AF2-412 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:08
Mainesburg 115 kV
130.0 MW Capacity / 130.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-412 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the PENELEC zone — Tioga County, Pennsylvania. The installed facilities will have a total capability of 130.0 MW with 130.0 MW of this output being recognized by PJM as Capacity.
Project Information | |
---|---|
Queue Number | AF2-412 |
Project Name | Mainesburg 115 kV |
Developer Name | Juno Power Management LLC |
State | Pennsylvania |
County | Tioga |
Transmission Owner | PENELEC |
MFO | 130.0 MW |
MWE | 130.0 MW |
MWC | 130.0 MW |
Fuel Type | Storage |
Basecase Study Year | 2023 |
Point of Interconnection
AF2-412 will interconnect with the PENELEC transmission system at the Mainesburg 115 kV substation. The interconnection of the project will be accomplished by constructing a new 115 kV breaker position in the existing Mainesburg 115 kV substation. The IC will be responsible for acquiring all easements, properties, and permits that may be required to construct both the new interconnection and the associated facilities.
Summer Peak Analysis
The Queue Project was evaluated as a 130.0 MW (Capacity 130.0 MW) injection in the PENELEC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
PJM |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer
999401 to 200011 ckt 4 |
PJM500_PN_P4-500-001A
CONTINGENCY 'PJM500_PN_P4-500-001A' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE H FROM BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE L FROM BUS 200033 /*KEYS G2 20.0 END |
Breaker | AC | 110.92 % | 113.11 % | 639.0 | B | 722.77 | 16.1 | |
PJM |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer
999401 to 200011 ckt 4 |
PJM500_PN_P4-500-001D
CONTINGENCY 'PJM500_PN_P4-500-001D' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE H FROM BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE L FROM BUS 200032 /*KEYS G1 20.0 END |
Breaker | AC | 110.84 % | 113.03 % | 639.0 | B | 722.26 | 16.1 | |
PJM/PL |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer
208009 to 200074 ckt 3 |
PL_P42_001057
CONTINGENCY 'PL_P42_001057' DISCONNECT BRANCH FROM BUS 208009 TO BUS 200074 CKT 4 /*LACK 230.0 - LACKAW 500.0 DISCONNECT BRANCH FROM BUS 208009 TO BUS 208049 CKT 1 /*LACK 230.0 - PAUP 230.0 DISCONNECT BRANCH FROM BUS 208009 TO BUS 211681 CKT 2 /*LACK 230.0 - LACK 69.0 END |
Breaker | AC | 107.07 % | 108.69 % | 1167.0 | B | 1268.41 | 21.76 | |
PJM/PL |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer
208009 to 200074 ckt 3 |
PL_P42_101231
CONTINGENCY 'PL_P42_101231' DISCONNECT BRANCH FROM BUS 208009 TO BUS 200074 CKT 4 /*LACK 230.0 - LACKAW 500.0 DISCONNECT BRANCH FROM BUS 208009 TO BUS 208049 CKT 1 /*LACK 230.0 - PAUP 230.0 DISCONNECT BRANCH FROM BUS 208009 TO BUS 211681 CKT 2 /*LACK 230.0 - LACK 69.0 END |
Breaker | AC | 107.07 % | 108.69 % | 1167.0 | B | 1268.41 | 21.76 | |
PENELEC |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line
200674 to 200677 ckt 1 |
PN-P1-2-PN-230-013A
CONTINGENCY 'PN-P1-2-PN-230-013A' DISCONNECT BRANCH FROM BUS 200675 TO BUS 200924 CKT 1 /*26E.TWANDA 230.0 - 26CANYON 230.0 DISCONNECT BRANCH FROM BUS 200924 TO BUS 200706 CKT 1 /*26CANYON 230.0 - 26N.MESHPN 230.0 END |
Single | AC | 115.27 % | 121.93 % | 202.0 | B | 246.3 | 17.94 | |
PENELEC |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
200767 to 200795 ckt 1 |
PN_P4-500-002F
CONTINGENCY 'PN_P4-500-002F' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200030 /*CONE G1 22.0 END |
Breaker | AC | 138.54 % | 141.41 % | 917.0 | B | 1296.73 | 27.31 | |
PENELEC |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
200767 to 200795 ckt 1 |
PN_P4-500-002A
CONTINGENCY 'PN_P4-500-002A' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200031 /*CONE G2 22.0 END |
Breaker | AC | 138.54 % | 141.41 % | 917.0 | B | 1296.73 | 27.31 | |
PENELEC |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
200795 to 200810 ckt 1 |
PN_P4-500-002F
CONTINGENCY 'PN_P4-500-002F' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200030 /*CONE G1 22.0 END |
Breaker | AC | 136.03 % | 138.63 % | 917.0 | B | 1271.24 | 27.33 | |
PENELEC |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
200795 to 200810 ckt 1 |
PN_P4-500-002A
CONTINGENCY 'PN_P4-500-002A' DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3 /*CONEM-GH 500.0 - 26CONEMAGH 230.0 DISCONNECT BUS 200031 /*CONE G2 22.0 END |
Breaker | AC | 136.03 % | 138.62 % | 917.0 | B | 1271.15 | 27.33 | |
PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
PN-P2-3-PN-345-003A-B10
CONTINGENCY 'PN-P2-3-PN-345-003A-B10' DISCONNECT BRANCH FROM BUS 200826 TO BUS 200595 CKT 1 /*26HANDSMLK 345.0 - 26WAYNE 345.0 OPEN BRANCH FROM BUS 200598 TO BUS 200595 CKT 2 /*26WAYNE 115.0 - 26WAYNE 345.0 END |
Breaker | AC | 125.1 % | 126.29 % | 666.0 | B | 841.09 | 9.43 | |
PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
PN-P2-3-PN-345-003A-B45
CONTINGENCY 'PN-P2-3-PN-345-003A-B45' DISCONNECT BRANCH FROM BUS 200826 TO BUS 200595 CKT 1 /*26HANDSMLK 345.0 - 26WAYNE 345.0 OPEN BRANCH FROM BUS 200598 TO BUS 200595 CKT 1 /*26WAYNE 115.0 - 26WAYNE 345.0 END |
Breaker | AC | 125.05 % | 126.24 % | 666.0 | B | 840.76 | 9.43 | |
PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
Base Case | Single | AC | 104.13 % | 105.39 % | 546.0 | A | 575.43 | 8.49 | |
PENELEC |
26GLADE-26WARREN 230.0 kV Ckt 1 line
200593 to 200811 ckt 1 |
PN-P1-2-PN-345-003
CONTINGENCY 'PN-P1-2-PN-345-003' DISCONNECT BRANCH FROM BUS 200826 TO BUS 200595 CKT 1 /*26HANDSMLK 345.0 - 26WAYNE 345.0 END |
Single | AC | 102.39 % | 103.56 % | 666.0 | B | 689.71 | 9.42 | |
PENELEC |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer
200769 to 999394 ckt N |
PN-P2-3-PN-230-9E
CONTINGENCY 'PN-P2-3-PN-230-9E' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202641 CKT S /*26HOMER CT 230.0 - 26HOMER CY 345.0 - 26HOMERCITYS 23.0 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200837 CKT 1 /*26HOMER CT 230.0 - 26HOMER C1 20.0 REMOVE MACHINE 1 FROM BUS 200837 /*26HOMER C1 20.0 END |
Breaker | AC | 118.8 % | 123.05 % | 807.0 | B | 993.01 | 34.93 | |
PENELEC |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer
999394 to 200767 ckt N |
PN-P2-3-PN-230-9E
CONTINGENCY 'PN-P2-3-PN-230-9E' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202641 CKT S /*26HOMER CT 230.0 - 26HOMER CY 345.0 - 26HOMERCITYS 23.0 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200837 CKT 1 /*26HOMER CT 230.0 - 26HOMER C1 20.0 REMOVE MACHINE 1 FROM BUS 200837 /*26HOMER C1 20.0 END |
Breaker | AC | 118.72 % | 122.97 % | 807.0 | B | 992.37 | 34.93 | |
PENELEC |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line
200675 to 200924 ckt 1 |
Base Case | Single | AC | 97.84 % | 100.78 % | 506.0 | A | 509.95 | 27.42 | |
PENELEC |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line
200927 to 200820 ckt 1 |
PN-P2-3-PN-230-6G
CONTINGENCY 'PN-P2-3-PN-230-6G' OPEN BUS 200819 /*26ERIE SE 230.0 OPEN BUS 200918 /*26ERIE S TIE 230.0 END |
Breaker | AC | 113.98 % | 116.46 % | 245.0 | B | 285.33 | 7.03 | |
PENELEC |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer
200810 to 999401 ckt 4 |
PJM500_PN_P4-500-001A
CONTINGENCY 'PJM500_PN_P4-500-001A' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE H FROM BUS 200033 /*KEYS G2 20.0 REMOVE MACHINE L FROM BUS 200033 /*KEYS G2 20.0 END |
Breaker | AC | 110.99 % | 113.17 % | 639.0 | B | 723.16 | 16.1 | |
PENELEC |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer
200810 to 999401 ckt 4 |
PJM500_PN_P4-500-001D
CONTINGENCY 'PJM500_PN_P4-500-001D' DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3 /*KEYSTONE 500.0 - 26KEYSTONE 230.0 DISCONNECT BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE H FROM BUS 200032 /*KEYS G1 20.0 REMOVE MACHINE L FROM BUS 200032 /*KEYS G1 20.0 END |
Breaker | AC | 110.94 % | 113.12 % | 639.0 | B | 722.84 | 16.1 | |
PENELEC |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer
999393 to 200767 ckt S |
PN-P2-2-PN-230-001T
CONTINGENCY 'PN-P2-2-PN-230-001T' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1 /*26HOMER CT 230.0 - 26PIERC230 230.0 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 TO BUS 202640 CKT N /*26HOMER CY 345.0 - 26HOMER CT 230.0 - 26HOMERCITYN 23.0 DISCONNECT BUS 200807 /*26PIERC230 230.0 DISCONNECT BUS 200808 /*26PIERC138 138.0 DISCONNECT BUS 200809 /*26SITHE 138.0 REMOVE MACHINE 1 FROM BUS 200809 /*26SITHE 138.0 END |
Bus | AC | 100.5 % | 104.66 % | 824.0 | B | 862.4 | 34.84 | |
PENELEC |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer
999393 to 200767 ckt S |
PN-P2-3-PN-230-9I
CONTINGENCY 'PN-P2-3-PN-230-9I' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202640 CKT N /*26HOMER CT 230.0 - 26HOMER CY 345.0 - 26HOMERCITYN 23.0 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1 /*26HOMER CT 230.0 - 26PIERC230 230.0 DISCONNECT BRANCH FROM BUS 200807 TO BUS 200808 CKT 1 /*26PIERC230 230.0 - 26PIERC138 138.0 DISCONNECT BRANCH FROM BUS 200808 TO BUS 200809 CKT 1 /*26PIERC138 138.0 - 26SITHE 138.0 REMOVE MACHINE 1 FROM BUS 200809 /*26SITHE 138.0 END |
Breaker | AC | 100.5 % | 104.66 % | 824.0 | B | 862.4 | 34.84 | |
PENELEC |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer
200769 to 999393 ckt S |
PN-P2-2-PN-230-001T
CONTINGENCY 'PN-P2-2-PN-230-001T' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1 /*26HOMER CT 230.0 - 26PIERC230 230.0 DISCONNECT BRANCH FROM BUS 200769 TO BUS 200767 TO BUS 202640 CKT N /*26HOMER CY 345.0 - 26HOMER CT 230.0 - 26HOMERCITYN 23.0 DISCONNECT BUS 200807 /*26PIERC230 230.0 DISCONNECT BUS 200808 /*26PIERC138 138.0 DISCONNECT BUS 200809 /*26SITHE 138.0 REMOVE MACHINE 1 FROM BUS 200809 /*26SITHE 138.0 END |
Bus | AC | 100.42 % | 104.57 % | 824.0 | B | 861.66 | 34.84 | |
PENELEC |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer
200769 to 999393 ckt S |
PN-P2-3-PN-230-9I
CONTINGENCY 'PN-P2-3-PN-230-9I' DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202640 CKT N /*26HOMER CT 230.0 - 26HOMER CY 345.0 - 26HOMERCITYN 23.0 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200807 CKT 1 /*26HOMER CT 230.0 - 26PIERC230 230.0 DISCONNECT BRANCH FROM BUS 200807 TO BUS 200808 CKT 1 /*26PIERC230 230.0 - 26PIERC138 138.0 DISCONNECT BRANCH FROM BUS 200808 TO BUS 200809 CKT 1 /*26PIERC138 138.0 - 26SITHE 138.0 REMOVE MACHINE 1 FROM BUS 200809 /*26SITHE 138.0 END |
Breaker | AC | 100.42 % | 104.57 % | 824.0 | B | 861.66 | 34.84 |
Details for STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 936991 | AD2-133 C | Adder | 2.2 MW | 1.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 936992 | AD2-133 E | Adder | 10.06 MW | 8.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942121 | AE2-224 C | 50/50 | 11.11 MW | 11.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942122 | AE2-224 E | 50/50 | 7.41 MW | 7.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942351 | AE2-248 C | Adder | 0.81 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942361 | AE2-249 C | 50/50 | 1.43 MW | 1.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942362 | AE2-249 E | 50/50 | 0.95 MW | 0.95 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942491 | AE2-262 C | Adder | 4.62 MW | 3.93 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942492 | AE2-262 E | Adder | 3.1 MW | 2.64 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942501 | AE2-263 C | Adder | 4.34 MW | 3.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942502 | AE2-263 E | Adder | 2.9 MW | 2.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942811 | AE2-299 C | Adder | 2.62 MW | 2.22 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942812 | AE2-299 E | Adder | 10.46 MW | 8.89 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942961 | AE2-316 C | Adder | 4.24 MW | 3.6 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942962 | AE2-316 E | Adder | 5.02 MW | 4.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943151 | AE2-344 C | Adder | 5.57 MW | 4.74 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943152 | AE2-344 E | Adder | 3.71 MW | 3.16 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943351 | AF1-006 C | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943352 | AF1-006 E | Adder | 0.54 MW | 0.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943711 | AF1-039 C O1 | Adder | 0.97 MW | 0.83 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943712 | AF1-039 E O1 | Adder | 0.65 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944181 | AF1-086 C O1 | Adder | 3.3 MW | 2.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944182 | AF1-086 E O1 | Adder | 14.34 MW | 12.19 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944261 | AF1-094 C | Adder | 1.02 MW | 0.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944262 | AF1-094 E | Adder | 0.68 MW | 0.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944301 | AF1-098 C | Adder | 4.02 MW | 3.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944302 | AF1-098 E | Adder | 2.68 MW | 2.27 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944311 | AF1-099 C | Adder | 7.22 MW | 6.13 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944312 | AF1-099 E | Adder | 4.81 MW | 4.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944321 | AF1-100 C | Adder | 14.93 MW | 12.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944322 | AF1-100 E | Adder | 9.95 MW | 8.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944411 | AF1-106 O1 | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944472 | AF1-112 E | Adder | 0.52 MW | 0.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944751 | AF1-140 C | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944752 | AF1-140 E | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944771 | AF1-142 C | Adder | 11.55 MW | 9.81 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944772 | AF1-142 E | Adder | 7.7 MW | 6.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944781 | AF1-143 C | Adder | 8.44 MW | 7.17 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944782 | AF1-143 E | Adder | 5.63 MW | 4.78 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945021 | AF1-167 C | Adder | 0.76 MW | 0.65 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945022 | AF1-167 E | Adder | 0.51 MW | 0.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945051 | AF1-170 C | Adder | 3.47 MW | 2.95 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945052 | AF1-170 E | Adder | 2.31 MW | 1.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945121 | AF1-177 | Adder | 0.52 MW | 0.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945161 | AF1-181 | Adder | 0.3 MW | 0.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945171 | AF1-182 | Adder | 0.4 MW | 0.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945181 | AF1-183 | Adder | 0.11 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945331 | AF1-198 | Adder | 0.28 MW | 0.24 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945451 | AF1-210 C | Adder | 0.83 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945452 | AF1-210 E | Adder | 0.56 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945751 | AF1-240 C O1 | Adder | 1.67 MW | 1.42 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945752 | AF1-240 E O1 | Adder | 1.11 MW | 0.94 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958471 | AF2-141 | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958731 | AF2-164 C O1 | Adder | 5.48 MW | 4.66 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958732 | AF2-164 E O1 | Adder | 3.66 MW | 3.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958741 | AF2-165 C | Adder | 1.21 MW | 1.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958742 | AF2-165 E | Adder | 0.81 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958751 | AF2-166 C | Adder | 1.26 MW | 1.07 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958752 | AF2-166 E | Adder | 0.84 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959441 | AF2-235 C | Adder | 0.57 MW | 0.49 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959442 | AF2-235 E | Adder | 0.38 MW | 0.33 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959471 | AF2-238 C | Adder | 1.3 MW | 1.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959472 | AF2-238 E | Adder | 0.87 MW | 0.74 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959521 | AF2-243 C | Adder | 0.91 MW | 0.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959522 | AF2-243 E | Adder | 0.61 MW | 0.52 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959802 | AF2-271 E | Adder | 0.44 MW | 0.37 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960022 | AF2-293 E | Adder | 0.1 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960031 | AF2-294 C | Adder | 0.99 MW | 0.84 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960032 | AF2-294 E | Adder | 0.66 MW | 0.56 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960051 | AF2-296 C | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960052 | AF2-296 E | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960451 | AF2-336 C | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960452 | AF2-336 E | Adder | 1.41 MW | 1.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960461 | AF2-337 C | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960462 | AF2-337 E | Adder | 1.41 MW | 1.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961141 | AF2-405 | Adder | 1.06 MW | 0.9 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961151 | AF2-406 | Adder | 7.91 MW | 6.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961211 | AF2-412 | Adder | 16.1 MW | 13.68 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961451 | AF2-436 | Adder | 0.12 MW | 0.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200636 | 26IUP CO-G | 50/50 | 0.51 MW | 0.51 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200794 | 26CONEMAGH | 50/50 | 0.35 MW | 0.35 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200805 | 26COLVER13 | 50/50 | 3.15 MW | 3.15 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200809 | 26SITHE | 50/50 | 1.6 MW | 1.6 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200837 | 26HOMER C1 | 50/50 | 27.61 MW | 27.61 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200838 | 26HOMER C2 | 50/50 | 23.13 MW | 23.13 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200839 | 26HOMER C3 | 50/50 | 24.49 MW | 24.49 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200846 | 26FORWARD | 50/50 | 0.19 MW | 0.19 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200888 | 26HIGHLAND | 50/50 | 0.41 MW | 0.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200894 | 26K02 | Adder | 5.07 MW | 4.31 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200925 | 26R32 | 50/50 | 0.47 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 203999 | P-047 E | Adder | 9.13 MW | 7.76 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 235003 | AC1-025 E | Adder | 0.13 MW | 0.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 916202 | Z1-069 E | Adder | 7.29 MW | 6.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 938951 | AE1-123 | Adder | 1.95 MW | 1.66 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 939291 | AE1-160 C | Adder | 1.21 MW | 1.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 939292 | AE1-160 E | Adder | 0.7 MW | 0.59 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940201 | AE2-001 C | Adder | 1.03 MW | 0.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940202 | AE2-001 E | Adder | 0.69 MW | 0.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940681 | AE2-055 C | Adder | 1.0 MW | 0.85 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940682 | AE2-055 E | Adder | 0.67 MW | 0.57 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940861 | AE2-074 C | Adder | 2.01 MW | 1.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940862 | AE2-074 E | Adder | 2.64 MW | 2.24 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941191 | AE2-113 C | Adder | 7.74 MW | 6.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941192 | AE2-113 E | Adder | 7.27 MW | 6.18 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941231 | AE2-117 C | Adder | 1.28 MW | 1.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941232 | AE2-117 E | Adder | 0.86 MW | 0.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941241 | AE2-118 C | Adder | 1.28 MW | 1.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941242 | AE2-118 E | Adder | 0.86 MW | 0.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941271 | AE2-121 C | Adder | 0.55 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941272 | AE2-121 E | Adder | 0.37 MW | 0.31 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941321 | AE2-126 C | Adder | 1.37 MW | 1.16 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941322 | AE2-126 E | Adder | 0.91 MW | 0.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941331 | AE2-129 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941332 | AE2-129 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941351 | AE2-131 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941352 | AE2-131 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941421 | AE2-139 C | Adder | 5.29 MW | 4.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941422 | AE2-139 E | Adder | 3.53 MW | 3.0 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946071 | AF1-272 C O1 | 50/50 | 15.81 MW | 15.81 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946072 | AF1-272 E O1 | 50/50 | 10.54 MW | 10.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946111 | AF1-276 C | Adder | 8.97 MW | 7.62 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946112 | AF1-276 E | Adder | 4.42 MW | 3.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946121 | AF1-277 C | Adder | 8.97 MW | 7.62 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946122 | AF1-277 E | Adder | 4.42 MW | 3.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946131 | AF1-278 C | Adder | 7.15 MW | 6.08 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946132 | AF1-278 E | Adder | 3.56 MW | 3.02 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946221 | AF1-287 C | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946222 | AF1-287 E | Adder | 0.64 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946382 | AF1-302 E | Adder | 2.47 MW | 2.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946571 | AF1-321 C O1 | 50/50 | 2.25 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946572 | AF1-321 E O1 | 50/50 | 1.5 MW | 1.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957001 | AF2-001 C O1 | 50/50 | 2.25 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957002 | AF2-001 E O1 | 50/50 | 1.5 MW | 1.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957011 | AF2-002 C O1 | 50/50 | 1.12 MW | 1.12 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957012 | AF2-002 E O1 | 50/50 | 0.75 MW | 0.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957161 | AF2-010 C | Adder | 3.93 MW | 3.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957162 | AF2-010 E | Adder | 2.65 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957451 | AF2-039 C | Adder | 0.94 MW | 0.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957452 | AF2-039 E | Adder | 0.62 MW | 0.53 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957561 | AF2-050 C | 50/50 | 5.55 MW | 5.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957562 | AF2-050 E | 50/50 | 3.7 MW | 3.7 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957931 | AF2-087 C | Adder | 0.46 MW | 0.39 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957932 | AF2-087 E | Adder | 0.63 MW | 0.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957941 | AF2-088 C | Adder | 0.45 MW | 0.38 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957942 | AF2-088 E | Adder | 0.3 MW | 0.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957981 | AF2-092 C | Adder | 1.27 MW | 1.08 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957982 | AF2-092 E | Adder | 0.84 MW | 0.72 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958271 | AF2-121 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958272 | AF2-121 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958361 | AF2-130 C | Adder | 1.26 MW | 1.07 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958362 | AF2-130 E | Adder | 0.84 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200833 | 26SEWRDB34 | 50/50 | 16.68 MW | 16.68 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200906 | 26KEYSTN#3 | 50/50 | 0.85 MW | 0.85 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 290086 | Q-036 E | Adder | 5.6 MW | 4.76 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 296332 | R-032 E | 50/50 | 10.78 MW | 10.78 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 917672 | Z2-108 E | Adder | 2.53 MW | 2.15 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944691 | AF1-134 C O1 | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944692 | AF1-134 E O1 | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200864 | K-013 E | 50/50 | 4.29 MW | 4.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200883 | Q-053 E | Adder | 5.0 MW | 4.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 292350 | K-023 | Adder | 3.5 MW | 2.98 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 292542 | L-013 1 | Adder | 4.5 MW | 3.83 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293301 | N-039 E | Adder | 10.49 MW | 8.91 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 923443 | AB1-160 E | Adder | 2.08 MW | 1.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293393 | V3-030E | Adder | 4.56 MW | 3.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293603 | O-018 E | 50/50 | 9.34 MW | 9.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293902 | O-048 E | Adder | 4.05 MW | 3.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 294515 | O38_P22 | Adder | 9.18 MW | 7.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 294903 | P-060 E | Adder | 7.19 MW | 6.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 913142 | Y1-033 E OP1 | Adder | 3.6 MW | 3.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946771 | AF1-217 C O2 | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946772 | AF1-217 E O2 | Adder | 0.64 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959301 | AF2-221 C | 50/50 | 1.17 MW | 1.17 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959302 | AF2-221 E | 50/50 | 1.61 MW | 1.61 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946421 | AF2-000A C | Adder | 5.11 MW | 4.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946422 | AF2-000A E | Adder | 15.33 MW | 13.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 916189 | Z1-066 BAT | Adder | 0.01 MW | 0.01 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.56 MW | 0.56 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.94 MW | 0.94 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.06 MW | 0.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.43 MW | 0.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.38 MW | 1.38 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.1 MW | 0.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.3 MW | 0.3 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.18 MW | 0.18 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.29 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.3 MW | 0.3 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.22 MW | 0.22 MW |
Details for STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 936991 | AD2-133 C | Adder | 2.2 MW | 1.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 936992 | AD2-133 E | Adder | 10.06 MW | 8.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942121 | AE2-224 C | 50/50 | 11.11 MW | 11.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942122 | AE2-224 E | 50/50 | 7.41 MW | 7.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942351 | AE2-248 C | Adder | 0.81 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942361 | AE2-249 C | 50/50 | 1.43 MW | 1.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942362 | AE2-249 E | 50/50 | 0.95 MW | 0.95 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942491 | AE2-262 C | Adder | 4.62 MW | 3.93 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942492 | AE2-262 E | Adder | 3.1 MW | 2.64 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942501 | AE2-263 C | Adder | 4.34 MW | 3.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942502 | AE2-263 E | Adder | 2.9 MW | 2.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942811 | AE2-299 C | Adder | 2.62 MW | 2.22 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942812 | AE2-299 E | Adder | 10.46 MW | 8.89 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942961 | AE2-316 C | Adder | 4.24 MW | 3.6 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942962 | AE2-316 E | Adder | 5.02 MW | 4.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943151 | AE2-344 C | Adder | 5.57 MW | 4.74 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943152 | AE2-344 E | Adder | 3.71 MW | 3.16 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943351 | AF1-006 C | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943352 | AF1-006 E | Adder | 0.54 MW | 0.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943711 | AF1-039 C O1 | Adder | 0.97 MW | 0.83 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943712 | AF1-039 E O1 | Adder | 0.65 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944181 | AF1-086 C O1 | Adder | 3.3 MW | 2.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944182 | AF1-086 E O1 | Adder | 14.34 MW | 12.19 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944261 | AF1-094 C | Adder | 1.02 MW | 0.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944262 | AF1-094 E | Adder | 0.68 MW | 0.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944301 | AF1-098 C | Adder | 4.02 MW | 3.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944302 | AF1-098 E | Adder | 2.68 MW | 2.27 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944311 | AF1-099 C | Adder | 7.22 MW | 6.13 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944312 | AF1-099 E | Adder | 4.81 MW | 4.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944321 | AF1-100 C | Adder | 14.93 MW | 12.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944322 | AF1-100 E | Adder | 9.95 MW | 8.46 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944411 | AF1-106 O1 | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944472 | AF1-112 E | Adder | 0.52 MW | 0.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944751 | AF1-140 C | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944752 | AF1-140 E | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944771 | AF1-142 C | Adder | 11.55 MW | 9.81 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944772 | AF1-142 E | Adder | 7.7 MW | 6.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944781 | AF1-143 C | Adder | 8.44 MW | 7.17 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944782 | AF1-143 E | Adder | 5.63 MW | 4.78 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945021 | AF1-167 C | Adder | 0.76 MW | 0.65 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945022 | AF1-167 E | Adder | 0.51 MW | 0.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945051 | AF1-170 C | Adder | 3.47 MW | 2.95 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945052 | AF1-170 E | Adder | 2.31 MW | 1.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945121 | AF1-177 | Adder | 0.52 MW | 0.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945161 | AF1-181 | Adder | 0.3 MW | 0.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945171 | AF1-182 | Adder | 0.4 MW | 0.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945181 | AF1-183 | Adder | 0.11 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945331 | AF1-198 | Adder | 0.28 MW | 0.24 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945451 | AF1-210 C | Adder | 0.83 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945452 | AF1-210 E | Adder | 0.56 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945751 | AF1-240 C O1 | Adder | 1.67 MW | 1.42 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945752 | AF1-240 E O1 | Adder | 1.11 MW | 0.94 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958471 | AF2-141 | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958731 | AF2-164 C O1 | Adder | 5.48 MW | 4.66 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958732 | AF2-164 E O1 | Adder | 3.66 MW | 3.