Adder | 50.93 MW | 43.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965691 | AG1-437 C O1 | Adder | 15.63 MW | 13.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965692 | AG1-437 E O1 | Adder | 10.42 MW | 8.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965701 | AG1-438 C O1 | Adder | 15.63 MW | 13.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965702 | AG1-438 E O1 | Adder | 10.42 MW | 8.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965741 | AG1-442 O1 | Adder | 9.12 MW | 7.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965751 | AG1-443 O1 | Adder | 9.12 MW | 7.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965811 | AG1-449 | Adder | 32.84 MW | 27.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966361 | AG1-505 C | Adder | 10.68 MW | 9.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966371 | AG1-506 C | Adder | 23.0 MW | 19.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 1.07 MW | 0.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314594 | 6PLYMOTH | Adder | 0.14 MW | 0.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 85.74 MW | 72.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 43.66 MW | 37.11 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 50.63 MW | 43.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 33.75 MW | 28.69 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 18.42 MW | 15.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 7.15 MW | 6.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315293 | 1DOMTR9 | Adder | 10.49 MW | 8.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 12.86 MW | 10.93 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 11.66 MW | 9.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 5.0 MW | 4.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 56.36 MW | 47.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 25.24 MW | 21.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 27.71 MW | 23.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 13.94 MW | 11.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 9.58 MW | 8.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 48.53 MW | 41.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C | Adder | 4.67 MW | 3.97 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E | Adder | 6.45 MW | 5.48 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 26.64 MW | 22.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 17.76 MW | 15.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 313717 | 6SLIGO L2192 | Adder | 3.91 MW | 3.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314177 | 3HAYES89 | Adder | 0.1 MW | 0.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314189 | 6PAPERMILL | Adder | 10.29 MW | 8.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314421 | 6WINCHST | 50/50 | 0.25 MW | 0.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314466 | 6FENTRES | 50/50 | 4.0 MW | 4.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314491 | 3PENDLTN | 50/50 | 0.61 MW | 0.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314525 | 6KINGFORK | Adder | 7.54 MW | 6.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314550 | 6HICKORY | Adder | 7.37 MW | 6.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314632 | 6AYDLETOLD | Adder | 3.92 MW | 3.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315092 | 1YORKTN3 | 50/50 | 44.3 MW | 44.3 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 11.45 MW | 9.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925863 | AC1-065 C | Adder | 9.32 MW | 7.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925865 | AC1-065 E | Adder | 14.97 MW | 12.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | Adder | 2.38 MW | 2.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926754 | AC1-161 C | 50/50 | 59.12 MW | 59.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926755 | AC1-161 E | 50/50 | 25.24 MW | 25.24 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926784 | AC1-164 C | Adder | 63.36 MW | 53.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926785 | AC1-164 E | Adder | 28.46 MW | 24.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927226 | AC1-216 E | Adder | 11.04 MW | 9.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934014 | AD1-025 C | Adder | 24.13 MW | 20.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934015 | AD1-025 E | Adder | 14.29 MW | 12.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | 50/50 | 13.55 MW | 13.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | 50/50 | 9.03 MW | 9.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934141 | AD1-041 C | Adder | 8.09 MW | 6.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934142 | AD1-041 E | Adder | 5.39 MW | 4.58 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934392 | AD1-063 E | Adder | 1.66 MW | 1.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 1.64 MW | 1.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 5.43 MW | 4.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 8.86 MW | 7.53 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | Adder | 10.48 MW | 8.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | Adder | 5.5 MW | 4.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 2.35 MW | 2.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 3.25 MW | 2.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | Adder | 11.02 MW | 9.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | Adder | 4.95 MW | 4.21 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943431 | AF1-014 C | Adder | 1.93 MW | 1.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943432 | AF1-014 E | Adder | 3.41 MW | 2.9 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 2.13 MW | 1.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 3.47 MW | 2.95 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943471 | AF1-018 | Adder | 11.04 MW | 9.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 3.06 MW | 2.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 1.62 MW | 1.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 3.87 MW | 3.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 2.0 MW | 1.7 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 9.13 MW | 7.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 6.09 MW | 5.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945361 | AF1-201 C O1 | Adder | 28.01 MW | 23.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945362 | AF1-201 E O1 | Adder | 18.68 MW | 15.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961711 | AG1-011 | Adder | 40.98 MW | 34.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315099 | 1CHESPKB | 50/50 | 1.35 MW | 1.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315108 | 1ELIZAR1 | 50/50 | 6.01 MW | 6.01 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315109 | 1ELIZAR2 | 50/50 | 5.91 MW | 5.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315110 | 1ELIZAR3 | 50/50 | 6.09 MW | 6.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315233 | 1SURRY 2 | 50/50 | 54.4 MW | 54.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316157 | AD2-030 E | Adder | 1.82 MW | 1.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 3.86 MW | 3.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | 50/50 | 3.38 MW | 3.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 2.18 MW | 1.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923842 | AB2-024 E | Adder | 1.73 MW | 1.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924814 | AB2-134 E | Adder | 18.08 MW | 15.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932044 | AC2-012 C | Adder | 14.43 MW | 12.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932046 | AC2-012 E | Adder | 23.54 MW | 20.01 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | Adder | 8.62 MW | 7.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | Adder | 14.07 MW | 11.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938535 | AE1-072 C | Adder | 31.24 MW | 26.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938536 | AE1-072 E | Adder | 16.28 MW | 13.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 2.41 MW | 2.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939414 | AE1-173_C1 | Adder | 50.9 MW | 43.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939415 | AE1-173_C2 | Adder | 43.63 MW | 37.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939416 | AE1-173_C3 | Adder | 50.9 MW | 43.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939423 | AE1-173_E1 | Adder | 33.93 MW | 28.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939424 | AE1-173_E2 | Adder | 29.09 MW | 24.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939425 | AE1-173_E3 | Adder | 33.93 MW | 28.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939431 | AE1-175 C | Adder | 4.27 MW | 3.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939432 | AE1-175 E | Adder | 2.12 MW | 1.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939611 | AE1-191 C | Adder | 16.17 MW | 13.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939612 | AE1-191 E | Adder | 10.78 MW | 9.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940231 | AE2-005 C | Adder | 2.04 MW | 1.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940232 | AE2-005 E | Adder | 3.33 MW | 2.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940551 | AE2-041 | Adder | 11.04 MW | 9.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 5.64 MW | 4.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 8.98 MW | 7.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | 50/50 | 51.18 MW | 51.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | 50/50 | 206.54 MW | 206.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | 50/50 | 52.6 MW | 52.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | 50/50 | 205.12 MW | 205.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | 50/50 | 47.84 MW | 47.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | 50/50 | 209.91 MW | 209.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 3.75 MW | 3.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 2.5 MW | 2.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957601 | AF2-054 C | Adder | 3.24 MW | 2.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957602 | AF2-054 E | Adder | 2.16 MW | 1.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | Adder | 6.44 MW | 5.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962531 | AG1-102 C | Adder | 1.86 MW | 1.58 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962532 | AG1-102 E | Adder | 3.88 MW | 3.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962961 | AG1-145 C | Adder | 3.85 MW | 3.27 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962962 | AG1-145 E | Adder | 2.57 MW | 2.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963221 | AG1-171 C | Adder | 3.07 MW | 2.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963222 | AG1-171 E | Adder | 2.05 MW | 1.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963231 | AG1-172 C | Adder | 3.07 MW | 2.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963232 | AG1-172 E | Adder | 2.05 MW | 1.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963241 | AG1-173 C | Adder | 3.07 MW | 2.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963242 | AG1-173 E | Adder | 2.05 MW | 1.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963251 | AG1-174 C | Adder | 3.07 MW | 2.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963252 | AG1-174 E | Adder | 2.05 MW | 1.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964951 | AG1-359 O1 | 50/50 | 41.15 MW | 41.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965001 | AG1-364 C O1 | 50/50 | 12.88 MW | 12.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965002 | AG1-364 E O1 | 50/50 | 19.33 MW | 19.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 79.41 MW | 67.5 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 1.85 MW | 1.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | 50/50 | 2.06 MW | 2.06 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933294 | AC2-141 C | 50/50 | 59.12 MW | 59.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933295 | AC2-141 E | 50/50 | 25.24 MW | 25.24 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 27.38 MW | 23.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 18.26 MW | 15.52 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | 50/50 | 32.22 MW | 32.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957831 | AF2-077 C | Adder | 3.62 MW | 3.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957832 | AF2-077 E | Adder | 2.41 MW | 2.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 17.82 MW | 15.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 7.64 MW | 6.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 2.33 MW | 1.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 3.64 MW | 3.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966611 | AG1-531 C | Adder | 9.96 MW | 8.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966612 | AG1-531 E | Adder | 6.64 MW | 5.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944581 | AF1-123 C O1 | 50/50 | 87.91 MW | 87.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944582 | AF1-123 E O1 | 50/50 | 201.29 MW | 201.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944591 | AF1-124 C O1 | 50/50 | 87.91 MW | 87.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944592 | AF1-124 E O1 | 50/50 | 201.29 MW | 201.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944601 | AF1-125 C O1 | 50/50 | 87.91 MW | 87.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | 50/50 | 201.29 MW | 201.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 13.65 MW | 11.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 7.43 MW | 6.32 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 6.66 MW | 5.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961611 | AG1-000B C | Adder | 24.98 MW | 21.23 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.61 MW | 6.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 115.85 MW | 115.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 25.62 MW | 25.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.04 MW | 34.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.02 MW | 10.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 4.16 MW | 4.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.44 MW | 8.44 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.57 MW | 0.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.32 MW | 1.32 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.18 MW | 4.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.97 MW | 1.97 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 26.51 MW | 26.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.25 MW | 0.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.78 MW | 6.78 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.64 MW | 0.64 MW |
| Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961941 | AG1-037 C | Adder | 0.2 MW | 0.17 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961942 | AG1-037 E | Adder | 0.13 MW | 0.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962331 | AG1-082 C | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962332 | AG1-082 E | Adder | 0.54 MW | 0.46 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962341 | AG1-083 C | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962342 | AG1-083 E | Adder | 0.54 MW | 0.46 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963041 | AG1-153 C | Adder | 1.88 MW | 1.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963042 | AG1-153 E | Adder | 2.82 MW | 2.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963112 | AG1-160 E | Adder | 2.86 MW | 2.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963291 | AG1-178 C O2 | Adder | 21.5 MW | 18.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963301 | AG1-179 C | Adder | 2.43 MW | 2.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963311 | AG1-180 | Adder | 1.18 MW | 1.01 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963351 | AG1-184 O2 | Adder | 11.58 MW | 9.85 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964801 | AG1-343 C | Adder | 2.45 MW | 2.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964802 | AG1-343 E | Adder | 1.93 MW | 1.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966801 | AG1-551 C | Adder | 0.84 MW | 0.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966802 | AG1-551 E | Adder | 0.36 MW | 0.3 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966811 | AG1-552 C | Adder | 0.9 MW | 0.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966812 | AG1-552 E | Adder | 0.38 MW | 0.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965291 | AG1-394 C | Adder | 0.84 MW | 0.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965292 | AG1-394 E | Adder | 0.56 MW | 0.48 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965601 | AG1-428 C O2 | Adder | 2.03 MW | 1.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965602 | AG1-428 E O2 | Adder | 1.35 MW | 1.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965691 | AG1-437 C O1 | Adder | 3.86 MW | 3.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965692 | AG1-437 E O1 | Adder | 2.57 MW | 2.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965701 | AG1-438 C O1 | Adder | 3.86 MW | 3.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965702 | AG1-438 E O1 | Adder | 2.57 MW | 2.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965741 | AG1-442 O1 | Adder | 2.25 MW | 1.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965751 | AG1-443 O1 | Adder | 2.25 MW | 1.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965811 | AG1-449 | Adder | 7.88 MW | 6.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966361 | AG1-505 C | Adder | 5.55 MW | 4.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966362 | AG1-505 E | Adder | 3.7 MW | 3.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966371 | AG1-506 C | Adder | 5.55 MW | 4.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966372 | AG1-506 E | Adder | 3.7 MW | 3.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 313506 | AB1-173 C OP | Adder | 3.19 MW | 2.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314572 | 3EMPORIA | Adder | 0.21 MW | 0.18 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314594 | 6PLYMOTH | Adder | 0.03 MW | 0.03 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918492 | AA1-063AE OP | Adder | 1.7 MW | 1.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918532 | AA1-067 E | Adder | 0.27 MW | 0.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919692 | AA2-053 E OP | Adder | 1.58 MW | 1.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919702 | AA2-057 E OP | Adder | 1.3 MW | 1.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920042 | AA2-088 E OP | Adder | 4.37 MW | 3.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925785 | AC1-054 E | Adder | 1.26 MW | 1.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926070 | AC1-086 C | Adder | 9.59 MW | 8.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926071 | AC1-086 E | Adder | 4.36 MW | 3.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926201 | AC1-098 C | Adder | 2.43 MW | 2.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926202 | AC1-098 E | Adder | 1.45 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927145 | AC1-208 C | Adder | 3.6 MW | 3.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927146 | AC1-208 E | Adder | 1.6 MW | 1.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934331 | AD1-057 C O1 | Adder | 4.05 MW | 3.44 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934332 | AD1-057 E O1 | Adder | 2.17 MW | 1.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 20.32 MW | 17.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 10.34 MW | 8.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 12.16 MW | 10.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 8.11 MW | 6.89 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943171 | AE2-346 C | Adder | 0.56 MW | 0.48 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943172 | AE2-346 E | Adder | 0.24 MW | 0.2 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 4.42 MW | 3.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 1.72 MW | 1.46 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 960081 | AF2-299 C | Adder | 1.28 MW | 1.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315293 | 1DOMTR9 | Adder | 2.54 MW | 2.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 3.12 MW | 2.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316088 | AB2-174 E | Adder | 3.06 MW | 2.6 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316097 | AB2-100 E1 | Adder | 1.58 MW | 1.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316099 | AB2-100 E2 | Adder | 1.58 MW | 1.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316129 | AC1-054 C | Adder | 2.74 MW | 2.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316140 | AB2-099 C | Adder | 0.23 MW | 0.2 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316141 | AB2-099 E | Adder | 0.1 MW | 0.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.18 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923262 | AB1-132 C OP | Adder | 6.51 MW | 5.54 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923263 | AB1-132 E OP | Adder | 2.79 MW | 2.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923573 | AB1-173 E OP | Adder | 1.52 MW | 1.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923991 | AB2-040 C O1 | Adder | 3.48 MW | 2.96 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923992 | AB2-040 E O1 | Adder | 2.84 MW | 2.42 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925122 | AB2-169 E | Adder | 2.14 MW | 1.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932631 | AC2-084 C | Adder | 3.46 MW | 2.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932632 | AC2-084 E | Adder | 1.71 MW | 1.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938222 | AE1-035 E | Adder | 0.43 MW | 0.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 2.65 MW | 2.25 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 1.14 MW | 0.96 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 13.53 MW | 11.5 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 6.06 MW | 5.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946281 | AF1-292 C | Adder | 0.76 MW | 0.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957521 | AF2-046 C | Adder | 6.86 MW | 5.83 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957522 | AF2-046 E | Adder | 3.45 MW | 2.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 6.3 MW | 5.35 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 3.17 MW | 2.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 2.49 MW | 2.12 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 10.3 MW | 8.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C | Adder | 1.2 MW | 1.02 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E | Adder | 1.65 MW | 1.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940481 | AE2-033 C | 50/50 | 10.12 MW | 10.12 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940482 | AE2-033 E | 50/50 | 6.82 MW | 6.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 5.83 MW | 4.96 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 3.89 MW | 3.3 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946011 | AF1-266 | 50/50 | 8.47 MW | 8.47 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 313717 | 6SLIGO L2192 | Adder | 0.76 MW | 0.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314314 | 3LOCKS | 50/50 | 0.22 MW | 0.22 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314331 | 6POE | 50/50 | 2.01 MW | 2.01 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314435 | 6SAPONY | 50/50 | 0.27 MW | 0.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314466 | 6FENTRES | Adder | 0.75 MW | 0.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314525 | 6KINGFORK | Adder | 1.57 MW | 1.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314550 | 6HICKORY | Adder | 1.39 MW | 1.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314632 | 6AYDLETOLD | Adder | 0.76 MW | 0.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315065 | 1CHESTF6 | 50/50 | 133.5 MW | 133.5 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315073 | 1STONECA | 50/50 | 4.94 MW | 4.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315076 | 1HOPPOLC | 50/50 | 1.16 MW | 1.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315077 | 1HOPHCF1 | 50/50 | 1.82 MW | 1.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315078 | 1HOPHCF2 | 50/50 | 1.82 MW | 1.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315079 | 1HOPHCF3 | 50/50 | 1.82 MW | 1.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315080 | 1HOPHCF4 | 50/50 | 2.76 MW | 2.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315083 | 1SPRUNCA | Adder | 3.61 MW | 3.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315084 | 1SPRUNCB | Adder | 3.61 MW | 3.07 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 2.2 MW | 1.87 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | Adder | 0.46 MW | 0.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927225 | AC1-216 C | 50/50 | 0.96 MW | 0.96 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927226 | AC1-216 E | 50/50 | 4.41 MW | 4.41 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934014 | AD1-025 C | 50/50 | 9.64 MW | 9.64 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934015 | AD1-025 E | 50/50 | 5.71 MW | 5.71 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | Adder | 2.55 MW | 2.17 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | Adder | 1.7 MW | 1.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934575 | AD1-082 C | 50/50 | 5.44 MW | 5.44 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934576 | AD1-082 E | 50/50 | 3.1 MW | 3.1 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 0.34 MW | 0.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935164 | AD1-151 C | 50/50 | 9.79 MW | 9.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935165 | AD1-151 E | 50/50 | 6.53 MW | 6.53 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 1.72 MW | 1.46 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 2.8 MW | 2.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936761 | AD2-097 C | Adder | 0.69 MW | 0.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936762 | AD2-097 E | Adder | 3.43 MW | 2.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | Adder | 2.0 MW | 1.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | Adder | 1.05 MW | 0.89 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942161 | AE2-228 C | 50/50 | 2.7 MW | 2.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942162 | AE2-228 E | 50/50 | 1.8 MW | 1.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 0.75 MW | 0.63 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 1.03 MW | 0.88 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942371 | AE2-250 C O1 | 50/50 | 7.0 MW | 7.0 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942372 | AE2-250 E O1 | 50/50 | 3.69 MW | 3.69 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | Adder | 2.1 MW | 1.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | Adder | 0.95 MW | 0.8 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942551 | AE2-270 | 50/50 | 15.72 MW | 15.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 0.68 MW | 0.57 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 1.1 MW | 0.