AF2-394 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:09
Nelson-Dixon 138 kV
40.0 MW Capacity / 40.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-394 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the ComEd zone — Adams County, Illinois. The installed facilities will have a total capability of 40.0 MW with 40.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-394 |
| Project Name | Nelson-Dixon 138 kV |
| Developer Name | Bison Meadows Wind Project, LLC |
| State | Illinois |
| County | Adams |
| Transmission Owner | ComEd |
| MFO | 40.0 MW |
| MWE | 40.0 MW |
| MWC | 40.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-394 proposes to add 40 MW battery storage to Bison Meadows Wind Farm built under PJM queue AF2-392. The proposed addition will increase output of Bison Meadows from 260 MW to 300 MW. The proposed addition is behind the Point-of-Interconnection between ComEd and Bison Meadows Wind Farm.
Summer Peak Analysis
The Queue Project was evaluated as a 40.0 MW (Capacity 40.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line
272097 to 271331 ckt 1 |
COMED_P4_155-38-TR81___-A
CONTINGENCY 'COMED_P4_155-38-TR81___-A' TRIP BRANCH FROM BUS 270828 TO BUS 272094 TO BUS 275341 CKT 1 /*NELSON ; B 345.0 - NELSON ; B 138.0 - NELSON ;1C 34.5 TRIP BRANCH FROM BUS 272094 TO BUS 272366 CKT 1 /*NELSON ; B 138.0 - ROCK FALL; B 138.0 TRIP BRANCH FROM BUS 272094 TO BUS 275204 CKT 1 /*NELSON ; B 138.0 - NELSON ;4M 138.0 TRIP BRANCH FROM BUS 272094 TO BUS 961010 CKT 1 /*NELSON ; B 138.0 - AF2-392 TAP 138.0 END |
Breaker | AC | 99.64 % | 104.65 % | 449.0 | STE | 469.88 | 22.55 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 99.95 % | 100.02 % | 1469.0 | STE | 1469.32 | 2.8 | |
| Details for NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 926431 | AC1-114 | Adder | -1.36 MW | -1.16 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 927511 | AC1-113 1 | Adder | -0.68 MW | -0.58 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 927521 | AC1-113 2 | Adder | -0.68 MW | -0.58 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 934431 | AD1-067 C | Adder | -0.32 MW | -0.28 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 276156 | O-029 C | 50/50 | 0.32 MW | 0.32 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 276157 | O-029 C | 50/50 | 0.34 MW | 0.34 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 276158 | O-029 C | 50/50 | 0.62 MW | 0.62 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293513 | O-009 C1 | 50/50 | 0.58 MW | 0.58 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293514 | O-009 C2 | 50/50 | 0.3 MW | 0.3 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293515 | O-009 C3 | 50/50 | 0.33 MW | 0.33 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293516 | O-009 E1 | 50/50 | 13.43 MW | 13.43 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293517 | O-009 E2 | 50/50 | 6.82 MW | 6.82 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293518 | O-009 E3 | 50/50 | 7.51 MW | 7.51 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293715 | O-029 E | 50/50 | 14.36 MW | 14.36 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293716 | O-029 E | 50/50 | 7.88 MW | 7.88 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 293717 | O-029 E | 50/50 | 7.24 MW | 7.24 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 916221 | Z1-073 E | Adder | -13.3 MW | -11.31 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 932881 | AC2-115 1 | Adder | -1.36 MW | -1.16 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 932891 | AC2-115 2 | Adder | -1.36 MW | -1.16 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 932921 | AC2-116 | Adder | -0.48 MW | -0.41 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 946321 | AF1-296 C O1 | Adder | 2.76 MW | 2.35 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 946322 | AF1-296 E O1 | Adder | 12.92 MW | 10.98 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 961022 | AF2-393 BAT | 50/50 | 33.83 MW | 33.83 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | 961032 | AF2-394 BAT | 50/50 | 22.55 MW | 22.55 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.09 MW | 0.09 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.24 MW | 0.24 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.23 MW | 4.23 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.5 MW | 0.5 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.0 MW | 1.0 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 2.67 MW | 2.67 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.4 MW | 1.4 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.57 MW | 2.57 MW |
| NELSON ;RT-DIXON ;8R 138.0 kV Ckt 1 line l/o COMED_P4_155-38-TR81___-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 2.71 MW | 2.71 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.63 MW | 3.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.77 MW | 1.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.67 MW | 1.42 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.27 MW | 1.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.27 MW | 1.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926351 | AC1-111 1 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926361 | AC1-111 2 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926371 | AC1-111 3 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926381 | AC1-111 4 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926391 | AC1-111 5 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926401 | AC1-111 6 | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926431 | AC1-114 | Adder | 1.58 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.38 MW | 4.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927201 | AC1-214 C O1 | Adder | 1.21 MW | 1.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.84 MW | 3.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927511 | AC1-113 1 | Adder | 0.79 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927521 | AC1-113 2 | Adder | 0.79 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.2 MW | 1.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.91 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.04 MW | 0.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.67 MW | 2.