AF2-201 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:08
Lena 138 kV
51.4 MW Capacity / 199.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-201 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Wind; Solar generating facility located in the ComEd zone — Stephenson County, Illinois. The installed facilities will have a total capability of 199.0 MW with 51.4 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-201 |
| Project Name | Lena 138 kV |
| Developer Name | Blue Violet Energy, LLC |
| State | Illinois |
| County | Stephenson |
| Transmission Owner | ComEd |
| MFO | 199.0 MW |
| MWE | 199.0 MW |
| MWC | 51.4 MW |
| Fuel Type | Wind; Solar |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-201 will interconnect on the ComEd transmission system. Under a prior queue position AF1-314, a new substation would be built adjacent to Lena. It is proposed to interconnect AF2- 201 generator lead to the interconnection substation to be built for AF1-314.
Summer Peak Analysis
The Queue Project was evaluated as a 199.0 MW (Capacity 51.4 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line
271897 to 272240 ckt 1 |
COMED_P2-2_119_LN-138___6
CONTINGENCY 'COMED_P2-2_119_LN-138___6' TRIP BRANCH FROM BUS 271897 TO BUS 271499 CKT 1 /*LANCASTER; R 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 271898 CKT 1 /*LANCASTER; R 138.0 - LANCASTER;BT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272598 CKT 1 /*LANCASTER; R 138.0 - ESS B427 ;1T 138.0 END |
Bus | AC | 81.29 % | 136.92 % | 316.0 | ALDR | 432.66 | 175.72 | |
| CE |
PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line
272240 to 272747 ckt 1 |
COMED_P2-2_119_LN-138___6
CONTINGENCY 'COMED_P2-2_119_LN-138___6' TRIP BRANCH FROM BUS 271897 TO BUS 271499 CKT 1 /*LANCASTER; R 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 271898 CKT 1 /*LANCASTER; R 138.0 - LANCASTER;BT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272598 CKT 1 /*LANCASTER; R 138.0 - ESS B427 ;1T 138.0 END |
Bus | AC | 78.91 % | 134.61 % | 316.0 | ALDR | 425.37 | 175.72 | |
| CE |
LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line
271897 to 271499 ckt 1 |
COMED_P2-2_119_LN-138___5-A
CONTINGENCY 'COMED_P2-2_119_LN-138___5-A' MOVE 100 PERCENT LOAD FROM BUS 271396 TO BUS 271397 /*ELEROY ; B 138.0 - ELEROY ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271494 TO BUS 271495 /*FREEPORT ;2R 138.0 - FREEPORT ;5R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271897 TO BUS 271495 /*LANCASTER; R 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 271396 CKT 1 /*ELEROY ;BT 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271494 TO BUS 274184 CKT 7 /*FREEPORT ;2R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271498 TO BUS 271398 CKT 1 /*FREEPORT ;BT 138.0 - ELEROY ;BT 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271494 CKT 1 /*FREEPORT ;BT 138.0 - FREEPORT ;2R 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271897 CKT 1 /*FREEPORT ;BT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272240 CKT 1 /*LANCASTER; R 138.0 - PECATONIC; B 138.0 END |
Bus | AC | 74.68 % | 102.89 % | 386.0 | ALDR | 397.15 | 106.49 | |
| CE |
LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line
271897 to 272240 ckt 1 |
COMED_P4_119-38-L11902_C
CONTINGENCY 'COMED_P4_119-38-L11902_C' TRIP BRANCH FROM BUS 271897 TO BUS 271499 CKT 1 /*LANCASTER; R 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272598 CKT 1 /*LANCASTER; R 138.0 - ESS B427 ;1T 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 272596 CKT 1 /*ESS B427 ;1T 138.0 - ESS B427 ; B 138.0 TRIP BRANCH FROM BUS 938860 TO BUS 272598 CKT 1 /*AE1-114 TAP 138.0 - ESS B427 ;1T 138.0 END |
Breaker | AC | 81.29 % | 136.92 % | 316.0 | ALDR | 432.66 | 175.72 | |
| CE |
LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line
271897 to 272240 ckt 1 |
COMED_P4_194-38-L19414_
CONTINGENCY 'COMED_P4_194-38-L19414_' CLOSE BRANCH FROM BUS 272596 TO BUS 272597 CKT 1 /*ESS B427 ; B 138.0 - ESS B427 ; R 138.0 DISCONNECT BUS 272433 /*SABROOKE ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271495 TO BUS 271494 /*FREEPORT ;5R 138.0 - FREEPORT ;2R 138.0 MOVE 100 PERCENT LOAD FROM BUS 272245 TO BUS 272244 /*PIERPONT ; R 138.0 - PIERPONT ; B 138.0 MOVE 100 PERCENT LOAD FROM BUS 272433 TO BUS 272432 /*SABROOKE ; R 138.0 - SABROOKE ; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272240 /*S PECATON; R 138.0 - PECATONIC; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272244 /*S PECATON; R 138.0 - PIERPONT ; B 138.0 TRIP BRANCH FROM BUS 271483 TO BUS 273154 CKT 1 /*FORDAM ; R 138.0 - FORDAM ; R 12.5 TRIP BRANCH FROM BUS 271495 TO BUS 274184 CKT 6 /*FREEPORT ;5R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271499 TO BUS 271495 CKT 1 /*FREEPORT ;RT 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271499 TO BUS 271897 CKT 1 /*FREEPORT ;RT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272245 TO BUS 271483 CKT 1 /*PIERPONT ; R 138.0 - FORDAM ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272245 CKT 1 /*PIERPONT ;RT 138.0 - PIERPONT ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272491 CKT 1 /*PIERPONT ;RT 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272433 TO BUS 272247 CKT 1 /*SABROOKE ; R 138.0 - PIERPONT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 271499 CKT 1 /*ESS B427 ;4T 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272491 CKT 1 /*ESS B427 ;4T 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272597 CKT 1 /*ESS B427 ;4T 138.0 - ESS B427 ; R 138.0 END |
Breaker | AC | 79.67 % | 114.45 % | 316.0 | ALDR | 361.65 | 115.08 | |
| CE |
PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line
272240 to 272747 ckt 1 |
COMED_P4_119-38-L11902_C
CONTINGENCY 'COMED_P4_119-38-L11902_C' TRIP BRANCH FROM BUS 271897 TO BUS 271499 CKT 1 /*LANCASTER; R 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272598 CKT 1 /*LANCASTER; R 138.0 - ESS B427 ;1T 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 272596 CKT 1 /*ESS B427 ;1T 138.0 - ESS B427 ; B 138.0 TRIP BRANCH FROM BUS 938860 TO BUS 272598 CKT 1 /*AE1-114 TAP 138.0 - ESS B427 ;1T 138.0 END |
Breaker | AC | 78.91 % | 134.61 % | 316.0 | ALDR | 425.37 | 175.72 | |
| CE |
PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line
272240 to 272747 ckt 1 |
COMED_P4_194-38-L19414_
CONTINGENCY 'COMED_P4_194-38-L19414_' CLOSE BRANCH FROM BUS 272596 TO BUS 272597 CKT 1 /*ESS B427 ; B 138.0 - ESS B427 ; R 138.0 DISCONNECT BUS 272433 /*SABROOKE ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271495 TO BUS 271494 /*FREEPORT ;5R 138.0 - FREEPORT ;2R 138.0 MOVE 100 PERCENT LOAD FROM BUS 272245 TO BUS 272244 /*PIERPONT ; R 138.0 - PIERPONT ; B 138.0 MOVE 100 PERCENT LOAD FROM BUS 272433 TO BUS 272432 /*SABROOKE ; R 138.0 - SABROOKE ; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272240 /*S PECATON; R 138.0 - PECATONIC; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272244 /*S PECATON; R 138.0 - PIERPONT ; B 138.0 TRIP BRANCH FROM BUS 271483 TO BUS 273154 CKT 1 /*FORDAM ; R 138.0 - FORDAM ; R 12.5 TRIP BRANCH FROM BUS 271495 TO BUS 274184 CKT 6 /*FREEPORT ;5R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271499 TO BUS 271495 CKT 1 /*FREEPORT ;RT 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271499 TO BUS 271897 CKT 1 /*FREEPORT ;RT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272245 TO BUS 271483 CKT 1 /*PIERPONT ; R 138.0 - FORDAM ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272245 CKT 1 /*PIERPONT ;RT 138.0 - PIERPONT ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272491 CKT 1 /*PIERPONT ;RT 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272433 TO BUS 272247 CKT 1 /*SABROOKE ; R 138.0 - PIERPONT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 271499 CKT 1 /*ESS B427 ;4T 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272491 CKT 1 /*ESS B427 ;4T 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272597 CKT 1 /*ESS B427 ;4T 138.0 - ESS B427 ; R 138.0 END |
Breaker | AC | 75.96 % | 110.77 % | 316.0 | ALDR | 350.05 | 115.08 | |
| CE |
LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line
271897 to 271499 ckt 1 |
COMED_P4_119-38-L17121_A
CONTINGENCY 'COMED_P4_119-38-L17121_A' MOVE 100 PERCENT LOAD FROM BUS 271396 TO BUS 271397 /*ELEROY ; B 138.0 - ELEROY ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271494 TO BUS 271495 /*FREEPORT ;2R 138.0 - FREEPORT ;5R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271897 TO BUS 271495 /*LANCASTER; R 138.0 - FREEPORT ;5R 138.0 MOVE 100 PERCENT LOAD FROM BUS 272240 TO BUS 272746 /*PECATONIC; B 138.0 - WEMPLETOW; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 271396 CKT 1 /*ELEROY ;BT 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271494 TO BUS 274184 CKT 7 /*FREEPORT ;2R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271498 TO BUS 271398 CKT 1 /*FREEPORT ;BT 138.0 - ELEROY ;BT 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271494 CKT 1 /*FREEPORT ;BT 138.0 - FREEPORT ;2R 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271897 CKT 1 /*FREEPORT ;BT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272240 TO BUS 271897 CKT 1 /*PECATONIC; B 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272747 TO BUS 272240 CKT 1 /*WEMPLETOW; R 138.0 - PECATONIC; B 138.0 END |
Breaker | AC | 74.68 % | 102.89 % | 386.0 | ALDR | 397.15 | 106.49 | |
| CE |
LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line
271897 to 271499 ckt 1 |
COMED_P4_119-38-L11904_A
CONTINGENCY 'COMED_P4_119-38-L11904_A' MOVE 100 PERCENT LOAD FROM BUS 271396 TO BUS 271397 /*ELEROY ; B 138.0 - ELEROY ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271494 TO BUS 271495 /*FREEPORT ;2R 138.0 - FREEPORT ;5R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271897 TO BUS 271495 /*LANCASTER; R 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 271396 CKT 1 /*ELEROY ;BT 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271494 TO BUS 274184 CKT 7 /*FREEPORT ;2R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271498 TO BUS 271398 CKT 1 /*FREEPORT ;BT 138.0 - ELEROY ;BT 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271494 CKT 1 /*FREEPORT ;BT 138.0 - FREEPORT ;2R 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271897 CKT 1 /*FREEPORT ;BT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272240 CKT 1 /*LANCASTER; R 138.0 - PECATONIC; B 138.0 END |
Breaker | AC | 74.68 % | 102.89 % | 386.0 | ALDR | 397.15 | 106.49 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 113.72 % | 114.1 % | 971.0 | B | 1107.91 | 19.03 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 113.61 % | 113.98 % | 971.0 | B | 1106.75 | 19.01 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 113.61 % | 113.98 % | 971.0 | B | 1106.75 | 19.01 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 113.72 % | 114.03 % | 971.0 | B | 1107.23 | 18.89 | |
| CE |
NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line
270828 to 957470 ckt 1 |
COMED_P4_155-45-BT6-7__
CONTINGENCY 'COMED_P4_155-45-BT6-7__' TRIP BRANCH FROM BUS 270828 TO BUS 946160 CKT 1 /*NELSON ; B 345.0 - AF1-281 TAP 345.0 TRIP BRANCH FROM BUS 275204 TO BUS 270828 CKT 1 /*NELSON ;4M 138.0 - NELSON ; B 345.0 TRIP BRANCH FROM BUS 275204 TO BUS 272094 CKT 1 /*NELSON ;4M 138.0 - NELSON ; B 138.0 TRIP BRANCH FROM BUS 275204 TO BUS 275304 CKT 1 /*NELSON ;4M 138.0 - NELSON ;4C 34.5 END |
Breaker | AC | 99.86 % | 100.48 % | 1837.0 | STE | 1845.78 | 13.19 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 112.81 % | 113.05 % | 971.0 | STE | 1097.72 | 18.89 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 112.23 % | 112.48 % | 971.0 | STE | 1092.18 | 19.03 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 112.14 % | 112.38 % | 971.0 | STE | 1091.21 | 19.01 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 112.13 % | 112.38 % | 971.0 | STE | 1091.21 | 19.01 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 110.88 % | 110.91 % | 1399.0 | B | 1551.63 | 24.15 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 110.78 % | 110.81 % | 1399.0 | B | 1550.23 | 23.95 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 110.55 % | 110.58 % | 1399.0 | B | 1547.01 | 24.07 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 110.53 % | 110.57 % | 1399.0 | B | 1546.87 | 24.07 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_023-65-BT4-5__
CONTINGENCY 'COMED_P4_023-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 110.46 % | 110.49 % | 1399.0 | B | 1545.76 | 24.05 | |
| CE |
LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line
271897 to 272240 ckt 1 |
COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A
CONTINGENCY 'COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A' CLOSE BRANCH FROM BUS 272596 TO BUS 272597 CKT 1 /*ESS B427 ; B 138.0 - ESS B427 ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271495 TO BUS 271494 /*FREEPORT ;5R 138.0 - FREEPORT ;2R 138.0 MOVE 100 PERCENT LOAD FROM BUS 272245 TO BUS 272244 /*PIERPONT ; R 138.0 - PIERPONT ; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272240 /*S PECATON; R 138.0 - PECATONIC; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272244 /*S PECATON; R 138.0 - PIERPONT ; B 138.0 TRIP BRANCH FROM BUS 271483 TO BUS 273154 CKT 1 /*FORDAM ; R 138.0 - FORDAM ; R 12.5 TRIP BRANCH FROM BUS 271495 TO BUS 274184 CKT 6 /*FREEPORT ;5R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271499 TO BUS 271495 CKT 1 /*FREEPORT ;RT 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271499 TO BUS 271897 CKT 1 /*FREEPORT ;RT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272245 TO BUS 271483 CKT 1 /*PIERPONT ; R 138.0 - FORDAM ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272245 CKT 1 /*PIERPONT ;RT 138.0 - PIERPONT ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272491 CKT 1 /*PIERPONT ;RT 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272433 TO BUS 272247 CKT 1 /*SABROOKE ; R 138.0 - PIERPONT ;RT 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 271897 CKT 1 /*ESS B427 ;1T 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 272596 CKT 1 /*ESS B427 ;1T 138.0 - ESS B427 ; B 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 271499 CKT 1 /*ESS B427 ;4T 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272491 CKT 1 /*ESS B427 ;4T 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272597 CKT 1 /*ESS B427 ;4T 138.0 - ESS B427 ; R 138.0 TRIP BRANCH FROM BUS 938860 TO BUS 272598 CKT 1 /*AE1-114 TAP 138.0 - ESS B427 ;1T 138.0 END |
Tower | AC | 83.82 % | 146.66 % | 316.0 | ALDR | 463.43 | 198.98 | |
| CE |
PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line
272240 to 272747 ckt 1 |
COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A
CONTINGENCY 'COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A' CLOSE BRANCH FROM BUS 272596 TO BUS 272597 CKT 1 /*ESS B427 ; B 138.0 - ESS B427 ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271495 TO BUS 271494 /*FREEPORT ;5R 138.0 - FREEPORT ;2R 138.0 MOVE 100 PERCENT LOAD FROM BUS 272245 TO BUS 272244 /*PIERPONT ; R 138.0 - PIERPONT ; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272240 /*S PECATON; R 138.0 - PECATONIC; B 138.0 MOVE 50 PERCENT LOAD FROM BUS 272491 TO BUS 272244 /*S PECATON; R 138.0 - PIERPONT ; B 138.0 TRIP BRANCH FROM BUS 271483 TO BUS 273154 CKT 1 /*FORDAM ; R 138.0 - FORDAM ; R 12.5 TRIP BRANCH FROM BUS 271495 TO BUS 274184 CKT 6 /*FREEPORT ;5R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271499 TO BUS 271495 CKT 1 /*FREEPORT ;RT 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271499 TO BUS 271897 CKT 1 /*FREEPORT ;RT 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272245 TO BUS 271483 CKT 1 /*PIERPONT ; R 138.0 - FORDAM ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272245 CKT 1 /*PIERPONT ;RT 138.0 - PIERPONT ; R 138.0 TRIP BRANCH FROM BUS 272247 TO BUS 272491 CKT 1 /*PIERPONT ;RT 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272433 TO BUS 272247 CKT 1 /*SABROOKE ; R 138.0 - PIERPONT ;RT 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 271897 CKT 1 /*ESS B427 ;1T 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 272596 CKT 1 /*ESS B427 ;1T 138.0 - ESS B427 ; B 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 271499 CKT 1 /*ESS B427 ;4T 138.0 - FREEPORT ;RT 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272491 CKT 1 /*ESS B427 ;4T 138.0 - S PECATON; R 138.0 TRIP BRANCH FROM BUS 272599 TO BUS 272597 CKT 1 /*ESS B427 ;4T 138.0 - ESS B427 ; R 138.0 TRIP BRANCH FROM BUS 938860 TO BUS 272598 CKT 1 /*AE1-114 TAP 138.0 - ESS B427 ;1T 138.0 END |
Tower | AC | 80.13 % | 142.98 % | 316.0 | ALDR | 451.82 | 198.98 | |
| CE |
LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line
271897 to 271499 ckt 1 |
COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A
CONTINGENCY 'COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A' MOVE 100 PERCENT LOAD FROM BUS 272240 TO BUS 272746 /*PECATONIC; B 138.0 - WEMPLETOW; B 138.0 TRIP BRANCH FROM BUS 271897 TO BUS 272598 CKT 1 /*LANCASTER; R 138.0 - ESS B427 ;1T 138.0 TRIP BRANCH FROM BUS 272240 TO BUS 271897 CKT 1 /*PECATONIC; B 138.0 - LANCASTER; R 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 272596 CKT 1 /*ESS B427 ;1T 138.0 - ESS B427 ; B 138.0 TRIP BRANCH FROM BUS 272598 TO BUS 938860 CKT 1 /*ESS B427 ;1T 138.0 - AE1-114 TAP 138.0 TRIP BRANCH FROM BUS 272747 TO BUS 272240 CKT 1 /*WEMPLETOW; R 138.0 - PECATONIC; B 138.0 END |
Tower | AC | 76.35 % | 129.79 % | 386.0 | ALDR | 500.98 | 197.87 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 104.75 % | 104.78 % | 1409.0 | B | 1476.35 | 26.76 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P4_023-65-BT4-5__
CONTINGENCY 'COMED_P4_023-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 102.37 % | 102.4 % | 1409.0 | B | 1442.82 | 27.35 | |
| Details for LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 937311 | AD2-172 C | 50/50 | 18.54 MW | 18.54 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 937312 | AD2-172 E | 50/50 | 25.61 MW | 25.61 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 959101 | AF2-201 C O1 | 50/50 | 45.39 MW | 45.39 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 959102 | AF2-201 E O1 | 50/50 | 130.33 MW | 130.33 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 274856 | ECOGROVE ;U1 | 50/50 | 3.06 MW | 3.06 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 294763 | P-046 E | 50/50 | 70.64 MW | 70.64 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 940501 | AE2-035 C | 50/50 | 18.54 MW | 18.54 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 940502 | AE2-035 E | 50/50 | 25.61 MW | 25.61 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 946501 | AF1-314 C | 50/50 | 32.85 MW | 32.85 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 946502 | AF1-314 E | 50/50 | 154.35 MW | 154.35 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.08 MW | 0.08 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 937311 | AD2-172 C | 50/50 | 18.54 MW | 18.54 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 937312 | AD2-172 E | 50/50 | 25.61 MW | 25.61 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 959101 | AF2-201 C O1 | 50/50 | 45.39 MW | 45.39 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 959102 | AF2-201 E O1 | 50/50 | 130.33 MW | 130.33 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 274856 | ECOGROVE ;U1 | 50/50 | 3.06 MW | 3.06 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 294763 | P-046 E | 50/50 | 70.64 MW | 70.64 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 940501 | AE2-035 C | 50/50 | 18.54 MW | 18.54 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 940502 | AE2-035 E | 50/50 | 25.61 MW | 25.61 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 946501 | AF1-314 C | 50/50 | 32.85 MW | 32.85 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | 946502 | AF1-314 E | 50/50 | 154.35 MW | 154.35 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.08 MW | 0.08 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___6 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 926431 | AC1-114 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 927511 | AC1-113 1 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 927521 | AC1-113 2 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 937311 | AD2-172 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 937312 | AD2-172 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 959101 | AF2-201 C O1 | 50/50 | 27.51 MW | 27.51 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 959102 | AF2-201 E O1 | 50/50 | 78.98 MW | 78.98 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 274856 | ECOGROVE ;U1 | 50/50 | 1.86 MW | 1.86 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 294763 | P-046 E | 50/50 | 42.81 MW | 42.81 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 932881 | AC2-115 1 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 932891 | AC2-115 2 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 932921 | AC2-116 | Adder | -0.45 MW | -0.38 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 938861 | AE1-114 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 938862 | AE1-114 E O1 | 50/50 | 39.15 MW | 39.15 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 940501 | AE2-035 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 940502 | AE2-035 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 946501 | AF1-314 C | 50/50 | 19.91 MW | 19.91 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | 946502 | AF1-314 E | 50/50 | 93.54 MW | 93.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.03 MW | 0.03 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.04 MW | 0.04 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 1.01 MW | 1.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.12 MW | 0.12 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.27 MW | 0.27 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.67 MW | 0.67 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.11 MW | 0.11 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P2-2_119_LN-138___5-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.6 MW | 0.6 MW |
| Details for LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 937311 | AD2-172 C | 50/50 | 18.54 MW | 18.54 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 937312 | AD2-172 E | 50/50 | 25.61 MW | 25.61 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 959101 | AF2-201 C O1 | 50/50 | 45.39 MW | 45.39 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 959102 | AF2-201 E O1 | 50/50 | 130.33 MW | 130.33 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 274856 | ECOGROVE ;U1 | 50/50 | 3.06 MW | 3.06 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 294763 | P-046 E | 50/50 | 70.64 MW | 70.64 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 940501 | AE2-035 C | 50/50 | 18.54 MW | 18.54 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 940502 | AE2-035 E | 50/50 | 25.61 MW | 25.61 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 946501 | AF1-314 C | 50/50 | 32.85 MW | 32.85 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 946502 | AF1-314 E | 50/50 | 154.35 MW | 154.35 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.08 MW | 0.08 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 937311 | AD2-172 C | 50/50 | 12.14 MW | 12.14 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 937312 | AD2-172 E | 50/50 | 16.77 MW | 16.77 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 959101 | AF2-201 C O1 | 50/50 | 29.73 MW | 29.73 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 959102 | AF2-201 E O1 | 50/50 | 85.36 MW | 85.36 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 274856 | ECOGROVE ;U1 | 50/50 | 2.01 MW | 2.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 294763 | P-046 E | 50/50 | 46.27 MW | 46.27 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 938861 | AE1-114 C O1 | 50/50 | 12.42 MW | 12.42 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 938862 | AE1-114 E O1 | 50/50 | 42.36 MW | 42.36 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 940501 | AE2-035 C | 50/50 | 12.14 MW | 12.14 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 940502 | AE2-035 E | 50/50 | 16.77 MW | 16.77 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 946501 | AF1-314 C | 50/50 | 21.51 MW | 21.51 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 946502 | AF1-314 E | 50/50 | 101.09 MW | 101.09 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.04 MW | 0.04 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.85 MW | 0.85 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.1 MW | 0.1 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.2 MW | 0.2 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.53 MW | 0.53 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
| Details for PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 937311 | AD2-172 C | 50/50 | 18.54 MW | 18.54 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 937312 | AD2-172 E | 50/50 | 25.61 MW | 25.61 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 959101 | AF2-201 C O1 | 50/50 | 45.39 MW | 45.39 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 959102 | AF2-201 E O1 | 50/50 | 130.33 MW | 130.33 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 274856 | ECOGROVE ;U1 | 50/50 | 3.06 MW | 3.06 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 294763 | P-046 E | 50/50 | 70.64 MW | 70.64 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 940501 | AE2-035 C | 50/50 | 18.54 MW | 18.54 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 940502 | AE2-035 E | 50/50 | 25.61 MW | 25.61 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 946501 | AF1-314 C | 50/50 | 32.85 MW | 32.85 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | 946502 | AF1-314 E | 50/50 | 154.35 MW | 154.35 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.08 MW | 0.08 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11902_C | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| Details for PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 937311 | AD2-172 C | 50/50 | 12.14 MW | 12.14 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 937312 | AD2-172 E | 50/50 | 16.77 MW | 16.77 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 959101 | AF2-201 C O1 | 50/50 | 29.73 MW | 29.73 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 959102 | AF2-201 E O1 | 50/50 | 85.36 MW | 85.36 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 274856 | ECOGROVE ;U1 | 50/50 | 2.01 MW | 2.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 294763 | P-046 E | 50/50 | 46.27 MW | 46.27 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 938861 | AE1-114 C O1 | 50/50 | 12.42 MW | 12.42 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 938862 | AE1-114 E O1 | 50/50 | 42.36 MW | 42.36 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 940501 | AE2-035 C | 50/50 | 12.14 MW | 12.14 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 940502 | AE2-035 E | 50/50 | 16.77 MW | 16.77 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 946501 | AF1-314 C | 50/50 | 21.51 MW | 21.51 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | 946502 | AF1-314 E | 50/50 | 101.09 MW | 101.09 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.02 MW | 0.02 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.04 MW | 0.04 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.85 MW | 0.85 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.1 MW | 0.1 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.2 MW | 0.2 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.53 MW | 0.53 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P4_194-38-L19414_ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
| Details for LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 926431 | AC1-114 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 927511 | AC1-113 1 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 927521 | AC1-113 2 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 937311 | AD2-172 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 937312 | AD2-172 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 959101 | AF2-201 C O1 | 50/50 | 27.51 MW | 27.51 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 959102 | AF2-201 E O1 | 50/50 | 78.98 MW | 78.98 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 274856 | ECOGROVE ;U1 | 50/50 | 1.86 MW | 1.86 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 294763 | P-046 E | 50/50 | 42.81 MW | 42.81 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 932881 | AC2-115 1 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 932891 | AC2-115 2 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 932921 | AC2-116 | Adder | -0.45 MW | -0.38 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 938861 | AE1-114 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 938862 | AE1-114 E O1 | 50/50 | 39.15 MW | 39.15 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 940501 | AE2-035 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 940502 | AE2-035 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 946501 | AF1-314 C | 50/50 | 19.91 MW | 19.91 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | 946502 | AF1-314 E | 50/50 | 93.54 MW | 93.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.03 MW | 0.03 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.04 MW | 0.04 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 1.01 MW | 1.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.12 MW | 0.12 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.27 MW | 0.27 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.67 MW | 0.67 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.11 MW | 0.11 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L17121_A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.6 MW | 0.6 MW |
| Details for LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 926431 | AC1-114 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 927511 | AC1-113 1 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 927521 | AC1-113 2 | Adder | -0.64 MW | -0.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 937311 | AD2-172 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 937312 | AD2-172 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 959101 | AF2-201 C O1 | 50/50 | 27.51 MW | 27.51 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 959102 | AF2-201 E O1 | 50/50 | 78.98 MW | 78.98 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 274856 | ECOGROVE ;U1 | 50/50 | 1.86 MW | 1.86 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 294763 | P-046 E | 50/50 | 42.81 MW | 42.81 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 932881 | AC2-115 1 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 932891 | AC2-115 2 | Adder | -1.28 MW | -1.09 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 932921 | AC2-116 | Adder | -0.45 MW | -0.38 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 938861 | AE1-114 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 938862 | AE1-114 E O1 | 50/50 | 39.15 MW | 39.15 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 940501 | AE2-035 C | 50/50 | 11.24 MW | 11.24 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 940502 | AE2-035 E | 50/50 | 15.52 MW | 15.52 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 946501 | AF1-314 C | 50/50 | 19.91 MW | 19.91 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | 946502 | AF1-314 E | 50/50 | 93.54 MW | 93.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.03 MW | 0.03 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.04 MW | 0.04 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.1 MW | 0.1 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 1.01 MW | 1.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.12 MW | 0.12 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.27 MW | 0.27 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.67 MW | 0.67 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.11 MW | 0.11 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P4_119-38-L11904_A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.6 MW | 0.6 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 15.79 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.23 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 14.5 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.51 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 2.41 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 13.33 MW | 11.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 8.27 MW | 7.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 6.71 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 10.5 MW | 8.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 5.16 MW | 4.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 6.98 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.14 MW | 2.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 5.86 MW | 4.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 11.71 MW | 9.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 7.81 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.92 MW | 4.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 14.12 MW | 12.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 17.85 MW | 15.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 11.9 MW | 10.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 4.86 MW | 4.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 3.24 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 5.73 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 3.82 MW | 3.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 12.81 MW | 10.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 16.27 MW | 13.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 7.65 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 5.38 MW | 4.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 3.56 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 16.72 MW | 14.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 1.96 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 17.57 MW | 14.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 11.71 MW | 9.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | Adder | 28.15 MW | 23.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | Adder | 13.25 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 53.8 MW | 45.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 58.79 MW | 49.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 60.57 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 23.09 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 4.75 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 19.91 MW | 16.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 254.71 MW | 216.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.88 MW | 15.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.3 MW | 49.3 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 53.75 MW | 45.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 53.74 MW | 45.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 15.67 MW | 13.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 8.48 MW | 7.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 14.4 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.56 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.56 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 3.47 MW | 2.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 3.47 MW | 2.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.49 MW | 1.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 2.39 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 15.64 MW | 13.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 72.98 MW | 62.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.73 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 1.98 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 13.25 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 3.63 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 17.72 MW | 15.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 2.13 MW | 1.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 6.88 MW | 5.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 4.58 MW | 3.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.05 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 8.2 MW | 6.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.45 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 7.35 MW | 6.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.71 MW | 0.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 4.36 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 3.28 MW | 2.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 10.39 MW | 8.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 5.1 MW | 4.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 6.91 MW | 5.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 3.42 MW | 2.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.11 MW | 2.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 9.93 MW | 8.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 6.62 MW | 5.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 9.14 MW | 7.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 6.09 MW | 5.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 3.87 MW | 3.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 11.62 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 4.88 MW | 4.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 14.01 MW | 11.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.9 MW | 2.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.9 MW | 2.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 4.36 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 17.7 MW | 15.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 11.8 MW | 10.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.27 MW | 3.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.85 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.28 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960681 | AF2-359 C | 50/50 | 63.92 MW | 63.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960682 | AF2-359 E | 50/50 | 42.61 MW | 42.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 4.81 MW | 4.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 3.21 MW | 2.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 5.67 MW | 4.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.78 MW | 3.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 14.94 MW | 12.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.03 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.03 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.19 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.03 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 12.69 MW | 10.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.87 MW | 6.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 15.28 MW | 12.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 16.11 MW | 13.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 7.59 MW | 6.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 4.38 MW | 3.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.68 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 2.03 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 3.31 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 7.51 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 0.67 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 2.3 MW | 1.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 4.97 MW | 4.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 30.55 MW | 25.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 8.32 MW | 7.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 7.68 MW | 6.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 5.33 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 9.6 MW | 8.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 3.53 MW | 3.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 16.59 MW | 14.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.96 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 17.42 MW | 14.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 11.62 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 14.51 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 6.83 MW | 5.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 27.9 MW | 23.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 13.13 MW | 11.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 14.94 MW | 12.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.12 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 53.36 MW | 45.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 58.39 MW | 49.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 60.06 MW | 51.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932931 | AC2-117 | Adder | 10.49 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 6.47 MW | 5.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 22.92 MW | 19.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 4.72 MW | 4.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.86 MW | 4.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 19.73 MW | 16.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274806 | UNIV PK N;2U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274808 | UNIV PK N;4U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274809 | UNIV PK N;5U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274811 | UNIV PK N;7U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274812 | UNIV PK N;8U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274814 | UNIV PK N;0U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274815 | UNIV PK N;XU | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 251.5 MW | 213.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.06 MW | 3.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 15.45 MW | 15.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.79 MW | 10.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.01 MW | 4.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.67 MW | 1.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.67 MW | 15.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.31 MW | 1.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 48.24 MW | 48.24 MW |