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 0.62 MW | 0.53 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 0.33 MW | 0.28 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 1.01 MW | 0.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 0.52 MW | 0.44 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 1.88 MW | 1.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 1.25 MW | 1.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961711 | AG1-011 | 50/50 | 16.38 MW | 16.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316033 | AB2-134 C | 50/50 | 1.25 MW | 1.25 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316108 | AB2-160 C | 50/50 | 3.94 MW | 3.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316109 | AB2-160 E | 50/50 | 6.43 MW | 6.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316132 | AB2-190 C | 50/50 | 11.31 MW | 11.31 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 0.77 MW | 0.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | Adder | 0.64 MW | 0.55 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 0.43 MW | 0.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923852 | AB2-025 E | 50/50 | 0.72 MW | 0.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924814 | AB2-134 E | 50/50 | 7.23 MW | 7.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932044 | AC2-012 C | Adder | 2.78 MW | 2.37 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932046 | AC2-012 E | Adder | 4.54 MW | 3.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | 50/50 | 3.25 MW | 3.25 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | 50/50 | 5.31 MW | 5.31 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938535 | AE1-072 C | Adder | 6.04 MW | 5.13 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938536 | AE1-072 E | Adder | 3.15 MW | 2.67 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939195 | AE1-149 C | 50/50 | 8.16 MW | 8.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939196 | AE1-149 E | 50/50 | 5.44 MW | 5.44 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 0.59 MW | 0.5 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939414 | AE1-173_C1 | Adder | 10.69 MW | 9.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939415 | AE1-173_C2 | Adder | 9.16 MW | 7.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939416 | AE1-173_C3 | Adder | 10.69 MW | 9.09 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939423 | AE1-173_E1 | Adder | 7.13 MW | 6.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939424 | AE1-173_E2 | Adder | 6.11 MW | 5.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939425 | AE1-173_E3 | Adder | 7.13 MW | 6.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940431 | AE2-027 C O1 | Adder | 6.76 MW | 5.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940432 | AE2-027 E O1 | Adder | 4.51 MW | 3.83 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940541 | AE2-040 | 50/50 | 1.83 MW | 1.83 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940651 | AE2-052 | 50/50 | 2.72 MW | 2.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 1.36 MW | 1.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 2.17 MW | 1.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | Adder | 9.75 MW | 8.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | Adder | 39.34 MW | 33.44 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | Adder | 10.02 MW | 8.52 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | Adder | 39.07 MW | 33.21 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | Adder | 9.1 MW | 7.74 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | Adder | 39.93 MW | 33.94 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946261 | AF1-291 C | 50/50 | 2.72 MW | 2.72 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946262 | AF1-291 E | 50/50 | 1.81 MW | 1.81 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 0.76 MW | 0.65 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 0.51 MW | 0.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | Adder | 1.24 MW | 1.06 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957711 | AF2-065 C | 50/50 | 8.02 MW | 8.02 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957712 | AF2-065 E | 50/50 | 7.7 MW | 7.7 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963221 | AG1-171 C | 50/50 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963222 | AG1-171 E | 50/50 | 0.82 MW | 0.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963231 | AG1-172 C | 50/50 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963232 | AG1-172 E | 50/50 | 0.82 MW | 0.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963241 | AG1-173 C | 50/50 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963242 | AG1-173 E | 50/50 | 0.82 MW | 0.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963251 | AG1-174 C | 50/50 | 1.23 MW | 1.23 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963252 | AG1-174 E | 50/50 | 0.82 MW | 0.82 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964951 | AG1-359 O1 | Adder | 7.74 MW | 6.58 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965001 | AG1-364 C O1 | Adder | 2.48 MW | 2.11 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965002 | AG1-364 E O1 | Adder | 3.72 MW | 3.16 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 16.31 MW | 13.86 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 0.37 MW | 0.32 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925332 | AB2-190 E | 50/50 | 4.85 MW | 4.85 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | Adder | 0.39 MW | 0.34 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 5.62 MW | 4.78 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 3.75 MW | 3.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | Adder | 6.2 MW | 5.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942001 | AE2-212 C | 50/50 | 2.38 MW | 2.38 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942002 | AE2-212 E | 50/50 | 1.59 MW | 1.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 3.42 MW | 2.91 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 1.47 MW | 1.25 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 0.56 MW | 0.48 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 0.88 MW | 0.75 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966611 | AG1-531 C | Adder | 2.1 MW | 1.79 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966612 | AG1-531 E | Adder | 1.4 MW | 1.19 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944592 | AF1-124 E O1 | Adder | 36.1 MW | 30.68 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | Adder | 5.28 MW | 4.49 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 3.31 MW | 2.81 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 1.8 MW | 1.53 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962572 | AG1-106 E | Adder | 1.21 MW | 1.03 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961681 | AG1-008 C | Adder | 6.87 MW | 5.84 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961682 | AG1-008 E | Adder | 3.44 MW | 2.92 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962271 | AG1-075 C O1 | 50/50 | 12.08 MW | 12.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962272 | AG1-075 E O1 | 50/50 | 7.36 MW | 7.36 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962571 | AG1-106 C | Adder | 2.67 MW | 2.27 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965281 | AG1-393 C | 50/50 | 1.4 MW | 1.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965282 | AG1-393 E | 50/50 | 0.93 MW | 0.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918512 | AA1-065 E OP | Adder | 1.57 MW | 1.33 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 1.51 MW | 1.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316083 | AB2-161 C | 50/50 | 2.39 MW | 2.39 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316084 | AB2-161 E | 50/50 | 3.89 MW | 3.89 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961611 | AG1-000B C | Adder | 7.63 MW | 6.49 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.76 MW | 1.76 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.48 MW | 0.48 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.05 MW | 31.05 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.45 MW | 8.45 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.95 MW | 9.95 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.66 MW | 2.66 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.03 MW | 1.03 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.4 MW | 2.4 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.29 MW | 1.29 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.48 MW | 0.48 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.59 MW | 6.59 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.93 MW | 1.93 MW |
| 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961941 | AG1-037 C | Adder | 0.2 MW | 0.17 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961942 | AG1-037 E | Adder | 0.13 MW | 0.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962331 | AG1-082 C | Adder | 0.8 MW | 0.68 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962332 | AG1-082 E | Adder | 0.54 MW | 0.46 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962341 | AG1-083 C | Adder | 0.8 MW | 0.68 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962342 | AG1-083 E | Adder | 0.54 MW | 0.46 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963041 | AG1-153 C | Adder | 1.88 MW | 1.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963042 | AG1-153 E | Adder | 2.82 MW | 2.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963111 | AG1-160 C | Adder | 1.91 MW | 1.62 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963112 | AG1-160 E | Adder | 2.86 MW | 2.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963291 | AG1-178 C O2 | Adder | 21.5 MW | 18.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963301 | AG1-179 C | Adder | 2.43 MW | 2.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963311 | AG1-180 | Adder | 1.18 MW | 1.01 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963351 | AG1-184 O2 | Adder | 11.58 MW | 9.85 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964801 | AG1-343 C | Adder | 2.45 MW | 2.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964802 | AG1-343 E | Adder | 1.93 MW | 1.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966801 | AG1-551 C | Adder | 0.84 MW | 0.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966802 | AG1-551 E | Adder | 0.36 MW | 0.3 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966811 | AG1-552 C | Adder | 0.9 MW | 0.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966812 | AG1-552 E | Adder | 0.38 MW | 0.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965291 | AG1-394 C | Adder | 0.84 MW | 0.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965292 | AG1-394 E | Adder | 0.56 MW | 0.48 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965601 | AG1-428 C O2 | Adder | 2.03 MW | 1.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965602 | AG1-428 E O2 | Adder | 1.35 MW | 1.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965691 | AG1-437 C O1 | Adder | 3.86 MW | 3.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965692 | AG1-437 E O1 | Adder | 2.57 MW | 2.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965701 | AG1-438 C O1 | Adder | 3.86 MW | 3.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965702 | AG1-438 E O1 | Adder | 2.57 MW | 2.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965741 | AG1-442 O1 | Adder | 2.25 MW | 1.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965751 | AG1-443 O1 | Adder | 2.25 MW | 1.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965811 | AG1-449 | Adder | 7.88 MW | 6.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966361 | AG1-505 C | Adder | 5.55 MW | 4.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966362 | AG1-505 E | Adder | 3.7 MW | 3.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966371 | AG1-506 C | Adder | 5.55 MW | 4.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966372 | AG1-506 E | Adder | 3.7 MW | 3.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 313506 | AB1-173 C OP | Adder | 3.19 MW | 2.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 0.28 MW | 0.24 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314572 | 3EMPORIA | Adder | 0.21 MW | 0.18 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314594 | 6PLYMOTH | Adder | 0.03 MW | 0.03 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918492 | AA1-063AE OP | Adder | 1.7 MW | 1.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918532 | AA1-067 E | Adder | 0.27 MW | 0.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919692 | AA2-053 E OP | Adder | 1.58 MW | 1.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919702 | AA2-057 E OP | Adder | 1.3 MW | 1.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920042 | AA2-088 E OP | Adder | 4.37 MW | 3.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925785 | AC1-054 E | Adder | 1.26 MW | 1.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926070 | AC1-086 C | Adder | 9.59 MW | 8.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926071 | AC1-086 E | Adder | 4.36 MW | 3.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926201 | AC1-098 C | Adder | 2.43 MW | 2.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926202 | AC1-098 E | Adder | 1.45 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927145 | AC1-208 C | Adder | 3.6 MW | 3.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927146 | AC1-208 E | Adder | 1.6 MW | 1.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934331 | AD1-057 C O1 | Adder | 4.05 MW | 3.44 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934332 | AD1-057 E O1 | Adder | 2.17 MW | 1.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 20.32 MW | 17.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 10.34 MW | 8.