AF2-200 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:04
Nelson-Electric Junction 345 kV
120.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-200 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Solar generating facility located in the ComEd zone — Lee County, Illinois. This project is an increase to the Interconnection Customer's original project, which will share the same point of interconnection. The AF2-200 queue position is a 200.0 MW uprate (120.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 600.0 MW.
| Project Information | |
|---|---|
| Queue Number | AF2-200 |
| Project Name | Nelson-Electric Junction 345 kV |
| Developer Name | Steward Creek Solar, LLC |
| State | Illinois |
| County | Lee |
| Transmission Owner | ComEd |
| MFO | 600.0 MW |
| MWE | 200.0 MW |
| MWC | 120.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-200 will interconnect on the ComEd on transmission system tapping the Nelson to Electric Junction 345 kV line utilizing the same attachment facilities as AF2-041.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 120.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
COMED_P2-2_111_EJ-345R__3
CONTINGENCY 'COMED_P2-2_111_EJ-345R__3' DISCONNECT BUS 270733 /*ELECT JCT;3R 345.0 DISCONNECT BUS 275183 /*ELECT JCT;3M 138.0 END |
Bus | AC | 99.95 % | 101.91 % | 1568.0 | STE | 1597.91 | 31.08 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 106.23 % | 112.28 % | 1837.0 | STE | 2062.55 | 124.43 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_006-45-BT3-4__
CONTINGENCY 'COMED_P4_006-45-BT3-4__' REMOVE UNIT 1 FROM BUS 274656 /*BYRON ;1U 25.0 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 END |
Breaker | AC | 103.0 % | 109.7 % | 1837.0 | STE | 2015.19 | 124.21 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_006-45-BT3-8__
CONTINGENCY 'COMED_P4_006-45-BT3-8__' TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT 1 /*BYRON ; B 345.0 - BYRON ; R 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 END |
Breaker | AC | 102.31 % | 108.96 % | 1837.0 | STE | 2001.61 | 124.22 | |
| CE |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line
270678 to 270694 ckt 1 |
COMED_P4_006-45-BT7-8__
CONTINGENCY 'COMED_P4_006-45-BT7-8__' TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT 1 /*BYRON ; B 345.0 - BYRON ; R 345.0 TRIP BRANCH FROM BUS 270678 TO BUS 930480 CKT 1 /*BYRON ; B 345.0 - AB1-089 TAP 345.0 END |
Breaker | AC | 111.33 % | 112.38 % | 1585.0 | STE | 1781.22 | 18.11 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 113.34 % | 113.72 % | 971.0 | B | 1104.22 | 19.52 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 113.23 % | 113.61 % | 971.0 | B | 1103.15 | 19.5 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 113.23 % | 113.61 % | 971.0 | B | 1103.15 | 19.5 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 113.41 % | 113.72 % | 971.0 | B | 1104.22 | 19.36 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 112.56 % | 112.81 % | 971.0 | STE | 1095.39 | 19.36 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 111.98 % | 112.23 % | 971.0 | STE | 1089.75 | 19.52 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 111.89 % | 112.14 % | 971.0 | STE | 1088.88 | 19.5 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 111.88 % | 112.13 % | 971.0 | STE | 1088.78 | 19.5 | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
COMED_P4_120-45-L12002_
CONTINGENCY 'COMED_P4_120-45-L12002_' CLOSE BRANCH FROM BUS 271734 TO BUS 271735 CKT 1 /*ITASCA ; B 138.0 - ITASCA ; R 138.0 DISCONNECT BUS 275198 /*LOMBARD ;2M 138.0 TRIP BRANCH FROM BUS 270813 TO BUS 270753 CKT 1 /*LOMBARD ; R 345.0 - ESS W407M;0T 345.0 TRIP BRANCH FROM BUS 270813 TO BUS 270781 CKT 1 /*LOMBARD ; R 345.0 - ITASCA ; R 345.0 TRIP BRANCH FROM BUS 270813 TO BUS 270809 CKT 1 /*LOMBARD ; R 345.0 - LISLE ; R 345.0 TRIP BRANCH FROM BUS 275191 TO BUS 270781 CKT 1 /*ITASCA ;2M 138.0 - ITASCA ; R 345.0 TRIP BRANCH FROM BUS 275191 TO BUS 271735 CKT 1 /*ITASCA ;2M 138.0 - ITASCA ; R 138.0 TRIP BRANCH FROM BUS 275191 TO BUS 275291 CKT 1 /*ITASCA ;2M 138.0 - ITASCA ;2C 34.5 END |
Breaker | AC | 100.05 % | 102.02 % | 1568.0 | STE | 1599.69 | 31.43 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_023-65-BT2-3__
CONTINGENCY 'COMED_P4_023-65-BT2-3__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Breaker | AC | 110.85 % | 110.88 % | 1399.0 | B | 1551.21 | 24.84 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 110.75 % | 110.78 % | 1399.0 | B | 1549.81 | 24.61 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 110.52 % | 110.55 % | 1399.0 | B | 1546.59 | 24.74 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 110.5 % | 110.53 % | 1399.0 | B | 1546.31 | 24.74 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_023-65-BT4-5__
CONTINGENCY 'COMED_P4_023-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 110.43 % | 110.46 % | 1399.0 | B | 1545.34 | 24.71 | |
| CE |
LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line
274768 to 270678 ckt 1 |
COMED_P1-2_345-L15502_B-R-B
CONTINGENCY 'COMED_P1-2_345-L15502_B-R-B' TRIP BRANCH FROM BUS 957470 TO BUS 270730 CKT 1 /*AF2-041 TAP 345.0 - ELECT JCT; B 345.0 END |
Single | AC | 97.68 % | 100.22 % | 1837.0 | STE | 1840.95 | 46.86 | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
Base Case | Single | AC | 100.11 % | 101.58 % | 1201.0 | A | 1219.98 | 18.13 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 104.54 % | 104.75 % | 1409.0 | B | 1475.93 | 27.41 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P4_023-65-BT4-5__
CONTINGENCY 'COMED_P4_023-65-BT4-5__' TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 102.15 % | 102.37 % | 1409.0 | B | 1442.39 | 28.05 | |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 290051 | GSG-6; E | Adder | 8.12 MW | 6.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 295109 | WESTBROOK E | Adder | 4.34 MW | 3.69 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 295111 | SUBLETTE E | Adder | 2.11 MW | 1.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926311 | AC1-109 1 | Adder | 1.09 MW | 0.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926321 | AC1-109 2 | Adder | 1.09 MW | 0.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926331 | AC1-110 1 | 50/50 | 2.54 MW | 2.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926341 | AC1-110 2 | 50/50 | 2.54 MW | 2.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926351 | AC1-111 1 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926361 | AC1-111 2 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926371 | AC1-111 3 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926381 | AC1-111 4 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926391 | AC1-111 5 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 926401 | AC1-111 6 | Adder | 0.59 MW | 0.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 933911 | AD1-013 C | Adder | 1.44 MW | 1.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 934431 | AD1-067 C | Adder | 0.1 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 934432 | AD1-067 E | Adder | 0.43 MW | 0.36 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 937001 | AD2-134 C | Adder | 1.96 MW | 1.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 937002 | AD2-134 E | Adder | 7.85 MW | 6.