AG1-005 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:56
Corbin-Crescent Ridge 138 kV
150.0 MW Capacity / 250.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-005 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the ComEd zone — Stephenson County, Illinois. The installed facilities will have a total capability of 250.0 MW with 150.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-005 |
| Project Name | Corbin-Crescent Ridge 138 kV |
| Developer Name | Sky Yield Solar Farm, LLC |
| State | Illinois |
| County | Stephenson |
| Transmission Owner | ComEd |
| MFO | 250.0 MW |
| MWE | 250.0 MW |
| MWC | 150.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-005 will interconnect on the ComEd transmission system by tying into Crescent - Corbin 138 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 250.0 MW (Capacity 150.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 163.22 % | 164.39 % | 1409.0 | B | 2316.31 | 19.53 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 163.22 % | 164.39 % | 1409.0 | B | 2316.26 | 19.53 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P2-1_074-L6101___-C
CONTINGENCY 'COMED_P2-1_074-L6101___-C' TRIP BRANCH FROM BUS 962720 TO BUS 271655 CKT 1 /*AG1-121 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 77.99 % | 140.23 % | 179.0 | B | 251.01 | 113.84 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P1-2_138-L6101___-S-B
CONTINGENCY 'COMED_P1-2_138-L6101___-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 END |
Single | AC | 79.34 % | 140.47 % | 179.0 | B | 251.44 | 112.47 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P2-1_HEN-L6101___
CONTINGENCY 'COMED_P2-1_HEN-L6101___' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 END |
Single | AC | 78.32 % | 139.21 % | 179.0 | B | 249.18 | 111.98 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
COMED_P2-1_074-L6101___-B
CONTINGENCY 'COMED_P2-1_074-L6101___-B' TRIP BRANCH FROM BUS 965670 TO BUS 962720 CKT 1 /*AG1-435 TAP 138.0 - AG1-121 TAP 138.0 END |
Single | AC | 77.97 % | 140.33 % | 179.0 | B | 251.19 | 113.84 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP
CONTINGENCY 'EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP' OPEN BRANCH FROM BUS 348921 TO BUS 348923 CKT 1 /*4BUREAU 138.0 - 4KEWANEE N 138.0 END |
Single | AC | 79.75 % | 142.0 % | 179.0 | B | 254.19 | 113.78 | |
| AMIL/CE |
AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line
958340 to 348935 ckt 1 |
Base Case | Single | AC | 70.27 % | 134.28 % | 179.0 | A | 240.35 | 116.29 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 107.91 % | 109.13 % | 971.0 | STE | 1059.65 | 13.52 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 107.91 % | 109.13 % | 971.0 | STE | 1059.65 | 13.52 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P1-2_345-L1202__B-S
CONTINGENCY 'COMED_P1-2_345-L1202__B-S' TRIP BRANCH FROM BUS 270716 TO BUS 930770 CKT 1 /*DRESDEN ; B 345.0 - AB1-122 TAP2 345.0 END |
Single | AC | 108.77 % | 110.03 % | 1568.0 | STE | 1725.25 | 19.44 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 106.34 % | 107.55 % | 1399.0 | B | 1504.67 | 17.02 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 106.33 % | 107.55 % | 1399.0 | B | 1504.62 | 17.02 | |
| CE |
AF1-318 TAP-CRESCENT ; R 138.0 kV Ckt 1 line
946540 to 271241 ckt 1 |
COMED_P1-2_138-L98105_R-S-D
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-D' TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Single | AC | 38.11 % | 117.77 % | 180.0 | STE | 211.99 | 150.0 | |
| CE |
CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line
271241 to 271836 ckt 1 |
COMED_P1-2_138-L98105_R-S-D
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-D' TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Single | AC | 43.87 % | 102.77 % | 245.0 | STE | 251.78 | 149.97 | |
| CE |
KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line
271836 to 271837 ckt 1 |
COMED_P1-2_138-L98105_R-S-D
CONTINGENCY 'COMED_P1-2_138-L98105_R-S-D' TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Single | AC | 64.04 % | 113.94 % | 247.0 | STE | 281.44 | 128.49 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
Base Case | Single | AC | 105.94 % | 107.53 % | 1201.0 | A | 1291.46 | 18.46 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 165.82 % | 166.2 % | 1466.0 | B | 2436.43 | 20.51 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3130_05EUGENE 345_B2
CONTINGENCY 'AEP_P4_#3130_05EUGENE 345_B2' OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 153.93 % | 154.21 % | 1466.0 | B | 2260.75 | 20.88 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P4_074-38-L15508_
CONTINGENCY 'COMED_P4_074-38-L15508_' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 MOVE 100 PERCENT LOAD FROM BUS 271331 TO BUS 271330 /*DIXON ;8R 138.0 - DIXON ;7B 138.0 TRIP BRANCH FROM BUS 271331 TO BUS 271333 CKT 1 /*DIXON ;8R 138.0 - DIXON ; R 138.0 TRIP BRANCH FROM BUS 272097 TO BUS 271331 CKT 1 /*NELSON ;RT 138.0 - DIXON ;8R 138.0 TRIP BRANCH FROM BUS 272097 TO BUS 272095 CKT 1 /*NELSON ;RT 138.0 - NELSON ; R 138.0 TRIP BRANCH FROM BUS 272505 TO BUS 272097 CKT 1 /*SCHAUFF R; R 138.0 - NELSON ;RT 138.0 END |
Breaker | AC | 86.54 % | 104.98 % | 265.0 | ALDR | 278.21 | 53.65 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P4_074-38-L7413__
CONTINGENCY 'COMED_P4_074-38-L7413__' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 END |
Breaker | AC | 86.09 % | 104.5 % | 265.0 | ALDR | 276.92 | 53.58 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P4_001-38-TR81___
CONTINGENCY 'COMED_P4_001-38-TR81___' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 TRIP BRANCH FROM BUS 270802 TO BUS 270803 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; R 345.0 TRIP BRANCH FROM BUS 270802 TO BUS 271908 CKT 1 /*LASCO STA; B 345.0 - LASCO STA; B 138.0 END |
Breaker | AC | 88.15 % | 109.4 % | 223.0 | B | 243.97 | 49.9 | |
| CE |
PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275207 to 270630 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 113.65 % | 113.97 % | 1469.0 | STE | 1674.2 | 17.04 | |
| CE |
PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line
270846 to 275207 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 113.43 % | 113.76 % | 1469.0 | STE | 1671.2 | 17.04 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 113.22 % | 113.46 % | 1469.0 | STE | 1666.77 | 16.5 | |
| CE |
PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line
270847 to 275208 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 112.81 % | 113.05 % | 1469.0 | STE | 1660.69 | 16.5 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 100.28 % | 117.6 % | 265.0 | ALDR | 311.64 | 49.9 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P2-2_#286_05EUGENE 345_2
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Bus | AC | 156.6 % | 156.7 % | 1466.0 | B | 2297.16 | 20.77 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P2-2_074_KE-138___1
CONTINGENCY 'COMED_P2-2_074_KE-138___1' DISCONNECT BUS 271836 /*KEWANEE ;11 138.0 DISCONNECT BUS 271837 /*KEWANEE ;12 138.0 DISCONNECT BUS 271838 /*KEWANEE ;13 138.0 END |
Bus | AC | 86.1 % | 104.51 % | 265.0 | ALDR | 276.94 | 53.58 | |
| AMIL/CE |
4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line
348935 to 936510 ckt 1 |
COMED_P2-2_001_LA-138B__1
CONTINGENCY 'COMED_P2-2_001_LA-138B__1' DISCONNECT BUS 271908 /*LASCO STA; B 138.0 END |
Bus | AC | 88.17 % | 109.42 % | 223.0 | B | 244.0 | 49.9 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 126.35 % | 149.11 % | 214.0 | B | 319.09 | 48.71 | |
| AMIL/CE |
POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line
272269 to 349600 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 126.35 % | 149.11 % | 214.0 | B | 319.09 | 48.71 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 125.78 % | 145.98 % | 449.0 | B | 655.45 | 90.71 | |
| AMIL/CE |
KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line
271838 to 348923 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 125.78 % | 145.98 % | 449.0 | B | 655.45 | 90.71 | |
| CE |
AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line
958340 to 946540 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | AC | 38.38 % | 151.62 % | 213.0 | ALDR | 322.95 | 250.0 | |
| CE |
AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line
958340 to 946540 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | AC | 38.38 % | 151.62 % | 213.0 | ALDR | 322.95 | 250.0 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 136.54 % | 138.48 % | 2033.0 | ALDR | 2815.31 | 36.98 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 150.01 % | 152.54 % | 1479.0 | B | 2256.11 | 36.98 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 125.47 % | 127.28 % | 2033.0 | ALDR | 2587.59 | 37.03 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 135.05 % | 137.77 % | 1479.0 | B | 2037.65 | 37.03 | |
| CE |
TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line
272607 to 272269 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 85.84 % | 101.3 % | 315.0 | ALDR | 319.09 | 48.71 | |
| CE |
TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line
272607 to 272269 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D' TRIP BRANCH FROM BUS 271655 TO BUS 348918 CKT 1 /*HENNEEPIN; T 138.0 - 4HENNEPIN S 138.0 TRIP BRANCH FROM BUS 271655 TO BUS 962720 CKT 1 /*HENNEEPIN; T 138.0 - AG1-121 TAP 138.0 TRIP BRANCH FROM BUS 926820 TO BUS 271655 CKT 1 /*AC1-168 TAP 138.0 - HENNEEPIN; T 138.0 TRIP BRANCH FROM BUS 958340 TO BUS 348935 CKT 1 /*AF2-128 TAP 138.0 - 4CORBIN 138.0 END |
Tower | DC | 85.84 % | 101.3 % | 315.0 | ALDR | 319.09 | 48.71 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A' TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 TRIP BRANCH FROM BUS 272521 TO BUS 926820 CKT 1 /*STREATOR ; 138.0 - AC1-168 TAP 138.0 END |
Tower | AC | 92.99 % | 112.22 % | 265.0 | ALDR | 297.39 | 55.64 | |
| CE |
AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line
936510 to 271987 ckt 1 |
COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B
CONTINGENCY 'COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B' TRIP BRANCH FROM BUS 271836 TO BUS 271241 CKT 1 /*KEWANEE ;11 138.0 - CRESCENT ; R 138.0 TRIP BRANCH FROM BUS 965670 TO BUS 271835 CKT 1 /*AG1-435 TAP 138.0 - KEWANEE ;23 138.0 END |
Tower | AC | 81.75 % | 101.13 % | 265.0 | ALDR | 267.99 | 56.3 | |
| CE |
DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line
270716 to 274702 ckt 1 |
COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S
CONTINGENCY 'COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S' TRIP BRANCH FROM BUS 270736 TO BUS 270770 CKT 1 /*ELWOOD ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270737 TO BUS 270769 CKT 1 /*ELWOOD ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 100.32 % | 101.29 % | 1477.0 | ALDR | 1495.99 | 16.34 | |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 961651 | AG1-005 C O1 | 80/20 | 113.84 MW | 113.84 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 962721 | AG1-121 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 965671 | AG1-435 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 927201 | AC1-214 C O1 | 80/20 | 1.11 MW | 1.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 934051 | AD1-031 C O1 | 80/20 | 2.6 MW | 2.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274848 | CAMPGROVE;RU | 80/20 | 0.37 MW | 0.37 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274849 | CRESCENT ;1U | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274851 | PROVIDENC;RU | 80/20 | 0.6 MW | 0.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274877 | BISHOP HL;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 274878 | BISHOP HL;2U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 925581 | AC1-033 C | 80/20 | 1.29 MW | 1.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 946541 | AF1-318 C O1 | 80/20 | 36.33 MW | 36.33 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957751 | AF2-069 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 957761 | AF2-070 C | 80/20 | 1.07 MW | 1.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | 958341 | AF2-128 C O1 | 80/20 | 10.62 MW | 10.62 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.58 MW | 4.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.0 MW | 1.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 961651 | AG1-005 C O1 | 80/20 | 112.47 MW | 112.47 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 962721 | AG1-121 C O1 | 80/20 | 4.85 MW | 4.85 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 965671 | AG1-435 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 927201 | AC1-214 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 934051 | AD1-031 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274848 | CAMPGROVE;RU | 80/20 | 0.35 MW | 0.35 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274849 | CRESCENT ;1U | 80/20 | 0.58 MW | 0.