AF2-306 Transition Sort Retool Results -- Qualifies for Expedited Process
v1.00 released 2023-12-14 11:04
Hope-Blevins Valley Tap 69 kV
26.0 MW Capacity / 26.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Eligible for Expedited Process:
The AF2-306 project has been determined to meet the initial screen to be eligible for the Expedited Process according to the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304. Though your project initially screens as eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project from the Expedited Process into TC1. Please see "Expedited Process Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Next Steps for your project:
Refreshed Retool for Projects in Expedited Process:
After the initial sorting retool, PJM will conduct a refreshed analysis of the projects in the Expedited Process with the Transition Cycle #1 projects lifted from the study case model. After this refreshed analysis (including load flow, short circuit and stability analysis), retooled System Impact Study reports can be delivered to the Project Developers. Once the project's Facilities Study report is completed (and no conditions exist that would require the project to shift to TC1, see "Expedited Process Rules" below), the final GIA will be tendered along with the Facilities Study report.
Expedited Process Rules:
Though your project initially screens to be eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project into TC1 until the final GIA is tendered.
- If stability analysis or a sag study is completed during the expedited process, and it is determined that a project has an estimated Network Upgrade cost greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If it is determined during the Facilities Study that the cost of a Network Upgrade is now estimated to be greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
- If the interconnected Transmission Owner identifies the need for a Network Upgrade due to a violation of their criteria that is in excess of $5M, the project will be removed from the expedited process and shifted to Transition Cycle #1.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the EKPC zone — Barren County, Kentucky. The installed facilities will have a total capability of 26.0 MW with 26.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-306 |
| Project Name | Hope-Blevins Valley Tap 69 kV |
| Developer Name | Flat Top Solar Project, LLC |
| State | Kentucky |
| County | Barren |
| Transmission Owner | EKPC |
| MFO | 26.0 MW |
| MWE | 26.0 MW |
| MWC | 26.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-306 will interconnect on the EKPC transmission system tapping of the Hope to Blevins Valley Tap 69 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 26.0 MW (Capacity 26.0 MW) injection in the EKPC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| EKPC |
2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line
342091 to 341923 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 151.28 % | 154.64 % | 63.0 | B | 97.42 | 2.49 | |
| EKPC/LGEE |
4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line
342649 to 324302 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 106.92 % | 109.76 % | 191.0 | B | 209.64 | 4.93 | |
| EKPC |
4GODDARD-4CRANSTON 138.0 kV Ckt 1 line
342589 to 342571 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 101.8 % | 103.34 % | 255.0 | B | 263.52 | 3.54 | |
| EKPC |
4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line
342571 to 342649 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 101.78 % | 103.33 % | 255.0 | B | 263.49 | 3.54 | |
| EKPC |
2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line
342100 to 341683 ckt 1 |
EKPC_P4-6_SPUR N39-92T
CONTINGENCY 'EKPC_P4-6_SPUR N39-92T' OPEN BRANCH FROM BUS 342622 TO BUS 342625 CKT 1 /*4MAYSVIL I T 138.0 - 4MAYSVIL IND 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342634 CKT 1 /*4MAYSVIL I T 138.0 - 4PLUMVILLE 138.0 OPEN BRANCH FROM BUS 342622 TO BUS 342664 CKT 1 /*4MAYSVIL I T 138.0 - 4SPURLOCK 138.0 OPEN BRANCH FROM BUS 945910 TO BUS 342664 CKT 1 /*AF1-256 TAP 138.0 - 4SPURLOCK 138.0 END |
Breaker | AC | 81.54 % | 102.78 % | 63.0 | B | 64.75 | 12.65 | |
| Details for 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 35.18 MW | 35.18 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 17.38 MW | 17.38 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 11.21 MW | 11.21 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 7.47 MW | 7.47 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960151 | AF2-306 | Adder | 2.49 MW | 2.12 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960161 | AF2-307 C | Adder | 3.79 MW | 3.22 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960162 | AF2-307 E | Adder | 2.53 MW | 2.15 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 15.96 MW | 15.96 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 7.91 MW | 7.91 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 19.93 MW | 19.93 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 9.9 MW | 9.9 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.05 MW | 0.05 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.05 MW | 0.05 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.12 MW | 0.12 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.07 MW | 0.07 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.06 MW | 0.06 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.01 MW | 0.01 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.02 MW | 0.02 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.33 MW | 0.33 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.08 MW | 0.08 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.04 MW | 0.04 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.28 MW | 0.28 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.19 MW | 0.19 MW |
| 2PLUMVILLE-2MURPHYSVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 79.69 MW | 79.69 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 39.37 MW | 39.37 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 25.4 MW | 25.4 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 16.93 MW | 16.93 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960151 | AF2-306 | 50/50 | 4.93 MW | 4.93 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960161 | AF2-307 C | 50/50 | 7.51 MW | 7.51 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960162 | AF2-307 E | 50/50 | 5.01 MW | 5.01 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 25.62 MW | 25.62 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 12.69 MW | 12.69 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 31.98 MW | 31.98 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 15.9 MW | 15.9 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.12 MW | 0.12 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.05 MW | 0.05 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.09 MW | 0.09 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.24 MW | 0.24 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.02 MW | 0.02 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.03 MW | 0.03 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.43 MW | 0.43 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.07 MW | 0.07 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.35 MW | 0.35 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.42 MW | 0.42 MW |