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934431 | AD1-067 C | Adder | 0.08 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934721 | AD1-100 C | Adder | 0.88 MW | 0.75 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934722 | AD1-100 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.61 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.41 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.71 MW | 9.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.56 MW | 3.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.04 MW | 2.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.56 MW | 5.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.58 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.75 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.42 MW | 7.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.14 MW | 3.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.6 MW | 4.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.77 MW | 2.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.61 MW | 2.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.74 MW | 1.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.97 MW | 11.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.64 MW | 7.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.49 MW | 3.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.97 MW | 7.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.98 MW | 5.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.3 MW | 9.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.53 MW | 3.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.71 MW | 12.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.81 MW | 8.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.87 MW | 3.29 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.93 MW | 3.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.62 MW | 2.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.61 MW | 3.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.08 MW | 2.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.46 MW | 2.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.53 MW | 9.8 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.2 MW | 3.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 33.56 MW | 33.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.7 MW | 33.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.22 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.22 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274745 | AURORA EC;9P | 50/50 | 0.61 MW | 0.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.61 MW | 0.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.75 MW | 0.75 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.02 MW | 5.97 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.02 MW | 5.97 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.95 MW | 0.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.03 MW | 7.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276167 | Z1-106 E2 | Adder | 0.95 MW | 0.8 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276168 | Z1-106 E1 | Adder | 0.94 MW | 0.8 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276169 | Z1-107 E | Adder | 1.25 MW | 1.06 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.72 MW | 1.46 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.26 MW | 0.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.29 MW | 17.29 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.56 MW | 4.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.11 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.94 MW | 5.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.26 MW | 2.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.76 MW | 3.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.95 MW | 21.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.94 MW | 4.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.94 MW | 4.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.12 MW | 5.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.36 MW | 2.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.36 MW | 2.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.36 MW | 2.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.85 MW | 2.42 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.5 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.81 MW | 0.69 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.41 MW | 4.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 932881 | AC2-115 1 | Adder | 1.58 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 932891 | AC2-115 2 | Adder | 1.58 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 932921 | AC2-116 | Adder | 0.55 MW | 0.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.23 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.52 MW | 2.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.61 MW | 7.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.44 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.3 MW | 3.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.87 MW | 2.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.28 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.87 MW | 8.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.35 MW | 2.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 10.99 MW | 9.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.85 MW | 2.42 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.38 MW | 11.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.37 MW | 1.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.57 MW | 1.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.36 MW | 2.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.54 MW | 0.46 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.46 MW | 11.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 8.97 MW | 7.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.96 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.77 MW | 7.46 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.13 MW | 3.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.42 MW | 19.06 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.55 MW | 8.97 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.07 MW | 6.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274881 | PILOT HIL;1E | Adder | 9.03 MW | 7.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 | Adder | 10.9 MW | 9.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925302 | AB2-191 E | Adder | 0.9 MW | 0.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930481 | AB1-089 | Adder | 44.79 MW | 38.