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 12.16 MW | 10.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 8.11 MW | 6.89 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943171 | AE2-346 C | Adder | 0.56 MW | 0.48 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943172 | AE2-346 E | Adder | 0.24 MW | 0.2 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 4.42 MW | 3.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 1.72 MW | 1.46 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 960081 | AF2-299 C | Adder | 1.28 MW | 1.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315293 | 1DOMTR9 | Adder | 2.54 MW | 2.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 3.12 MW | 2.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316088 | AB2-174 E | Adder | 3.06 MW | 2.6 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316097 | AB2-100 E1 | Adder | 1.58 MW | 1.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316099 | AB2-100 E2 | Adder | 1.58 MW | 1.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316129 | AC1-054 C | Adder | 2.74 MW | 2.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316140 | AB2-099 C | Adder | 0.23 MW | 0.2 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316141 | AB2-099 E | Adder | 0.1 MW | 0.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.18 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923262 | AB1-132 C OP | Adder | 6.51 MW | 5.54 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923263 | AB1-132 E OP | Adder | 2.79 MW | 2.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923573 | AB1-173 E OP | Adder | 1.52 MW | 1.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923991 | AB2-040 C O1 | Adder | 3.48 MW | 2.96 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923992 | AB2-040 E O1 | Adder | 2.84 MW | 2.42 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925122 | AB2-169 E | Adder | 2.14 MW | 1.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932631 | AC2-084 C | Adder | 3.46 MW | 2.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932632 | AC2-084 E | Adder | 1.71 MW | 1.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938222 | AE1-035 E | Adder | 0.43 MW | 0.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 2.65 MW | 2.25 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 1.14 MW | 0.96 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 13.53 MW | 11.5 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 6.06 MW | 5.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946281 | AF1-292 C | Adder | 0.76 MW | 0.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957521 | AF2-046 C | Adder | 6.86 MW | 5.83 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957522 | AF2-046 E | Adder | 3.45 MW | 2.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 6.3 MW | 5.35 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 3.17 MW | 2.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 2.49 MW | 2.12 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 10.3 MW | 8.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C | Adder | 1.2 MW | 1.02 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E | Adder | 1.65 MW | 1.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940481 | AE2-033 C | 50/50 | 10.12 MW | 10.12 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940482 | AE2-033 E | 50/50 | 6.82 MW | 6.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 5.83 MW | 4.96 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 3.89 MW | 3.3 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946011 | AF1-266 | 50/50 | 8.47 MW | 8.47 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 313717 | 6SLIGO L2192 | Adder | 0.76 MW | 0.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314314 | 3LOCKS | 50/50 | 0.22 MW | 0.22 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314331 | 6POE | 50/50 | 2.01 MW | 2.01 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314435 | 6SAPONY | 50/50 | 0.27 MW | 0.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314466 | 6FENTRES | Adder | 0.75 MW | 0.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314525 | 6KINGFORK | Adder | 1.57 MW | 1.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314550 | 6HICKORY | Adder | 1.39 MW | 1.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314632 | 6AYDLETOLD | Adder | 0.76 MW | 0.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315065 | 1CHESTF6 | 50/50 | 133.5 MW | 133.5 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315073 | 1STONECA | 50/50 | 4.94 MW | 4.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315076 | 1HOPPOLC | 50/50 | 1.16 MW | 1.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315077 | 1HOPHCF1 | 50/50 | 1.82 MW | 1.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315078 | 1HOPHCF2 | 50/50 | 1.82 MW | 1.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315079 | 1HOPHCF3 | 50/50 | 1.82 MW | 1.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315080 | 1HOPHCF4 | 50/50 | 2.76 MW | 2.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315083 | 1SPRUNCA | Adder | 3.61 MW | 3.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315084 | 1SPRUNCB | Adder | 3.61 MW | 3.07 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 2.2 MW | 1.87 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | Adder | 0.46 MW | 0.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927225 | AC1-216 C | 50/50 | 0.96 MW | 0.96 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927226 | AC1-216 E | 50/50 | 4.41 MW | 4.41 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934014 | AD1-025 C | 50/50 | 9.64 MW | 9.64 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934015 | AD1-025 E | 50/50 | 5.71 MW | 5.71 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | Adder | 2.55 MW | 2.17 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | Adder | 1.7 MW | 1.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934575 | AD1-082 C | 50/50 | 5.44 MW | 5.44 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934576 | AD1-082 E | 50/50 | 3.1 MW | 3.1 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 0.34 MW | 0.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935164 | AD1-151 C | 50/50 | 9.79 MW | 9.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935165 | AD1-151 E | 50/50 | 6.53 MW | 6.53 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 1.72 MW | 1.46 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 2.8 MW | 2.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936761 | AD2-097 C | Adder | 0.69 MW | 0.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936762 | AD2-097 E | Adder | 3.43 MW | 2.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | Adder | 2.0 MW | 1.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | Adder | 1.05 MW | 0.89 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942161 | AE2-228 C | 50/50 | 2.7 MW | 2.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942162 | AE2-228 E | 50/50 | 1.8 MW | 1.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 0.75 MW | 0.63 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 1.03 MW | 0.88 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942371 | AE2-250 C O1 | 50/50 | 7.0 MW | 7.0 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942372 | AE2-250 E O1 | 50/50 | 3.69 MW | 3.69 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | Adder | 2.1 MW | 1.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | Adder | 0.95 MW | 0.8 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942551 | AE2-270 | 50/50 | 15.72 MW | 15.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 0.68 MW | 0.57 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 1.1 MW | 0.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 0.62 MW | 0.53 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 0.33 MW | 0.28 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 1.01 MW | 0.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 0.52 MW | 0.44 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 1.88 MW | 1.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 1.25 MW | 1.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961711 | AG1-011 | 50/50 | 16.38 MW | 16.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316033 | AB2-134 C | 50/50 | 1.25 MW | 1.25 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316108 | AB2-160 C | 50/50 | 3.94 MW | 3.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316109 | AB2-160 E | 50/50 | 6.43 MW | 6.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316132 | AB2-190 C | 50/50 | 11.31 MW | 11.31 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 0.77 MW | 0.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | Adder | 0.64 MW | 0.55 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 0.43 MW | 0.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923852 | AB2-025 E | 50/50 | 0.72 MW | 0.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924814 | AB2-134 E | 50/50 | 7.23 MW | 7.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932044 | AC2-012 C | Adder | 2.78 MW | 2.37 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932046 | AC2-012 E | Adder | 4.54 MW | 3.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | 50/50 | 3.25 MW | 3.25 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | 50/50 | 5.31 MW | 5.31 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938535 | AE1-072 C | Adder | 6.04 MW | 5.13 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938536 | AE1-072 E | Adder | 3.15 MW | 2.67 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939195 | AE1-149 C | 50/50 | 8.16 MW | 8.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939196 | AE1-149 E | 50/50 | 5.44 MW | 5.44 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 0.59 MW | 0.5 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939414 | AE1-173_C1 | Adder | 10.69 MW | 9.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939415 | AE1-173_C2 | Adder | 9.16 MW | 7.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939416 | AE1-173_C3 | Adder | 10.69 MW | 9.09 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939423 | AE1-173_E1 | Adder | 7.13 MW | 6.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939424 | AE1-173_E2 | Adder | 6.11 MW | 5.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939425 | AE1-173_E3 | Adder | 7.13 MW | 6.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940431 | AE2-027 C O1 | Adder | 6.76 MW | 5.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940432 | AE2-027 E O1 | Adder | 4.51 MW | 3.83 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940541 | AE2-040 | 50/50 | 1.83 MW | 1.83 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940651 | AE2-052 | 50/50 | 2.72 MW | 2.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 1.36 MW | 1.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 2.17 MW | 1.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | Adder | 9.75 MW | 8.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | Adder | 39.34 MW | 33.44 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | Adder | 10.02 MW | 8.52 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | Adder | 39.07 MW | 33.21 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | Adder | 9.1 MW | 7.74 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | Adder | 39.93 MW | 33.94 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946261 | AF1-291 C | 50/50 | 2.72 MW | 2.72 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 946262 | AF1-291 E | 50/50 | 1.81 MW | 1.81 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 0.76 MW | 0.65 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 0.51 MW | 0.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | Adder | 1.24 MW | 1.06 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957711 | AF2-065 C | 50/50 | 8.02 MW | 8.02 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957712 | AF2-065 E | 50/50 | 7.7 MW | 7.7 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963221 | AG1-171 C | 50/50 | 1.23 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963222 | AG1-171 E | 50/50 | 0.82 MW | 0.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963231 | AG1-172 C | 50/50 | 1.23 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963232 | AG1-172 E | 50/50 | 0.82 MW | 0.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963241 | AG1-173 C | 50/50 | 1.23 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963242 | AG1-173 E | 50/50 | 0.82 MW | 0.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963251 | AG1-174 C | 50/50 | 1.23 MW | 1.23 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 963252 | AG1-174 E | 50/50 | 0.82 MW | 0.82 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 964951 | AG1-359 O1 | Adder | 7.74 MW | 6.58 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965001 | AG1-364 C O1 | Adder | 2.48 MW | 2.11 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965002 | AG1-364 E O1 | Adder | 3.72 MW | 3.16 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 16.31 MW | 13.86 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 0.37 MW | 0.32 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925332 | AB2-190 E | 50/50 | 4.85 MW | 4.85 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | Adder | 0.39 MW | 0.34 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 5.62 MW | 4.78 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 3.75 MW | 3.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | Adder | 6.2 MW | 5.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942001 | AE2-212 C | 50/50 | 2.38 MW | 2.38 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942002 | AE2-212 E | 50/50 | 1.59 MW | 1.