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 937311 | AD2-172 C | Adder | 1.14 MW | 0.97 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 937312 | AD2-172 E | Adder | 1.58 MW | 1.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 943121 | AE2-341 C | 50/50 | 10.69 MW | 10.69 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 943122 | AE2-341 E | 50/50 | 5.25 MW | 5.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 943591 | AF1-030 C O1 | 50/50 | 7.11 MW | 7.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 943592 | AF1-030 E O1 | 50/50 | 3.52 MW | 3.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 958911 | AF2-182 C | Adder | 12.88 MW | 10.95 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 958912 | AF2-182 E | Adder | 8.59 MW | 7.3 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 958922 | AF2-183 E | Adder | 3.43 MW | 2.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959081 | AF2-199 C | 50/50 | 9.32 MW | 9.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959082 | AF2-199 E | 50/50 | 6.21 MW | 6.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959091 | AF2-200 C O1 | 50/50 | 18.65 MW | 18.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959092 | AF2-200 E O1 | 50/50 | 12.43 MW | 12.43 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959101 | AF2-201 C O1 | Adder | 2.79 MW | 2.38 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 959102 | AF2-201 E O1 | Adder | 8.02 MW | 6.82 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 960381 | AF2-329 | 50/50 | 4.48 MW | 4.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 960721 | AF2-363 C O1 | Adder | 4.03 MW | 3.42 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 960722 | AF2-363 E O1 | Adder | 2.68 MW | 2.28 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 960751 | AF2-366 C | 50/50 | 5.8 MW | 5.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 960752 | AF2-366 E | 50/50 | 3.87 MW | 3.87 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 961011 | AF2-392 C O1 | Adder | 2.56 MW | 2.17 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 961012 | AF2-392 E O1 | Adder | 11.98 MW | 10.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 961021 | AF2-393 O1 | Adder | 4.36 MW | 3.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 961031 | AF2-394 O1 | Adder | 2.91 MW | 2.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 274738 | AURORA EC;3P | 50/50 | 4.47 MW | 4.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 274740 | AURORA EC;4P | 50/50 | 4.47 MW | 4.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 274859 | EASYR;U1 E | Adder | 6.65 MW | 5.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 274860 | EASYR;U2 E | Adder | 6.65 MW | 5.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 276167 | Z1-106 E2 | 50/50 | 1.12 MW | 1.12 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 276168 | Z1-106 E1 | 50/50 | 1.12 MW | 1.12 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293516 | O-009 E1 | Adder | 5.14 MW | 4.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293517 | O-009 E2 | Adder | 2.61 MW | 2.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293518 | O-009 E3 | Adder | 2.88 MW | 2.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293715 | O-029 E | Adder | 5.5 MW | 4.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293716 | O-029 E | Adder | 3.01 MW | 2.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 293717 | O-029 E | Adder | 2.77 MW | 2.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 294763 | P-046 E | Adder | 4.35 MW | 3.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 916221 | Z1-073 E | Adder | 4.19 MW | 3.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 938861 | AE1-114 C O1 | Adder | 2.09 MW | 1.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 938862 | AE1-114 E O1 | Adder | 7.14 MW | 6.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 939051 | AE1-134 1 | Adder | 0.94 MW | 0.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 939061 | AE1-134 2 | Adder | 0.94 MW | 0.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 940501 | AE2-035 C | Adder | 1.14 MW | 0.97 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 940502 | AE2-035 E | Adder | 1.58 MW | 1.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 941131 | AE2-107 C | 50/50 | 5.4 MW | 5.4 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 941132 | AE2-107 E | 50/50 | 3.6 MW | 3.6 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946151 | AF1-280 C O1 | Adder | 9.8 MW | 8.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946152 | AF1-280 E O1 | Adder | 4.51 MW | 3.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946321 | AF1-296 C O1 | Adder | 2.1 MW | 1.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946322 | AF1-296 E O1 | Adder | 9.83 MW | 8.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946501 | AF1-314 C | Adder | 2.02 MW | 1.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946502 | AF1-314 E | Adder | 9.5 MW | 8.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 957471 | AF2-041 C | 50/50 | 27.97 MW | 27.97 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 957472 | AF2-041 E | 50/50 | 18.65 MW | 18.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 919581 | AA2-030 | Adder | 12.07 MW | 10.26 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 925302 | AB2-191 E | Adder | 1.07 MW | 0.91 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 930481 | AB1-089 | Adder | 34.96 MW | 29.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946161 | AF1-281 C | Adder | 0.21 MW | 0.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 946162 | AF1-281 E | Adder | 1.22 MW | 1.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 292543 | L-013 2 | 50/50 | 0.56 MW | 0.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 274872 | LEE DEKAL;1U | 50/50 | 0.83 MW | 0.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 290108 | LEEDK;1U E | 50/50 | 20.01 MW | 20.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 276165 | Z1-106 BAT2 | 50/50 | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 276166 | Z1-106 BAT1 | 50/50 | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 945351 | AF1-200 FTIR | Adder | 207.21 MW | 176.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 957333 | AF2-027 BAT | Adder | 3.7 MW | 3.14 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | 955971 | J1084 | External Queue | 7.75 MW | 7.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 3.77 MW | 3.77 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.39 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.21 MW | 1.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.09 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.78 MW | 1.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.19 MW | 0.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.79 MW | 2.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.72 MW | 3.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.75 MW | 1.75 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 7.95 MW | 6.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.26 MW | 3.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.07 MW | 1.