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958741 | AF2-165 C | Adder | 1.21 MW | 1.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958742 | AF2-165 E | Adder | 0.81 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958751 | AF2-166 C | Adder | 1.26 MW | 1.07 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958752 | AF2-166 E | Adder | 0.84 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959441 | AF2-235 C | Adder | 0.57 MW | 0.49 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959442 | AF2-235 E | Adder | 0.38 MW | 0.33 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959471 | AF2-238 C | Adder | 1.3 MW | 1.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959472 | AF2-238 E | Adder | 0.87 MW | 0.74 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959521 | AF2-243 C | Adder | 0.91 MW | 0.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959522 | AF2-243 E | Adder | 0.61 MW | 0.52 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959802 | AF2-271 E | Adder | 0.44 MW | 0.37 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960022 | AF2-293 E | Adder | 0.1 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960031 | AF2-294 C | Adder | 0.99 MW | 0.84 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960032 | AF2-294 E | Adder | 0.66 MW | 0.56 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960051 | AF2-296 C | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960052 | AF2-296 E | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960451 | AF2-336 C | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960452 | AF2-336 E | Adder | 1.41 MW | 1.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960461 | AF2-337 C | Adder | 2.11 MW | 1.79 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960462 | AF2-337 E | Adder | 1.41 MW | 1.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961141 | AF2-405 | Adder | 1.06 MW | 0.9 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961151 | AF2-406 | Adder | 7.91 MW | 6.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961211 | AF2-412 | Adder | 16.1 MW | 13.68 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961451 | AF2-436 | Adder | 0.12 MW | 0.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200636 | 26IUP CO-G | 50/50 | 0.51 MW | 0.51 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200794 | 26CONEMAGH | 50/50 | 0.35 MW | 0.35 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200805 | 26COLVER13 | 50/50 | 3.15 MW | 3.15 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200809 | 26SITHE | 50/50 | 1.6 MW | 1.6 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200837 | 26HOMER C1 | 50/50 | 27.61 MW | 27.61 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200838 | 26HOMER C2 | 50/50 | 23.13 MW | 23.13 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200839 | 26HOMER C3 | 50/50 | 24.49 MW | 24.49 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200846 | 26FORWARD | 50/50 | 0.19 MW | 0.19 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200888 | 26HIGHLAND | 50/50 | 0.41 MW | 0.41 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200894 | 26K02 | Adder | 5.07 MW | 4.31 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200925 | 26R32 | 50/50 | 0.47 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 203999 | P-047 E | Adder | 9.13 MW | 7.76 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 235003 | AC1-025 E | Adder | 0.13 MW | 0.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 916202 | Z1-069 E | Adder | 7.29 MW | 6.2 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 938951 | AE1-123 | Adder | 1.95 MW | 1.66 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 939291 | AE1-160 C | Adder | 1.21 MW | 1.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 939292 | AE1-160 E | Adder | 0.7 MW | 0.59 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940201 | AE2-001 C | Adder | 1.03 MW | 0.87 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940202 | AE2-001 E | Adder | 0.69 MW | 0.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940681 | AE2-055 C | Adder | 1.0 MW | 0.85 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940682 | AE2-055 E | Adder | 0.67 MW | 0.57 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940861 | AE2-074 C | Adder | 2.01 MW | 1.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940862 | AE2-074 E | Adder | 2.64 MW | 2.24 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941191 | AE2-113 C | Adder | 7.74 MW | 6.58 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941192 | AE2-113 E | Adder | 7.27 MW | 6.18 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941231 | AE2-117 C | Adder | 1.28 MW | 1.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941232 | AE2-117 E | Adder | 0.86 MW | 0.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941241 | AE2-118 C | Adder | 1.28 MW | 1.09 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941242 | AE2-118 E | Adder | 0.86 MW | 0.73 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941271 | AE2-121 C | Adder | 0.55 MW | 0.47 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941272 | AE2-121 E | Adder | 0.37 MW | 0.31 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941321 | AE2-126 C | Adder | 1.37 MW | 1.16 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941322 | AE2-126 E | Adder | 0.91 MW | 0.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941331 | AE2-129 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941332 | AE2-129 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941351 | AE2-131 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941352 | AE2-131 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941421 | AE2-139 C | Adder | 5.29 MW | 4.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941422 | AE2-139 E | Adder | 3.53 MW | 3.0 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946071 | AF1-272 C O1 | 50/50 | 15.81 MW | 15.81 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946072 | AF1-272 E O1 | 50/50 | 10.54 MW | 10.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946111 | AF1-276 C | Adder | 8.97 MW | 7.62 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946112 | AF1-276 E | Adder | 4.42 MW | 3.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946121 | AF1-277 C | Adder | 8.97 MW | 7.62 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946122 | AF1-277 E | Adder | 4.42 MW | 3.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946131 | AF1-278 C | Adder | 7.15 MW | 6.08 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946132 | AF1-278 E | Adder | 3.56 MW | 3.02 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946221 | AF1-287 C | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946222 | AF1-287 E | Adder | 0.64 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946382 | AF1-302 E | Adder | 2.47 MW | 2.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946571 | AF1-321 C O1 | 50/50 | 2.25 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946572 | AF1-321 E O1 | 50/50 | 1.5 MW | 1.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957001 | AF2-001 C O1 | 50/50 | 2.25 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957002 | AF2-001 E O1 | 50/50 | 1.5 MW | 1.5 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957011 | AF2-002 C O1 | 50/50 | 1.12 MW | 1.12 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957012 | AF2-002 E O1 | 50/50 | 0.75 MW | 0.75 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957161 | AF2-010 C | Adder | 3.93 MW | 3.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957162 | AF2-010 E | Adder | 2.65 MW | 2.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957451 | AF2-039 C | Adder | 0.94 MW | 0.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957452 | AF2-039 E | Adder | 0.62 MW | 0.53 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957561 | AF2-050 C | 50/50 | 5.55 MW | 5.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957562 | AF2-050 E | 50/50 | 3.7 MW | 3.7 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957931 | AF2-087 C | Adder | 0.46 MW | 0.39 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957932 | AF2-087 E | Adder | 0.63 MW | 0.54 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957941 | AF2-088 C | Adder | 0.45 MW | 0.38 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957942 | AF2-088 E | Adder | 0.3 MW | 0.26 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957981 | AF2-092 C | Adder | 1.27 MW | 1.08 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957982 | AF2-092 E | Adder | 0.84 MW | 0.72 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958271 | AF2-121 C | Adder | 1.55 MW | 1.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958272 | AF2-121 E | Adder | 1.03 MW | 0.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958361 | AF2-130 C | Adder | 1.26 MW | 1.07 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958362 | AF2-130 E | Adder | 0.84 MW | 0.71 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200833 | 26SEWRDB34 | 50/50 | 16.68 MW | 16.68 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200906 | 26KEYSTN#3 | 50/50 | 0.85 MW | 0.85 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 290086 | Q-036 E | Adder | 5.6 MW | 4.76 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 296332 | R-032 E | 50/50 | 10.78 MW | 10.78 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 917672 | Z2-108 E | Adder | 2.53 MW | 2.15 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944691 | AF1-134 C O1 | Adder | 1.7 MW | 1.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944692 | AF1-134 E O1 | Adder | 1.13 MW | 0.96 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200864 | K-013 E | 50/50 | 4.29 MW | 4.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200883 | Q-053 E | Adder | 5.0 MW | 4.25 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 292350 | K-023 | Adder | 3.5 MW | 2.98 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 292542 | L-013 1 | Adder | 4.5 MW | 3.83 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293301 | N-039 E | Adder | 10.49 MW | 8.91 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 923443 | AB1-160 E | Adder | 2.08 MW | 1.77 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293393 | V3-030E | Adder | 4.56 MW | 3.88 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293603 | O-018 E | 50/50 | 9.34 MW | 9.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293902 | O-048 E | Adder | 4.05 MW | 3.44 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 294515 | O38_P22 | Adder | 9.18 MW | 7.8 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 294903 | P-060 E | Adder | 7.19 MW | 6.11 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 913142 | Y1-033 E OP1 | Adder | 3.6 MW | 3.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946771 | AF1-217 C O2 | Adder | 0.96 MW | 0.82 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946772 | AF1-217 E O2 | Adder | 0.64 MW | 0.55 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959301 | AF2-221 C | 50/50 | 1.17 MW | 1.17 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959302 | AF2-221 E | 50/50 | 1.61 MW | 1.61 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946421 | AF2-000A C | Adder | 5.11 MW | 4.34 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946422 | AF2-000A E | Adder | 15.33 MW | 13.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 916189 | Z1-066 BAT | Adder | 0.01 MW | 0.01 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.56 MW | 0.56 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.94 MW | 0.94 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.06 MW | 0.06 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.43 MW | 0.43 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.38 MW | 1.38 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.1 MW | 0.1 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.3 MW | 0.3 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.18 MW | 0.18 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.29 MW | 0.29 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.3 MW | 0.3 MW |
STAR592-KEYSTONE 1.0/500.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.22 MW | 0.22 MW |
Details for LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 944411 | AF1-106 O1 | Adder | 4.08 MW | 3.46 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 945331 | AF1-198 | Adder | 0.45 MW | 0.38 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 959471 | AF2-238 C | Adder | 2.36 MW | 2.0 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 959472 | AF2-238 E | Adder | 1.57 MW | 1.34 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 960031 | AF2-294 C | Adder | 2.34 MW | 1.99 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 960032 | AF2-294 E | Adder | 1.56 MW | 1.32 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 961141 | AF2-405 | Adder | 2.04 MW | 1.73 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 961151 | AF2-406 | Adder | 15.28 MW | 12.99 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 961211 | AF2-412 | Adder | 21.76 MW | 18.5 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 961451 | AF2-436 | Adder | 0.41 MW | 0.35 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 961461 | AF2-437 | Adder | 0.54 MW | 0.46 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 200823 | 26MHP_X3-003 | Adder | 19.06 MW | 16.2 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 200894 | 26K02 | Adder | 10.71 MW | 9.1 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 203907 | 26Y2-042 | Adder | 6.64 MW | 5.65 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 203999 | P-047 E | Adder | 15.05 MW | 12.79 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 916202 | Z1-069 E | Adder | 7.53 MW | 6.4 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 940861 | AE2-074 C | Adder | 1.56 MW | 1.32 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 940862 | AE2-074 E | Adder | 2.05 MW | 1.74 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 941421 | AE2-139 C | Adder | 14.08 MW | 11.97 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 941422 | AE2-139 E | Adder | 9.39 MW | 7.98 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 208055 | LAEN G1 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 959922 | AF2-283 E | 50/50 | 0.95 MW | 0.95 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 209003 | KSTN IPP | 50/50 | 0.41 MW | 0.41 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 209009 | PEIP 2 | 50/50 | 3.65 MW | 3.65 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 209010 | PEIP 1 | 50/50 | 2.23 MW | 2.23 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 209029 | WAYM IPP | 50/50 | 0.74 MW | 0.74 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 923673 | AB1-182 E | Adder | 4.21 MW | 3.58 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 208052 | LAEN G2 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 208053 | LAEN G3 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 917631 | Z2-104 | 50/50 | 0.1 MW | 0.1 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 918601 | AA1-077 C | 50/50 | 2.84 MW | 2.84 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 918602 | AA1-077 E | 50/50 | 37.66 MW | 37.66 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 914271 | Y2-089 | 50/50 | 30.86 MW | 30.86 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 923443 | AB1-160 E | Adder | 2.15 MW | 1.83 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 938401 | AE1-059 C O1 | Adder | 64.64 MW | 54.95 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | 294573 | P-028 E | Adder | 36.22 MW | 30.79 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.14 MW | 0.14 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 1.67 MW | 1.67 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.21 MW | 0.21 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.09 MW | 0.09 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 32.77 MW | 32.77 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.44 MW | 1.44 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 4.69 MW | 4.69 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.41 MW | 0.41 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_001057 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.03 MW | 4.03 MW |
Details for LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 944411 | AF1-106 O1 | Adder | 4.08 MW | 3.46 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 945331 | AF1-198 | Adder | 0.45 MW | 0.38 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 959471 | AF2-238 C | Adder | 2.36 MW | 2.0 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 959472 | AF2-238 E | Adder | 1.57 MW | 1.34 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 960031 | AF2-294 C | Adder | 2.34 MW | 1.99 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 960032 | AF2-294 E | Adder | 1.56 MW | 1.32 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 961141 | AF2-405 | Adder | 2.04 MW | 1.73 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 961151 | AF2-406 | Adder | 15.28 MW | 12.99 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 961211 | AF2-412 | Adder | 21.76 MW | 18.5 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 961451 | AF2-436 | Adder | 0.41 MW | 0.35 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 961461 | AF2-437 | Adder | 0.54 MW | 0.46 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 200823 | 26MHP_X3-003 | Adder | 19.06 MW | 16.2 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 200894 | 26K02 | Adder | 10.71 MW | 9.1 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 203907 | 26Y2-042 | Adder | 6.64 MW | 5.65 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 203999 | P-047 E | Adder | 15.05 MW | 12.79 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 916202 | Z1-069 E | Adder | 7.53 MW | 6.4 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 940861 | AE2-074 C | Adder | 1.56 MW | 1.32 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 940862 | AE2-074 E | Adder | 2.05 MW | 1.74 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 941421 | AE2-139 C | Adder | 14.08 MW | 11.97 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 941422 | AE2-139 E | Adder | 9.39 MW | 7.98 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 208055 | LAEN G1 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 959922 | AF2-283 E | 50/50 | 0.95 MW | 0.95 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 209003 | KSTN IPP | 50/50 | 0.41 MW | 0.41 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 209009 | PEIP 2 | 50/50 | 3.65 MW | 3.65 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 209010 | PEIP 1 | 50/50 | 2.23 MW | 2.23 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 209029 | WAYM IPP | 50/50 | 0.74 MW | 0.74 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 923673 | AB1-182 E | Adder | 4.21 MW | 3.58 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 208052 | LAEN G2 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 208053 | LAEN G3 | 50/50 | 27.8 MW | 27.8 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 917631 | Z2-104 | 50/50 | 0.1 MW | 0.1 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 918601 | AA1-077 C | 50/50 | 2.84 MW | 2.84 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 918602 | AA1-077 E | 50/50 | 37.66 MW | 37.66 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 914271 | Y2-089 | 50/50 | 30.86 MW | 30.86 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 923443 | AB1-160 E | Adder | 2.15 MW | 1.83 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 938401 | AE1-059 C O1 | Adder | 64.64 MW | 54.95 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | 294573 | P-028 E | Adder | 36.22 MW | 30.79 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.14 MW | 0.14 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 1.67 MW | 1.67 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.21 MW | 0.21 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.09 MW | 0.09 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 32.77 MW | 32.77 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.44 MW | 1.44 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 4.69 MW | 4.69 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.41 MW | 0.41 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
LACK-LACKAW 230.0/500.0 kV Ckt 3 transformer l/o PL_P42_101231 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.03 MW | 4.03 MW |
Details for 26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 942491 | AE2-262 C | 80/20 | 2.55 MW | 2.55 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 942501 | AE2-263 C | 80/20 | 2.4 MW | 2.4 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 944311 | AF1-099 C | 80/20 | 4.15 MW | 4.15 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 944321 | AF1-100 C | 80/20 | 7.99 MW | 7.99 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 944411 | AF1-106 O1 | 80/20 | 3.44 MW | 3.44 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 944771 | AF1-142 C | 80/20 | 6.64 MW | 6.64 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 945161 | AF1-181 | 80/20 | 0.15 MW | 0.15 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 945171 | AF1-182 | 80/20 | 0.2 MW | 0.2 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 945331 | AF1-198 | 80/20 | 0.37 MW | 0.37 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 959471 | AF2-238 C | 80/20 | 2.12 MW | 2.12 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 961141 | AF2-405 | 80/20 | 1.72 MW | 1.72 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 961151 | AF2-406 | 80/20 | 12.91 MW | 12.91 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 961211 | AF2-412 | 80/20 | 17.94 MW | 17.94 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 961451 | AF2-436 | 80/20 | 0.1 MW | 0.1 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 961461 | AF2-437 | Adder | -0.18 MW | -0.16 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 200649 | 26PENNTECH | 80/20 | 0.38 MW | 0.38 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 200665 | 26SHAWVL 3 | 80/20 | 1.55 MW | 1.55 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 200666 | 26SHAWVL 4 | 80/20 | 1.54 MW | 1.54 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 200887 | 26ARMNA MT | 80/20 | 0.59 MW | 0.59 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203261 | 26BLOSSBCT | 80/20 | 0.49 MW | 0.49 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203283 | 26MANOR_T86 | 80/20 | 0.05 MW | 0.05 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203349 | 26Z1-069 C | 80/20 | 0.25 MW | 0.25 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203350 | 26MILZ1-092 | 80/20 | 0.6 MW | 0.6 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203351 | 26GROZ1-110 | 80/20 | 0.59 MW | 0.59 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 203352 | 26CANZ2-011 | 80/20 | 0.59 MW | 0.59 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 940861 | AE2-074 C | 80/20 | 1.22 MW | 1.22 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 941191 | AE2-113 C | 80/20 | 3.44 MW | 3.44 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 941421 | AE2-139 C | 80/20 | 11.26 MW | 11.26 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 946111 | AF1-276 C | 80/20 | 3.52 MW | 3.52 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 946121 | AF1-277 C | 80/20 | 3.52 MW | 3.52 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 946131 | AF1-278 C | 80/20 | 2.81 MW | 2.81 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 920351 | AA2-133 | 80/20 | 0.22 MW | 0.22 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 934801 | AD1-108 | 80/20 | 0.04 MW | 0.04 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 934811 | AD1-109 | 80/20 | 0.03 MW | 0.03 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 935061 | AD1-142 | 80/20 | 0.03 MW | 0.03 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 200949 | 26X1-109 | 80/20 | 26.21 MW | 26.21 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 923442 | AB1-160 C | 80/20 | 0.07 MW | 0.07 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | 946421 | AF2-000A C | 80/20 | 2.48 MW | 2.48 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.32 MW | 0.32 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.22 MW | 0.22 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.37 MW | 4.37 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.7 MW | 0.7 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.18 MW | 0.18 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 2.2 MW | 2.2 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.36 MW | 4.36 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.9 MW | 0.9 MW |
26TOWANDA-26NO MESHO 115.0 kV Ckt 1 line l/o PN-P1-2-PN-230-013A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.63 MW | 7.63 MW |
Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936991 | AD2-133 C | 50/50 | 3.57 MW | 3.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936992 | AD2-133 E | 50/50 | 16.33 MW | 16.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942121 | AE2-224 C | 50/50 | 21.18 MW | 21.18 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942122 | AE2-224 E | 50/50 | 14.12 MW | 14.12 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942351 | AE2-248 C | Adder | 1.31 MW | 1.12 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942352 | AE2-248 E | Adder | 0.88 MW | 0.74 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942361 | AE2-249 C | 50/50 | 2.47 MW | 2.47 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942362 | AE2-249 E | 50/50 | 1.65 MW | 1.65 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942491 | AE2-262 C | Adder | 7.38 MW | 6.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942492 | AE2-262 E | Adder | 4.96 MW | 4.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942501 | AE2-263 C | Adder | 6.94 MW | 5.9 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942502 | AE2-263 E | Adder | 4.63 MW | 3.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942811 | AE2-299 C | Adder | 4.33 MW | 3.68 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942812 | AE2-299 E | Adder | 17.32 MW | 14.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942961 | AE2-316 C | Adder | 6.71 MW | 5.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942962 | AE2-316 E | Adder | 7.95 MW | 6.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943151 | AE2-344 C | Adder | 9.12 MW | 7.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943152 | AE2-344 E | Adder | 6.08 MW | 5.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943351 | AF1-006 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943352 | AF1-006 E | Adder | 0.89 MW | 0.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943711 | AF1-039 C O1 | Adder | 1.68 MW | 1.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943712 | AF1-039 E O1 | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944181 | AF1-086 C O1 | Adder | 3.4 MW | 2.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944182 | AF1-086 E O1 | Adder | 14.79 MW | 12.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944261 | AF1-094 C | Adder | 1.61 MW | 1.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944262 | AF1-094 E | Adder | 1.07 MW | 0.91 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944301 | AF1-098 C | Adder | 6.61 MW | 5.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944302 | AF1-098 E | Adder | 4.41 MW | 3.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944311 | AF1-099 C | Adder | 11.49 MW | 9.77 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944312 | AF1-099 E | Adder | 7.66 MW | 6.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944321 | AF1-100 C | Adder | 23.48 MW | 19.96 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944322 | AF1-100 E | Adder | 15.65 MW | 13.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944391 | AF1-104 O1 | Adder | 2.31 MW | 1.96 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944411 | AF1-106 O1 | Adder | 3.56 MW | 3.03 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944471 | AF1-112 C | Adder | 1.22 MW | 1.04 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944472 | AF1-112 E | Adder | 0.84 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944751 | AF1-140 C | 50/50 | 2.93 MW | 2.93 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944752 | AF1-140 E | 50/50 | 1.95 MW | 1.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944771 | AF1-142 C | Adder | 18.38 MW | 15.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944772 | AF1-142 E | Adder | 12.26 MW | 10.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944781 | AF1-143 C | 50/50 | 14.58 MW | 14.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944782 | AF1-143 E | 50/50 | 9.72 MW | 9.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944881 | AF1-153 C O1 | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944882 | AF1-153 E O1 | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944901 | AF1-155 C | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944902 | AF1-155 E | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945021 | AF1-167 C | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945022 | AF1-167 E | Adder | 0.75 MW | 0.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945051 | AF1-170 C | Adder | 5.7 MW | 4.84 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945052 | AF1-170 E | Adder | 3.8 MW | 3.23 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945121 | AF1-177 | Adder | 0.85 MW | 0.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945161 | AF1-181 | Adder | 0.47 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945171 | AF1-182 | Adder | 0.63 MW | 0.53 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945181 | AF1-183 | Adder | 0.16 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945331 | AF1-198 | Adder | 0.48 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945451 | AF1-210 C | Adder | 1.23 MW | 1.05 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945452 | AF1-210 E | Adder | 0.82 MW | 0.7 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945751 | AF1-240 C O1 | Adder | 1.8 MW | 1.53 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945752 | AF1-240 E O1 | Adder | 1.2 MW | 1.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958471 | AF2-141 | 50/50 | 1.94 MW | 1.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958731 | AF2-164 C O1 | Adder | 9.12 MW | 7.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958732 | AF2-164 E O1 | Adder | 6.08 MW | 5.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958741 | AF2-165 C | Adder | 1.77 MW | 1.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958742 | AF2-165 E | Adder | 1.18 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958751 | AF2-166 C | Adder | 1.76 MW | 1.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958752 | AF2-166 E | Adder | 1.17 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959441 | AF2-235 C | Adder | 0.86 MW | 0.73 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959442 | AF2-235 E | Adder | 0.57 MW | 0.48 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959471 | AF2-238 C | Adder | 2.19 MW | 1.86 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959472 | AF2-238 E | Adder | 1.46 MW | 1.24 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959521 | AF2-243 C | Adder | 1.33 MW | 1.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959522 | AF2-243 E | Adder | 0.89 MW | 0.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959802 | AF2-271 E | 50/50 | 0.72 MW | 0.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960022 | AF2-293 E | Adder | 0.16 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960031 | AF2-294 C | Adder | 1.67 MW | 1.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960032 | AF2-294 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960041 | AF2-295 C | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960042 | AF2-295 E | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960051 | AF2-296 C | Adder | 2.02 MW | 1.