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 3.42 MW | 2.91 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 1.47 MW | 1.25 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 0.56 MW | 0.48 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 0.88 MW | 0.75 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966611 | AG1-531 C | Adder | 2.1 MW | 1.79 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 966612 | AG1-531 E | Adder | 1.4 MW | 1.19 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944582 | AF1-123 E O1 | Adder | 36.1 MW | 30.68 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | Adder | 5.28 MW | 4.49 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 3.31 MW | 2.81 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 1.8 MW | 1.53 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962572 | AG1-106 E | Adder | 1.21 MW | 1.03 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961681 | AG1-008 C | Adder | 6.87 MW | 5.84 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961682 | AG1-008 E | Adder | 3.44 MW | 2.92 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962271 | AG1-075 C O1 | 50/50 | 12.08 MW | 12.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962272 | AG1-075 E O1 | 50/50 | 7.36 MW | 7.36 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 962571 | AG1-106 C | Adder | 2.67 MW | 2.27 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965281 | AG1-393 C | 50/50 | 1.4 MW | 1.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 965282 | AG1-393 E | 50/50 | 0.93 MW | 0.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918512 | AA1-065 E OP | Adder | 1.57 MW | 1.33 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 1.51 MW | 1.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316083 | AB2-161 C | 50/50 | 2.39 MW | 2.39 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 316084 | AB2-161 E | 50/50 | 3.89 MW | 3.89 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 961611 | AG1-000B C | Adder | 7.63 MW | 6.49 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.76 MW | 1.76 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.48 MW | 0.48 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.05 MW | 31.05 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.45 MW | 8.45 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.95 MW | 9.95 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.66 MW | 2.66 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.03 MW | 1.03 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.4 MW | 2.4 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.29 MW | 1.29 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.48 MW | 0.48 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.59 MW | 6.59 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.93 MW | 1.93 MW |
| 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 314525 | 6KINGFORK | Adder | 2.14 MW | 1.82 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315073 | 1STONECA | Adder | -5.81 MW | -4.94 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 926662 | AC1-147 E | Adder | 0.61 MW | 0.52 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 927225 | AC1-216 C | 50/50 | 4.72 MW | 4.72 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 927226 | AC1-216 E | 50/50 | 21.77 MW | 21.77 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 934014 | AD1-025 C | 50/50 | 47.59 MW | 47.59 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 934015 | AD1-025 E | 50/50 | 28.19 MW | 28.19 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 935112 | AD1-144 E | Adder | 0.47 MW | 0.4 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 935164 | AD1-151 C | 50/50 | 52.98 MW | 52.98 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 935165 | AD1-151 E | 50/50 | 35.32 MW | 35.32 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 942551 | AE2-270 | 50/50 | 33.77 MW | 33.77 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 943621 | AF1-033 C | 50/50 | 2.68 MW | 2.68 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 943622 | AF1-033 E | 50/50 | 1.38 MW | 1.38 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 961711 | AG1-011 | 50/50 | 80.83 MW | 80.83 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315116 | 1SURRY 1 | 50/50 | 32.4 MW | 32.4 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315117 | 1GRAVELC | 50/50 | 1.14 MW | 1.14 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315119 | 1GRAVEL3 | 50/50 | 3.29 MW | 3.29 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315120 | 1GRAVEL4 | 50/50 | 3.33 MW | 3.33 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315121 | 1GRAVEL5 | 50/50 | 3.29 MW | 3.29 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 315122 | 1GRAVEL6 | 50/50 | 3.33 MW | 3.33 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 316033 | AB2-134 C | 50/50 | 6.18 MW | 6.18 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 316258 | AE1-162 C | 50/50 | 0.35 MW | 0.35 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 916192 | Z1-068 E | Adder | 0.79 MW | 0.67 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 924814 | AB2-134 E | 50/50 | 35.66 MW | 35.66 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 932044 | AC2-012 C | Adder | 3.69 MW | 3.13 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 932046 | AC2-012 E | Adder | 6.02 MW | 5.11 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 939312 | AE1-162 E | 50/50 | 1.36 MW | 1.36 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941281 | AE2-122 C O1 | Adder | 11.83 MW | 10.05 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941282 | AE2-122 E O1 | Adder | 47.73 MW | 40.57 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941291 | AE2-123 C O1 | Adder | 12.16 MW | 10.33 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941292 | AE2-123 E O1 | Adder | 47.41 MW | 40.3 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941301 | AE2-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941302 | AE2-124 E O1 | Adder | 48.0 MW | 40.8 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 957631 | AF2-057 | Adder | 1.64 MW | 1.4 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 957711 | AF2-065 C | 50/50 | 17.22 MW | 17.22 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 957712 | AF2-065 E | 50/50 | 16.55 MW | 16.55 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963221 | AG1-171 C | 50/50 | 6.06 MW | 6.06 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963222 | AG1-171 E | 50/50 | 4.04 MW | 4.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963231 | AG1-172 C | 50/50 | 6.06 MW | 6.06 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963232 | AG1-172 E | 50/50 | 4.04 MW | 4.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963241 | AG1-173 C | 50/50 | 6.06 MW | 6.06 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963242 | AG1-173 E | 50/50 | 4.04 MW | 4.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963251 | AG1-174 C | 50/50 | 6.06 MW | 6.06 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 963252 | AG1-174 E | 50/50 | 4.04 MW | 4.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 965001 | AG1-364 C O1 | Adder | 3.26 MW | 2.77 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 965002 | AG1-364 E O1 | Adder | 4.89 MW | 4.16 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 925522 | AC1-027 E | Adder | 0.48 MW | 0.41 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 941591 | AE2-156 O1 | Adder | 8.14 MW | 6.92 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 966611 | AG1-531 C | 50/50 | 4.81 MW | 4.81 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 966612 | AG1-531 E | 50/50 | 3.21 MW | 3.21 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | 961611 | AG1-000B C | 50/50 | 20.04 MW | 20.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.45 MW | 0.45 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.28 MW | 7.28 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.26 MW | 1.26 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.68 MW | 0.68 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.38 MW | 0.38 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.09 MW | 0.09 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.22 MW | 0.22 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.88 MW | 2.88 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.31 MW | 0.31 MW |
| AD1-151 TAP-6HOPEWLL 230.0 kV Ckt 1 line l/o DVP_P4-2: 240T2041 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 314314 | 3LOCKS | 50/50 | 0.18 MW | 0.18 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 314331 | 6POE | 50/50 | 1.63 MW | 1.63 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315065 | 1CHESTF6 | 50/50 | 102.35 MW | 102.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315073 | 1STONECA | 50/50 | 17.23 MW | 17.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315076 | 1HOPPOLC | 50/50 | 4.06 MW | 4.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315077 | 1HOPHCF1 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315078 | 1HOPHCF2 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315079 | 1HOPHCF3 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 315080 | 1HOPHCF4 | 50/50 | 9.62 MW | 9.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 927225 | AC1-216 C | 50/50 | 4.19 MW | 4.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 927226 | AC1-216 E | 50/50 | 19.33 MW | 19.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 934014 | AD1-025 C | 50/50 | 42.26 MW | 42.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 934015 | AD1-025 E | 50/50 | 25.03 MW | 25.03 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 934575 | AD1-082 C | 50/50 | 5.82 MW | 5.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 934576 | AD1-082 E | 50/50 | 3.32 MW | 3.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 935164 | AD1-151 C | 50/50 | 40.37 MW | 40.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 935165 | AD1-151 E | 50/50 | 26.91 MW | 26.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942161 | AE2-228 C | 50/50 | 2.07 MW | 2.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942162 | AE2-228 E | 50/50 | 1.38 MW | 1.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942371 | AE2-250 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942372 | AE2-250 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942551 | AE2-270 | 50/50 | 67.29 MW | 67.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 961711 | AG1-011 | 50/50 | 71.77 MW | 71.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316033 | AB2-134 C | 50/50 | 5.49 MW | 5.49 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316108 | AB2-160 C | 50/50 | 3.14 MW | 3.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316109 | AB2-160 E | 50/50 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316132 | AB2-190 C | 50/50 | 47.1 MW | 47.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 924814 | AB2-134 E | 50/50 | 31.67 MW | 31.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 939195 | AE1-149 C | 50/50 | 9.32 MW | 9.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 939196 | AE1-149 E | 50/50 | 6.21 MW | 6.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 940651 | AE2-052 | 50/50 | 3.11 MW | 3.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 946261 | AF1-291 C | 50/50 | 2.1 MW | 2.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 946262 | AF1-291 E | 50/50 | 1.4 MW | 1.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 957711 | AF2-065 C | 50/50 | 34.32 MW | 34.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 957712 | AF2-065 E | 50/50 | 32.97 MW | 32.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963221 | AG1-171 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963222 | AG1-171 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963231 | AG1-172 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963232 | AG1-172 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963241 | AG1-173 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963242 | AG1-173 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963251 | AG1-174 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 963252 | AG1-174 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 925332 | AB2-190 E | 50/50 | 20.19 MW | 20.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942001 | AE2-212 C | 50/50 | 1.8 MW | 1.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 942002 | AE2-212 E | 50/50 | 1.2 MW | 1.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 962271 | AG1-075 C O1 | 50/50 | 9.61 MW | 9.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 962272 | AG1-075 E O1 | 50/50 | 5.86 MW | 5.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316083 | AB2-161 C | 50/50 | 2.55 MW | 2.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 316084 | AB2-161 E | 50/50 | 4.16 MW | 4.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | 961611 | AG1-000B C | 50/50 | 39.92 MW | 39.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.56 MW | 0.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 9.73 MW | 9.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.25 MW | 2.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.89 MW | 2.89 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.85 MW | 0.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.34 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.71 MW | 0.71 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.36 MW | 0.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.14 MW | 2.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.57 MW | 0.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 314314 | 3LOCKS | 50/50 | 0.18 MW | 0.18 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 314331 | 6POE | 50/50 | 1.63 MW | 1.63 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315065 | 1CHESTF6 | 50/50 | 102.35 MW | 102.35 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315073 | 1STONECA | 50/50 | 17.23 MW | 17.