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.8 MW | 8.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.78 MW | 1.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.67 MW | 4.82 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.34 MW | 1.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.14 MW | 1.82 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | Adder | 3.0 MW | 2.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | Adder | 4.9 MW | 4.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934431 | AD1-067 C | Adder | 0.1 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.42 MW | 0.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 1.92 MW | 1.64 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 7.69 MW | 6.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 58.14 MW | 58.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 38.76 MW | 38.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.34 MW | 10.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 15.5 MW | 15.5 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959081 | AF2-199 C | 50/50 | 37.33 MW | 37.33 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959082 | AF2-199 E | 50/50 | 24.89 MW | 24.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959091 | AF2-200 C O1 | 50/50 | 74.66 MW | 74.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959092 | AF2-200 E O1 | 50/50 | 49.77 MW | 49.77 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.42 MW | 9.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.11 MW | 44.11 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.06 MW | 16.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.71 MW | 10.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 37.1 MW | 37.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.51 MW | 6.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.51 MW | 6.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.32 MW | 7.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.44 MW | 9.44 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 6.89 MW | 6.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.51 MW | 9.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 6.95 MW | 6.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 1.34 MW | 1.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 1.34 MW | 1.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 31.0 MW | 31.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 31.0 MW | 31.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.45 MW | 0.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.89 MW | 0.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.84 MW | 0.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.42 MW | 0.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.3 MW | 19.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 9.8 MW | 9.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 10.79 MW | 10.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 20.63 MW | 20.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.31 MW | 11.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.4 MW | 10.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.56 MW | 4.72 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | Adder | 9.08 MW | 7.72 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | Adder | 9.08 MW | 7.72 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.2 MW | 3.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.1 MW | 3.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | Adder | 1.49 MW | 1.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | Adder | 9.96 MW | 8.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 4.71 MW | 4.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 16.07 MW | 13.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 3.94 MW | 3.94 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 3.94 MW | 3.94 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 44.25 MW | 44.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 20.35 MW | 20.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 8.56 MW | 7.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 40.08 MW | 34.07 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.74 MW | 1.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957471 | AF2-041 C | 50/50 | 111.99 MW | 111.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957472 | AF2-041 E | 50/50 | 74.66 MW | 74.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.67 MW | 0.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.29 MW | 0.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.41 MW | 1.2 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.22 MW | 10.39 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 | 50/50 | 50.72 MW | 50.72 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925302 | AB2-191 E | Adder | 1.05 MW | 0.9 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C | 50/50 | 0.97 MW | 0.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E | 50/50 | 5.49 MW | 5.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950401 | J041 C | External Queue | 1.54 MW | 1.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950402 | J041 E | External Queue | 6.14 MW | 6.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950471 | J438 C | External Queue | 3.15 MW | 3.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.84 MW | 2.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.52 MW | 8.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951221 | J475 C | External Queue | 3.47 MW | 3.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951222 | J475 E | External Queue | 13.89 MW | 13.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.4 MW | 5.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.23 MW | 3.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 5.14 MW | 5.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 20.56 MW | 20.56 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.9 MW | 1.9 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 10.26 MW | 10.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950472 | J438 E | External Queue | 12.59 MW | 12.59 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 13.22 MW | 13.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954901 | J963 | External Queue | 1.32 MW | 1.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.53 MW | 29.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.83 MW | 15.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956832 | J1181 E | External Queue | 17.98 MW | 17.98 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 21.05 MW | 21.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.93 MW | 0.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.94 MW | 3.94 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.89 MW | 12.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.14 MW | 0.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 13.69 MW | 13.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 17.15 MW | 17.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 45.54 MW | 45.54 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 919221 | AA1-146 | 50/50 | 8.77 MW | 8.77 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 934051 | AD1-031 C O1 | Adder | 2.97 MW | 2.