| Details for NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 290051 | GSG-6; E | Adder | 7.48 MW | 6.36 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.0 MW | 3.4 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 1.95 MW | 1.66 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 919221 | AA1-146 | 50/50 | 8.93 MW | 8.93 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 926331 | AC1-110 1 | Adder | -0.98 MW | -0.83 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 926341 | AC1-110 2 | Adder | -0.98 MW | -0.83 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 927201 | AC1-214 C O1 | Adder | 1.74 MW | 1.48 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 927202 | AC1-214 E O1 | Adder | 5.55 MW | 4.71 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.26 MW | 1.07 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.01 MW | 1.71 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 934051 | AD1-031 C O1 | 50/50 | 2.94 MW | 2.94 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 934052 | AD1-031 E O1 | 50/50 | 4.79 MW | 4.79 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 934431 | AD1-067 C | Adder | 0.09 MW | 0.08 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.4 MW | 0.34 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 937001 | AD2-134 C | Adder | 1.81 MW | 1.54 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 937002 | AD2-134 E | Adder | 7.23 MW | 6.15 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 937311 | AD2-172 C | Adder | 1.39 MW | 1.18 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 937312 | AD2-172 E | Adder | 1.92 MW | 1.63 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 959101 | AF2-201 C O1 | Adder | 3.41 MW | 2.9 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 959102 | AF2-201 E O1 | Adder | 9.78 MW | 8.32 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 961011 | AF2-392 C O1 | 50/50 | 8.82 MW | 8.82 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 961012 | AF2-392 E O1 | 50/50 | 41.31 MW | 41.31 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 961021 | AF2-393 O1 | 50/50 | 15.04 MW | 15.04 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 961031 | AF2-394 O1 | 50/50 | 10.03 MW | 10.03 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274662 | QUAD CITI;1U | 50/50 | 37.43 MW | 37.43 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274663 | QUAD CITI;2U | 50/50 | 37.5 MW | 37.5 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274699 | CORDOVA ;1C | 50/50 | 6.58 MW | 6.58 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274700 | CORDOVA ;2C | 50/50 | 6.58 MW | 6.58 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274701 | CORDOVA ;1S | 50/50 | 7.4 MW | 7.4 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274715 | NELSON EC;1C | 50/50 | 9.57 MW | 9.57 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274716 | NELSON EC;1S | 50/50 | 6.98 MW | 6.98 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274717 | NELSON EC;2C | 50/50 | 9.65 MW | 9.65 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274718 | NELSON EC;2S | 50/50 | 7.05 MW | 7.05 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274877 | BISHOP HL;1U | 50/50 | 0.39 MW | 0.39 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 274878 | BISHOP HL;2U | 50/50 | 0.39 MW | 0.39 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 276156 | O-029 C | 50/50 | 0.44 MW | 0.44 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 276157 | O-029 C | 50/50 | 0.47 MW | 0.47 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 276158 | O-029 C | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293513 | O-009 C1 | 50/50 | 0.81 MW | 0.81 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293514 | O-009 C2 | 50/50 | 0.41 MW | 0.41 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293515 | O-009 C3 | 50/50 | 0.46 MW | 0.46 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293516 | O-009 E1 | 50/50 | 18.69 MW | 18.69 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293517 | O-009 E2 | 50/50 | 9.49 MW | 9.49 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293518 | O-009 E3 | 50/50 | 10.45 MW | 10.45 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293715 | O-029 E | 50/50 | 19.98 MW | 19.98 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293716 | O-029 E | 50/50 | 10.95 MW | 10.95 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293717 | O-029 E | 50/50 | 10.07 MW | 10.07 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 293771 | O-035 E | Adder | 5.44 MW | 4.62 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 294401 | BSHIL;1U E | 50/50 | 8.88 MW | 8.88 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 294410 | BSHIL;2U E | 50/50 | 8.88 MW | 8.88 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 294763 | P-046 E | Adder | 5.3 MW | 4.51 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 916211 | Z1-072 E | Adder | 4.11 MW | 3.5 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 916221 | Z1-073 E | Adder | 3.86 MW | 3.28 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 925581 | AC1-033 C | 50/50 | 1.46 MW | 1.46 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 925582 | AC1-033 E | 50/50 | 9.74 MW | 9.74 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 4.45 MW | 4.45 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 15.18 MW | 15.18 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 939051 | AE1-134 1 | 50/50 | 4.0 MW | 4.0 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 939061 | AE1-134 2 | 50/50 | 4.0 MW | 4.0 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 940501 | AE2-035 C | Adder | 1.39 MW | 1.18 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 940502 | AE2-035 E | Adder | 1.92 MW | 1.63 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946321 | AF1-296 C O1 | 50/50 | 8.37 MW | 8.37 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946322 | AF1-296 E O1 | 50/50 | 39.17 MW | 39.17 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946501 | AF1-314 C | Adder | 2.47 MW | 2.1 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946502 | AF1-314 E | Adder | 11.59 MW | 9.85 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.63 MW | 1.39 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 957752 | AF2-069 E | Adder | 0.65 MW | 0.55 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 957762 | AF2-070 E | Adder | 1.38 MW | 1.18 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 990901 | L-005 E | Adder | 11.98 MW | 10.18 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 276160 | W4-084 | 50/50 | 0.14 MW | 0.14 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 919581 | AA2-030 | 50/50 | 51.45 MW | 51.45 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 925302 | AB2-191 E | Adder | 0.99 MW | 0.84 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946541 | AF1-318 C O1 | Adder | 3.42 MW | 2.91 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 946542 | AF1-318 E O1 | Adder | 16.02 MW | 13.62 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950181 | J407 C | External Queue | 2.84 MW | 2.84 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950182 | J407 E | External Queue | 11.37 MW | 11.37 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950401 | J041 C | External Queue | 1.55 MW | 1.55 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950402 | J041 E | External Queue | 6.19 MW | 6.19 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950471 | J438 C | External Queue | 3.17 MW | 3.17 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950501 | J449 C | External Queue | 3.05 MW | 3.05 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950502 | J449 E | External Queue | 12.21 MW | 12.21 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950522 | J455 E | External Queue | 20.25 MW | 20.25 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951031 | J344 C | External Queue | 2.86 MW | 2.86 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951032 | J344 E | External Queue | 8.59 MW | 8.59 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951221 | J475 C | External Queue | 3.5 MW | 3.5 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951222 | J475 E | External Queue | 14.01 MW | 14.01 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951301 | J495 C | External Queue | 3.27 MW | 3.27 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951302 | J495 E | External Queue | 9.82 MW | 9.82 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951381 | J504 | External Queue | 5.45 MW | 5.45 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951421 | J514 | External Queue | 3.26 MW | 3.26 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951441 | J523 C | External Queue | 2.08 MW | 2.08 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951451 | J524 C | External Queue | 4.23 MW | 4.23 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951501 | J529 C | External Queue | 3.24 MW | 3.24 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951502 | J529 E | External Queue | 12.96 MW | 12.96 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951511 | J530 C | External Queue | 5.19 MW | 5.19 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951512 | J530 E | External Queue | 20.74 MW | 20.74 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951541 | J534 C | External Queue | 3.34 MW | 3.34 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951542 | J534 E | External Queue | 13.38 MW | 13.38 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951551 | J535 C | External Queue | 2.84 MW | 2.84 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951552 | J535 E | External Queue | 11.37 MW | 11.37 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951821 | J541 C | External Queue | 4.17 MW | 4.17 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951822 | J541 E | External Queue | 22.56 MW | 22.56 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951841 | J555 C | External Queue | 1.91 MW | 1.91 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951842 | J555 E | External Queue | 10.35 MW | 10.35 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952021 | J614 C | External Queue | 0.71 MW | 0.71 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952022 | J614 E | External Queue | 3.82 MW | 3.82 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952191 | J583 C | External Queue | 2.02 MW | 2.02 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952192 | J583 E | External Queue | 10.93 MW | 10.93 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952211 | J590 C | External Queue | 0.95 MW | 0.95 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 952212 | J590 E | External Queue | 5.13 MW | 5.13 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 953082 | J836 E | External Queue | 13.49 MW | 13.49 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 954131 | J877 | External Queue | 16.87 MW | 16.87 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 950472 | J438 E | External Queue | 12.69 MW | 12.69 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951351 | J500 C | External Queue | 6.4 MW | 6.4 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951352 | J500 E | External Queue | 25.6 MW | 25.6 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951442 | J523 E | External Queue | 1.38 MW | 1.38 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 951452 | J524 E | External Queue | 2.82 MW | 2.82 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 954702 | J844 E | External Queue | 13.25 MW | 13.25 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 954901 | J963 | External Queue | 1.32 MW | 1.32 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 954931 | J967 C | External Queue | 1.71 MW | 1.71 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 954932 | J967 E | External Queue | 9.24 MW | 9.24 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955061 | J982 C | External Queue | 3.03 MW | 3.03 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955062 | J982 E | External Queue | 16.4 MW | 16.4 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955221 | J1000 | External Queue | 3.75 MW | 3.75 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955661 | J1050 C | External Queue | 2.6 MW | 2.6 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955662 | J1050 E | External Queue | 14.09 MW | 14.09 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955871 | J1072 | External Queue | 10.94 MW | 10.94 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 955971 | J1084 | External Queue | 29.84 MW | 29.84 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 956411 | J1131 | External Queue | 15.96 MW | 15.96 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 956431 | J1135 | External Queue | 3.82 MW | 3.82 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 956761 | J1174 | External Queue | 11.93 MW | 11.93 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 956772 | J1175 E | External Queue | 11.93 MW | 11.93 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | 956832 | J1181 E | External Queue | 18.11 MW | 18.11 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.11 MW | 0.11 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 21.26 MW | 21.26 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.85 MW | 0.85 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 4.04 MW | 4.04 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.07 MW | 13.07 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.13 MW | 0.13 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 13.74 MW | 13.74 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 17.29 MW | 17.29 MW |
| NELSON ; B-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_155-45-BT6-7__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 45.86 MW | 45.86 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 15.67 MW | 13.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 8.48 MW | 7.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 14.4 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.56 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.56 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 3.47 MW | 2.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 3.47 MW | 2.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.49 MW | 1.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 2.39 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 15.64 MW | 13.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 72.98 MW | 62.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.73 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 1.98 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 13.25 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 3.63 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 17.72 MW | 15.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 2.13 MW | 1.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 6.88 MW | 5.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 4.58 MW | 3.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.05 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 8.2 MW | 6.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.45 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 7.35 MW | 6.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.71 MW | 0.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 4.36 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 3.28 MW | 2.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 10.39 MW | 8.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 5.1 MW | 4.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 6.91 MW | 5.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 3.42 MW | 2.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.11 MW | 2.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 9.93 MW | 8.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 6.62 MW | 5.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 9.14 MW | 7.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 6.09 MW | 5.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 3.87 MW | 3.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 11.62 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 4.88 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 14.01 MW | 11.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.9 MW | 2.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.9 MW | 2.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 4.36 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 17.7 MW | 15.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 11.8 MW | 10.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.27 MW | 3.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.85 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.28 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 4.81 MW | 4.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 3.21 MW | 2.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 5.67 MW | 4.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.78 MW | 3.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 14.94 MW | 12.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.03 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.03 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.19 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.03 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 12.69 MW | 10.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.87 MW | 6.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 15.28 MW | 12.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 16.11 MW | 13.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 7.59 MW | 6.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 4.38 MW | 3.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.68 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 2.03 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 3.31 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 7.51 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 3.18 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 10.84 MW | 9.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 4.97 MW | 4.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 30.55 MW | 25.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 8.32 MW | 7.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 7.68 MW | 6.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 5.33 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 9.6 MW | 8.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 3.53 MW | 3.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 16.59 MW | 14.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.96 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 17.42 MW | 14.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 11.62 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 14.51 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 6.83 MW | 5.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 27.9 MW | 23.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 13.13 MW | 11.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 14.94 MW | 12.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 53.36 MW | 45.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 58.39 MW | 49.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 60.06 MW | 51.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932931 | AC2-117 | Adder | 10.49 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 6.47 MW | 5.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 22.92 MW | 19.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 4.72 MW | 4.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.86 MW | 4.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 19.73 MW | 16.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274806 | UNIV PK N;2U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274808 | UNIV PK N;4U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274809 | UNIV PK N;5U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274811 | UNIV PK N;7U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274812 | UNIV PK N;8U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274814 | UNIV PK N;0U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274815 | UNIV PK N;XU | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 251.5 MW | 213.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.06 MW | 3.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 15.45 MW | 15.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.79 MW | 10.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.01 MW | 4.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.67 MW | 1.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.67 MW | 15.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.31 MW | 1.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 48.24 MW | 48.24 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 15.79 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 14.5 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.51 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 2.41 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 13.33 MW | 11.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 8.27 MW | 7.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 6.71 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 10.5 MW | 8.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 5.16 MW | 4.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 6.98 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.14 MW | 2.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 5.86 MW | 4.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 11.71 MW | 9.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 7.81 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.92 MW | 4.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 14.12 MW | 12.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 17.85 MW | 15.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 11.9 MW | 10.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 4.86 MW | 4.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 3.24 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 5.73 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 3.82 MW | 3.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 12.81 MW | 10.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 16.27 MW | 13.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 7.65 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 10.92 MW | 9.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 5.38 MW | 4.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 3.56 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 1.96 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 17.57 MW | 14.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 11.71 MW | 9.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | Adder | 28.15 MW | 23.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | Adder | 13.25 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 53.8 MW | 45.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 58.79 MW | 49.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 60.57 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 23.09 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 19.91 MW | 16.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 254.71 MW | 216.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.88 MW | 15.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.3 MW | 49.3 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 10.91 MW | 9.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 53.75 MW | 45.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.91 MW | 9.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 53.74 MW | 45.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 20.43 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 10.84 MW | 9.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 5.8 MW | 4.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.82 MW | 2.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 15.81 MW | 13.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.55 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.99 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.99 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.98 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.98 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 1.24 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 1.24 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.91 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 3.05 MW | 2.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.58 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 19.63 MW | 16.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 91.62 MW | 77.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.63 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.62 MW | 2.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 10.48 MW | 8.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.55 MW | 2.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 3.52 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 9.58 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 5.18 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 8.51 MW | 7.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 4.19 MW | 3.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 13.24 MW | 11.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 6.5 MW | 5.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 8.81 MW | 7.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 4.36 MW | 3.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.65 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.9 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 7.45 MW | 6.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 4.97 MW | 4.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 14.9 MW | 12.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 9.94 MW | 8.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 6.24 MW | 5.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 17.92 MW | 15.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 5.56 MW | 4.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 22.66 MW | 19.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 15.1 MW | 12.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 6.15 MW | 5.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 4.1 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 7.25 MW | 6.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 4.83 MW | 4.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274654 | BRAIDWOOD;1U | 50/50 | 30.03 MW | 30.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.21 MW | 29.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.32 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.32 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 16.33 MW | 13.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 23.75 MW | 23.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 20.74 MW | 17.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 5.59 MW | 4.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 8.91 MW | 7.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 36.29 MW | 30.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.55 MW | 2.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 3.52 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 6.81 MW | 5.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 4.54 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 12.14 MW | 10.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 4.52 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 21.22 MW | 18.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 2.09 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 2.48 MW | 2.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 22.36 MW | 19.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 14.9 MW | 12.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 16.38 MW | 13.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 7.71 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | 50/50 | 40.33 MW | 40.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | 50/50 | 18.98 MW | 18.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.44 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 68.28 MW | 58.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 73.42 MW | 62.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 78.73 MW | 66.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 8.3 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 8.29 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 8.43 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 29.88 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 5.94 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 6.37 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 25.21 MW | 21.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 324.28 MW | 275.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.91 MW | 3.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 14.0 MW | 14.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.26 MW | 20.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.2 MW | 13.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.29 MW | 2.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.23 MW | 56.23 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 20.33 MW | 17.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 10.73 MW | 9.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 5.75 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.79 MW | 2.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 4.45 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 1.22 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 1.22 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.89 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 3.02 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.56 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 19.56 MW | 16.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 91.29 MW | 77.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.34 MW | 1.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 15.67 MW | 13.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 0.59 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 8.56 MW | 7.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 5.7 MW | 4.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 10.38 MW | 8.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 3.49 MW | 2.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 3.18 MW | 2.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 9.53 MW | 8.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 5.16 MW | 4.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 8.44 MW | 7.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 4.16 MW | 3.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 13.07 MW | 11.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 6.42 MW | 5.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 8.69 MW | 7.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 4.3 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.94 MW | 3.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.63 MW | 2.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 10.81 MW | 9.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 7.38 MW | 6.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 4.92 MW | 4.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 9.84 MW | 8.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 6.19 MW | 5.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 17.77 MW | 15.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | 50/50 | 2.99 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | 50/50 | 4.48 MW | 4.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | 50/50 | 2.99 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | 50/50 | 4.48 MW | 4.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 5.48 MW | 4.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 22.46 MW | 19.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 14.97 MW | 12.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 7.18 MW | 6.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.79 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 6.09 MW | 5.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 7.17 MW | 6.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 4.78 MW | 4.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274654 | BRAIDWOOD;1U | 50/50 | 29.83 MW | 29.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274655 | BRAIDWOOD;2U | 50/50 | 29.02 MW | 29.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274751 | CRETE EC ;1U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274752 | CRETE EC ;2U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274753 | CRETE EC ;3U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274754 | CRETE EC ;4U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.3 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.3 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.5 MW | 2.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.57 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 16.16 MW | 13.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | 50/50 | 12.19 MW | 12.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | 50/50 | 23.66 MW | 23.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 20.53 MW | 17.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 9.63 MW | 8.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 5.54 MW | 4.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 9.71 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 5.88 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 36.14 MW | 30.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 10.47 MW | 8.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 9.66 MW | 8.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 3.49 MW | 2.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 6.74 MW | 5.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 12.08 MW | 10.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 8.05 MW | 6.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 21.04 MW | 17.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.45 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 2.45 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.51 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 1.29 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 22.15 MW | 18.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 16.27 MW | 13.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 7.66 MW | 6.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | 50/50 | 40.09 MW | 40.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | 50/50 | 18.87 MW | 18.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.42 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 67.68 MW | 57.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 73.22 MW | 62.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 78.27 MW | 66.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 8.27 MW | 7.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 8.25 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 8.39 MW | 7.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 29.73 MW | 25.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 5.92 MW | 5.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 6.33 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 24.95 MW | 21.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 317.6 MW | 269.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.88 MW | 3.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 18.31 MW | 18.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.14 MW | 1.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.93 MW | 13.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.88 MW | 3.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.15 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.06 MW | 20.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.16 MW | 13.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.69 MW | 0.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.3 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 55.23 MW | 55.23 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 20.42 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.79 MW | 9.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.78 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.04 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 91.66 MW | 77.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.43 MW | 8.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.19 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.18 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.15 MW | 11.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.46 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.75 MW | 7.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.33 MW | 3.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.97 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 10.86 MW | 9.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.42 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 4.95 MW | 4.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.9 MW | 8.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 6.22 MW | 5.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 17.85 MW | 15.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.52 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.58 MW | 19.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.81 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 16.25 MW | 13.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 20.64 MW | 17.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 9.68 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.57 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.77 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.92 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 36.31 MW | 30.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.52 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 21.14 MW | 17.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.27 MW | 18.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 16.37 MW | 13.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 7.7 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.27 MW | 40.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 68.04 MW | 57.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 73.64 MW | 62.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 78.69 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.3 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 29.87 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.96 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.09 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 320.0 MW | 272.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.22 MW | 20.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.17 MW | 13.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.07 MW | 56.07 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 20.42 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 10.79 MW | 9.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 5.78 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 3.03 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 91.67 MW | 77.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 19.98 MW | 16.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.41 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 10.43 MW | 8.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 5.19 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 4.18 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 13.15 MW | 11.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 6.46 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 8.74 MW | 7.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 4.33 MW | 3.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.97 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 10.86 MW | 9.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 7.42 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 4.95 MW | 4.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 9.89 MW | 8.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 6.22 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 5.52 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 22.58 MW | 19.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 2.52 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 1.68 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 4.81 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 16.25 MW | 13.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 20.64 MW | 17.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 9.68 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 5.57 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.73 MW | 3.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 8.92 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 36.31 MW | 30.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 4.51 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 21.14 MW | 17.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 22.26 MW | 18.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 40.27 MW | 40.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 68.03 MW | 57.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 73.63 MW | 62.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 78.68 MW | 66.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 8.3 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 29.87 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 25.08 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 319.88 MW | 271.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.22 MW | 20.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.17 MW | 13.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.06 MW | 56.06 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290021 | O50 E | Adder | 20.41 MW | 17.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.78 MW | 9.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.77 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.47 MW | 3.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.03 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.66 MW | 16.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934722 | AD1-100 E | Adder | 91.76 MW | 78.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.42 MW | 8.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937312 | AD2-172 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.18 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.17 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.13 MW | 11.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.45 MW | 5.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.73 MW | 7.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.32 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.96 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958491 | AF2-143 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.41 MW | 6.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959082 | AF2-199 E | Adder | 4.94 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.83 MW | 12.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.88 MW | 8.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 6.21 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 17.84 MW | 15.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.51 MW | 4.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.56 MW | 19.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.04 MW | 12.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.12 MW | 5.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.58 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293061 | N-015 E | Adder | 16.24 MW | 13.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294392 | P-010 E | Adder | 20.63 MW | 17.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294763 | P-046 E | Adder | 9.67 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.56 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.91 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 36.29 MW | 30.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940502 | AE2-035 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.51 MW | 3.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.14 MW | 10.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946502 | AF1-314 E | Adder | 21.12 MW | 17.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.46 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.24 MW | 18.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957472 | AF2-041 E | Adder | 14.83 MW | 12.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 16.38 MW | 13.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 7.71 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.28 MW | 40.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930481 | AB1-089 | Adder | 67.96 MW | 57.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 73.52 MW | 62.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 78.64 MW | 66.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.29 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938852 | AE1-113 E | Adder | 29.85 MW | 25.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.06 MW | 21.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 319.26 MW | 271.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.68 MW | 17.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.21 MW | 20.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.16 MW | 13.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.01 MW | 56.01 MW |
| Details for LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 937311 | AD2-172 C | 50/50 | 21.0 MW | 21.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 937312 | AD2-172 E | 50/50 | 29.0 MW | 29.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 959101 | AF2-201 C O1 | 50/50 | 51.4 MW | 51.4 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 959102 | AF2-201 E O1 | 50/50 | 147.59 MW | 147.59 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 274856 | ECOGROVE ;U1 | 50/50 | 3.47 MW | 3.47 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 294763 | P-046 E | 50/50 | 79.99 MW | 79.99 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 940501 | AE2-035 C | 50/50 | 21.0 MW | 21.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 940502 | AE2-035 E | 50/50 | 29.0 MW | 29.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 946501 | AF1-314 C | 50/50 | 37.2 MW | 37.2 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 946502 | AF1-314 E | 50/50 | 174.78 MW | 174.78 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-PECATONIC; B 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| Details for PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 937311 | AD2-172 C | 50/50 | 21.0 MW | 21.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 937312 | AD2-172 E | 50/50 | 29.0 MW | 29.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 959101 | AF2-201 C O1 | 50/50 | 51.4 MW | 51.4 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 959102 | AF2-201 E O1 | 50/50 | 147.59 MW | 147.59 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 274856 | ECOGROVE ;U1 | 50/50 | 3.47 MW | 3.47 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 294763 | P-046 E | 50/50 | 79.99 MW | 79.99 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 940501 | AE2-035 C | 50/50 | 21.0 MW | 21.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 940502 | AE2-035 E | 50/50 | 29.0 MW | 29.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 946501 | AF1-314 C | 50/50 | 37.2 MW | 37.2 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | 946502 | AF1-314 E | 50/50 | 174.78 MW | 174.78 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.0 MW | 0.0 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| PECATONIC; B-WEMPLETOW; R 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L19414GR-R-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| Details for LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 937311 | AD2-172 C | 50/50 | 20.88 MW | 20.88 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 937312 | AD2-172 E | 50/50 | 28.84 MW | 28.84 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 959101 | AF2-201 C O1 | 50/50 | 51.11 MW | 51.11 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 959102 | AF2-201 E O1 | 50/50 | 146.76 MW | 146.76 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 274856 | ECOGROVE ;U1 | 50/50 | 3.45 MW | 3.45 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 294763 | P-046 E | 50/50 | 79.54 MW | 79.54 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 940501 | AE2-035 C | 50/50 | 20.88 MW | 20.88 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 940502 | AE2-035 E | 50/50 | 28.84 MW | 28.84 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 946501 | AF1-314 C | 50/50 | 36.99 MW | 36.99 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | 946502 | AF1-314 E | 50/50 | 173.8 MW | 173.8 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.03 MW | 0.03 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.07 MW | 0.07 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.0 MW | 0.0 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.02 MW | 0.02 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| LANCASTER; R-FREEPORT ;RT 138.0 kV Ckt 1 line l/o COMED_P7_138-L11902GB-R_+_138-L17121_R-R-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 22.21 MW | 18.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 12.0 MW | 10.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 6.43 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 3.12 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 910542 | X3-005 E | Adder | 1.0 MW | 0.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 18.65 MW | 15.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.8 MW | 2.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 2.18 MW | 1.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 2.18 MW | 1.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 4.82 MW | 4.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 4.82 MW | 4.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 2.11 MW | 1.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 3.38 MW | 2.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 1.06 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.74 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.63 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 22.37 MW | 19.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 104.38 MW | 88.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 1.04 MW | 0.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.69 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.68 MW | 2.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 17.93 MW | 15.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 5.4 MW | 4.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 26.37 MW | 22.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 3.18 MW | 2.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 9.66 MW | 8.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 6.44 MW | 5.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 11.61 MW | 9.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 3.47 MW | 2.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 10.41 MW | 8.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.96 MW | 0.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 5.91 MW | 5.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 9.38 MW | 7.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 4.62 MW | 3.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 14.62 MW | 12.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 7.18 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 9.72 MW | 8.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 4.81 MW | 4.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 4.38 MW | 3.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 12.86 MW | 10.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 8.58 MW | 7.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 12.37 MW | 10.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 8.24 MW | 7.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 8.22 MW | 6.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 5.48 MW | 4.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 16.44 MW | 13.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 10.96 MW | 9.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 1.24 MW | 1.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 3.57 MW | 3.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 6.13 MW | 5.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 24.98 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 16.66 MW | 14.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 9.53 MW | 8.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 6.35 MW | 5.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.91 MW | 1.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 6.8 MW | 5.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 4.53 MW | 3.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 8.0 MW | 6.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 5.34 MW | 4.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 14.66 MW | 12.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 21.98 MW | 18.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274724 | RIVER EC ;11 | 50/50 | 5.37 MW | 5.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274788 | SE CHICAG;5U | 50/50 | 7.29 MW | 7.