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274851 | PROVIDENC;RU | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274877 | BISHOP HL;1U | 80/20 | 0.32 MW | 0.32 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 274878 | BISHOP HL;2U | 80/20 | 0.32 MW | 0.32 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 925581 | AC1-033 C | 80/20 | 1.23 MW | 1.23 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 946541 | AF1-318 C O1 | 80/20 | 35.87 MW | 35.87 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 957751 | AF2-069 C | 80/20 | 0.74 MW | 0.74 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 957761 | AF2-070 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | 958341 | AF2-128 C O1 | 80/20 | 10.49 MW | 10.49 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.3 MW | 4.3 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.01 MW | 1.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L6101___-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 961651 | AG1-005 C O1 | 80/20 | 111.98 MW | 111.98 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 962721 | AG1-121 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 965671 | AG1-435 C O1 | 80/20 | 2.63 MW | 2.63 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 927201 | AC1-214 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 934051 | AD1-031 C O1 | 80/20 | 2.27 MW | 2.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 274848 | CAMPGROVE;RU | 80/20 | 0.32 MW | 0.32 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 274849 | CRESCENT ;1U | 80/20 | 0.57 MW | 0.57 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 274851 | PROVIDENC;RU | 80/20 | 0.58 MW | 0.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 274877 | BISHOP HL;1U | 80/20 | 0.29 MW | 0.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 274878 | BISHOP HL;2U | 80/20 | 0.29 MW | 0.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 925581 | AC1-033 C | 80/20 | 1.13 MW | 1.13 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 946541 | AF1-318 C O1 | 80/20 | 35.67 MW | 35.67 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 957751 | AF2-069 C | 80/20 | 0.73 MW | 0.73 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 957761 | AF2-070 C | 80/20 | 1.03 MW | 1.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | 958341 | AF2-128 C O1 | 80/20 | 10.45 MW | 10.45 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.08 MW | 0.08 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.88 MW | 3.88 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.55 MW | 0.55 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.19 MW | 0.19 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.9 MW | 0.9 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.06 MW | 0.06 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_HEN-L6101___ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 961651 | AG1-005 C O1 | 80/20 | 113.84 MW | 113.84 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 965671 | AG1-435 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 927201 | AC1-214 C O1 | 80/20 | 1.11 MW | 1.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 934051 | AD1-031 C O1 | 80/20 | 2.6 MW | 2.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 274848 | CAMPGROVE;RU | 80/20 | 0.37 MW | 0.37 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 274849 | CRESCENT ;1U | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 274851 | PROVIDENC;RU | 80/20 | 0.6 MW | 0.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 274877 | BISHOP HL;1U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 274878 | BISHOP HL;2U | 80/20 | 0.34 MW | 0.34 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 925581 | AC1-033 C | 80/20 | 1.29 MW | 1.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 946541 | AF1-318 C O1 | 80/20 | 36.33 MW | 36.33 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 957751 | AF2-069 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 957761 | AF2-070 C | 80/20 | 1.07 MW | 1.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | 958341 | AF2-128 C O1 | 80/20 | 10.62 MW | 10.62 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.58 MW | 4.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.0 MW | 1.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o COMED_P2-1_074-L6101___-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 961651 | AG1-005 C O1 | 80/20 | 113.78 MW | 113.78 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 927201 | AC1-214 C O1 | 80/20 | 1.11 MW | 1.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 934051 | AD1-031 C O1 | 80/20 | 2.6 MW | 2.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 274848 | CAMPGROVE;RU | 80/20 | 0.37 MW | 0.37 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 274849 | CRESCENT ;1U | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 274851 | PROVIDENC;RU | 80/20 | 0.6 MW | 0.6 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 274877 | BISHOP HL;1U | 80/20 | 0.33 MW | 0.33 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 274878 | BISHOP HL;2U | 80/20 | 0.33 MW | 0.33 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 925581 | AC1-033 C | 80/20 | 1.29 MW | 1.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 946541 | AF1-318 C O1 | 80/20 | 36.31 MW | 36.31 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 957751 | AF2-069 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 957761 | AF2-070 C | 80/20 | 1.07 MW | 1.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | 958341 | AF2-128 C O1 | 80/20 | 10.61 MW | 10.61 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.1 MW | 0.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.57 MW | 4.57 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.99 MW | 0.99 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.11 MW | 0.11 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o EXT_P21:138:AMIL::EKEWANEE:PRINCETONTAP | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 116.29 MW | 116.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.29 MW | 0.29 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.58 MW | 0.58 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.59 MW | 0.59 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.74 MW | 0.74 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 10.85 MW | 10.85 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.06 MW | 0.06 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.73 MW | 3.73 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.79 MW | 0.79 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.9 MW | 0.9 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| AF2-128 TAP-4CORBIN 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.09 MW | 0.09 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 961651 | AG1-005 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 962721 | AG1-121 C O1 | 80/20 | 8.57 MW | 8.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 966821 | AG1-553 C O1 | 80/20 | 20.71 MW | 20.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965141 | AG1-379 C | 80/20 | 59.32 MW | 59.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965671 | AG1-435 C O1 | 80/20 | 6.0 MW | 6.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965911 | AG1-460 C | 80/20 | 0.74 MW | 0.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 965931 | AG1-462 C O1 | 80/20 | 13.4 MW | 13.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 926821 | AC1-168 C O1 | 80/20 | 1.32 MW | 1.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 927201 | AC1-214 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934051 | AD1-031 C O1 | 80/20 | 4.82 MW | 4.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 935141 | AD1-148 | 80/20 | 1.83 MW | 1.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936291 | AD2-038 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936771 | AD2-100 C | 80/20 | 7.61 MW | 7.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 936971 | AD2-131 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942421 | AE2-255 C O1 | 80/20 | 10.81 MW | 10.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942481 | AE2-261 C | 80/20 | 11.03 MW | 11.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 942651 | AE2-281 C O1 | 80/20 | 1.74 MW | 1.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 945871 | AF1-252 O1 | 80/20 | 3.57 MW | 3.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 945881 | AF1-253 | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958481 | AF2-142 C | 80/20 | 15.36 MW | 15.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958491 | AF2-143 C | 80/20 | 22.36 MW | 22.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 959351 | AF2-226 C | 80/20 | 3.26 MW | 3.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 960261 | AF2-317 | 80/20 | 0.79 MW | 0.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 960281 | AF2-319 C | 80/20 | 3.26 MW | 3.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274650 | KINCAID ;1U | 80/20 | 5.86 MW | 5.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274651 | KINCAID ;2U | 80/20 | 5.87 MW | 5.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274662 | QUAD CITI;1U | 80/20 | 13.55 MW | 13.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274663 | QUAD CITI;2U | 80/20 | 13.51 MW | 13.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274677 | POWERTON ;5U | 80/20 | 56.64 MW | 56.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274678 | POWERTON ;6U | 80/20 | 56.78 MW | 56.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274699 | CORDOVA ;1C | 80/20 | 2.4 MW | 2.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274700 | CORDOVA ;2C | 80/20 | 2.4 MW | 2.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274701 | CORDOVA ;1S | 80/20 | 2.7 MW | 2.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274848 | CAMPGROVE;RU | 80/20 | 0.9 MW | 0.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274861 | TOP CROP ;1U | 80/20 | 0.51 MW | 0.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274862 | TOP CROP ;2U | 80/20 | 0.97 MW | 0.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274879 | MINONK ;1U | 80/20 | 2.95 MW | 2.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 274891 | OTTER CRK;1U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276156 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276157 | O-029 C | 80/20 | 0.17 MW | 0.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 276158 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293513 | O-009 C1 | 80/20 | 0.29 MW | 0.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293514 | O-009 C2 | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 293515 | O-009 C3 | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 925581 | AC1-033 C | 80/20 | 2.35 MW | 2.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 930761 | AB1-122 CT1 | 80/20 | 379.71 MW | 379.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 930771 | AB1-122 CT2 | 80/20 | 248.59 MW | 248.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 938851 | AE1-113 C O1 | 80/20 | 28.54 MW | 28.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 939321 | AE1-163 C O1 | 80/20 | 12.18 MW | 12.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 944221 | AF1-090 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 946321 | AF1-296 C O1 | 80/20 | 3.0 MW | 3.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 946541 | AF1-318 C O1 | 80/20 | 7.12 MW | 7.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957381 | AF2-032 C | 80/20 | 0.84 MW | 0.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957751 | AF2-069 C | 80/20 | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 957761 | AF2-070 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 958341 | AF2-128 C O1 | 80/20 | 1.81 MW | 1.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934101 | AD2-000 1 | 80/20 | 30.71 MW | 30.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 934111 | AD2-000 2 | 80/20 | 20.1 MW | 20.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 951631 | J456 C | External Queue | 3.93 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 952651 | J756 C | External Queue | 3.6 MW | 3.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 952871 | J757 C | External Queue | 4.6 MW | 4.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 953201 | J715 C | External Queue | 1.47 MW | 1.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 953951 | J859 | External Queue | 23.64 MW | 23.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 954981 | J974 C | External Queue | 13.89 MW | 13.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 955711 | J1055 C | External Queue | 4.5 MW | 4.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 956151 | J1102 | External Queue | 6.35 MW | 6.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 956411 | J1131 | External Queue | 7.79 MW | 7.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990051 | J1200 | External Queue | 2.98 MW | 2.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990351 | J1289 C | External Queue | 4.41 MW | 4.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 990751 | J1383 | External Queue | 32.96 MW | 32.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991091 | J1477 | External Queue | 3.89 MW | 3.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991216 | J1653 | External Queue | 31.41 MW | 31.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991276 | J1725 C | External Queue | 3.27 MW | 3.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | 991301 | J1755 C | External Queue | 3.13 MW | 3.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.88 MW | 0.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.32 MW | 11.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 32.69 MW | 32.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.95 MW | 34.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.57 MW | 6.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.06 MW | 13.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L1202__B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.75 MW | 3.75 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for AF1-318 TAP-CRESCENT ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-318 TAP-CRESCENT ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 80/20 | 150.0 MW | 150.0 MW |