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315076 | 1HOPPOLC | 50/50 | 4.06 MW | 4.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315077 | 1HOPHCF1 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315078 | 1HOPHCF2 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315079 | 1HOPHCF3 | 50/50 | 6.34 MW | 6.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 315080 | 1HOPHCF4 | 50/50 | 9.62 MW | 9.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 927225 | AC1-216 C | 50/50 | 4.19 MW | 4.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 927226 | AC1-216 E | 50/50 | 19.33 MW | 19.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 934014 | AD1-025 C | 50/50 | 42.26 MW | 42.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 934015 | AD1-025 E | 50/50 | 25.03 MW | 25.03 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 934575 | AD1-082 C | 50/50 | 5.82 MW | 5.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 934576 | AD1-082 E | 50/50 | 3.32 MW | 3.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 935164 | AD1-151 C | 50/50 | 40.37 MW | 40.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 935165 | AD1-151 E | 50/50 | 26.91 MW | 26.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942161 | AE2-228 C | 50/50 | 2.07 MW | 2.07 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942162 | AE2-228 E | 50/50 | 1.38 MW | 1.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942371 | AE2-250 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942372 | AE2-250 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942551 | AE2-270 | 50/50 | 67.29 MW | 67.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 961711 | AG1-011 | 50/50 | 71.77 MW | 71.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316033 | AB2-134 C | 50/50 | 5.49 MW | 5.49 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316108 | AB2-160 C | 50/50 | 3.14 MW | 3.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316109 | AB2-160 E | 50/50 | 5.12 MW | 5.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316132 | AB2-190 C | 50/50 | 47.1 MW | 47.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 924814 | AB2-134 E | 50/50 | 31.67 MW | 31.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 932591 | AC2-079 C O1 | Adder | 2.73 MW | 2.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 932592 | AC2-079 E O1 | Adder | 4.45 MW | 3.79 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 939195 | AE1-149 C | 50/50 | 9.32 MW | 9.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 939196 | AE1-149 E | 50/50 | 6.21 MW | 6.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 940651 | AE2-052 | 50/50 | 3.11 MW | 3.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 946261 | AF1-291 C | 50/50 | 2.1 MW | 2.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 946262 | AF1-291 E | 50/50 | 1.4 MW | 1.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 957711 | AF2-065 C | 50/50 | 34.32 MW | 34.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 957712 | AF2-065 E | 50/50 | 32.97 MW | 32.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963221 | AG1-171 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963222 | AG1-171 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963231 | AG1-172 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963232 | AG1-172 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963241 | AG1-173 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963242 | AG1-173 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963251 | AG1-174 C | 50/50 | 5.38 MW | 5.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 963252 | AG1-174 E | 50/50 | 3.59 MW | 3.59 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 925332 | AB2-190 E | 50/50 | 20.19 MW | 20.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942001 | AE2-212 C | 50/50 | 1.8 MW | 1.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 942002 | AE2-212 E | 50/50 | 1.2 MW | 1.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 962271 | AG1-075 C O1 | 50/50 | 9.61 MW | 9.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 962272 | AG1-075 E O1 | 50/50 | 5.86 MW | 5.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316083 | AB2-161 C | 50/50 | 2.55 MW | 2.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | 316084 | AB2-161 E | 50/50 | 4.16 MW | 4.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.56 MW | 0.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 9.73 MW | 9.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.25 MW | 2.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.89 MW | 2.89 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.85 MW | 0.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.34 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.71 MW | 0.71 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.36 MW | 0.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.16 MW | 0.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.14 MW | 2.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.57 MW | 0.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 212-240-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315073 | 1STONECA | 50/50 | 10.85 MW | 10.85 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315076 | 1HOPPOLC | 50/50 | 2.56 MW | 2.56 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315077 | 1HOPHCF1 | 50/50 | 3.99 MW | 3.99 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315078 | 1HOPHCF2 | 50/50 | 3.99 MW | 3.99 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315079 | 1HOPHCF3 | 50/50 | 3.99 MW | 3.99 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315080 | 1HOPHCF4 | 50/50 | 6.06 MW | 6.06 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 927225 | AC1-216 C | 50/50 | 1.77 MW | 1.77 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 927226 | AC1-216 E | 50/50 | 8.2 MW | 8.2 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 934014 | AD1-025 C | 50/50 | 17.92 MW | 17.92 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 934015 | AD1-025 E | 50/50 | 10.61 MW | 10.61 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 934575 | AD1-082 C | Adder | -5.45 MW | -4.63 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 935164 | AD1-151 C | 50/50 | 19.14 MW | 19.14 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 935165 | AD1-151 E | 50/50 | 12.76 MW | 12.76 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 942551 | AE2-270 | 50/50 | 29.8 MW | 29.8 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 943621 | AF1-033 C | Adder | 1.37 MW | 1.17 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 943622 | AF1-033 E | Adder | 0.71 MW | 0.6 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 961711 | AG1-011 | 50/50 | 30.43 MW | 30.43 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315116 | 1SURRY 1 | 50/50 | 16.55 MW | 16.55 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315120 | 1GRAVEL4 | 50/50 | 1.7 MW | 1.7 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315121 | 1GRAVEL5 | 50/50 | 1.68 MW | 1.68 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 315122 | 1GRAVEL6 | 50/50 | 1.7 MW | 1.7 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 316033 | AB2-134 C | 50/50 | 2.33 MW | 2.33 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 316132 | AB2-190 C | 50/50 | 21.96 MW | 21.96 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 924814 | AB2-134 E | 50/50 | 13.43 MW | 13.43 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 939312 | AE1-162 E | Adder | 0.68 MW | 0.58 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 957711 | AF2-065 C | 50/50 | 15.2 MW | 15.2 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 957712 | AF2-065 E | 50/50 | 14.6 MW | 14.6 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963221 | AG1-171 C | 50/50 | 2.28 MW | 2.28 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963222 | AG1-171 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963231 | AG1-172 C | 50/50 | 2.28 MW | 2.28 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963232 | AG1-172 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963241 | AG1-173 C | 50/50 | 2.28 MW | 2.28 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963242 | AG1-173 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963251 | AG1-174 C | 50/50 | 2.28 MW | 2.28 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 963252 | AG1-174 E | 50/50 | 1.52 MW | 1.52 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 925332 | AB2-190 E | 50/50 | 9.41 MW | 9.41 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 966611 | AG1-531 C | Adder | 2.47 MW | 2.1 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 966612 | AG1-531 E | Adder | 1.65 MW | 1.4 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 316083 | AB2-161 C | Adder | -2.39 MW | -2.03 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 961611 | AG1-000B C | 50/50 | 11.71 MW | 11.71 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 940652 | AE2-052 BAT | 50/50 | 3.02 MW | 3.02 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.14 MW | 0.14 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.25 MW | 0.25 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.05 MW | 0.05 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.25 MW | 0.25 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.21 MW | 0.21 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.08 MW | 0.08 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.11 MW | 0.11 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.36 MW | 1.36 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.35 MW | 0.35 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
Light Load Analysis
The Queue Project was evaluated as a 160.0 MW (Capacity 160.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P1-2: LN 211
CONTINGENCY 'DVP_P1-2: LN 211' OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 SET PRECONTRATING 797 BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 END |
Single | AC | 136.59 % | 149.01 % | 449.32 | B | 669.53 | 59.62 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 SET PRECONTRATING 2538 BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 139.74 % | 147.17 % | 449.32 | B | 661.26 | 39.55 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P4-2: 211T2124
CONTINGENCY 'DVP_P4-2: 211T2124' OPEN BRANCH FROM BUS 314269 TO BUS 314291 CKT 1 /*6PRGEORG 230.0 - 3PRGEORG 115.0 OPEN BRANCH FROM BUS 314269 TO BUS 314303 CKT 1 /*6PRGEORG 230.0 - 6HOPEWLL 230.0 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 OPEN BUS 314269 /*6PRGEORG 230.0 END |
Breaker | AC | 114.29 % | 126.5 % | 549.0 | C | 694.48 | 67.9 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 103.03 % | 109.94 % | 549.0 | C | 603.57 | 38.82 | |
| DVP |
6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line
314303 to 314286 ckt 1 |
Base Case | Single | AC | 102.44 % | 110.08 % | 449.32 | A | 494.61 | 37.77 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P1-2: LN 228
CONTINGENCY 'DVP_P1-2: LN 228' OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1 /*6CHESTF A 230.0 - 6HOPEWLL 230.0 END |
Single | AC | 133.14 % | 146.52 % | 449.32 | B | 658.34 | 61.94 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P1-3: 8CARSON-TX#2
CONTINGENCY 'DVP_P1-3: 8CARSON-TX#2' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 END |
Single | AC | 100.98 % | 109.25 % | 449.32 | B | 490.88 | 37.59 | |
| DVP |
6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line
314303 to 314287 ckt 1 |
DVP_P1-2: LN 208
CONTINGENCY 'DVP_P1-2: LN 208' OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1 /*6CHESTF A 230.0 - 6IRON208 230.0 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1 /*6IRON208 230.0 - 6SOUWEST 230.0 OPEN BUS 314309 /*6IRON208 230.0 END |
Single | AC | 98.59 % | 108.16 % | 449.32 | B | 485.98 | 42.84 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 114.4 % | 115.39 % | 678.68 | B | 783.13 | 9.5 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 113.37 % | 114.36 % | 678.68 | B | 776.14 | 9.5 | |
| DVP |
6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer
314269 to 314291 ckt 1 |
DVP_P7-1: LN 211-228
CONTINGENCY 'DVP_P7-1: LN 211-228' OPEN BRANCH FROM BUS 314286 TO BUS 314303 CKT 1 /*6CHESTF A 230.0 - 6HOPEWLL 230.0 OPEN BRANCH FROM BUS 314287 TO BUS 314303 CKT 1 /*6CHESTF B 230.0 - 6HOPEWLL 230.0 END |