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 934052 | AD1-031 E O1 | Adder | 4.85 MW | 4.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 958911 | AF2-182 C | 50/50 | 57.93 MW | 57.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 958912 | AF2-182 E | 50/50 | 38.62 MW | 38.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 958921 | AF2-183 C | 50/50 | 10.3 MW | 10.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 958922 | AF2-183 E | 50/50 | 15.45 MW | 15.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 959081 | AF2-199 C | 50/50 | 37.26 MW | 37.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 959082 | AF2-199 E | 50/50 | 24.84 MW | 24.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 959091 | AF2-200 C O1 | 50/50 | 74.52 MW | 74.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 959092 | AF2-200 E O1 | 50/50 | 49.68 MW | 49.68 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 961011 | AF2-392 C O1 | Adder | 9.38 MW | 7.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 961012 | AF2-392 E O1 | Adder | 43.92 MW | 37.33 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 961021 | AF2-393 O1 | Adder | 15.99 MW | 13.59 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 961031 | AF2-394 O1 | Adder | 10.66 MW | 9.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274715 | NELSON EC;1C | 50/50 | 9.4 MW | 9.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274716 | NELSON EC;1S | 50/50 | 6.86 MW | 6.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274717 | NELSON EC;2C | 50/50 | 9.48 MW | 9.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274718 | NELSON EC;2S | 50/50 | 6.92 MW | 6.92 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274761 | LEE CO EC;2U | 50/50 | 4.41 MW | 4.41 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274764 | LEE CO EC;5U | 50/50 | 4.42 MW | 4.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274765 | LEE CO EC;6U | 50/50 | 4.42 MW | 4.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274859 | EASYR;U1 E | Adder | 30.9 MW | 26.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 274860 | EASYR;U2 E | Adder | 30.9 MW | 26.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293516 | O-009 E1 | Adder | 19.21 MW | 16.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293517 | O-009 E2 | Adder | 9.76 MW | 8.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293518 | O-009 E3 | Adder | 10.74 MW | 9.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293715 | O-029 E | Adder | 20.53 MW | 17.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293716 | O-029 E | Adder | 11.26 MW | 9.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 293717 | O-029 E | Adder | 10.35 MW | 8.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 294401 | BSHIL;1U E | Adder | 8.99 MW | 7.64 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 294410 | BSHIL;2U E | Adder | 8.99 MW | 7.64 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 925582 | AC1-033 E | Adder | 9.86 MW | 8.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 4.67 MW | 3.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 15.94 MW | 13.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 939051 | AE1-134 1 | 50/50 | 3.93 MW | 3.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 939061 | AE1-134 2 | 50/50 | 3.93 MW | 3.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946151 | AF1-280 C O1 | 50/50 | 44.09 MW | 44.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946152 | AF1-280 E O1 | 50/50 | 20.28 MW | 20.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946321 | AF1-296 C O1 | Adder | 8.52 MW | 7.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946322 | AF1-296 E O1 | Adder | 39.89 MW | 33.91 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 957471 | AF2-041 C | 50/50 | 111.78 MW | 111.78 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 957472 | AF2-041 E | 50/50 | 74.52 MW | 74.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 990901 | L-005 E | Adder | 12.09 MW | 10.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 919581 | AA2-030 | 50/50 | 50.54 MW | 50.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946161 | AF1-281 C | 50/50 | 0.97 MW | 0.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 946162 | AF1-281 E | 50/50 | 5.47 MW | 5.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 951381 | J504 | External Queue | 5.4 MW | 5.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 951421 | J514 | External Queue | 3.23 MW | 3.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 951511 | J530 C | External Queue | 5.14 MW | 5.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 951512 | J530 E | External Queue | 20.56 MW | 20.56 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 954901 | J963 | External Queue | 1.32 MW | 1.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 955971 | J1084 | External Queue | 29.53 MW | 29.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | 956411 | J1131 | External Queue | 15.83 MW | 15.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.25 MW | 0.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 20.12 MW | 20.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.38 MW | 2.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.69 MW | 1.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.29 MW | 3.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 11.93 MW | 11.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.26 MW | 0.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 13.69 MW | 13.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.97 MW | 16.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 44.12 MW | 44.12 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919221 | AA1-146 | 50/50 | 8.79 MW | 8.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934052 | AD1-031 E O1 | Adder | 4.86 MW | 4.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958911 | AF2-182 C | 50/50 | 58.02 MW | 58.02 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958912 | AF2-182 E | 50/50 | 38.68 MW | 38.68 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958921 | AF2-183 C | 50/50 | 10.31 MW | 10.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958922 | AF2-183 E | 50/50 | 15.47 MW | 15.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959081 | AF2-199 C | 50/50 | 37.27 MW | 37.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959082 | AF2-199 E | 50/50 | 24.84 MW | 24.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959091 | AF2-200 C O1 | 50/50 | 74.53 MW | 74.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959092 | AF2-200 E O1 | 50/50 | 49.69 MW | 49.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961011 | AF2-392 C O1 | Adder | 9.4 MW | 7.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961012 | AF2-392 E O1 | Adder | 44.03 MW | 37.43 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961021 | AF2-393 O1 | Adder | 16.03 MW | 13.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961031 | AF2-394 O1 | Adder | 10.69 MW | 9.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274715 | NELSON EC;1C | 50/50 | 9.42 MW | 9.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274716 | NELSON EC;1S | 50/50 | 6.87 MW | 6.