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274789 | SE CHICAG;6U | 50/50 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274790 | SE CHICAG;7U | 50/50 | 7.4 MW | 7.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274791 | SE CHICAG;8U | 50/50 | 7.4 MW | 7.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274792 | SE CHICAG;9U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274793 | SE CHICAG;0U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274794 | SE CHICAG;1U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274795 | SE CHICAG;2U | 50/50 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 22.24 MW | 18.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.45 MW | 1.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.45 MW | 1.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 3.02 MW | 2.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.85 MW | 2.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 17.51 MW | 14.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 11.91 MW | 10.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 23.13 MW | 19.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 22.24 MW | 18.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.96 MW | 0.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 3.02 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 4.92 MW | 4.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 10.49 MW | 8.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 9.59 MW | 8.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 41.36 MW | 35.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 11.76 MW | 9.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 10.85 MW | 9.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 6.08 MW | 5.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 28.5 MW | 24.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 7.52 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 5.02 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 13.57 MW | 11.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 9.04 MW | 7.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 2.3 MW | 1.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.5 MW | 0.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 2.74 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.86 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957371 | AF2-031 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957372 | AF2-031 E O1 | 50/50 | 2.29 MW | 2.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 1.37 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 24.67 MW | 20.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 16.44 MW | 13.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 21.6 MW | 18.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 10.17 MW | 8.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 38.54 MW | 32.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 18.14 MW | 15.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 22.24 MW | 18.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.59 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 75.42 MW | 64.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 82.1 MW | 69.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 84.71 MW | 72.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 8.93 MW | 7.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 8.92 MW | 7.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 9.16 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 32.49 MW | 27.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 6.64 MW | 5.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 6.85 MW | 5.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 27.87 MW | 23.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 353.64 MW | 300.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.32 MW | 4.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 29.02 MW | 29.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.31 MW | 1.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.35 MW | 2.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 15.49 MW | 15.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 11.6 MW | 11.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.39 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 22.07 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.38 MW | 15.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.04 MW | 0.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 78.25 MW | 78.25 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290021 | O50 E | Adder | 22.71 MW | 19.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290051 | GSG-6; E | Adder | 12.29 MW | 10.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 6.58 MW | 5.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 3.2 MW | 2.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 910542 | X3-005 E | Adder | 1.03 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 19.14 MW | 16.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.87 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 2.24 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 2.24 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 2.24 MW | 1.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 2.24 MW | 1.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.96 MW | 4.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.96 MW | 4.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.4 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.4 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.46 MW | 2.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933931 | AD1-016 C | Adder | 1.09 MW | 0.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.78 MW | 1.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.65 MW | 0.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934721 | AD1-100 C | Adder | 23.03 MW | 19.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934722 | AD1-100 E | Adder | 107.46 MW | 91.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.71 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.74 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 18.33 MW | 15.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 5.57 MW | 4.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 27.2 MW | 23.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936461 | AD2-060 | Adder | 3.28 MW | 2.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 9.88 MW | 8.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 6.59 MW | 5.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937002 | AD2-134 E | Adder | 11.88 MW | 10.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.55 MW | 3.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 10.65 MW | 9.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 6.04 MW | 5.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942991 | AE2-321 C | Adder | 9.61 MW | 8.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.73 MW | 4.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943121 | AE2-341 C | Adder | 15.03 MW | 12.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943122 | AE2-341 E | Adder | 7.38 MW | 6.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 10.0 MW | 8.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.95 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943801 | AF1-048 C | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943802 | AF1-048 E | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958481 | AF2-142 C | Adder | 13.2 MW | 11.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958482 | AF2-142 E | Adder | 8.8 MW | 7.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958491 | AF2-143 C | Adder | 12.64 MW | 10.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958492 | AF2-143 E | Adder | 8.43 MW | 7.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959081 | AF2-199 C | Adder | 8.42 MW | 7.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959082 | AF2-199 E | Adder | 5.61 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 16.83 MW | 14.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 11.22 MW | 9.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 3.65 MW | 3.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959351 | AF2-226 C | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959352 | AF2-226 E | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960281 | AF2-319 C | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960282 | AF2-319 E | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960381 | AF2-329 | Adder | 6.31 MW | 5.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960581 | AF2-349 C | Adder | 25.59 MW | 21.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960582 | AF2-349 E | Adder | 17.06 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 9.83 MW | 8.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 6.55 MW | 5.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 1.31 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.97 MW | 1.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.96 MW | 5.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.64 MW | 3.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960751 | AF2-366 C | Adder | 8.21 MW | 6.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960752 | AF2-366 E | Adder | 5.47 MW | 4.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961501 | AF2-441 C O1 | Adder | 15.13 MW | 12.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961502 | AF2-441 E O1 | Adder | 22.69 MW | 19.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274724 | RIVER EC ;11 | 50/50 | 5.55 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274788 | SE CHICAG;5U | 50/50 | 7.53 MW | 7.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274789 | SE CHICAG;6U | 50/50 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274790 | SE CHICAG;7U | 50/50 | 7.65 MW | 7.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274791 | SE CHICAG;8U | 50/50 | 7.65 MW | 7.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274792 | SE CHICAG;9U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274793 | SE CHICAG;0U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274794 | SE CHICAG;1U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274795 | SE CHICAG;2U | 50/50 | 7.56 MW | 7.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 22.94 MW | 19.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.49 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.49 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276169 | Z1-107 E | Adder | 3.11 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.93 MW | 2.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293061 | N-015 E | Adder | 18.02 MW | 15.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293644 | O22 E1 | Adder | 12.22 MW | 10.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293645 | O22 E2 | Adder | 23.73 MW | 20.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294392 | P-010 E | Adder | 22.89 MW | 19.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 916221 | Z1-073 E | Adder | 6.34 MW | 5.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.98 MW | 0.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933411 | AC2-154 C | Adder | 3.11 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933412 | AC2-154 E | Adder | 5.08 MW | 4.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 10.77 MW | 9.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 9.85 MW | 8.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 6.88 MW | 5.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 42.29 MW | 35.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 12.12 MW | 10.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 11.18 MW | 9.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 6.2 MW | 5.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 29.08 MW | 24.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941131 | AE2-107 C | Adder | 7.71 MW | 6.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941132 | AE2-107 E | Adder | 5.14 MW | 4.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 13.98 MW | 11.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 9.32 MW | 7.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.36 MW | 2.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.52 MW | 0.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.94 MW | 2.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957332 | AF2-027 E | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957371 | AF2-031 C O1 | 50/50 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957372 | AF2-031 E O1 | 50/50 | 2.37 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.65 MW | 1.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.41 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957471 | AF2-041 C | Adder | 25.25 MW | 21.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957472 | AF2-041 E | Adder | 16.83 MW | 14.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 22.28 MW | 18.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 10.49 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958021 | AF2-096 C | Adder | 39.77 MW | 33.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958022 | AF2-096 E | Adder | 18.72 MW | 15.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 22.94 MW | 19.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.63 MW | 1.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930481 | AB1-089 | Adder | 77.19 MW | 65.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 83.76 MW | 71.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 86.99 MW | 73.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 9.17 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 9.16 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938851 | AE1-113 C | Adder | 9.37 MW | 7.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938852 | AE1-113 E | Adder | 33.21 MW | 28.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 6.77 MW | 5.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 28.56 MW | 24.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 364.98 MW | 310.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 25.05 MW | 25.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 15.77 MW | 15.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.18 MW | 7.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 22.98 MW | 22.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.35 MW | 15.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.68 MW | 1.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 83.08 MW | 83.08 MW |
Light Load Analysis
The Queue Project was evaluated as a 199.0 MW (Capacity 51.4 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
270927 to 275233 ckt 1 |
COMED_P4_112-65-BT2-3__
CONTINGENCY 'COMED_P4_112-65-BT2-3__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 143.19 % | 143.49 % | 1469.0 | STE | 2107.8 | 19.7 | |
| CE |
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
270926 to 275232 ckt 1 |
COMED_P4_112-65-BT5-6__
CONTINGENCY 'COMED_P4_112-65-BT5-6__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 140.26 % | 140.56 % | 1469.0 | STE | 2064.78 | 19.29 | |
| CE |
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
275233 to 270644 ckt 1 |
COMED_P4_112-65-BT2-3__
CONTINGENCY 'COMED_P4_112-65-BT2-3__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 139.14 % | 139.45 % | 1469.0 | STE | 2048.5 | 19.7 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441-B
CONTINGENCY 'AEP_P1-2_#7441-B' OPEN BRANCH FROM BUS 958430 TO BUS 246999 CKT 1 /*AF2-137 TAP 765.0 - 05SORENS 765.0 END |
Single | DC | 134.33 % | 135.4 % | 897.0 | B | 1214.54 | 9.65 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441-A
CONTINGENCY 'AEP_P1-2_#7441-A' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Single | DC | 134.31 % | 135.38 % | 897.0 | B | 1214.36 | 9.65 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P4_#7445_05MARYSV 765_B-A
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B-A' OPEN BRANCH FROM BUS 242922 TO BUS 242928 CKT 1 /*05FLTLCK 765.0 - 05MARYSV 765.0 OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Breaker | AC | 112.28 % | 113.17 % | 897.0 | B | 1015.13 | 9.55 | |
| CE |
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
275232 to 270644 ckt 1 |
COMED_P4_112-65-BT5-6__
CONTINGENCY 'COMED_P4_112-65-BT5-6__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 135.28 % | 135.61 % | 1469.0 | STE | 1992.1 | 19.29 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 135.6 % | 136.8 % | 971.0 | STE | 1328.33 | 12.92 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 121.54 % | 122.16 % | 971.0 | STE | 1186.17 | 12.94 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 121.5 % | 122.1 % | 971.0 | STE | 1185.59 | 12.93 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 135.54 % | 136.74 % | 971.0 | B | 1327.75 | 12.92 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 121.11 % | 121.71 % | 971.0 | B | 1181.8 | 12.94 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 121.07 % | 121.65 % | 971.0 | B | 1181.22 | 12.93 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 125.32 % | 125.94 % | 1483.0 | STE | 1867.67 | 16.35 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 125.0 % | 125.19 % | 1483.0 | STE | 1856.61 | 16.43 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 124.56 % | 124.74 % | 1483.0 | STE | 1849.9 | 16.37 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 132.37 % | 133.04 % | 1399.0 | B | 1861.23 | 16.35 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 132.05 % | 132.25 % | 1399.0 | B | 1850.18 | 16.43 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 131.58 % | 131.77 % | 1399.0 | B | 1843.46 | 16.37 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 126.0 % | 126.82 % | 1409.0 | B | 1786.89 | 18.58 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 127.04 % | 128.16 % | 1409.0 | B | 1805.77 | 18.55 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 126.86 % | 127.98 % | 1409.0 | B | 1803.24 | 18.54 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
Base Case | Single | AC | 110.35 % | 111.21 % | 3555.0 | A | 3953.52 | 36.07 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
COMED_P7_345-L6607__B-S_+_345-L6608__R-S
CONTINGENCY 'COMED_P7_345-L6607__B-S_+_345-L6608__R-S' TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1 /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0 TRIP BRANCH FROM BUS 270729 TO BUS 274804 CKT 1 /*E FRANKFO; R 345.0 - UNIV PK N;RP 345.0 END |
Tower | AC | 108.86 % | 109.73 % | 4105.0 | B | 4504.42 | 41.89 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A
CONTINGENCY 'COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A' TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1 /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0 TRIP BRANCH FROM BUS 274804 TO BUS 960680 CKT 1 /*UNIV PK N;RP 345.0 - AF2-359 TAP 345.0 END |
Tower | AC | 108.8 % | 109.67 % | 4105.0 | B | 4501.95 | 41.89 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 108.57 % | 109.23 % | 1441.0 | B | 1574.0 | 15.28 | |
| CE/NIPS |
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
270677 to 255109 ckt 1 |
COMED_P4_023-65-BT4-5__
CONTINGENCY 'COMED_P4_023-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 106.36 % | 107.27 % | 1441.0 | B | 1545.76 | 15.28 | |
| CE |
AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line
946500 to 271399 ckt 1 |
COMED_P1-2_138-L11904_B-R-A
CONTINGENCY 'COMED_P1-2_138-L11904_B-R-A' MOVE 100 PERCENT LOAD FROM BUS 271396 TO BUS 271397 /*ELEROY ; B 138.0 - ELEROY ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271494 TO BUS 271495 /*FREEPORT ;2R 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 271396 CKT 1 /*ELEROY ;BT 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271494 TO BUS 274184 CKT 7 /*FREEPORT ;2R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271498 TO BUS 271398 CKT 1 /*FREEPORT ;BT 138.0 - ELEROY ;BT 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271494 CKT 1 /*FREEPORT ;BT 138.0 - FREEPORT ;2R 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271897 CKT 1 /*FREEPORT ;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 65.6 % | 108.07 % | 320.0 | STE | 345.82 | 139.94 | |
| CE |
AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line
946500 to 271399 ckt 1 |
271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1
CONTINGENCY '271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1' OPEN BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 END |
Single | AC | 65.61 % | 108.07 % | 320.0 | STE | 345.82 | 139.94 | |
| CE |
AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line
946500 to 271398 ckt 1 |
COMED_P1-2_138-L11902GB-R-B
CONTINGENCY 'COMED_P1-2_138-L11902GB-R-B' MOVE 100 PERCENT LOAD FROM BUS 271397 TO BUS 271396 /*ELEROY ; R 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271399 TO BUS 271397 CKT 1 /*ELEROY ;RT 138.0 - ELEROY ; R 138.0 TRIP BRANCH FROM BUS 271399 TO BUS 946500 CKT 1 /*ELEROY ;RT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271399 CKT 1 /*LANCASTER;BT 138.0 - ELEROY ;RT 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 65.61 % | 108.07 % | 320.0 | STE | 345.82 | 139.94 | |
| CE |
AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line
946500 to 271398 ckt 1 |
COMED_P2-1_119-L11902__
CONTINGENCY 'COMED_P2-1_119-L11902__' TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 63.7 % | 106.16 % | 320.0 | STE | 339.7 | 139.94 | |
| CE |
ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line
271399 to 271898 ckt 1 |
271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1
CONTINGENCY '271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1' OPEN BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 END |
Single | AC | 63.61 % | 106.06 % | 320.0 | STE | 339.38 | 139.94 | |
| CE |
ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line
271399 to 271898 ckt 1 |
COMED_P1-2_138-L11904_B-R-A
CONTINGENCY 'COMED_P1-2_138-L11904_B-R-A' MOVE 100 PERCENT LOAD FROM BUS 271396 TO BUS 271397 /*ELEROY ; B 138.0 - ELEROY ; R 138.0 MOVE 100 PERCENT LOAD FROM BUS 271494 TO BUS 271495 /*FREEPORT ;2R 138.0 - FREEPORT ;5R 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 271396 CKT 1 /*ELEROY ;BT 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271398 TO BUS 946500 CKT 1 /*ELEROY ;BT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271494 TO BUS 274184 CKT 7 /*FREEPORT ;2R 138.0 - FREEPORT; 34.5 TRIP BRANCH FROM BUS 271498 TO BUS 271398 CKT 1 /*FREEPORT ;BT 138.0 - ELEROY ;BT 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271494 CKT 1 /*FREEPORT ;BT 138.0 - FREEPORT ;2R 138.0 TRIP BRANCH FROM BUS 271498 TO BUS 271897 CKT 1 /*FREEPORT ;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 61.48 % | 103.92 % | 320.0 | STE | 332.53 | 139.94 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 100.46 % | 101.54 % | 971.0 | B | 985.95 | 10.54 | |
| CE |
ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line
271398 to 271498 ckt 1 |
COMED_P2-1_119-L11902__
CONTINGENCY 'COMED_P2-1_119-L11902__' TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 61.54 % | 104.0 % | 320.0 | STE | 332.79 | 139.94 | |
| CE |
ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line
271398 to 271498 ckt 1 |
COMED_P1-2_138-L11902GB-R-B
CONTINGENCY 'COMED_P1-2_138-L11902GB-R-B' MOVE 100 PERCENT LOAD FROM BUS 271397 TO BUS 271396 /*ELEROY ; R 138.0 - ELEROY ; B 138.0 TRIP BRANCH FROM BUS 271399 TO BUS 271397 CKT 1 /*ELEROY ;RT 138.0 - ELEROY ; R 138.0 TRIP BRANCH FROM BUS 271399 TO BUS 946500 CKT 1 /*ELEROY ;RT 138.0 - AF1-314 TAP 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271399 CKT 1 /*LANCASTER;BT 138.0 - ELEROY ;RT 138.0 TRIP BRANCH FROM BUS 271898 TO BUS 271897 CKT 1 /*LANCASTER;BT 138.0 - LANCASTER; R 138.0 END |
Single | AC | 61.49 % | 103.93 % | 320.0 | STE | 332.56 | 139.94 | |
| Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274847 | GR RIDGE ;BU | 50/50 | 1.92 MW | 1.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274850 | MENDOTA H;RU | 50/50 | 0.3 MW | 0.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274855 | GSG-6 ;RU | 50/50 | 1.26 MW | 1.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274856 | ECOGROVE ;U1 | 50/50 | 1.13 MW | 1.13 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 1.32 MW | 1.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 1.32 MW | 1.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 5.28 MW | 5.28 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 5.28 MW | 5.28 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 1.23 MW | 1.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 2.4 MW | 2.4 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274863 | CAYUGA RI;1U | 50/50 | 1.98 MW | 1.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274864 | CAYUGA RI;2U | 50/50 | 1.98 MW | 1.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274871 | GR RIDGE ;2U | 50/50 | 2.44 MW | 2.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274872 | LEE DEKAL;1U | 50/50 | 2.81 MW | 2.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274879 | MINONK ;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 276170 | Z1-108 E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290021 | O50 E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290051 | GSG-6; E | 50/50 | 5.04 MW | 5.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290108 | LEEDK;1U E | 50/50 | 11.71 MW | 11.71 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293061 | N-015 E | 50/50 | 7.68 MW | 7.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 4.94 MW | 4.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 9.59 MW | 9.59 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 294392 | P-010 E | 50/50 | 9.75 MW | 9.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 294763 | P-046 E | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 295108 | WESTBROOK C | 50/50 | 0.46 MW | 0.46 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 295109 | WESTBROOK E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.2 MW | 0.2 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 1.47 MW | 1.47 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 916211 | Z1-072 E | Adder | 4.73 MW | 4.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 916221 | Z1-073 E | 50/50 | 2.6 MW | 2.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 917502 | Z2-087 E | 50/50 | 10.02 MW | 10.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 7.92 MW | 7.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 920272 | AA2-123 E | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 25.04 MW | 25.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925581 | AC1-033 C | Adder | 1.37 MW | 1.16 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925582 | AC1-033 E | Adder | 9.16 MW | 7.78 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 926821 | AC1-168 C O1 | 50/50 | 1.12 MW | 1.12 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 926822 | AC1-168 E O1 | 50/50 | 7.55 MW | 7.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 2.0 MW | 1.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 6.37 MW | 5.42 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934431 | AD1-067 C | 50/50 | 0.13 MW | 0.13 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934432 | AD1-067 E | 50/50 | 0.53 MW | 0.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934721 | AD1-100 C | 50/50 | 23.29 MW | 23.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934722 | AD1-100 E | 50/50 | 108.71 MW | 108.71 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 935141 | AD1-148 | Adder | 2.9 MW | 2.46 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 4.53 MW | 4.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 22.1 MW | 22.1 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937001 | AD2-134 C | 50/50 | 2.44 MW | 2.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937002 | AD2-134 E | 50/50 | 9.74 MW | 9.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 12.88 MW | 12.88 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939321 | AE1-163 C O1 | 50/50 | 5.69 MW | 5.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939322 | AE1-163 E O1 | 50/50 | 34.93 MW | 34.93 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939401 | AE1-172 C O1 | 50/50 | 6.35 MW | 6.35 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939402 | AE1-172 E O1 | 50/50 | 29.81 MW | 29.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 7.19 MW | 7.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942111 | AE2-223 C | 50/50 | 2.25 MW | 2.25 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942112 | AE2-223 E | 50/50 | 15.02 MW | 15.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942421 | AE2-255 C O1 | 50/50 | 2.91 MW | 2.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942422 | AE2-255 E O1 | 50/50 | 8.74 MW | 8.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942651 | AE2-281 C O1 | 50/50 | 0.81 MW | 0.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942652 | AE2-281 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943801 | AF1-048 C | 50/50 | 4.6 MW | 4.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943802 | AF1-048 E | 50/50 | 3.06 MW | 3.06 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 3.78 MW | 3.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 17.69 MW | 15.03 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946501 | AF1-314 C | 50/50 | 4.19 MW | 4.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946502 | AF1-314 E | 50/50 | 19.68 MW | 19.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957331 | AF2-027 C | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957332 | AF2-027 E | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957371 | AF2-031 C O1 | 50/50 | 1.13 MW | 1.13 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957372 | AF2-031 E O1 | 50/50 | 1.69 MW | 1.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957401 | AF2-034 C | 50/50 | 1.68 MW | 1.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957402 | AF2-034 E | 50/50 | 1.43 MW | 1.43 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.23 MW | 0.2 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.75 MW | 0.64 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.33 MW | 0.28 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.59 MW | 1.35 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958921 | AF2-183 C | 50/50 | 4.37 MW | 4.37 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958922 | AF2-183 E | 50/50 | 6.55 MW | 6.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959102 | AF2-201 E O1 | 50/50 | 19.7 MW | 19.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 3.02 MW | 3.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.54 MW | 4.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959611 | AF2-252 C | Adder | 2.42 MW | 2.05 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959612 | AF2-252 E | Adder | 3.62 MW | 3.08 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 3.02 MW | 3.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.54 MW | 4.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960381 | AF2-329 | 50/50 | 6.46 MW | 6.46 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960601 | AF2-351 C O1 | 50/50 | 1.33 MW | 1.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960602 | AF2-351 E O1 | 50/50 | 2.0 MW | 2.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960611 | AF2-352 C | Adder | 2.42 MW | 2.05 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960612 | AF2-352 E | Adder | 3.62 MW | 3.08 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 3.8 MW | 3.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 17.8 MW | 17.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 5.4 MW | 4.59 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936291 | AD2-038 C O1 | 50/50 | 2.26 MW | 2.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936292 | AD2-038 E O1 | 50/50 | 15.14 MW | 15.14 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274890 | CAYUG;1U E | 50/50 | 7.94 MW | 7.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274891 | CAYUG;2U E | 50/50 | 7.94 MW | 7.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 917501 | Z2-087 C | 50/50 | 1.5 MW | 1.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 1.18 MW | 1.18 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 2.14 MW | 1.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 14.31 MW | 12.16 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925301 | AB2-191 | 50/50 | 0.54 MW | 0.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925302 | AB2-191 E | 50/50 | 1.33 MW | 1.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925771 | AC1-053 C | Adder | 2.12 MW | 1.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 925772 | AC1-053 E | Adder | 14.17 MW | 12.05 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938851 | AE1-113 C | 50/50 | 7.69 MW | 7.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938852 | AE1-113 E | 50/50 | 27.27 MW | 27.27 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.16 MW | 0.16 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 944221 | AF1-090 C O1 | Adder | 2.07 MW | 1.76 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 944222 | AF1-090 E O1 | Adder | 9.67 MW | 8.22 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 945871 | AF1-252 O1 | Adder | 4.58 MW | 3.89 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 945881 | AF1-253 O1 | Adder | 3.17 MW | 2.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946161 | AF1-281 C | 50/50 | 0.41 MW | 0.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946162 | AF1-281 E | 50/50 | 2.32 MW | 2.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 5.65 MW | 4.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 26.45 MW | 22.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 1.5 MW | 1.28 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 7.03 MW | 5.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957382 | AF2-032 E | Adder | 0.17 MW | 0.15 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961021 | AF2-393 C | 50/50 | 7.42 MW | 7.42 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.68 MW | 0.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 945351 | AF1-200 FTIR | 50/50 | 256.07 MW | 256.07 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 953201 | J715 C | External Queue | 1.23 MW | 1.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 953202 | J715 E | External Queue | 6.64 MW | 6.64 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 954702 | J844 E | External Queue | 7.22 MW | 7.22 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 954741 | J928 C | External Queue | 0.98 MW | 0.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 954742 | J928 E | External Queue | 5.32 MW | 5.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 956141 | J1101 | External Queue | 1.63 MW | 1.63 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 954981 | J974 C | External Queue | 2.53 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 954982 | J974 E | External Queue | 13.68 MW | 13.68 MW |
| Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 1.88 MW | 1.88 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.29 MW | 0.29 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 1.23 MW | 1.23 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274856 | ECOGROVE ;U1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274857 | BIG SKY ;U1 | 50/50 | 1.29 MW | 1.29 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274858 | BIG SKY ;U2 | 50/50 | 1.29 MW | 1.29 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274859 | EASYR;U1 E | 50/50 | 5.17 MW | 5.17 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274860 | EASYR;U2 E | 50/50 | 5.17 MW | 5.17 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274861 | TOP CROP ;1U | 50/50 | 1.21 MW | 1.21 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274862 | TOP CROP ;2U | 50/50 | 2.35 MW | 2.35 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274863 | CAYUGA RI;1U | 50/50 | 1.95 MW | 1.95 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274864 | CAYUGA RI;2U | 50/50 | 1.95 MW | 1.95 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 2.39 MW | 2.39 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 2.75 MW | 2.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274879 | MINONK ;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274887 | PILOT HIL;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 275149 | KELLYCK ;1E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 276170 | Z1-108 E | 50/50 | 2.93 MW | 2.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290021 | O50 E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290051 | GSG-6; E | 50/50 | 4.93 MW | 4.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 11.46 MW | 11.46 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293061 | N-015 E | 50/50 | 7.52 MW | 7.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293644 | O22 E1 | 50/50 | 4.83 MW | 4.83 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293645 | O22 E2 | 50/50 | 9.39 MW | 9.39 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 294392 | P-010 E | 50/50 | 9.55 MW | 9.55 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 294763 | P-046 E | 50/50 | 4.41 MW | 4.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.45 MW | 0.45 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 295110 | SUBLETTE C | 50/50 | 0.2 MW | 0.2 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 295111 | SUBLETTE E | 50/50 | 1.43 MW | 1.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 916211 | Z1-072 E | Adder | 4.63 MW | 3.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 916221 | Z1-073 E | 50/50 | 2.54 MW | 2.54 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 917502 | Z2-087 E | 50/50 | 9.82 MW | 9.82 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 918052 | AA1-018 E OP | 50/50 | 7.75 MW | 7.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 920272 | AA2-123 E | 50/50 | 2.88 MW | 2.88 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 924041 | AB2-047 C O1 | 50/50 | 3.67 MW | 3.67 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 924042 | AB2-047 E O1 | 50/50 | 24.54 MW | 24.54 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925581 | AC1-033 C | Adder | 1.34 MW | 1.14 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925582 | AC1-033 E | Adder | 8.97 MW | 7.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 926821 | AC1-168 C O1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 926822 | AC1-168 E O1 | 50/50 | 7.39 MW | 7.39 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 927201 | AC1-214 C O1 | Adder | 1.96 MW | 1.67 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 6.24 MW | 5.3 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.12 MW | 0.12 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.52 MW | 0.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934721 | AD1-100 C | 50/50 | 22.84 MW | 22.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934722 | AD1-100 E | 50/50 | 106.59 MW | 106.59 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 935141 | AD1-148 | Adder | 2.84 MW | 2.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936371 | AD2-047 C O1 | 50/50 | 4.43 MW | 4.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936372 | AD2-047 E O1 | 50/50 | 21.64 MW | 21.64 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.39 MW | 2.39 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.54 MW | 9.54 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938861 | AE1-114 C O1 | 50/50 | 3.7 MW | 3.7 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938862 | AE1-114 E O1 | 50/50 | 12.61 MW | 12.61 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939321 | AE1-163 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939322 | AE1-163 E O1 | 50/50 | 34.19 MW | 34.19 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939401 | AE1-172 C O1 | 50/50 | 6.23 MW | 6.23 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939402 | AE1-172 E O1 | 50/50 | 29.23 MW | 29.23 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 941731 | AE2-173 O1 | 50/50 | 7.05 MW | 7.05 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942112 | AE2-223 E | 50/50 | 14.72 MW | 14.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942421 | AE2-255 C O1 | 50/50 | 2.85 MW | 2.85 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942422 | AE2-255 E O1 | 50/50 | 8.56 MW | 8.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942651 | AE2-281 C O1 | 50/50 | 0.8 MW | 0.8 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942652 | AE2-281 E O1 | 50/50 | 4.88 MW | 4.88 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943801 | AF1-048 C | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943802 | AF1-048 E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 3.7 MW | 3.14 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 17.32 MW | 14.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946501 | AF1-314 C | 50/50 | 4.1 MW | 4.1 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946502 | AF1-314 E | 50/50 | 19.27 MW | 19.27 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957331 | AF2-027 C | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957332 | AF2-027 E | 50/50 | 4.41 MW | 4.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957371 | AF2-031 C O1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957372 | AF2-031 E O1 | 50/50 | 1.65 MW | 1.65 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957401 | AF2-034 C | 50/50 | 1.65 MW | 1.65 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957402 | AF2-034 E | 50/50 | 1.4 MW | 1.4 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957751 | AF2-069 C | Adder | 0.23 MW | 0.19 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957752 | AF2-069 E | Adder | 0.73 MW | 0.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957761 | AF2-070 C | Adder | 0.32 MW | 0.27 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957762 | AF2-070 E | Adder | 1.56 MW | 1.32 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958921 | AF2-183 C | 50/50 | 4.28 MW | 4.28 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958922 | AF2-183 E | 50/50 | 6.41 MW | 6.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959102 | AF2-201 E O1 | 50/50 | 19.29 MW | 19.29 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959351 | AF2-226 C | 50/50 | 2.96 MW | 2.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959352 | AF2-226 E | 50/50 | 4.44 MW | 4.44 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959611 | AF2-252 C | Adder | 2.37 MW | 2.01 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959612 | AF2-252 E | Adder | 3.55 MW | 3.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960281 | AF2-319 C | 50/50 | 2.96 MW | 2.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960282 | AF2-319 E | 50/50 | 4.44 MW | 4.44 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.33 MW | 6.33 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960601 | AF2-351 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960602 | AF2-351 E O1 | 50/50 | 1.96 MW | 1.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960611 | AF2-352 C | Adder | 2.37 MW | 2.01 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960612 | AF2-352 E | Adder | 3.55 MW | 3.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.72 MW | 3.16 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961012 | AF2-392 E O1 | 50/50 | 17.43 MW | 17.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961031 | AF2-394 O1 | Adder | 5.29 MW | 4.49 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936291 | AD2-038 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936292 | AD2-038 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274881 | PILOT HIL;1E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274888 | KELLYCK ;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274890 | CAYUG;1U E | 50/50 | 7.78 MW | 7.78 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274891 | CAYUG;2U E | 50/50 | 7.78 MW | 7.78 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 917501 | Z2-087 C | 50/50 | 1.47 MW | 1.47 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 918051 | AA1-018 C OP | 50/50 | 1.16 MW | 1.16 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 924261 | AB2-070 C O1 | Adder | 2.1 MW | 1.78 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 924262 | AB2-070 E O1 | Adder | 14.02 MW | 11.92 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925301 | AB2-191 | 50/50 | 0.53 MW | 0.53 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925302 | AB2-191 E | 50/50 | 1.31 MW | 1.31 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925771 | AC1-053 C | Adder | 2.08 MW | 1.76 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 925772 | AC1-053 E | Adder | 13.89 MW | 11.8 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938851 | AE1-113 C | 50/50 | 7.53 MW | 7.53 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938852 | AE1-113 E | 50/50 | 26.7 MW | 26.7 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 940752 | AE2-062 E | 50/50 | 0.15 MW | 0.15 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 944221 | AF1-090 C O1 | Adder | 2.02 MW | 1.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 944222 | AF1-090 E O1 | Adder | 9.48 MW | 8.05 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 945871 | AF1-252 O1 | Adder | 4.48 MW | 3.81 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 945881 | AF1-253 O1 | Adder | 3.1 MW | 2.64 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946161 | AF1-281 C | 50/50 | 0.4 MW | 0.4 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946162 | AF1-281 E | 50/50 | 2.27 MW | 2.27 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 5.53 MW | 4.7 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 25.9 MW | 22.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 1.47 MW | 1.25 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 6.88 MW | 5.85 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957382 | AF2-032 E | Adder | 0.17 MW | 0.14 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961021 | AF2-393 C | 50/50 | 7.27 MW | 7.27 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961023 | AF2-393 E | Adder | 0.66 MW | 0.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 250.75 MW | 250.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 953201 | J715 C | External Queue | 1.2 MW | 1.2 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 953202 | J715 E | External Queue | 6.51 MW | 6.51 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 954702 | J844 E | External Queue | 7.07 MW | 7.07 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 954741 | J928 C | External Queue | 0.96 MW | 0.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 954742 | J928 E | External Queue | 5.21 MW | 5.21 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 956141 | J1101 | External Queue | 1.59 MW | 1.59 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 954981 | J974 C | External Queue | 2.48 MW | 2.48 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 954982 | J974 E | External Queue | 13.4 MW | 13.4 MW |
| Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274847 | GR RIDGE ;BU | 50/50 | 1.92 MW | 1.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274850 | MENDOTA H;RU | 50/50 | 0.3 MW | 0.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274855 | GSG-6 ;RU | 50/50 | 1.26 MW | 1.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274856 | ECOGROVE ;U1 | 50/50 | 1.13 MW | 1.13 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 1.32 MW | 1.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 1.32 MW | 1.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 5.28 MW | 5.28 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 5.28 MW | 5.28 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 1.23 MW | 1.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 2.4 MW | 2.4 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274863 | CAYUGA RI;1U | 50/50 | 1.98 MW | 1.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274864 | CAYUGA RI;2U | 50/50 | 1.98 MW | 1.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274871 | GR RIDGE ;2U | 50/50 | 2.44 MW | 2.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274872 | LEE DEKAL;1U | 50/50 | 2.81 MW | 2.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274879 | MINONK ;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 276170 | Z1-108 E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290021 | O50 E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290051 | GSG-6; E | 50/50 | 5.04 MW | 5.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290108 | LEEDK;1U E | 50/50 | 11.71 MW | 11.71 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293061 | N-015 E | 50/50 | 7.68 MW | 7.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 4.94 MW | 4.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 9.59 MW | 9.59 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 294392 | P-010 E | 50/50 | 9.75 MW | 9.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 294763 | P-046 E | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 295108 | WESTBROOK C | 50/50 | 0.46 MW | 0.46 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 295109 | WESTBROOK E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.2 MW | 0.2 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 1.47 MW | 1.47 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 916211 | Z1-072 E | Adder | 4.73 MW | 4.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 916221 | Z1-073 E | 50/50 | 2.6 MW | 2.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 917502 | Z2-087 E | 50/50 | 10.02 MW | 10.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 7.92 MW | 7.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 920272 | AA2-123 E | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 3.74 MW | 3.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 25.04 MW | 25.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925581 | AC1-033 C | Adder | 1.37 MW | 1.16 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925582 | AC1-033 E | Adder | 9.16 MW | 7.78 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 926821 | AC1-168 C O1 | 50/50 | 1.12 MW | 1.12 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 926822 | AC1-168 E O1 | 50/50 | 7.55 MW | 7.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 2.0 MW | 1.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 6.37 MW | 5.42 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934431 | AD1-067 C | 50/50 | 0.13 MW | 0.13 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934432 | AD1-067 E | 50/50 | 0.53 MW | 0.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934721 | AD1-100 C | 50/50 | 23.29 MW | 23.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934722 | AD1-100 E | 50/50 | 108.71 MW | 108.71 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 4.53 MW | 4.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 22.1 MW | 22.1 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937001 | AD2-134 C | 50/50 | 2.44 MW | 2.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937002 | AD2-134 E | 50/50 | 9.74 MW | 9.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 3.77 MW | 3.77 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 12.88 MW | 12.88 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939321 | AE1-163 C O1 | 50/50 | 5.69 MW | 5.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939322 | AE1-163 E O1 | 50/50 | 34.93 MW | 34.93 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939401 | AE1-172 C O1 | 50/50 | 6.35 MW | 6.35 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939402 | AE1-172 E O1 | 50/50 | 29.81 MW | 29.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 7.19 MW | 7.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942111 | AE2-223 C | 50/50 | 2.25 MW | 2.25 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942112 | AE2-223 E | 50/50 | 15.02 MW | 15.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942421 | AE2-255 C O1 | 50/50 | 2.91 MW | 2.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942422 | AE2-255 E O1 | 50/50 | 8.74 MW | 8.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942651 | AE2-281 C O1 | 50/50 | 0.81 MW | 0.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942652 | AE2-281 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943801 | AF1-048 C | 50/50 | 4.6 MW | 4.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943802 | AF1-048 E | 50/50 | 3.06 MW | 3.06 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 3.78 MW | 3.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 17.69 MW | 15.03 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946501 | AF1-314 C | 50/50 | 4.19 MW | 4.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946502 | AF1-314 E | 50/50 | 19.68 MW | 19.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957331 | AF2-027 C | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957332 | AF2-027 E | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957371 | AF2-031 C O1 | 50/50 | 1.13 MW | 1.13 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957372 | AF2-031 E O1 | 50/50 | 1.69 MW | 1.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957401 | AF2-034 C | 50/50 | 1.68 MW | 1.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957402 | AF2-034 E | 50/50 | 1.43 MW | 1.43 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.23 MW | 0.2 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.75 MW | 0.64 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.33 MW | 0.28 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.59 MW | 1.35 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958921 | AF2-183 C | 50/50 | 4.37 MW | 4.37 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958922 | AF2-183 E | 50/50 | 6.55 MW | 6.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959102 | AF2-201 E O1 | 50/50 | 19.7 MW | 19.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 3.02 MW | 3.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.54 MW | 4.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959611 | AF2-252 C | Adder | 2.42 MW | 2.05 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959612 | AF2-252 E | Adder | 3.62 MW | 3.08 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 3.02 MW | 3.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.54 MW | 4.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960381 | AF2-329 | 50/50 | 6.46 MW | 6.46 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960601 | AF2-351 C O1 | 50/50 | 1.33 MW | 1.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960602 | AF2-351 E O1 | 50/50 | 2.0 MW | 2.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960611 | AF2-352 C | Adder | 2.42 MW | 2.05 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960612 | AF2-352 E | Adder | 3.62 MW | 3.08 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 3.8 MW | 3.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 17.8 MW | 17.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 5.4 MW | 4.59 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936291 | AD2-038 C O1 | 50/50 | 2.26 MW | 2.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936292 | AD2-038 E O1 | 50/50 | 15.14 MW | 15.14 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 9.32 MW | 9.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 2.33 MW | 2.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274890 | CAYUG;1U E | 50/50 | 7.94 MW | 7.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274891 | CAYUG;2U E | 50/50 | 7.94 MW | 7.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 917501 | Z2-087 C | 50/50 | 1.5 MW | 1.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 1.18 MW | 1.18 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 2.14 MW | 1.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 14.31 MW | 12.16 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925301 | AB2-191 | 50/50 | 0.54 MW | 0.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925302 | AB2-191 E | 50/50 | 1.33 MW | 1.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925771 | AC1-053 C | Adder | 2.12 MW | 1.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 925772 | AC1-053 E | Adder | 14.17 MW | 12.05 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938851 | AE1-113 C | 50/50 | 7.69 MW | 7.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938852 | AE1-113 E | 50/50 | 27.27 MW | 27.27 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.16 MW | 0.16 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946161 | AF1-281 C | 50/50 | 0.41 MW | 0.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946162 | AF1-281 E | 50/50 | 2.32 MW | 2.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 5.65 MW | 4.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 26.45 MW | 22.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 1.5 MW | 1.28 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 7.03 MW | 5.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961021 | AF2-393 C | 50/50 | 7.42 MW | 7.42 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.68 MW | 0.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 945351 | AF1-200 FTIR | 50/50 | 256.07 MW | 256.07 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247255 | 05WLD G2 C | 80/20 | 0.36 MW | 0.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243859 | 05FR-11G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243862 | 05FR-12G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243864 | 05FR-21G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243866 | 05FR-22G C | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243870 | 05FR-3G C | 80/20 | 1.06 MW | 1.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243873 | 05FR-4G C | 80/20 | 0.82 MW | 0.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247901 | 05FR-12G E | 80/20 | 2.06 MW | 2.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247902 | 05FR-21G E | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247904 | 05FR-3G E | 80/20 | 4.26 MW | 4.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247905 | 05FR-4G E | 80/20 | 3.34 MW | 3.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247906 | 05MDL-1G E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247907 | 05MDL-2G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247912 | 05MDL-3G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247913 | 05MDL-4G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247958 | 05WLD G2 E | 80/20 | 4.65 MW | 4.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274847 | GR RIDGE ;BU | 80/20 | 0.87 MW | 0.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274848 | CAMPGROVE;RU | 80/20 | 0.8 MW | 0.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274850 | MENDOTA H;RU | 80/20 | 0.14 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274851 | PROVIDENC;RU | 80/20 | 0.4 MW | 0.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274853 | TWINGROVE;U1 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274854 | TWINGROVE;U2 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274855 | GSG-6 ;RU | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274859 | EASYR;U1 E | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274860 | EASYR;U2 E | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274861 | TOP CROP ;1U | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274862 | TOP CROP ;2U | 80/20 | 1.14 MW | 1.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274863 | CAYUGA RI;1U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274864 | CAYUGA RI;2U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274871 | GR RIDGE ;2U | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274872 | LEE DEKAL;1U | 80/20 | 1.35 MW | 1.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274877 | BISHOP HL;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274878 | BISHOP HL;2U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274879 | MINONK ;1U | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 275149 | KELLYCK ;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 276158 | O-029 C | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 290021 | O50 E | 80/20 | 4.51 MW | 4.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 290051 | GSG-6; E | 80/20 | 2.44 MW | 2.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 290108 | LEEDK;1U E | 80/20 | 5.64 MW | 5.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 290261 | S-027 E | 80/20 | 4.06 MW | 4.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 290265 | S-028 E | 80/20 | 4.06 MW | 4.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293061 | N-015 E | 80/20 | 3.5 MW | 3.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293516 | O-009 E1 | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293517 | O-009 E2 | 80/20 | 1.12 MW | 1.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293518 | O-009 E3 | 80/20 | 1.23 MW | 1.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293644 | O22 E1 | 80/20 | 2.34 MW | 2.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293645 | O22 E2 | 80/20 | 4.55 MW | 4.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293715 | O-029 E | 80/20 | 2.36 MW | 2.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293716 | O-029 E | 80/20 | 1.29 MW | 1.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293717 | O-029 E | 80/20 | 1.19 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 293771 | O-035 E | 80/20 | 1.59 MW | 1.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 294392 | P-010 E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 294401 | BSHIL;1U E | 80/20 | 2.13 MW | 2.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 294410 | BSHIL;2U E | 80/20 | 2.13 MW | 2.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 294763 | P-046 E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 295108 | WESTBROOK C | 80/20 | 0.22 MW | 0.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 917502 | Z2-087 E | 80/20 | 4.7 MW | 4.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 924041 | AB2-047 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 924042 | AB2-047 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925581 | AC1-033 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925582 | AC1-033 E | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 926821 | AC1-168 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 926822 | AC1-168 E O1 | 80/20 | 3.74 MW | 3.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 927201 | AC1-214 C O1 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 927202 | AC1-214 E O1 | 80/20 | 3.24 MW | 3.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 930041 | AB1-006 C | 80/20 | 0.72 MW | 0.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 930042 | AB1-006 E | 80/20 | 4.84 MW | 4.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 933281 | AC2-140 C | 80/20 | 3.11 MW | 3.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 934432 | AD1-067 E | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 934721 | AD1-100 C | 80/20 | 8.8 MW | 8.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 934722 | AD1-100 E | 80/20 | 41.07 MW | 41.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 935141 | AD1-148 | 80/20 | 1.78 MW | 1.78 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936372 | AD2-047 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 937001 | AD2-134 C | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 937002 | AD2-134 E | 80/20 | 4.73 MW | 4.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 938861 | AE1-114 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 938862 | AE1-114 E O1 | 80/20 | 6.35 MW | 6.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939321 | AE1-163 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939322 | AE1-163 E O1 | 80/20 | 16.89 MW | 16.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939401 | AE1-172 C O1 | 80/20 | 2.53 MW | 2.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939402 | AE1-172 E O1 | 80/20 | 11.87 MW | 11.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 941731 | AE2-173 O1 | 80/20 | 3.37 MW | 3.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942111 | AE2-223 C | 80/20 | 1.05 MW | 1.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942112 | AE2-223 E | 80/20 | 7.04 MW | 7.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942421 | AE2-255 C O1 | 80/20 | 1.41 MW | 1.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942422 | AE2-255 E O1 | 80/20 | 4.22 MW | 4.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942651 | AE2-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942652 | AE2-281 E O1 | 80/20 | 2.41 MW | 2.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 943021 | AE2-325 C | 80/20 | 2.62 MW | 2.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 943801 | AF1-048 C | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 943802 | AF1-048 E | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944242 | AF1-092 E O1 | 80/20 | 12.49 MW | 12.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944532 | AF1-118 E O1 | 80/20 | 35.49 MW | 35.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944542 | AF1-119 E O1 | 80/20 | 17.65 MW | 17.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944832 | AF1-148 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944932 | AF1-158 E O1 | 80/20 | 12.38 MW | 12.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944961 | AF1-161 C | 80/20 | 2.09 MW | 2.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944962 | AF1-161 E | 80/20 | 2.09 MW | 2.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945111 | AF1-176 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945112 | AF1-176 E O1 | 80/20 | 6.48 MW | 6.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945371 | AF1-202 C O1 | 80/20 | 2.3 MW | 2.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945372 | AF1-202 E O1 | 80/20 | 11.23 MW | 11.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945391 | AF1-204 C O1 | 80/20 | 2.85 MW | 2.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945392 | AF1-204 E O1 | 80/20 | 8.56 MW | 8.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946321 | AF1-296 C O1 | 80/20 | 1.94 MW | 1.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946322 | AF1-296 E O1 | 80/20 | 9.1 MW | 9.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946501 | AF1-314 C | 80/20 | 2.05 MW | 2.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946502 | AF1-314 E | 80/20 | 9.63 MW | 9.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957331 | AF2-027 C | 80/20 | 1.43 MW | 1.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957332 | AF2-027 E | 80/20 | 2.14 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957371 | AF2-031 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957372 | AF2-031 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957401 | AF2-034 C | 80/20 | 0.79 MW | 0.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957402 | AF2-034 E | 80/20 | 0.67 MW | 0.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957752 | AF2-069 E | 80/20 | 0.38 MW | 0.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957762 | AF2-070 E | 80/20 | 0.81 MW | 0.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958861 | AF2-177 C O1 | 80/20 | 1.84 MW | 1.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958862 | AF2-177 E O1 | 80/20 | 12.3 MW | 12.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958921 | AF2-183 C | 80/20 | 2.17 MW | 2.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958922 | AF2-183 E | 80/20 | 3.25 MW | 3.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 959102 | AF2-201 E O1 | 80/20 | 9.65 MW | 9.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 959351 | AF2-226 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 959352 | AF2-226 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 959611 | AF2-252 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 959612 | AF2-252 E | 80/20 | 1.93 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960281 | AF2-319 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960282 | AF2-319 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960381 | AF2-329 | 80/20 | 3.06 MW | 3.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960611 | AF2-352 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960612 | AF2-352 E | 80/20 | 1.93 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960851 | AF2-376 C | 80/20 | 1.83 MW | 1.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960852 | AF2-376 E | 80/20 | 2.75 MW | 2.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960861 | AF2-377 C | 80/20 | 2.14 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960862 | AF2-377 E | 80/20 | 3.21 MW | 3.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960971 | AF2-388 C | 80/20 | 2.55 MW | 2.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 960972 | AF2-388 E | 80/20 | 11.94 MW | 11.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961011 | AF2-392 C O1 | 80/20 | 1.9 MW | 1.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961012 | AF2-392 E O1 | 80/20 | 8.89 MW | 8.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961031 | AF2-394 O1 | 80/20 | 2.7 MW | 2.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246953 | 05TIMB G C | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246991 | 05WLD G1 C | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247536 | 05BLUFF P WF | 80/20 | 0.62 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247543 | V3-007 C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247911 | 05TIMB G E | 80/20 | 4.43 MW | 4.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247929 | S-071 E | 80/20 | 2.49 MW | 2.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247963 | 05HDWTR1G E | 80/20 | 4.36 MW | 4.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936291 | AD2-038 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936292 | AD2-038 E O1 | 80/20 | 7.32 MW | 7.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939781 | AE1-209 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939782 | AE1-209 E O1 | 80/20 | 4.96 MW | 4.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939791 | AE1-210 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 939792 | AE1-210 E O1 | 80/20 | 4.96 MW | 4.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 941721 | AE2-172 | 80/20 | 2.87 MW | 2.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961161 | AF2-407 | 80/20 | 17.73 MW | 17.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961171 | AF2-408 | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246909 | 05MDL-1G C | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246910 | 05MDL-2G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246976 | 05MDL-3G C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 246979 | 05MDL-4G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247521 | T-131 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247556 | T-127 C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247925 | T-131 E | 80/20 | 5.14 MW | 5.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 247943 | T-127 E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274880 | GENERATOR; | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274881 | PILOT HIL;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274882 | W4-005 E | 80/20 | 6.43 MW | 6.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274888 | KELLYCK ;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274890 | CAYUG;1U E | 80/20 | 3.33 MW | 3.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 274891 | CAYUG;2U E | 80/20 | 3.33 MW | 3.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 917501 | Z2-087 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 918051 | AA1-018 C OP | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 924261 | AB2-070 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 924262 | AB2-070 E O1 | 80/20 | 8.6 MW | 8.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925301 | AB2-191 | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925302 | AB2-191 E | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925771 | AC1-053 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 925772 | AC1-053 E | 80/20 | 8.57 MW | 8.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 926861 | AC1-173 C | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 926862 | AC1-173 E | 80/20 | 2.89 MW | 2.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 933591 | AC2-176 C O1 | 80/20 | 0.25 MW | 0.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 933592 | AC2-176 E O1 | 80/20 | 3.21 MW | 3.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 938851 | AE1-113 C | 80/20 | 3.72 MW | 3.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 938852 | AE1-113 E | 80/20 | 13.18 MW | 13.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 940752 | AE2-062 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944221 | AF1-090 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 944222 | AF1-090 E O1 | 80/20 | 7.39 MW | 7.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945871 | AF1-252 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945881 | AF1-253 O1 | 80/20 | 2.42 MW | 2.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946162 | AF1-281 E | 80/20 | 1.15 MW | 1.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946541 | AF1-318 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946542 | AF1-318 E O1 | 80/20 | 13.37 MW | 13.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958341 | AF2-128 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 958342 | AF2-128 E O1 | 80/20 | 3.55 MW | 3.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 243795 | 05HDWTR1G C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 990901 | L-005 E | 80/20 | 3.19 MW | 3.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961021 | AF2-393 C | 80/20 | 3.71 MW | 3.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 961023 | AF2-393 E | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936722 | AD2-091 BAT | 80/20 | 6.82 MW | 6.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 936752 | AD2-096 BAT | 80/20 | 3.14 MW | 3.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 942042 | AE2-216 BAT | 80/20 | 7.5 MW | 7.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 945351 | AF1-200 FTIR | 80/20 | 120.03 MW | 120.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-B | 946203 | AF1-285 BAT | 80/20 | 2.5 MW | 2.5 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247255 | 05WLD G2 C | 80/20 | 0.36 MW | 0.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243859 | 05FR-11G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243862 | 05FR-12G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243864 | 05FR-21G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243866 | 05FR-22G C | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243870 | 05FR-3G C | 80/20 | 1.06 MW | 1.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243873 | 05FR-4G C | 80/20 | 0.82 MW | 0.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247901 | 05FR-12G E | 80/20 | 2.06 MW | 2.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247902 | 05FR-21G E | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247904 | 05FR-3G E | 80/20 | 4.26 MW | 4.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247905 | 05FR-4G E | 80/20 | 3.34 MW | 3.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247906 | 05MDL-1G E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247907 | 05MDL-2G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247912 | 05MDL-3G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247913 | 05MDL-4G E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247958 | 05WLD G2 E | 80/20 | 4.65 MW | 4.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274847 | GR RIDGE ;BU | 80/20 | 0.87 MW | 0.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274848 | CAMPGROVE;RU | 80/20 | 0.8 MW | 0.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274850 | MENDOTA H;RU | 80/20 | 0.14 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274851 | PROVIDENC;RU | 80/20 | 0.4 MW | 0.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274853 | TWINGROVE;U1 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274854 | TWINGROVE;U2 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274855 | GSG-6 ;RU | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274859 | EASYR;U1 E | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274860 | EASYR;U2 E | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274861 | TOP CROP ;1U | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274862 | TOP CROP ;2U | 80/20 | 1.14 MW | 1.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274863 | CAYUGA RI;1U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274864 | CAYUGA RI;2U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274871 | GR RIDGE ;2U | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274872 | LEE DEKAL;1U | 80/20 | 1.35 MW | 1.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274877 | BISHOP HL;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274878 | BISHOP HL;2U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274879 | MINONK ;1U | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 275149 | KELLYCK ;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 276158 | O-029 C | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 290021 | O50 E | 80/20 | 4.51 MW | 4.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 290051 | GSG-6; E | 80/20 | 2.44 MW | 2.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 290108 | LEEDK;1U E | 80/20 | 5.64 MW | 5.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 290261 | S-027 E | 80/20 | 4.06 MW | 4.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 290265 | S-028 E | 80/20 | 4.06 MW | 4.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293061 | N-015 E | 80/20 | 3.5 MW | 3.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293516 | O-009 E1 | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293517 | O-009 E2 | 80/20 | 1.12 MW | 1.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293518 | O-009 E3 | 80/20 | 1.23 MW | 1.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293644 | O22 E1 | 80/20 | 2.34 MW | 2.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293645 | O22 E2 | 80/20 | 4.55 MW | 4.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293715 | O-029 E | 80/20 | 2.36 MW | 2.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293716 | O-029 E | 80/20 | 1.29 MW | 1.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293717 | O-029 E | 80/20 | 1.19 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 293771 | O-035 E | 80/20 | 1.59 MW | 1.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 294392 | P-010 E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 294401 | BSHIL;1U E | 80/20 | 2.13 MW | 2.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 294410 | BSHIL;2U E | 80/20 | 2.13 MW | 2.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 294763 | P-046 E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 295108 | WESTBROOK C | 80/20 | 0.22 MW | 0.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 917502 | Z2-087 E | 80/20 | 4.7 MW | 4.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 924041 | AB2-047 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 924042 | AB2-047 E O1 | 80/20 | 11.74 MW | 11.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925581 | AC1-033 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925582 | AC1-033 E | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 926821 | AC1-168 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 926822 | AC1-168 E O1 | 80/20 | 3.74 MW | 3.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 927201 | AC1-214 C O1 | 80/20 | 1.02 MW | 1.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 927202 | AC1-214 E O1 | 80/20 | 3.24 MW | 3.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 930041 | AB1-006 C | 80/20 | 0.72 MW | 0.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 930042 | AB1-006 E | 80/20 | 4.84 MW | 4.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 933281 | AC2-140 C | 80/20 | 3.11 MW | 3.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 934432 | AD1-067 E | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 934721 | AD1-100 C | 80/20 | 8.8 MW | 8.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 934722 | AD1-100 E | 80/20 | 41.07 MW | 41.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 935141 | AD1-148 | 80/20 | 1.78 MW | 1.78 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936372 | AD2-047 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 937001 | AD2-134 C | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 937002 | AD2-134 E | 80/20 | 4.73 MW | 4.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 938861 | AE1-114 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 938862 | AE1-114 E O1 | 80/20 | 6.35 MW | 6.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939321 | AE1-163 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939322 | AE1-163 E O1 | 80/20 | 16.89 MW | 16.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939401 | AE1-172 C O1 | 80/20 | 2.53 MW | 2.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939402 | AE1-172 E O1 | 80/20 | 11.87 MW | 11.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 941731 | AE2-173 O1 | 80/20 | 3.37 MW | 3.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942111 | AE2-223 C | 80/20 | 1.05 MW | 1.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942112 | AE2-223 E | 80/20 | 7.04 MW | 7.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942421 | AE2-255 C O1 | 80/20 | 1.41 MW | 1.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942422 | AE2-255 E O1 | 80/20 | 4.22 MW | 4.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942651 | AE2-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942652 | AE2-281 E O1 | 80/20 | 2.41 MW | 2.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 943021 | AE2-325 C | 80/20 | 2.62 MW | 2.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 943801 | AF1-048 C | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 943802 | AF1-048 E | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944242 | AF1-092 E O1 | 80/20 | 12.49 MW | 12.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944532 | AF1-118 E O1 | 80/20 | 35.49 MW | 35.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944542 | AF1-119 E O1 | 80/20 | 17.65 MW | 17.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944832 | AF1-148 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944932 | AF1-158 E O1 | 80/20 | 12.38 MW | 12.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944961 | AF1-161 C | 80/20 | 2.09 MW | 2.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944962 | AF1-161 E | 80/20 | 2.09 MW | 2.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945111 | AF1-176 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945112 | AF1-176 E O1 | 80/20 | 6.48 MW | 6.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945371 | AF1-202 C O1 | 80/20 | 2.3 MW | 2.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945372 | AF1-202 E O1 | 80/20 | 11.23 MW | 11.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945391 | AF1-204 C O1 | 80/20 | 2.85 MW | 2.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945392 | AF1-204 E O1 | 80/20 | 8.56 MW | 8.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946321 | AF1-296 C O1 | 80/20 | 1.94 MW | 1.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946322 | AF1-296 E O1 | 80/20 | 9.1 MW | 9.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946501 | AF1-314 C | 80/20 | 2.05 MW | 2.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946502 | AF1-314 E | 80/20 | 9.63 MW | 9.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957331 | AF2-027 C | 80/20 | 1.43 MW | 1.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957332 | AF2-027 E | 80/20 | 2.14 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957371 | AF2-031 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957372 | AF2-031 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957401 | AF2-034 C | 80/20 | 0.79 MW | 0.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957402 | AF2-034 E | 80/20 | 0.67 MW | 0.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957752 | AF2-069 E | 80/20 | 0.38 MW | 0.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957762 | AF2-070 E | 80/20 | 0.81 MW | 0.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958861 | AF2-177 C O1 | 80/20 | 1.84 MW | 1.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958862 | AF2-177 E O1 | 80/20 | 12.3 MW | 12.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958921 | AF2-183 C | 80/20 | 2.17 MW | 2.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958922 | AF2-183 E | 80/20 | 3.25 MW | 3.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 959102 | AF2-201 E O1 | 80/20 | 9.65 MW | 9.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 959351 | AF2-226 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 959352 | AF2-226 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 959611 | AF2-252 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 959612 | AF2-252 E | 80/20 | 1.93 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960281 | AF2-319 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960282 | AF2-319 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960381 | AF2-329 | 80/20 | 3.06 MW | 3.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960611 | AF2-352 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960612 | AF2-352 E | 80/20 | 1.93 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960851 | AF2-376 C | 80/20 | 1.83 MW | 1.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960852 | AF2-376 E | 80/20 | 2.75 MW | 2.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960861 | AF2-377 C | 80/20 | 2.14 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960862 | AF2-377 E | 80/20 | 3.21 MW | 3.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960971 | AF2-388 C | 80/20 | 2.55 MW | 2.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 960972 | AF2-388 E | 80/20 | 11.94 MW | 11.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961011 | AF2-392 C O1 | 80/20 | 1.9 MW | 1.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961012 | AF2-392 E O1 | 80/20 | 8.89 MW | 8.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961031 | AF2-394 O1 | 80/20 | 2.7 MW | 2.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246953 | 05TIMB G C | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246991 | 05WLD G1 C | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247536 | 05BLUFF P WF | 80/20 | 0.62 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247543 | V3-007 C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247911 | 05TIMB G E | 80/20 | 4.43 MW | 4.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247929 | S-071 E | 80/20 | 2.49 MW | 2.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247963 | 05HDWTR1G E | 80/20 | 4.36 MW | 4.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936291 | AD2-038 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936292 | AD2-038 E O1 | 80/20 | 7.32 MW | 7.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939781 | AE1-209 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939782 | AE1-209 E O1 | 80/20 | 4.96 MW | 4.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939791 | AE1-210 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 939792 | AE1-210 E O1 | 80/20 | 4.96 MW | 4.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 941721 | AE2-172 | 80/20 | 2.87 MW | 2.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961161 | AF2-407 | 80/20 | 17.73 MW | 17.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961171 | AF2-408 | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246909 | 05MDL-1G C | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246910 | 05MDL-2G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246976 | 05MDL-3G C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 246979 | 05MDL-4G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247521 | T-131 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247556 | T-127 C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247925 | T-131 E | 80/20 | 5.14 MW | 5.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 247943 | T-127 E | 80/20 | 2.23 MW | 2.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274880 | GENERATOR; | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274881 | PILOT HIL;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274882 | W4-005 E | 80/20 | 6.43 MW | 6.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274888 | KELLYCK ;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274890 | CAYUG;1U E | 80/20 | 3.33 MW | 3.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 274891 | CAYUG;2U E | 80/20 | 3.33 MW | 3.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 917501 | Z2-087 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 918051 | AA1-018 C OP | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 924261 | AB2-070 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 924262 | AB2-070 E O1 | 80/20 | 8.6 MW | 8.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925301 | AB2-191 | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925302 | AB2-191 E | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925771 | AC1-053 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 925772 | AC1-053 E | 80/20 | 8.57 MW | 8.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 926861 | AC1-173 C | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 926862 | AC1-173 E | 80/20 | 2.89 MW | 2.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 933591 | AC2-176 C O1 | 80/20 | 0.25 MW | 0.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 933592 | AC2-176 E O1 | 80/20 | 3.21 MW | 3.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 938851 | AE1-113 C | 80/20 | 3.72 MW | 3.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 938852 | AE1-113 E | 80/20 | 13.18 MW | 13.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 940752 | AE2-062 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944221 | AF1-090 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 944222 | AF1-090 E O1 | 80/20 | 7.39 MW | 7.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945871 | AF1-252 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945881 | AF1-253 O1 | 80/20 | 2.42 MW | 2.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946162 | AF1-281 E | 80/20 | 1.15 MW | 1.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946541 | AF1-318 C O1 | 80/20 | 2.86 MW | 2.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946542 | AF1-318 E O1 | 80/20 | 13.37 MW | 13.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958341 | AF2-128 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 958342 | AF2-128 E O1 | 80/20 | 3.55 MW | 3.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 243795 | 05HDWTR1G C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 990901 | L-005 E | 80/20 | 3.19 MW | 3.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961021 | AF2-393 C | 80/20 | 3.71 MW | 3.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 961023 | AF2-393 E | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936722 | AD2-091 BAT | 80/20 | 6.82 MW | 6.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 936752 | AD2-096 BAT | 80/20 | 3.14 MW | 3.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 942042 | AE2-216 BAT | 80/20 | 7.5 MW | 7.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 945351 | AF1-200 FTIR | 80/20 | 120.03 MW | 120.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441-A | 946203 | AF1-285 BAT | 80/20 | 2.5 MW | 2.5 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 276170 | Z1-108 E | Adder | 1.41 MW | 1.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 916211 | Z1-072 E | Adder | 2.38 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 920272 | AA2-123 E | Adder | 1.4 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 924041 | AB2-047 C O1 | Adder | 1.74 MW | 1.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 924042 | AB2-047 E O1 | Adder | 11.62 MW | 9.88 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 925581 | AC1-033 C | Adder | 0.69 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 925582 | AC1-033 E | Adder | 4.64 MW | 3.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 926821 | AC1-168 C O1 | Adder | 0.55 MW | 0.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 926822 | AC1-168 E O1 | Adder | 3.71 MW | 3.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 927201 | AC1-214 C O1 | Adder | 1.01 MW | 0.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 927202 | AC1-214 E O1 | Adder | 3.21 MW | 2.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 933281 | AC2-140 C | Adder | 3.07 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 934431 | AD1-067 C | Adder | 0.06 MW | 0.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 934432 | AD1-067 E | Adder | 0.26 MW | 0.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 934721 | AD1-100 C | Adder | 8.7 MW | 7.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 934722 | AD1-100 E | Adder | 40.62 MW | 34.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 935141 | AD1-148 | Adder | 1.76 MW | 1.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 936371 | AD2-047 C O1 | Adder | 1.99 MW | 1.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 936372 | AD2-047 E O1 | Adder | 9.74 MW | 8.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 937001 | AD2-134 C | Adder | 1.17 MW | 1.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 937002 | AD2-134 E | Adder | 4.68 MW | 3.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 938861 | AE1-114 C O1 | Adder | 1.84 MW | 1.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 938862 | AE1-114 E O1 | Adder | 6.29 MW | 5.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939321 | AE1-163 C O1 | Adder | 2.72 MW | 2.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939322 | AE1-163 E O1 | Adder | 16.72 MW | 14.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939401 | AE1-172 C O1 | Adder | 2.5 MW | 2.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939402 | AE1-172 E O1 | Adder | 11.74 MW | 9.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 941731 | AE2-173 O1 | Adder | 3.34 MW | 2.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942111 | AE2-223 C | Adder | 1.04 MW | 0.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942112 | AE2-223 E | Adder | 6.97 MW | 5.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942421 | AE2-255 C O1 | Adder | 1.39 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942422 | AE2-255 E O1 | Adder | 4.18 MW | 3.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942651 | AE2-281 C O1 | Adder | 0.39 MW | 0.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942652 | AE2-281 E O1 | Adder | 2.39 MW | 2.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 943021 | AE2-325 C | Adder | 2.58 MW | 2.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 943022 | AE2-325 E | Adder | 1.72 MW | 1.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 943801 | AF1-048 C | Adder | 2.19 MW | 1.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 943802 | AF1-048 E | Adder | 1.46 MW | 1.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944241 | AF1-092 C O1 | 50/50 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944242 | AF1-092 E O1 | 50/50 | 12.34 MW | 12.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944532 | AF1-118 E O1 | 50/50 | 35.02 MW | 35.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944542 | AF1-119 E O1 | Adder | 17.41 MW | 14.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944831 | AF1-148 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944832 | AF1-148 E O1 | Adder | 15.55 MW | 13.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944931 | AF1-158 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944932 | AF1-158 E O1 | Adder | 12.21 MW | 10.