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960052 | AF2-296 E | Adder | 1.35 MW | 1.15 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960451 | AF2-336 C | 50/50 | 3.64 MW | 3.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960452 | AF2-336 E | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960461 | AF2-337 C | 50/50 | 3.64 MW | 3.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960462 | AF2-337 E | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961141 | AF2-405 | Adder | 1.78 MW | 1.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961151 | AF2-406 | Adder | 13.35 MW | 11.35 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961211 | AF2-412 | 50/50 | 27.31 MW | 27.31 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961451 | AF2-436 | Adder | 0.2 MW | 0.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200503 | 26C.SLOPE | 50/50 | 2.75 MW | 2.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200794 | 26CONEMAGH | 50/50 | 0.58 MW | 0.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200809 | 26SITHE | 50/50 | 2.8 MW | 2.8 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200823 | 26MHP_X3-003 | Adder | 7.07 MW | 6.01 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200834 | 26SW_E13_K22 | 50/50 | 0.09 MW | 0.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200835 | 26ARN_Z1-066 | 50/50 | 0.44 MW | 0.44 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200837 | 26HOMER C1 | 50/50 | 48.22 MW | 48.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200838 | 26HOMER C2 | 50/50 | 40.08 MW | 40.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200839 | 26HOMER C3 | 50/50 | 42.43 MW | 42.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200846 | 26FORWARD | 50/50 | 0.32 MW | 0.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200852 | 26WARR RDG | 50/50 | 0.2 MW | 0.2 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200887 | 26ARMNA MT | 50/50 | 0.68 MW | 0.68 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200888 | 26HIGHLAND | 50/50 | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200889 | 26STNY CRK | 50/50 | 0.54 MW | 0.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200890 | 26BF_G21_K23 | 50/50 | 0.22 MW | 0.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200891 | 26CSLMN_L13 | 50/50 | 0.34 MW | 0.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200892 | 26LOOKOUT | 50/50 | 0.32 MW | 0.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200894 | 26K02 | Adder | 8.33 MW | 7.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200925 | 26R32 | 50/50 | 0.82 MW | 0.82 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200945 | 26CT_V3-030 | 50/50 | 0.28 MW | 0.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 202225 | 26SCI_S29B | 50/50 | 0.14 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203349 | 26Z1-069 C | 50/50 | 0.51 MW | 0.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203999 | P-047 E | 50/50 | 15.43 MW | 15.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 235003 | AC1-025 E | Adder | 0.2 MW | 0.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 236828 | 01GRAYMONT | Adder | 0.55 MW | 0.47 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916202 | Z1-069 E | 50/50 | 12.31 MW | 12.31 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 938951 | AE1-123 | Adder | 2.63 MW | 2.24 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939291 | AE1-160 C | Adder | 1.81 MW | 1.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939292 | AE1-160 E | Adder | 1.04 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940201 | AE2-001 C | Adder | 1.66 MW | 1.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940202 | AE2-001 E | Adder | 1.11 MW | 0.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940681 | AE2-055 C | Adder | 1.63 MW | 1.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940682 | AE2-055 E | Adder | 1.08 MW | 0.92 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940861 | AE2-074 C | 50/50 | 3.38 MW | 3.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940862 | AE2-074 E | 50/50 | 4.45 MW | 4.45 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941191 | AE2-113 C | 50/50 | 12.75 MW | 12.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941192 | AE2-113 E | 50/50 | 11.97 MW | 11.97 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941231 | AE2-117 C | 50/50 | 2.33 MW | 2.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941232 | AE2-117 E | 50/50 | 1.56 MW | 1.56 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941241 | AE2-118 C | 50/50 | 2.33 MW | 2.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941242 | AE2-118 E | 50/50 | 1.56 MW | 1.56 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941271 | AE2-121 C | Adder | 0.89 MW | 0.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941272 | AE2-121 E | Adder | 0.59 MW | 0.5 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941321 | AE2-126 C | Adder | 2.11 MW | 1.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941322 | AE2-126 E | Adder | 1.41 MW | 1.2 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941331 | AE2-129 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941332 | AE2-129 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941351 | AE2-131 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941352 | AE2-131 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941421 | AE2-139 C | Adder | 8.8 MW | 7.48 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941422 | AE2-139 E | Adder | 5.87 MW | 4.99 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946111 | AF1-276 C | 50/50 | 15.08 MW | 15.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946112 | AF1-276 E | 50/50 | 7.43 MW | 7.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946121 | AF1-277 C | 50/50 | 15.08 MW | 15.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946122 | AF1-277 E | 50/50 | 7.43 MW | 7.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946131 | AF1-278 C | 50/50 | 12.02 MW | 12.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946132 | AF1-278 E | 50/50 | 5.98 MW | 5.98 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946221 | AF1-287 C | Adder | 1.57 MW | 1.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946222 | AF1-287 E | Adder | 1.05 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946381 | AF1-302 C | Adder | 2.93 MW | 2.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946382 | AF1-302 E | Adder | 3.91 MW | 3.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946571 | AF1-321 C O1 | 50/50 | 3.87 MW | 3.87 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946572 | AF1-321 E O1 | 50/50 | 2.58 MW | 2.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957001 | AF2-001 C O1 | 50/50 | 3.87 MW | 3.87 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957002 | AF2-001 E O1 | 50/50 | 2.58 MW | 2.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957011 | AF2-002 C O1 | 50/50 | 1.94 MW | 1.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957012 | AF2-002 E O1 | 50/50 | 1.29 MW | 1.29 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957161 | AF2-010 C | Adder | 6.19 MW | 5.26 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957162 | AF2-010 E | Adder | 4.17 MW | 3.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957451 | AF2-039 C | Adder | 1.4 MW | 1.19 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957452 | AF2-039 E | Adder | 0.93 MW | 0.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957561 | AF2-050 C | 50/50 | 10.59 MW | 10.59 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957562 | AF2-050 E | 50/50 | 7.06 MW | 7.06 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957931 | AF2-087 C | 50/50 | 0.81 MW | 0.81 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957932 | AF2-087 E | 50/50 | 1.11 MW | 1.11 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957941 | AF2-088 C | Adder | 0.67 MW | 0.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957942 | AF2-088 E | Adder | 0.45 MW | 0.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957981 | AF2-092 C | 50/50 | 2.19 MW | 2.19 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957982 | AF2-092 E | 50/50 | 1.46 MW | 1.46 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958271 | AF2-121 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958272 | AF2-121 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958361 | AF2-130 C | Adder | 1.76 MW | 1.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958362 | AF2-130 E | Adder | 1.17 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200833 | 26SEWRDB34 | 50/50 | 34.13 MW | 34.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200812 | 26ALY HYDR | 50/50 | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200886 | 26ARWF_N39 | 50/50 | 0.86 MW | 0.86 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200915 | 26CHSTN_FL | 50/50 | 0.37 MW | 0.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203034 | 26NA_O38_P22 | 50/50 | 0.76 MW | 0.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 290086 | Q-036 E | 50/50 | 9.08 MW | 9.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 296332 | R-032 E | 50/50 | 18.79 MW | 18.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 917672 | Z2-108 E | 50/50 | 4.37 MW | 4.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944691 | AF1-134 C O1 | Adder | 2.02 MW | 1.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944692 | AF1-134 E O1 | Adder | 1.35 MW | 1.15 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200864 | K-013 E | 50/50 | 7.41 MW | 7.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200883 | Q-053 E | 50/50 | 8.54 MW | 8.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292350 | K-023 | 50/50 | 6.05 MW | 6.05 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292542 | L-013 1 | 50/50 | 7.78 MW | 7.78 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293301 | N-039 E | 50/50 | 19.78 MW | 19.78 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 923442 | AB1-160 C | 50/50 | 0.14 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 923443 | AB1-160 E | 50/50 | 3.52 MW | 3.52 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293393 | V3-030E | 50/50 | 5.89 MW | 5.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293432 | R-040 E | 50/50 | 0.44 MW | 0.44 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293603 | O-018 E | 50/50 | 16.28 MW | 16.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293902 | O-048 E | 50/50 | 7.0 MW | 7.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294515 | O38_P22 | 50/50 | 17.3 MW | 17.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294573 | P-028 E | Adder | 13.43 MW | 11.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294903 | P-060 E | 50/50 | 12.4 MW | 12.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 913142 | Y1-033 E OP1 | Adder | 6.23 MW | 5.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946771 | AF1-217 C O2 | Adder | 1.57 MW | 1.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946772 | AF1-217 E O2 | Adder | 1.05 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959301 | AF2-221 C | 50/50 | 2.03 MW | 2.03 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959302 | AF2-221 E | 50/50 | 2.8 MW | 2.8 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946421 | AF2-000A C | Adder | 8.14 MW | 6.92 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946422 | AF2-000A E | Adder | 24.42 MW | 20.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200905 | 26Q36 | 50/50 | 0.4 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916189 | Z1-066 BAT | 50/50 | 0.02 MW | 0.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.18 MW | 1.18 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.75 MW | 1.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.16 MW | 1.16 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.13 MW | 0.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.41 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.21 MW | 0.21 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.4 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.29 MW | 0.29 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.02 MW | 0.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.36 MW | 0.36 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.41 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.04 MW | 0.04 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.38 MW | 0.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936991 | AD2-133 C | 50/50 | 3.57 MW | 3.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936992 | AD2-133 E | 50/50 | 16.33 MW | 16.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942121 | AE2-224 C | 50/50 | 21.18 MW | 21.18 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942122 | AE2-224 E | 50/50 | 14.12 MW | 14.12 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942351 | AE2-248 C | Adder | 1.31 MW | 1.12 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942352 | AE2-248 E | Adder | 0.88 MW | 0.74 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942361 | AE2-249 C | 50/50 | 2.47 MW | 2.47 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942362 | AE2-249 E | 50/50 | 1.65 MW | 1.65 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942491 | AE2-262 C | Adder | 7.38 MW | 6.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942492 | AE2-262 E | Adder | 4.96 MW | 4.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942501 | AE2-263 C | Adder | 6.94 MW | 5.9 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942502 | AE2-263 E | Adder | 4.63 MW | 3.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942811 | AE2-299 C | Adder | 4.33 MW | 3.68 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942812 | AE2-299 E | Adder | 17.32 MW | 14.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942961 | AE2-316 C | Adder | 6.71 MW | 5.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942962 | AE2-316 E | Adder | 7.95 MW | 6.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943151 | AE2-344 C | Adder | 9.12 MW | 7.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943152 | AE2-344 E | Adder | 6.08 MW | 5.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943351 | AF1-006 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943352 | AF1-006 E | Adder | 0.89 MW | 0.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943711 | AF1-039 C O1 | Adder | 1.68 MW | 1.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943712 | AF1-039 E O1 | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944181 | AF1-086 C O1 | Adder | 3.4 MW | 2.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944182 | AF1-086 E O1 | Adder | 14.79 MW | 12.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944261 | AF1-094 C | Adder | 1.61 MW | 1.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944262 | AF1-094 E | Adder | 1.07 MW | 0.91 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944301 | AF1-098 C | Adder | 6.61 MW | 5.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944302 | AF1-098 E | Adder | 4.41 MW | 3.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944311 | AF1-099 C | Adder | 11.49 MW | 9.77 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944312 | AF1-099 E | Adder | 7.66 MW | 6.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944321 | AF1-100 C | Adder | 23.48 MW | 19.96 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944322 | AF1-100 E | Adder | 15.65 MW | 13.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944391 | AF1-104 O1 | Adder | 2.31 MW | 1.96 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944411 | AF1-106 O1 | Adder | 3.56 MW | 3.03 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944471 | AF1-112 C | Adder | 1.22 MW | 1.04 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944472 | AF1-112 E | Adder | 0.84 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944751 | AF1-140 C | 50/50 | 2.93 MW | 2.93 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944752 | AF1-140 E | 50/50 | 1.95 MW | 1.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944771 | AF1-142 C | Adder | 18.38 MW | 15.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944772 | AF1-142 E | Adder | 12.26 MW | 10.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944781 | AF1-143 C | 50/50 | 14.58 MW | 14.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944782 | AF1-143 E | 50/50 | 9.72 MW | 9.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944881 | AF1-153 C O1 | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944882 | AF1-153 E O1 | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944901 | AF1-155 C | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944902 | AF1-155 E | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945021 | AF1-167 C | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945022 | AF1-167 E | Adder | 0.75 MW | 0.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945051 | AF1-170 C | Adder | 5.7 MW | 4.84 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945052 | AF1-170 E | Adder | 3.8 MW | 3.23 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945121 | AF1-177 | Adder | 0.85 MW | 0.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945161 | AF1-181 | Adder | 0.47 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945171 | AF1-182 | Adder | 0.63 MW | 0.53 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945181 | AF1-183 | Adder | 0.16 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945331 | AF1-198 | Adder | 0.48 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945451 | AF1-210 C | Adder | 1.23 MW | 1.05 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945452 | AF1-210 E | Adder | 0.82 MW | 0.7 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945751 | AF1-240 C O1 | Adder | 1.8 MW | 1.53 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945752 | AF1-240 E O1 | Adder | 1.2 MW | 1.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958471 | AF2-141 | 50/50 | 1.94 MW | 1.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958731 | AF2-164 C O1 | Adder | 9.12 MW | 7.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958732 | AF2-164 E O1 | Adder | 6.08 MW | 5.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958741 | AF2-165 C | Adder | 1.77 MW | 1.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958742 | AF2-165 E | Adder | 1.18 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958751 | AF2-166 C | Adder | 1.76 MW | 1.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958752 | AF2-166 E | Adder | 1.17 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959441 | AF2-235 C | Adder | 0.86 MW | 0.73 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959442 | AF2-235 E | Adder | 0.57 MW | 0.48 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959471 | AF2-238 C | Adder | 2.19 MW | 1.86 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959472 | AF2-238 E | Adder | 1.46 MW | 1.24 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959521 | AF2-243 C | Adder | 1.33 MW | 1.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959522 | AF2-243 E | Adder | 0.89 MW | 0.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959802 | AF2-271 E | 50/50 | 0.72 MW | 0.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960022 | AF2-293 E | Adder | 0.16 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960031 | AF2-294 C | Adder | 1.67 MW | 1.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960032 | AF2-294 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960041 | AF2-295 C | Adder | 1.93 MW | 1.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960042 | AF2-295 E | Adder | 1.29 MW | 1.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960051 | AF2-296 C | Adder | 2.02 MW | 1.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960052 | AF2-296 E | Adder | 1.35 MW | 1.15 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960451 | AF2-336 C | 50/50 | 3.64 MW | 3.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960452 | AF2-336 E | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960461 | AF2-337 C | 50/50 | 3.64 MW | 3.64 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960462 | AF2-337 E | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961141 | AF2-405 | Adder | 1.78 MW | 1.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961151 | AF2-406 | Adder | 13.35 MW | 11.35 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961211 | AF2-412 | 50/50 | 27.31 MW | 27.31 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961451 | AF2-436 | Adder | 0.2 MW | 0.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200503 | 26C.SLOPE | 50/50 | 2.75 MW | 2.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200794 | 26CONEMAGH | 50/50 | 0.58 MW | 0.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200809 | 26SITHE | 50/50 | 2.8 MW | 2.8 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200823 | 26MHP_X3-003 | Adder | 7.07 MW | 6.01 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200834 | 26SW_E13_K22 | 50/50 | 0.09 MW | 0.09 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200835 | 26ARN_Z1-066 | 50/50 | 0.44 MW | 0.44 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200837 | 26HOMER C1 | 50/50 | 48.22 MW | 48.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200838 | 26HOMER C2 | 50/50 | 40.08 MW | 40.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200839 | 26HOMER C3 | 50/50 | 42.43 MW | 42.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200846 | 26FORWARD | 50/50 | 0.32 MW | 0.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200852 | 26WARR RDG | 50/50 | 0.2 MW | 0.2 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200887 | 26ARMNA MT | 50/50 | 0.68 MW | 0.68 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200888 | 26HIGHLAND | 50/50 | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200889 | 26STNY CRK | 50/50 | 0.54 MW | 0.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200890 | 26BF_G21_K23 | 50/50 | 0.22 MW | 0.22 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200891 | 26CSLMN_L13 | 50/50 | 0.34 MW | 0.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200892 | 26LOOKOUT | 50/50 | 0.32 MW | 0.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200894 | 26K02 | Adder | 8.33 MW | 7.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200925 | 26R32 | 50/50 | 0.82 MW | 0.82 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200945 | 26CT_V3-030 | 50/50 | 0.28 MW | 0.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 202225 | 26SCI_S29B | 50/50 | 0.14 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203349 | 26Z1-069 C | 50/50 | 0.51 MW | 0.51 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203999 | P-047 E | 50/50 | 15.43 MW | 15.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 235003 | AC1-025 E | Adder | 0.2 MW | 0.17 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 236828 | 01GRAYMONT | Adder | 0.55 MW | 0.47 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916202 | Z1-069 E | 50/50 | 12.31 MW | 12.31 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 938951 | AE1-123 | Adder | 2.63 MW | 2.24 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939291 | AE1-160 C | Adder | 1.81 MW | 1.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939292 | AE1-160 E | Adder | 1.04 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940201 | AE2-001 C | Adder | 1.66 MW | 1.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940202 | AE2-001 E | Adder | 1.11 MW | 0.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940681 | AE2-055 C | Adder | 1.63 MW | 1.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940682 | AE2-055 E | Adder | 1.08 MW | 0.92 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940861 | AE2-074 C | 50/50 | 3.38 MW | 3.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940862 | AE2-074 E | 50/50 | 4.45 MW | 4.45 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941191 | AE2-113 C | 50/50 | 12.75 MW | 12.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941192 | AE2-113 E | 50/50 | 11.97 MW | 11.97 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941231 | AE2-117 C | 50/50 | 2.33 MW | 2.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941232 | AE2-117 E | 50/50 | 1.56 MW | 1.56 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941241 | AE2-118 C | 50/50 | 2.33 MW | 2.33 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941242 | AE2-118 E | 50/50 | 1.56 MW | 1.56 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941271 | AE2-121 C | Adder | 0.89 MW | 0.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941272 | AE2-121 E | Adder | 0.59 MW | 0.5 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941321 | AE2-126 C | Adder | 2.11 MW | 1.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941322 | AE2-126 E | Adder | 1.41 MW | 1.2 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941331 | AE2-129 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941332 | AE2-129 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941351 | AE2-131 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941352 | AE2-131 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941421 | AE2-139 C | Adder | 8.8 MW | 7.48 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941422 | AE2-139 E | Adder | 5.87 MW | 4.99 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946111 | AF1-276 C | 50/50 | 15.08 MW | 15.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946112 | AF1-276 E | 50/50 | 7.43 MW | 7.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946121 | AF1-277 C | 50/50 | 15.08 MW | 15.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946122 | AF1-277 E | 50/50 | 7.43 MW | 7.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946131 | AF1-278 C | 50/50 | 12.02 MW | 12.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946132 | AF1-278 E | 50/50 | 5.98 MW | 5.98 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946221 | AF1-287 C | Adder | 1.57 MW | 1.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946222 | AF1-287 E | Adder | 1.05 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946381 | AF1-302 C | Adder | 2.93 MW | 2.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946382 | AF1-302 E | Adder | 3.91 MW | 3.32 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946571 | AF1-321 C O1 | 50/50 | 3.87 MW | 3.87 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946572 | AF1-321 E O1 | 50/50 | 2.58 MW | 2.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957001 | AF2-001 C O1 | 50/50 | 3.87 MW | 3.87 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957002 | AF2-001 E O1 | 50/50 | 2.58 MW | 2.58 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957011 | AF2-002 C O1 | 50/50 | 1.94 MW | 1.94 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957012 | AF2-002 E O1 | 50/50 | 1.29 MW | 1.29 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957161 | AF2-010 C | Adder | 6.19 MW | 5.26 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957162 | AF2-010 E | Adder | 4.17 MW | 3.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957451 | AF2-039 C | Adder | 1.4 MW | 1.19 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957452 | AF2-039 E | Adder | 0.93 MW | 0.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957561 | AF2-050 C | 50/50 | 10.59 MW | 10.59 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957562 | AF2-050 E | 50/50 | 7.06 MW | 7.06 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957931 | AF2-087 C | 50/50 | 0.81 MW | 0.81 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957932 | AF2-087 E | 50/50 | 1.11 MW | 1.11 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957941 | AF2-088 C | Adder | 0.67 MW | 0.57 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957942 | AF2-088 E | Adder | 0.45 MW | 0.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957981 | AF2-092 C | 50/50 | 2.19 MW | 2.19 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957982 | AF2-092 E | 50/50 | 1.46 MW | 1.46 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958271 | AF2-121 C | 50/50 | 2.43 MW | 2.43 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958272 | AF2-121 E | 50/50 | 1.62 MW | 1.62 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958361 | AF2-130 C | Adder | 1.76 MW | 1.49 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958362 | AF2-130 E | Adder | 1.17 MW | 1.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200833 | 26SEWRDB34 | 50/50 | 34.13 MW | 34.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200812 | 26ALY HYDR | 50/50 | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200886 | 26ARWF_N39 | 50/50 | 0.86 MW | 0.86 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200915 | 26CHSTN_FL | 50/50 | 0.37 MW | 0.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203034 | 26NA_O38_P22 | 50/50 | 0.76 MW | 0.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 290086 | Q-036 E | 50/50 | 9.08 MW | 9.08 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 296332 | R-032 E | 50/50 | 18.79 MW | 18.79 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 917672 | Z2-108 E | 50/50 | 4.37 MW | 4.37 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944691 | AF1-134 C O1 | Adder | 2.02 MW | 1.72 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944692 | AF1-134 E O1 | Adder | 1.35 MW | 1.15 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200864 | K-013 E | 50/50 | 7.41 MW | 7.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200883 | Q-053 E | 50/50 | 8.54 MW | 8.54 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292350 | K-023 | 50/50 | 6.05 MW | 6.05 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292542 | L-013 1 | 50/50 | 7.78 MW | 7.78 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293301 | N-039 E | 50/50 | 19.78 MW | 19.78 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 923442 | AB1-160 C | 50/50 | 0.14 MW | 0.14 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 923443 | AB1-160 E | 50/50 | 3.52 MW | 3.52 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293393 | V3-030E | 50/50 | 5.89 MW | 5.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293432 | R-040 E | 50/50 | 0.44 MW | 0.44 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293603 | O-018 E | 50/50 | 16.28 MW | 16.28 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293902 | O-048 E | 50/50 | 7.0 MW | 7.0 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294515 | O38_P22 | 50/50 | 17.3 MW | 17.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294573 | P-028 E | Adder | 13.43 MW | 11.42 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294903 | P-060 E | 50/50 | 12.4 MW | 12.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 913142 | Y1-033 E OP1 | Adder | 6.23 MW | 5.3 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946771 | AF1-217 C O2 | Adder | 1.57 MW | 1.34 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946772 | AF1-217 E O2 | Adder | 1.05 MW | 0.89 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959301 | AF2-221 C | 50/50 | 2.03 MW | 2.03 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959302 | AF2-221 E | 50/50 | 2.8 MW | 2.8 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946421 | AF2-000A C | Adder | 8.14 MW | 6.92 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946422 | AF2-000A E | Adder | 24.42 MW | 20.76 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200905 | 26Q36 | 50/50 | 0.4 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916189 | Z1-066 BAT | 50/50 | 0.02 MW | 0.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.71 MW | 0.71 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.18 MW | 1.18 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.75 MW | 1.75 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.16 MW | 1.16 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.13 MW | 0.13 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.41 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.21 MW | 0.21 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.4 MW | 0.4 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.29 MW | 0.29 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.02 MW | 0.02 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.36 MW | 0.36 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.41 MW | 0.41 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.04 MW | 0.04 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.38 MW | 0.38 MW |