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930751 | AB1-122 2O1 | Adder | 33.57 MW | 28.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.49 MW | 2.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.33 MW | 13.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.93 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.36 MW | 3.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934111 | AD2-000 2 | Adder | 2.72 MW | 2.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.92 MW | 13.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.23 MW | 627.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.36 MW | 2.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.15 MW | 0.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.4 MW | 8.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.42 MW | 0.42 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 7.87 MW | 7.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.94 MW | 0.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.22 MW | 1.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 11.31 MW | 11.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.31 MW | 7.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.32 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.44 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 38.99 MW | 38.99 MW |
Light Load Analysis
The Queue Project was evaluated as a 40.0 MW (Capacity 40.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11216__-S
CONTINGENCY 'COMED_P1-2_765-L11216__-S' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 END |
Single | DC | 99.77 % | 100.04 % | 971.0 | STE | 971.39 | 2.6 | |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274847 | GR RIDGE ;BU | 80/20 | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274849 | CRESCENT ;1U | 80/20 | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274850 | MENDOTA H;RU | 80/20 | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274851 | PROVIDENC;RU | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274855 | GSG-6 ;RU | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.64 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.64 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274859 | EASYR;U1 E | 80/20 | 2.55 MW | 2.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274860 | EASYR;U2 E | 80/20 | 2.55 MW | 2.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274861 | TOP CROP ;1U | 80/20 | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274862 | TOP CROP ;2U | 80/20 | 1.09 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.69 MW | 0.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.69 MW | 0.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274871 | GR RIDGE ;2U | 80/20 | 1.16 MW | 1.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.37 MW | 1.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274877 | BISHOP HL;1U | 80/20 | 0.49 MW | 0.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274878 | BISHOP HL;2U | 80/20 | 0.49 MW | 0.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274879 | MINONK ;1U | 80/20 | 1.13 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274887 | PILOT HIL;1U | 80/20 | 1.06 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 275149 | KELLYCK ;1E | 80/20 | 4.25 MW | 4.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276156 | O-029 C | 80/20 | 0.28 MW | 0.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276157 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276158 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290021 | O50 E | 80/20 | 4.51 MW | 4.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290051 | GSG-6; E | 80/20 | 2.44 MW | 2.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290108 | LEEDK;1U E | 80/20 | 5.7 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293061 | N-015 E | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293513 | O-009 C1 | 80/20 | 0.52 MW | 0.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293514 | O-009 C2 | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293515 | O-009 C3 | 80/20 | 0.29 MW | 0.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293516 | O-009 E1 | 80/20 | 2.1 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293517 | O-009 E2 | 80/20 | 1.06 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293518 | O-009 E3 | 80/20 | 1.17 MW | 1.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293644 | O22 E1 | 80/20 | 2.24 MW | 2.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293645 | O22 E2 | 80/20 | 4.35 MW | 4.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293715 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293716 | O-029 E | 80/20 | 1.23 MW | 1.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293717 | O-029 E | 80/20 | 1.13 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293771 | O-035 E | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294392 | P-010 E | 80/20 | 4.63 MW | 4.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294401 | BSHIL;1U E | 80/20 | 1.96 MW | 1.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294410 | BSHIL;2U E | 80/20 | 1.96 MW | 1.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294763 | P-046 E | 80/20 | 2.19 MW | 2.19 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295108 | WESTBROOK C | 80/20 | 0.22 MW | 0.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917502 | Z2-087 E | 80/20 | 3.77 MW | 3.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924041 | AB2-047 C O1 | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924042 | AB2-047 E O1 | 80/20 | 9.42 MW | 9.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925581 | AC1-033 C | 80/20 | 0.64 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925582 | AC1-033 E | 80/20 | 4.3 MW | 4.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926821 | AC1-168 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926822 | AC1-168 E O1 | 80/20 | 3.54 MW | 3.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927202 | AC1-214 E O1 | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934432 | AD1-067 E | 80/20 | 0.26 MW | 0.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934721 | AD1-100 C | 80/20 | 8.21 MW | 8.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934722 | AD1-100 E | 80/20 | 38.3 MW | 38.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936371 | AD2-047 C O1 | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936372 | AD2-047 E O1 | 80/20 | 10.07 MW | 10.