AF2-396 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:07
Stinger 138 kV
200.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-396 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the AEP zone — Cass County, Michigan. The installed facilities will have a total capability of 200.0 MW with 200.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-396 |
| Project Name | Stinger 138 kV |
| Developer Name | Steelhead Solar, LLC |
| State | Michigan |
| County | Cass |
| Transmission Owner | AEP |
| MFO | 200.0 MW |
| MWE | 200.0 MW |
| MWC | 200.0 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-396 will interconnect on the AEP transmission system at the Stinger 138 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 200.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line
243346 to 243287 ckt 1 |
AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1
CONTINGENCY 'AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Bus | AC | 98.63 % | 123.3 % | 185.0 | B | 228.1 | 47.88 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1
CONTINGENCY 'AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Bus | AC | 99.42 % | 121.43 % | 185.0 | B | 224.65 | 42.97 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1
CONTINGENCY 'AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1' OPEN BRANCH FROM BUS 243204 TO BUS 243386 CKT 1 /*05VALLEYEQ 999.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 243204 TO BUS 246550 CKT 1 /*05VALLEYEQ 999.0 - 05VALLEY 34.5 OPEN BRANCH FROM BUS 243204 TO BUS 246551 CKT 1 /*05VALLEYEQ 999.0 - 05VALLEY 69.0 OPEN BRANCH FROM BUS 243261 TO BUS 243386 CKT 1 /*05COLBYTAPSS 138.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 243307 TO BUS 243386 CKT 1 /*05HARTFO 138.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 246509 TO BUS 246551 CKT 1 /*05CAMERON 69.0 - 05VALLEY 69.0 OPEN BRANCH FROM BUS 247174 TO BUS 246550 CKT 1 /*05ROTHDEW 34.5 - 05VALLEY 34.5 OPEN BRANCH FROM BUS 247329 TO BUS 243386 CKT 1 /*05STINGER 138.0 - 05VALLY 138.0 REMOVE SWSHUNT FROM BUS 243386 /*05VALLY 138.0 END |
Bus | AC | 80.82 % | 121.34 % | 185.0 | B | 224.48 | 76.87 | |
| AEP |
05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line
243346 to 243287 ckt 1 |
AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA
CONTINGENCY 'AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246555 CKT 1 /*05DAILEY 8 69.0 - 05WOLVERIN 69.0 OPEN BRANCH FROM BUS 960980 TO BUS 246555 CKT 1 /*AF2-389 TAP 69.0 - 05WOLVERIN 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 99.35 % | 123.99 % | 185.0 | B | 229.38 | 47.88 | |
| AEP |
05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line
243346 to 243287 ckt 1 |
AEP_SUBT_P4_#1281_05POKAGON 69.0_H
CONTINGENCY 'AEP_SUBT_P4_#1281_05POKAGON 69.0_H' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246505 TO BUS 246506 CKT 1 /*05BARRETT8 69.0 - 05BARRETTZ 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246511 CKT 1 /*05BARRETTZ 69.0 - 05COLBY 69.0 OPEN BRANCH FROM BUS 246511 TO BUS 243420 CKT 1 /*05COLBY 69.0 - 05COLBY 34.5 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 98.74 % | 123.41 % | 185.0 | B | 228.31 | 47.88 | |
| AEP |
05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line
243346 to 243287 ckt 1 |
AEP_SUBT_P4_#1282_05POKAGON 69.0_E
CONTINGENCY 'AEP_SUBT_P4_#1282_05POKAGON 69.0_E' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 98.63 % | 123.3 % | 185.0 | B | 228.1 | 47.88 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA
CONTINGENCY 'AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246555 CKT 1 /*05DAILEY 8 69.0 - 05WOLVERIN 69.0 OPEN BRANCH FROM BUS 960980 TO BUS 246555 CKT 1 /*AF2-389 TAP 69.0 - 05WOLVERIN 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 99.98 % | 121.96 % | 185.0 | B | 225.63 | 42.97 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P4_#1342_05VALLEY 69.0_A
CONTINGENCY 'AEP_SUBT_P4_#1342_05VALLEY 69.0_A' OPEN BRANCH FROM BUS 243204 TO BUS 243386 CKT 1 /*05VALLEYEQ 999.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 243204 TO BUS 246550 CKT 1 /*05VALLEYEQ 999.0 - 05VALLEY 34.5 OPEN BRANCH FROM BUS 243204 TO BUS 246551 CKT 1 /*05VALLEYEQ 999.0 - 05VALLEY 69.0 OPEN BRANCH FROM BUS 243261 TO BUS 243386 CKT 1 /*05COLBYTAPSS 138.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 243307 TO BUS 243386 CKT 1 /*05HARTFO 138.0 - 05VALLY 138.0 OPEN BRANCH FROM BUS 246502 TO BUS 246509 CKT 1 /*05ALMENA 69.0 - 05CAMERON 69.0 OPEN BRANCH FROM BUS 246509 TO BUS 246551 CKT 1 /*05CAMERON 69.0 - 05VALLEY 69.0 OPEN BRANCH FROM BUS 247174 TO BUS 246550 CKT 1 /*05ROTHDEW 34.5 - 05VALLEY 34.5 OPEN BRANCH FROM BUS 247329 TO BUS 243386 CKT 1 /*05STINGER 138.0 - 05VALLY 138.0 REMOVE SWSHUNT FROM BUS 243386 /*05VALLY 138.0 END |
Breaker | AC | 81.26 % | 121.78 % | 185.0 | B | 225.29 | 76.87 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P4_#1281_05POKAGON 69.0_H
CONTINGENCY 'AEP_SUBT_P4_#1281_05POKAGON 69.0_H' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246505 TO BUS 246506 CKT 1 /*05BARRETT8 69.0 - 05BARRETTZ 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246511 CKT 1 /*05BARRETTZ 69.0 - 05COLBY 69.0 OPEN BRANCH FROM BUS 246511 TO BUS 243420 CKT 1 /*05COLBY 69.0 - 05COLBY 34.5 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 99.52 % | 121.53 % | 185.0 | B | 224.83 | 42.97 | |
| AEP |
05COREY-05MOTTV 138.0 kV Ckt 1 line
243265 to 243346 ckt 1 |
AEP_SUBT_P4_#1282_05POKAGON 69.0_E
CONTINGENCY 'AEP_SUBT_P4_#1282_05POKAGON 69.0_E' OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246464 TO BUS 246480 CKT 1 /*05LAKE ST 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246506 TO BUS 246480 CKT 1 /*05BARRETTZ 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 REMOVE SWSHUNT FROM BUS 246480 /*05POKAGON 69.0 END |
Breaker | AC | 99.42 % | 121.43 % | 185.0 | B | 224.65 | 42.97 | |
| AEP |
05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line
243287 to 243346 ckt 1 |
AEP_P4_#9220_05KENZIE 138_J2
CONTINGENCY 'AEP_P4_#9220_05KENZIE 138_J2' OPEN BRANCH FROM BUS 243265 TO BUS 243322 CKT 1 /*05COREY 138.0 - 05KENZIE 138.0 OPEN BRANCH FROM BUS 243322 TO BUS 243360 CKT 1 /*05KENZIE 138.0 - 05POKAGO 138.0 OPEN BRANCH FROM BUS 243355 TO BUS 246764 CKT 1 /*05ONTWAZ 138.0 - 05SAUKTR 138.0 OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 243360 TO BUS 246764 CKT 1 /*05POKAGO 138.0 - 05SAUKTR 138.0 END |
Breaker | AC | 106.54 % | 114.33 % | 185.0 | B | 211.51 | 23.99 | |
| AEP |
05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line
247330 to 243294 ckt 1 |
AEP_P4_#9218_05KENZIE 138_G
CONTINGENCY 'AEP_P4_#9218_05KENZIE 138_G' OPEN BRANCH FROM BUS 243322 TO BUS 244510 CKT 1 /*05KENZIE 138.0 - 05BLOSSOM TR 138.0 OPEN BRANCH FROM BUS 244510 TO BUS 243365 CKT 1 /*05BLOSSOM TR 138.0 - 05RIVRSD 138.0 OPEN BRANCH FROM BUS 939390 TO BUS 243322 CKT 1 /*AE1-170 TAP 138.0 - 05KENZIE 138.0 END |
Breaker | AC | 62.73 % | 106.15 % | 251.0 | B | 266.44 | 111.42 | |
| AEP |
05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line
243294 to 243345 ckt 1 |
AEP_P4_#9218_05KENZIE 138_G
CONTINGENCY 'AEP_P4_#9218_05KENZIE 138_G' OPEN BRANCH FROM BUS 243322 TO BUS 244510 CKT 1 /*05KENZIE 138.0 - 05BLOSSOM TR 138.0 OPEN BRANCH FROM BUS 244510 TO BUS 243365 CKT 1 /*05BLOSSOM TR 138.0 - 05RIVRSD 138.0 OPEN BRANCH FROM BUS 939390 TO BUS 243322 CKT 1 /*AE1-170 TAP 138.0 - 05KENZIE 138.0 END |