| AF1-318 TAP-CRESCENT ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 80/20 | 52.8 MW | 52.8 MW |
| AF1-318 TAP-CRESCENT ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 80/20 | 13.99 MW | 13.99 MW |
| Details for CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 80/20 | 149.97 MW | 149.97 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 80/20 | 3.23 MW | 3.23 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 80/20 | 1.7 MW | 1.7 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 80/20 | 1.75 MW | 1.75 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 80/20 | 52.78 MW | 52.78 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957751 | AF2-069 C | 80/20 | 2.2 MW | 2.2 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957761 | AF2-070 C | 80/20 | 3.1 MW | 3.1 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 80/20 | 13.99 MW | 13.99 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.04 MW | 0.04 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| CRESCENT ; R-KEWANEE ;11 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 80/20 | 128.49 MW | 128.49 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 80/20 | 1.46 MW | 1.46 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 80/20 | 1.5 MW | 1.5 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276156 | O-029 C | 80/20 | 0.23 MW | 0.23 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276157 | O-029 C | 80/20 | 0.25 MW | 0.25 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 276158 | O-029 C | 80/20 | 0.45 MW | 0.45 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293513 | O-009 C1 | 80/20 | 0.42 MW | 0.42 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293514 | O-009 C2 | 80/20 | 0.21 MW | 0.21 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 293515 | O-009 C3 | 80/20 | 0.24 MW | 0.24 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 925581 | AC1-033 C | Adder | -1.87 MW | -1.59 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 80/20 | 45.23 MW | 45.23 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957751 | AF2-069 C | 80/20 | 1.89 MW | 1.89 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 957761 | AF2-070 C | 80/20 | 2.66 MW | 2.66 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 80/20 | 11.99 MW | 11.99 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.22 MW | 0.22 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.83 MW | 6.83 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;11-KEWANEE ;12 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 18.46 MW | 18.46 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | 80/20 | 8.03 MW | 8.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 19.75 MW | 19.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965141 | AG1-379 C | 80/20 | 26.97 MW | 26.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 0.66 MW | 0.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.25 MW | 1.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 4.5 MW | 4.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936291 | AD2-038 C O1 | 80/20 | 5.59 MW | 5.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 6.76 MW | 6.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 0.45 MW | 0.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942481 | AE2-261 C | 80/20 | 9.79 MW | 9.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.48 MW | 1.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 3.18 MW | 3.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 2.2 MW | 2.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958481 | AF2-142 C | 80/20 | 13.06 MW | 13.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958491 | AF2-143 C | 80/20 | 19.05 MW | 19.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274650 | KINCAID ;1U | 80/20 | 5.2 MW | 5.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274651 | KINCAID ;2U | 80/20 | 5.21 MW | 5.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 12.92 MW | 12.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 12.88 MW | 12.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274677 | POWERTON ;5U | 80/20 | 48.16 MW | 48.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274678 | POWERTON ;6U | 80/20 | 48.42 MW | 48.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.57 MW | 2.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.84 MW | 0.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.27 MW | 0.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.44 MW | 0.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.34 MW | 1.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.48 MW | 0.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.19 MW | 2.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | 80/20 | 367.02 MW | 367.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 12.97 MW | 12.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 10.37 MW | 10.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.75 MW | 6.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957381 | AF2-032 C | 80/20 | 0.75 MW | 0.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.47 MW | 0.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.72 MW | 1.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | 80/20 | 29.68 MW | 29.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951511 | J530 C | External Queue | 3.3 MW | 3.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951631 | J456 C | External Queue | 3.6 MW | 3.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951821 | J541 C | External Queue | 4.19 MW | 4.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952651 | J756 C | External Queue | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952871 | J757 C | External Queue | 4.15 MW | 4.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953201 | J715 C | External Queue | 1.4 MW | 1.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953951 | J859 | External Queue | 21.59 MW | 21.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954721 | J750 C | External Queue | 1.45 MW | 1.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954981 | J974 C | External Queue | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 4.11 MW | 4.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956151 | J1102 | External Queue | 5.67 MW | 5.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956411 | J1131 | External Queue | 7.32 MW | 7.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 4.02 MW | 4.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990751 | J1383 | External Queue | 30.22 MW | 30.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991091 | J1477 | External Queue | 3.66 MW | 3.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991216 | J1653 | External Queue | 28.71 MW | 28.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 C | External Queue | 2.99 MW | 2.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 C | External Queue | 2.92 MW | 2.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.8 MW | 0.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 32.25 MW | 32.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.99 MW | 31.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.51 MW | 0.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.29 MW | 12.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.44 MW | 3.44 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961651 | AG1-005 C O1 | Adder | 12.31 MW | 10.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961652 | AG1-005 E O1 | Adder | 8.21 MW | 6.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C O1 | Adder | 4.22 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E O1 | Adder | 19.72 MW | 16.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964581 | AG1-321 C O1 | Adder | 11.78 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964582 | AG1-321 E O1 | Adder | 6.86 MW | 5.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 18.91 MW | 16.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 3.81 MW | 3.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965091 | AG1-374 C | 50/50 | 21.96 MW | 21.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 14.64 MW | 14.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C | 50/50 | 7.26 MW | 7.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E | 50/50 | 33.99 MW | 33.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 | 50/50 | 13.75 MW | 13.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C O1 | Adder | 2.87 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E O1 | Adder | 13.45 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965931 | AG1-462 C O1 | Adder | 12.24 MW | 10.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965932 | AG1-462 E O1 | Adder | 8.16 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 C | Adder | 11.31 MW | 9.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.79 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.29 MW | 4.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 4.96 MW | 4.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 5.71 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C | 50/50 | 22.42 MW | 22.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E | 50/50 | 14.95 MW | 14.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C | 50/50 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E | 50/50 | 7.42 MW | 7.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.04 MW | 31.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.7 MW | 20.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 20.29 MW | 17.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958911 | AF2-182 C | Adder | 12.64 MW | 10.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958912 | AF2-182 E | Adder | 8.43 MW | 7.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.25 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.37 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959341 | AF2-225 C | 50/50 | 7.12 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959342 | AF2-225 E | 50/50 | 9.83 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.38 MW | 1.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 2.47 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.52 MW | 2.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 11.79 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.86 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 1.17 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.11 MW | 5.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.11 MW | 2.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.54 MW | 5.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.58 MW | 3.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.29 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 4.86 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293777 | CAYUG;1U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293778 | CAYUG;2U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 39.32 MW | 39.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 19.65 MW | 19.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 24.56 MW | 24.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.91 MW | 3.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 23.69 MW | 23.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.21 MW | 6.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930761 | AB1-122 CT1 | Adder | 39.4 MW | 33.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 7.94 MW | 6.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.04 MW | 13.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | 50/50 | 9.49 MW | 9.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 6.77 MW | 6.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 31.68 MW | 31.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946151 | AF1-280 C O1 | Adder | 9.62 MW | 8.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946152 | AF1-280 E O1 | Adder | 4.42 MW | 3.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 13.76 MW | 11.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 4.33 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957381 | AF2-032 C | 50/50 | 2.33 MW | 2.