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944961 | AF1-161 C | Adder | 2.06 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944962 | AF1-161 E | Adder | 2.06 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945111 | AF1-176 C O1 | Adder | 4.25 MW | 3.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945112 | AF1-176 E O1 | Adder | 6.38 MW | 5.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945371 | AF1-202 C O1 | Adder | 2.27 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945372 | AF1-202 E O1 | Adder | 11.07 MW | 9.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945391 | AF1-204 C O1 | Adder | 2.83 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945392 | AF1-204 E O1 | Adder | 8.49 MW | 7.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946321 | AF1-296 C O1 | Adder | 1.93 MW | 1.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946322 | AF1-296 E O1 | Adder | 9.02 MW | 7.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946501 | AF1-314 C | Adder | 2.03 MW | 1.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946502 | AF1-314 E | Adder | 9.54 MW | 8.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957331 | AF2-027 C | Adder | 1.41 MW | 1.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957332 | AF2-027 E | Adder | 2.12 MW | 1.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957371 | AF2-031 C O1 | Adder | 0.6 MW | 0.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957372 | AF2-031 E O1 | Adder | 0.9 MW | 0.77 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957401 | AF2-034 C | Adder | 0.78 MW | 0.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957402 | AF2-034 E | Adder | 0.66 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957751 | AF2-069 C | Adder | 0.12 MW | 0.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957752 | AF2-069 E | Adder | 0.38 MW | 0.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957761 | AF2-070 C | Adder | 0.16 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957762 | AF2-070 E | Adder | 0.8 MW | 0.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958861 | AF2-177 C O1 | Adder | 1.81 MW | 1.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958862 | AF2-177 E O1 | Adder | 12.12 MW | 10.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958921 | AF2-183 C | Adder | 2.15 MW | 1.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958922 | AF2-183 E | Adder | 3.22 MW | 2.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 959102 | AF2-201 E O1 | Adder | 9.55 MW | 8.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 959351 | AF2-226 C | Adder | 1.42 MW | 1.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 959352 | AF2-226 E | Adder | 2.13 MW | 1.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 959611 | AF2-252 C | Adder | 1.27 MW | 1.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 959612 | AF2-252 E | Adder | 1.91 MW | 1.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960281 | AF2-319 C | Adder | 1.42 MW | 1.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960282 | AF2-319 E | Adder | 2.13 MW | 1.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960381 | AF2-329 | Adder | 3.02 MW | 2.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960601 | AF2-351 C O1 | Adder | 0.59 MW | 0.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960602 | AF2-351 E O1 | Adder | 0.88 MW | 0.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960611 | AF2-352 C | Adder | 1.27 MW | 1.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960612 | AF2-352 E | Adder | 1.91 MW | 1.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960851 | AF2-376 C | Adder | 1.78 MW | 1.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960852 | AF2-376 E | Adder | 2.67 MW | 2.27 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960861 | AF2-377 C | 50/50 | 2.09 MW | 2.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960862 | AF2-377 E | 50/50 | 3.13 MW | 3.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960971 | AF2-388 C | Adder | 2.51 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 960972 | AF2-388 E | Adder | 11.77 MW | 10.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961011 | AF2-392 C O1 | Adder | 1.88 MW | 1.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961012 | AF2-392 E O1 | Adder | 8.8 MW | 7.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961031 | AF2-394 O1 | Adder | 2.67 MW | 2.27 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 936291 | AD2-038 C O1 | Adder | 1.08 MW | 0.92 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 936292 | AD2-038 E O1 | Adder | 7.25 MW | 6.16 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939781 | AE1-209 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939782 | AE1-209 E O1 | Adder | 4.88 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939791 | AE1-210 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 939792 | AE1-210 E O1 | Adder | 4.88 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 941721 | AE2-172 | Adder | 2.83 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961161 | AF2-407 | Adder | 17.47 MW | 14.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961171 | AF2-408 | Adder | 4.61 MW | 3.92 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 247521 | T-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 247925 | T-131 E | 50/50 | 5.01 MW | 5.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 924261 | AB2-070 C O1 | Adder | 1.27 MW | 1.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 924262 | AB2-070 E O1 | Adder | 8.53 MW | 7.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 925302 | AB2-191 E | Adder | 0.64 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 925771 | AC1-053 C | Adder | 1.27 MW | 1.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 925772 | AC1-053 E | Adder | 8.5 MW | 7.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 926861 | AC1-173 C | 50/50 | 0.42 MW | 0.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 926862 | AC1-173 E | 50/50 | 2.82 MW | 2.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 938851 | AE1-113 C | Adder | 3.68 MW | 3.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 938852 | AE1-113 E | Adder | 13.04 MW | 11.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944221 | AF1-090 C O1 | Adder | 1.57 MW | 1.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 944222 | AF1-090 E O1 | Adder | 7.33 MW | 6.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945871 | AF1-252 O1 | Adder | 3.47 MW | 2.95 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945881 | AF1-253 O1 | Adder | 2.4 MW | 2.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946161 | AF1-281 C | Adder | 0.2 MW | 0.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946162 | AF1-281 E | Adder | 1.14 MW | 0.97 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946541 | AF1-318 C O1 | Adder | 2.83 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946542 | AF1-318 E O1 | Adder | 13.24 MW | 11.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958341 | AF2-128 C O1 | Adder | 0.75 MW | 0.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 958342 | AF2-128 E O1 | Adder | 3.51 MW | 2.99 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961021 | AF2-393 C | Adder | 3.67 MW | 3.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 961023 | AF2-393 E | Adder | 0.33 MW | 0.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 936722 | AD2-091 BAT | 50/50 | 7.16 MW | 7.16 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 942042 | AE2-216 BAT | 50/50 | 7.87 MW | 7.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 945351 | AF1-200 FTIR | Adder | 174.56 MW | 148.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B-A | 946203 | AF1-285 BAT | 50/50 | 2.65 MW | 2.65 MW |
| Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 1.88 MW | 1.88 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.29 MW | 0.29 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 1.23 MW | 1.23 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274856 | ECOGROVE ;U1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274857 | BIG SKY ;U1 | 50/50 | 1.29 MW | 1.29 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274858 | BIG SKY ;U2 | 50/50 | 1.29 MW | 1.29 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274859 | EASYR;U1 E | 50/50 | 5.17 MW | 5.17 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274860 | EASYR;U2 E | 50/50 | 5.17 MW | 5.17 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274861 | TOP CROP ;1U | 50/50 | 1.21 MW | 1.21 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274862 | TOP CROP ;2U | 50/50 | 2.35 MW | 2.35 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274863 | CAYUGA RI;1U | 50/50 | 1.95 MW | 1.95 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274864 | CAYUGA RI;2U | 50/50 | 1.95 MW | 1.95 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 2.39 MW | 2.39 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 2.75 MW | 2.75 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274879 | MINONK ;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274887 | PILOT HIL;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 275149 | KELLYCK ;1E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 276170 | Z1-108 E | 50/50 | 2.93 MW | 2.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290021 | O50 E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290051 | GSG-6; E | 50/50 | 4.93 MW | 4.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 11.46 MW | 11.46 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293061 | N-015 E | 50/50 | 7.52 MW | 7.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293644 | O22 E1 | 50/50 | 4.83 MW | 4.83 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293645 | O22 E2 | 50/50 | 9.39 MW | 9.39 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 294392 | P-010 E | 50/50 | 9.55 MW | 9.55 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 294763 | P-046 E | 50/50 | 4.41 MW | 4.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.45 MW | 0.45 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 295110 | SUBLETTE C | 50/50 | 0.2 MW | 0.2 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 295111 | SUBLETTE E | 50/50 | 1.43 MW | 1.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 916211 | Z1-072 E | Adder | 4.63 MW | 3.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 916221 | Z1-073 E | 50/50 | 2.54 MW | 2.54 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 917502 | Z2-087 E | 50/50 | 9.82 MW | 9.82 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 918052 | AA1-018 E OP | 50/50 | 7.75 MW | 7.75 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 920272 | AA2-123 E | 50/50 | 2.88 MW | 2.88 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 924041 | AB2-047 C O1 | 50/50 | 3.67 MW | 3.67 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 924042 | AB2-047 E O1 | 50/50 | 24.54 MW | 24.54 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 925581 | AC1-033 C | Adder | 1.34 MW | 1.14 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 925582 | AC1-033 E | Adder | 8.97 MW | 7.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 926821 | AC1-168 C O1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 926822 | AC1-168 E O1 | 50/50 | 7.39 MW | 7.39 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 927201 | AC1-214 C O1 | Adder | 1.96 MW | 1.67 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 6.24 MW | 5.3 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.12 MW | 0.12 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.52 MW | 0.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934721 | AD1-100 C | 50/50 | 22.84 MW | 22.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934722 | AD1-100 E | 50/50 | 106.59 MW | 106.59 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936371 | AD2-047 C O1 | 50/50 | 4.43 MW | 4.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936372 | AD2-047 E O1 | 50/50 | 21.64 MW | 21.64 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.39 MW | 2.39 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.54 MW | 9.54 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938861 | AE1-114 C O1 | 50/50 | 3.7 MW | 3.7 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938862 | AE1-114 E O1 | 50/50 | 12.61 MW | 12.61 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939321 | AE1-163 C O1 | 50/50 | 5.57 MW | 5.57 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939322 | AE1-163 E O1 | 50/50 | 34.19 MW | 34.19 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939401 | AE1-172 C O1 | 50/50 | 6.23 MW | 6.23 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939402 | AE1-172 E O1 | 50/50 | 29.23 MW | 29.23 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 941731 | AE2-173 O1 | 50/50 | 7.05 MW | 7.05 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942112 | AE2-223 E | 50/50 | 14.72 MW | 14.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942421 | AE2-255 C O1 | 50/50 | 2.85 MW | 2.85 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942422 | AE2-255 E O1 | 50/50 | 8.56 MW | 8.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942651 | AE2-281 C O1 | 50/50 | 0.8 MW | 0.8 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942652 | AE2-281 E O1 | 50/50 | 4.88 MW | 4.88 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943801 | AF1-048 C | 50/50 | 4.5 MW | 4.5 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943802 | AF1-048 E | 50/50 | 3.0 MW | 3.0 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 3.7 MW | 3.14 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 17.32 MW | 14.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946501 | AF1-314 C | 50/50 | 4.1 MW | 4.1 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946502 | AF1-314 E | 50/50 | 19.27 MW | 19.27 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957331 | AF2-027 C | 50/50 | 2.94 MW | 2.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957332 | AF2-027 E | 50/50 | 4.41 MW | 4.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957371 | AF2-031 C O1 | 50/50 | 1.1 MW | 1.1 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957372 | AF2-031 E O1 | 50/50 | 1.65 MW | 1.65 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957401 | AF2-034 C | 50/50 | 1.65 MW | 1.65 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957402 | AF2-034 E | 50/50 | 1.4 MW | 1.4 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957751 | AF2-069 C | Adder | 0.23 MW | 0.19 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957752 | AF2-069 E | Adder | 0.73 MW | 0.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957761 | AF2-070 C | Adder | 0.32 MW | 0.27 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957762 | AF2-070 E | Adder | 1.56 MW | 1.32 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958921 | AF2-183 C | 50/50 | 4.28 MW | 4.28 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958922 | AF2-183 E | 50/50 | 6.41 MW | 6.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959102 | AF2-201 E O1 | 50/50 | 19.29 MW | 19.29 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959351 | AF2-226 C | 50/50 | 2.96 MW | 2.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959352 | AF2-226 E | 50/50 | 4.44 MW | 4.44 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959611 | AF2-252 C | Adder | 2.37 MW | 2.01 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959612 | AF2-252 E | Adder | 3.55 MW | 3.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960281 | AF2-319 C | 50/50 | 2.96 MW | 2.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960282 | AF2-319 E | 50/50 | 4.44 MW | 4.44 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.33 MW | 6.33 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960601 | AF2-351 C O1 | 50/50 | 1.3 MW | 1.3 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960602 | AF2-351 E O1 | 50/50 | 1.96 MW | 1.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960611 | AF2-352 C | Adder | 2.37 MW | 2.01 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960612 | AF2-352 E | Adder | 3.55 MW | 3.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.72 MW | 3.16 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961012 | AF2-392 E O1 | 50/50 | 17.43 MW | 17.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961031 | AF2-394 O1 | Adder | 5.29 MW | 4.49 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936291 | AD2-038 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936292 | AD2-038 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274881 | PILOT HIL;1E | 50/50 | 9.13 MW | 9.13 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274888 | KELLYCK ;1U | 50/50 | 2.28 MW | 2.28 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274890 | CAYUG;1U E | 50/50 | 7.78 MW | 7.78 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274891 | CAYUG;2U E | 50/50 | 7.78 MW | 7.78 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 917501 | Z2-087 C | 50/50 | 1.47 MW | 1.47 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 918051 | AA1-018 C OP | 50/50 | 1.16 MW | 1.16 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 924261 | AB2-070 C O1 | Adder | 2.1 MW | 1.78 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 924262 | AB2-070 E O1 | Adder | 14.02 MW | 11.92 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 925301 | AB2-191 | 50/50 | 0.53 MW | 0.53 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 925302 | AB2-191 E | 50/50 | 1.31 MW | 1.31 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938851 | AE1-113 C | 50/50 | 7.53 MW | 7.53 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938852 | AE1-113 E | 50/50 | 26.7 MW | 26.7 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 940752 | AE2-062 E | 50/50 | 0.15 MW | 0.15 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946161 | AF1-281 C | 50/50 | 0.4 MW | 0.4 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946162 | AF1-281 E | 50/50 | 2.27 MW | 2.27 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 5.53 MW | 4.7 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 25.9 MW | 22.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 1.47 MW | 1.25 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 6.88 MW | 5.85 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961021 | AF2-393 C | 50/50 | 7.27 MW | 7.27 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961023 | AF2-393 E | Adder | 0.66 MW | 0.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 250.75 MW | 250.75 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.24 MW | 1.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 0.99 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.33 MW | 0.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.2 MW | 0.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.5 MW | 0.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.05 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.05 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.74 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 0.86 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 3.45 MW | 3.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 3.45 MW | 3.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 1.5 MW | 1.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.03 MW | 1.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 1.57 MW | 1.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.67 MW | 0.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.39 MW | 0.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.42 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.76 MW | 0.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 6.11 MW | 6.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 3.31 MW | 3.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 7.69 MW | 7.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 4.21 MW | 4.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 4.96 MW | 4.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.71 MW | 0.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.36 MW | 0.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.4 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 2.85 MW | 2.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 1.59 MW | 1.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 6.0 MW | 6.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 3.04 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 1.67 MW | 1.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.0 MW | 2.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 6.3 MW | 6.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 2.67 MW | 2.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 2.67 MW | 2.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 2.95 MW | 2.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.3 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 5.49 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 2.05 MW | 2.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 13.73 MW | 13.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 5.87 MW | 5.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.72 MW | 0.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 4.83 MW | 4.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.08 MW | 0.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 12.23 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 57.06 MW | 57.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 1.61 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 13.88 MW | 13.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 1.6 MW | 1.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 6.39 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 2.47 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 8.43 MW | 8.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 3.87 MW | 3.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 23.78 MW | 23.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 3.24 MW | 3.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 15.19 MW | 15.19 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 3.95 MW | 3.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.23 MW | 1.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 8.24 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 1.91 MW | 1.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 5.73 MW | 5.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.55 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 3.4 MW | 3.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 3.03 MW | 3.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.02 MW | 2.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 2.45 MW | 2.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 11.46 MW | 11.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 2.75 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 12.91 MW | 12.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 1.99 MW | 1.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.11 MW | 1.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 0.94 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.02 MW | 1.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 2.85 MW | 2.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 4.28 MW | 4.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 12.92 MW | 12.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 1.89 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 2.84 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.33 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 1.99 MW | 1.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 1.89 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 2.84 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 4.26 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.25 MW | 1.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.33 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 1.99 MW | 1.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 11.6 MW | 11.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 3.52 MW | 3.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.54 MW | 1.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 10.31 MW | 10.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.05 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 5.98 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 4.14 MW | 4.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 4.14 MW | 4.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 0.82 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.35 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 0.88 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.18 MW | 1.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 7.88 MW | 7.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 5.04 MW | 5.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 17.87 MW | 17.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.11 MW | 0.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.27 MW | 0.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.51 MW | 1.51 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 3.61 MW | 3.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 16.9 MW | 16.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 4.49 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 3.95 MW | 3.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 4.84 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 167.18 MW | 167.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954741 | J928 C | External Queue | 0.29 MW | 0.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954742 | J928 E | External Queue | 1.58 MW | 1.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 1.98 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916211 | Z1-072 E | Adder | 3.03 MW | 2.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 5.61 MW | 5.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924041 | AB2-047 C O1 | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924042 | AB2-047 E O1 | Adder | 13.72 MW | 11.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925581 | AC1-033 C | Adder | 0.88 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925582 | AC1-033 E | Adder | 5.87 MW | 4.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.28 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 4.08 MW | 3.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.08 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.35 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 12.22 MW | 10.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 57.04 MW | 48.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 935141 | AD1-148 | Adder | 1.61 MW | 1.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 2.84 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 13.88 MW | 13.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 8.44 MW | 7.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 3.87 MW | 3.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 23.77 MW | 20.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 15.18 MW | 12.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941731 | AE2-173 O1 | Adder | 3.94 MW | 3.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942111 | AE2-223 C | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942112 | AE2-223 E | Adder | 8.23 MW | 7.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.55 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 3.4 MW | 2.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.02 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 2.45 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 11.47 MW | 9.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 12.93 MW | 10.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 2.99 MW | 2.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957371 | AF2-031 C O1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957372 | AF2-031 E O1 | Adder | 0.94 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.11 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.94 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.02 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958921 | AF2-183 C | Adder | 2.86 MW | 2.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958922 | AF2-183 E | Adder | 4.28 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.94 MW | 11.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959611 | AF2-252 C | Adder | 1.33 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959612 | AF2-252 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.27 MW | 3.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | 50/50 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960611 | AF2-352 C | Adder | 1.33 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960612 | AF2-352 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 2.48 MW | 2.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961012 | AF2-392 E O1 | Adder | 11.62 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 3.52 MW | 3.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.54 MW | 1.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 10.31 MW | 8.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 1.19 MW | 1.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 0.88 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925771 | AC1-053 C | Adder | 1.18 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925772 | AC1-053 E | Adder | 7.87 MW | 6.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 5.04 MW | 4.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.11 MW | 0.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946161 | AF1-281 C | Adder | 0.27 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946162 | AF1-281 E | Adder | 1.52 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 3.61 MW | 3.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 16.91 MW | 14.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 4.49 MW | 3.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961021 | AF2-393 C | Adder | 4.85 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.44 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 247.05 MW | 209.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953202 | J715 E | External Queue | 4.48 MW | 4.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954741 | J928 C | External Queue | 0.69 MW | 0.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954742 | J928 E | External Queue | 3.76 MW | 3.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | 50/50 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 1.98 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916211 | Z1-072 E | Adder | 3.02 MW | 2.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | 50/50 | 5.61 MW | 5.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924041 | AB2-047 C O1 | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 13.73 MW | 11.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925581 | AC1-033 C | Adder | 0.88 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925582 | AC1-033 E | Adder | 5.87 MW | 4.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927201 | AC1-214 C O1 | Adder | 1.28 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 4.08 MW | 3.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.08 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.35 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 12.22 MW | 10.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 57.05 MW | 48.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 935141 | AD1-148 | Adder | 1.61 MW | 1.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | 50/50 | 2.84 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | 50/50 | 13.88 MW | 13.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 6.39 MW | 5.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 8.43 MW | 7.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 3.87 MW | 3.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 23.78 MW | 20.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 3.24 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 15.18 MW | 12.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941731 | AE2-173 O1 | Adder | 3.94 MW | 3.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942111 | AE2-223 C | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942112 | AE2-223 E | Adder | 8.24 MW | 7.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.55 MW | 0.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.4 MW | 2.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.02 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 2.45 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 11.46 MW | 9.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 12.91 MW | 10.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 2.99 MW | 2.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957371 | AF2-031 C O1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957372 | AF2-031 E O1 | Adder | 0.94 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.11 MW | 0.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.94 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957762 | AF2-070 E | Adder | 1.02 MW | 0.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958921 | AF2-183 C | Adder | 2.85 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958922 | AF2-183 E | Adder | 4.28 MW | 3.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 12.93 MW | 10.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959611 | AF2-252 C | Adder | 1.33 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959612 | AF2-252 E | Adder | 1.99 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.26 MW | 3.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | 50/50 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960611 | AF2-352 C | Adder | 1.33 MW | 1.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960612 | AF2-352 E | Adder | 1.99 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 2.48 MW | 2.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 11.61 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.52 MW | 2.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.54 MW | 1.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 10.31 MW | 8.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | 50/50 | 5.85 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274888 | KELLYCK ;1U | 50/50 | 1.46 MW | 1.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918051 | AA1-018 C OP | 50/50 | 0.84 MW | 0.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924261 | AB2-070 C O1 | Adder | 1.19 MW | 1.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924262 | AB2-070 E O1 | Adder | 7.95 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 0.88 MW | 0.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925771 | AC1-053 C | Adder | 1.18 MW | 1.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925772 | AC1-053 E | Adder | 7.88 MW | 6.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 5.04 MW | 4.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | 50/50 | 0.11 MW | 0.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946161 | AF1-281 C | Adder | 0.27 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946162 | AF1-281 E | Adder | 1.52 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 3.61 MW | 3.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 16.9 MW | 14.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 4.49 MW | 3.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961021 | AF2-393 C | Adder | 4.84 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961023 | AF2-393 E | Adder | 0.44 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 246.07 MW | 209.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953202 | J715 E | External Queue | 4.47 MW | 4.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954741 | J928 C | External Queue | 0.69 MW | 0.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954742 | J928 E | External Queue | 3.75 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.24 MW | 1.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 0.99 MW | 0.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.33 MW | 0.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.2 MW | 0.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.5 MW | 0.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.05 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.05 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.74 MW | 0.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 0.86 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 3.45 MW | 3.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 3.45 MW | 3.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 0.77 MW | 0.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 1.5 MW | 1.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.03 MW | 1.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 1.57 MW | 1.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.67 MW | 0.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.39 MW | 0.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 6.11 MW | 6.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 3.31 MW | 3.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 7.69 MW | 7.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 4.21 MW | 4.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 4.96 MW | 4.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.71 MW | 0.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.36 MW | 0.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.4 MW | 0.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 2.85 MW | 2.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 1.59 MW | 1.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 3.09 MW | 3.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 6.0 MW | 6.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 3.04 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 1.67 MW | 1.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.53 MW | 1.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.0 MW | 2.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 6.3 MW | 6.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 2.67 MW | 2.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 2.67 MW | 2.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 2.95 MW | 2.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.3 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 5.49 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 2.05 MW | 2.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 13.73 MW | 13.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 5.87 MW | 5.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.72 MW | 0.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 4.83 MW | 4.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 4.08 MW | 4.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.08 MW | 0.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 12.23 MW | 12.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 57.06 MW | 57.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 1.61 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 13.88 MW | 13.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 1.6 MW | 1.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 6.39 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 2.47 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 8.43 MW | 8.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 3.87 MW | 3.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 23.78 MW | 23.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 3.24 MW | 3.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 15.19 MW | 15.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 3.95 MW | 3.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.23 MW | 1.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 8.24 MW | 8.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 1.91 MW | 1.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 5.73 MW | 5.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.55 MW | 0.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 3.4 MW | 3.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 3.03 MW | 3.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.02 MW | 2.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 2.45 MW | 2.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 11.46 MW | 11.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 2.75 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 12.91 MW | 12.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 1.99 MW | 1.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 2.99 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.63 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.11 MW | 1.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 0.94 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.02 MW | 1.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 2.85 MW | 2.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 4.28 MW | 4.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 12.92 MW | 12.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 1.89 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 2.84 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.33 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 1.99 MW | 1.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 1.89 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 2.84 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 4.26 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.25 MW | 1.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.33 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 1.99 MW | 1.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 11.6 MW | 11.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 3.52 MW | 3.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.54 MW | 1.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 10.31 MW | 10.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.05 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 5.98 MW | 5.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 4.14 MW | 4.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 4.14 MW | 4.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 0.82 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 7.95 MW | 7.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.35 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 0.88 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.18 MW | 1.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 7.88 MW | 7.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 5.04 MW | 5.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 17.87 MW | 17.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.11 MW | 0.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.27 MW | 0.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.51 MW | 1.51 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 3.61 MW | 3.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 16.9 MW | 16.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 4.49 MW | 4.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 3.95 MW | 3.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 4.84 MW | 4.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 167.18 MW | 167.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954741 | J928 C | External Queue | 0.29 MW | 0.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954742 | J928 E | External Queue | 1.58 MW | 1.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 1.98 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916211 | Z1-072 E | Adder | 3.03 MW | 2.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 5.61 MW | 5.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924041 | AB2-047 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924042 | AB2-047 E O1 | Adder | 13.72 MW | 11.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925581 | AC1-033 C | Adder | 0.88 MW | 0.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925582 | AC1-033 E | Adder | 5.87 MW | 4.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.28 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 4.08 MW | 3.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.08 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.35 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 12.22 MW | 10.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 57.04 MW | 48.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 935141 | AD1-148 | Adder | 1.61 MW | 1.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 2.84 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 13.88 MW | 13.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 8.44 MW | 7.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 3.87 MW | 3.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 23.77 MW | 20.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 3.23 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 15.18 MW | 12.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941731 | AE2-173 O1 | Adder | 3.94 MW | 3.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942111 | AE2-223 C | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942112 | AE2-223 E | Adder | 8.23 MW | 7.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.55 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 3.4 MW | 2.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.04 MW | 2.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.02 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 2.45 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 11.47 MW | 9.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 12.93 MW | 10.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 2.99 MW | 2.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957371 | AF2-031 C O1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957372 | AF2-031 E O1 | Adder | 0.94 MW | 0.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.11 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.94 MW | 0.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.02 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958921 | AF2-183 C | Adder | 2.86 MW | 2.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958922 | AF2-183 E | Adder | 4.28 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.94 MW | 11.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959611 | AF2-252 C | Adder | 1.33 MW | 1.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959612 | AF2-252 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.27 MW | 3.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | 50/50 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960611 | AF2-352 C | Adder | 1.33 MW | 1.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960612 | AF2-352 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 2.48 MW | 2.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961012 | AF2-392 E O1 | Adder | 11.62 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 3.52 MW | 3.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.54 MW | 1.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 10.31 MW | 8.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 1.19 MW | 1.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 0.88 MW | 0.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925771 | AC1-053 C | Adder | 1.18 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925772 | AC1-053 E | Adder | 7.87 MW | 6.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 5.04 MW | 4.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.11 MW | 0.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946161 | AF1-281 C | Adder | 0.27 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946162 | AF1-281 E | Adder | 1.52 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 3.61 MW | 3.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 16.91 MW | 14.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 4.49 MW | 3.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961021 | AF2-393 C | Adder | 4.85 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.44 MW | 0.