Breaker | AC | 61.84 % | 105.27 % | 251.0 | B | 264.23 | 111.42 | |
| AEP |
05COOK-05OLIVE 345.0 kV Ckt 1 line
243215 to 243229 ckt 1 |
AEP_P4_#7443_05DUMONT 765_A
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A' OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1 /*05COOK 765.0 - 05DUMONT 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 246999 CKT 1 /*05DUMONT 765.0 - 05SORENS 765.0 END |
Breaker | AC | 100.43 % | 101.92 % | 1409.0 | B | 1436.05 | 21.87 | |
| AEP/NIPS |
05STURGI-17HOWE 69.0 kV Ckt 1 line
243412 to 255331 ckt 1 |
AEP_P1-2_#5577
CONTINGENCY 'AEP_P1-2_#5577' OPEN BRANCH FROM BUS 243287 TO BUS 243346 CKT 1 /*05E.ELKHART 138.0 - 05MOTTV 138.0 END |
Single | AC | 94.89 % | 133.56 % | 47.0 | B | 62.77 | 19.76 | |
| AEP/NIPS |
05STURGI-17HOWE 69.0 kV Ckt 1 line
243412 to 255331 ckt 1 |
AEP_P1-2_#6388
CONTINGENCY 'AEP_P1-2_#6388' OPEN BRANCH FROM BUS 243220 TO BUS 255105 CKT 1 /*05E.ELKHART 345.0 - 17HIPLE 345.0 END |
Single | AC | 89.1 % | 114.6 % | 47.0 | B | 53.86 | 13.02 | |
| AEP/NIPS |
05STURGI-17HOWE 69.0 kV Ckt 1 line
243412 to 255331 ckt 1 |
AEP_SUBT_P1-2_#726-B
CONTINGENCY 'AEP_SUBT_P1-2_#726-B' OPEN BRANCH FROM BUS 246516 TO BUS 246480 CKT 1 /*05DAILEY 8 69.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 246516 TO BUS 246555 CKT 1 /*05DAILEY 8 69.0 - 05WOLVERIN 69.0 OPEN BRANCH FROM BUS 960980 TO BUS 246555 CKT 1 /*AF2-389 TAP 69.0 - 05WOLVERIN 69.0 END |
Single | AC | 86.57 % | 111.63 % | 47.0 | B | 52.47 | 13.1 | |
| AEP/NIPS |
05STURGI-17HOWE 69.0 kV Ckt 1 line
243412 to 255331 ckt 1 |
AEP_P1-2_#10604
CONTINGENCY 'AEP_P1-2_#10604' OPEN BRANCH FROM BUS 247329 TO BUS 243386 CKT 1 /*05STINGER 138.0 - 05VALLY 138.0 END |
Single | AC | 66.47 % | 108.29 % | 47.0 | B | 50.9 | 21.45 | |
| AEP/NIPS |
05STURGI-17HOWE 69.0 kV Ckt 1 line
243412 to 255331 ckt 1 |
AEP_SUBT_P1-2_#726-C
CONTINGENCY 'AEP_SUBT_P1-2_#726-C' OPEN BRANCH FROM BUS 957890 TO BUS 960980 CKT 1 /*AF2-083 TAP 69.0 - AF2-389 TAP 69.0 END |
Single | AC | 79.15 % | 104.44 % | 47.0 | B | 49.09 | 13.1 | |
| AEP |
05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer
243212 to 243250 ckt 1 |
AEP_P7-1_#10998
CONTINGENCY 'AEP_P7-1_#10998' OPEN BRANCH FROM BUS 243212 TO BUS 243215 CKT 1 /*05BENTON 345.0 - 05COOK 345.0 OPEN BRANCH FROM BUS 243215 TO BUS 247803 CKT 1 /*05COOK 345.0 - 05SEGRETO 345.0 END |
Tower | AC | 151.72 % | 154.37 % | 564.0 | B | 870.65 | 14.39 | |
| Details for 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 246536 | 05MOTTVILL | 50/50 | 0.15 MW | 0.15 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 247966 | 05WTRV SLR E | Adder | 0.17 MW | 0.14 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 936141 | AD2-020 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 936142 | AD2-020 E O1 | 50/50 | 5.48 MW | 5.48 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 943021 | AE2-325 C | 50/50 | 4.51 MW | 4.51 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 943022 | AE2-325 E | 50/50 | 3.0 MW | 3.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944161 | AF1-084 C | 50/50 | 6.68 MW | 6.68 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944162 | AF1-084 E | 50/50 | 3.81 MW | 3.81 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944961 | AF1-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944962 | AF1-161 E | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 945111 | AF1-176 C O1 | 50/50 | 61.98 MW | 61.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 945112 | AF1-176 E O1 | 50/50 | 57.46 MW | 57.46 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 960981 | AF2-389 C | 50/50 | 11.39 MW | 11.39 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 960982 | AF2-389 E | 50/50 | 7.6 MW | 7.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 961051 | AF2-396 O1 | 50/50 | 47.88 MW | 47.88 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 957891 | AF2-083 C O1 | 50/50 | 37.98 MW | 37.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 957892 | AF2-083 E O1 | 50/50 | 18.99 MW | 18.99 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 939391 | AE1-170 C O1 | Adder | 3.91 MW | 3.32 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 939392 | AE1-170 E O1 | Adder | 5.4 MW | 4.59 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.04 MW | 0.04 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.08 MW | 0.08 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.23 MW | 1.23 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 247966 | 05WTRV SLR E | Adder | 0.15 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 936141 | AD2-020 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 936142 | AD2-020 E O1 | 50/50 | 4.9 MW | 4.9 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 943021 | AE2-325 C | 50/50 | 4.03 MW | 4.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 943022 | AE2-325 E | 50/50 | 2.68 MW | 2.68 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944161 | AF1-084 C | 50/50 | 5.87 MW | 5.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944162 | AF1-084 E | 50/50 | 3.35 MW | 3.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944961 | AF1-161 C | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 944962 | AF1-161 E | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 945111 | AF1-176 C O1 | 50/50 | 57.91 MW | 57.91 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 945112 | AF1-176 E O1 | 50/50 | 53.69 MW | 53.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 960981 | AF2-389 C | 50/50 | 8.79 MW | 8.79 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 960982 | AF2-389 E | 50/50 | 5.86 MW | 5.86 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 961051 | AF2-396 O1 | 50/50 | 42.97 MW | 42.97 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 957891 | AF2-083 C O1 | 50/50 | 29.31 MW | 29.31 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 957892 | AF2-083 E O1 | 50/50 | 14.65 MW | 14.65 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 939391 | AE1-170 C O1 | Adder | 3.64 MW | 3.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | 939392 | AE1-170 E O1 | Adder | 5.02 MW | 4.27 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.13 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1279_05POKAGON 69.0_1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.2 MW | 1.2 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 936141 | AD2-020 C O1 | 50/50 | 9.32 MW | 9.32 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 936142 | AD2-020 E O1 | 50/50 | 5.74 MW | 5.74 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 943021 | AE2-325 C | 50/50 | 4.72 MW | 4.72 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 943022 | AE2-325 E | 50/50 | 3.14 MW | 3.14 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 944161 | AF1-084 C | Adder | 5.28 MW | 4.49 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 944162 | AF1-084 E | Adder | 3.02 MW | 2.56 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 944961 | AF1-161 C | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 944962 | AF1-161 E | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 945111 | AF1-176 C O1 | 50/50 | 64.28 MW | 64.28 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 945112 | AF1-176 E O1 | 50/50 | 59.59 MW | 59.59 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 960981 | AF2-389 C | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 960982 | AF2-389 E | 50/50 | 2.51 MW | 2.51 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 961051 | AF2-396 O1 | 50/50 | 76.87 MW | 76.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 957891 | AF2-083 C O1 | 50/50 | 12.69 MW | 12.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 957892 | AF2-083 E O1 | 50/50 | 6.35 MW | 6.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 939391 | AE1-170 C O1 | Adder | 3.27 MW | 2.78 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | 939392 | AE1-170 E O1 | Adder | 4.52 MW | 3.84 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.12 MW | 0.12 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.05 MW | 0.05 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P2-2_#1012_05VALLEY 69.0_1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.94 MW | 0.94 MW |