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.58 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.24 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 1.15 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 5.38 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 10.49 MW | 8.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 3.19 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 279.8 MW | 279.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.99 MW | 13.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.84 MW | 31.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 18.15 MW | 18.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 40.39 MW | 40.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.21 MW | 32.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 9.11 MW | 9.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 5.26 MW | 5.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 28.46 MW | 28.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.27 MW | 14.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 C | External Queue | 33.84 MW | 33.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954821 | J955 | External Queue | 112.27 MW | 112.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 16.19 MW | 16.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956451 | J1139 | External Queue | 20.56 MW | 20.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.99 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990071 | J1204 | External Queue | 65.14 MW | 65.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 107.73 MW | 107.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990672 | J1360 E | External Queue | 35.45 MW | 35.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991196 | J1626 | External Queue | 27.49 MW | 27.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991266 | J1714 | External Queue | 18.33 MW | 18.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 C | External Queue | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991262 | J1713 E | External Queue | 16.55 MW | 16.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.68 MW | 2.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.49 MW | 16.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.32 MW | 68.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 74.8 MW | 74.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.26 MW | 13.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.26 MW | 15.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.99 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.32 MW | 8.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961651 | AG1-005 C O1 | Adder | 12.53 MW | 10.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961652 | AG1-005 E O1 | Adder | 8.35 MW | 7.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962721 | AG1-121 C O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962722 | AG1-121 E O1 | Adder | 20.08 MW | 17.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963831 | AG1-236 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963832 | AG1-236 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964581 | AG1-321 C O1 | Adder | 11.86 MW | 10.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964582 | AG1-321 E O1 | Adder | 6.91 MW | 5.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966821 | AG1-553 C O1 | Adder | 19.16 MW | 16.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965091 | AG1-374 C | 50/50 | 21.61 MW | 21.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965092 | AG1-374 E | 50/50 | 14.4 MW | 14.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965331 | AG1-398 | 50/50 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965341 | AG1-399 C | 50/50 | 7.08 MW | 7.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965342 | AG1-399 E | 50/50 | 33.15 MW | 33.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965351 | AG1-400 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965371 | AG1-402 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965391 | AG1-404 | 50/50 | 13.41 MW | 13.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965671 | AG1-435 C O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965672 | AG1-435 E O1 | Adder | 13.68 MW | 11.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965911 | AG1-460 C | 50/50 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965912 | AG1-460 E | 50/50 | 3.0 MW | 3.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965931 | AG1-462 C O1 | Adder | 12.4 MW | 10.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965932 | AG1-462 E O1 | Adder | 8.27 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290261 | S-027 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290265 | S-028 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 295111 | SUBLETTE E | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 919581 | AA2-030 C | Adder | 11.63 MW | 9.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925771 | AC1-053 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925772 | AC1-053 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926821 | AC1-168 C O1 | Adder | 0.81 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926822 | AC1-168 E O1 | Adder | 5.42 MW | 4.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 927202 | AC1-214 E O1 | Adder | 5.04 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934051 | AD1-031 C O1 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934052 | AD1-031 E O1 | Adder | 3.62 MW | 3.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 935141 | AD1-148 | 50/50 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936511 | AD2-066 C O1 | Adder | 4.85 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936512 | AD2-066 E O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936771 | AD2-100 C | 50/50 | 21.54 MW | 21.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936772 | AD2-100 E | 50/50 | 14.36 MW | 14.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936971 | AD2-131 C | 50/50 | 1.42 MW | 1.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936972 | AD2-131 E | 50/50 | 7.13 MW | 7.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937311 | AD2-172 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937312 | AD2-172 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942111 | AE2-223 C | 50/50 | 2.18 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942112 | AE2-223 E | 50/50 | 14.59 MW | 14.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942481 | AE2-261 C | 50/50 | 29.87 MW | 29.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942482 | AE2-261 E | 50/50 | 19.91 MW | 19.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945871 | AF1-252 O1 | 50/50 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945881 | AF1-253 | 50/50 | 7.95 MW | 7.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946542 | AF1-318 E O1 | Adder | 20.64 MW | 17.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958911 | AF2-182 C | Adder | 13.04 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958912 | AF2-182 E | Adder | 8.69 MW | 7.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958921 | AF2-183 C | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958922 | AF2-183 E | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959101 | AF2-201 C O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959102 | AF2-201 E O1 | Adder | 10.24 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959341 | AF2-225 C | 50/50 | 7.04 MW | 7.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959342 | AF2-225 E | 50/50 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959611 | AF2-252 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959612 | AF2-252 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960141 | AF2-305 | 50/50 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960261 | AF2-317 | 50/50 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960611 | AF2-352 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960612 | AF2-352 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961011 | AF2-392 C O1 | Adder | 2.59 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961012 | AF2-392 E O1 | Adder | 12.14 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961021 | AF2-393 O1 | Adder | 4.42 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961031 | AF2-394 O1 | Adder | 2.95 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274650 | KINCAID ;1U | 50/50 | 15.61 MW | 15.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274651 | KINCAID ;2U | 50/50 | 15.6 MW | 15.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274853 | TWINGROVE;U1 | 50/50 | 0.71 MW | 0.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274854 | TWINGROVE;U2 | 50/50 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274859 | EASYR;U1 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274860 | EASYR;U2 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274880 | RADFORD R;1U | 50/50 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276615 | W2-048 GEN | 50/50 | 7.85 MW | 7.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276621 | X2-022 GEN | 50/50 | 28.17 MW | 28.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293516 | O-009 E1 | Adder | 6.27 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293517 | O-009 E2 | Adder | 3.18 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293518 | O-009 E3 | Adder | 3.51 MW | 2.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293715 | O-029 E | Adder | 6.7 MW | 5.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293716 | O-029 E | Adder | 3.67 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293717 | O-029 E | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293771 | O-035 E | Adder | 4.94 MW | 4.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293777 | CAYUG;1U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293778 | CAYUG;2U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293798 | W4-005 E | 50/50 | 38.12 MW | 38.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294401 | BSHIL;1U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294410 | BSHIL;2U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294763 | P-046 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 916211 | Z1-072 E | Adder | 3.74 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 917502 | Z2-087 E | 50/50 | 19.45 MW | 19.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924042 | AB2-047 E O1 | 50/50 | 24.32 MW | 24.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924261 | AB2-070 C O1 | 50/50 | 3.79 MW | 3.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924262 | AB2-070 E O1 | 50/50 | 22.98 MW | 22.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925582 | AC1-033 E | Adder | 7.32 MW | 6.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 930761 | AB1-122 CT1 | Adder | 41.0 MW | 34.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938861 | AE1-114 C O1 | Adder | 2.41 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938862 | AE1-114 E O1 | Adder | 8.22 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939401 | AE1-172 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939402 | AE1-172 E O1 | Adder | 16.51 MW | 14.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939741 | AE1-205 C O1 | 50/50 | 9.39 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939742 | AE1-205 E O1 | 50/50 | 12.97 MW | 12.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940501 | AE2-035 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940502 | AE2-035 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941731 | AE2-173 O1 | 50/50 | 5.59 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944221 | AF1-090 C O1 | 50/50 | 6.48 MW | 6.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944222 | AF1-090 E O1 | 50/50 | 30.33 MW | 30.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946151 | AF1-280 C O1 | Adder | 9.92 MW | 8.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946152 | AF1-280 E O1 | Adder | 4.56 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946162 | AF1-281 E O1 | Adder | 1.23 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946322 | AF1-296 E O1 | Adder | 13.97 MW | 11.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946501 | AF1-314 C | Adder | 2.58 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946502 | AF1-314 E | Adder | 12.12 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946541 | AF1-318 C O1 | Adder | 4.41 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957381 | AF2-032 C | 50/50 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957382 | AF2-032 E | 50/50 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957762 | AF2-070 E | Adder | 1.26 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958341 | AF2-128 C O1 | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958342 | AF2-128 E O1 | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990901 | L-005 E | Adder | 10.63 MW | 9.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934101 | AD2-000 1 | Adder | 3.32 MW | 2.