| 4ROWAN CO-4RODBURN 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| Details for 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936381 | AD2-048 C | Adder | 2.69 MW | 2.29 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936382 | AD2-048 E | Adder | 1.34 MW | 1.14 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 88.92 MW | 88.92 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 43.93 MW | 43.93 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 28.34 MW | 28.34 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 18.89 MW | 18.89 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960151 | AF2-306 | 50/50 | 3.54 MW | 3.54 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960161 | AF2-307 C | 50/50 | 5.39 MW | 5.39 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960162 | AF2-307 E | 50/50 | 3.59 MW | 3.59 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 28.41 MW | 28.41 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 14.07 MW | 14.07 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 35.48 MW | 35.48 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 17.63 MW | 17.63 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.34 MW | 0.34 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.39 MW | 0.39 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 4GODDARD-4CRANSTON 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.46 MW | 0.46 MW |
| Details for 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936381 | AD2-048 C | Adder | 2.69 MW | 2.29 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 936382 | AD2-048 E | Adder | 1.34 MW | 1.14 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945681 | AF1-233 C | 50/50 | 88.92 MW | 88.92 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945682 | AF1-233 E | 50/50 | 43.93 MW | 43.93 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945911 | AF1-256 C | 50/50 | 28.34 MW | 28.34 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945912 | AF1-256 E | 50/50 | 18.89 MW | 18.89 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960151 | AF2-306 | 50/50 | 3.54 MW | 3.54 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960161 | AF2-307 C | 50/50 | 5.39 MW | 5.39 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960162 | AF2-307 E | 50/50 | 3.59 MW | 3.59 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940531 | AE2-038 C O1 | 50/50 | 28.41 MW | 28.41 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 940532 | AE2-038 E O1 | 50/50 | 14.07 MW | 14.07 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939141 | AE2-000C C | 50/50 | 35.48 MW | 35.48 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 939142 | AE2-000C E | 50/50 | 17.63 MW | 17.63 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.34 MW | 0.34 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.39 MW | 0.39 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 4CRANSTON-4ROWAN CO 138.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.46 MW | 0.46 MW |
| Details for 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 945683 | AF1-233 BAT | Adder | 4.33 MW | 3.68 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | 960152 | AF2-306 BAT | 50/50 | 12.65 MW | 12.65 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.02 MW | 0.02 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.76 MW | 0.76 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.11 MW | 0.11 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.25 MW | 0.25 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.15 MW | 1.15 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.02 MW | 0.02 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.11 MW | 0.11 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.1 MW | 0.1 MW |
| 2POWELL CO-2JEFFERSNVIL 69.0 kV Ckt 1 line l/o EKPC_P4-6_SPUR N39-92T | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.47 MW | 0.47 MW |
Light Load Analysis
The Queue Project was evaluated as a 26.0 MW (Capacity 26.0 MW) injection in the EKPC area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7008 | Increase the maximum operating temperature of the 266 MCM ACSR conductor in the Powell County-Jeffersonville Tap 69 kV line section to 266 degrees F (8.5 miles) | $675,000 | |
| n6480.5 | Change the Zone 3 relay setting at Murphysville associated with the line protection to at least 108 MVA LTE rating. | $0 | |
| n6480.4 | Replace the 600A disconnect switches N34-613 and N34-615 at the Plumville substation with 1200A equipment | $100,000 | |
| n6480.3 | Replace the 4/0 copper bus and jumpers at the Plumville substation using 750 MCM copper or equivalent | $120,000 | |
| n6480 | Increase the maximum operating temperature of the 266 MCM ACSR conductor in the Murphysville-Plumville 69 kV line section to 266 degrees F (9.9 miles) | $650,000 | |
| n6480.2 | Replace the 4/0 copper bus and jumpers at the Murphysville substation using 750 MCM copper or equivalent | $120,000 | |
| n6480.1 | Rebuild the Plumville-Murphysville 69 kV line section using 795 MCM ACSR conductor at 212 degrees F (9.9 miles) | $8,140,000 | |
| n6828 | Increase the maximum operating temperature of the 795 MCM ACSR conductor in the Goddard-Cranston 138 kV line section to 275 degrees F (12.7 miles) | $1,150,000 | |
| n6829 | Increase the maximum operating temperature of the 795 MCM ACSR conductor in the Cranston-Rowan County 138 kV line section to 275 degrees F (7.5 miles) | $680,000 | |
| n6827 | Replace the 800A wave trap at Rodburn substation with 1200A equipment. | $90,000 | |
| (TBD) | LGEE violation (non PJM area). EKPC emergency rating at 255 MVA The extern [...] Owner, LGEE, will not evaluate this violation until the facility study phase. | $0 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-306 is eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A). See next steps for your project in the "Introduction" section above.