| Details for 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 246536 | 05MOTTVILL | 50/50 | 0.15 MW | 0.15 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 247966 | 05WTRV SLR E | Adder | 0.17 MW | 0.14 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 936141 | AD2-020 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 936142 | AD2-020 E O1 | 50/50 | 5.48 MW | 5.48 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 943021 | AE2-325 C | 50/50 | 4.51 MW | 4.51 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 943022 | AE2-325 E | 50/50 | 3.0 MW | 3.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944161 | AF1-084 C | 50/50 | 6.68 MW | 6.68 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944162 | AF1-084 E | 50/50 | 3.81 MW | 3.81 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944961 | AF1-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944962 | AF1-161 E | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 945111 | AF1-176 C O1 | 50/50 | 61.98 MW | 61.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 945112 | AF1-176 E O1 | 50/50 | 57.46 MW | 57.46 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 960981 | AF2-389 C | 50/50 | 11.39 MW | 11.39 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 960982 | AF2-389 E | 50/50 | 7.6 MW | 7.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 961051 | AF2-396 O1 | 50/50 | 47.88 MW | 47.88 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 957891 | AF2-083 C O1 | 50/50 | 37.98 MW | 37.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 957892 | AF2-083 E O1 | 50/50 | 18.99 MW | 18.99 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 939391 | AE1-170 C O1 | Adder | 3.91 MW | 3.32 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 939392 | AE1-170 E O1 | Adder | 5.4 MW | 4.59 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.04 MW | 0.04 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.08 MW | 0.08 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.23 MW | 1.23 MW |
| Details for 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 246536 | 05MOTTVILL | 50/50 | 0.15 MW | 0.15 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 247966 | 05WTRV SLR E | Adder | 0.17 MW | 0.14 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 936141 | AD2-020 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 936142 | AD2-020 E O1 | 50/50 | 5.48 MW | 5.48 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 943021 | AE2-325 C | 50/50 | 4.51 MW | 4.51 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 943022 | AE2-325 E | 50/50 | 3.0 MW | 3.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944161 | AF1-084 C | 50/50 | 6.68 MW | 6.68 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944162 | AF1-084 E | 50/50 | 3.81 MW | 3.81 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944961 | AF1-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944962 | AF1-161 E | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 945111 | AF1-176 C O1 | 50/50 | 61.98 MW | 61.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 945112 | AF1-176 E O1 | 50/50 | 57.46 MW | 57.46 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 960981 | AF2-389 C | 50/50 | 11.39 MW | 11.39 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 960982 | AF2-389 E | 50/50 | 7.6 MW | 7.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 961051 | AF2-396 O1 | 50/50 | 47.88 MW | 47.88 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 957891 | AF2-083 C O1 | 50/50 | 37.98 MW | 37.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 957892 | AF2-083 E O1 | 50/50 | 18.99 MW | 18.99 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 939391 | AE1-170 C O1 | Adder | 3.91 MW | 3.32 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 939392 | AE1-170 E O1 | Adder | 5.4 MW | 4.59 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.04 MW | 0.04 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.08 MW | 0.08 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.23 MW | 1.23 MW |
| Details for 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 246536 | 05MOTTVILL | 50/50 | 0.15 MW | 0.15 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 247966 | 05WTRV SLR E | Adder | 0.17 MW | 0.14 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 936141 | AD2-020 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 936142 | AD2-020 E O1 | 50/50 | 5.48 MW | 5.48 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 943021 | AE2-325 C | 50/50 | 4.51 MW | 4.51 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 943022 | AE2-325 E | 50/50 | 3.0 MW | 3.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944161 | AF1-084 C | 50/50 | 6.68 MW | 6.68 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944162 | AF1-084 E | 50/50 | 3.81 MW | 3.81 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944961 | AF1-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944962 | AF1-161 E | 50/50 | 3.6 MW | 3.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 945111 | AF1-176 C O1 | 50/50 | 61.98 MW | 61.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 945112 | AF1-176 E O1 | 50/50 | 57.46 MW | 57.46 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 960981 | AF2-389 C | 50/50 | 11.39 MW | 11.39 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 960982 | AF2-389 E | 50/50 | 7.6 MW | 7.6 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 961051 | AF2-396 O1 | 50/50 | 47.88 MW | 47.88 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 957891 | AF2-083 C O1 | 50/50 | 37.98 MW | 37.98 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 957892 | AF2-083 E O1 | 50/50 | 18.99 MW | 18.99 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 939391 | AE1-170 C O1 | Adder | 3.91 MW | 3.32 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 939392 | AE1-170 E O1 | Adder | 5.4 MW | 4.59 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.04 MW | 0.04 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.08 MW | 0.08 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.03 MW | 0.03 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05MOTTV-05E.ELKHART 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.23 MW | 1.23 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 247966 | 05WTRV SLR E | Adder | 0.15 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 936141 | AD2-020 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 936142 | AD2-020 E O1 | 50/50 | 4.9 MW | 4.9 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 943021 | AE2-325 C | 50/50 | 4.03 MW | 4.