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944202 | AF1-088 FTWR | 50/50 | 309.06 MW | 309.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942602 | AE2-276 BAT | 50/50 | 15.45 MW | 15.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941343 | AE2-130 BAT | 50/50 | 34.8 MW | 34.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953401 | J811 | External Queue | 17.16 MW | 17.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953641 | J813 | External Queue | 37.62 MW | 37.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953651 | J815 | External Queue | 30.66 MW | 30.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953881 | J848 C | External Queue | 4.99 MW | 4.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953882 | J848 E | External Queue | 27.02 MW | 27.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954411 | J912 | External Queue | 13.54 MW | 13.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954681 | J949 C | External Queue | 31.51 MW | 31.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954821 | J955 | External Queue | 84.37 MW | 84.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 956451 | J1139 | External Queue | 19.36 MW | 19.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990056 | J1201 | External Queue | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990071 | J1204 | External Queue | 61.78 MW | 61.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990271 | J1263 | External Queue | 101.39 MW | 101.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990672 | J1360 E | External Queue | 33.75 MW | 33.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991196 | J1626 | External Queue | 26.01 MW | 26.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991266 | J1714 | External Queue | 17.34 MW | 17.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991261 | J1713 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991262 | J1713 E | External Queue | 15.68 MW | 15.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.8 MW | 3.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.57 MW | 13.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.43 MW | 71.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.74 MW | 67.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.36 MW | 12.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.6 MW | 1.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.01 MW | 15.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.1 MW | 5.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.1 MW | 2.1 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 961651 | AG1-005 C O1 | 50/50 | 32.19 MW | 32.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 961652 | AG1-005 E O1 | 50/50 | 21.46 MW | 21.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 962721 | AG1-121 C O1 | 50/50 | 5.3 MW | 5.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 962722 | AG1-121 E O1 | 50/50 | 24.82 MW | 24.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 965671 | AG1-435 C O1 | Adder | 3.05 MW | 2.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 965672 | AG1-435 E O1 | Adder | 14.28 MW | 12.14 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 926821 | AC1-168 C O1 | 50/50 | 1.31 MW | 1.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 926822 | AC1-168 E O1 | 50/50 | 8.78 MW | 8.78 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 927202 | AC1-214 E O1 | 50/50 | 12.96 MW | 12.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 936511 | AD2-066 C O1 | 50/50 | 44.55 MW | 44.55 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 936512 | AD2-066 E O1 | 50/50 | 29.7 MW | 29.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 946542 | AF1-318 E O1 | 50/50 | 53.04 MW | 53.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 293771 | O-035 E | 50/50 | 12.7 MW | 12.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 294401 | BSHIL;1U E | Adder | 4.89 MW | 4.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 294410 | BSHIL;2U E | Adder | 4.89 MW | 4.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 916211 | Z1-072 E | 50/50 | 9.61 MW | 9.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 946541 | AF1-318 C O1 | 50/50 | 11.33 MW | 11.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957761 | AF2-070 C | 50/50 | 0.67 MW | 0.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 958342 | AF2-128 E O1 | 50/50 | 14.06 MW | 14.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 990901 | L-005 E | Adder | 6.61 MW | 5.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 953201 | J715 C | External Queue | 3.32 MW | 3.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 953202 | J715 E | External Queue | 17.95 MW | 17.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 990051 | J1200 | External Queue | 3.5 MW | 3.5 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | 991302 | J1755 E | External Queue | 13.93 MW | 13.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.69 MW | 1.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.69 MW | 2.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L15508_ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 961651 | AG1-005 C O1 | 50/50 | 32.15 MW | 32.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 961652 | AG1-005 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 962721 | AG1-121 C O1 | 50/50 | 5.27 MW | 5.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 962722 | AG1-121 E O1 | 50/50 | 24.64 MW | 24.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 965671 | AG1-435 C O1 | Adder | 3.02 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 965672 | AG1-435 E O1 | Adder | 14.13 MW | 12.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 926821 | AC1-168 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 926822 | AC1-168 E O1 | 50/50 | 8.76 MW | 8.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 927202 | AC1-214 E O1 | 50/50 | 12.95 MW | 12.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 936511 | AD2-066 C O1 | 50/50 | 44.54 MW | 44.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 936512 | AD2-066 E O1 | 50/50 | 29.69 MW | 29.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 946542 | AF1-318 E O1 | 50/50 | 52.97 MW | 52.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 293771 | O-035 E | 50/50 | 12.69 MW | 12.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 294401 | BSHIL;1U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 294410 | BSHIL;2U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 916211 | Z1-072 E | 50/50 | 9.6 MW | 9.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 946541 | AF1-318 C O1 | 50/50 | 11.31 MW | 11.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957761 | AF2-070 C | 50/50 | 0.66 MW | 0.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 958342 | AF2-128 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 990901 | L-005 E | Adder | 6.49 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 953201 | J715 C | External Queue | 3.31 MW | 3.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 953202 | J715 E | External Queue | 17.92 MW | 17.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 990051 | J1200 | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | 991302 | J1755 E | External Queue | 13.9 MW | 13.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.71 MW | 1.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.46 MW | 0.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P4_074-38-L7413__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P4_001-38-TR81___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 936511 | AD2-066 C O1 | 50/50 | 44.34 MW | 44.34 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 936512 | AD2-066 E O1 | 50/50 | 29.56 MW | 29.56 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961651 | AG1-005 C O1 | Adder | 12.46 MW | 10.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961652 | AG1-005 E O1 | Adder | 8.31 MW | 7.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962721 | AG1-121 C O1 | Adder | 4.27 MW | 3.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962722 | AG1-121 E O1 | Adder | 19.98 MW | 16.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963831 | AG1-236 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963832 | AG1-236 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964581 | AG1-321 C O1 | Adder | 11.85 MW | 10.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964582 | AG1-321 E O1 | Adder | 6.9 MW | 5.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966821 | AG1-553 C O1 | Adder | 19.15 MW | 16.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965061 | AG1-371 | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965081 | AG1-373 | Adder | 0.66 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965091 | AG1-374 C | 50/50 | 21.84 MW | 21.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965092 | AG1-374 E | 50/50 | 14.56 MW | 14.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965331 | AG1-398 | 50/50 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965341 | AG1-399 C | 50/50 | 7.19 MW | 7.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965342 | AG1-399 E | 50/50 | 33.66 MW | 33.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965351 | AG1-400 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965371 | AG1-402 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965391 | AG1-404 | 50/50 | 13.62 MW | 13.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965661 | AG1-434 C O1 | Adder | 2.4 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965662 | AG1-434 E O1 | Adder | 11.22 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965671 | AG1-435 C O1 | Adder | 2.91 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965672 | AG1-435 E O1 | Adder | 13.62 MW | 11.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965911 | AG1-460 C | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965912 | AG1-460 E | 50/50 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965931 | AG1-462 C O1 | Adder | 12.39 MW | 10.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965932 | AG1-462 E O1 | Adder | 8.26 MW | 7.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 272364 | ESS H440N ;R | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290051 | GSG-6; E | Adder | 5.74 MW | 4.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290261 | S-027 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290265 | S-028 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295109 | WESTBROOK E | Adder | 3.07 MW | 2.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295111 | SUBLETTE E | Adder | 1.64 MW | 1.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 919581 | AA2-030 C | Adder | 11.53 MW | 9.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925771 | AC1-053 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925772 | AC1-053 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 927202 | AC1-214 E O1 | Adder | 5.02 MW | 4.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933911 | AD1-013 C | Adder | 1.01 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933912 | AD1-013 E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934051 | AD1-031 C O1 | Adder | 2.21 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934052 | AD1-031 E O1 | Adder | 3.61 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 935141 | AD1-148 | 50/50 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936771 | AD2-100 C | 50/50 | 22.11 MW | 22.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936772 | AD2-100 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936971 | AD2-131 C | 50/50 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936972 | AD2-131 E | 50/50 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937001 | AD2-134 C | Adder | 1.39 MW | 1.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937002 | AD2-134 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937311 | AD2-172 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937312 | AD2-172 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942111 | AE2-223 C | 50/50 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942112 | AE2-223 E | 50/50 | 14.69 MW | 14.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942481 | AE2-261 C | 50/50 | 30.63 MW | 30.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942482 | AE2-261 E | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945871 | AF1-252 O1 | 50/50 | 11.82 MW | 11.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945881 | AF1-253 | 50/50 | 8.19 MW | 8.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946542 | AF1-318 E O1 | Adder | 20.54 MW | 17.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958911 | AF2-182 C | Adder | 12.9 MW | 10.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958912 | AF2-182 E | Adder | 8.6 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958922 | AF2-183 E | Adder | 3.44 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959081 | AF2-199 C | Adder | 3.98 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959082 | AF2-199 E | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959091 | AF2-200 C O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959092 | AF2-200 E O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959101 | AF2-201 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959102 | AF2-201 E O1 | Adder | 10.09 MW | 8.