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 247.05 MW | 209.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953202 | J715 E | External Queue | 4.48 MW | 4.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954741 | J928 C | External Queue | 0.69 MW | 0.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954742 | J928 E | External Queue | 3.76 MW | 3.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274887 | PILOT HIL;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | 50/50 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 1.98 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916211 | Z1-072 E | Adder | 3.02 MW | 2.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | 50/50 | 5.61 MW | 5.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924041 | AB2-047 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 13.73 MW | 11.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925581 | AC1-033 C | Adder | 0.88 MW | 0.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925582 | AC1-033 E | Adder | 5.87 MW | 4.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926821 | AC1-168 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926822 | AC1-168 E O1 | Adder | 4.84 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927201 | AC1-214 C O1 | Adder | 1.28 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 4.08 MW | 3.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.08 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.35 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 12.22 MW | 10.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 57.05 MW | 48.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 935141 | AD1-148 | Adder | 1.61 MW | 1.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | 50/50 | 2.84 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | 50/50 | 13.88 MW | 13.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 1.6 MW | 1.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 6.39 MW | 5.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 8.43 MW | 7.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 3.87 MW | 3.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 23.78 MW | 20.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 3.24 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 15.18 MW | 12.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941731 | AE2-173 O1 | Adder | 3.94 MW | 3.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942111 | AE2-223 C | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942112 | AE2-223 E | Adder | 8.24 MW | 7.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 1.91 MW | 1.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 5.73 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.55 MW | 0.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.4 MW | 2.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.03 MW | 2.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.02 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 2.45 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 11.46 MW | 9.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 12.91 MW | 10.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 2.99 MW | 2.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957371 | AF2-031 C O1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957372 | AF2-031 E O1 | Adder | 0.94 MW | 0.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.11 MW | 0.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.94 MW | 0.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957762 | AF2-070 E | Adder | 1.02 MW | 0.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958921 | AF2-183 C | Adder | 2.85 MW | 2.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958922 | AF2-183 E | Adder | 4.28 MW | 3.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 12.93 MW | 10.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959611 | AF2-252 C | Adder | 1.33 MW | 1.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959612 | AF2-252 E | Adder | 1.99 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.89 MW | 1.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.84 MW | 2.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.26 MW | 3.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | 50/50 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | 50/50 | 1.25 MW | 1.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960611 | AF2-352 C | Adder | 1.33 MW | 1.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960612 | AF2-352 E | Adder | 1.99 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 2.48 MW | 2.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 11.61 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.52 MW | 2.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.54 MW | 1.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 10.31 MW | 8.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | 50/50 | 5.85 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274888 | KELLYCK ;1U | 50/50 | 1.46 MW | 1.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918051 | AA1-018 C OP | 50/50 | 0.84 MW | 0.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924261 | AB2-070 C O1 | Adder | 1.19 MW | 1.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924262 | AB2-070 E O1 | Adder | 7.95 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 0.88 MW | 0.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925771 | AC1-053 C | Adder | 1.18 MW | 1.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925772 | AC1-053 E | Adder | 7.88 MW | 6.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 5.04 MW | 4.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | 50/50 | 0.11 MW | 0.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946161 | AF1-281 C | Adder | 0.27 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946162 | AF1-281 E | Adder | 1.52 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 3.61 MW | 3.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 16.9 MW | 14.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 0.96 MW | 0.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 4.49 MW | 3.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961021 | AF2-393 C | Adder | 4.84 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961023 | AF2-393 E | Adder | 0.44 MW | 0.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 246.07 MW | 209.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953201 | J715 C | External Queue | 0.83 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953202 | J715 E | External Queue | 4.47 MW | 4.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954741 | J928 C | External Queue | 0.69 MW | 0.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954742 | J928 E | External Queue | 3.75 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 956141 | J1101 | External Queue | 1.15 MW | 1.15 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.58 MW | 1.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.41 MW | 0.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.63 MW | 0.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.31 MW | 1.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.31 MW | 1.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 4.37 MW | 4.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 4.37 MW | 4.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 1.18 MW | 1.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 2.29 MW | 2.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.28 MW | 1.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.28 MW | 1.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 2.33 MW | 2.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.85 MW | 0.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.85 MW | 0.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.98 MW | 1.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.49 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.53 MW | 0.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.96 MW | 0.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 7.9 MW | 7.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 4.17 MW | 4.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 9.7 MW | 9.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 5.22 MW | 5.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 5.22 MW | 5.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 6.3 MW | 6.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.9 MW | 0.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.46 MW | 0.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.51 MW | 0.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 3.6 MW | 3.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.83 MW | 1.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 4.73 MW | 4.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 9.18 MW | 9.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 2.11 MW | 2.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.94 MW | 1.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.52 MW | 2.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 8.01 MW | 8.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 3.38 MW | 3.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 3.38 MW | 3.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 3.74 MW | 3.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.38 MW | 0.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 6.82 MW | 6.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 2.55 MW | 2.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 17.05 MW | 17.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 1.11 MW | 1.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 7.42 MW | 7.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 6.11 MW | 6.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.62 MW | 1.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 5.15 MW | 5.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.1 MW | 0.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 15.25 MW | 15.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 71.16 MW | 71.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 3.17 MW | 3.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 15.47 MW | 15.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 8.06 MW | 8.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 3.13 MW | 3.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 10.67 MW | 10.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 28.18 MW | 28.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 18.83 MW | 18.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 4.9 MW | 4.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.53 MW | 1.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 10.23 MW | 10.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 2.47 MW | 2.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 4.03 MW | 4.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 3.84 MW | 3.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.56 MW | 2.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 3.1 MW | 3.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 14.5 MW | 14.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 3.48 MW | 3.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 16.34 MW | 16.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 2.52 MW | 2.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.6 MW | 0.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.28 MW | 1.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 3.61 MW | 3.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 5.42 MW | 5.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 16.35 MW | 16.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 4.35 MW | 4.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 2.47 MW | 2.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 4.35 MW | 4.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 5.34 MW | 5.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.4 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.65 MW | 1.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 2.47 MW | 2.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 14.69 MW | 14.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 4.46 MW | 4.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.82 MW | 1.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 12.22 MW | 12.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.3 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 5.14 MW | 5.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 5.14 MW | 5.14 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 1.02 MW | 1.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.45 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 1.1 MW | 1.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.46 MW | 1.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 9.76 MW | 9.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 23.11 MW | 23.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.13 MW | 0.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944221 | AF1-090 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944222 | AF1-090 E O1 | 80/20 | 6.65 MW | 6.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945871 | AF1-252 O1 | 80/20 | 3.15 MW | 3.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945881 | AF1-253 O1 | 80/20 | 2.18 MW | 2.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.34 MW | 0.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.92 MW | 1.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 4.55 MW | 4.55 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 21.29 MW | 21.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 5.65 MW | 5.65 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 5.0 MW | 5.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 6.13 MW | 6.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.56 MW | 0.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 210.55 MW | 210.55 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274847 | GR RIDGE ;BU | 50/50 | 1.58 MW | 1.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274850 | MENDOTA H;RU | 50/50 | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274855 | GSG-6 ;RU | 50/50 | 1.05 MW | 1.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 1.18 MW | 1.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 2.29 MW | 2.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274871 | GR RIDGE ;2U | 50/50 | 2.01 MW | 2.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274872 | LEE DEKAL;1U | 50/50 | 2.34 MW | 2.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274879 | MINONK ;1U | 50/50 | 1.98 MW | 1.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | 50/50 | 2.52 MW | 2.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | 50/50 | 7.91 MW | 7.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | 50/50 | 4.19 MW | 4.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | 50/50 | 9.76 MW | 9.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | 50/50 | 6.34 MW | 6.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 4.73 MW | 4.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 9.18 MW | 9.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | 50/50 | 8.05 MW | 8.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | 50/50 | 3.75 MW | 3.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295108 | WESTBROOK C | 50/50 | 0.38 MW | 0.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | 50/50 | 2.5 MW | 2.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916211 | Z1-072 E | Adder | 3.83 MW | 3.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | 50/50 | 2.16 MW | 2.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 6.16 MW | 6.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | 50/50 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924041 | AB2-047 C O1 | Adder | 2.54 MW | 2.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924042 | AB2-047 E O1 | Adder | 17.01 MW | 14.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925581 | AC1-033 C | Adder | 1.11 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925582 | AC1-033 E | Adder | 7.44 MW | 6.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926821 | AC1-168 C O1 | Adder | 0.91 MW | 0.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926822 | AC1-168 E O1 | Adder | 6.13 MW | 5.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.62 MW | 1.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.16 MW | 4.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | 50/50 | 0.1 MW | 0.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | 50/50 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | 50/50 | 15.22 MW | 15.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | 50/50 | 71.04 MW | 71.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 935141 | AD1-148 | Adder | 2.0 MW | 1.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | 50/50 | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | 50/50 | 8.11 MW | 8.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 3.14 MW | 2.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 10.72 MW | 9.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | 50/50 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | 50/50 | 28.17 MW | 28.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 4.0 MW | 3.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 18.78 MW | 15.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941731 | AE2-173 O1 | Adder | 4.89 MW | 4.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942111 | AE2-223 C | Adder | 1.53 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942112 | AE2-223 E | Adder | 10.21 MW | 8.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | 50/50 | 2.47 MW | 2.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | 50/50 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | 50/50 | 4.02 MW | 4.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | 50/50 | 3.85 MW | 3.85 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | 50/50 | 2.57 MW | 2.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 3.11 MW | 2.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 14.56 MW | 12.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | 50/50 | 3.49 MW | 3.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | 50/50 | 16.41 MW | 16.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | 50/50 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | 50/50 | 3.8 MW | 3.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957371 | AF2-031 C O1 | Adder | 0.49 MW | 0.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957372 | AF2-031 E O1 | Adder | 0.74 MW | 0.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | 50/50 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | 50/50 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.19 MW | 0.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.61 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.26 MW | 0.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.29 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958921 | AF2-183 C | Adder | 3.63 MW | 3.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958922 | AF2-183 E | Adder | 5.44 MW | 4.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | 50/50 | 16.43 MW | 16.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.34 MW | 4.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959611 | AF2-252 C | Adder | 1.65 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959612 | AF2-252 E | Adder | 2.47 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.34 MW | 4.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | 50/50 | 5.39 MW | 5.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.93 MW | 0.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.4 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960611 | AF2-352 C | Adder | 1.65 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960612 | AF2-352 E | Adder | 2.47 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 3.15 MW | 2.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961012 | AF2-392 E O1 | Adder | 14.75 MW | 12.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 4.47 MW | 3.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | 50/50 | 12.21 MW | 12.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 1.47 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 9.83 MW | 8.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925301 | AB2-191 | 50/50 | 0.45 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | 50/50 | 1.11 MW | 1.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925771 | AC1-053 C | Adder | 1.46 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925772 | AC1-053 E | Adder | 9.75 MW | 8.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | 50/50 | 23.12 MW | 23.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.13 MW | 0.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946161 | AF1-281 C | Adder | 0.34 MW | 0.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946162 | AF1-281 E | Adder | 1.93 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 4.56 MW | 3.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 21.33 MW | 18.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 1.21 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 5.66 MW | 4.81 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961021 | AF2-393 C | Adder | 6.15 MW | 5.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.56 MW | 0.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | 50/50 | 213.97 MW | 213.97 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950501 | J449 C | External Queue | 1.78 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950502 | J449 E | External Queue | 7.13 MW | 7.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952022 | J614 E | External Queue | 2.94 MW | 2.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953201 | J715 C | External Queue | 1.07 MW | 1.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953202 | J715 E | External Queue | 5.77 MW | 5.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954511 | J926 C | External Queue | 0.88 MW | 0.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954512 | J926 E | External Queue | 4.76 MW | 4.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954702 | J844 E | External Queue | 8.73 MW | 8.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954741 | J928 C | External Queue | 0.9 MW | 0.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954742 | J928 E | External Queue | 4.89 MW | 4.89 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954931 | J967 C | External Queue | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954932 | J967 E | External Queue | 6.6 MW | 6.6 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956141 | J1101 | External Queue | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954981 | J974 C | External Queue | 2.27 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954982 | J974 E | External Queue | 12.31 MW | 12.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956832 | J1181 E | External Queue | 10.42 MW | 10.42 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274847 | GR RIDGE ;BU | 50/50 | 1.58 MW | 1.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274850 | MENDOTA H;RU | 50/50 | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274855 | GSG-6 ;RU | 50/50 | 1.04 MW | 1.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.94 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 1.18 MW | 1.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 2.29 MW | 2.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274871 | GR RIDGE ;2U | 50/50 | 2.0 MW | 2.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274872 | LEE DEKAL;1U | 50/50 | 2.33 MW | 2.33 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274879 | MINONK ;1U | 50/50 | 1.98 MW | 1.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274887 | PILOT HIL;1U | 50/50 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | 50/50 | 2.51 MW | 2.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | 50/50 | 7.9 MW | 7.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | 50/50 | 4.17 MW | 4.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | 50/50 | 9.71 MW | 9.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | 50/50 | 6.31 MW | 6.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 4.73 MW | 4.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 9.18 MW | 9.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | 50/50 | 8.01 MW | 8.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | 50/50 | 3.74 MW | 3.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295108 | WESTBROOK C | 50/50 | 0.38 MW | 0.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | 50/50 | 2.49 MW | 2.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295110 | SUBLETTE C | 50/50 | 0.17 MW | 0.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | 50/50 | 1.21 MW | 1.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916211 | Z1-072 E | Adder | 3.82 MW | 3.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | 50/50 | 2.15 MW | 2.15 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | 50/50 | 6.17 MW | 6.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | 50/50 | 2.46 MW | 2.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924041 | AB2-047 C O1 | Adder | 2.55 MW | 2.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924042 | AB2-047 E O1 | Adder | 17.05 MW | 14.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925581 | AC1-033 C | Adder | 1.11 MW | 0.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925582 | AC1-033 E | Adder | 7.43 MW | 6.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926821 | AC1-168 C O1 | Adder | 0.91 MW | 0.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926822 | AC1-168 E O1 | Adder | 6.11 MW | 5.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927201 | AC1-214 C O1 | Adder | 1.62 MW | 1.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927202 | AC1-214 E O1 | Adder | 5.15 MW | 4.38 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | 50/50 | 0.1 MW | 0.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | 50/50 | 0.44 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | 50/50 | 15.23 MW | 15.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | 50/50 | 71.09 MW | 71.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 935141 | AD1-148 | Adder | 2.0 MW | 1.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | 50/50 | 2.02 MW | 2.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | 50/50 | 8.07 MW | 8.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.13 MW | 2.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.68 MW | 9.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | 50/50 | 4.59 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | 50/50 | 28.19 MW | 28.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 4.01 MW | 3.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 18.82 MW | 15.99 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941731 | AE2-173 O1 | Adder | 4.9 MW | 4.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942111 | AE2-223 C | Adder | 1.53 MW | 1.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942112 | AE2-223 E | Adder | 10.23 MW | 8.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | 50/50 | 2.47 MW | 2.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | 50/50 | 0.66 MW | 0.66 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | 50/50 | 4.03 MW | 4.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | 50/50 | 3.84 MW | 3.84 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | 50/50 | 2.56 MW | 2.56 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946321 | AF1-296 C O1 | Adder | 3.1 MW | 2.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946322 | AF1-296 E O1 | Adder | 14.52 MW | 12.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | 50/50 | 3.48 MW | 3.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | 50/50 | 16.35 MW | 16.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | 50/50 | 2.53 MW | 2.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | 50/50 | 3.79 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957371 | AF2-031 C O1 | Adder | 0.49 MW | 0.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957372 | AF2-031 E O1 | Adder | 0.74 MW | 0.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | 50/50 | 1.47 MW | 1.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | 50/50 | 1.25 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957751 | AF2-069 C | Adder | 0.19 MW | 0.16 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957752 | AF2-069 E | Adder | 0.61 MW | 0.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957761 | AF2-070 C | Adder | 0.26 MW | 0.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957762 | AF2-070 E | Adder | 1.28 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958921 | AF2-183 C | Adder | 3.61 MW | 3.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958922 | AF2-183 E | Adder | 5.42 MW | 4.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | 50/50 | 16.37 MW | 16.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.35 MW | 4.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959611 | AF2-252 C | Adder | 1.65 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959612 | AF2-252 E | Adder | 2.47 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 2.9 MW | 2.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.35 MW | 4.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | 50/50 | 5.35 MW | 5.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.93 MW | 0.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.4 MW | 1.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960611 | AF2-352 C | Adder | 1.65 MW | 1.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960612 | AF2-352 E | Adder | 2.47 MW | 2.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961011 | AF2-392 C O1 | Adder | 3.14 MW | 2.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961012 | AF2-392 E O1 | Adder | 14.7 MW | 12.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961031 | AF2-394 O1 | Adder | 4.46 MW | 3.79 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | 50/50 | 12.22 MW | 12.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274888 | KELLYCK ;1U | 50/50 | 1.63 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918051 | AA1-018 C OP | 50/50 | 0.92 MW | 0.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924261 | AB2-070 C O1 | Adder | 1.47 MW | 1.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924262 | AB2-070 E O1 | Adder | 9.85 MW | 8.37 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925301 | AB2-191 | 50/50 | 0.45 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | 50/50 | 1.11 MW | 1.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925771 | AC1-053 C | Adder | 1.46 MW | 1.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925772 | AC1-053 E | Adder | 9.76 MW | 8.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | 50/50 | 6.52 MW | 6.52 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | 50/50 | 23.12 MW | 23.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | 50/50 | 0.13 MW | 0.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946161 | AF1-281 C | Adder | 0.34 MW | 0.29 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946162 | AF1-281 E | Adder | 1.92 MW | 1.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946541 | AF1-318 C O1 | Adder | 4.55 MW | 3.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946542 | AF1-318 E O1 | Adder | 21.3 MW | 18.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958341 | AF2-128 C O1 | Adder | 1.21 MW | 1.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958342 | AF2-128 E O1 | Adder | 5.66 MW | 4.81 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961021 | AF2-393 C | Adder | 6.13 MW | 5.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961023 | AF2-393 E | Adder | 0.56 MW | 0.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | 50/50 | 211.04 MW | 211.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 950501 | J449 C | External Queue | 1.78 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 950502 | J449 E | External Queue | 7.11 MW | 7.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 952022 | J614 E | External Queue | 2.93 MW | 2.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 953201 | J715 C | External Queue | 1.06 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 953202 | J715 E | External Queue | 5.76 MW | 5.76 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954511 | J926 C | External Queue | 0.88 MW | 0.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954512 | J926 E | External Queue | 4.74 MW | 4.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954702 | J844 E | External Queue | 8.73 MW | 8.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954741 | J928 C | External Queue | 0.9 MW | 0.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954742 | J928 E | External Queue | 4.88 MW | 4.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954931 | J967 C | External Queue | 1.22 MW | 1.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954932 | J967 E | External Queue | 6.58 MW | 6.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 956141 | J1101 | External Queue | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954981 | J974 C | External Queue | 2.28 MW | 2.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954982 | J974 E | External Queue | 12.32 MW | 12.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 956832 | J1181 E | External Queue | 10.39 MW | 10.39 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.58 MW | 1.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.41 MW | 0.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.63 MW | 0.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.31 MW | 1.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.31 MW | 1.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.93 MW | 0.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 1.09 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 1.09 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 2.29 MW | 2.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.28 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.28 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.85 MW | 0.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.85 MW | 0.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.98 MW | 1.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.49 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.96 MW | 0.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 7.9 MW | 7.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 4.17 MW | 4.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 9.7 MW | 9.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 5.22 MW | 5.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 5.22 MW | 5.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 6.3 MW | 6.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.46 MW | 0.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.51 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 3.6 MW | 3.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.83 MW | 1.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 4.73 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 9.18 MW | 9.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 2.11 MW | 2.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.94 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.52 MW | 2.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 8.01 MW | 8.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 3.38 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 3.38 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 3.74 MW | 3.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.38 MW | 0.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 6.82 MW | 6.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 2.55 MW | 2.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 17.05 MW | 17.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 1.11 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 7.42 MW | 7.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 6.11 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.62 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 5.15 MW | 5.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 15.25 MW | 15.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 71.16 MW | 71.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 3.17 MW | 3.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 15.47 MW | 15.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 8.06 MW | 8.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 3.13 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 10.67 MW | 10.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 28.18 MW | 28.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 18.83 MW | 18.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 4.9 MW | 4.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.53 MW | 1.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 10.23 MW | 10.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 2.47 MW | 2.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 4.03 MW | 4.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 3.84 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.56 MW | 2.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 3.1 MW | 3.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 14.5 MW | 14.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 3.48 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 16.34 MW | 16.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 2.52 MW | 2.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 0.74 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.19 MW | 0.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.6 MW | 0.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.28 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 3.61 MW | 3.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 5.42 MW | 5.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 16.35 MW | 16.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 4.35 MW | 4.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 2.47 MW | 2.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 4.35 MW | 4.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 5.34 MW | 5.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.4 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.65 MW | 1.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 2.47 MW | 2.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 14.69 MW | 14.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.82 MW | 1.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 12.22 MW | 12.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.3 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 5.14 MW | 5.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 5.14 MW | 5.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 1.02 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.45 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 1.1 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.46 MW | 1.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 9.76 MW | 9.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 23.11 MW | 23.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944221 | AF1-090 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944222 | AF1-090 E O1 | 80/20 | 6.65 MW | 6.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945871 | AF1-252 O1 | 80/20 | 3.15 MW | 3.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945881 | AF1-253 O1 | 80/20 | 2.18 MW | 2.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.34 MW | 0.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.92 MW | 1.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 4.55 MW | 4.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 21.29 MW | 21.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 5.65 MW | 5.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 5.0 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 6.13 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.56 MW | 0.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 210.55 MW | 210.55 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274847 | GR RIDGE ;BU | 50/50 | 1.58 MW | 1.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274850 | MENDOTA H;RU | 50/50 | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274855 | GSG-6 ;RU | 50/50 | 1.05 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 2.29 MW | 2.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274871 | GR RIDGE ;2U | 50/50 | 2.01 MW | 2.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274872 | LEE DEKAL;1U | 50/50 | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274879 | MINONK ;1U | 50/50 | 1.98 MW | 1.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | 50/50 | 2.52 MW | 2.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | 50/50 | 7.91 MW | 7.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | 50/50 | 4.19 MW | 4.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | 50/50 | 9.76 MW | 9.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | 50/50 | 6.34 MW | 6.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 4.73 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 9.18 MW | 9.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | 50/50 | 8.05 MW | 8.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | 50/50 | 3.75 MW | 3.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295108 | WESTBROOK C | 50/50 | 0.38 MW | 0.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | 50/50 | 2.5 MW | 2.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916211 | Z1-072 E | Adder | 3.83 MW | 3.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | 50/50 | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | 50/50 | 6.16 MW | 6.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | 50/50 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924041 | AB2-047 C O1 | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924042 | AB2-047 E O1 | Adder | 17.01 MW | 14.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925581 | AC1-033 C | Adder | 1.11 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925582 | AC1-033 E | Adder | 7.44 MW | 6.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926821 | AC1-168 C O1 | Adder | 0.91 MW | 0.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926822 | AC1-168 E O1 | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.62 MW | 1.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.16 MW | 4.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | 50/50 | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | 50/50 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | 50/50 | 15.22 MW | 15.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | 50/50 | 71.04 MW | 71.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 935141 | AD1-148 | Adder | 2.0 MW | 1.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | 50/50 | 2.03 MW | 2.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | 50/50 | 8.11 MW | 8.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 3.14 MW | 2.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 10.72 MW | 9.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | 50/50 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | 50/50 | 28.17 MW | 28.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 4.0 MW | 3.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 18.78 MW | 15.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941731 | AE2-173 O1 | Adder | 4.89 MW | 4.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942111 | AE2-223 C | Adder | 1.53 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942112 | AE2-223 E | Adder | 10.21 MW | 8.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | 50/50 | 2.47 MW | 2.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | 50/50 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | 50/50 | 4.02 MW | 4.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | 50/50 | 3.85 MW | 3.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | 50/50 | 2.57 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 3.11 MW | 2.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 14.56 MW | 12.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | 50/50 | 3.49 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | 50/50 | 16.41 MW | 16.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | 50/50 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | 50/50 | 3.8 MW | 3.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957371 | AF2-031 C O1 | Adder | 0.49 MW | 0.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957372 | AF2-031 E O1 | Adder | 0.74 MW | 0.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | 50/50 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | 50/50 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.19 MW | 0.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.61 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.26 MW | 0.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.29 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958921 | AF2-183 C | Adder | 3.63 MW | 3.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958922 | AF2-183 E | Adder | 5.44 MW | 4.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | 50/50 | 16.43 MW | 16.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.34 MW | 4.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959611 | AF2-252 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959612 | AF2-252 E | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.34 MW | 4.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | 50/50 | 5.39 MW | 5.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.4 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960611 | AF2-352 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960612 | AF2-352 E | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 3.15 MW | 2.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961012 | AF2-392 E O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 4.47 MW | 3.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | 50/50 | 12.21 MW | 12.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918051 | AA1-018 C OP | 50/50 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 9.83 MW | 8.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925301 | AB2-191 | 50/50 | 0.45 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | 50/50 | 1.11 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925771 | AC1-053 C | Adder | 1.46 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925772 | AC1-053 E | Adder | 9.75 MW | 8.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | 50/50 | 23.12 MW | 23.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | 50/50 | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946161 | AF1-281 C | Adder | 0.34 MW | 0.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946162 | AF1-281 E | Adder | 1.93 MW | 1.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 4.56 MW | 3.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 21.33 MW | 18.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 1.21 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 5.66 MW | 4.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961021 | AF2-393 C | Adder | 6.15 MW | 5.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.56 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | 50/50 | 213.97 MW | 213.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950501 | J449 C | External Queue | 1.78 MW | 1.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950502 | J449 E | External Queue | 7.13 MW | 7.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952022 | J614 E | External Queue | 2.94 MW | 2.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953201 | J715 C | External Queue | 1.07 MW | 1.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953202 | J715 E | External Queue | 5.77 MW | 5.