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274717 | NELSON EC;2C | 50/50 | 9.49 MW | 9.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274718 | NELSON EC;2S | 50/50 | 6.93 MW | 6.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274761 | LEE CO EC;2U | 50/50 | 4.41 MW | 4.41 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274764 | LEE CO EC;5U | 50/50 | 4.42 MW | 4.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274765 | LEE CO EC;6U | 50/50 | 4.42 MW | 4.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274859 | EASYR;U1 E | Adder | 30.94 MW | 26.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274860 | EASYR;U2 E | Adder | 30.94 MW | 26.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293516 | O-009 E1 | Adder | 19.25 MW | 16.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293517 | O-009 E2 | Adder | 9.78 MW | 8.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293518 | O-009 E3 | Adder | 10.77 MW | 9.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293715 | O-029 E | Adder | 20.58 MW | 17.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293716 | O-029 E | Adder | 11.28 MW | 9.59 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293717 | O-029 E | Adder | 10.37 MW | 8.81 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294401 | BSHIL;1U E | Adder | 9.01 MW | 7.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294410 | BSHIL;2U E | Adder | 9.01 MW | 7.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925581 | AC1-033 C | Adder | 1.48 MW | 1.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925582 | AC1-033 E | Adder | 9.88 MW | 8.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938861 | AE1-114 C O1 | Adder | 4.74 MW | 4.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938862 | AE1-114 E O1 | Adder | 16.17 MW | 13.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939051 | AE1-134 1 | 50/50 | 3.93 MW | 3.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939061 | AE1-134 2 | 50/50 | 3.93 MW | 3.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946151 | AF1-280 C O1 | 50/50 | 44.16 MW | 44.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946152 | AF1-280 E O1 | 50/50 | 20.31 MW | 20.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946321 | AF1-296 C O1 | Adder | 8.54 MW | 7.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946322 | AF1-296 E O1 | Adder | 40.0 MW | 34.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957471 | AF2-041 C | 50/50 | 111.8 MW | 111.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957472 | AF2-041 E | 50/50 | 74.53 MW | 74.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 990901 | L-005 E | Adder | 12.11 MW | 10.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919581 | AA2-030 | 50/50 | 50.62 MW | 50.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946161 | AF1-281 C | 50/50 | 0.97 MW | 0.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946162 | AF1-281 E | 50/50 | 5.48 MW | 5.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951381 | J504 | External Queue | 5.42 MW | 5.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951421 | J514 | External Queue | 3.24 MW | 3.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951511 | J530 C | External Queue | 5.14 MW | 5.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951512 | J530 E | External Queue | 20.57 MW | 20.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 954901 | J963 | External Queue | 1.32 MW | 1.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 955971 | J1084 | External Queue | 29.53 MW | 29.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 956411 | J1131 | External Queue | 15.83 MW | 15.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.25 MW | 0.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 20.24 MW | 20.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.7 MW | 1.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.31 MW | 3.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.0 MW | 12.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.26 MW | 0.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 13.88 MW | 13.88 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 17.08 MW | 17.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 45.05 MW | 45.05 MW |
| Details for BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 926431 | AC1-114 | Adder | -4.1 MW | -3.48 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 927511 | AC1-113 1 | Adder | -2.05 MW | -1.74 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 927521 | AC1-113 2 | Adder | -2.05 MW | -1.74 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958911 | AF2-182 C | Adder | 50.96 MW | 43.31 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958912 | AF2-182 E | Adder | 33.97 MW | 28.88 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958921 | AF2-183 C | Adder | 9.06 MW | 7.7 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958922 | AF2-183 E | Adder | 13.59 MW | 11.55 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959081 | AF2-199 C | Adder | 5.43 MW | 4.62 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959082 | AF2-199 E | Adder | 3.62 MW | 3.08 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959091 | AF2-200 C O1 | Adder | 10.86 MW | 9.23 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959092 | AF2-200 E O1 | Adder | 7.24 MW | 6.16 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961011 | AF2-392 C O1 | Adder | 5.11 MW | 4.34 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961012 | AF2-392 E O1 | Adder | 23.92 MW | 20.34 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961021 | AF2-393 O1 | Adder | 8.71 MW | 7.4 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961031 | AF2-394 O1 | Adder | 5.81 MW | 4.94 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274656 | BYRON ;1U | 50/50 | 101.86 MW | 101.86 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274760 | LEE CO EC;1U | 50/50 | 4.37 MW | 4.37 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274761 | LEE CO EC;2U | 50/50 | 4.37 MW | 4.37 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274763 | LEE CO EC;4U | 50/50 | 4.33 MW | 4.33 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274764 | LEE CO EC;5U | 50/50 | 4.38 MW | 4.38 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274765 | LEE CO EC;6U | 50/50 | 4.38 MW | 4.38 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274766 | LEE CO EC;7U | 50/50 | 4.32 MW | 4.32 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274767 | LEE CO EC;8U | 50/50 | 4.32 MW | 4.32 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274859 | EASYR;U1 E | Adder | 30.66 MW | 26.06 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274860 | EASYR;U2 E | Adder | 30.66 MW | 26.06 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293516 | O-009 E1 | Adder | 10.74 MW | 9.13 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293517 | O-009 E2 | Adder | 5.45 MW | 4.63 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293518 | O-009 E3 | Adder | 6.01 MW | 5.11 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293715 | O-029 E | Adder | 11.48 MW | 9.76 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293716 | O-029 E | Adder | 6.29 MW | 5.35 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293717 | O-029 E | Adder | 5.78 MW | 4.92 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932881 | AC2-115 1 | Adder | -4.1 MW | -3.48 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932891 | AC2-115 2 | Adder | -4.1 MW | -3.48 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932921 | AC2-116 | Adder | -1.43 MW | -1.22 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 939051 | AE1-134 1 | Adder | 2.43 MW | 2.07 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 939061 | AE1-134 2 | Adder | 2.43 MW | 2.07 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946151 | AF1-280 C O1 | Adder | 38.78 MW | 32.97 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946152 | AF1-280 E O1 | Adder | 17.83 MW | 15.16 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946321 | AF1-296 C O1 | Adder | 4.78 MW | 4.06 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946322 | AF1-296 E O1 | Adder | 22.37 MW | 19.01 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 957471 | AF2-041 C | Adder | 16.3 MW | 13.85 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 957472 | AF2-041 E | Adder | 10.86 MW | 9.23 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 919581 | AA2-030 | Adder | 31.29 MW | 26.59 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946161 | AF1-281 C | Adder | 0.85 MW | 0.72 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946162 | AF1-281 E | Adder | 4.81 MW | 4.09 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 276172 | Z1-108 BAT | Adder | 2.09 MW | 1.78 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 920273 | AA2-123 BAT | Adder | 3.41 MW | 2.9 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 943803 | AF1-048 BAT | Adder | 9.14 MW | 7.77 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 954901 | J963 | External Queue | 0.88 MW | 0.88 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 955971 | J1084 | External Queue | 20.17 MW | 20.17 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 956411 | J1131 | External Queue | 10.86 MW | 10.86 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 7.45 MW | 7.45 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.76 MW | 0.76 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.16 MW | 2.16 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.24 MW | 0.24 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.53 MW | 3.53 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.33 MW | 0.33 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.57 MW | 1.57 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.8 MW | 6.8 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.32 MW | 0.32 MW |
| BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 15.79 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.23 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 14.5 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.51 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 2.41 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.52 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 13.33 MW | 11.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 8.27 MW | 7.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 6.71 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 10.5 MW | 8.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 5.16 MW | 4.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 6.98 MW | 5.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.14 MW | 2.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 5.86 MW | 4.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 11.71 MW | 9.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 7.81 MW | 6.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.92 MW | 4.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 14.12 MW | 12.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 17.85 MW | 15.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 11.9 MW | 10.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 4.86 MW | 4.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 3.24 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 5.73 MW | 4.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 3.82 MW | 3.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 12.81 MW | 10.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 16.27 MW | 13.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 7.65 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 5.38 MW | 4.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 3.56 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 16.72 MW | 14.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 1.96 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 17.57 MW | 14.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 11.71 MW | 9.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | Adder | 28.15 MW | 23.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | Adder | 13.25 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 53.8 MW | 45.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 58.79 MW | 49.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 60.57 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 23.09 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 4.75 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 19.91 MW | 16.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 254.71 MW | 216.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.88 MW | 15.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.3 MW | 49.3 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 53.75 MW | 45.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960681 | AF2-359 C | 50/50 | 64.1 MW | 64.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960682 | AF2-359 E | 50/50 | 42.74 MW | 42.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 0.68 MW | 0.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 2.32 MW | 1.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 53.74 MW | 45.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 15.67 MW | 13.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 8.48 MW | 7.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.21 MW | 1.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 14.4 MW | 12.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.56 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.56 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 3.47 MW | 2.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 3.47 MW | 2.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.49 MW | 1.27 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 2.39 MW | 2.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 15.64 MW | 13.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 72.98 MW | 62.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.73 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 1.98 MW | 1.68 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 13.25 MW | 11.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 3.63 MW | 3.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 17.72 MW | 15.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 2.13 MW | 1.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 6.88 MW | 5.