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959341 | AF2-225 C | 50/50 | 7.09 MW | 7.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959342 | AF2-225 E | 50/50 | 9.79 MW | 9.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959611 | AF2-252 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959612 | AF2-252 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960141 | AF2-305 | 50/50 | 1.37 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960261 | AF2-317 | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960611 | AF2-352 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960612 | AF2-352 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961012 | AF2-392 E O1 | Adder | 12.02 MW | 10.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274650 | KINCAID ;1U | 50/50 | 16.0 MW | 16.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274651 | KINCAID ;2U | 50/50 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274859 | EASYR;U1 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274860 | EASYR;U2 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274880 | RADFORD R;1U | 50/50 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276615 | W2-048 GEN | 50/50 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276621 | X2-022 GEN | 50/50 | 28.76 MW | 28.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293516 | O-009 E1 | Adder | 6.22 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293517 | O-009 E2 | Adder | 3.16 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293518 | O-009 E3 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293715 | O-029 E | Adder | 6.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293716 | O-029 E | Adder | 3.65 MW | 3.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293717 | O-029 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293771 | O-035 E | Adder | 4.92 MW | 4.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293777 | CAYUG;1U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293778 | CAYUG;2U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293798 | W4-005 E | 50/50 | 38.82 MW | 38.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294401 | BSHIL;1U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294410 | BSHIL;2U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294763 | P-046 E | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916211 | Z1-072 E | Adder | 3.73 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916221 | Z1-073 E | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 917502 | Z2-087 E | 50/50 | 19.59 MW | 19.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924042 | AB2-047 E O1 | 50/50 | 24.48 MW | 24.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924261 | AB2-070 C O1 | 50/50 | 3.86 MW | 3.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924262 | AB2-070 E O1 | 50/50 | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925582 | AC1-033 E | Adder | 7.3 MW | 6.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930482 | AB1-089 CT | Adder | 20.14 MW | 17.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930483 | AB1-089 ST | Adder | 16.01 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930761 | AB1-122 CT1 | Adder | 40.35 MW | 34.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938861 | AE1-114 C O1 | Adder | 2.38 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938862 | AE1-114 E O1 | Adder | 8.12 MW | 6.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939401 | AE1-172 C O1 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939402 | AE1-172 E O1 | Adder | 16.31 MW | 13.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939741 | AE1-205 C O1 | 50/50 | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939742 | AE1-205 E O1 | 50/50 | 13.06 MW | 13.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940501 | AE2-035 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940502 | AE2-035 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941731 | AE2-173 O1 | 50/50 | 5.63 MW | 5.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944221 | AF1-090 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944222 | AF1-090 E O1 | 50/50 | 31.22 MW | 31.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946151 | AF1-280 C O1 | Adder | 9.82 MW | 8.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946152 | AF1-280 E O1 | Adder | 4.52 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946322 | AF1-296 E O1 | Adder | 13.95 MW | 11.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946501 | AF1-314 C | Adder | 2.54 MW | 2.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946502 | AF1-314 E | Adder | 11.95 MW | 10.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946541 | AF1-318 C O1 | Adder | 4.39 MW | 3.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946671 | AF1-331 | Adder | 1.31 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957381 | AF2-032 C | 50/50 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957382 | AF2-032 E | 50/50 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957471 | AF2-041 C | Adder | 11.94 MW | 10.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957472 | AF2-041 E | Adder | 5.97 MW | 5.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957762 | AF2-070 E | Adder | 1.25 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958341 | AF2-128 C O1 | Adder | 1.16 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958342 | AF2-128 E O1 | Adder | 5.44 MW | 4.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990901 | L-005 E | Adder | 10.6 MW | 9.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934101 | AD2-000 1 | Adder | 3.26 MW | 2.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944202 | AF1-088 FTWR | 50/50 | 260.6 MW | 260.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942602 | AE2-276 BAT | 50/50 | 13.03 MW | 13.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941343 | AE2-130 BAT | 50/50 | 29.76 MW | 29.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953401 | J811 | External Queue | 18.24 MW | 18.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953641 | J813 | External Queue | 40.35 MW | 40.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953881 | J848 C | External Queue | 5.27 MW | 5.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953882 | J848 E | External Queue | 28.49 MW | 28.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954411 | J912 | External Queue | 14.3 MW | 14.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954681 | J949 C | External Queue | 32.68 MW | 32.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 956451 | J1139 | External Queue | 20.06 MW | 20.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990056 | J1201 | External Queue | 7.03 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990071 | J1204 | External Queue | 65.85 MW | 65.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990271 | J1263 | External Queue | 106.84 MW | 106.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991196 | J1626 | External Queue | 27.64 MW | 27.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991266 | J1714 | External Queue | 18.43 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991261 | J1713 C | External Queue | 3.03 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991262 | J1713 E | External Queue | 3.46 MW | 3.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.0 MW | 15.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 69.74 MW | 69.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.94 MW | 68.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.87 MW | 12.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.25 MW | 15.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.06 MW | 2.06 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 961651 | AG1-005 C O1 | 50/50 | 32.15 MW | 32.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 961652 | AG1-005 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 962721 | AG1-121 C O1 | 50/50 | 5.27 MW | 5.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 962722 | AG1-121 E O1 | 50/50 | 24.64 MW | 24.64 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 965671 | AG1-435 C O1 | Adder | 3.02 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 965672 | AG1-435 E O1 | Adder | 14.13 MW | 12.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 926821 | AC1-168 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 926822 | AC1-168 E O1 | 50/50 | 8.76 MW | 8.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 927201 | AC1-214 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 927202 | AC1-214 E O1 | 50/50 | 12.95 MW | 12.95 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 936511 | AD2-066 C O1 | 50/50 | 44.54 MW | 44.54 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 936512 | AD2-066 E O1 | 50/50 | 29.69 MW | 29.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 946542 | AF1-318 E O1 | 50/50 | 52.97 MW | 52.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 274849 | CRESCENT ;1U | 50/50 | 0.36 MW | 0.36 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 274851 | PROVIDENC;RU | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 293771 | O-035 E | 50/50 | 12.69 MW | 12.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 294401 | BSHIL;1U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 294410 | BSHIL;2U E | Adder | 4.8 MW | 4.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 916211 | Z1-072 E | 50/50 | 9.6 MW | 9.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 946541 | AF1-318 C O1 | 50/50 | 11.31 MW | 11.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957751 | AF2-069 C | 50/50 | 0.47 MW | 0.47 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957752 | AF2-069 E | 50/50 | 1.52 MW | 1.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957761 | AF2-070 C | 50/50 | 0.66 MW | 0.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 957762 | AF2-070 E | 50/50 | 3.23 MW | 3.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 958341 | AF2-128 C O1 | 50/50 | 3.0 MW | 3.0 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 958342 | AF2-128 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 990901 | L-005 E | Adder | 6.49 MW | 5.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 953201 | J715 C | External Queue | 3.31 MW | 3.31 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 953202 | J715 E | External Queue | 17.92 MW | 17.92 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 990051 | J1200 | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 991301 | J1755 C | External Queue | 2.57 MW | 2.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | 991302 | J1755 E | External Queue | 13.9 MW | 13.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.1 MW | 1.1 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.71 MW | 1.71 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.68 MW | 2.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.46 MW | 0.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.8 MW | 0.8 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P2-2_074_KE-138___1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.21 MW | 0.21 MW |