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936991 | AD2-133 C | Adder | 4.1 MW | 3.49 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 936992 | AD2-133 E | Adder | 18.78 MW | 15.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942121 | AE2-224 C | 50/50 | 21.8 MW | 21.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942122 | AE2-224 E | 50/50 | 14.54 MW | 14.54 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942351 | AE2-248 C | Adder | 1.45 MW | 1.23 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942352 | AE2-248 E | Adder | 0.97 MW | 0.82 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942361 | AE2-249 C | 50/50 | 2.71 MW | 2.71 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942362 | AE2-249 E | 50/50 | 1.8 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942491 | AE2-262 C | Adder | 8.21 MW | 6.98 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942492 | AE2-262 E | Adder | 5.52 MW | 4.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942501 | AE2-263 C | Adder | 7.71 MW | 6.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942502 | AE2-263 E | Adder | 5.15 MW | 4.38 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942811 | AE2-299 C | Adder | 4.56 MW | 3.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942812 | AE2-299 E | Adder | 18.24 MW | 15.5 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942961 | AE2-316 C | Adder | 7.43 MW | 6.31 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 942962 | AE2-316 E | Adder | 8.8 MW | 7.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943151 | AE2-344 C | Adder | 9.74 MW | 8.28 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943152 | AE2-344 E | Adder | 6.49 MW | 5.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943351 | AF1-006 C | Adder | 1.69 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943352 | AF1-006 E | Adder | 0.95 MW | 0.81 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943711 | AF1-039 C O1 | Adder | 1.84 MW | 1.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 943712 | AF1-039 E O1 | Adder | 1.23 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944181 | AF1-086 C O1 | Adder | 5.91 MW | 5.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944182 | AF1-086 E O1 | Adder | 25.72 MW | 21.86 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944261 | AF1-094 C | Adder | 1.78 MW | 1.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944262 | AF1-094 E | Adder | 1.19 MW | 1.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944301 | AF1-098 C | Adder | 7.01 MW | 5.96 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944302 | AF1-098 E | Adder | 4.67 MW | 3.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944311 | AF1-099 C | Adder | 12.79 MW | 10.87 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944312 | AF1-099 E | Adder | 8.53 MW | 7.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944321 | AF1-100 C | Adder | 26.49 MW | 22.51 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944322 | AF1-100 E | Adder | 17.66 MW | 15.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944411 | AF1-106 O1 | Adder | 3.58 MW | 3.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944471 | AF1-112 C | Adder | 1.35 MW | 1.15 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944472 | AF1-112 E | Adder | 0.92 MW | 0.79 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944751 | AF1-140 C | 50/50 | 3.24 MW | 3.24 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944752 | AF1-140 E | 50/50 | 2.16 MW | 2.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944771 | AF1-142 C | Adder | 20.46 MW | 17.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944772 | AF1-142 E | Adder | 13.64 MW | 11.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944781 | AF1-143 C | Adder | 15.87 MW | 13.49 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944782 | AF1-143 E | Adder | 10.58 MW | 8.99 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944881 | AF1-153 C O1 | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944882 | AF1-153 E O1 | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944901 | AF1-155 C | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944902 | AF1-155 E | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945021 | AF1-167 C | Adder | 1.34 MW | 1.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945022 | AF1-167 E | Adder | 0.9 MW | 0.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945051 | AF1-170 C | Adder | 6.07 MW | 5.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945052 | AF1-170 E | Adder | 4.05 MW | 3.44 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945121 | AF1-177 | Adder | 0.89 MW | 0.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945161 | AF1-181 | Adder | 0.53 MW | 0.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945171 | AF1-182 | Adder | 0.71 MW | 0.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945181 | AF1-183 | Adder | 0.19 MW | 0.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945331 | AF1-198 | Adder | 0.48 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945451 | AF1-210 C | Adder | 1.47 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945452 | AF1-210 E | Adder | 0.98 MW | 0.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945751 | AF1-240 C O1 | Adder | 2.96 MW | 2.51 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 945752 | AF1-240 E O1 | Adder | 1.97 MW | 1.68 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958471 | AF2-141 | Adder | 2.12 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958731 | AF2-164 C O1 | Adder | 9.46 MW | 8.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958732 | AF2-164 E O1 | Adder | 6.3 MW | 5.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958741 | AF2-165 C | Adder | 2.12 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958742 | AF2-165 E | Adder | 1.42 MW | 1.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958751 | AF2-166 C | Adder | 2.21 MW | 1.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958752 | AF2-166 E | Adder | 1.48 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959441 | AF2-235 C | Adder | 1.01 MW | 0.85 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959442 | AF2-235 E | Adder | 0.67 MW | 0.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959471 | AF2-238 C | Adder | 2.2 MW | 1.87 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959472 | AF2-238 E | Adder | 1.47 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959521 | AF2-243 C | Adder | 1.59 MW | 1.35 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959522 | AF2-243 E | Adder | 1.06 MW | 0.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959802 | AF2-271 E | Adder | 0.82 MW | 0.7 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960022 | AF2-293 E | Adder | 0.18 MW | 0.15 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960031 | AF2-294 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960032 | AF2-294 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960041 | AF2-295 C | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960042 | AF2-295 E | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960051 | AF2-296 C | Adder | 3.04 MW | 2.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960052 | AF2-296 E | Adder | 2.03 MW | 1.72 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960451 | AF2-336 C | 50/50 | 4.0 MW | 4.0 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960452 | AF2-336 E | 50/50 | 2.67 MW | 2.67 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960461 | AF2-337 C | 50/50 | 4.0 MW | 4.0 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 960462 | AF2-337 E | 50/50 | 2.67 MW | 2.67 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961141 | AF2-405 | Adder | 1.79 MW | 1.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961151 | AF2-406 | Adder | 13.42 MW | 11.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961211 | AF2-412 | Adder | 27.33 MW | 23.23 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 961451 | AF2-436 | Adder | 0.2 MW | 0.17 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200503 | 26C.SLOPE | 50/50 | 3.09 MW | 3.09 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200636 | 26IUP CO-G | 50/50 | 0.85 MW | 0.85 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200794 | 26CONEMAGH | 50/50 | 0.69 MW | 0.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200809 | 26SITHE | 50/50 | 2.71 MW | 2.71 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200837 | 26HOMER C1 | 50/50 | 46.62 MW | 46.62 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200838 | 26HOMER C2 | 50/50 | 39.18 MW | 39.18 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200839 | 26HOMER C3 | 50/50 | 41.48 MW | 41.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200846 | 26FORWARD | 50/50 | 0.35 MW | 0.35 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200888 | 26HIGHLAND | 50/50 | 0.78 MW | 0.78 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200889 | 26STNY CRK | 50/50 | 0.59 MW | 0.59 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200894 | 26K02 | Adder | 8.71 MW | 7.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200925 | 26R32 | 50/50 | 0.91 MW | 0.91 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200945 | 26CT_V3-030 | 50/50 | 0.41 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 202158 | 26CON.GEN1 | 50/50 | 0.14 MW | 0.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203999 | P-047 E | Adder | 15.48 MW | 13.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 235003 | AC1-025 E | Adder | 0.23 MW | 0.19 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 236828 | 01GRAYMONT | Adder | 0.61 MW | 0.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916202 | Z1-069 E | Adder | 12.43 MW | 10.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 938951 | AE1-123 | Adder | 3.44 MW | 2.92 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939291 | AE1-160 C | Adder | 2.13 MW | 1.81 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 939292 | AE1-160 E | Adder | 1.22 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940201 | AE2-001 C | Adder | 1.84 MW | 1.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940202 | AE2-001 E | Adder | 1.22 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940681 | AE2-055 C | Adder | 1.8 MW | 1.53 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940682 | AE2-055 E | Adder | 1.2 MW | 1.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940861 | AE2-074 C | Adder | 3.43 MW | 2.92 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 940862 | AE2-074 E | Adder | 4.52 MW | 3.84 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941191 | AE2-113 C | Adder | 13.41 MW | 11.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941192 | AE2-113 E | Adder | 12.58 MW | 10.7 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941231 | AE2-117 C | Adder | 2.45 MW | 2.08 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941232 | AE2-117 E | Adder | 1.63 MW | 1.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941241 | AE2-118 C | Adder | 2.45 MW | 2.08 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941242 | AE2-118 E | Adder | 1.63 MW | 1.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941271 | AE2-121 C | Adder | 0.98 MW | 0.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941272 | AE2-121 E | Adder | 0.65 MW | 0.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941321 | AE2-126 C | Adder | 2.42 MW | 2.06 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941322 | AE2-126 E | Adder | 1.62 MW | 1.37 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941331 | AE2-129 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941332 | AE2-129 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941351 | AE2-131 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941352 | AE2-131 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941421 | AE2-139 C | Adder | 8.98 MW | 7.63 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 941422 | AE2-139 E | Adder | 5.99 MW | 5.09 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946071 | AF1-272 C O1 | 50/50 | 25.73 MW | 25.73 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946072 | AF1-272 E O1 | 50/50 | 17.16 MW | 17.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946111 | AF1-276 C | Adder | 15.41 MW | 13.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946112 | AF1-276 E | Adder | 7.59 MW | 6.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946121 | AF1-277 C | Adder | 15.41 MW | 13.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946122 | AF1-277 E | Adder | 7.59 MW | 6.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946131 | AF1-278 C | Adder | 12.28 MW | 10.44 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946132 | AF1-278 E | Adder | 6.11 MW | 5.19 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946221 | AF1-287 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946222 | AF1-287 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946381 | AF1-302 C | Adder | 3.24 MW | 2.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946382 | AF1-302 E | Adder | 4.33 MW | 3.68 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946571 | AF1-321 C O1 | 50/50 | 4.2 MW | 4.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946572 | AF1-321 E O1 | 50/50 | 2.8 MW | 2.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957001 | AF2-001 C O1 | 50/50 | 4.2 MW | 4.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957002 | AF2-001 E O1 | 50/50 | 2.8 MW | 2.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957011 | AF2-002 C O1 | 50/50 | 2.1 MW | 2.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957012 | AF2-002 E O1 | 50/50 | 1.4 MW | 1.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957161 | AF2-010 C | Adder | 6.88 MW | 5.84 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957162 | AF2-010 E | Adder | 4.63 MW | 3.94 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957451 | AF2-039 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957452 | AF2-039 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957561 | AF2-050 C | 50/50 | 10.9 MW | 10.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957562 | AF2-050 E | 50/50 | 7.27 MW | 7.27 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957931 | AF2-087 C | Adder | 0.88 MW | 0.75 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957932 | AF2-087 E | Adder | 1.21 MW | 1.03 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957941 | AF2-088 C | Adder | 0.81 MW | 0.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957942 | AF2-088 E | Adder | 0.54 MW | 0.46 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957981 | AF2-092 C | 50/50 | 2.4 MW | 2.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 957982 | AF2-092 E | 50/50 | 1.6 MW | 1.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958271 | AF2-121 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958272 | AF2-121 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958361 | AF2-130 C | Adder | 2.21 MW | 1.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 958362 | AF2-130 E | Adder | 1.48 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200833 | 26SEWRDB34 | 50/50 | 35.48 MW | 35.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200886 | 26ARWF_N39 | 50/50 | 0.9 MW | 0.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 203034 | 26NA_O38_P22 | 50/50 | 0.78 MW | 0.78 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 290086 | Q-036 E | Adder | 10.45 MW | 8.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 296332 | R-032 E | 50/50 | 20.69 MW | 20.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 917672 | Z2-108 E | Adder | 4.76 MW | 4.05 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944691 | AF1-134 C O1 | Adder | 3.04 MW | 2.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 944692 | AF1-134 E O1 | Adder | 2.03 MW | 1.72 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200864 | K-013 E | 50/50 | 8.04 MW | 8.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 200883 | Q-053 E | Adder | 9.58 MW | 8.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292350 | K-023 | Adder | 6.59 MW | 5.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 292542 | L-013 1 | Adder | 8.47 MW | 7.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293301 | N-039 E | 50/50 | 20.47 MW | 20.47 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 923443 | AB1-160 E | Adder | 3.55 MW | 3.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293393 | V3-030E | 50/50 | 8.47 MW | 8.47 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293432 | R-040 E | Adder | 0.48 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293603 | O-018 E | 50/50 | 17.93 MW | 17.93 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 293902 | O-048 E | Adder | 7.62 MW | 6.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294515 | O38_P22 | 50/50 | 17.91 MW | 17.91 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 294903 | P-060 E | 50/50 | 13.53 MW | 13.53 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 913142 | Y1-033 E OP1 | Adder | 6.81 MW | 5.79 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946771 | AF1-217 C O2 | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946772 | AF1-217 E O2 | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959301 | AF2-221 C | 50/50 | 2.21 MW | 2.21 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 959302 | AF2-221 E | 50/50 | 3.05 MW | 3.05 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946421 | AF2-000A C | Adder | 8.99 MW | 7.64 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 946422 | AF2-000A E | Adder | 26.98 MW | 22.93 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | 916189 | Z1-066 BAT | Adder | 0.03 MW | 0.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.58 MW | 0.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.97 MW | 0.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.45 MW | 1.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.94 MW | 2.94 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.11 MW | 0.11 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.36 MW | 0.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.17 MW | 0.17 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.57 MW | 0.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.01 MW | 0.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.31 MW | 0.31 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002F | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936991 | AD2-133 C | Adder | 4.1 MW | 3.49 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 936992 | AD2-133 E | Adder | 18.78 MW | 15.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942121 | AE2-224 C | 50/50 | 21.8 MW | 21.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942122 | AE2-224 E | 50/50 | 14.54 MW | 14.54 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942351 | AE2-248 C | Adder | 1.45 MW | 1.23 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942352 | AE2-248 E | Adder | 0.97 MW | 0.82 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942361 | AE2-249 C | 50/50 | 2.71 MW | 2.71 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942362 | AE2-249 E | 50/50 | 1.8 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942491 | AE2-262 C | Adder | 8.21 MW | 6.98 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942492 | AE2-262 E | Adder | 5.52 MW | 4.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942501 | AE2-263 C | Adder | 7.71 MW | 6.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942502 | AE2-263 E | Adder | 5.15 MW | 4.38 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942811 | AE2-299 C | Adder | 4.56 MW | 3.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942812 | AE2-299 E | Adder | 18.24 MW | 15.5 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942961 | AE2-316 C | Adder | 7.43 MW | 6.31 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 942962 | AE2-316 E | Adder | 8.8 MW | 7.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943151 | AE2-344 C | Adder | 9.74 MW | 8.28 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943152 | AE2-344 E | Adder | 6.49 MW | 5.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943351 | AF1-006 C | Adder | 1.69 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943352 | AF1-006 E | Adder | 0.95 MW | 0.81 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943711 | AF1-039 C O1 | Adder | 1.84 MW | 1.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 943712 | AF1-039 E O1 | Adder | 1.23 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944181 | AF1-086 C O1 | Adder | 5.91 MW | 5.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944182 | AF1-086 E O1 | Adder | 25.72 MW | 21.86 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944261 | AF1-094 C | Adder | 1.78 MW | 1.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944262 | AF1-094 E | Adder | 1.19 MW | 1.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944301 | AF1-098 C | Adder | 7.01 MW | 5.96 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944302 | AF1-098 E | Adder | 4.67 MW | 3.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944311 | AF1-099 C | Adder | 12.79 MW | 10.87 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944312 | AF1-099 E | Adder | 8.53 MW | 7.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944321 | AF1-100 C | Adder | 26.49 MW | 22.51 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944322 | AF1-100 E | Adder | 17.66 MW | 15.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944411 | AF1-106 O1 | Adder | 3.58 MW | 3.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944471 | AF1-112 C | Adder | 1.35 MW | 1.15 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944472 | AF1-112 E | Adder | 0.92 MW | 0.79 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944751 | AF1-140 C | 50/50 | 3.24 MW | 3.24 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944752 | AF1-140 E | 50/50 | 2.16 MW | 2.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944771 | AF1-142 C | Adder | 20.46 MW | 17.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944772 | AF1-142 E | Adder | 13.64 MW | 11.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944781 | AF1-143 C | Adder | 15.87 MW | 13.49 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944782 | AF1-143 E | Adder | 10.58 MW | 8.99 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944881 | AF1-153 C O1 | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944882 | AF1-153 E O1 | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944901 | AF1-155 C | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944902 | AF1-155 E | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945021 | AF1-167 C | Adder | 1.34 MW | 1.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945022 | AF1-167 E | Adder | 0.9 MW | 0.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945051 | AF1-170 C | Adder | 6.07 MW | 5.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945052 | AF1-170 E | Adder | 4.05 MW | 3.44 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945121 | AF1-177 | Adder | 0.89 MW | 0.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945161 | AF1-181 | Adder | 0.53 MW | 0.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945171 | AF1-182 | Adder | 0.71 MW | 0.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945181 | AF1-183 | Adder | 0.19 MW | 0.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945331 | AF1-198 | Adder | 0.48 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945451 | AF1-210 C | Adder | 1.47 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945452 | AF1-210 E | Adder | 0.98 MW | 0.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945751 | AF1-240 C O1 | Adder | 2.96 MW | 2.51 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 945752 | AF1-240 E O1 | Adder | 1.97 MW | 1.68 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958471 | AF2-141 | Adder | 2.12 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958731 | AF2-164 C O1 | Adder | 9.46 MW | 8.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958732 | AF2-164 E O1 | Adder | 6.3 MW | 5.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958741 | AF2-165 C | Adder | 2.12 MW | 1.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958742 | AF2-165 E | Adder | 1.42 MW | 1.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958751 | AF2-166 C | Adder | 2.21 MW | 1.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958752 | AF2-166 E | Adder | 1.48 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959441 | AF2-235 C | Adder | 1.01 MW | 0.85 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959442 | AF2-235 E | Adder | 0.67 MW | 0.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959471 | AF2-238 C | Adder | 2.2 MW | 1.87 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959472 | AF2-238 E | Adder | 1.47 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959521 | AF2-243 C | Adder | 1.59 MW | 1.35 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959522 | AF2-243 E | Adder | 1.06 MW | 0.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959802 | AF2-271 E | Adder | 0.82 MW | 0.7 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960022 | AF2-293 E | Adder | 0.18 MW | 0.15 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960031 | AF2-294 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960032 | AF2-294 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960041 | AF2-295 C | Adder | 2.16 MW | 1.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960042 | AF2-295 E | Adder | 1.44 MW | 1.22 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960051 | AF2-296 C | Adder | 3.04 MW | 2.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960052 | AF2-296 E | Adder | 2.03 MW | 1.72 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960451 | AF2-336 C | 50/50 | 4.0 MW | 4.0 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960452 | AF2-336 E | 50/50 | 2.67 MW | 2.67 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960461 | AF2-337 C | 50/50 | 4.0 MW | 4.0 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 960462 | AF2-337 E | 50/50 | 2.67 MW | 2.67 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961141 | AF2-405 | Adder | 1.79 MW | 1.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961151 | AF2-406 | Adder | 13.42 MW | 11.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961211 | AF2-412 | Adder | 27.33 MW | 23.23 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 961451 | AF2-436 | Adder | 0.2 MW | 0.17 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200503 | 26C.SLOPE | 50/50 | 3.09 MW | 3.09 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200636 | 26IUP CO-G | 50/50 | 0.85 MW | 0.85 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200794 | 26CONEMAGH | 50/50 | 0.69 MW | 0.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200809 | 26SITHE | 50/50 | 2.71 MW | 2.71 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200837 | 26HOMER C1 | 50/50 | 46.62 MW | 46.62 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200838 | 26HOMER C2 | 50/50 | 39.18 MW | 39.18 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200839 | 26HOMER C3 | 50/50 | 41.48 MW | 41.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200846 | 26FORWARD | 50/50 | 0.35 MW | 0.35 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200888 | 26HIGHLAND | 50/50 | 0.78 MW | 0.78 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200889 | 26STNY CRK | 50/50 | 0.59 MW | 0.59 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200894 | 26K02 | Adder | 8.71 MW | 7.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200925 | 26R32 | 50/50 | 0.91 MW | 0.91 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200945 | 26CT_V3-030 | 50/50 | 0.41 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 202158 | 26CON.GEN1 | 50/50 | 0.14 MW | 0.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203999 | P-047 E | Adder | 15.48 MW | 13.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 235003 | AC1-025 E | Adder | 0.23 MW | 0.19 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 236828 | 01GRAYMONT | Adder | 0.61 MW | 0.52 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916202 | Z1-069 E | Adder | 12.43 MW | 10.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 938951 | AE1-123 | Adder | 3.44 MW | 2.92 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939291 | AE1-160 C | Adder | 2.13 MW | 1.81 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 939292 | AE1-160 E | Adder | 1.22 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940201 | AE2-001 C | Adder | 1.84 MW | 1.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940202 | AE2-001 E | Adder | 1.22 MW | 1.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940681 | AE2-055 C | Adder | 1.8 MW | 1.53 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940682 | AE2-055 E | Adder | 1.2 MW | 1.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940861 | AE2-074 C | Adder | 3.43 MW | 2.92 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 940862 | AE2-074 E | Adder | 4.52 MW | 3.84 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941191 | AE2-113 C | Adder | 13.41 MW | 11.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941192 | AE2-113 E | Adder | 12.58 MW | 10.7 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941231 | AE2-117 C | Adder | 2.45 MW | 2.08 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941232 | AE2-117 E | Adder | 1.63 MW | 1.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941241 | AE2-118 C | Adder | 2.45 MW | 2.08 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941242 | AE2-118 E | Adder | 1.63 MW | 1.39 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941271 | AE2-121 C | Adder | 0.98 MW | 0.83 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941272 | AE2-121 E | Adder | 0.65 MW | 0.56 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941321 | AE2-126 C | Adder | 2.42 MW | 2.06 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941322 | AE2-126 E | Adder | 1.62 MW | 1.37 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941331 | AE2-129 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941332 | AE2-129 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941351 | AE2-131 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941352 | AE2-131 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941421 | AE2-139 C | Adder | 8.98 MW | 7.63 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 941422 | AE2-139 E | Adder | 5.99 MW | 5.09 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946071 | AF1-272 C O1 | 50/50 | 25.73 MW | 25.73 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946072 | AF1-272 E O1 | 50/50 | 17.16 MW | 17.16 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946111 | AF1-276 C | Adder | 15.41 MW | 13.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946112 | AF1-276 E | Adder | 7.59 MW | 6.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946121 | AF1-277 C | Adder | 15.41 MW | 13.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946122 | AF1-277 E | Adder | 7.59 MW | 6.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946131 | AF1-278 C | Adder | 12.28 MW | 10.44 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946132 | AF1-278 E | Adder | 6.11 MW | 5.19 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946221 | AF1-287 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946222 | AF1-287 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946381 | AF1-302 C | Adder | 3.24 MW | 2.76 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946382 | AF1-302 E | Adder | 4.33 MW | 3.68 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946571 | AF1-321 C O1 | 50/50 | 4.2 MW | 4.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946572 | AF1-321 E O1 | 50/50 | 2.8 MW | 2.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957001 | AF2-001 C O1 | 50/50 | 4.2 MW | 4.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957002 | AF2-001 E O1 | 50/50 | 2.8 MW | 2.8 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957011 | AF2-002 C O1 | 50/50 | 2.1 MW | 2.1 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957012 | AF2-002 E O1 | 50/50 | 1.4 MW | 1.