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954511 | J926 C | External Queue | 0.88 MW | 0.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954512 | J926 E | External Queue | 4.76 MW | 4.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954702 | J844 E | External Queue | 8.73 MW | 8.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954741 | J928 C | External Queue | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954742 | J928 E | External Queue | 4.89 MW | 4.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954931 | J967 C | External Queue | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954932 | J967 E | External Queue | 6.6 MW | 6.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956141 | J1101 | External Queue | 1.49 MW | 1.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954981 | J974 C | External Queue | 2.27 MW | 2.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954982 | J974 E | External Queue | 12.31 MW | 12.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956832 | J1181 E | External Queue | 10.42 MW | 10.42 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274847 | GR RIDGE ;BU | 50/50 | 1.58 MW | 1.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274850 | MENDOTA H;RU | 50/50 | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274855 | GSG-6 ;RU | 50/50 | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.94 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 2.29 MW | 2.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274871 | GR RIDGE ;2U | 50/50 | 2.0 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274872 | LEE DEKAL;1U | 50/50 | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274879 | MINONK ;1U | 50/50 | 1.98 MW | 1.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274887 | PILOT HIL;1U | 50/50 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | 50/50 | 2.51 MW | 2.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | 50/50 | 7.9 MW | 7.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | 50/50 | 4.17 MW | 4.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | 50/50 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | 50/50 | 6.31 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 4.73 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 9.18 MW | 9.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | 50/50 | 8.01 MW | 8.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | 50/50 | 3.74 MW | 3.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295108 | WESTBROOK C | 50/50 | 0.38 MW | 0.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | 50/50 | 2.49 MW | 2.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295110 | SUBLETTE C | 50/50 | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | 50/50 | 1.21 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916211 | Z1-072 E | Adder | 3.82 MW | 3.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | 50/50 | 2.15 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | 50/50 | 6.17 MW | 6.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | 50/50 | 2.46 MW | 2.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924041 | AB2-047 C O1 | Adder | 2.55 MW | 2.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924042 | AB2-047 E O1 | Adder | 17.05 MW | 14.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925581 | AC1-033 C | Adder | 1.11 MW | 0.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925582 | AC1-033 E | Adder | 7.43 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926821 | AC1-168 C O1 | Adder | 0.91 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926822 | AC1-168 E O1 | Adder | 6.11 MW | 5.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927201 | AC1-214 C O1 | Adder | 1.62 MW | 1.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927202 | AC1-214 E O1 | Adder | 5.15 MW | 4.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | 50/50 | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | 50/50 | 0.44 MW | 0.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | 50/50 | 15.23 MW | 15.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | 50/50 | 71.09 MW | 71.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 935141 | AD1-148 | Adder | 2.0 MW | 1.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | 50/50 | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | 50/50 | 8.07 MW | 8.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.13 MW | 2.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.68 MW | 9.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | 50/50 | 4.59 MW | 4.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | 50/50 | 28.19 MW | 28.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 4.01 MW | 3.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 18.82 MW | 15.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941731 | AE2-173 O1 | Adder | 4.9 MW | 4.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942111 | AE2-223 C | Adder | 1.53 MW | 1.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942112 | AE2-223 E | Adder | 10.23 MW | 8.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | 50/50 | 2.47 MW | 2.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | 50/50 | 0.66 MW | 0.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | 50/50 | 4.03 MW | 4.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | 50/50 | 3.84 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | 50/50 | 2.56 MW | 2.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946321 | AF1-296 C O1 | Adder | 3.1 MW | 2.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946322 | AF1-296 E O1 | Adder | 14.52 MW | 12.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | 50/50 | 3.48 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | 50/50 | 16.35 MW | 16.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | 50/50 | 2.53 MW | 2.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | 50/50 | 3.79 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957371 | AF2-031 C O1 | Adder | 0.49 MW | 0.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957372 | AF2-031 E O1 | Adder | 0.74 MW | 0.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | 50/50 | 1.47 MW | 1.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | 50/50 | 1.25 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957751 | AF2-069 C | Adder | 0.19 MW | 0.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957752 | AF2-069 E | Adder | 0.61 MW | 0.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957761 | AF2-070 C | Adder | 0.26 MW | 0.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957762 | AF2-070 E | Adder | 1.28 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958921 | AF2-183 C | Adder | 3.61 MW | 3.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958922 | AF2-183 E | Adder | 5.42 MW | 4.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | 50/50 | 16.37 MW | 16.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.35 MW | 4.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959611 | AF2-252 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959612 | AF2-252 E | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 2.9 MW | 2.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.35 MW | 4.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | 50/50 | 5.35 MW | 5.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.4 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960611 | AF2-352 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960612 | AF2-352 E | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961011 | AF2-392 C O1 | Adder | 3.14 MW | 2.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961012 | AF2-392 E O1 | Adder | 14.7 MW | 12.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961031 | AF2-394 O1 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | 50/50 | 12.22 MW | 12.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274888 | KELLYCK ;1U | 50/50 | 1.63 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918051 | AA1-018 C OP | 50/50 | 0.92 MW | 0.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924261 | AB2-070 C O1 | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 924262 | AB2-070 E O1 | Adder | 9.85 MW | 8.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925301 | AB2-191 | 50/50 | 0.45 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | 50/50 | 1.11 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925771 | AC1-053 C | Adder | 1.46 MW | 1.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925772 | AC1-053 E | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | 50/50 | 23.12 MW | 23.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | 50/50 | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946161 | AF1-281 C | Adder | 0.34 MW | 0.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946162 | AF1-281 E | Adder | 1.92 MW | 1.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946541 | AF1-318 C O1 | Adder | 4.55 MW | 3.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946542 | AF1-318 E O1 | Adder | 21.3 MW | 18.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958341 | AF2-128 C O1 | Adder | 1.21 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958342 | AF2-128 E O1 | Adder | 5.66 MW | 4.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961021 | AF2-393 C | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 961023 | AF2-393 E | Adder | 0.56 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | 50/50 | 211.04 MW | 211.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 950501 | J449 C | External Queue | 1.78 MW | 1.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 950502 | J449 E | External Queue | 7.11 MW | 7.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 952022 | J614 E | External Queue | 2.93 MW | 2.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 953201 | J715 C | External Queue | 1.06 MW | 1.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 953202 | J715 E | External Queue | 5.76 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954511 | J926 C | External Queue | 0.88 MW | 0.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954512 | J926 E | External Queue | 4.74 MW | 4.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954702 | J844 E | External Queue | 8.73 MW | 8.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954741 | J928 C | External Queue | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954742 | J928 E | External Queue | 4.88 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954931 | J967 C | External Queue | 1.22 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954932 | J967 E | External Queue | 6.58 MW | 6.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 956141 | J1101 | External Queue | 1.49 MW | 1.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954981 | J974 C | External Queue | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 954982 | J974 E | External Queue | 12.32 MW | 12.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 956832 | J1181 E | External Queue | 10.39 MW | 10.39 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.74 MW | 1.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 1.44 MW | 1.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.47 MW | 0.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.28 MW | 0.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.72 MW | 0.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.59 MW | 1.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.59 MW | 1.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 1.19 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 1.06 MW | 1.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 1.24 MW | 1.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 1.24 MW | 1.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 4.97 MW | 4.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 4.97 MW | 4.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 1.18 MW | 1.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 2.3 MW | 2.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 2.65 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.97 MW | 0.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.97 MW | 0.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 8.9 MW | 8.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.56 MW | 0.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 1.1 MW | 1.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 8.79 MW | 8.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 4.75 MW | 4.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 11.04 MW | 11.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 6.36 MW | 6.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 6.36 MW | 6.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 6.97 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.52 MW | 0.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 4.11 MW | 4.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 2.09 MW | 2.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 2.3 MW | 2.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 4.73 MW | 4.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 9.19 MW | 9.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 4.39 MW | 4.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.89 MW | 2.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 8.85 MW | 8.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 3.88 MW | 3.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 3.88 MW | 3.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 4.25 MW | 4.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.43 MW | 0.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.19 MW | 0.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 8.16 MW | 8.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 3.05 MW | 3.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 20.39 MW | 20.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 1.27 MW | 1.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 8.5 MW | 8.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 6.95 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 5.9 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.12 MW | 0.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 17.82 MW | 17.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 83.17 MW | 83.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 2.49 MW | 2.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 21.11 MW | 21.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 2.3 MW | 2.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 9.18 MW | 9.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 3.56 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 12.13 MW | 12.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 5.33 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 32.73 MW | 32.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 22.45 MW | 22.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 5.86 MW | 5.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.83 MW | 1.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 12.24 MW | 12.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 8.24 MW | 8.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 4.68 MW | 4.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 4.34 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.9 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 16.6 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 3.95 MW | 3.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 18.55 MW | 18.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 4.27 MW | 4.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 1.36 MW | 1.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.21 MW | 0.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.47 MW | 1.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 4.11 MW | 4.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 6.17 MW | 6.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 18.58 MW | 18.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 2.9 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 3.01 MW | 3.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 2.9 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 1.27 MW | 1.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.91 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 3.01 MW | 3.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 16.73 MW | 16.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 5.08 MW | 5.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 14.19 MW | 14.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.61 MW | 1.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 8.9 MW | 8.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 9.19 MW | 9.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 1.22 MW | 1.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 1.11 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.83 MW | 1.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 12.23 MW | 12.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.81 MW | 1.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 12.13 MW | 12.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 7.25 MW | 7.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 25.71 MW | 25.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.15 MW | 0.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944221 | AF1-090 C O1 | 80/20 | 1.84 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 944222 | AF1-090 E O1 | 80/20 | 8.62 MW | 8.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945871 | AF1-252 O1 | 80/20 | 4.08 MW | 4.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945881 | AF1-253 O1 | 80/20 | 2.82 MW | 2.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 2.18 MW | 2.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 5.21 MW | 5.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 24.42 MW | 24.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 1.39 MW | 1.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 6.49 MW | 6.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 5.74 MW | 5.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957382 | AF2-032 E | 80/20 | 0.15 MW | 0.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 6.98 MW | 6.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.64 MW | 0.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 239.51 MW | 239.51 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274887 | PILOT HIL;1U | 50/50 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | 50/50 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.83 MW | 2.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916211 | Z1-072 E | Adder | 4.37 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.78 MW | 2.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924041 | AB2-047 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 20.4 MW | 17.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925581 | AC1-033 C | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925582 | AC1-033 E | Adder | 8.49 MW | 7.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926821 | AC1-168 C O1 | Adder | 1.03 MW | 0.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926822 | AC1-168 E O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927201 | AC1-214 C O1 | Adder | 1.85 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.9 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.12 MW | 0.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.5 MW | 0.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 17.84 MW | 15.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 83.26 MW | 70.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 935141 | AD1-148 | Adder | 2.49 MW | 2.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 4.32 MW | 3.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 21.12 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.29 MW | 1.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 9.17 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.55 MW | 3.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 12.12 MW | 10.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.33 MW | 4.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 32.72 MW | 27.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 4.79 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 22.47 MW | 19.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941731 | AE2-173 O1 | Adder | 5.86 MW | 4.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942111 | AE2-223 C | Adder | 1.83 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942112 | AE2-223 E | Adder | 12.24 MW | 10.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.75 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 8.24 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.76 MW | 0.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.67 MW | 3.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 4.34 MW | 3.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.89 MW | 2.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.54 MW | 3.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.58 MW | 14.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.94 MW | 3.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 18.53 MW | 15.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.84 MW | 2.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 4.26 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957371 | AF2-031 C O1 | 50/50 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957372 | AF2-031 E O1 | 50/50 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.6 MW | 1.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957752 | AF2-069 E | Adder | 0.69 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957761 | AF2-070 C | Adder | 0.3 MW | 0.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957762 | AF2-070 E | Adder | 1.47 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958921 | AF2-183 C | Adder | 4.11 MW | 3.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958922 | AF2-183 E | Adder | 6.16 MW | 5.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 18.55 MW | 15.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 4.35 MW | 3.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959611 | AF2-252 C | Adder | 2.01 MW | 1.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959612 | AF2-252 E | Adder | 3.01 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 4.35 MW | 3.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 6.09 MW | 5.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.91 MW | 1.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960611 | AF2-352 C | Adder | 2.01 MW | 1.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960612 | AF2-352 E | Adder | 3.01 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.57 MW | 3.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.71 MW | 14.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961031 | AF2-394 O1 | Adder | 5.07 MW | 4.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.12 MW | 1.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 14.19 MW | 12.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | 50/50 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274888 | KELLYCK ;1U | 50/50 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924261 | AB2-070 C O1 | Adder | 1.83 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 924262 | AB2-070 E O1 | Adder | 12.23 MW | 10.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.26 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925771 | AC1-053 C | Adder | 1.81 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925772 | AC1-053 E | Adder | 12.13 MW | 10.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 7.25 MW | 6.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 25.7 MW | 21.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 944221 | AF1-090 C O1 | Adder | 1.84 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 944222 | AF1-090 E O1 | Adder | 8.62 MW | 7.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945871 | AF1-252 O1 | Adder | 4.08 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945881 | AF1-253 O1 | Adder | 2.82 MW | 2.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946161 | AF1-281 C | Adder | 0.38 MW | 0.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946162 | AF1-281 E | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 5.21 MW | 4.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 24.4 MW | 20.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.38 MW | 1.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 6.48 MW | 5.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957382 | AF2-032 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961021 | AF2-393 C | Adder | 6.97 MW | 5.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 961023 | AF2-393 E | Adder | 0.63 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 351.19 MW | 298.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950501 | J449 C | External Queue | 2.09 MW | 2.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 950502 | J449 E | External Queue | 8.35 MW | 8.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 952022 | J614 E | External Queue | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953201 | J715 C | External Queue | 1.09 MW | 1.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953202 | J715 E | External Queue | 5.9 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954511 | J926 C | External Queue | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954512 | J926 E | External Queue | 4.73 MW | 4.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954702 | J844 E | External Queue | 8.77 MW | 8.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954741 | J928 C | External Queue | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954742 | J928 E | External Queue | 4.94 MW | 4.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954931 | J967 C | External Queue | 1.21 MW | 1.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954932 | J967 E | External Queue | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 956141 | J1101 | External Queue | 1.51 MW | 1.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953921 | J855 C | External Queue | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 953922 | J855 E | External Queue | 4.3 MW | 4.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954981 | J974 C | External Queue | 2.28 MW | 2.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 954982 | J974 E | External Queue | 12.34 MW | 12.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 956832 | J1181 E | External Queue | 10.34 MW | 10.34 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274887 | PILOT HIL;1U | 50/50 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | 50/50 | 8.9 MW | 8.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.83 MW | 2.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916211 | Z1-072 E | Adder | 4.37 MW | 3.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.77 MW | 2.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924041 | AB2-047 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924042 | AB2-047 E O1 | Adder | 20.41 MW | 17.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925581 | AC1-033 C | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925582 | AC1-033 E | Adder | 8.49 MW | 7.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926821 | AC1-168 C O1 | Adder | 1.03 MW | 0.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926822 | AC1-168 E O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.85 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.89 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.12 MW | 0.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.5 MW | 0.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 17.84 MW | 15.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 83.24 MW | 70.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 935141 | AD1-148 | Adder | 2.49 MW | 2.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 4.32 MW | 3.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 21.11 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.29 MW | 1.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 9.15 MW | 7.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 3.55 MW | 3.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 12.11 MW | 10.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.33 MW | 4.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 32.74 MW | 27.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 4.79 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 22.48 MW | 19.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941731 | AE2-173 O1 | Adder | 5.87 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942111 | AE2-223 C | Adder | 1.83 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942112 | AE2-223 E | Adder | 12.25 MW | 10.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 2.75 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 8.24 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.76 MW | 0.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 4.33 MW | 3.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.89 MW | 2.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 3.54 MW | 3.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 16.57 MW | 14.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 3.94 MW | 3.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 18.52 MW | 15.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.84 MW | 2.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 4.26 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957371 | AF2-031 C O1 | 50/50 | 1.54 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957372 | AF2-031 E O1 | 50/50 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.6 MW | 1.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957752 | AF2-069 E | Adder | 0.69 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957761 | AF2-070 C | Adder | 0.3 MW | 0.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957762 | AF2-070 E | Adder | 1.47 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958921 | AF2-183 C | Adder | 4.1 MW | 3.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958922 | AF2-183 E | Adder | 6.15 MW | 5.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 18.54 MW | 15.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 4.35 MW | 3.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959611 | AF2-252 C | Adder | 2.01 MW | 1.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959612 | AF2-252 E | Adder | 3.02 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 4.35 MW | 3.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 6.07 MW | 5.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.91 MW | 1.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960611 | AF2-352 C | Adder | 2.01 MW | 1.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960612 | AF2-352 E | Adder | 3.02 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961011 | AF2-392 C O1 | Adder | 3.57 MW | 3.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961012 | AF2-392 E O1 | Adder | 16.7 MW | 14.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961031 | AF2-394 O1 | Adder | 5.07 MW | 4.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 2.12 MW | 1.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 14.19 MW | 12.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | 50/50 | 8.9 MW | 8.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274888 | KELLYCK ;1U | 50/50 | 2.23 MW | 2.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924261 | AB2-070 C O1 | Adder | 1.83 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 924262 | AB2-070 E O1 | Adder | 12.24 MW | 10.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.25 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925771 | AC1-053 C | Adder | 1.81 MW | 1.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925772 | AC1-053 E | Adder | 12.14 MW | 10.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 7.25 MW | 6.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 25.71 MW | 21.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 944221 | AF1-090 C O1 | Adder | 1.84 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 944222 | AF1-090 E O1 | Adder | 8.62 MW | 7.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945871 | AF1-252 O1 | Adder | 4.08 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945881 | AF1-253 O1 | Adder | 2.82 MW | 2.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946161 | AF1-281 C | Adder | 0.38 MW | 0.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946162 | AF1-281 E | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946541 | AF1-318 C O1 | Adder | 5.21 MW | 4.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946542 | AF1-318 E O1 | Adder | 24.39 MW | 20.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958341 | AF2-128 C O1 | Adder | 1.38 MW | 1.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958342 | AF2-128 E O1 | Adder | 6.48 MW | 5.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957382 | AF2-032 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961021 | AF2-393 C | Adder | 6.97 MW | 5.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 961023 | AF2-393 E | Adder | 0.63 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 349.37 MW | 296.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950501 | J449 C | External Queue | 2.08 MW | 2.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 950502 | J449 E | External Queue | 8.34 MW | 8.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952021 | J614 C | External Queue | 0.54 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 952022 | J614 E | External Queue | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953201 | J715 C | External Queue | 1.09 MW | 1.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953202 | J715 E | External Queue | 5.9 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954511 | J926 C | External Queue | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954512 | J926 E | External Queue | 4.73 MW | 4.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954702 | J844 E | External Queue | 8.78 MW | 8.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954741 | J928 C | External Queue | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954742 | J928 E | External Queue | 4.93 MW | 4.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954931 | J967 C | External Queue | 1.21 MW | 1.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954932 | J967 E | External Queue | 6.53 MW | 6.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956141 | J1101 | External Queue | 1.51 MW | 1.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953921 | J855 C | External Queue | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 953922 | J855 E | External Queue | 4.3 MW | 4.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954981 | J974 C | External Queue | 2.28 MW | 2.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 954982 | J974 E | External Queue | 12.35 MW | 12.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 956832 | J1181 E | External Queue | 10.33 MW | 10.33 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 3.43 MW | 3.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 2.71 MW | 2.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.9 MW | 0.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.56 MW | 0.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 1.37 MW | 1.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 3.06 MW | 3.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 3.06 MW | 3.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 2.35 MW | 2.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 2.06 MW | 2.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 2.41 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 2.41 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 9.64 MW | 9.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 9.64 MW | 9.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 2.02 MW | 2.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 3.92 MW | 3.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 3.0 MW | 3.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 3.0 MW | 3.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 4.35 MW | 4.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 5.26 MW | 5.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 1.83 MW | 1.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 1.83 MW | 1.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 4.01 MW | 4.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 3.62 MW | 3.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 14.49 MW | 14.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 1.07 MW | 1.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 1.16 MW | 1.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 2.12 MW | 2.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 16.04 MW | 16.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 9.38 MW | 9.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 21.93 MW | 21.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 12.23 MW | 12.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 12.23 MW | 12.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 13.71 MW | 13.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 1.98 MW | 1.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 1.0 MW | 1.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 1.11 MW | 1.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 7.92 MW | 7.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 4.02 MW | 4.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 4.43 MW | 4.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293644 | O22 E1 | 80/20 | 8.08 MW | 8.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293645 | O22 E2 | 80/20 | 15.69 MW | 15.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 8.47 MW | 8.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 4.64 MW | 4.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 4.27 MW | 4.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 5.47 MW | 5.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 17.41 MW | 17.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 7.34 MW | 7.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 7.34 MW | 7.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 8.24 MW | 8.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.86 MW | 0.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.38 MW | 0.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 15.9 MW | 15.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 39.76 MW | 39.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.4 MW | 2.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 16.1 MW | 16.1 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.97 MW | 1.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 13.22 MW | 13.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 3.51 MW | 3.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 11.16 MW | 11.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.23 MW | 0.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.99 MW | 0.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 33.94 MW | 33.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 158.39 MW | 158.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 4.69 MW | 4.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 34.37 MW | 34.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 4.54 MW | 4.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 18.14 MW | 18.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 23.55 MW | 23.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 9.51 MW | 9.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 58.44 MW | 58.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 9.38 MW | 9.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 44.03 MW | 44.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 11.43 MW | 11.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 3.56 MW | 3.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 23.86 MW | 23.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 5.01 MW | 5.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 15.04 MW | 15.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.36 MW | 1.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 8.35 MW | 8.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 8.45 MW | 8.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 5.63 MW | 5.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 6.82 MW | 6.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 31.92 MW | 31.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 7.67 MW | 7.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 36.02 MW | 36.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957331 | AF2-027 C | 80/20 | 5.41 MW | 5.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957332 | AF2-027 E | 80/20 | 8.12 MW | 8.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957371 | AF2-031 C O1 | 80/20 | 1.68 MW | 1.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957372 | AF2-031 E O1 | 80/20 | 2.52 MW | 2.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957401 | AF2-034 C | 80/20 | 2.9 MW | 2.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957402 | AF2-034 E | 80/20 | 2.47 MW | 2.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.41 MW | 0.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 1.31 MW | 1.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.57 MW | 0.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 2.78 MW | 2.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 7.97 MW | 7.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 11.96 MW | 11.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 36.06 MW | 36.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 4.95 MW | 4.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959352 | AF2-226 E | 80/20 | 7.43 MW | 7.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 3.86 MW | 3.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 5.79 MW | 5.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 4.95 MW | 4.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960282 | AF2-319 E | 80/20 | 7.43 MW | 7.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 12.53 MW | 12.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 2.07 MW | 2.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 3.11 MW | 3.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 3.86 MW | 3.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 5.79 MW | 5.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 6.93 MW | 6.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 32.43 MW | 32.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 9.84 MW | 9.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936291 | AD2-038 C O1 | 80/20 | 3.79 MW | 3.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 936292 | AD2-038 E O1 | 80/20 | 25.34 MW | 25.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274880 | GENERATOR; | 80/20 | 3.05 MW | 3.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274881 | PILOT HIL;1E | 80/20 | 14.49 MW | 14.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274882 | W4-005 E | 80/20 | 17.42 MW | 17.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274888 | KELLYCK ;1U | 80/20 | 3.62 MW | 3.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274890 | CAYUG;1U E | 80/20 | 12.0 MW | 12.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 274891 | CAYUG;2U E | 80/20 | 12.0 MW | 12.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 917501 | Z2-087 C | 80/20 | 2.38 MW | 2.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 918051 | AA1-018 C OP | 80/20 | 1.94 MW | 1.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 23.12 MW | 23.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925301 | AB2-191 | 80/20 | 1.0 MW | 1.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925302 | AB2-191 E | 80/20 | 2.48 MW | 2.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.42 MW | 3.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 22.91 MW | 22.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C | 80/20 | 13.24 MW | 13.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E | 80/20 | 46.93 MW | 46.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 940752 | AE2-062 E | 80/20 | 0.27 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 15.84 MW | 15.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 7.5 MW | 7.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 O1 | 80/20 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C | 80/20 | 0.75 MW | 0.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E | 80/20 | 4.24 MW | 4.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 46.1 MW | 46.1 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 2.61 MW | 2.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 12.24 MW | 12.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 990901 | L-005 E | 80/20 | 10.84 MW | 10.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 C | 80/20 | 13.53 MW | 13.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 961023 | AF2-393 E | 80/20 | 1.23 MW | 1.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 547.46 MW | 547.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o Base Case | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 2.3 MW | 2.3 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 274847 | GR RIDGE ;BU | 50/50 | 3.99 MW | 3.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 274871 | GR RIDGE ;2U | 50/50 | 5.07 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 276170 | Z1-108 E | Adder | 6.39 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 293061 | N-015 E | 50/50 | 15.96 MW | 15.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 294392 | P-010 E | 50/50 | 20.27 MW | 20.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 916211 | Z1-072 E | Adder | 9.65 MW | 8.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 920272 | AA2-123 E | Adder | 6.28 MW | 5.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 924041 | AB2-047 C O1 | Adder | 6.83 MW | 5.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 924042 | AB2-047 E O1 | Adder | 45.72 MW | 38.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 925581 | AC1-033 C | Adder | 2.8 MW | 2.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 925582 | AC1-033 E | Adder | 18.76 MW | 15.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 926821 | AC1-168 C O1 | Adder | 2.3 MW | 1.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 926822 | AC1-168 E O1 | Adder | 15.42 MW | 13.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 927201 | AC1-214 C O1 | Adder | 4.09 MW | 3.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 927202 | AC1-214 E O1 | Adder | 13.02 MW | 11.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 934431 | AD1-067 C | Adder | 0.27 MW | 0.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 934432 | AD1-067 E | Adder | 1.15 MW | 0.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 934721 | AD1-100 C | 50/50 | 39.41 MW | 39.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 934722 | AD1-100 E | 50/50 | 183.9 MW | 183.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 935141 | AD1-148 | Adder | 5.39 MW | 4.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 936371 | AD2-047 C O1 | Adder | 8.29 MW | 7.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 936372 | AD2-047 E O1 | Adder | 40.49 MW | 34.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 937001 | AD2-134 C | Adder | 5.25 MW | 4.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 937002 | AD2-134 E | Adder | 20.98 MW | 17.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 938861 | AE1-114 C O1 | Adder | 8.02 MW | 6.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 938862 | AE1-114 E O1 | Adder | 27.35 MW | 23.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 939321 | AE1-163 C O1 | Adder | 11.3 MW | 9.