| Details for 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961651 | AG1-005 C O1 | 50/50 | 29.94 MW | 29.94 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 961652 | AG1-005 E O1 | 50/50 | 19.96 MW | 19.96 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962721 | AG1-121 C O1 | 50/50 | 6.19 MW | 6.19 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 962722 | AG1-121 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965671 | AG1-435 C O1 | 50/50 | 3.69 MW | 3.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 965672 | AG1-435 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926821 | AC1-168 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 926822 | AC1-168 E O1 | 50/50 | 10.9 MW | 10.9 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927201 | AC1-214 C O1 | 50/50 | 0.41 MW | 0.41 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 927202 | AC1-214 E O1 | 50/50 | 7.57 MW | 7.57 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934051 | AD1-031 C O1 | Adder | 2.15 MW | 1.82 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 934052 | AD1-031 E O1 | Adder | 3.5 MW | 2.98 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946542 | AF1-318 E O1 | 50/50 | 46.2 MW | 46.2 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274847 | GR RIDGE ;BU | 50/50 | 0.8 MW | 0.8 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274849 | CRESCENT ;1U | 50/50 | 0.21 MW | 0.21 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274851 | PROVIDENC;RU | 50/50 | 0.22 MW | 0.22 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 274871 | GR RIDGE ;2U | 50/50 | 0.3 MW | 0.3 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 276173 | Z2-081 | 50/50 | 0.38 MW | 0.38 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293061 | N-015 E | 50/50 | 20.58 MW | 20.58 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 293771 | O-035 E | 50/50 | 7.42 MW | 7.42 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294392 | P-010 E | 50/50 | 26.13 MW | 26.13 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294401 | BSHIL;1U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 294410 | BSHIL;2U E | Adder | 6.5 MW | 5.52 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 916211 | Z1-072 E | 50/50 | 5.61 MW | 5.61 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925581 | AC1-033 C | Adder | 1.06 MW | 0.91 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 925582 | AC1-033 E | Adder | 7.13 MW | 6.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 946541 | AF1-318 C O1 | 50/50 | 9.87 MW | 9.87 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957751 | AF2-069 C | 50/50 | 0.28 MW | 0.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957752 | AF2-069 E | 50/50 | 0.89 MW | 0.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957761 | AF2-070 C | 50/50 | 0.39 MW | 0.39 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 957762 | AF2-070 E | 50/50 | 1.89 MW | 1.89 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958341 | AF2-128 C O1 | 50/50 | 2.79 MW | 2.79 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 958342 | AF2-128 E O1 | 50/50 | 13.07 MW | 13.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990901 | L-005 E | Adder | 8.78 MW | 7.46 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953201 | J715 C | External Queue | 3.28 MW | 3.28 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 953202 | J715 E | External Queue | 17.74 MW | 17.74 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 990051 | J1200 | External Queue | 3.77 MW | 3.77 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991301 | J1755 C | External Queue | 2.69 MW | 2.69 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | 991302 | J1755 E | External Queue | 14.54 MW | 14.54 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.25 MW | 1.25 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.17 MW | 3.17 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.29 MW | 3.29 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.59 MW | 0.59 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.16 MW | 1.16 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.36 MW | 0.36 MW |
| 4CORBIN-AD2-066 TAP 138.0 kV Ckt 1 line l/o COMED_P2-2_001_LA-138B__1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.16 MW | 0.16 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| POWERTON ;-4TOWERLINE 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 54.42 MW | 54.42 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 36.28 MW | 36.28 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 89.68 MW | 89.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 19.16 MW | 19.16 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 5.08 MW | 5.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 23.77 MW | 23.77 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 54.42 MW | 54.42 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 36.28 MW | 36.28 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962012 | AG1-044 E | Adder | 0.03 MW | 0.03 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 18.8 MW | 18.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 87.98 MW | 87.98 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 12.76 MW | 12.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 59.72 MW | 59.72 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 21.92 MW | 21.92 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 15.61 MW | 15.61 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 89.68 MW | 89.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.35 MW | 1.35 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.62 MW | 0.62 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.64 MW | 0.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 1.24 MW | 1.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276156 | O-029 C | 50/50 | 0.22 MW | 0.22 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276157 | O-029 C | 50/50 | 0.24 MW | 0.24 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 276158 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293513 | O-009 C1 | 50/50 | 0.41 MW | 0.41 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293514 | O-009 C2 | 50/50 | 0.21 MW | 0.21 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293515 | O-009 C3 | 50/50 | 0.23 MW | 0.23 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | 50/50 | 9.64 MW | 9.64 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | 50/50 | 4.89 MW | 4.89 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | 50/50 | 5.39 MW | 5.39 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | 50/50 | 10.3 MW | 10.3 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | 50/50 | 5.65 MW | 5.65 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | 50/50 | 5.19 MW | 5.19 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 21.48 MW | 21.48 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 29.04 MW | 29.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 16.26 MW | 16.26 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 4.76 MW | 4.76 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 31.84 MW | 31.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 19.16 MW | 19.16 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.8 MW | 0.8 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 2.58 MW | 2.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 1.12 MW | 1.12 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 5.46 MW | 5.46 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 5.08 MW | 5.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 23.77 MW | 23.77 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 37.84 MW | 37.84 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.25 MW | 0.25 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.18 MW | 0.18 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.68 MW | 0.68 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.58 MW | 0.58 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.6 MW | 0.6 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| KEWANEE ;13-4KEWANEE N 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 150.0 MW | 150.0 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 100.0 MW | 100.0 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 13.99 MW | 13.99 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 65.51 MW | 65.51 MW |
| Details for AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 150.0 MW | 150.0 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 100.0 MW | 100.0 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 13.99 MW | 13.99 MW |
| AF2-128 TAP-AF1-318 TAP 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 65.51 MW | 65.51 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | 50/50 | 395.01 MW | 395.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934101 | AD2-000 1 | 50/50 | 31.94 MW | 31.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | Adder | -179.99 MW | -152.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | 50/50 | 395.13 MW | 395.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934101 | AD2-000 1 | 50/50 | 31.95 MW | 31.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965911 | AG1-460 C | Adder | 0.84 MW | 0.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965912 | AG1-460 E | Adder | 1.26 MW | 1.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942481 | AE2-261 C | Adder | 12.56 MW | 10.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942482 | AE2-261 E | Adder | 8.38 MW | 7.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | Adder | -179.87 MW | -152.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957381 | AF2-032 C | Adder | 0.96 MW | 0.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957382 | AF2-032 E | Adder | 0.45 MW | 0.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951031 | J344 C | External Queue | 2.36 MW | 2.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951032 | J344 E | External Queue | 7.09 MW | 7.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951841 | J555 C | External Queue | 1.61 MW | 1.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951842 | J555 E | External Queue | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954721 | J750 C | External Queue | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954722 | J750 E | External Queue | 9.84 MW | 9.84 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991191 | J1610 | External Queue | 7.16 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961651 | AG1-005 C O1 | 50/50 | 29.23 MW | 29.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 961652 | AG1-005 E O1 | 50/50 | 19.48 MW | 19.48 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962721 | AG1-121 C O1 | 50/50 | 10.17 MW | 10.17 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 962722 | AG1-121 E O1 | 50/50 | 47.57 MW | 47.57 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965671 | AG1-435 C O1 | 50/50 | 6.9 MW | 6.9 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 965672 | AG1-435 E O1 | 50/50 | 32.29 MW | 32.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927201 | AC1-214 C O1 | 50/50 | 0.63 MW | 0.63 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 927202 | AC1-214 E O1 | 50/50 | 11.77 MW | 11.77 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934051 | AD1-031 C O1 | 50/50 | 5.13 MW | 5.13 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 934052 | AD1-031 E O1 | 50/50 | 8.37 MW | 8.37 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946542 | AF1-318 E O1 | 50/50 | 48.16 MW | 48.16 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274848 | CAMPGROVE;RU | 50/50 | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274849 | CRESCENT ;1U | 50/50 | 0.33 MW | 0.33 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274851 | PROVIDENC;RU | 50/50 | 0.34 MW | 0.34 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274877 | BISHOP HL;1U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 274878 | BISHOP HL;2U | 50/50 | 0.67 MW | 0.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293516 | O-009 E1 | Adder | 5.84 MW | 4.96 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293517 | O-009 E2 | Adder | 2.97 MW | 2.52 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293518 | O-009 E3 | Adder | 3.27 MW | 2.78 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293715 | O-029 E | Adder | 6.24 MW | 5.31 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293716 | O-029 E | Adder | 3.42 MW | 2.91 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293717 | O-029 E | Adder | 3.15 MW | 2.67 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 293771 | O-035 E | 50/50 | 11.54 MW | 11.54 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294401 | BSHIL;1U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 294410 | BSHIL;2U E | 50/50 | 15.65 MW | 15.65 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 916211 | Z1-072 E | 50/50 | 8.73 MW | 8.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925581 | AC1-033 C | 50/50 | 2.55 MW | 2.55 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 925582 | AC1-033 E | 50/50 | 17.1 MW | 17.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 946541 | AF1-318 C O1 | 50/50 | 10.29 MW | 10.29 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957751 | AF2-069 C | 50/50 | 0.43 MW | 0.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957752 | AF2-069 E | 50/50 | 1.38 MW | 1.38 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957761 | AF2-070 C | 50/50 | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 957762 | AF2-070 E | 50/50 | 2.93 MW | 2.93 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958341 | AF2-128 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 958342 | AF2-128 E O1 | 50/50 | 12.76 MW | 12.76 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990901 | L-005 E | 50/50 | 39.94 MW | 39.94 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 990051 | J1200 | External Queue | 1.43 MW | 1.43 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991301 | J1755 C | External Queue | 2.88 MW | 2.88 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | 991302 | J1755 E | External Queue | 15.58 MW | 15.58 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.41 MW | 0.41 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.68 MW | 7.68 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.11 MW | 0.11 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.53 MW | 1.53 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.6 MW | 0.6 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| TOULON ; R-POWERTON ; 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L98105_R-S-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 961651 | AG1-005 C O1 | 50/50 | 33.38 MW | 33.