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957161 | AF2-010 C | Adder | 6.88 MW | 5.84 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957162 | AF2-010 E | Adder | 4.63 MW | 3.94 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957451 | AF2-039 C | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957452 | AF2-039 E | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957561 | AF2-050 C | 50/50 | 10.9 MW | 10.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957562 | AF2-050 E | 50/50 | 7.27 MW | 7.27 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957931 | AF2-087 C | Adder | 0.88 MW | 0.75 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957932 | AF2-087 E | Adder | 1.21 MW | 1.03 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957941 | AF2-088 C | Adder | 0.81 MW | 0.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957942 | AF2-088 E | Adder | 0.54 MW | 0.46 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957981 | AF2-092 C | 50/50 | 2.4 MW | 2.4 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 957982 | AF2-092 E | 50/50 | 1.6 MW | 1.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958271 | AF2-121 C | Adder | 2.85 MW | 2.42 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958272 | AF2-121 E | Adder | 1.9 MW | 1.61 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958361 | AF2-130 C | Adder | 2.21 MW | 1.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 958362 | AF2-130 E | Adder | 1.48 MW | 1.25 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200833 | 26SEWRDB34 | 50/50 | 35.48 MW | 35.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200886 | 26ARWF_N39 | 50/50 | 0.9 MW | 0.9 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 203034 | 26NA_O38_P22 | 50/50 | 0.78 MW | 0.78 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 290086 | Q-036 E | Adder | 10.45 MW | 8.88 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 296332 | R-032 E | 50/50 | 20.69 MW | 20.69 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 917672 | Z2-108 E | Adder | 4.76 MW | 4.05 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944691 | AF1-134 C O1 | Adder | 3.04 MW | 2.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 944692 | AF1-134 E O1 | Adder | 2.03 MW | 1.72 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200864 | K-013 E | 50/50 | 8.04 MW | 8.04 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 200883 | Q-053 E | Adder | 9.58 MW | 8.14 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292350 | K-023 | Adder | 6.59 MW | 5.6 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 292542 | L-013 1 | Adder | 8.47 MW | 7.2 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293301 | N-039 E | 50/50 | 20.47 MW | 20.47 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 923443 | AB1-160 E | Adder | 3.55 MW | 3.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293393 | V3-030E | 50/50 | 8.47 MW | 8.47 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293432 | R-040 E | Adder | 0.48 MW | 0.41 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293603 | O-018 E | 50/50 | 17.93 MW | 17.93 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 293902 | O-048 E | Adder | 7.62 MW | 6.48 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294515 | O38_P22 | 50/50 | 17.91 MW | 17.91 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 294903 | P-060 E | 50/50 | 13.53 MW | 13.53 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 913142 | Y1-033 E OP1 | Adder | 6.81 MW | 5.79 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946771 | AF1-217 C O2 | Adder | 1.68 MW | 1.43 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946772 | AF1-217 E O2 | Adder | 1.12 MW | 0.95 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959301 | AF2-221 C | 50/50 | 2.21 MW | 2.21 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 959302 | AF2-221 E | 50/50 | 3.05 MW | 3.05 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946421 | AF2-000A C | Adder | 8.99 MW | 7.64 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 946422 | AF2-000A E | Adder | 26.98 MW | 22.93 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | 916189 | Z1-066 BAT | Adder | 0.03 MW | 0.02 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.58 MW | 0.58 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.97 MW | 0.97 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.45 MW | 1.45 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.94 MW | 2.94 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.11 MW | 0.11 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.36 MW | 0.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.17 MW | 0.17 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.57 MW | 0.57 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.01 MW | 0.01 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.31 MW | 0.31 MW |
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P4-500-002A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 936991 | AD2-133 C | Adder | 1.26 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 936992 | AD2-133 E | Adder | 5.75 MW | 4.89 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942351 | AE2-248 C | Adder | 0.91 MW | 0.77 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942352 | AE2-248 E | Adder | 0.61 MW | 0.52 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942491 | AE2-262 C | 50/50 | 5.56 MW | 5.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942492 | AE2-262 E | 50/50 | 3.74 MW | 3.74 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942501 | AE2-263 C | 50/50 | 5.23 MW | 5.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942502 | AE2-263 E | 50/50 | 3.49 MW | 3.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942961 | AE2-316 C | 50/50 | 4.2 MW | 4.2 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942962 | AE2-316 E | 50/50 | 4.98 MW | 4.98 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944311 | AF1-099 C | 50/50 | 8.86 MW | 8.86 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944312 | AF1-099 E | 50/50 | 5.9 MW | 5.9 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944321 | AF1-100 C | 50/50 | 18.22 MW | 18.22 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944322 | AF1-100 E | 50/50 | 12.15 MW | 12.15 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944471 | AF1-112 C | Adder | 0.85 MW | 0.72 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944472 | AF1-112 E | Adder | 0.58 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944771 | AF1-142 C | 50/50 | 14.17 MW | 14.17 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944772 | AF1-142 E | 50/50 | 9.45 MW | 9.45 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944881 | AF1-153 C O1 | 50/50 | 1.62 MW | 1.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944882 | AF1-153 E O1 | 50/50 | 1.08 MW | 1.08 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944901 | AF1-155 C | 50/50 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944902 | AF1-155 E | 50/50 | 1.07 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 945121 | AF1-177 | Adder | -2.69 MW | -2.28 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 945161 | AF1-181 | 50/50 | 0.36 MW | 0.36 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 945171 | AF1-182 | 50/50 | 0.49 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 945181 | AF1-183 | 50/50 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 945331 | AF1-198 | Adder | 0.19 MW | 0.16 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 959471 | AF2-238 C | Adder | 0.83 MW | 0.7 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 959472 | AF2-238 E | Adder | 0.55 MW | 0.47 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 959802 | AF2-271 E | Adder | 0.22 MW | 0.18 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 960022 | AF2-293 E | Adder | 0.11 MW | 0.1 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 960041 | AF2-295 C | 50/50 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 960042 | AF2-295 E | 50/50 | 1.07 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 960051 | AF2-296 C | Adder | 0.96 MW | 0.82 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 960052 | AF2-296 E | Adder | 0.64 MW | 0.55 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 961211 | AF2-412 | Adder | 9.43 MW | 8.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200642 | 26SENECA#1 | 50/50 | 14.07 MW | 14.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200643 | 26SENECA#2 | 50/50 | 12.61 MW | 12.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200644 | 26SENECA#3 | 50/50 | 1.32 MW | 1.32 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200649 | 26PENNTECH | 50/50 | 1.34 MW | 1.34 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200665 | 26SHAWVL 3 | 50/50 | 3.65 MW | 3.65 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200666 | 26SHAWVL 4 | 50/50 | 3.63 MW | 3.63 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200715 | 26SHAWVL 1 | 50/50 | 2.5 MW | 2.5 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200722 | 26SHAWVL 2 | 50/50 | 2.56 MW | 2.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200894 | 26K02 | Adder | 4.47 MW | 3.8 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 200913 | 26SHAW-D | 50/50 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 203349 | 26Z1-069 C | 50/50 | 0.26 MW | 0.26 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 203999 | P-047 E | Adder | 5.55 MW | 4.72 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 235003 | AC1-025 E | Adder | 0.14 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 236828 | 01GRAYMONT | Adder | 0.39 MW | 0.33 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 916202 | Z1-069 E | 50/50 | 6.41 MW | 6.41 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940201 | AE2-001 C | Adder | 1.17 MW | 0.99 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940202 | AE2-001 E | Adder | 0.78 MW | 0.66 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940681 | AE2-055 C | Adder | 1.12 MW | 0.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940682 | AE2-055 E | Adder | 0.74 MW | 0.63 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940861 | AE2-074 C | 50/50 | 2.23 MW | 2.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 940862 | AE2-074 E | 50/50 | 2.93 MW | 2.93 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941191 | AE2-113 C | 50/50 | 10.93 MW | 10.93 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941192 | AE2-113 E | 50/50 | 10.26 MW | 10.26 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941271 | AE2-121 C | Adder | 0.62 MW | 0.53 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941272 | AE2-121 E | Adder | 0.42 MW | 0.35 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941321 | AE2-126 C | 50/50 | 1.76 MW | 1.76 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941322 | AE2-126 E | 50/50 | 1.17 MW | 1.17 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941331 | AE2-129 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941332 | AE2-129 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941351 | AE2-131 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 941352 | AE2-131 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946111 | AF1-276 C | 50/50 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946112 | AF1-276 E | 50/50 | 7.4 MW | 7.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946121 | AF1-277 C | 50/50 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946122 | AF1-277 E | 50/50 | 7.4 MW | 7.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946131 | AF1-278 C | 50/50 | 11.97 MW | 11.97 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946132 | AF1-278 E | 50/50 | 5.95 MW | 5.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946381 | AF1-302 C | 50/50 | 1.84 MW | 1.84 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946382 | AF1-302 E | 50/50 | 2.45 MW | 2.45 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 957451 | AF2-039 C | 50/50 | 0.91 MW | 0.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 957452 | AF2-039 E | 50/50 | 0.61 MW | 0.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 957941 | AF2-088 C | 50/50 | 0.44 MW | 0.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 957942 | AF2-088 E | 50/50 | 0.29 MW | 0.29 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 958271 | AF2-121 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 958272 | AF2-121 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 290086 | Q-036 E | Adder | 3.2 MW | 2.72 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944691 | AF1-134 C O1 | Adder | 0.96 MW | 0.82 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944692 | AF1-134 E O1 | Adder | 0.64 MW | 0.55 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 923442 | AB1-160 C | 50/50 | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 923443 | AB1-160 E | 50/50 | 1.83 MW | 1.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946421 | AF2-000A C | 50/50 | 7.99 MW | 7.99 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 946422 | AF2-000A E | 50/50 | 23.97 MW | 23.97 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 942813 | AE2-299 BAT | 50/50 | 29.66 MW | 29.66 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | 944392 | AF1-104 BAT | 50/50 | 3.1 MW | 3.1 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.44 MW | 1.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.3 MW | 2.3 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 4.13 MW | 4.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 11.33 MW | 11.33 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.35 MW | 3.35 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.27 MW | 0.27 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.49 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.87 MW | 0.87 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.05 MW | 0.05 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.73 MW | 0.73 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.74 MW | 0.74 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B10 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 936991 | AD2-133 C | Adder | 1.25 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 936992 | AD2-133 E | Adder | 5.74 MW | 4.88 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942351 | AE2-248 C | Adder | 0.91 MW | 0.77 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942352 | AE2-248 E | Adder | 0.61 MW | 0.52 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942491 | AE2-262 C | 50/50 | 5.56 MW | 5.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942492 | AE2-262 E | 50/50 | 3.73 MW | 3.73 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942501 | AE2-263 C | 50/50 | 5.22 MW | 5.22 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942502 | AE2-263 E | 50/50 | 3.49 MW | 3.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942961 | AE2-316 C | 50/50 | 4.2 MW | 4.2 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942962 | AE2-316 E | 50/50 | 4.97 MW | 4.97 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944311 | AF1-099 C | 50/50 | 8.85 MW | 8.85 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944312 | AF1-099 E | 50/50 | 5.9 MW | 5.9 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944321 | AF1-100 C | 50/50 | 18.21 MW | 18.21 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944322 | AF1-100 E | 50/50 | 12.14 MW | 12.14 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944471 | AF1-112 C | Adder | 0.85 MW | 0.72 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944472 | AF1-112 E | Adder | 0.58 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944771 | AF1-142 C | 50/50 | 14.16 MW | 14.16 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944772 | AF1-142 E | 50/50 | 9.44 MW | 9.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944881 | AF1-153 C O1 | 50/50 | 1.62 MW | 1.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944882 | AF1-153 E O1 | 50/50 | 1.08 MW | 1.08 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944901 | AF1-155 C | 50/50 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944902 | AF1-155 E | 50/50 | 1.07 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945121 | AF1-177 | Adder | -2.69 MW | -2.28 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945161 | AF1-181 | 50/50 | 0.36 MW | 0.36 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945171 | AF1-182 | 50/50 | 0.49 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945181 | AF1-183 | 50/50 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 945331 | AF1-198 | Adder | 0.19 MW | 0.16 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 959471 | AF2-238 C | Adder | 0.83 MW | 0.7 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 959472 | AF2-238 E | Adder | 0.55 MW | 0.47 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 959802 | AF2-271 E | Adder | 0.22 MW | 0.18 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960022 | AF2-293 E | Adder | 0.11 MW | 0.1 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960041 | AF2-295 C | 50/50 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960042 | AF2-295 E | 50/50 | 1.07 MW | 1.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960051 | AF2-296 C | Adder | 0.96 MW | 0.82 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 960052 | AF2-296 E | Adder | 0.64 MW | 0.54 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 961211 | AF2-412 | Adder | 9.43 MW | 8.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200642 | 26SENECA#1 | 50/50 | 14.07 MW | 14.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200643 | 26SENECA#2 | 50/50 | 12.6 MW | 12.6 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200644 | 26SENECA#3 | 50/50 | 1.32 MW | 1.32 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200649 | 26PENNTECH | 50/50 | 1.34 MW | 1.34 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200665 | 26SHAWVL 3 | 50/50 | 3.65 MW | 3.65 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200666 | 26SHAWVL 4 | 50/50 | 3.63 MW | 3.63 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200715 | 26SHAWVL 1 | 50/50 | 2.5 MW | 2.5 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200722 | 26SHAWVL 2 | 50/50 | 2.56 MW | 2.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200894 | 26K02 | Adder | 4.46 MW | 3.79 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 200913 | 26SHAW-D | 50/50 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 203349 | 26Z1-069 C | 50/50 | 0.26 MW | 0.26 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 203999 | P-047 E | Adder | 5.54 MW | 4.71 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 235003 | AC1-025 E | Adder | 0.14 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 236828 | 01GRAYMONT | Adder | 0.39 MW | 0.33 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 916202 | Z1-069 E | 50/50 | 6.41 MW | 6.41 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940201 | AE2-001 C | Adder | 1.17 MW | 0.99 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940202 | AE2-001 E | Adder | 0.78 MW | 0.66 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940681 | AE2-055 C | Adder | 1.12 MW | 0.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940682 | AE2-055 E | Adder | 0.74 MW | 0.63 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940861 | AE2-074 C | 50/50 | 2.23 MW | 2.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 940862 | AE2-074 E | 50/50 | 2.93 MW | 2.93 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941191 | AE2-113 C | 50/50 | 10.93 MW | 10.93 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941192 | AE2-113 E | 50/50 | 10.25 MW | 10.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941271 | AE2-121 C | Adder | 0.62 MW | 0.53 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941272 | AE2-121 E | Adder | 0.42 MW | 0.35 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941321 | AE2-126 C | 50/50 | 1.76 MW | 1.76 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941322 | AE2-126 E | 50/50 | 1.17 MW | 1.17 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941331 | AE2-129 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941332 | AE2-129 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941351 | AE2-131 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 941352 | AE2-131 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946111 | AF1-276 C | 50/50 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946112 | AF1-276 E | 50/50 | 7.4 MW | 7.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946121 | AF1-277 C | 50/50 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946122 | AF1-277 E | 50/50 | 7.4 MW | 7.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946131 | AF1-278 C | 50/50 | 11.97 MW | 11.97 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946132 | AF1-278 E | 50/50 | 5.95 MW | 5.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946381 | AF1-302 C | 50/50 | 1.83 MW | 1.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946382 | AF1-302 E | 50/50 | 2.44 MW | 2.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957451 | AF2-039 C | 50/50 | 0.91 MW | 0.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957452 | AF2-039 E | 50/50 | 0.61 MW | 0.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957941 | AF2-088 C | 50/50 | 0.44 MW | 0.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 957942 | AF2-088 E | 50/50 | 0.29 MW | 0.29 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 958271 | AF2-121 C | Adder | 1.13 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 958272 | AF2-121 E | Adder | 0.76 MW | 0.64 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 290086 | Q-036 E | Adder | 3.2 MW | 2.72 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944691 | AF1-134 C O1 | Adder | 0.96 MW | 0.82 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944692 | AF1-134 E O1 | Adder | 0.64 MW | 0.54 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 923442 | AB1-160 C | 50/50 | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 923443 | AB1-160 E | 50/50 | 1.83 MW | 1.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946421 | AF2-000A C | 50/50 | 7.99 MW | 7.99 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 946422 | AF2-000A E | 50/50 | 23.96 MW | 23.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 942813 | AE2-299 BAT | 50/50 | 29.65 MW | 29.65 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | 944392 | AF1-104 BAT | 50/50 | 3.1 MW | 3.1 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.44 MW | 1.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.3 MW | 2.3 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 4.13 MW | 4.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 11.32 MW | 11.32 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.34 MW | 3.34 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.27 MW | 0.27 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.49 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.87 MW | 0.87 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.05 MW | 0.05 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.73 MW | 0.73 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.74 MW | 0.74 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P2-3-PN-345-003A-B45 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 936991 | AD2-133 C | 80/20 | 1.15 MW | 1.15 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 942351 | AE2-248 C | 80/20 | 0.87 MW | 0.87 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 942491 | AE2-262 C | 80/20 | 5.34 MW | 5.34 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 942501 | AE2-263 C | 80/20 | 5.02 MW | 5.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 942961 | AE2-316 C | 80/20 | 3.71 MW | 3.71 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944311 | AF1-099 C | 80/20 | 8.53 MW | 8.53 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944321 | AF1-100 C | 80/20 | 17.58 MW | 17.58 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944411 | AF1-106 O1 | 80/20 | 1.12 MW | 1.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944471 | AF1-112 C | 80/20 | 0.81 MW | 0.81 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944771 | AF1-142 C | 80/20 | 13.65 MW | 13.65 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944881 | AF1-153 C O1 | 80/20 | 1.56 MW | 1.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944901 | AF1-155 C | 80/20 | 1.55 MW | 1.55 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 945121 | AF1-177 | Adder | -2.63 MW | -2.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 945161 | AF1-181 | 80/20 | 0.35 MW | 0.35 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 945171 | AF1-182 | 80/20 | 0.47 MW | 0.47 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 945181 | AF1-183 | 80/20 | 0.11 MW | 0.11 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 945331 | AF1-198 | 80/20 | 0.17 MW | 0.17 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 959471 | AF2-238 C | 80/20 | 0.75 MW | 0.75 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 960031 | AF2-294 C | 80/20 | 0.53 MW | 0.53 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 960041 | AF2-295 C | 80/20 | 1.55 MW | 1.55 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 960051 | AF2-296 C | 80/20 | 0.89 MW | 0.89 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 961141 | AF2-405 | 80/20 | 0.56 MW | 0.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 961151 | AF2-406 | 80/20 | 4.21 MW | 4.21 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 961211 | AF2-412 | 80/20 | 8.49 MW | 8.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 961451 | AF2-436 | 80/20 | 0.08 MW | 0.08 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200642 | 26SENECA#1 | 80/20 | 14.3 MW | 14.3 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200643 | 26SENECA#2 | 80/20 | 12.81 MW | 12.81 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200644 | 26SENECA#3 | 80/20 | 1.34 MW | 1.34 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200649 | 26PENNTECH | 80/20 | 1.32 MW | 1.32 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200665 | 26SHAWVL 3 | 80/20 | 3.52 MW | 3.52 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200666 | 26SHAWVL 4 | 80/20 | 3.51 MW | 3.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200715 | 26SHAWVL 1 | 80/20 | 2.4 MW | 2.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200722 | 26SHAWVL 2 | 80/20 | 2.46 MW | 2.46 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200887 | 26ARMNA MT | 80/20 | 0.22 MW | 0.22 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200913 | 26SHAW-D | 80/20 | 0.11 MW | 0.11 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203261 | 26BLOSSBCT | 80/20 | 0.23 MW | 0.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203283 | 26MANOR_T86 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203349 | 26Z1-069 C | 80/20 | 0.25 MW | 0.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203350 | 26MILZ1-092 | 80/20 | 0.2 MW | 0.2 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203351 | 26GROZ1-110 | 80/20 | 0.23 MW | 0.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 203352 | 26CANZ2-011 | 80/20 | 0.23 MW | 0.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 940201 | AE2-001 C | 80/20 | 1.11 MW | 1.11 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 940681 | AE2-055 C | 80/20 | 1.06 MW | 1.06 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 940861 | AE2-074 C | 80/20 | 2.16 MW | 2.16 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941191 | AE2-113 C | 80/20 | 10.74 MW | 10.74 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941271 | AE2-121 C | 80/20 | 0.6 MW | 0.6 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941321 | AE2-126 C | 80/20 | 1.71 MW | 1.71 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941331 | AE2-129 C | 80/20 | 1.06 MW | 1.06 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941351 | AE2-131 C | 80/20 | 1.06 MW | 1.06 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 941421 | AE2-139 C | 80/20 | 3.61 MW | 3.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 946111 | AF1-276 C | 80/20 | 14.95 MW | 14.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 946121 | AF1-277 C | 80/20 | 14.95 MW | 14.95 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 946131 | AF1-278 C | 80/20 | 11.91 MW | 11.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 946381 | AF1-302 C | 80/20 | 1.62 MW | 1.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 957451 | AF2-039 C | 80/20 | 0.87 MW | 0.87 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 957941 | AF2-088 C | 80/20 | 0.42 MW | 0.42 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 958271 | AF2-121 C | 80/20 | 1.06 MW | 1.06 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 920351 | AA2-133 | 80/20 | 0.18 MW | 0.18 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 934801 | AD1-108 | 80/20 | 0.02 MW | 0.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 934811 | AD1-109 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 935061 | AD1-142 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 944691 | AF1-134 C O1 | 80/20 | 0.89 MW | 0.89 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200949 | 26X1-109 | 80/20 | 7.46 MW | 7.46 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 923442 | AB1-160 C | 80/20 | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 946421 | AF2-000A C | 80/20 | 7.83 MW | 7.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | 200905 | 26Q36 | 80/20 | 0.13 MW | 0.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.17 MW | 1.17 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.86 MW | 1.86 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 3.41 MW | 3.41 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 9.37 MW | 9.37 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.71 MW | 2.71 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.22 MW | 0.22 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.42 MW | 0.42 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.4 MW | 0.4 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.71 MW | 0.71 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.05 MW | 0.05 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.59 MW | 0.59 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.42 MW | 0.42 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.06 MW | 0.06 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.6 MW | 0.6 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o Base Case | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