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 943022 | AE2-325 E | 50/50 | 2.68 MW | 2.68 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944161 | AF1-084 C | 50/50 | 5.87 MW | 5.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944162 | AF1-084 E | 50/50 | 3.35 MW | 3.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944961 | AF1-161 C | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 944962 | AF1-161 E | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 945111 | AF1-176 C O1 | 50/50 | 57.91 MW | 57.91 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 945112 | AF1-176 E O1 | 50/50 | 53.69 MW | 53.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 960981 | AF2-389 C | 50/50 | 8.79 MW | 8.79 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 960982 | AF2-389 E | 50/50 | 5.86 MW | 5.86 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 961051 | AF2-396 O1 | 50/50 | 42.97 MW | 42.97 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 957891 | AF2-083 C O1 | 50/50 | 29.31 MW | 29.31 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 957892 | AF2-083 E O1 | 50/50 | 14.65 MW | 14.65 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 939391 | AE1-170 C O1 | Adder | 3.64 MW | 3.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | 939392 | AE1-170 E O1 | Adder | 5.02 MW | 4.27 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.13 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1280_05POKAGON 69.0_F-AA | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.2 MW | 1.2 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 936141 | AD2-020 C O1 | 50/50 | 9.32 MW | 9.32 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 936142 | AD2-020 E O1 | 50/50 | 5.74 MW | 5.74 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 943021 | AE2-325 C | 50/50 | 4.72 MW | 4.72 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 943022 | AE2-325 E | 50/50 | 3.14 MW | 3.14 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 944161 | AF1-084 C | Adder | 5.28 MW | 4.49 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 944162 | AF1-084 E | Adder | 3.02 MW | 2.56 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 944961 | AF1-161 C | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 944962 | AF1-161 E | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 945111 | AF1-176 C O1 | 50/50 | 64.28 MW | 64.28 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 945112 | AF1-176 E O1 | 50/50 | 59.59 MW | 59.59 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 960981 | AF2-389 C | 50/50 | 3.76 MW | 3.76 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 960982 | AF2-389 E | 50/50 | 2.51 MW | 2.51 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 961051 | AF2-396 O1 | 50/50 | 76.87 MW | 76.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 957891 | AF2-083 C O1 | 50/50 | 12.69 MW | 12.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 957892 | AF2-083 E O1 | 50/50 | 6.35 MW | 6.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 939391 | AE1-170 C O1 | Adder | 3.27 MW | 2.78 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | 939392 | AE1-170 E O1 | Adder | 4.52 MW | 3.84 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.12 MW | 0.12 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.05 MW | 0.05 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1342_05VALLEY 69.0_A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.94 MW | 0.94 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 247966 | 05WTRV SLR E | Adder | 0.15 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 936141 | AD2-020 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 936142 | AD2-020 E O1 | 50/50 | 4.9 MW | 4.9 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 943021 | AE2-325 C | 50/50 | 4.03 MW | 4.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 943022 | AE2-325 E | 50/50 | 2.68 MW | 2.68 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944161 | AF1-084 C | 50/50 | 5.87 MW | 5.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944162 | AF1-084 E | 50/50 | 3.35 MW | 3.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944961 | AF1-161 C | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 944962 | AF1-161 E | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 945111 | AF1-176 C O1 | 50/50 | 57.91 MW | 57.91 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 945112 | AF1-176 E O1 | 50/50 | 53.69 MW | 53.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 960981 | AF2-389 C | 50/50 | 8.79 MW | 8.79 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 960982 | AF2-389 E | 50/50 | 5.86 MW | 5.86 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 961051 | AF2-396 O1 | 50/50 | 42.97 MW | 42.97 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 957891 | AF2-083 C O1 | 50/50 | 29.31 MW | 29.31 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 957892 | AF2-083 E O1 | 50/50 | 14.65 MW | 14.65 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 939391 | AE1-170 C O1 | Adder | 3.64 MW | 3.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | 939392 | AE1-170 E O1 | Adder | 5.02 MW | 4.27 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.13 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1281_05POKAGON 69.0_H | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.2 MW | 1.2 MW |
| Details for 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 247966 | 05WTRV SLR E | Adder | 0.15 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 936141 | AD2-020 C O1 | 50/50 | 7.96 MW | 7.96 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 936142 | AD2-020 E O1 | 50/50 | 4.9 MW | 4.9 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 943021 | AE2-325 C | 50/50 | 4.03 MW | 4.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 943022 | AE2-325 E | 50/50 | 2.68 MW | 2.68 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944161 | AF1-084 C | 50/50 | 5.87 MW | 5.87 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944162 | AF1-084 E | 50/50 | 3.35 MW | 3.35 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944961 | AF1-161 C | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 944962 | AF1-161 E | 50/50 | 3.22 MW | 3.22 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 945111 | AF1-176 C O1 | 50/50 | 57.91 MW | 57.91 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 945112 | AF1-176 E O1 | 50/50 | 53.69 MW | 53.69 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 960981 | AF2-389 C | 50/50 | 8.79 MW | 8.79 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 960982 | AF2-389 E | 50/50 | 5.86 MW | 5.86 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 961051 | AF2-396 O1 | 50/50 | 42.97 MW | 42.97 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 957891 | AF2-083 C O1 | 50/50 | 29.31 MW | 29.31 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 957892 | AF2-083 E O1 | 50/50 | 14.65 MW | 14.65 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 939391 | AE1-170 C O1 | Adder | 3.64 MW | 3.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | 939392 | AE1-170 E O1 | Adder | 5.02 MW | 4.27 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.13 MW | 0.13 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05COREY-05MOTTV 138.0 kV Ckt 1 line l/o AEP_SUBT_P4_#1282_05POKAGON 69.0_E | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.2 MW | 1.2 MW |