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 939322 | AE1-163 E O1 | Adder | 69.41 MW | 59.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 939401 | AE1-172 C O1 | Adder | 10.79 MW | 9.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 939402 | AE1-172 E O1 | Adder | 50.61 MW | 43.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 941731 | AE2-173 O1 | Adder | 13.14 MW | 11.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942111 | AE2-223 C | Adder | 4.1 MW | 3.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942112 | AE2-223 E | Adder | 27.43 MW | 23.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942421 | AE2-255 C O1 | Adder | 5.92 MW | 5.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942422 | AE2-255 E O1 | Adder | 17.75 MW | 15.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942651 | AE2-281 C O1 | Adder | 1.61 MW | 1.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 942652 | AE2-281 E O1 | Adder | 9.92 MW | 8.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 943801 | AF1-048 C | Adder | 9.81 MW | 8.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 943802 | AF1-048 E | Adder | 6.54 MW | 5.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946321 | AF1-296 C O1 | Adder | 7.92 MW | 6.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946322 | AF1-296 E O1 | Adder | 37.08 MW | 31.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946501 | AF1-314 C | Adder | 8.9 MW | 7.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946502 | AF1-314 E | Adder | 41.84 MW | 35.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957331 | AF2-027 C | Adder | 6.32 MW | 5.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957332 | AF2-027 E | Adder | 9.49 MW | 8.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957371 | AF2-031 C O1 | Adder | 1.89 MW | 1.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957372 | AF2-031 E O1 | Adder | 2.84 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957401 | AF2-034 C | Adder | 3.43 MW | 2.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957402 | AF2-034 E | Adder | 2.92 MW | 2.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957751 | AF2-069 C | Adder | 0.47 MW | 0.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957752 | AF2-069 E | Adder | 1.53 MW | 1.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957761 | AF2-070 C | Adder | 0.67 MW | 0.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957762 | AF2-070 E | Adder | 3.24 MW | 2.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 958921 | AF2-183 C | Adder | 9.26 MW | 7.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 958922 | AF2-183 E | Adder | 13.88 MW | 11.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 959102 | AF2-201 E O1 | Adder | 41.88 MW | 35.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 959351 | AF2-226 C | Adder | 5.97 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 959352 | AF2-226 E | Adder | 8.95 MW | 7.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 959611 | AF2-252 C | Adder | 4.44 MW | 3.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 959612 | AF2-252 E | Adder | 6.66 MW | 5.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960281 | AF2-319 C | Adder | 5.97 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960282 | AF2-319 E | Adder | 8.95 MW | 7.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960381 | AF2-329 | 50/50 | 14.37 MW | 14.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960601 | AF2-351 C O1 | Adder | 2.44 MW | 2.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960602 | AF2-351 E O1 | Adder | 3.66 MW | 3.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960611 | AF2-352 C | Adder | 4.44 MW | 3.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 960612 | AF2-352 E | Adder | 6.66 MW | 5.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 961011 | AF2-392 C O1 | Adder | 8.04 MW | 6.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 961012 | AF2-392 E O1 | Adder | 37.65 MW | 32.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 961031 | AF2-394 O1 | Adder | 11.42 MW | 9.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 936291 | AD2-038 C O1 | Adder | 4.5 MW | 3.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 936292 | AD2-038 E O1 | Adder | 30.09 MW | 25.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 924261 | AB2-070 C O1 | Adder | 3.97 MW | 3.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 924262 | AB2-070 E O1 | Adder | 26.55 MW | 22.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 925302 | AB2-191 E | Adder | 2.87 MW | 2.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 925771 | AC1-053 C | Adder | 3.93 MW | 3.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 925772 | AC1-053 E | Adder | 26.32 MW | 22.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 938851 | AE1-113 C | Adder | 15.62 MW | 13.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 938852 | AE1-113 E | Adder | 55.39 MW | 47.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 940752 | AE2-062 E | Adder | 0.32 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 944221 | AF1-090 C O1 | Adder | 3.88 MW | 3.29 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 944222 | AF1-090 E O1 | Adder | 18.14 MW | 15.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 945871 | AF1-252 O1 | Adder | 8.59 MW | 7.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 945881 | AF1-253 O1 | Adder | 5.95 MW | 5.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946161 | AF1-281 C | Adder | 0.87 MW | 0.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946162 | AF1-281 E | Adder | 4.92 MW | 4.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946541 | AF1-318 C O1 | Adder | 11.49 MW | 9.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 946542 | AF1-318 E O1 | Adder | 53.78 MW | 45.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 958341 | AF2-128 C O1 | Adder | 3.05 MW | 2.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 958342 | AF2-128 E O1 | Adder | 14.28 MW | 12.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 957382 | AF2-032 E | Adder | 0.32 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 961021 | AF2-393 C | Adder | 15.71 MW | 13.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 961023 | AF2-393 E | Adder | 1.43 MW | 1.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 945351 | AF1-200 FTIR | 50/50 | 614.67 MW | 614.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 950181 | J407 C | External Queue | 4.59 MW | 4.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 950182 | J407 E | External Queue | 18.37 MW | 18.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 950501 | J449 C | External Queue | 4.94 MW | 4.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 950502 | J449 E | External Queue | 19.77 MW | 19.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 951301 | J495 C | External Queue | 3.28 MW | 3.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 951302 | J495 E | External Queue | 9.85 MW | 9.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 952021 | J614 C | External Queue | 1.28 MW | 1.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 952022 | J614 E | External Queue | 6.91 MW | 6.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953201 | J715 C | External Queue | 2.51 MW | 2.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953202 | J715 E | External Queue | 13.58 MW | 13.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954511 | J926 C | External Queue | 2.07 MW | 2.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954512 | J926 E | External Queue | 11.17 MW | 11.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954702 | J844 E | External Queue | 20.33 MW | 20.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954741 | J928 C | External Queue | 2.14 MW | 2.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954742 | J928 E | External Queue | 11.56 MW | 11.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954931 | J967 C | External Queue | 2.86 MW | 2.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954932 | J967 E | External Queue | 15.48 MW | 15.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 955711 | J1055 C | External Queue | 2.44 MW | 2.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 955712 | J1055 E | External Queue | 13.2 MW | 13.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 956141 | J1101 | External Queue | 3.53 MW | 3.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953031 | J545 C | External Queue | 2.57 MW | 2.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953032 | J545 E | External Queue | 13.91 MW | 13.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953921 | J855 C | External Queue | 1.88 MW | 1.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 953922 | J855 E | External Queue | 10.18 MW | 10.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954981 | J974 C | External Queue | 5.15 MW | 5.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 954982 | J974 E | External Queue | 27.85 MW | 27.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | 956832 | J1181 E | External Queue | 24.48 MW | 24.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L6608__R-S | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 2.7 MW | 2.7 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 274847 | GR RIDGE ;BU | 50/50 | 3.99 MW | 3.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 274871 | GR RIDGE ;2U | 50/50 | 5.07 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 276170 | Z1-108 E | Adder | 6.39 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 293061 | N-015 E | 50/50 | 15.96 MW | 15.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 294392 | P-010 E | 50/50 | 20.27 MW | 20.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 916211 | Z1-072 E | Adder | 9.65 MW | 8.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 920272 | AA2-123 E | Adder | 6.28 MW | 5.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 924041 | AB2-047 C O1 | Adder | 6.83 MW | 5.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 924042 | AB2-047 E O1 | Adder | 45.72 MW | 38.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 925581 | AC1-033 C | Adder | 2.8 MW | 2.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 925582 | AC1-033 E | Adder | 18.76 MW | 15.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 926821 | AC1-168 C O1 | Adder | 2.3 MW | 1.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 926822 | AC1-168 E O1 | Adder | 15.42 MW | 13.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 927201 | AC1-214 C O1 | Adder | 4.09 MW | 3.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 927202 | AC1-214 E O1 | Adder | 13.02 MW | 11.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 934431 | AD1-067 C | Adder | 0.27 MW | 0.23 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 934432 | AD1-067 E | Adder | 1.15 MW | 0.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 934721 | AD1-100 C | 50/50 | 39.41 MW | 39.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 934722 | AD1-100 E | 50/50 | 183.9 MW | 183.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 935141 | AD1-148 | Adder | 5.39 MW | 4.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 936371 | AD2-047 C O1 | Adder | 8.29 MW | 7.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 936372 | AD2-047 E O1 | Adder | 40.49 MW | 34.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 937001 | AD2-134 C | Adder | 5.25 MW | 4.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 937002 | AD2-134 E | Adder | 20.98 MW | 17.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 938861 | AE1-114 C O1 | Adder | 8.02 MW | 6.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 938862 | AE1-114 E O1 | Adder | 27.35 MW | 23.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 939321 | AE1-163 C O1 | Adder | 11.3 MW | 9.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 939322 | AE1-163 E O1 | Adder | 69.41 MW | 59.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 939401 | AE1-172 C O1 | Adder | 10.79 MW | 9.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 939402 | AE1-172 E O1 | Adder | 50.61 MW | 43.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 941731 | AE2-173 O1 | Adder | 13.14 MW | 11.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942111 | AE2-223 C | Adder | 4.1 MW | 3.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942112 | AE2-223 E | Adder | 27.43 MW | 23.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942421 | AE2-255 C O1 | Adder | 5.92 MW | 5.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942422 | AE2-255 E O1 | Adder | 17.75 MW | 15.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942651 | AE2-281 C O1 | Adder | 1.61 MW | 1.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 942652 | AE2-281 E O1 | Adder | 9.92 MW | 8.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 943801 | AF1-048 C | Adder | 9.81 MW | 8.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 943802 | AF1-048 E | Adder | 6.54 MW | 5.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946321 | AF1-296 C O1 | Adder | 7.92 MW | 6.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946322 | AF1-296 E O1 | Adder | 37.08 MW | 31.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946501 | AF1-314 C | Adder | 8.9 MW | 7.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946502 | AF1-314 E | Adder | 41.84 MW | 35.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957331 | AF2-027 C | Adder | 6.32 MW | 5.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957332 | AF2-027 E | Adder | 9.49 MW | 8.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957371 | AF2-031 C O1 | Adder | 1.89 MW | 1.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957372 | AF2-031 E O1 | Adder | 2.84 MW | 2.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957401 | AF2-034 C | Adder | 3.43 MW | 2.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957402 | AF2-034 E | Adder | 2.92 MW | 2.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957751 | AF2-069 C | Adder | 0.47 MW | 0.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957752 | AF2-069 E | Adder | 1.53 MW | 1.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957761 | AF2-070 C | Adder | 0.67 MW | 0.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957762 | AF2-070 E | Adder | 3.24 MW | 2.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 958921 | AF2-183 C | Adder | 9.26 MW | 7.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 958922 | AF2-183 E | Adder | 13.88 MW | 11.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 959102 | AF2-201 E O1 | Adder | 41.88 MW | 35.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 959351 | AF2-226 C | Adder | 5.97 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 959352 | AF2-226 E | Adder | 8.95 MW | 7.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 959611 | AF2-252 C | Adder | 4.44 MW | 3.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 959612 | AF2-252 E | Adder | 6.66 MW | 5.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960281 | AF2-319 C | Adder | 5.97 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960282 | AF2-319 E | Adder | 8.95 MW | 7.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960381 | AF2-329 | 50/50 | 14.37 MW | 14.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960601 | AF2-351 C O1 | Adder | 2.44 MW | 2.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960602 | AF2-351 E O1 | Adder | 3.66 MW | 3.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960611 | AF2-352 C | Adder | 4.44 MW | 3.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 960612 | AF2-352 E | Adder | 6.66 MW | 5.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 961011 | AF2-392 C O1 | Adder | 8.04 MW | 6.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 961012 | AF2-392 E O1 | Adder | 37.65 MW | 32.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 961031 | AF2-394 O1 | Adder | 11.42 MW | 9.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 936291 | AD2-038 C O1 | Adder | 4.5 MW | 3.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 936292 | AD2-038 E O1 | Adder | 30.09 MW | 25.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 924261 | AB2-070 C O1 | Adder | 3.97 MW | 3.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 924262 | AB2-070 E O1 | Adder | 26.55 MW | 22.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 925302 | AB2-191 E | Adder | 2.87 MW | 2.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 925771 | AC1-053 C | Adder | 3.93 MW | 3.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 925772 | AC1-053 E | Adder | 26.32 MW | 22.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 938851 | AE1-113 C | Adder | 15.62 MW | 13.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 938852 | AE1-113 E | Adder | 55.39 MW | 47.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 940752 | AE2-062 E | Adder | 0.32 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 944221 | AF1-090 C O1 | Adder | 3.88 MW | 3.29 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 944222 | AF1-090 E O1 | Adder | 18.14 MW | 15.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 945871 | AF1-252 O1 | Adder | 8.59 MW | 7.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 945881 | AF1-253 O1 | Adder | 5.95 MW | 5.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946161 | AF1-281 C | Adder | 0.87 MW | 0.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946162 | AF1-281 E | Adder | 4.92 MW | 4.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946541 | AF1-318 C O1 | Adder | 11.49 MW | 9.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 946542 | AF1-318 E O1 | Adder | 53.78 MW | 45.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 958341 | AF2-128 C O1 | Adder | 3.05 MW | 2.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 958342 | AF2-128 E O1 | Adder | 14.28 MW | 12.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 957382 | AF2-032 E | Adder | 0.32 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 961021 | AF2-393 C | Adder | 15.71 MW | 13.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 961023 | AF2-393 E | Adder | 1.43 MW | 1.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 945351 | AF1-200 FTIR | 50/50 | 614.67 MW | 614.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 950181 | J407 C | External Queue | 4.59 MW | 4.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 950182 | J407 E | External Queue | 18.37 MW | 18.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 950501 | J449 C | External Queue | 4.94 MW | 4.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 950502 | J449 E | External Queue | 19.77 MW | 19.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 951301 | J495 C | External Queue | 3.28 MW | 3.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 951302 | J495 E | External Queue | 9.85 MW | 9.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 952021 | J614 C | External Queue | 1.28 MW | 1.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 952022 | J614 E | External Queue | 6.91 MW | 6.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953201 | J715 C | External Queue | 2.51 MW | 2.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953202 | J715 E | External Queue | 13.58 MW | 13.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954511 | J926 C | External Queue | 2.07 MW | 2.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954512 | J926 E | External Queue | 11.17 MW | 11.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954702 | J844 E | External Queue | 20.33 MW | 20.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954741 | J928 C | External Queue | 2.14 MW | 2.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954742 | J928 E | External Queue | 11.56 MW | 11.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954931 | J967 C | External Queue | 2.86 MW | 2.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954932 | J967 E | External Queue | 15.48 MW | 15.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 955711 | J1055 C | External Queue | 2.44 MW | 2.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 955712 | J1055 E | External Queue | 13.2 MW | 13.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 956141 | J1101 | External Queue | 3.53 MW | 3.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953031 | J545 C | External Queue | 2.57 MW | 2.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953032 | J545 E | External Queue | 13.91 MW | 13.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953921 | J855 C | External Queue | 1.88 MW | 1.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 953922 | J855 E | External Queue | 10.18 MW | 10.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954981 | J974 C | External Queue | 5.15 MW | 5.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 954982 | J974 E | External Queue | 27.85 MW | 27.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | 956832 | J1181 E | External Queue | 24.48 MW | 24.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7_345-L6607__B-S_+_345-L97008_R-S-A | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 2.7 MW | 2.7 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.44 MW | 1.44 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 1.17 MW | 1.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.39 MW | 0.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.23 MW | 0.23 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 1.28 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 1.28 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 0.98 MW | 0.98 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.87 MW | 0.87 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 1.02 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 4.08 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 1.74 MW | 1.74 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 1.28 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 1.28 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 1.82 MW | 1.82 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 2.19 MW | 2.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.79 MW | 0.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.79 MW | 0.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.99 MW | 1.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 7.97 MW | 7.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.46 MW | 0.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.49 MW | 0.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.9 MW | 0.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 7.16 MW | 7.16 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 3.91 MW | 3.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 9.12 MW | 9.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 5.13 MW | 5.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 5.13 MW | 5.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 5.75 MW | 5.75 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.84 MW | 0.84 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.43 MW | 0.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.47 MW | 0.47 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 3.36 MW | 3.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.71 MW | 1.71 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 1.88 MW | 1.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 3.58 MW | 3.58 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 6.95 MW | 6.95 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 3.6 MW | 3.6 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 1.97 MW | 1.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.81 MW | 1.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 2.35 MW | 2.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 7.3 MW | 7.3 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 3.15 MW | 3.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 3.15 MW | 3.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 3.49 MW | 3.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.36 MW | 0.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.16 MW | 0.16 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 6.71 MW | 6.71 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 2.51 MW | 2.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 16.77 MW | 16.77 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 1.03 MW | 1.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 6.92 MW | 6.92 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 5.67 MW | 5.67 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.1 MW | 0.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.41 MW | 0.41 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 15.14 MW | 15.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 70.64 MW | 70.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 935141 | AD1-148 | 80/20 | 1.95 MW | 1.95 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 3.87 MW | 3.87 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 18.91 MW | 18.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 1.89 MW | 1.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 7.57 MW | 7.57 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 9.97 MW | 9.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 27.69 MW | 27.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 4.03 MW | 4.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 18.89 MW | 18.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 4.82 MW | 4.82 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.5 MW | 1.5 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 10.06 MW | 10.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 6.71 MW | 6.71 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.64 MW | 0.64 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 3.96 MW | 3.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 3.58 MW | 3.58 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 2.39 MW | 2.39 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 2.89 MW | 2.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 13.54 MW | 13.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 3.25 MW | 3.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 15.26 MW | 15.26 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 2.35 MW | 2.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 3.52 MW | 3.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 1.3 MW | 1.3 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.17 MW | 0.17 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.56 MW | 0.56 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.25 MW | 0.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 1.2 MW | 1.2 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 3.37 MW | 3.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 5.06 MW | 5.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 15.28 MW | 15.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 2.19 MW | 2.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 3.29 MW | 3.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.62 MW | 1.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 2.19 MW | 2.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 3.29 MW | 3.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 5.06 MW | 5.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.71 MW | 1.71 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.62 MW | 1.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 2.43 MW | 2.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 2.93 MW | 2.93 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 13.72 MW | 13.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 4.16 MW | 4.16 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 12.0 MW | 12.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274880 | GENERATOR; | 80/20 | 1.27 MW | 1.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 7.97 MW | 7.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274882 | W4-005 E | 80/20 | 7.25 MW | 7.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.99 MW | 1.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 5.12 MW | 5.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 5.12 MW | 5.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 1.0 MW | 1.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924261 | AB2-070 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924262 | AB2-070 E O1 | 80/20 | 9.62 MW | 9.62 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.42 MW | 0.42 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 1.04 MW | 1.04 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925771 | AC1-053 C | 80/20 | 1.43 MW | 1.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925772 | AC1-053 E | 80/20 | 9.54 MW | 9.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 5.91 MW | 5.91 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 20.94 MW | 20.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.13 MW | 0.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.32 MW | 0.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 4.25 MW | 4.25 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 19.9 MW | 19.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 5.29 MW | 5.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 4.66 MW | 4.66 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957382 | AF2-032 E | 80/20 | 0.12 MW | 0.12 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 5.72 MW | 5.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.52 MW | 0.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 199.61 MW | 199.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954741 | J928 C | External Queue | 0.33 MW | 0.33 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 954742 | J928 E | External Queue | 1.79 MW | 1.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 956141 | J1101 | External Queue | 1.38 MW | 1.38 MW |
| Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274847 | GR RIDGE ;BU | 50/50 | 1.44 MW | 1.44 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274871 | GR RIDGE ;2U | 50/50 | 1.83 MW | 1.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274887 | PILOT HIL;1U | 50/50 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 275149 | KELLYCK ;1E | 50/50 | 7.99 MW | 7.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.34 MW | 1.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293061 | N-015 E | 50/50 | 5.76 MW | 5.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294392 | P-010 E | 50/50 | 7.32 MW | 7.32 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 916211 | Z1-072 E | Adder | 3.56 MW | 3.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918052 | AA1-018 E OP | 50/50 | 6.49 MW | 6.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.29 MW | 1.95 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 924041 | AB2-047 C O1 | Adder | 2.5 MW | 2.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 16.74 MW | 14.23 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925581 | AC1-033 C | Adder | 1.03 MW | 0.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925582 | AC1-033 E | Adder | 6.91 MW | 5.87 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926822 | AC1-168 E O1 | Adder | 5.67 MW | 4.82 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927201 | AC1-214 C O1 | Adder | 1.51 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 4.8 MW | 4.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.1 MW | 0.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.41 MW | 0.35 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934721 | AD1-100 C | 50/50 | 15.19 MW | 15.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934722 | AD1-100 E | 50/50 | 70.86 MW | 70.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 935141 | AD1-148 | Adder | 1.95 MW | 1.66 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936371 | AD2-047 C O1 | 50/50 | 3.88 MW | 3.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936372 | AD2-047 E O1 | 50/50 | 18.94 MW | 18.94 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937001 | AD2-134 C | Adder | 1.9 MW | 1.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937002 | AD2-134 E | Adder | 7.58 MW | 6.44 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 2.92 MW | 2.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 9.97 MW | 8.47 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.5 MW | 3.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 27.64 MW | 23.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 4.03 MW | 3.43 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 18.91 MW | 16.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941731 | AE2-173 O1 | Adder | 4.81 MW | 4.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942111 | AE2-223 C | Adder | 1.5 MW | 1.28 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942112 | AE2-223 E | Adder | 10.05 MW | 8.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.23 MW | 1.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 6.7 MW | 5.69 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.64 MW | 0.55 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.95 MW | 3.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.58 MW | 3.05 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.39 MW | 2.03 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 2.89 MW | 2.46 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 13.54 MW | 11.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946502 | AF1-314 E | Adder | 15.26 MW | 12.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.35 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.52 MW | 3.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957371 | AF2-031 C O1 | Adder | 0.59 MW | 0.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957372 | AF2-031 E O1 | Adder | 0.89 MW | 0.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957401 | AF2-034 C | 50/50 | 1.29 MW | 1.29 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.1 MW | 1.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957752 | AF2-069 E | Adder | 0.56 MW | 0.48 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957762 | AF2-070 E | Adder | 1.2 MW | 1.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958921 | AF2-183 C | Adder | 3.37 MW | 2.87 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958922 | AF2-183 E | Adder | 5.06 MW | 4.3 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.28 MW | 12.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959351 | AF2-226 C | Adder | 2.19 MW | 1.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959352 | AF2-226 E | Adder | 3.28 MW | 2.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959611 | AF2-252 C | Adder | 1.62 MW | 1.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959612 | AF2-252 E | Adder | 2.42 MW | 2.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960281 | AF2-319 C | Adder | 2.19 MW | 1.86 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960282 | AF2-319 E | Adder | 3.28 MW | 2.79 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960381 | AF2-329 | 50/50 | 5.08 MW | 5.08 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960601 | AF2-351 C O1 | 50/50 | 1.14 MW | 1.14 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960602 | AF2-351 E O1 | 50/50 | 1.71 MW | 1.71 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960611 | AF2-352 C | Adder | 1.62 MW | 1.37 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960612 | AF2-352 E | Adder | 2.42 MW | 2.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 2.93 MW | 2.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 13.72 MW | 11.66 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961031 | AF2-394 O1 | Adder | 4.16 MW | 3.54 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.79 MW | 1.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.98 MW | 10.19 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274881 | PILOT HIL;1E | 50/50 | 7.99 MW | 7.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274888 | KELLYCK ;1U | 50/50 | 2.0 MW | 2.0 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918051 | AA1-018 C OP | 50/50 | 0.97 MW | 0.97 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 924261 | AB2-070 C O1 | Adder | 1.44 MW | 1.22 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 924262 | AB2-070 E O1 | Adder | 9.6 MW | 8.16 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.04 MW | 0.88 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925771 | AC1-053 C | Adder | 1.42 MW | 1.21 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925772 | AC1-053 E | Adder | 9.52 MW | 8.09 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938851 | AE1-113 C | Adder | 5.89 MW | 5.01 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938852 | AE1-113 E | Adder | 20.9 MW | 17.76 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940752 | AE2-062 E | 50/50 | 0.13 MW | 0.13 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946161 | AF1-281 C | Adder | 0.32 MW | 0.27 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946162 | AF1-281 E | Adder | 1.79 MW | 1.52 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.25 MW | 3.61 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 19.88 MW | 16.9 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.13 MW | 0.96 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.28 MW | 4.49 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957382 | AF2-032 E | Adder | 0.12 MW | 0.1 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961021 | AF2-393 C | Adder | 5.72 MW | 4.87 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961023 | AF2-393 E | Adder | 0.52 MW | 0.44 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 945351 | AF1-200 FTIR | 50/50 | 201.06 MW | 201.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 953201 | J715 C | External Queue | 0.99 MW | 0.99 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 953202 | J715 E | External Queue | 5.36 MW | 5.36 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954511 | J926 C | External Queue | 0.81 MW | 0.81 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954512 | J926 E | External Queue | 4.4 MW | 4.4 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954702 | J844 E | External Queue | 8.02 MW | 8.02 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954741 | J928 C | External Queue | 0.83 MW | 0.83 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954742 | J928 E | External Queue | 4.51 MW | 4.51 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 956141 | J1101 | External Queue | 1.38 MW | 1.38 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954981 | J974 C | External Queue | 2.06 MW | 2.06 MW |
| BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 954982 | J974 E | External Queue | 11.15 MW | 11.15 MW |
| Details for AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| AF1-314 TAP-ELEROY ;RT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| AF1-314 TAP-ELEROY ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o 271398 ELEROY ;BT 138 946500 AF1-314 TAP 138 1 | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| ELEROY ;RT-LANCASTER;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11904_B-R-A | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.0 MW | 1.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 0.81 MW | 0.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.16 MW | 0.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 0.87 MW | 0.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 0.67 MW | 0.67 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.6 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 2.82 MW | 2.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 2.82 MW | 2.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 1.37 MW | 1.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 0.85 MW | 0.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 0.85 MW | 0.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 1.27 MW | 1.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 1.5 MW | 1.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.26 MW | 1.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.21 MW | 1.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 4.84 MW | 4.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 5.02 MW | 5.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 2.69 MW | 2.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 6.27 MW | 6.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 3.48 MW | 3.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 3.48 MW | 3.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 3.99 MW | 3.99 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.33 MW | 0.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 2.81 MW | 2.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 5.46 MW | 5.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 1.63 MW | 1.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 5.07 MW | 5.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 2.18 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 2.18 MW | 2.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 2.41 MW | 2.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.25 MW | 0.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.11 MW | 0.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 4.52 MW | 4.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 11.31 MW | 11.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 4.79 MW | 4.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 3.93 MW | 3.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 3.32 MW | 3.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.07 MW | 0.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 10.07 MW | 10.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 47.0 MW | 47.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 2.35 MW | 2.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 11.48 MW | 11.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 1.3 MW | 1.3 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 5.21 MW | 5.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 6.88 MW | 6.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 18.39 MW | 18.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 12.56 MW | 12.56 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 3.25 MW | 3.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.01 MW | 1.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 6.79 MW | 6.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 1.57 MW | 1.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 4.71 MW | 4.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 2.63 MW | 2.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 2.47 MW | 2.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 1.65 MW | 1.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 9.37 MW | 9.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 2.24 MW | 2.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 10.53 MW | 10.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 1.62 MW | 1.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 2.43 MW | 2.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 1.1 MW | 1.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 0.93 MW | 0.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 0.79 MW | 0.79 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 2.33 MW | 2.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 3.49 MW | 3.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 10.54 MW | 10.54 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 2.59 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.1 MW | 1.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 1.65 MW | 1.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 1.73 MW | 1.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 2.59 MW | 2.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 3.46 MW | 3.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.69 MW | 0.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.04 MW | 1.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.1 MW | 1.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 1.65 MW | 1.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 9.47 MW | 9.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 7.97 MW | 7.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 4.84 MW | 4.84 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.21 MW | 1.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 3.42 MW | 3.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 3.42 MW | 3.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 0.68 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.62 MW | 0.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.29 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 0.71 MW | 0.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 4.14 MW | 4.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 14.69 MW | 14.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.09 MW | 0.09 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.24 MW | 1.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 13.75 MW | 13.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 3.65 MW | 3.65 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 3.23 MW | 3.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 3.95 MW | 3.95 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.36 MW | 0.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 136.26 MW | 136.26 MW |
| Details for ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P2-1_119-L11902__ | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
| Details for ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 274856 | ECOGROVE ;U1 | 80/20 | 8.0 MW | 8.0 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 294763 | P-046 E | 80/20 | 31.99 MW | 31.99 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 946501 | AF1-314 C | 80/20 | 29.75 MW | 29.75 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 946502 | AF1-314 E | 80/20 | 139.78 MW | 139.78 MW |
| ELEROY ;BT-FREEPORT ;BT 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11902GB-R-B | 959102 | AF2-201 E O1 | 80/20 | 139.94 MW | 139.94 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| n6860 | Wilton Upgrade exisiting Current Transformers | $1,000,000 | |
| n5252 | Mitigate the sag on L11215 | $9,000,000 | |
| n6600 | Replace Dumont Circuit Breaker B1 | $3,000,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| s2631 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n6740 | Sag Study - Allen and Rpmone 345 kV line (12.25 miles). Completed, Rate B should be 1057MVA. | $49,000 | |
| n8196.2 | In addition to N8196.1, replace an additional existing double circuit towers with steel double circuit single pole structures on the Allen - RPMone 345kV line. | $458,600 | |
| n8196.1 | AEP will replace two (2) existing double circuit towers with steel double circuit single pole structures on the Allen - RPMone 345kV line. | $916,437 | |
| (TBD) | Upgrade 0.6 miles of line to bundled conductor and additional susbtation upgrades required. | $5,000,000 | |
| n5912 | Re-conductor of the line along with station conductor upgrade at Burnham | $1,000,000 | |
| n5912.3 | The existing SLD/ALDR rating are 1767/2032 MVA. Reconductor the line and replace the 345kV BT 10-11 & BT 9-10 CB disconnect switches at TSS 177 along with upgrading the L17703 MOD. | $18,400,000 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| b3775.5 | Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker. | $0 | |
| b3775.4 | Rebuild 345 kV double circuit extending from Crete to E. Frankfort. | $0 | |
| (TBD) | Re-conductor the line conductor and upgrade station conductor. | $3,800,000 | |
| (TBD) | ComEd Review Required | $0 | |
| n8350 | Freeport - Lancaster 138 kV - Mitigate Sag and upgrade station conductor | $750,000 | |
| n8348 | ComEd L17121 138 kV line reconductor | $12,300,000 | |
| n5145 | Reconfigure Wilton 765kV bus | $55,229,373 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-201 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.