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 961652 | AG1-005 E O1 | 50/50 | 22.26 MW | 22.26 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 962721 | AG1-121 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 962722 | AG1-121 E O1 | 50/50 | 26.57 MW | 26.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 965671 | AG1-435 C O1 | Adder | 3.23 MW | 2.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 965672 | AG1-435 E O1 | Adder | 15.13 MW | 12.86 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 926821 | AC1-168 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 926822 | AC1-168 E O1 | 50/50 | 10.67 MW | 10.67 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 927201 | AC1-214 C O1 | 50/50 | 0.72 MW | 0.72 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 927202 | AC1-214 E O1 | 50/50 | 13.44 MW | 13.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 934051 | AD1-031 C O1 | Adder | 1.66 MW | 1.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 934052 | AD1-031 E O1 | Adder | 2.71 MW | 2.3 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 936511 | AD2-066 C O1 | 50/50 | 44.77 MW | 44.77 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 936512 | AD2-066 E O1 | 50/50 | 29.85 MW | 29.85 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 946542 | AF1-318 E O1 | 50/50 | 55.01 MW | 55.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 274849 | CRESCENT ;1U | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 274851 | PROVIDENC;RU | 50/50 | 0.39 MW | 0.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 293771 | O-035 E | 50/50 | 13.18 MW | 13.18 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 294401 | BSHIL;1U E | Adder | 5.03 MW | 4.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 294410 | BSHIL;2U E | Adder | 5.03 MW | 4.28 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 916211 | Z1-072 E | 50/50 | 9.97 MW | 9.97 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 925581 | AC1-033 C | Adder | 0.82 MW | 0.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 925582 | AC1-033 E | Adder | 5.51 MW | 4.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 946541 | AF1-318 C O1 | 50/50 | 11.75 MW | 11.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957751 | AF2-069 C | 50/50 | 0.49 MW | 0.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957752 | AF2-069 E | 50/50 | 1.58 MW | 1.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957761 | AF2-070 C | 50/50 | 0.69 MW | 0.69 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 957762 | AF2-070 E | 50/50 | 3.35 MW | 3.35 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 958341 | AF2-128 C O1 | 50/50 | 3.11 MW | 3.11 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 958342 | AF2-128 E O1 | 50/50 | 14.58 MW | 14.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 990901 | L-005 E | Adder | 6.85 MW | 5.82 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 953201 | J715 C | External Queue | 3.44 MW | 3.44 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 953202 | J715 E | External Queue | 18.58 MW | 18.58 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 990051 | J1200 | External Queue | 3.76 MW | 3.76 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 991301 | J1755 C | External Queue | 2.48 MW | 2.48 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | 991302 | J1755 E | External Queue | 13.42 MW | 13.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.18 MW | 1.18 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.33 MW | 2.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.96 MW | 2.96 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.52 MW | 0.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.94 MW | 0.94 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.32 MW | 0.32 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.19 MW | 0.19 MW |
| Details for AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 33.78 MW | 33.78 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 22.52 MW | 22.52 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 8.21 MW | 8.21 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 38.42 MW | 38.42 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 26.07 MW | 26.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.45 MW | 1.45 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.73 MW | 0.73 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 13.6 MW | 13.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 936511 | AD2-066 C O1 | 50/50 | 44.9 MW | 44.9 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 936512 | AD2-066 E O1 | 50/50 | 29.93 MW | 29.93 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 55.66 MW | 55.66 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.38 MW | 0.38 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.4 MW | 0.4 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 293771 | O-035 E | 50/50 | 13.33 MW | 13.33 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 916211 | Z1-072 E | 50/50 | 10.09 MW | 10.09 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 11.89 MW | 11.89 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957751 | AF2-069 C | 50/50 | 0.49 MW | 0.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957752 | AF2-069 E | 50/50 | 1.6 MW | 1.6 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957761 | AF2-070 C | 50/50 | 0.7 MW | 0.7 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 957762 | AF2-070 E | 50/50 | 3.39 MW | 3.39 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 3.15 MW | 3.15 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 14.75 MW | 14.75 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 953201 | J715 C | External Queue | 3.49 MW | 3.49 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 953202 | J715 E | External Queue | 18.87 MW | 18.87 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 990051 | J1200 | External Queue | 3.83 MW | 3.83 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 991301 | J1755 C | External Queue | 2.27 MW | 2.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | 991302 | J1755 E | External Queue | 12.27 MW | 12.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.04 MW | 0.04 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.02 MW | 1.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.23 MW | 1.23 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.46 MW | 2.46 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.07 MW | 0.07 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.65 MW | 0.65 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| AD2-066 TAP-MAZON ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L6101___-S_+_138-L7413__R-S-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.2 MW | 0.2 MW |
| Details for DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274836 | EQUISTAR ; R | 50/50 | 3.98 MW | 3.98 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 961651 | AG1-005 C O1 | Adder | 9.81 MW | 8.34 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 961652 | AG1-005 E O1 | Adder | 6.54 MW | 5.56 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 965141 | AG1-379 C | Adder | 25.44 MW | 21.62 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 965142 | AG1-379 E | Adder | 11.64 MW | 9.9 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 966091 | AG1-478 C | Adder | 2.25 MW | 1.91 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 966092 | AG1-478 E | Adder | 0.57 MW | 0.48 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 290021 | O50 E | Adder | 29.67 MW | 25.22 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 927091 | AC1-204 GEN1 | 50/50 | 19.15 MW | 19.15 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 927093 | AC1-204 GEN2 | 50/50 | 19.29 MW | 19.29 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 936511 | AD2-066 C O1 | Adder | 10.0 MW | 8.5 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 936512 | AD2-066 E O1 | Adder | 6.67 MW | 5.67 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 937401 | AD2-194 1 | Adder | 12.09 MW | 10.28 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 937411 | AD2-194 2 | 50/50 | 12.18 MW | 12.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 942421 | AE2-255 C O1 | Adder | 4.64 MW | 3.94 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 942422 | AE2-255 E O1 | Adder | 13.91 MW | 11.82 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 946542 | AF1-318 E O1 | Adder | 15.72 MW | 13.37 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274658 | DRESDEN ;2U | 50/50 | 60.82 MW | 60.82 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274728 | ELWOOD EC;5P | 50/50 | 5.18 MW | 5.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274730 | ELWOOD EC;6P | 50/50 | 5.18 MW | 5.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274732 | ELWOOD EC;7P | 50/50 | 5.18 MW | 5.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274734 | ELWOOD EC;8P | 50/50 | 5.18 MW | 5.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 274736 | ELWOOD EC;9P | 50/50 | 5.18 MW | 5.18 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 930761 | AB1-122 CT1 | Adder | 43.98 MW | 37.38 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 930771 | AB1-122 CT2 | 50/50 | 185.17 MW | 185.17 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 938511 | AE1-070 1 | 50/50 | 14.31 MW | 14.31 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 938521 | AE1-070 2 | Adder | 13.0 MW | 11.05 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 938851 | AE1-113 C O1 | Adder | 12.24 MW | 10.4 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 938852 | AE1-113 E O1 | Adder | 43.39 MW | 36.88 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 946541 | AF1-318 C O1 | Adder | 3.36 MW | 2.85 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.78 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 958342 | AF2-128 E O1 | Adder | 4.28 MW | 3.64 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 934101 | AD2-000 1 | Adder | 3.56 MW | 3.02 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 934111 | AD2-000 2 | 50/50 | 14.97 MW | 14.97 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 957403 | AF2-034 BAT | 50/50 | 4.76 MW | 4.76 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 953201 | J715 C | External Queue | 0.99 MW | 0.99 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | 953202 | J715 E | External Queue | 5.36 MW | 5.36 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.09 MW | 0.09 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.24 MW | 0.24 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.13 MW | 0.13 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.52 MW | 1.52 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.15 MW | 7.15 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.39 MW | 0.39 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.05 MW | 0.05 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.25 MW | 1.25 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.94 MW | 2.94 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.53 MW | 2.53 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| DRESDEN ; B-KENDALL ;BU 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L11620_B-S_+_345-L11622_R-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.5 | Replace 4 Dumont switches (3000 A). | $2,400,000 | |
| n5769.3 | Replace 11 jumpers/risers at Dumont substation | $275,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Upgrade transmission conductor and conductor drop.. (MISO - Upgrade #3) | $6,500,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
| n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
| n7925.4 | Replace three 2-2000 AAC 91 Str | $300,000 | |
| n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| n6992 | Re-conductor a portion of the Corbin 138 kV line. | $7,200,000 | |
| (TBD) | MISO review required. | $0 | |
| n8376 | Construct new 345kV from AB1-122 Intercoonection Substation to Ameren (Tazewell) Station. | $306,000,000 | |
| (TBD) | MISO review required. | $0 | |
| n8375 | AB1-122 - Tazewell 345 kV Line Sag Mitigation | $39,900,000 | |
| n7094.1 | Perform sag mitigation on AF1-318 - Crescent 138 kV line | $3,600,000 | |
| n6993 | Kewanee L7413 re-conductor a portion of the line, upgrade a disconnect switch and line trap, upgrade station conductor | $9,100,000 | |
| n5919 | Mitigate Sag on Dresden - Kendall 345 kV Line. | $10,200,000 | |
| n5324 | Re-conductor the line segment - Dresden - AB1-122 345 kV line | $4,000,000 | |
| n5324.1 | Dresden - AB1-122 345 kV line - Re-conductor the line segment and upgrade relay package. | $5,000,000 | |
| n8378 | Kewanee 138 kV - Re-conductor the line segment. | $2,500,000 | |
| (TBD) | MISO review required | $0 | |
| b3677 | Mazon - Lasalle 138 kV line rebuild | $42,060,000 | |
| s2768 | Mazon Circuit Breaker Replacement | $2,500,000 | |
| n8373 | Plano - Install 3rd Auto Transformer at TSS 167 Plano. | $20,000,000 | |
| n6270 | Disconnect Switch Upgrade on Toulon - Powerton 138 kV line | $600,000 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-005 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.