| Details for 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 938261 | AE1-039 | Adder | -0.04 MW | -0.04 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 943023 | AE2-325 BAT | 50/50 | 8.77 MW | 8.77 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 944963 | AF1-161 BAT | 50/50 | 8.4 MW | 8.4 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 945113 | AF1-176 BAT | 50/50 | 63.75 MW | 63.75 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 961052 | AF2-396 BAT | 50/50 | 23.99 MW | 23.99 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.27 MW | 0.27 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.12 MW | 0.12 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.26 MW | 0.26 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 247966 | 05WTRV SLR E | 50/50 | 0.34 MW | 0.34 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 936141 | AD2-020 C O1 | 50/50 | 21.33 MW | 21.33 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 936142 | AD2-020 E O1 | 50/50 | 13.13 MW | 13.13 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 938261 | AE1-039 | Adder | 0.07 MW | 0.06 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 943021 | AE2-325 C | 50/50 | 10.8 MW | 10.8 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 943022 | AE2-325 E | 50/50 | 7.18 MW | 7.18 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944161 | AF1-084 C | 50/50 | 11.88 MW | 11.88 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944162 | AF1-084 E | 50/50 | 6.78 MW | 6.78 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944961 | AF1-161 C | 50/50 | 8.61 MW | 8.61 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944962 | AF1-161 E | 50/50 | 8.61 MW | 8.61 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 961051 | AF2-396 O1 | 50/50 | 111.42 MW | 111.42 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 244412 | 05WTRV SLR C | 50/50 | 0.06 MW | 0.06 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 939391 | AE1-170 C O1 | 50/50 | 20.99 MW | 20.99 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 939392 | AE1-170 E O1 | 50/50 | 28.98 MW | 28.98 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 945113 | AF1-176 BAT | 50/50 | 16.25 MW | 16.25 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.05 MW | 0.05 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05BRODY-05FLWRFD8 SS 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.34 MW | 1.34 MW |
| Details for 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 247966 | 05WTRV SLR E | 50/50 | 0.34 MW | 0.34 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 936141 | AD2-020 C O1 | 50/50 | 21.33 MW | 21.33 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 936142 | AD2-020 E O1 | 50/50 | 13.13 MW | 13.13 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 938261 | AE1-039 | Adder | 0.07 MW | 0.06 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 943021 | AE2-325 C | 50/50 | 10.8 MW | 10.8 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 943022 | AE2-325 E | 50/50 | 7.18 MW | 7.18 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944161 | AF1-084 C | 50/50 | 11.88 MW | 11.88 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944162 | AF1-084 E | 50/50 | 6.78 MW | 6.78 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944961 | AF1-161 C | 50/50 | 8.61 MW | 8.61 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 944962 | AF1-161 E | 50/50 | 8.61 MW | 8.61 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 961051 | AF2-396 O1 | 50/50 | 111.42 MW | 111.42 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 244412 | 05WTRV SLR C | 50/50 | 0.06 MW | 0.06 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 939391 | AE1-170 C O1 | 50/50 | 20.99 MW | 20.99 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 939392 | AE1-170 E O1 | 50/50 | 28.98 MW | 28.98 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | 945113 | AF1-176 BAT | 50/50 | 16.25 MW | 16.25 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.02 MW | 0.02 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.05 MW | 0.05 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.09 MW | 0.09 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.06 MW | 0.06 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05FLWRFD8 SS-05MOORPK 138.0 kV Ckt 1 line l/o AEP_P4_#9218_05KENZIE 138_G | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.34 MW | 1.34 MW |
| Details for 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247966 | 05WTRV SLR E | 50/50 | 0.31 MW | 0.31 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 918052 | AA1-018 E OP | Adder | -9.22 MW | -7.83 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926311 | AC1-109 1 | Adder | -1.03 MW | -0.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926321 | AC1-109 2 | Adder | -1.03 MW | -0.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926331 | AC1-110 1 | Adder | -1.03 MW | -0.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926341 | AC1-110 2 | Adder | -1.03 MW | -0.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926351 | AC1-111 1 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926361 | AC1-111 2 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926371 | AC1-111 3 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926381 | AC1-111 4 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926391 | AC1-111 5 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926401 | AC1-111 6 | Adder | -0.41 MW | -0.35 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926431 | AC1-114 | Adder | -1.32 MW | -1.12 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 927511 | AC1-113 1 | Adder | -0.66 MW | -0.56 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 927521 | AC1-113 2 | Adder | -0.66 MW | -0.56 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 934431 | AD1-067 C | Adder | -0.07 MW | -0.06 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 936141 | AD2-020 C O1 | 50/50 | 7.27 MW | 7.27 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 936142 | AD2-020 E O1 | 50/50 | 4.48 MW | 4.48 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 938261 | AE1-039 | 50/50 | 0.11 MW | 0.11 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 943021 | AE2-325 C | 50/50 | 3.68 MW | 3.68 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 943022 | AE2-325 E | 50/50 | 2.45 MW | 2.45 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 944161 | AF1-084 C | 50/50 | 6.7 MW | 6.7 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 944162 | AF1-084 E | 50/50 | 3.83 MW | 3.83 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 944961 | AF1-161 C | 50/50 | 2.94 MW | 2.94 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 944962 | AF1-161 E | 50/50 | 2.94 MW | 2.94 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 945111 | AF1-176 C O1 | Adder | 15.07 MW | 12.81 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 945112 | AF1-176 E O1 | Adder | 13.97 MW | 11.