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 4.58 MW | 3.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.05 MW | 1.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 8.2 MW | 6.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.45 MW | 2.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 7.35 MW | 6.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.71 MW | 0.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 4.36 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 3.28 MW | 2.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 10.39 MW | 8.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 5.1 MW | 4.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 6.91 MW | 5.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 3.42 MW | 2.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.11 MW | 2.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 9.93 MW | 8.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 6.62 MW | 5.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 9.14 MW | 7.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 6.09 MW | 5.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 3.87 MW | 3.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 11.62 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 7.74 MW | 6.58 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 4.88 MW | 4.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 14.01 MW | 11.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.9 MW | 2.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.9 MW | 2.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 4.36 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 17.7 MW | 15.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 11.8 MW | 10.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.27 MW | 3.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.85 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.28 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960681 | AF2-359 C | 50/50 | 63.92 MW | 63.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960682 | AF2-359 E | 50/50 | 42.61 MW | 42.61 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 4.81 MW | 4.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 3.21 MW | 2.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 5.67 MW | 4.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.78 MW | 3.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 14.94 MW | 12.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.03 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.03 MW | 0.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.19 MW | 1.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.03 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 12.69 MW | 10.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.87 MW | 6.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 15.28 MW | 12.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 16.11 MW | 13.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 7.59 MW | 6.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 4.38 MW | 3.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 1.93 MW | 1.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.68 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 2.03 MW | 1.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 3.31 MW | 2.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 7.51 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 0.67 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 2.3 MW | 1.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 4.97 MW | 4.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 30.55 MW | 25.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 8.32 MW | 7.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 7.68 MW | 6.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 2.75 MW | 2.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 5.33 MW | 4.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 3.55 MW | 3.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 9.6 MW | 8.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 3.53 MW | 3.0 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 16.59 MW | 14.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.94 MW | 1.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.13 MW | 0.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.96 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 17.42 MW | 14.81 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 11.62 MW | 9.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 14.51 MW | 12.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 6.83 MW | 5.8 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 27.9 MW | 23.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 13.13 MW | 11.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 14.94 MW | 12.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.12 MW | 0.95 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 53.36 MW | 45.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 58.39 MW | 49.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 60.06 MW | 51.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932931 | AC2-117 | Adder | 10.49 MW | 8.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 6.47 MW | 5.5 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 22.92 MW | 19.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 4.72 MW | 4.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.86 MW | 4.13 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 19.73 MW | 16.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274806 | UNIV PK N;2U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274808 | UNIV PK N;4U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274809 | UNIV PK N;5U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274811 | UNIV PK N;7U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274812 | UNIV PK N;8U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274814 | UNIV PK N;0U | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274815 | UNIV PK N;XU | 50/50 | 1.85 MW | 1.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 251.5 MW | 213.78 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.06 MW | 3.06 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 15.45 MW | 15.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.79 MW | 10.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.01 MW | 4.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.67 MW | 1.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.67 MW | 15.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.31 MW | 1.31 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 48.24 MW | 48.24 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 15.67 MW | 13.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 8.48 MW | 7.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 14.4 MW | 12.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.56 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.56 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 3.47 MW | 2.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 3.47 MW | 2.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.49 MW | 1.