Tower | AC | 111.65 % | 125.16 % | 219.8 | C | 275.1 | 30.38 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 100.01 % | 100.83 % | 661.76 | B | 667.25 | 8.36 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 100.04 % | 100.86 % | 661.76 | B | 667.45 | 8.36 | |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315605 | 6W1-029WIND | 80/20 | 1.11 MW | 1.11 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315611 | 6Z1-036WIND | 80/20 | 0.66 MW | 0.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 901082 | W1-029 E | 80/20 | 7.46 MW | 7.46 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 916042 | Z1-036 E | 80/20 | 8.92 MW | 8.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 916192 | Z1-068 E | 80/20 | 0.34 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 940651 | AE2-052 | 80/20 | 2.5 MW | 2.5 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941281 | AE2-122 C O1 | 80/20 | 10.33 MW | 10.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941282 | AE2-122 E O1 | 80/20 | 41.69 MW | 41.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941291 | AE2-123 C O1 | 80/20 | 10.62 MW | 10.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941292 | AE2-123 E O1 | 80/20 | 41.4 MW | 41.4 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941301 | AE2-124 C O1 | 80/20 | 9.57 MW | 9.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941302 | AE2-124 E O1 | 80/20 | 41.98 MW | 41.98 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 941591 | AE2-156 O1 | 80/20 | 8.78 MW | 8.78 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 942551 | AE2-270 | 80/20 | 58.3 MW | 58.3 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 957631 | AF2-057 | 80/20 | 1.77 MW | 1.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 961711 | AG1-011 | 80/20 | 59.62 MW | 59.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 961942 | AG1-037 E | 80/20 | 0.08 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 962332 | AG1-082 E | 80/20 | 0.34 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 962342 | AG1-083 E | 80/20 | 0.34 MW | 0.34 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 964801 | AG1-343 C | 80/20 | 0.27 MW | 0.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 964802 | AG1-343 E | 80/20 | 0.41 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 964951 | AG1-359 | 80/20 | 9.7 MW | 9.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 965001 | AG1-364 C O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 965002 | AG1-364 E O1 | 80/20 | 5.27 MW | 5.27 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 965741 | AG1-442 O1 | 80/20 | 1.92 MW | 1.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 965751 | AG1-443 O1 | 80/20 | 1.92 MW | 1.92 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 315292 | 1DOMTR78 | 80/20 | 2.69 MW | 2.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944581 | AF1-123 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944582 | AF1-123 E O1 | 80/20 | 32.99 MW | 32.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944591 | AF1-124 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944592 | AF1-124 E O1 | 80/20 | 32.99 MW | 32.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944601 | AF1-125 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 944602 | AF1-125 E O1 | 80/20 | 32.99 MW | 32.99 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 211 | 961611 | AG1-000B C | 80/20 | 19.64 MW | 19.64 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315065 | 1CHESTF6 | 80/20 | 55.54 MW | 55.54 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 1.08 MW | 1.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 0.66 MW | 0.66 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 901082 | W1-029 E | 80/20 | 7.23 MW | 7.23 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 916042 | Z1-036 E | 80/20 | 8.86 MW | 8.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 916192 | Z1-068 E | 80/20 | 0.31 MW | 0.31 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940541 | AE2-040 | 80/20 | 1.22 MW | 1.22 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940651 | AE2-052 | 80/20 | 2.74 MW | 2.74 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 9.46 MW | 9.46 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941282 | AE2-122 E O1 | 80/20 | 38.19 MW | 38.19 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941292 | AE2-123 E O1 | 80/20 | 37.93 MW | 37.93 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 8.8 MW | 8.8 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941302 | AE2-124 E O1 | 80/20 | 38.6 MW | 38.6 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 7.81 MW | 7.81 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942551 | AE2-270 | 80/20 | 38.55 MW | 38.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946011 | AF1-266 | 80/20 | 5.7 MW | 5.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.57 MW | 1.57 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961711 | AG1-011 | 80/20 | 39.55 MW | 39.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963102 | AG1-159 E | 80/20 | 1.04 MW | 1.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964801 | AG1-343 C | 80/20 | 0.32 MW | 0.32 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964802 | AG1-343 E | 80/20 | 0.48 MW | 0.48 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 964951 | AG1-359 | 80/20 | 9.12 MW | 9.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965001 | AG1-364 C O1 | 80/20 | 3.13 MW | 3.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965002 | AG1-364 E O1 | 80/20 | 4.69 MW | 4.69 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965741 | AG1-442 O1 | 80/20 | 2.13 MW | 2.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 965751 | AG1-443 O1 | 80/20 | 2.13 MW | 2.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315292 | 1DOMTR78 | 80/20 | 2.97 MW | 2.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 14.2 MW | 14.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944582 | AF1-123 E O1 | 80/20 | 32.52 MW | 32.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 14.2 MW | 14.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944592 | AF1-124 E O1 | 80/20 | 32.52 MW | 32.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 14.2 MW | 14.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944602 | AF1-125 E O1 | 80/20 | 32.52 MW | 32.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963311 | AG1-180 C | 80/20 | 0.84 MW | 0.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963312 | AG1-180 E | 80/20 | 0.7 MW | 0.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 961611 | AG1-000B C | 80/20 | 13.44 MW | 13.44 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940552 | AE2-041 BAT | 80/20 | 2.42 MW | 2.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943472 | AF1-018 BAT | 80/20 | 2.42 MW | 2.42 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 963613 | AG1-210 BAT | 80/20 | 0.52 MW | 0.52 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 966663 | AG1-536 BAT | 80/20 | 3.85 MW | 3.85 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 916042 | Z1-036 E | Adder | 8.97 MW | 7.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941281 | AE2-122 C O1 | Adder | 11.03 MW | 9.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941282 | AE2-122 E O1 | Adder | 44.52 MW | 37.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941291 | AE2-123 C O1 | Adder | 11.34 MW | 9.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941292 | AE2-123 E O1 | Adder | 44.21 MW | 37.58 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941301 | AE2-124 C O1 | Adder | 10.2 MW | 8.67 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941302 | AE2-124 E O1 | Adder | 44.78 MW | 38.06 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 941591 | AE2-156 O1 | Adder | 9.47 MW | 8.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 942551 | AE2-270 | 50/50 | 66.43 MW | 66.43 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 957631 | AF2-057 | Adder | 1.91 MW | 1.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 961711 | AG1-011 | 50/50 | 67.9 MW | 67.9 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 964951 | AG1-359 | Adder | 10.3 MW | 8.75 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 965001 | AG1-364 C O1 | Adder | 3.79 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 965002 | AG1-364 E O1 | Adder | 5.69 MW | 4.84 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 965741 | AG1-442 O1 | Adder | 1.8 MW | 1.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 965751 | AG1-443 O1 | Adder | 1.8 MW | 1.53 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 314539 | 3UNCAMP | Adder | 1.93 MW | 1.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 315292 | 1DOMTR78 | Adder | 2.54 MW | 2.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944581 | AF1-123 C O1 | Adder | 15.26 MW | 12.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944582 | AF1-123 E O1 | Adder | 34.94 MW | 29.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944591 | AF1-124 C O1 | Adder | 15.26 MW | 12.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944592 | AF1-124 E O1 | Adder | 34.94 MW | 29.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944601 | AF1-125 C O1 | Adder | 15.26 MW | 12.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 944602 | AF1-125 E O1 | Adder | 34.94 MW | 29.7 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 211T2124 | 961611 | AG1-000B C | 50/50 | 22.26 MW | 22.26 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315065 | 1CHESTF6 | 50/50 | 56.2 MW | 56.2 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 916042 | Z1-036 E | Adder | 7.82 MW | 6.65 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | Adder | 1.32 MW | 1.12 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 2.76 MW | 2.76 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 11.59 MW | 9.85 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941281 | AE2-122 C O1 | Adder | 7.98 MW | 6.78 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941282 | AE2-122 E O1 | Adder | 32.18 MW | 27.36 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941291 | AE2-123 C O1 | Adder | 8.2 MW | 6.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941292 | AE2-123 E O1 | Adder | 31.96 MW | 27.17 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941301 | AE2-124 C O1 | Adder | 7.4 MW | 6.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941302 | AE2-124 E O1 | Adder | 32.49 MW | 27.62 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941591 | AE2-156 O1 | Adder | 6.63 MW | 5.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942551 | AE2-270 | 50/50 | 37.93 MW | 37.93 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 3.79 MW | 3.22 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 1.47 MW | 1.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | Adder | 6.13 MW | 5.21 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957631 | AF2-057 | Adder | 1.34 MW | 1.14 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961711 | AG1-011 | 50/50 | 38.82 MW | 38.82 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.1 MW | 0.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.39 MW | 0.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.39 MW | 0.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 1.61 MW | 1.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 2.41 MW | 2.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963102 | AG1-159 E | Adder | 1.07 MW | 0.91 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 1.63 MW | 1.39 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 2.45 MW | 2.08 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 0.31 MW | 0.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 0.46 MW | 0.39 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964951 | AG1-359 | Adder | 7.61 MW | 6.47 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965001 | AG1-364 C O1 | Adder | 2.66 MW | 2.26 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965002 | AG1-364 E O1 | Adder | 3.98 MW | 3.39 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 2.01 MW | 1.71 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 2.01 MW | 1.71 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 6.74 MW | 5.73 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.31 MW | 1.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315292 | 1DOMTR78 | Adder | 2.79 MW | 2.38 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944581 | AF1-123 C O1 | Adder | 11.49 MW | 9.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944582 | AF1-123 E O1 | Adder | 26.32 MW | 22.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944591 | AF1-124 C O1 | Adder | 11.49 MW | 9.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944592 | AF1-124 E O1 | Adder | 26.32 MW | 22.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944601 | AF1-125 C O1 | Adder | 11.49 MW | 9.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944602 | AF1-125 E O1 | Adder | 26.32 MW | 22.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 C | Adder | 0.9 MW | 0.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963312 | AG1-180 E | Adder | 0.75 MW | 0.64 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 C | Adder | 9.94 MW | 8.45 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963352 | AG1-184 E | Adder | 70.93 MW | 60.29 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961611 | AG1-000B C | 50/50 | 12.9 MW | 12.9 MW |
| Details for 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 315065 | 1CHESTF6 | 80/20 | 53.94 MW | 53.94 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 916192 | Z1-068 E | 80/20 | 0.22 MW | 0.22 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 | 80/20 | 1.05 MW | 1.05 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940651 | AE2-052 | 80/20 | 2.55 MW | 2.55 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941281 | AE2-122 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941282 | AE2-122 E O1 | 80/20 | 26.83 MW | 26.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941291 | AE2-123 C O1 | 80/20 | 6.83 MW | 6.83 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941292 | AE2-123 E O1 | 80/20 | 26.65 MW | 26.65 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941301 | AE2-124 C O1 | 80/20 | 6.16 MW | 6.16 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941302 | AE2-124 E O1 | 80/20 | 27.04 MW | 27.04 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 941591 | AE2-156 O1 | 80/20 | 5.61 MW | 5.61 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 942551 | AE2-270 | 80/20 | 36.97 MW | 36.97 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 4.9 MW | 4.9 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 957631 | AF2-057 | 80/20 | 1.13 MW | 1.13 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 961711 | AG1-011 | 80/20 | 37.77 MW | 37.77 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 965001 | AG1-364 C O1 | 80/20 | 2.25 MW | 2.25 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 965002 | AG1-364 E O1 | 80/20 | 3.37 MW | 3.37 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944581 | AF1-123 C O1 | Adder | 9.25 MW | 7.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944582 | AF1-123 E O1 | Adder | 21.18 MW | 18.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944591 | AF1-124 C O1 | Adder | 9.25 MW | 7.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944592 | AF1-124 E O1 | Adder | 21.18 MW | 18.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944601 | AF1-125 C O1 | Adder | 9.25 MW | 7.86 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 944602 | AF1-125 E O1 | Adder | 21.18 MW | 18.0 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 961611 | AG1-000B C | 80/20 | 12.33 MW | 12.33 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 940552 | AE2-041 BAT | 80/20 | 2.56 MW | 2.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 943472 | AF1-018 BAT | 80/20 | 2.56 MW | 2.56 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 963613 | AG1-210 BAT | 80/20 | 0.54 MW | 0.54 MW |