Details for 26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 936991 | AD2-133 C | 80/20 | 1.25 MW | 1.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 942351 | AE2-248 C | 80/20 | 0.91 MW | 0.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 942491 | AE2-262 C | 80/20 | 5.55 MW | 5.55 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 942501 | AE2-263 C | 80/20 | 5.22 MW | 5.22 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 942961 | AE2-316 C | 80/20 | 4.19 MW | 4.19 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944181 | AF1-086 C O1 | 80/20 | 1.14 MW | 1.14 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944311 | AF1-099 C | 80/20 | 8.84 MW | 8.84 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944321 | AF1-100 C | 80/20 | 18.19 MW | 18.19 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944411 | AF1-106 O1 | 80/20 | 1.23 MW | 1.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944471 | AF1-112 C | 80/20 | 0.85 MW | 0.85 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944771 | AF1-142 C | 80/20 | 14.15 MW | 14.15 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944881 | AF1-153 C O1 | 80/20 | 1.62 MW | 1.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944901 | AF1-155 C | 80/20 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 945121 | AF1-177 | Adder | -2.69 MW | -2.28 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 945161 | AF1-181 | 80/20 | 0.36 MW | 0.36 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 945171 | AF1-182 | 80/20 | 0.48 MW | 0.48 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 945181 | AF1-183 | 80/20 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 945331 | AF1-198 | 80/20 | 0.19 MW | 0.19 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 959471 | AF2-238 C | 80/20 | 0.83 MW | 0.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 960031 | AF2-294 C | 80/20 | 0.58 MW | 0.58 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 960041 | AF2-295 C | 80/20 | 1.61 MW | 1.61 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 960051 | AF2-296 C | 80/20 | 0.96 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 961141 | AF2-405 | 80/20 | 0.62 MW | 0.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 961151 | AF2-406 | 80/20 | 4.62 MW | 4.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 961211 | AF2-412 | 80/20 | 9.42 MW | 9.42 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 961451 | AF2-436 | 80/20 | 0.08 MW | 0.08 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200642 | 26SENECA#1 | 80/20 | 14.07 MW | 14.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200643 | 26SENECA#2 | 80/20 | 12.6 MW | 12.6 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200644 | 26SENECA#3 | 80/20 | 1.32 MW | 1.32 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200649 | 26PENNTECH | 80/20 | 1.33 MW | 1.33 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200665 | 26SHAWVL 3 | 80/20 | 3.65 MW | 3.65 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200666 | 26SHAWVL 4 | 80/20 | 3.63 MW | 3.63 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200715 | 26SHAWVL 1 | 80/20 | 2.5 MW | 2.5 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200722 | 26SHAWVL 2 | 80/20 | 2.56 MW | 2.56 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200851 | 26MEHOOP3 | 80/20 | 0.52 MW | 0.52 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200887 | 26ARMNA MT | 80/20 | 0.24 MW | 0.24 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200913 | 26SHAW-D | 80/20 | 0.12 MW | 0.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200917 | 26MTNTP_P28 | 80/20 | 0.26 MW | 0.26 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203261 | 26BLOSSBCT | 80/20 | 0.25 MW | 0.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203283 | 26MANOR_T86 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203347 | 26NME_Y1-047 | 80/20 | 0.23 MW | 0.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203349 | 26Z1-069 C | 80/20 | 0.26 MW | 0.26 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203350 | 26MILZ1-092 | 80/20 | 0.21 MW | 0.21 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203351 | 26GROZ1-110 | 80/20 | 0.25 MW | 0.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 203352 | 26CANZ2-011 | 80/20 | 0.25 MW | 0.25 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 940201 | AE2-001 C | 80/20 | 1.16 MW | 1.16 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 940681 | AE2-055 C | 80/20 | 1.11 MW | 1.11 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 940861 | AE2-074 C | 80/20 | 2.23 MW | 2.23 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941191 | AE2-113 C | 80/20 | 10.92 MW | 10.92 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941271 | AE2-121 C | 80/20 | 0.62 MW | 0.62 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941321 | AE2-126 C | 80/20 | 1.75 MW | 1.75 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941331 | AE2-129 C | 80/20 | 1.13 MW | 1.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941351 | AE2-131 C | 80/20 | 1.13 MW | 1.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 941421 | AE2-139 C | 80/20 | 3.91 MW | 3.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 946111 | AF1-276 C | 80/20 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 946121 | AF1-277 C | 80/20 | 15.02 MW | 15.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 946131 | AF1-278 C | 80/20 | 11.97 MW | 11.97 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 946381 | AF1-302 C | 80/20 | 1.83 MW | 1.83 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 957451 | AF2-039 C | 80/20 | 0.91 MW | 0.91 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 957941 | AF2-088 C | 80/20 | 0.44 MW | 0.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 958271 | AF2-121 C | 80/20 | 1.13 MW | 1.13 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 920351 | AA2-133 | 80/20 | 0.19 MW | 0.19 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 934801 | AD1-108 | 80/20 | 0.02 MW | 0.02 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 934811 | AD1-109 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 934821 | AD1-110 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 935061 | AD1-142 | 80/20 | 0.01 MW | 0.01 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 944691 | AF1-134 C O1 | 80/20 | 0.96 MW | 0.96 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200949 | 26X1-109 | 80/20 | 8.15 MW | 8.15 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 923442 | AB1-160 C | 80/20 | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 946421 | AF2-000A C | 80/20 | 7.98 MW | 7.98 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | 200905 | 26Q36 | 80/20 | 0.14 MW | 0.14 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.44 MW | 1.44 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.29 MW | 2.29 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 4.12 MW | 4.12 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 11.29 MW | 11.29 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.33 MW | 3.33 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.27 MW | 0.27 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.49 MW | 0.49 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.87 MW | 0.87 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.05 MW | 0.05 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.73 MW | 0.73 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.51 MW | 0.51 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.07 MW | 0.07 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.74 MW | 0.74 MW |
26GLADE-26WARREN 230.0 kV Ckt 1 line l/o PN-P1-2-PN-345-003 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
Details for 26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942811 | AE2-299 C | Adder | 5.42 MW | 4.61 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942812 | AE2-299 E | Adder | 21.67 MW | 18.42 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942961 | AE2-316 C | Adder | 6.63 MW | 5.63 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943151 | AE2-344 C | Adder | 11.43 MW | 9.72 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943152 | AE2-344 E | Adder | 7.62 MW | 6.48 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944262 | AF1-094 E | Adder | 1.27 MW | 1.08 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944302 | AF1-098 E | Adder | 5.37 MW | 4.57 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944311 | AF1-099 C | Adder | 6.96 MW | 5.92 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944312 | AF1-099 E | Adder | 4.64 MW | 3.94 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944321 | AF1-100 C | Adder | 14.05 MW | 11.94 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944322 | AF1-100 E | Adder | 9.37 MW | 7.96 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.77 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944771 | AF1-142 C | Adder | 11.14 MW | 9.47 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944772 | AF1-142 E | Adder | 7.43 MW | 6.31 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945052 | AF1-170 E | Adder | 4.82 MW | 4.1 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945161 | AF1-181 | Adder | 0.27 MW | 0.23 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945171 | AF1-182 | Adder | 0.36 MW | 0.31 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958731 | AF2-164 C O1 | Adder | 12.08 MW | 10.27 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958732 | AF2-164 E O1 | Adder | 8.06 MW | 6.85 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959471 | AF2-238 C | Adder | 2.7 MW | 2.29 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960032 | AF2-294 E | Adder | 1.39 MW | 1.19 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961141 | AF2-405 | Adder | 2.22 MW | 1.89 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961151 | AF2-406 | Adder | 16.63 MW | 14.13 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961211 | AF2-412 | 50/50 | 34.93 MW | 34.93 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200823 | 26MHP_X3-003 | Adder | 8.38 MW | 7.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200829 | 26HNSMLK 2 | 50/50 | 2.36 MW | 2.36 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200830 | 26HNSMLK 3 | 50/50 | 2.36 MW | 2.36 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200831 | 26HNSMLK 4 | 50/50 | 2.36 MW | 2.36 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200832 | 26HNSMLK 5 | 50/50 | 2.36 MW | 2.36 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200838 | 26HOMER C2 | 50/50 | 56.44 MW | 56.44 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200839 | 26HOMER C3 | 50/50 | 59.74 MW | 59.74 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203907 | 26Y2-042 | Adder | 1.76 MW | 1.5 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203999 | P-047 E | Adder | 19.43 MW | 16.52 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 916202 | Z1-069 E | 50/50 | 15.41 MW | 15.41 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 938951 | AE1-123 | Adder | 2.31 MW | 1.96 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 940861 | AE2-074 C | 50/50 | 4.16 MW | 4.16 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 940862 | AE2-074 E | 50/50 | 5.47 MW | 5.47 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941191 | AE2-113 C | Adder | 13.74 MW | 11.68 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941192 | AE2-113 E | Adder | 12.89 MW | 10.96 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941321 | AE2-126 C | Adder | 1.34 MW | 1.14 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941422 | AE2-139 E | Adder | 6.68 MW | 5.67 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946111 | AF1-276 C | 50/50 | 18.52 MW | 18.52 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946112 | AF1-276 E | 50/50 | 9.12 MW | 9.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946121 | AF1-277 C | 50/50 | 18.52 MW | 18.52 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946122 | AF1-277 E | 50/50 | 9.12 MW | 9.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946131 | AF1-278 C | 50/50 | 14.76 MW | 14.76 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946132 | AF1-278 E | 50/50 | 7.34 MW | 7.34 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946381 | AF1-302 C | Adder | 2.9 MW | 2.46 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 917672 | Z2-108 E | Adder | -2.26 MW | -1.93 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 923443 | AB1-160 E | 50/50 | 4.4 MW | 4.4 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 294573 | P-028 E | Adder | 15.93 MW | 13.54 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946422 | AF2-000A E | Adder | 19.8 MW | 16.83 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 917673 | Z2-108 BAT | Adder | 2.66 MW | 2.27 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958472 | AF2-141 BAT | Adder | 2.96 MW | 2.52 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.03 MW | 0.03 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.93 MW | 4.93 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.89 MW | 0.89 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.15 MW | 0.15 MW |
26HOMER CY-STAR599 345.0/1.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 3.82 MW | 3.82 MW |
Details for STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942811 | AE2-299 C | Adder | 5.42 MW | 4.61 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942812 | AE2-299 E | Adder | 21.67 MW | 18.42 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942961 | AE2-316 C | Adder | 6.63 MW | 5.63 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943151 | AE2-344 C | Adder | 11.43 MW | 9.72 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943152 | AE2-344 E | Adder | 7.62 MW | 6.48 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944262 | AF1-094 E | Adder | 1.27 MW | 1.08 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944302 | AF1-098 E | Adder | 5.37 MW | 4.57 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944311 | AF1-099 C | Adder | 6.96 MW | 5.92 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944312 | AF1-099 E | Adder | 4.64 MW | 3.94 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944321 | AF1-100 C | Adder | 14.05 MW | 11.94 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944322 | AF1-100 E | Adder | 9.37 MW | 7.96 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.77 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944771 | AF1-142 C | Adder | 11.14 MW | 9.47 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944772 | AF1-142 E | Adder | 7.43 MW | 6.31 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945052 | AF1-170 E | Adder | 4.82 MW | 4.1 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945161 | AF1-181 | Adder | 0.27 MW | 0.23 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945171 | AF1-182 | Adder | 0.36 MW | 0.31 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958731 | AF2-164 C O1 | Adder | 12.08 MW | 10.27 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958732 | AF2-164 E O1 | Adder | 8.06 MW | 6.85 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959471 | AF2-238 C | Adder | 2.7 MW | 2.29 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960032 | AF2-294 E | Adder | 1.39 MW | 1.19 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961141 | AF2-405 | Adder | 2.22 MW | 1.89 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961151 | AF2-406 | Adder | 16.63 MW | 14.13 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961211 | AF2-412 | 50/50 | 34.93 MW | 34.93 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200823 | 26MHP_X3-003 | Adder | 8.38 MW | 7.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200829 | 26HNSMLK 2 | 50/50 | 2.36 MW | 2.36 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200830 | 26HNSMLK 3 | 50/50 | 2.36 MW | 2.36 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200831 | 26HNSMLK 4 | 50/50 | 2.36 MW | 2.36 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200832 | 26HNSMLK 5 | 50/50 | 2.36 MW | 2.36 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200838 | 26HOMER C2 | 50/50 | 56.44 MW | 56.44 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200839 | 26HOMER C3 | 50/50 | 59.74 MW | 59.74 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203907 | 26Y2-042 | Adder | 1.76 MW | 1.5 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 203999 | P-047 E | Adder | 19.43 MW | 16.52 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 916202 | Z1-069 E | 50/50 | 15.41 MW | 15.41 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 938951 | AE1-123 | Adder | 2.31 MW | 1.96 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 940861 | AE2-074 C | 50/50 | 4.16 MW | 4.16 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 940862 | AE2-074 E | 50/50 | 5.47 MW | 5.47 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941191 | AE2-113 C | Adder | 13.74 MW | 11.68 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941192 | AE2-113 E | Adder | 12.89 MW | 10.96 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941321 | AE2-126 C | Adder | 1.34 MW | 1.14 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 941422 | AE2-139 E | Adder | 6.68 MW | 5.67 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946111 | AF1-276 C | 50/50 | 18.52 MW | 18.52 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946112 | AF1-276 E | 50/50 | 9.12 MW | 9.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946121 | AF1-277 C | 50/50 | 18.52 MW | 18.52 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946122 | AF1-277 E | 50/50 | 9.12 MW | 9.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946131 | AF1-278 C | 50/50 | 14.76 MW | 14.76 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946132 | AF1-278 E | 50/50 | 7.34 MW | 7.34 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946381 | AF1-302 C | Adder | 2.9 MW | 2.46 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 917672 | Z2-108 E | Adder | -2.26 MW | -1.93 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 923443 | AB1-160 E | 50/50 | 4.4 MW | 4.4 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 294573 | P-028 E | Adder | 15.93 MW | 13.54 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 946422 | AF2-000A E | Adder | 19.8 MW | 16.83 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 917673 | Z2-108 BAT | Adder | 2.66 MW | 2.27 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | 958472 | AF2-141 BAT | Adder | 2.96 MW | 2.52 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.03 MW | 0.03 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.93 MW | 4.93 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.89 MW | 0.89 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.15 MW | 0.15 MW |
STAR599-26HOMER CT 1.0/230.0 kV Ckt N transformer l/o PN-P2-3-PN-230-9E | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 3.82 MW | 3.82 MW |
Details for 26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 936991 | AD2-133 C | 80/20 | 1.03 MW | 1.03 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942351 | AE2-248 C | 80/20 | 0.74 MW | 0.74 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942491 | AE2-262 C | 80/20 | 4.92 MW | 4.92 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942501 | AE2-263 C | 80/20 | 4.63 MW | 4.63 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942811 | AE2-299 C | 80/20 | 2.02 MW | 2.02 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 942961 | AE2-316 C | 80/20 | 3.04 MW | 3.04 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944301 | AF1-098 C | 80/20 | 2.89 MW | 2.89 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944311 | AF1-099 C | 80/20 | 8.01 MW | 8.01 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944321 | AF1-100 C | 80/20 | 15.37 MW | 15.37 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944411 | AF1-106 O1 | 80/20 | 4.98 MW | 4.98 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944471 | AF1-112 C | 80/20 | 0.69 MW | 0.69 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944771 | AF1-142 C | 80/20 | 12.82 MW | 12.82 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944881 | AF1-153 C O1 | 80/20 | 1.08 MW | 1.08 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944901 | AF1-155 C | 80/20 | 1.07 MW | 1.07 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945121 | AF1-177 | 80/20 | 0.39 MW | 0.39 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945161 | AF1-181 | 80/20 | 0.3 MW | 0.3 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945171 | AF1-182 | 80/20 | 0.4 MW | 0.4 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945181 | AF1-183 | 80/20 | 0.09 MW | 0.09 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 945331 | AF1-198 | 80/20 | 0.62 MW | 0.62 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 959471 | AF2-238 C | 80/20 | 3.07 MW | 3.07 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 960041 | AF2-295 C | 80/20 | 1.07 MW | 1.07 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 960051 | AF2-296 C | 80/20 | 0.84 MW | 0.84 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961141 | AF2-405 | 80/20 | 2.49 MW | 2.49 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961151 | AF2-406 | 80/20 | 18.68 MW | 18.68 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961211 | AF2-412 | 80/20 | 27.42 MW | 27.42 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961451 | AF2-436 | 80/20 | 0.16 MW | 0.16 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 961461 | AF2-437 | Adder | -0.26 MW | -0.22 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200642 | 26SENECA#1 | 80/20 | 3.52 MW | 3.52 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200643 | 26SENECA#2 | 80/20 | 3.15 MW | 3.15 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200644 | 26SENECA#3 | 80/20 | 0.33 MW | 0.33 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200649 | 26PENNTECH | 80/20 | 0.71 MW | 0.71 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200665 | 26SHAWVL 3 | 80/20 | 2.99 MW | 2.99 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200666 | 26SHAWVL 4 | 80/20 | 2.95 MW | 2.95 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200715 | 26SHAWVL 1 | 80/20 | 2.0 MW | 2.0 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200722 | 26SHAWVL 2 | 80/20 | 2.04 MW | 2.04 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200839 | 26HOMER C3 | 80/20 | 6.58 MW | 6.58 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200887 | 26ARMNA MT | 80/20 | 0.82 MW | 0.82 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200913 | 26SHAW-D | 80/20 | 0.09 MW | 0.09 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203261 | 26BLOSSBCT | 80/20 | 0.82 MW | 0.82 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203283 | 26MANOR_T86 | 80/20 | 0.06 MW | 0.06 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203349 | 26Z1-069 C | 80/20 | 0.4 MW | 0.4 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203350 | 26MILZ1-092 | 80/20 | 0.87 MW | 0.87 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203351 | 26GROZ1-110 | 80/20 | 1.07 MW | 1.07 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 203352 | 26CANZ2-011 | 80/20 | 1.07 MW | 1.07 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940201 | AE2-001 C | 80/20 | 0.96 MW | 0.96 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940681 | AE2-055 C | 80/20 | 0.9 MW | 0.9 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 940861 | AE2-074 C | 80/20 | 2.03 MW | 2.03 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941191 | AE2-113 C | 80/20 | 6.24 MW | 6.24 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941271 | AE2-121 C | 80/20 | 0.52 MW | 0.52 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941321 | AE2-126 C | 80/20 | 1.1 MW | 1.1 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941331 | AE2-129 C | 80/20 | 0.91 MW | 0.91 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941351 | AE2-131 C | 80/20 | 0.91 MW | 0.91 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 941421 | AE2-139 C | 80/20 | 22.45 MW | 22.45 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946111 | AF1-276 C | 80/20 | 6.41 MW | 6.41 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946121 | AF1-277 C | 80/20 | 6.41 MW | 6.41 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946131 | AF1-278 C | 80/20 | 5.11 MW | 5.11 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946381 | AF1-302 C | 80/20 | 1.33 MW | 1.33 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 957451 | AF2-039 C | 80/20 | 0.71 MW | 0.71 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 957941 | AF2-088 C | 80/20 | 0.34 MW | 0.34 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 958271 | AF2-121 C | 80/20 | 0.91 MW | 0.91 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 920351 | AA2-133 | 80/20 | 0.38 MW | 0.38 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 934801 | AD1-108 | 80/20 | 0.08 MW | 0.08 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 934811 | AD1-109 | 80/20 | 0.06 MW | 0.06 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 935061 | AD1-142 | 80/20 | 0.05 MW | 0.05 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 944691 | AF1-134 C O1 | 80/20 | 0.84 MW | 0.84 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200949 | 26X1-109 | 80/20 | 52.41 MW | 52.41 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 923442 | AB1-160 C | 80/20 | 0.11 MW | 0.11 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 946421 | AF2-000A C | 80/20 | 4.71 MW | 4.71 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 201201 | 26WRREN CT | 80/20 | 0.78 MW | 0.78 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | 200905 | 26Q36 | 80/20 | 0.12 MW | 0.12 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.58 MW | 0.58 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.38 MW | 0.38 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 7.83 MW | 7.83 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.25 MW | 1.25 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.9 MW | 3.9 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.79 MW | 7.79 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.61 MW | 1.61 MW |
26E.TWANDA-26CANYON 230.0 kV Ckt 1 line l/o Base Case | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.7 MW | 13.7 MW |
Details for 26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 942811 | AE2-299 C | 50/50 | 13.86 MW | 13.86 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 942812 | AE2-299 E | 50/50 | 55.42 MW | 55.42 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 944301 | AF1-098 C | 50/50 | 21.85 MW | 21.85 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 944302 | AF1-098 E | 50/50 | 14.57 MW | 14.57 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 944411 | AF1-106 O1 | Adder | 1.16 MW | 0.99 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 945121 | AF1-177 | 50/50 | 0.77 MW | 0.77 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 945331 | AF1-198 | Adder | 0.13 MW | 0.11 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 959471 | AF2-238 C | Adder | 0.61 MW | 0.52 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 959472 | AF2-238 E | Adder | 0.41 MW | 0.35 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 960031 | AF2-294 C | Adder | 0.57 MW | 0.48 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 960032 | AF2-294 E | Adder | 0.38 MW | 0.32 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 961141 | AF2-405 | Adder | 0.58 MW | 0.49 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 961151 | AF2-406 | Adder | 4.36 MW | 3.71 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 961211 | AF2-412 | Adder | 7.03 MW | 5.97 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 200642 | 26SENECA#1 | 50/50 | 4.33 MW | 4.33 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 200643 | 26SENECA#2 | 50/50 | 3.87 MW | 3.87 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 200644 | 26SENECA#3 | 50/50 | 0.41 MW | 0.41 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 203999 | P-047 E | Adder | 4.18 MW | 3.55 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 916202 | Z1-069 E | Adder | 3.53 MW | 3.0 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 940861 | AE2-074 C | Adder | 1.05 MW | 0.89 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 940862 | AE2-074 E | Adder | 1.38 MW | 1.17 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 941191 | AE2-113 C | Adder | 4.22 MW | 3.59 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 941192 | AE2-113 E | Adder | 3.96 MW | 3.37 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946111 | AF1-276 C | Adder | 5.76 MW | 4.89 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946112 | AF1-276 E | Adder | 2.84 MW | 2.41 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946121 | AF1-277 C | Adder | 5.76 MW | 4.89 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946122 | AF1-277 E | Adder | 2.84 MW | 2.41 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946131 | AF1-278 C | Adder | 4.59 MW | 3.9 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946132 | AF1-278 E | Adder | 2.28 MW | 1.94 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 923443 | AB1-160 E | Adder | 1.01 MW | 0.86 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946421 | AF2-000A C | Adder | 2.6 MW | 2.21 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 946422 | AF2-000A E | Adder | 7.8 MW | 6.63 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 201201 | 26WRREN CT | 50/50 | 1.53 MW | 1.53 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | 944392 | AF1-104 BAT | Adder | 1.29 MW | 1.1 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.64 MW | 0.64 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.02 MW | 1.02 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 2.02 MW | 2.02 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.59 MW | 5.59 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | AA3-300 | LTFEXP_AA3-300->LTFIMP_AA3-300 | LTF | 5.27 MW | 5.27 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.48 MW | 1.48 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.12 MW | 0.12 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.23 MW | 0.23 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.22 MW | 0.22 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.38 MW | 0.38 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.32 MW | 0.32 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.23 MW | 0.23 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.33 MW | 0.33 MW |
26FOURMILE-26ERIE SE 115.0 kV Ckt 1 line l/o PN-P2-3-PN-230-6G | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