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 960981 | AF2-389 C | Adder | 2.71 MW | 2.3 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 960982 | AF2-389 E | Adder | 1.81 MW | 1.54 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 961051 | AF2-396 O1 | 50/50 | 21.87 MW | 21.87 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 243440 | 05CKG1 | 50/50 | 51.12 MW | 51.12 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 243441 | 05CKG2 | 50/50 | 57.7 MW | 57.7 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 244412 | 05WTRV SLR C | 50/50 | 0.05 MW | 0.05 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 916221 | Z1-073 E | Adder | -2.98 MW | -2.54 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 932881 | AC2-115 1 | Adder | -1.32 MW | -1.12 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 932891 | AC2-115 2 | Adder | -1.32 MW | -1.12 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 932921 | AC2-116 | Adder | -0.46 MW | -0.39 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 933281 | AC2-140 C | 50/50 | 11.0 MW | 11.0 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957891 | AF2-083 C O1 | Adder | 9.04 MW | 7.68 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957892 | AF2-083 E O1 | Adder | 4.52 MW | 3.84 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247528 | 05COVRT1 | 50/50 | 7.67 MW | 7.67 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247529 | 05COVRT2 | 50/50 | 7.67 MW | 7.67 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247530 | 05COVRT3 | 50/50 | 7.67 MW | 7.67 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247531 | 05COVRT4 | 50/50 | 4.6 MW | 4.6 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247532 | 05COVRT5 | 50/50 | 4.6 MW | 4.6 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247533 | 05COVRT6 | 50/50 | 4.6 MW | 4.6 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 925961 | AC1-072 | 50/50 | 0.71 MW | 0.71 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 926581 | AC1-141 | 50/50 | 2.74 MW | 2.74 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 932931 | AC2-117 | Adder | -4.24 MW | -3.6 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 939391 | AE1-170 C O1 | 50/50 | 7.16 MW | 7.16 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 939392 | AE1-170 E O1 | 50/50 | 9.89 MW | 9.89 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247604 | X1-042 | 50/50 | 0.07 MW | 0.07 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 247651 | AA2-116 | 50/50 | 29.97 MW | 29.97 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 276172 | Z1-108 BAT | Adder | 1.6 MW | 1.36 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 920273 | AA2-123 BAT | Adder | 1.58 MW | 1.34 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 945352 | AF1-200 NFTW | Adder | 167.73 MW | 142.57 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 946163 | AF1-281 BAT | Adder | 1.51 MW | 1.28 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957333 | AF2-027 BAT | Adder | 4.02 MW | 3.42 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957373 | AF2-031 BAT | Adder | 1.68 MW | 1.43 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957403 | AF2-034 BAT | Adder | 1.66 MW | 1.41 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 957843 | AF2-078 BAT | Adder | 1.71 MW | 1.46 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 958013 | AF2-095 BAT | Adder | 3.39 MW | 2.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 958023 | AF2-096 BAT | Adder | 6.42 MW | 5.46 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 958923 | AF2-183 BAT | Adder | 6.04 MW | 5.13 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 959353 | AF2-226 BAT | Adder | 4.09 MW | 3.47 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 960283 | AF2-319 BAT | Adder | 4.09 MW | 3.47 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 960382 | AF2-329 BAT | Adder | 3.39 MW | 2.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 960603 | AF2-351 BAT | Adder | 1.7 MW | 1.44 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 961503 | AF2-441 BAT | Adder | 16.85 MW | 14.32 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 943803 | AF1-048 BAT | Adder | 4.12 MW | 3.5 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950311 | G934 C | External Queue | 4.41 MW | 4.41 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950312 | G934 E | External Queue | 17.66 MW | 17.66 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950351 | J466 | External Queue | 3.55 MW | 3.55 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950791 | J201 C | External Queue | 0.5 MW | 0.5 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950792 | J201 E | External Queue | 2.01 MW | 2.01 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950871 | J246 C | External Queue | 0.2 MW | 0.2 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950872 | J246 E | External Queue | 0.8 MW | 0.8 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 950942 | J325 E | External Queue | 0.46 MW | 0.46 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 951531 | J533 C | External Queue | 5.71 MW | 5.71 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 951532 | J533 E | External Queue | 22.83 MW | 22.83 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 951571 | J538 C | External Queue | 3.25 MW | 3.25 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 951572 | J538 E | External Queue | 13.02 MW | 13.02 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952161 | J571 | External Queue | 0.9 MW | 0.9 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952201 | J589 C | External Queue | 4.33 MW | 4.33 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952202 | J589 E | External Queue | 23.41 MW | 23.41 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952312 | J646 E | External Queue | 0.17 MW | 0.17 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952401 | J752 C | External Queue | 1.87 MW | 1.87 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952402 | J752 E | External Queue | 10.12 MW | 10.12 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952611 | J717 C | External Queue | 4.14 MW | 4.14 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952612 | J717 E | External Queue | 22.4 MW | 22.4 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952881 | J758 | External Queue | 26.51 MW | 26.51 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953071 | J794 C | External Queue | 0.27 MW | 0.27 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953072 | J794 E | External Queue | 1.43 MW | 1.43 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953271 | J701 C | External Queue | 0.92 MW | 0.92 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953272 | J701 E | External Queue | 4.98 MW | 4.98 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953291 | J796 | External Queue | 31.17 MW | 31.17 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953321 | J799 | External Queue | 18.26 MW | 18.26 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953361 | J806 | External Queue | 18.81 MW | 18.81 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953771 | J832 | External Queue | 14.07 MW | 14.07 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953781 | J833 | External Queue | 9.59 MW | 9.59 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 953941 | J857 | External Queue | 16.14 MW | 16.14 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 954111 | J875 | External Queue | 15.68 MW | 15.68 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952761 | J728 C | External Queue | 3.85 MW | 3.85 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952762 | J728 E | External Queue | 20.86 MW | 20.86 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 952971 | J793 | External Queue | 144.86 MW | 144.86 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 955071 | J984 C | External Queue | 4.59 MW | 4.59 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 955072 | J984 E | External Queue | 24.84 MW | 24.84 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 955181 | J996 | External Queue | 7.62 MW | 7.62 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 955781 | J1062 | External Queue | 12.81 MW | 12.81 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 955861 | J1071 | External Queue | 15.68 MW | 15.68 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | 956741 | J1172 | External Queue | 6.22 MW | 6.22 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 4.15 MW | 4.15 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.27 MW | 0.27 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.88 MW | 1.