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937001 | AD2-134 C | 80/20 | 1.18 MW | 1.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937002 | AD2-134 E | 80/20 | 4.73 MW | 4.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938861 | AE1-114 C O1 | 80/20 | 1.83 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938862 | AE1-114 E O1 | 80/20 | 6.23 MW | 6.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939321 | AE1-163 C O1 | 80/20 | 2.9 MW | 2.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939322 | AE1-163 E O1 | 80/20 | 17.79 MW | 17.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939401 | AE1-172 C O1 | 80/20 | 2.14 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939402 | AE1-172 E O1 | 80/20 | 10.04 MW | 10.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 941731 | AE2-173 O1 | 80/20 | 2.71 MW | 2.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942111 | AE2-223 C | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942112 | AE2-223 E | 80/20 | 5.65 MW | 5.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942421 | AE2-255 C O1 | 80/20 | 1.41 MW | 1.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942422 | AE2-255 E O1 | 80/20 | 4.23 MW | 4.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942651 | AE2-281 C O1 | 80/20 | 0.41 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942652 | AE2-281 E O1 | 80/20 | 2.54 MW | 2.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943801 | AF1-048 C | 80/20 | 2.25 MW | 2.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943802 | AF1-048 E | 80/20 | 1.5 MW | 1.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946321 | AF1-296 C O1 | 80/20 | 1.8 MW | 1.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946322 | AF1-296 E O1 | 80/20 | 8.44 MW | 8.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946501 | AF1-314 C | 80/20 | 2.03 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946502 | AF1-314 E | 80/20 | 9.55 MW | 9.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957331 | AF2-027 C | 80/20 | 1.48 MW | 1.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957332 | AF2-027 E | 80/20 | 2.22 MW | 2.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957371 | AF2-031 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957372 | AF2-031 E O1 | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957401 | AF2-034 C | 80/20 | 0.82 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957402 | AF2-034 E | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957751 | AF2-069 C | 80/20 | 0.11 MW | 0.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957752 | AF2-069 E | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957761 | AF2-070 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957762 | AF2-070 E | 80/20 | 0.74 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958921 | AF2-183 C | 80/20 | 2.11 MW | 2.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958922 | AF2-183 E | 80/20 | 3.16 MW | 3.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959102 | AF2-201 E O1 | 80/20 | 9.56 MW | 9.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959351 | AF2-226 C | 80/20 | 1.37 MW | 1.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959352 | AF2-226 E | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960281 | AF2-319 C | 80/20 | 1.37 MW | 1.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960282 | AF2-319 E | 80/20 | 2.06 MW | 2.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960381 | AF2-329 | 80/20 | 3.16 MW | 3.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960601 | AF2-351 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960602 | AF2-351 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961011 | AF2-392 C O1 | 80/20 | 1.83 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961012 | AF2-392 E O1 | 80/20 | 8.56 MW | 8.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961031 | AF2-394 O1 | 80/20 | 2.6 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936291 | AD2-038 C O1 | 80/20 | 1.15 MW | 1.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936292 | AD2-038 E O1 | 80/20 | 7.71 MW | 7.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274881 | PILOT HIL;1E | 80/20 | 4.25 MW | 4.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274888 | KELLYCK ;1U | 80/20 | 1.06 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274890 | CAYUG;1U E | 80/20 | 2.77 MW | 2.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274891 | CAYUG;2U E | 80/20 | 2.77 MW | 2.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917501 | Z2-087 C | 80/20 | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 918051 | AA1-018 C OP | 80/20 | 0.64 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925301 | AB2-191 | 80/20 | 0.26 MW | 0.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925302 | AB2-191 E | 80/20 | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938851 | AE1-113 C | 80/20 | 3.72 MW | 3.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938852 | AE1-113 E | 80/20 | 13.2 MW | 13.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 940752 | AE2-062 E | 80/20 | 0.08 MW | 0.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946162 | AF1-281 E | 80/20 | 1.12 MW | 1.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946541 | AF1-318 C O1 | 80/20 | 2.64 MW | 2.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946542 | AF1-318 E O1 | 80/20 | 12.37 MW | 12.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958341 | AF2-128 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958342 | AF2-128 E O1 | 80/20 | 3.29 MW | 3.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 990901 | L-005 E | 80/20 | 2.89 MW | 2.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961021 | AF2-393 C | 80/20 | 3.57 MW | 3.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961023 | AF2-393 E | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945351 | AF1-200 FTIR | 80/20 | 123.79 MW | 123.79 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n5907 | Reconductor ComEd 138 kV L15508. 351/449/459/498/573 MVA (SN/SLTE/SSTE/SLD/ALDR). | $15,100,000 | |
| (TBD) | ComEd Reinforcement Required | $0 | |
| n8392 | install a new 345kV bus tie circuit breaker at TSS 167 Plano (BT CB 8-14) | $6,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-394 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.