Details for 26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 936991 | AD2-133 C | Adder | 2.2 MW | 1.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 936992 | AD2-133 E | Adder | 10.06 MW | 8.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942121 | AE2-224 C | 50/50 | 11.11 MW | 11.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942122 | AE2-224 E | 50/50 | 7.41 MW | 7.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942351 | AE2-248 C | Adder | 0.81 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942361 | AE2-249 C | 50/50 | 1.43 MW | 1.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942362 | AE2-249 E | 50/50 | 0.95 MW | 0.95 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942491 | AE2-262 C | Adder | 4.62 MW | 3.93 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942492 | AE2-262 E | Adder | 3.1 MW | 2.64 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942501 | AE2-263 C | Adder | 4.34 MW | 3.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942502 | AE2-263 E | Adder | 2.9 MW | 2.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942811 | AE2-299 C | Adder | 2.62 MW | 2.22 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942812 | AE2-299 E | Adder | 10.46 MW | 8.89 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942961 | AE2-316 C | Adder | 4.24 MW | 3.6 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 942962 | AE2-316 E | Adder | 5.02 MW | 4.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943151 | AE2-344 C | Adder | 5.57 MW | 4.74 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943152 | AE2-344 E | Adder | 3.71 MW | 3.16 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943351 | AF1-006 C | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943352 | AF1-006 E | Adder | 0.54 MW | 0.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943711 | AF1-039 C O1 | Adder | 0.97 MW | 0.83 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 943712 | AF1-039 E O1 | Adder | 0.65 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944181 | AF1-086 C O1 | Adder | 3.3 MW | 2.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944182 | AF1-086 E O1 | Adder | 14.34 MW | 12.19 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944261 | AF1-094 C | Adder | 1.02 MW | 0.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944262 | AF1-094 E | Adder | 0.68 MW | 0.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944301 | AF1-098 C | Adder | 4.02 MW | 3.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944302 | AF1-098 E | Adder | 2.68 MW | 2.27 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944311 | AF1-099 C | Adder | 7.22 MW | 6.13 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944312 | AF1-099 E | Adder | 4.81 MW | 4.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944321 | AF1-100 C | Adder | 14.93 MW | 12.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944322 | AF1-100 E | Adder | 9.95 MW | 8.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944411 | AF1-106 O1 | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944472 | AF1-112 E | Adder | 0.52 MW | 0.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944751 | AF1-140 C | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944752 | AF1-140 E | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944771 | AF1-142 C | Adder | 11.55 MW | 9.81 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944772 | AF1-142 E | Adder | 7.7 MW | 6.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944781 | AF1-143 C | Adder | 8.44 MW | 7.17 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944782 | AF1-143 E | Adder | 5.63 MW | 4.78 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945021 | AF1-167 C | Adder | 0.76 MW | 0.65 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945022 | AF1-167 E | Adder | 0.51 MW | 0.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945051 | AF1-170 C | Adder | 3.47 MW | 2.95 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945052 | AF1-170 E | Adder | 2.31 MW | 1.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945121 | AF1-177 | Adder | 0.52 MW | 0.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945161 | AF1-181 | Adder | 0.3 MW | 0.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945171 | AF1-182 | Adder | 0.4 MW | 0.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945181 | AF1-183 | Adder | 0.11 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945331 | AF1-198 | Adder | 0.28 MW | 0.24 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945451 | AF1-210 C | Adder | 0.83 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945452 | AF1-210 E | Adder | 0.56 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945751 | AF1-240 C O1 | Adder | 1.67 MW | 1.42 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 945752 | AF1-240 E O1 | Adder | 1.11 MW | 0.94 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958471 | AF2-141 | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958731 | AF2-164 C O1 | Adder | 5.48 MW | 4.66 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958732 | AF2-164 E O1 | Adder | 3.66 MW | 3.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958741 | AF2-165 C | Adder | 1.21 MW | 1.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958742 | AF2-165 E | Adder | 0.81 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958751 | AF2-166 C | Adder | 1.26 MW | 1.07 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958752 | AF2-166 E | Adder | 0.84 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959441 | AF2-235 C | Adder | 0.57 MW | 0.49 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959442 | AF2-235 E | Adder | 0.38 MW | 0.33 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959471 | AF2-238 C | Adder | 1.3 MW | 1.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959472 | AF2-238 E | Adder | 0.87 MW | 0.74 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959521 | AF2-243 C | Adder | 0.91 MW | 0.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959522 | AF2-243 E | Adder | 0.61 MW | 0.52 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959802 | AF2-271 E | Adder | 0.44 MW | 0.37 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960022 | AF2-293 E | Adder | 0.1 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960031 | AF2-294 C | Adder | 0.99 MW | 0.84 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960032 | AF2-294 E | Adder | 0.66 MW | 0.56 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960051 | AF2-296 C | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960052 | AF2-296 E | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960451 | AF2-336 C | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960452 | AF2-336 E | Adder | 1.41 MW | 1.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960461 | AF2-337 C | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 960462 | AF2-337 E | Adder | 1.41 MW | 1.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961141 | AF2-405 | Adder | 1.06 MW | 0.9 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961151 | AF2-406 | Adder | 7.91 MW | 6.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961211 | AF2-412 | Adder | 16.1 MW | 13.68 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 961451 | AF2-436 | Adder | 0.12 MW | 0.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200636 | 26IUP CO-G | 50/50 | 0.51 MW | 0.51 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200794 | 26CONEMAGH | 50/50 | 0.35 MW | 0.35 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200805 | 26COLVER13 | 50/50 | 3.15 MW | 3.15 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200809 | 26SITHE | 50/50 | 1.6 MW | 1.6 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200837 | 26HOMER C1 | 50/50 | 27.61 MW | 27.61 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200838 | 26HOMER C2 | 50/50 | 23.13 MW | 23.13 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200839 | 26HOMER C3 | 50/50 | 24.49 MW | 24.49 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200846 | 26FORWARD | 50/50 | 0.19 MW | 0.19 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200888 | 26HIGHLAND | 50/50 | 0.41 MW | 0.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200894 | 26K02 | Adder | 5.07 MW | 4.31 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200925 | 26R32 | 50/50 | 0.47 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 203999 | P-047 E | Adder | 9.13 MW | 7.76 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 235003 | AC1-025 E | Adder | 0.13 MW | 0.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 916202 | Z1-069 E | Adder | 7.29 MW | 6.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 938951 | AE1-123 | Adder | 1.95 MW | 1.66 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 939291 | AE1-160 C | Adder | 1.21 MW | 1.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 939292 | AE1-160 E | Adder | 0.7 MW | 0.59 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940201 | AE2-001 C | Adder | 1.03 MW | 0.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940202 | AE2-001 E | Adder | 0.69 MW | 0.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940681 | AE2-055 C | Adder | 1.0 MW | 0.85 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940682 | AE2-055 E | Adder | 0.67 MW | 0.57 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940861 | AE2-074 C | Adder | 2.01 MW | 1.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 940862 | AE2-074 E | Adder | 2.64 MW | 2.24 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941191 | AE2-113 C | Adder | 7.74 MW | 6.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941192 | AE2-113 E | Adder | 7.27 MW | 6.18 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941231 | AE2-117 C | Adder | 1.28 MW | 1.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941232 | AE2-117 E | Adder | 0.86 MW | 0.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941241 | AE2-118 C | Adder | 1.28 MW | 1.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941242 | AE2-118 E | Adder | 0.86 MW | 0.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941271 | AE2-121 C | Adder | 0.55 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941272 | AE2-121 E | Adder | 0.37 MW | 0.31 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941321 | AE2-126 C | Adder | 1.37 MW | 1.16 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941322 | AE2-126 E | Adder | 0.91 MW | 0.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941331 | AE2-129 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941332 | AE2-129 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941351 | AE2-131 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941352 | AE2-131 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941421 | AE2-139 C | Adder | 5.29 MW | 4.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 941422 | AE2-139 E | Adder | 3.53 MW | 3.0 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946071 | AF1-272 C O1 | 50/50 | 15.81 MW | 15.81 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946072 | AF1-272 E O1 | 50/50 | 10.54 MW | 10.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946111 | AF1-276 C | Adder | 8.97 MW | 7.62 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946112 | AF1-276 E | Adder | 4.42 MW | 3.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946121 | AF1-277 C | Adder | 8.97 MW | 7.62 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946122 | AF1-277 E | Adder | 4.42 MW | 3.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946131 | AF1-278 C | Adder | 7.15 MW | 6.08 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946132 | AF1-278 E | Adder | 3.56 MW | 3.02 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946221 | AF1-287 C | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946222 | AF1-287 E | Adder | 0.64 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946382 | AF1-302 E | Adder | 2.47 MW | 2.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946571 | AF1-321 C O1 | 50/50 | 2.25 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946572 | AF1-321 E O1 | 50/50 | 1.5 MW | 1.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957001 | AF2-001 C O1 | 50/50 | 2.25 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957002 | AF2-001 E O1 | 50/50 | 1.5 MW | 1.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957011 | AF2-002 C O1 | 50/50 | 1.12 MW | 1.12 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957012 | AF2-002 E O1 | 50/50 | 0.75 MW | 0.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957161 | AF2-010 C | Adder | 3.93 MW | 3.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957162 | AF2-010 E | Adder | 2.65 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957451 | AF2-039 C | Adder | 0.94 MW | 0.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957452 | AF2-039 E | Adder | 0.62 MW | 0.53 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957561 | AF2-050 C | 50/50 | 5.55 MW | 5.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957562 | AF2-050 E | 50/50 | 3.7 MW | 3.7 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957931 | AF2-087 C | Adder | 0.46 MW | 0.39 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957932 | AF2-087 E | Adder | 0.63 MW | 0.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957941 | AF2-088 C | Adder | 0.45 MW | 0.38 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957942 | AF2-088 E | Adder | 0.3 MW | 0.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957981 | AF2-092 C | Adder | 1.27 MW | 1.08 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 957982 | AF2-092 E | Adder | 0.84 MW | 0.72 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958271 | AF2-121 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958272 | AF2-121 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958361 | AF2-130 C | Adder | 1.26 MW | 1.07 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 958362 | AF2-130 E | Adder | 0.84 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200833 | 26SEWRDB34 | 50/50 | 16.68 MW | 16.68 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200906 | 26KEYSTN#3 | 50/50 | 0.85 MW | 0.85 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 290086 | Q-036 E | Adder | 5.6 MW | 4.76 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 296332 | R-032 E | 50/50 | 10.78 MW | 10.78 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 917672 | Z2-108 E | Adder | 2.53 MW | 2.15 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944691 | AF1-134 C O1 | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 944692 | AF1-134 E O1 | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200864 | K-013 E | 50/50 | 4.29 MW | 4.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 200883 | Q-053 E | Adder | 5.0 MW | 4.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 292350 | K-023 | Adder | 3.5 MW | 2.98 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 292542 | L-013 1 | Adder | 4.5 MW | 3.83 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293301 | N-039 E | Adder | 10.49 MW | 8.91 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 923443 | AB1-160 E | Adder | 2.08 MW | 1.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293393 | V3-030E | Adder | 4.56 MW | 3.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293603 | O-018 E | 50/50 | 9.34 MW | 9.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 293902 | O-048 E | Adder | 4.05 MW | 3.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 294515 | O38_P22 | Adder | 9.18 MW | 7.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 294903 | P-060 E | Adder | 7.19 MW | 6.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 913142 | Y1-033 E OP1 | Adder | 3.6 MW | 3.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946771 | AF1-217 C O2 | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946772 | AF1-217 E O2 | Adder | 0.64 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959301 | AF2-221 C | 50/50 | 1.17 MW | 1.17 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 959302 | AF2-221 E | 50/50 | 1.61 MW | 1.61 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946421 | AF2-000A C | Adder | 5.11 MW | 4.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 946422 | AF2-000A E | Adder | 15.33 MW | 13.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | 916189 | Z1-066 BAT | Adder | 0.01 MW | 0.01 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.56 MW | 0.56 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.94 MW | 0.94 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.06 MW | 0.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.43 MW | 0.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.38 MW | 1.38 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.1 MW | 0.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.3 MW | 0.3 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.18 MW | 0.18 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.29 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.3 MW | 0.3 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.22 MW | 0.22 MW |
Details for 26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 936991 | AD2-133 C | Adder | 2.2 MW | 1.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 936992 | AD2-133 E | Adder | 10.06 MW | 8.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942121 | AE2-224 C | 50/50 | 11.11 MW | 11.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942122 | AE2-224 E | 50/50 | 7.41 MW | 7.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942351 | AE2-248 C | Adder | 0.81 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942352 | AE2-248 E | Adder | 0.54 MW | 0.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942361 | AE2-249 C | 50/50 | 1.43 MW | 1.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942362 | AE2-249 E | 50/50 | 0.95 MW | 0.95 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942491 | AE2-262 C | Adder | 4.62 MW | 3.93 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942492 | AE2-262 E | Adder | 3.1 MW | 2.64 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942501 | AE2-263 C | Adder | 4.34 MW | 3.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942502 | AE2-263 E | Adder | 2.9 MW | 2.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942811 | AE2-299 C | Adder | 2.62 MW | 2.22 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942812 | AE2-299 E | Adder | 10.46 MW | 8.89 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942961 | AE2-316 C | Adder | 4.24 MW | 3.6 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 942962 | AE2-316 E | Adder | 5.02 MW | 4.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943151 | AE2-344 C | Adder | 5.57 MW | 4.74 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943152 | AE2-344 E | Adder | 3.71 MW | 3.16 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943351 | AF1-006 C | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943352 | AF1-006 E | Adder | 0.54 MW | 0.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943711 | AF1-039 C O1 | Adder | 0.97 MW | 0.83 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 943712 | AF1-039 E O1 | Adder | 0.65 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944181 | AF1-086 C O1 | Adder | 3.3 MW | 2.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944182 | AF1-086 E O1 | Adder | 14.34 MW | 12.19 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944261 | AF1-094 C | Adder | 1.02 MW | 0.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944262 | AF1-094 E | Adder | 0.68 MW | 0.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944301 | AF1-098 C | Adder | 4.02 MW | 3.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944302 | AF1-098 E | Adder | 2.68 MW | 2.27 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944311 | AF1-099 C | Adder | 7.22 MW | 6.13 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944312 | AF1-099 E | Adder | 4.81 MW | 4.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944321 | AF1-100 C | Adder | 14.93 MW | 12.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944322 | AF1-100 E | Adder | 9.95 MW | 8.46 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944411 | AF1-106 O1 | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944471 | AF1-112 C | Adder | 0.75 MW | 0.64 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944472 | AF1-112 E | Adder | 0.52 MW | 0.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944751 | AF1-140 C | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944752 | AF1-140 E | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944771 | AF1-142 C | Adder | 11.55 MW | 9.81 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944772 | AF1-142 E | Adder | 7.7 MW | 6.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944781 | AF1-143 C | Adder | 8.44 MW | 7.17 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944782 | AF1-143 E | Adder | 5.63 MW | 4.78 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944881 | AF1-153 C O1 | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944882 | AF1-153 E O1 | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944901 | AF1-155 C | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944902 | AF1-155 E | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945021 | AF1-167 C | Adder | 0.76 MW | 0.65 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945022 | AF1-167 E | Adder | 0.51 MW | 0.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945051 | AF1-170 C | Adder | 3.47 MW | 2.95 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945052 | AF1-170 E | Adder | 2.31 MW | 1.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945121 | AF1-177 | Adder | 0.52 MW | 0.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945161 | AF1-181 | Adder | 0.3 MW | 0.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945171 | AF1-182 | Adder | 0.4 MW | 0.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945181 | AF1-183 | Adder | 0.11 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945331 | AF1-198 | Adder | 0.28 MW | 0.24 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945451 | AF1-210 C | Adder | 0.83 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945452 | AF1-210 E | Adder | 0.56 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945751 | AF1-240 C O1 | Adder | 1.67 MW | 1.42 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 945752 | AF1-240 E O1 | Adder | 1.11 MW | 0.94 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958471 | AF2-141 | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958731 | AF2-164 C O1 | Adder | 5.48 MW | 4.66 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958732 | AF2-164 E O1 | Adder | 3.66 MW | 3.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958741 | AF2-165 C | Adder | 1.21 MW | 1.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958742 | AF2-165 E | Adder | 0.81 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958751 | AF2-166 C | Adder | 1.26 MW | 1.07 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958752 | AF2-166 E | Adder | 0.84 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959441 | AF2-235 C | Adder | 0.57 MW | 0.49 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959442 | AF2-235 E | Adder | 0.38 MW | 0.33 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959471 | AF2-238 C | Adder | 1.3 MW | 1.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959472 | AF2-238 E | Adder | 0.87 MW | 0.74 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959521 | AF2-243 C | Adder | 0.91 MW | 0.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959522 | AF2-243 E | Adder | 0.61 MW | 0.52 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959802 | AF2-271 E | Adder | 0.44 MW | 0.37 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960022 | AF2-293 E | Adder | 0.1 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960031 | AF2-294 C | Adder | 0.99 MW | 0.84 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960032 | AF2-294 E | Adder | 0.66 MW | 0.56 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960041 | AF2-295 C | Adder | 1.23 MW | 1.04 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960042 | AF2-295 E | Adder | 0.82 MW | 0.69 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960051 | AF2-296 C | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960052 | AF2-296 E | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960451 | AF2-336 C | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960452 | AF2-336 E | Adder | 1.41 MW | 1.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960461 | AF2-337 C | Adder | 2.11 MW | 1.79 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 960462 | AF2-337 E | Adder | 1.41 MW | 1.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961141 | AF2-405 | Adder | 1.06 MW | 0.9 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961151 | AF2-406 | Adder | 7.91 MW | 6.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961211 | AF2-412 | Adder | 16.1 MW | 13.68 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 961451 | AF2-436 | Adder | 0.12 MW | 0.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200636 | 26IUP CO-G | 50/50 | 0.51 MW | 0.51 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200794 | 26CONEMAGH | 50/50 | 0.35 MW | 0.35 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200805 | 26COLVER13 | 50/50 | 3.15 MW | 3.15 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200809 | 26SITHE | 50/50 | 1.6 MW | 1.6 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200837 | 26HOMER C1 | 50/50 | 27.61 MW | 27.61 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200838 | 26HOMER C2 | 50/50 | 23.13 MW | 23.13 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200839 | 26HOMER C3 | 50/50 | 24.49 MW | 24.49 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200846 | 26FORWARD | 50/50 | 0.19 MW | 0.19 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200888 | 26HIGHLAND | 50/50 | 0.41 MW | 0.41 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200894 | 26K02 | Adder | 5.07 MW | 4.31 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200925 | 26R32 | 50/50 | 0.47 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 202158 | 26CON.GEN1 | 50/50 | 0.09 MW | 0.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 202160 | 26CON.GEN2 | 50/50 | 0.06 MW | 0.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 203999 | P-047 E | Adder | 9.13 MW | 7.76 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 235003 | AC1-025 E | Adder | 0.13 MW | 0.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 236828 | 01GRAYMONT | Adder | 0.34 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 916202 | Z1-069 E | Adder | 7.29 MW | 6.2 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 938951 | AE1-123 | Adder | 1.95 MW | 1.66 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 939291 | AE1-160 C | Adder | 1.21 MW | 1.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 939292 | AE1-160 E | Adder | 0.7 MW | 0.59 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940201 | AE2-001 C | Adder | 1.03 MW | 0.87 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940202 | AE2-001 E | Adder | 0.69 MW | 0.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940681 | AE2-055 C | Adder | 1.0 MW | 0.85 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940682 | AE2-055 E | Adder | 0.67 MW | 0.57 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940861 | AE2-074 C | Adder | 2.01 MW | 1.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 940862 | AE2-074 E | Adder | 2.64 MW | 2.24 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941191 | AE2-113 C | Adder | 7.74 MW | 6.58 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941192 | AE2-113 E | Adder | 7.27 MW | 6.18 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941231 | AE2-117 C | Adder | 1.28 MW | 1.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941232 | AE2-117 E | Adder | 0.86 MW | 0.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941241 | AE2-118 C | Adder | 1.28 MW | 1.09 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941242 | AE2-118 E | Adder | 0.86 MW | 0.73 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941271 | AE2-121 C | Adder | 0.55 MW | 0.47 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941272 | AE2-121 E | Adder | 0.37 MW | 0.31 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941321 | AE2-126 C | Adder | 1.37 MW | 1.16 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941322 | AE2-126 E | Adder | 0.91 MW | 0.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941331 | AE2-129 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941332 | AE2-129 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941351 | AE2-131 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941352 | AE2-131 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941421 | AE2-139 C | Adder | 5.29 MW | 4.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 941422 | AE2-139 E | Adder | 3.53 MW | 3.0 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946071 | AF1-272 C O1 | 50/50 | 15.81 MW | 15.81 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946072 | AF1-272 E O1 | 50/50 | 10.54 MW | 10.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946111 | AF1-276 C | Adder | 8.97 MW | 7.62 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946112 | AF1-276 E | Adder | 4.42 MW | 3.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946121 | AF1-277 C | Adder | 8.97 MW | 7.62 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946122 | AF1-277 E | Adder | 4.42 MW | 3.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946131 | AF1-278 C | Adder | 7.15 MW | 6.08 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946132 | AF1-278 E | Adder | 3.56 MW | 3.02 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946221 | AF1-287 C | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946222 | AF1-287 E | Adder | 0.64 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946381 | AF1-302 C | Adder | 1.85 MW | 1.57 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946382 | AF1-302 E | Adder | 2.47 MW | 2.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946571 | AF1-321 C O1 | 50/50 | 2.25 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946572 | AF1-321 E O1 | 50/50 | 1.5 MW | 1.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957001 | AF2-001 C O1 | 50/50 | 2.25 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957002 | AF2-001 E O1 | 50/50 | 1.5 MW | 1.5 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957011 | AF2-002 C O1 | 50/50 | 1.12 MW | 1.12 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957012 | AF2-002 E O1 | 50/50 | 0.75 MW | 0.75 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957161 | AF2-010 C | Adder | 3.93 MW | 3.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957162 | AF2-010 E | Adder | 2.65 MW | 2.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957451 | AF2-039 C | Adder | 0.94 MW | 0.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957452 | AF2-039 E | Adder | 0.62 MW | 0.53 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957561 | AF2-050 C | 50/50 | 5.55 MW | 5.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957562 | AF2-050 E | 50/50 | 3.7 MW | 3.7 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957931 | AF2-087 C | Adder | 0.46 MW | 0.39 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957932 | AF2-087 E | Adder | 0.63 MW | 0.54 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957941 | AF2-088 C | Adder | 0.45 MW | 0.38 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957942 | AF2-088 E | Adder | 0.3 MW | 0.26 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957981 | AF2-092 C | Adder | 1.27 MW | 1.08 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 957982 | AF2-092 E | Adder | 0.84 MW | 0.72 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958271 | AF2-121 C | Adder | 1.55 MW | 1.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958272 | AF2-121 E | Adder | 1.03 MW | 0.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958361 | AF2-130 C | Adder | 1.26 MW | 1.07 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 958362 | AF2-130 E | Adder | 0.84 MW | 0.71 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200833 | 26SEWRDB34 | 50/50 | 16.68 MW | 16.68 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200906 | 26KEYSTN#3 | 50/50 | 0.85 MW | 0.85 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 290086 | Q-036 E | Adder | 5.6 MW | 4.76 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 296332 | R-032 E | 50/50 | 10.78 MW | 10.78 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 917672 | Z2-108 E | Adder | 2.53 MW | 2.15 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944691 | AF1-134 C O1 | Adder | 1.7 MW | 1.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 944692 | AF1-134 E O1 | Adder | 1.13 MW | 0.96 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200864 | K-013 E | 50/50 | 4.29 MW | 4.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 200883 | Q-053 E | Adder | 5.0 MW | 4.25 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 292350 | K-023 | Adder | 3.5 MW | 2.98 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 292542 | L-013 1 | Adder | 4.5 MW | 3.83 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293301 | N-039 E | Adder | 10.49 MW | 8.91 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 923443 | AB1-160 E | Adder | 2.08 MW | 1.77 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293393 | V3-030E | Adder | 4.56 MW | 3.88 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293432 | R-040 E | Adder | 0.25 MW | 0.21 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293603 | O-018 E | 50/50 | 9.34 MW | 9.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 293902 | O-048 E | Adder | 4.05 MW | 3.44 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 294515 | O38_P22 | Adder | 9.18 MW | 7.8 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 294903 | P-060 E | Adder | 7.19 MW | 6.11 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 913142 | Y1-033 E OP1 | Adder | 3.6 MW | 3.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946771 | AF1-217 C O2 | Adder | 0.96 MW | 0.82 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946772 | AF1-217 E O2 | Adder | 0.64 MW | 0.55 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959301 | AF2-221 C | 50/50 | 1.17 MW | 1.17 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 959302 | AF2-221 E | 50/50 | 1.61 MW | 1.61 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946421 | AF2-000A C | Adder | 5.11 MW | 4.34 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 946422 | AF2-000A E | Adder | 15.33 MW | 13.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | 916189 | Z1-066 BAT | Adder | 0.01 MW | 0.01 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.56 MW | 0.56 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.94 MW | 0.94 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.06 MW | 0.06 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.43 MW | 0.43 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.38 MW | 1.38 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.1 MW | 0.1 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.3 MW | 0.3 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.18 MW | 0.18 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.32 MW | 0.32 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.29 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.29 MW | 0.29 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.03 MW | 0.03 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.3 MW | 0.3 MW |