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.06 MW | 5.06 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 1.43 MW | 1.43 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 9.98 MW | 9.98 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.88 MW | 0.88 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.66 MW | 0.66 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 2.19 MW | 2.19 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 2.85 MW | 2.85 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | LGE-TSR-0092018 | LTFEXP_LGE-TSR-0092018->LTFIMP_LGE-TSR-0092018 | LTF | 0.0 MW | 0.0 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.67 MW | 0.67 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 3.07 MW | 3.07 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.97 MW | 0.97 MW |
| 05COOK-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#7443_05DUMONT 765_A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| Details for 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 246536 | 05MOTTVILL | 80/20 | 0.06 MW | 0.06 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 936141 | AD2-020 C O1 | 80/20 | 3.88 MW | 3.88 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 943021 | AE2-325 C | 80/20 | 1.97 MW | 1.97 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 944161 | AF1-084 C | 80/20 | 3.03 MW | 3.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 944961 | AF1-161 C | 80/20 | 1.57 MW | 1.57 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 945111 | AF1-176 C O1 | 80/20 | 22.62 MW | 22.62 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 960981 | AF2-389 C | 80/20 | 2.15 MW | 2.15 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 961051 | AF2-396 O1 | 80/20 | 19.76 MW | 19.76 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | 957891 | AF2-083 C O1 | 80/20 | 7.25 MW | 7.25 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.33 MW | 0.33 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.02 MW | 0.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.11 MW | 0.11 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.3 MW | 0.3 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.01 MW | 0.01 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#5577 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.0 MW | 1.0 MW |
| Details for 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | 246536 | 05MOTTVILL | 80/20 | 0.04 MW | 0.04 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | 945111 | AF1-176 C O1 | 80/20 | 13.65 MW | 13.65 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | 960981 | AF2-389 C | 80/20 | 1.56 MW | 1.56 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | 961051 | AF2-396 O1 | 80/20 | 13.02 MW | 13.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | 957891 | AF2-083 C O1 | 80/20 | 5.25 MW | 5.25 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.38 MW | 0.38 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.03 MW | 0.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.11 MW | 0.11 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.38 MW | 0.38 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.22 MW | 0.22 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.01 MW | 0.01 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#6388 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.15 MW | 1.15 MW |
| Details for 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | 246536 | 05MOTTVILL | 80/20 | 0.04 MW | 0.04 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | 945111 | AF1-176 C O1 | 80/20 | 14.03 MW | 14.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | 960981 | AF2-389 C | 80/20 | 3.94 MW | 3.94 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | 961051 | AF2-396 O1 | 80/20 | 13.1 MW | 13.1 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | 957891 | AF2-083 C O1 | 80/20 | 13.14 MW | 13.14 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.36 MW | 0.36 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.03 MW | 0.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.15 MW | 0.15 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.27 MW | 0.27 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.17 MW | 0.17 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.78 MW | 0.78 MW |
| Details for 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | 246536 | 05MOTTVILL | 80/20 | 0.04 MW | 0.04 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | 945111 | AF1-176 C O1 | 80/20 | 15.14 MW | 15.14 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | 960981 | AF2-389 C | 80/20 | 1.56 MW | 1.56 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | 961051 | AF2-396 O1 | 80/20 | 21.45 MW | 21.45 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | 957891 | AF2-083 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.37 MW | 0.37 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.03 MW | 0.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.16 MW | 0.16 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.27 MW | 0.27 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_P1-2_#10604 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.71 MW | 0.71 MW |
| Details for 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | 246536 | 05MOTTVILL | 80/20 | 0.04 MW | 0.04 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | 945111 | AF1-176 C O1 | 80/20 | 14.03 MW | 14.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | 961051 | AF2-396 O1 | 80/20 | 13.1 MW | 13.1 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | 957891 | AF2-083 C O1 | 80/20 | 13.14 MW | 13.14 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.36 MW | 0.36 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.03 MW | 0.03 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.15 MW | 0.15 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.27 MW | 0.27 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.17 MW | 0.17 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 05STURGI-17HOWE 69.0 kV Ckt 1 line l/o AEP_SUBT_P1-2_#726-C | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.78 MW | 0.78 MW |