| 6HOPEWLL-6CHESTF A 230.0 kV Ckt 1 line l/o Base Case | 966663 | AG1-536 BAT | 80/20 | 4.02 MW | 4.02 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 314295 | 6BIRDNECK | 80/20 | 0.05 MW | 0.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315605 | 6W1-029WIND | 80/20 | 1.09 MW | 1.09 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 315611 | 6Z1-036WIND | 80/20 | 0.63 MW | 0.63 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 901082 | W1-029 E | 80/20 | 7.27 MW | 7.27 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 916042 | Z1-036 E | 80/20 | 8.47 MW | 8.47 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 916192 | Z1-068 E | 80/20 | 0.35 MW | 0.35 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 940651 | AE2-052 | 80/20 | 1.4 MW | 1.4 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941281 | AE2-122 C O1 | 80/20 | 10.6 MW | 10.6 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941282 | AE2-122 E O1 | 80/20 | 42.79 MW | 42.79 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941291 | AE2-123 C O1 | 80/20 | 10.9 MW | 10.9 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941292 | AE2-123 E O1 | 80/20 | 42.49 MW | 42.49 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941301 | AE2-124 C O1 | 80/20 | 9.81 MW | 9.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941302 | AE2-124 E O1 | 80/20 | 43.06 MW | 43.06 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 941591 | AE2-156 O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 942551 | AE2-270 | 80/20 | 60.53 MW | 60.53 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 945361 | AF1-201 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 945362 | AF1-201 E O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 957631 | AF2-057 | 80/20 | 1.83 MW | 1.83 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 961711 | AG1-011 | 80/20 | 61.94 MW | 61.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 964951 | AG1-359 | 80/20 | 9.93 MW | 9.93 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 965001 | AG1-364 C O1 | 80/20 | 3.63 MW | 3.63 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 965002 | AG1-364 E O1 | 80/20 | 5.44 MW | 5.44 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944581 | AF1-123 C O1 | 80/20 | 14.81 MW | 14.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944582 | AF1-123 E O1 | 80/20 | 33.91 MW | 33.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944591 | AF1-124 C O1 | 80/20 | 14.81 MW | 14.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944592 | AF1-124 E O1 | 80/20 | 33.91 MW | 33.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944601 | AF1-125 C O1 | 80/20 | 14.81 MW | 14.81 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 944602 | AF1-125 E O1 | 80/20 | 33.91 MW | 33.91 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 228 | 961611 | AG1-000B C | 80/20 | 20.53 MW | 20.53 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 314295 | 6BIRDNECK | 80/20 | 0.03 MW | 0.03 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 315060 | 1CHESTF5 | 80/20 | 20.43 MW | 20.43 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 916192 | Z1-068 E | 80/20 | 0.23 MW | 0.23 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941281 | AE2-122 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941282 | AE2-122 E O1 | 80/20 | 28.42 MW | 28.42 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941291 | AE2-123 C O1 | 80/20 | 7.24 MW | 7.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941292 | AE2-123 E O1 | 80/20 | 28.22 MW | 28.22 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941301 | AE2-124 C O1 | 80/20 | 6.52 MW | 6.52 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941302 | AE2-124 E O1 | 80/20 | 28.6 MW | 28.6 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 941591 | AE2-156 O1 | 80/20 | 6.03 MW | 6.03 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 942551 | AE2-270 | 80/20 | 36.68 MW | 36.68 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 945361 | AF1-201 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 945362 | AF1-201 E O1 | 80/20 | 1.06 MW | 1.06 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 957631 | AF2-057 | 80/20 | 1.21 MW | 1.21 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 961711 | AG1-011 | 80/20 | 37.59 MW | 37.59 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 962531 | AG1-102 C | 80/20 | 0.31 MW | 0.31 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 962532 | AG1-102 E | 80/20 | 0.65 MW | 0.65 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 964951 | AG1-359 | 80/20 | 6.62 MW | 6.62 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 965001 | AG1-364 C O1 | 80/20 | 2.41 MW | 2.41 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 965002 | AG1-364 E O1 | 80/20 | 3.62 MW | 3.62 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944581 | AF1-123 C O1 | Adder | 10.31 MW | 8.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944582 | AF1-123 E O1 | Adder | 23.61 MW | 20.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944591 | AF1-124 C O1 | Adder | 10.31 MW | 8.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944592 | AF1-124 E O1 | Adder | 23.61 MW | 20.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944601 | AF1-125 C O1 | Adder | 10.31 MW | 8.77 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 944602 | AF1-125 E O1 | Adder | 23.61 MW | 20.07 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 961611 | AG1-000B C | 80/20 | 12.68 MW | 12.68 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 940542 | AE2-040 BAT | 80/20 | 2.17 MW | 2.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-3: 8CARSON-TX#2 | 946012 | AF1-266 BAT | 80/20 | 9.81 MW | 9.81 MW |
| Details for 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 314295 | 6BIRDNECK | 80/20 | 0.04 MW | 0.04 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 315060 | 1CHESTF5 | 80/20 | 30.53 MW | 30.53 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 916192 | Z1-068 E | 80/20 | 0.26 MW | 0.26 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 940551 | AE2-041 | 80/20 | 2.5 MW | 2.5 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941281 | AE2-122 C O1 | 80/20 | 7.72 MW | 7.72 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941282 | AE2-122 E O1 | 80/20 | 31.17 MW | 31.17 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941291 | AE2-123 C O1 | 80/20 | 7.94 MW | 7.94 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941292 | AE2-123 E O1 | 80/20 | 30.96 MW | 30.96 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941301 | AE2-124 C O1 | 80/20 | 7.15 MW | 7.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941302 | AE2-124 E O1 | 80/20 | 31.38 MW | 31.38 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 941591 | AE2-156 O1 | 80/20 | 6.6 MW | 6.6 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 942551 | AE2-270 | 80/20 | 41.8 MW | 41.8 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 943471 | AF1-018 | 80/20 | 2.5 MW | 2.5 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 945361 | AF1-201 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 945362 | AF1-201 E O1 | 80/20 | 1.35 MW | 1.35 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 957631 | AF2-057 | 80/20 | 1.33 MW | 1.33 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 961711 | AG1-011 | 80/20 | 42.84 MW | 42.84 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 962531 | AG1-102 C | 80/20 | 0.41 MW | 0.41 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 962532 | AG1-102 E | 80/20 | 0.85 MW | 0.85 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 964951 | AG1-359 | 80/20 | 7.24 MW | 7.24 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 965001 | AG1-364 C O1 | 80/20 | 2.64 MW | 2.64 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 965002 | AG1-364 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944581 | AF1-123 C O1 | 80/20 | 10.98 MW | 10.98 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944582 | AF1-123 E O1 | 80/20 | 25.15 MW | 25.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944591 | AF1-124 C O1 | 80/20 | 10.98 MW | 10.98 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944592 | AF1-124 E O1 | 80/20 | 25.15 MW | 25.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944601 | AF1-125 C O1 | 80/20 | 10.98 MW | 10.98 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 944602 | AF1-125 E O1 | 80/20 | 25.15 MW | 25.15 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 961611 | AG1-000B C | 80/20 | 14.45 MW | 14.45 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 940542 | AE2-040 BAT | 80/20 | 0.89 MW | 0.89 MW |
| 6HOPEWLL-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 208 | 946012 | AF1-266 BAT | 80/20 | 3.98 MW | 3.98 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941281 | AE2-122 C O1 | Adder | 4.1 MW | 3.48 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941282 | AE2-122 E O1 | Adder | 16.54 MW | 14.06 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941291 | AE2-123 C O1 | Adder | 4.21 MW | 3.58 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941292 | AE2-123 E O1 | Adder | 16.42 MW | 13.96 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941301 | AE2-124 C O1 | Adder | 3.78 MW | 3.21 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 941302 | AE2-124 E O1 | Adder | 16.57 MW | 14.09 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 942551 | AE2-270 | 50/50 | 29.76 MW | 29.76 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 961711 | AG1-011 | 50/50 | 30.38 MW | 30.38 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944581 | AF1-123 C O1 | Adder | 5.52 MW | 4.69 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944582 | AF1-123 E O1 | Adder | 12.63 MW | 10.74 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944591 | AF1-124 C O1 | Adder | 5.52 MW | 4.69 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944592 | AF1-124 E O1 | Adder | 12.63 MW | 10.74 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944601 | AF1-125 C O1 | Adder | 5.52 MW | 4.69 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 944602 | AF1-125 E O1 | Adder | 12.63 MW | 10.74 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 961611 | AG1-000B C | 50/50 | 9.85 MW | 9.85 MW |
| 6PRGEORG-3PRGEORG 230.0/115.0 kV Ckt 1 transformer l/o DVP_P7-1: LN 211-228 | 940652 | AE2-052 BAT | 50/50 | 3.03 MW | 3.03 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7643 | Add Additional 230/115 kV Transformer at Chesterfield Sub. | $6,000,000 | |
| b2990 | PJM Baseline Upgrade b2990. | $350,000 | |
| n6130 | Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with 2-636 ACSR. | $31,000,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n8238 | Rebuild 1.38 mi miles of 230 kV Line 217 from Varina to Charles City with 2-768.2 ACSS 250 C | $2,070,000 | |
| b3694.12 | Upgrade equipment at Chesterfield substation to not limit ratings on Lines 211 and 228. | $0 | |
| b3694.13 | Upgrade equipment at Hopewell substation to not limit ratings on Lines 211 and 228. | $0 | |
| b2922 | PJM Baseline Upgrade b2922. Rebuild 8 of 11 miles of 230kV Lines #211 | $0 | |
| b3694.11 | Reconductor approximately 2.9 miles of 230 kV Line #228 Chesterfield – Hopewell to achieve a minimum summer emergency rating of 1046 MVA. | $0 | |
| b3694.10 | Reconductor approximately 2.9 miles of 230 kV Line #211 Chesterfield – Hopewell to achieve a minimum summer emergency rating of 1046 MVA. | $0 | |
| n7199 | Rebuild 1.63 miles of 230 kV Line 2197 from Hopewell to Colonial Trail with 2-636 ACSR. | $2,445,000 | |
| n8149 | Add Additional 500/230 kV Transformer at Elmont Substation | $22,000,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
| n8056 | Wreck and rebuild the existing 115 kV Line and Add new 230 kV Circuit | $32,493,499 | |
| n8239 | Rebuild 9.46 miles of 230 kV Line 217 from Chesterfield to Varina with 2-768.2 ACSS 250 C | $14,190,000 | |
| b3692 | Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy. | $0 | |
| n6324 | Replace Terminal Equipment at Surry and Chickahominy Substations | $4,000,000 | |
| b3020 | PJM baseline upgrade b3020: Rebuild 500kV Line #574 Ladysmith to Elmont . | $0 | |
| n6063 | Replace Wave traps at Ladysmith and Possum Pt 500 kV substations. | $500,000 | |
| n6157 | Relay Change Outs (CT) at Ladysmith and Possum Pt 500 kV substations. | $120,000 | |
| n6055 | Replace Wave traps at Midlothian and North Anna 500kV substations | $300,000 | |
| n5609 | Rebuild 41.13 miles of 500 kV Line 576 from Midlothian to North Anna with 3-1351.5 125C ACSR. | $127,503,000 | |
| n6160 | Rebuild 18.75 miles of 500 kV Line 594 from Spotsylvania to Morrisvile with 3-1351.5 113C ACSR. | $58,125,000 | |
| n6132 | Rebuild 14.02 miles of 500 kV Line 573 from North Anna to Spotsylvania with 3-1351.5 113C ACSR. | $43,462,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-011 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.