26KEYSTONE-STAR592 230.0/1.0 kV Ckt 4 transformer l/o PJM500_PN_P4-500-001D | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.22 MW | 0.22 MW |
Details for STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942811 | AE2-299 C | Adder | 5.42 MW | 4.6 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942812 | AE2-299 E | Adder | 21.66 MW | 18.41 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942961 | AE2-316 C | Adder | 6.62 MW | 5.63 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943151 | AE2-344 C | Adder | 11.43 MW | 9.71 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943152 | AE2-344 E | Adder | 7.62 MW | 6.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944262 | AF1-094 E | Adder | 1.26 MW | 1.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944302 | AF1-098 E | Adder | 5.37 MW | 4.56 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944311 | AF1-099 C | Adder | 6.99 MW | 5.94 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944312 | AF1-099 E | Adder | 4.66 MW | 3.96 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944321 | AF1-100 C | Adder | 14.1 MW | 11.98 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944322 | AF1-100 E | Adder | 9.4 MW | 7.99 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944771 | AF1-142 C | Adder | 11.18 MW | 9.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944772 | AF1-142 E | Adder | 7.45 MW | 6.33 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945052 | AF1-170 E | Adder | 4.82 MW | 4.09 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945161 | AF1-181 | Adder | 0.28 MW | 0.23 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945171 | AF1-182 | Adder | 0.37 MW | 0.31 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958731 | AF2-164 C O1 | Adder | 12.06 MW | 10.25 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958732 | AF2-164 E O1 | Adder | 8.04 MW | 6.83 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959471 | AF2-238 C | Adder | 2.69 MW | 2.29 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960032 | AF2-294 E | Adder | 1.39 MW | 1.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961141 | AF2-405 | Adder | 2.21 MW | 1.88 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961151 | AF2-406 | Adder | 16.6 MW | 14.11 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961211 | AF2-412 | 50/50 | 34.84 MW | 34.84 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200823 | 26MHP_X3-003 | Adder | 8.39 MW | 7.13 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200829 | 26HNSMLK 2 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200830 | 26HNSMLK 3 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200831 | 26HNSMLK 4 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200832 | 26HNSMLK 5 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200838 | 26HOMER C2 | 50/50 | 56.21 MW | 56.21 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200839 | 26HOMER C3 | 50/50 | 59.51 MW | 59.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203907 | 26Y2-042 | Adder | 1.77 MW | 1.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203999 | P-047 E | Adder | 19.39 MW | 16.48 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 916202 | Z1-069 E | 50/50 | 15.37 MW | 15.37 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 938951 | AE1-123 | Adder | 2.31 MW | 1.97 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 940861 | AE2-074 C | 50/50 | 4.14 MW | 4.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 940862 | AE2-074 E | 50/50 | 5.46 MW | 5.46 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941191 | AE2-113 C | Adder | 13.71 MW | 11.65 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941192 | AE2-113 E | Adder | 12.87 MW | 10.94 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941422 | AE2-139 E | Adder | 6.67 MW | 5.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946111 | AF1-276 C | 50/50 | 18.47 MW | 18.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946112 | AF1-276 E | 50/50 | 9.1 MW | 9.1 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946121 | AF1-277 C | 50/50 | 18.47 MW | 18.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946122 | AF1-277 E | 50/50 | 9.1 MW | 9.1 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946131 | AF1-278 C | 50/50 | 14.72 MW | 14.72 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946132 | AF1-278 E | 50/50 | 7.32 MW | 7.32 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946381 | AF1-302 C | Adder | 2.89 MW | 2.46 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 917672 | Z2-108 E | Adder | -2.24 MW | -1.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 923443 | AB1-160 E | 50/50 | 4.39 MW | 4.39 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 294573 | P-028 E | Adder | 15.94 MW | 13.55 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946422 | AF2-000A E | Adder | 19.81 MW | 16.84 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 917673 | Z2-108 BAT | Adder | 2.63 MW | 2.24 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958472 | AF2-141 BAT | Adder | 2.92 MW | 2.49 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.56 MW | 0.56 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.34 MW | 4.34 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.8 MW | 0.8 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.29 MW | 0.29 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.83 MW | 4.83 MW |
Details for STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942811 | AE2-299 C | Adder | 5.42 MW | 4.6 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942812 | AE2-299 E | Adder | 21.66 MW | 18.41 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942961 | AE2-316 C | Adder | 6.62 MW | 5.63 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943151 | AE2-344 C | Adder | 11.43 MW | 9.71 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943152 | AE2-344 E | Adder | 7.62 MW | 6.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944262 | AF1-094 E | Adder | 1.26 MW | 1.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944302 | AF1-098 E | Adder | 5.37 MW | 4.56 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944311 | AF1-099 C | Adder | 6.99 MW | 5.94 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944312 | AF1-099 E | Adder | 4.66 MW | 3.96 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944321 | AF1-100 C | Adder | 14.1 MW | 11.98 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944322 | AF1-100 E | Adder | 9.4 MW | 7.99 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944771 | AF1-142 C | Adder | 11.18 MW | 9.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944772 | AF1-142 E | Adder | 7.45 MW | 6.33 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945052 | AF1-170 E | Adder | 4.82 MW | 4.09 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945161 | AF1-181 | Adder | 0.28 MW | 0.23 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945171 | AF1-182 | Adder | 0.37 MW | 0.31 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958731 | AF2-164 C O1 | Adder | 12.06 MW | 10.25 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958732 | AF2-164 E O1 | Adder | 8.04 MW | 6.83 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959471 | AF2-238 C | Adder | 2.69 MW | 2.29 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960032 | AF2-294 E | Adder | 1.39 MW | 1.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961141 | AF2-405 | Adder | 2.21 MW | 1.88 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961151 | AF2-406 | Adder | 16.6 MW | 14.11 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961211 | AF2-412 | 50/50 | 34.84 MW | 34.84 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200823 | 26MHP_X3-003 | Adder | 8.39 MW | 7.13 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200829 | 26HNSMLK 2 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200830 | 26HNSMLK 3 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200831 | 26HNSMLK 4 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200832 | 26HNSMLK 5 | 50/50 | 2.35 MW | 2.35 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200838 | 26HOMER C2 | 50/50 | 56.21 MW | 56.21 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200839 | 26HOMER C3 | 50/50 | 59.51 MW | 59.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203907 | 26Y2-042 | Adder | 1.77 MW | 1.5 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203999 | P-047 E | Adder | 19.39 MW | 16.48 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 916202 | Z1-069 E | 50/50 | 15.37 MW | 15.37 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 938951 | AE1-123 | Adder | 2.31 MW | 1.97 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 940861 | AE2-074 C | 50/50 | 4.14 MW | 4.14 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 940862 | AE2-074 E | 50/50 | 5.46 MW | 5.46 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941191 | AE2-113 C | Adder | 13.71 MW | 11.65 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941192 | AE2-113 E | Adder | 12.87 MW | 10.94 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941422 | AE2-139 E | Adder | 6.67 MW | 5.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946111 | AF1-276 C | 50/50 | 18.47 MW | 18.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946112 | AF1-276 E | 50/50 | 9.1 MW | 9.1 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946121 | AF1-277 C | 50/50 | 18.47 MW | 18.47 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946122 | AF1-277 E | 50/50 | 9.1 MW | 9.1 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946131 | AF1-278 C | 50/50 | 14.72 MW | 14.72 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946132 | AF1-278 E | 50/50 | 7.32 MW | 7.32 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946381 | AF1-302 C | Adder | 2.89 MW | 2.46 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 917672 | Z2-108 E | Adder | -2.24 MW | -1.9 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 923443 | AB1-160 E | 50/50 | 4.39 MW | 4.39 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 294573 | P-028 E | Adder | 15.94 MW | 13.55 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946422 | AF2-000A E | Adder | 19.81 MW | 16.84 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 917673 | Z2-108 BAT | Adder | 2.63 MW | 2.24 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958472 | AF2-141 BAT | Adder | 2.92 MW | 2.49 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.56 MW | 0.56 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.34 MW | 4.34 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.8 MW | 0.8 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.29 MW | 0.29 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
STAR600-26HOMER CT 1.0/230.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.83 MW | 4.83 MW |
Details for 26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942811 | AE2-299 C | Adder | 5.42 MW | 4.6 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942812 | AE2-299 E | Adder | 21.66 MW | 18.41 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942961 | AE2-316 C | Adder | 6.62 MW | 5.63 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943151 | AE2-344 C | Adder | 11.43 MW | 9.71 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943152 | AE2-344 E | Adder | 7.62 MW | 6.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944262 | AF1-094 E | Adder | 1.26 MW | 1.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944302 | AF1-098 E | Adder | 5.37 MW | 4.56 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944311 | AF1-099 C | Adder | 6.99 MW | 5.94 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944312 | AF1-099 E | Adder | 4.66 MW | 3.96 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944321 | AF1-100 C | Adder | 14.1 MW | 11.98 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944322 | AF1-100 E | Adder | 9.4 MW | 7.99 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944771 | AF1-142 C | Adder | 11.18 MW | 9.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944772 | AF1-142 E | Adder | 7.45 MW | 6.33 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945052 | AF1-170 E | Adder | 4.82 MW | 4.09 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945161 | AF1-181 | Adder | 0.28 MW | 0.23 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945171 | AF1-182 | Adder | 0.37 MW | 0.31 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958731 | AF2-164 C O1 | Adder | 12.06 MW | 10.25 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958732 | AF2-164 E O1 | Adder | 8.04 MW | 6.83 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959471 | AF2-238 C | Adder | 2.69 MW | 2.29 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960032 | AF2-294 E | Adder | 1.39 MW | 1.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961141 | AF2-405 | Adder | 2.21 MW | 1.88 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961151 | AF2-406 | Adder | 16.6 MW | 14.11 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961211 | AF2-412 | 50/50 | 34.84 MW | 34.84 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200823 | 26MHP_X3-003 | Adder | 8.39 MW | 7.13 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200829 | 26HNSMLK 2 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200830 | 26HNSMLK 3 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200831 | 26HNSMLK 4 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200832 | 26HNSMLK 5 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200838 | 26HOMER C2 | 50/50 | 56.21 MW | 56.21 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200839 | 26HOMER C3 | 50/50 | 59.51 MW | 59.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203907 | 26Y2-042 | Adder | 1.77 MW | 1.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 203999 | P-047 E | Adder | 19.39 MW | 16.48 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 916202 | Z1-069 E | 50/50 | 15.37 MW | 15.37 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 938951 | AE1-123 | Adder | 2.31 MW | 1.97 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 940861 | AE2-074 C | 50/50 | 4.14 MW | 4.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 940862 | AE2-074 E | 50/50 | 5.46 MW | 5.46 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941191 | AE2-113 C | Adder | 13.71 MW | 11.65 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941192 | AE2-113 E | Adder | 12.87 MW | 10.94 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 941422 | AE2-139 E | Adder | 6.67 MW | 5.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946111 | AF1-276 C | 50/50 | 18.47 MW | 18.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946112 | AF1-276 E | 50/50 | 9.1 MW | 9.1 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946121 | AF1-277 C | 50/50 | 18.47 MW | 18.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946122 | AF1-277 E | 50/50 | 9.1 MW | 9.1 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946131 | AF1-278 C | 50/50 | 14.72 MW | 14.72 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946132 | AF1-278 E | 50/50 | 7.32 MW | 7.32 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946381 | AF1-302 C | Adder | 2.89 MW | 2.46 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 917672 | Z2-108 E | Adder | -2.24 MW | -1.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 923443 | AB1-160 E | 50/50 | 4.39 MW | 4.39 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 294573 | P-028 E | Adder | 15.94 MW | 13.55 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 946422 | AF2-000A E | Adder | 19.81 MW | 16.84 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 917673 | Z2-108 BAT | Adder | 2.63 MW | 2.24 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | 958472 | AF2-141 BAT | Adder | 2.92 MW | 2.49 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.56 MW | 0.56 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.34 MW | 4.34 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.8 MW | 0.8 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.29 MW | 0.29 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-2-PN-230-001T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.83 MW | 4.83 MW |
Details for 26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942811 | AE2-299 C | Adder | 5.42 MW | 4.6 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942812 | AE2-299 E | Adder | 21.66 MW | 18.41 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942961 | AE2-316 C | Adder | 6.62 MW | 5.63 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 942962 | AE2-316 E | Adder | 7.85 MW | 6.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943151 | AE2-344 C | Adder | 11.43 MW | 9.71 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943152 | AE2-344 E | Adder | 7.62 MW | 6.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943351 | AF1-006 C | Adder | 1.99 MW | 1.69 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 943352 | AF1-006 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944261 | AF1-094 C | Adder | 1.9 MW | 1.61 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944262 | AF1-094 E | Adder | 1.26 MW | 1.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944301 | AF1-098 C | Adder | 8.06 MW | 6.85 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944302 | AF1-098 E | Adder | 5.37 MW | 4.56 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944311 | AF1-099 C | Adder | 6.99 MW | 5.94 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944312 | AF1-099 E | Adder | 4.66 MW | 3.96 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944321 | AF1-100 C | Adder | 14.1 MW | 11.98 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944322 | AF1-100 E | Adder | 9.4 MW | 7.99 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944391 | AF1-104 O1 | Adder | 2.96 MW | 2.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944411 | AF1-106 O1 | Adder | 4.43 MW | 3.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944771 | AF1-142 C | Adder | 11.18 MW | 9.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944772 | AF1-142 E | Adder | 7.45 MW | 6.33 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944881 | AF1-153 C O1 | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944882 | AF1-153 E O1 | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944901 | AF1-155 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 944902 | AF1-155 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945021 | AF1-167 C | Adder | 1.19 MW | 1.01 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945022 | AF1-167 E | Adder | 0.8 MW | 0.68 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945051 | AF1-170 C | Adder | 7.23 MW | 6.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945052 | AF1-170 E | Adder | 4.82 MW | 4.09 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945121 | AF1-177 | Adder | 0.97 MW | 0.83 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945161 | AF1-181 | Adder | 0.28 MW | 0.23 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945171 | AF1-182 | Adder | 0.37 MW | 0.31 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945331 | AF1-198 | Adder | 0.58 MW | 0.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945451 | AF1-210 C | Adder | 1.34 MW | 1.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 945452 | AF1-210 E | Adder | 0.89 MW | 0.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958731 | AF2-164 C O1 | Adder | 12.06 MW | 10.25 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958732 | AF2-164 E O1 | Adder | 8.04 MW | 6.83 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958741 | AF2-165 C | Adder | 1.86 MW | 1.58 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958742 | AF2-165 E | Adder | 1.24 MW | 1.06 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958751 | AF2-166 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958752 | AF2-166 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959441 | AF2-235 C | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959442 | AF2-235 E | Adder | 0.62 MW | 0.53 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959471 | AF2-238 C | Adder | 2.69 MW | 2.29 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959472 | AF2-238 E | Adder | 1.8 MW | 1.53 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959521 | AF2-243 C | Adder | 1.4 MW | 1.19 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 959522 | AF2-243 E | Adder | 0.93 MW | 0.79 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960031 | AF2-294 C | Adder | 2.09 MW | 1.78 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960032 | AF2-294 E | Adder | 1.39 MW | 1.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960041 | AF2-295 C | Adder | 1.59 MW | 1.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960042 | AF2-295 E | Adder | 1.06 MW | 0.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960891 | AF2-380 C | Adder | 0.85 MW | 0.72 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 960892 | AF2-380 E | Adder | 0.57 MW | 0.48 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961141 | AF2-405 | Adder | 2.21 MW | 1.88 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961151 | AF2-406 | Adder | 16.6 MW | 14.11 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961211 | AF2-412 | 50/50 | 34.84 MW | 34.84 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961451 | AF2-436 | Adder | 0.24 MW | 0.2 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 961461 | AF2-437 | Adder | 0.14 MW | 0.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200823 | 26MHP_X3-003 | Adder | 8.39 MW | 7.13 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200829 | 26HNSMLK 2 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200830 | 26HNSMLK 3 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200831 | 26HNSMLK 4 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200832 | 26HNSMLK 5 | 50/50 | 2.35 MW | 2.35 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200838 | 26HOMER C2 | 50/50 | 56.21 MW | 56.21 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200839 | 26HOMER C3 | 50/50 | 59.51 MW | 59.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 200894 | 26K02 | Adder | 8.39 MW | 7.13 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203349 | 26Z1-069 C | 50/50 | 0.63 MW | 0.63 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203907 | 26Y2-042 | Adder | 1.77 MW | 1.5 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 203999 | P-047 E | Adder | 19.39 MW | 16.48 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 916202 | Z1-069 E | 50/50 | 15.37 MW | 15.37 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 938951 | AE1-123 | Adder | 2.31 MW | 1.97 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 939291 | AE1-160 C | Adder | 1.96 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 939292 | AE1-160 E | Adder | 1.13 MW | 0.96 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 940861 | AE2-074 C | 50/50 | 4.14 MW | 4.14 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 940862 | AE2-074 E | 50/50 | 5.46 MW | 5.46 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941191 | AE2-113 C | Adder | 13.71 MW | 11.65 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941192 | AE2-113 E | Adder | 12.87 MW | 10.94 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941321 | AE2-126 C | Adder | 1.35 MW | 1.15 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941322 | AE2-126 E | Adder | 0.9 MW | 0.76 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941421 | AE2-139 C | Adder | 10.01 MW | 8.51 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 941422 | AE2-139 E | Adder | 6.67 MW | 5.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946111 | AF1-276 C | 50/50 | 18.47 MW | 18.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946112 | AF1-276 E | 50/50 | 9.1 MW | 9.1 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946121 | AF1-277 C | 50/50 | 18.47 MW | 18.47 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946122 | AF1-277 E | 50/50 | 9.1 MW | 9.1 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946131 | AF1-278 C | 50/50 | 14.72 MW | 14.72 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946132 | AF1-278 E | 50/50 | 7.32 MW | 7.32 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946221 | AF1-287 C | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946222 | AF1-287 E | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946381 | AF1-302 C | Adder | 2.89 MW | 2.46 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946382 | AF1-302 E | Adder | 3.86 MW | 3.28 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 957161 | AF2-010 C | Adder | 7.27 MW | 6.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 957162 | AF2-010 E | Adder | 4.9 MW | 4.16 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958361 | AF2-130 C | Adder | 1.68 MW | 1.43 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958362 | AF2-130 E | Adder | 1.12 MW | 0.95 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 917672 | Z2-108 E | Adder | -2.24 MW | -1.9 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 923442 | AB1-160 C | 50/50 | 0.18 MW | 0.18 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 923443 | AB1-160 E | 50/50 | 4.39 MW | 4.39 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 294573 | P-028 E | Adder | 15.94 MW | 13.55 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946771 | AF1-217 C O2 | Adder | 1.97 MW | 1.67 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946772 | AF1-217 E O2 | Adder | 1.31 MW | 1.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946421 | AF2-000A C | Adder | 6.6 MW | 5.61 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 946422 | AF2-000A E | Adder | 19.81 MW | 16.84 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 916189 | Z1-066 BAT | Adder | -0.01 MW | -0.01 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 917673 | Z2-108 BAT | Adder | 2.63 MW | 2.24 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | 958472 | AF2-141 BAT | Adder | 2.92 MW | 2.49 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.56 MW | 0.56 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.34 MW | 4.34 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.8 MW | 0.8 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.29 MW | 0.29 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
26HOMER CY-STAR600 345.0/1.0 kV Ckt S transformer l/o PN-P2-3-PN-230-9I | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.83 MW | 4.83 MW |
Light Load Analysis
The Queue Project was evaluated as a 130.0 MW (Capacity 130.0 MW) injection in the PENELEC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Light Load Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
NYISO/PENELEC |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line
200676 to 130836 ckt 1 |
PN-P1-2-PN-115-103
CONTINGENCY 'PN-P1-2-PN-115-103' DISCONNECT BRANCH FROM BUS 200885 TO BUS 200929 CKT 1 /*26EVERT DR 115.0 - 26MAINESBURG 115.0 END |
Single | AC | 134.36 % | 139.54 % | 128.0 | B | 178.61 | 6.84 | |
PENELEC |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line
200885 to 200673 ckt 1 |
PN-P1-2-PN-345-104T
CONTINGENCY 'PN-P1-2-PN-345-104T' DISCONNECT BRANCH FROM BUS 200930 TO BUS 130757 CKT 1 /*26MAINESBURG 345.0 - WATRC345 345.0 END |
Single | AC | 85.09 % | 104.27 % | 242.0 | B | 252.33 | 45.33 |
Details for 26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 200887 | 26ARMNA MT | 80/20 | 1.03 MW | 1.03 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 200917 | 26MTNTP_P28 | 80/20 | 0.65 MW | 0.65 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 203999 | P-047 E | 80/20 | 4.14 MW | 4.14 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 944411 | AF1-106 O1 | 80/20 | 12.02 MW | 12.02 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 961141 | AF2-405 | 80/20 | 6.01 MW | 6.01 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 961151 | AF2-406 | 80/20 | 45.07 MW | 45.07 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 294573 | P-028 E | 80/20 | 2.54 MW | 2.54 MW |
26E.SAYRE-N.WAV115 115.0 kV Ckt 1 line l/o PN-P1-2-PN-115-103 | 961212 | AF2-412 BAT | 80/20 | 6.84 MW | 6.84 MW |
Details for 26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 200887 | 26ARMNA MT | 80/20 | 3.99 MW | 3.99 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 203349 | 26Z1-069 C | 80/20 | 1.19 MW | 1.19 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 203999 | P-047 E | 80/20 | 15.97 MW | 15.97 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 916202 | Z1-069 E | 80/20 | 5.05 MW | 5.05 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 961211 | AF2-412 | 80/20 | 45.33 MW | 45.33 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 923442 | AB1-160 C | 80/20 | 0.34 MW | 0.34 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 923443 | AB1-160 E | 80/20 | 1.44 MW | 1.44 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 915953 | AF2-000 | 80/20 | 19.04 MW | 19.04 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 944412 | AF1-106 BAT | 80/20 | 1.96 MW | 1.96 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 961142 | AF2-405 BAT | 80/20 | 0.98 MW | 0.98 MW |
26EVERT DR-26SOUTH TR 115.0 kV Ckt 1 line l/o PN-P1-2-PN-345-104T | 961152 | AF2-406 BAT | 80/20 | 7.35 MW | 7.35 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
b3665 | Replace several pieces of 1033.5 AAC substation conductor at East Towanda 230 kV | $407,700 | |
n6506.1 | Reconductor 4.62 miles of transmission line. Replace line drops at Four Mile and Erie South substations | $14,150,000 | |
n6506.2 | Replace the substation conductor at Four Mile | $200,000 | |
n6855.1 | Replace substation conductor at Warren and Glade substations | $350,000 | |
n6855.2 | Rebuild 11.53 miles of transmission line between Warren and Glade. | $42,390,000 | |
n6855.3 | Replace line trap at Glade | $230,000 | |
n6855.4 | Adjust/replace the relays and meters | $978,240 | |
s2053 | Replace the Homer City North 345/230-23 kV transformer with three (3) single phase units (Projected ISD 12/15/2023) | $17,700,000 | |
n8280 | Replace the Homer City South 345/230 kV transformer with a larger unit | $37,700,000 | |
s2279.3 | Replace line trap at Homer City on the Homer City - Shelocta 230 kV Line. | $200,000 | |
n8112 | Reconductor/rebuild the Homer City - Shelocta 230 kV (~11 miles) | $50,929,813 | |
n8112.3 | Replace disconnect switches and leads at Shelocta Substation | $1,744,708 | |
n8112.2 | Replace disconnect switches and substation conductor at Homer City Substation. | $3,333,312 | |
n8112.1 | Adjust/replace relays at Homer City and Shelocta substations. | $2,668,506 | |
s2279.2 | Replace line trap at Keystone on the Keystone – Shelocta 230 kV Line. | $200,000 | |
n8192 | Reconductor/rebuild the Shelocta - Keystone 230 kV line (~2.5 miles) | $13,311,228 | |
n8192.1 | Adjust/replace relaying at Keystone and Shelocta substations. | $2,668,506 | |
n8192.2 | Replace substation conductor at Keystone substation | $1,142,812 | |
n8192.3 | Replace line drops at Keystone Substation | $430,625 | |
n8192.4 | Replace bus conductor at Keystone Substation | $1,142,812 | |
n8192.5 | Replace disconnect switches at Keystone Substation | $2,629,706 | |
n8192.6 | Replace breaker leads at Keystone Substation | $430,625 | |
n8192.7 | Replace disconnect switches and leads at Shelocta Substation | $1,744,708 | |
n8263 | Reconductor 3.4 miles of the Everts Drive - South Troy 115 kV Line | $8,400,000 | |
b3137 | Rebuild 20 miles of the East Towanda - North Meshoppen 115kV line. | $58,600,000 | |
b3672 | East Towanda-North Meshoppen 115 kV line: Rebuild 2.5 miles of 636 ACSR with 1113 ACSS conductor using single circuit construction | $6,600,000 | |
n8281 | Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker | $41,580,000 | |
(TBD) | East Sayre-North Waverly 115kV line upgrade - NYSEG (NYISO CY17 driven upgrade) | $0 | |
n8471 | East Sayre-North Waverly 115kV line upgrade - FE (NYISO CY17 driven upgrade) | $0 | |
(TBD) | NYSEG would need to replace their section of the limiting conductor/equipment and provide estimates for their replacement. | $0 | |
b3730 | Reterminate the Lackawanna T3 and T4 500 / 230 kV transformers on the 230 kV side | $10,700,000 |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-412 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.