| Details for 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 938261 | AE1-039 | Adder | -0.35 MW | -0.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247528 | 05COVRT1 | 50/50 | 7.99 MW | 7.99 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247529 | 05COVRT2 | 50/50 | 7.99 MW | 7.99 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247530 | 05COVRT3 | 50/50 | 7.99 MW | 7.99 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247531 | 05COVRT4 | 50/50 | 4.79 MW | 4.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247532 | 05COVRT5 | 50/50 | 4.79 MW | 4.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247533 | 05COVRT6 | 50/50 | 4.79 MW | 4.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 925961 | AC1-072 | 50/50 | 0.74 MW | 0.74 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 943023 | AE2-325 BAT | 50/50 | 11.58 MW | 11.58 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 944963 | AF1-161 BAT | 50/50 | 11.09 MW | 11.09 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 945113 | AF1-176 BAT | 50/50 | 13.73 MW | 13.73 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 945352 | AF1-200 NFTW | Adder | 58.01 MW | 49.31 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 961052 | AF2-396 BAT | 50/50 | 14.39 MW | 14.39 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950311 | G934 C | External Queue | 3.49 MW | 3.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950312 | G934 E | External Queue | 13.96 MW | 13.96 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950351 | J466 | External Queue | 2.55 MW | 2.55 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950791 | J201 C | External Queue | 0.37 MW | 0.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950792 | J201 E | External Queue | 1.49 MW | 1.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950871 | J246 C | External Queue | 0.16 MW | 0.16 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950872 | J246 E | External Queue | 0.62 MW | 0.62 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950942 | J325 E | External Queue | 0.33 MW | 0.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951531 | J533 C | External Queue | 4.46 MW | 4.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951532 | J533 E | External Queue | 17.84 MW | 17.84 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951571 | J538 C | External Queue | 2.07 MW | 2.07 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951572 | J538 E | External Queue | 8.28 MW | 8.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952161 | J571 | External Queue | 0.65 MW | 0.65 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952201 | J589 C | External Queue | 3.34 MW | 3.34 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952202 | J589 E | External Queue | 18.05 MW | 18.05 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952312 | J646 E | External Queue | 0.12 MW | 0.12 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952401 | J752 C | External Queue | 1.35 MW | 1.35 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952402 | J752 E | External Queue | 7.33 MW | 7.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952611 | J717 C | External Queue | 3.13 MW | 3.13 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952612 | J717 E | External Queue | 16.95 MW | 16.95 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952881 | J758 | External Queue | 18.86 MW | 18.86 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953071 | J794 C | External Queue | 0.2 MW | 0.2 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953072 | J794 E | External Queue | 1.1 MW | 1.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953271 | J701 C | External Queue | 0.67 MW | 0.67 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953272 | J701 E | External Queue | 3.61 MW | 3.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953291 | J796 | External Queue | 23.44 MW | 23.44 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953321 | J799 | External Queue | 11.71 MW | 11.71 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953361 | J806 | External Queue | 13.23 MW | 13.23 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953771 | J832 | External Queue | 10.89 MW | 10.89 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953781 | J833 | External Queue | 6.11 MW | 6.11 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953941 | J857 | External Queue | 11.4 MW | 11.4 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 954111 | J875 | External Queue | 10.3 MW | 10.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952761 | J728 C | External Queue | 2.91 MW | 2.91 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952762 | J728 E | External Queue | 15.79 MW | 15.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952971 | J793 | External Queue | 100.26 MW | 100.26 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955071 | J984 C | External Queue | 3.63 MW | 3.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955072 | J984 E | External Queue | 19.63 MW | 19.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955181 | J996 | External Queue | 4.76 MW | 4.76 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955781 | J1062 | External Queue | 7.63 MW | 7.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955861 | J1071 | External Queue | 12.59 MW | 12.59 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 956741 | J1172 | External Queue | 4.57 MW | 4.57 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.52 MW | 1.52 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.74 MW | 2.74 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.61 MW | 0.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.63 MW | 3.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.32 MW | 0.32 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.75 MW | 0.75 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.45 MW | 1.45 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.46 MW | 0.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.11 MW | 0.11 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.37 MW | 23.37 MW |
Light Load Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 200.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7508 | Add another 345/138kV transformer with associated equipment | $7,912,565 | |
| (TBD) | Replace 2 Cook circuit breakers (3000A) | $2,000,000 | |
| (TBD) | Replace 2 Olive circuit breakers (3000A) | $2,000,001 | |
| n3800 | Olive - Cook 345 kV Line Sag Study will be required on the 23.6 miles section | $93,600 | |
| n7018 | A Sag Study will be required on the 8.5 mile section of ACSR 477 26/7 HAWK [...] n time would be 24 to 36 months after signing an interconnection agreement. | $34,000 | |
| n7018.1 | Replace 800A Wavetrap at Mottville | $50,000 | |
| n7017 | A Sag Study will be required on the 7.8 mile section of ACSR 477 26/7 HAWK [...] n time would be 24 to 36 months after signing an interconnection agreement. | $31,200 | |
| n8063 | A Sag Study will be required on the 8.5 mile section of ACSR ~ 795 ~ 45/7 [...] n time would be 24 to 36 months after signing an interconnection agreement. | $34,000 | |
| n8062 | A Sag Study will be required on the 0.7 mile section of ACSR 954 45/7 RAIL [...] n time would be 24 to 36 months after signing an interconnection agreement. | $20,000 | |
| n4713 | Reconductor/Reconductor ~3 miles of ACSR 211.6 Penguin (4/0) | $3,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-396 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.