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 2.39 MW | 2.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 15.64 MW | 13.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 72.98 MW | 62.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.73 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 1.98 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 13.25 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 3.63 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 17.72 MW | 15.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 2.13 MW | 1.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 6.88 MW | 5.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 4.58 MW | 3.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.05 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 8.2 MW | 6.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.45 MW | 2.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 7.35 MW | 6.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.71 MW | 0.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 4.36 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 3.28 MW | 2.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 10.39 MW | 8.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 5.1 MW | 4.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 6.91 MW | 5.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 3.42 MW | 2.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.11 MW | 2.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 9.93 MW | 8.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 6.62 MW | 5.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 9.14 MW | 7.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 6.09 MW | 5.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 3.87 MW | 3.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 11.62 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 4.88 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 14.01 MW | 11.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.9 MW | 2.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.9 MW | 2.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 4.36 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 17.7 MW | 15.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 11.8 MW | 10.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.27 MW | 3.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.85 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.28 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 4.81 MW | 4.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 3.21 MW | 2.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 5.67 MW | 4.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.78 MW | 3.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 14.94 MW | 12.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.03 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.03 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.19 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.03 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 12.69 MW | 10.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.87 MW | 6.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 15.28 MW | 12.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 16.11 MW | 13.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 7.59 MW | 6.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 4.38 MW | 3.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 1.93 MW | 1.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.68 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 2.03 MW | 1.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 3.31 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 7.51 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938861 | AE1-114 C O1 | Adder | 3.18 MW | 2.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938862 | AE1-114 E O1 | Adder | 10.84 MW | 9.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 4.97 MW | 4.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 30.55 MW | 25.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 8.32 MW | 7.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 7.68 MW | 6.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 2.75 MW | 2.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 5.33 MW | 4.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 9.6 MW | 8.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 3.53 MW | 3.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 16.59 MW | 14.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.96 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 17.42 MW | 14.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 11.62 MW | 9.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 14.51 MW | 12.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 6.83 MW | 5.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 27.9 MW | 23.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 13.13 MW | 11.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 14.94 MW | 12.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 53.36 MW | 45.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 58.39 MW | 49.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 60.06 MW | 51.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932931 | AC2-117 | Adder | 10.49 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 6.47 MW | 5.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 22.92 MW | 19.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 4.72 MW | 4.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.86 MW | 4.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 19.73 MW | 16.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274806 | UNIV PK N;2U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274808 | UNIV PK N;4U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274809 | UNIV PK N;5U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274811 | UNIV PK N;7U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274812 | UNIV PK N;8U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274814 | UNIV PK N;0U | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274815 | UNIV PK N;XU | 50/50 | 1.85 MW | 1.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 251.5 MW | 213.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.06 MW | 3.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 15.45 MW | 15.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.79 MW | 10.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.01 MW | 4.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.67 MW | 1.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.67 MW | 15.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.31 MW | 1.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 48.24 MW | 48.24 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 15.79 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.27 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 14.5 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.51 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 2.41 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.52 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 13.33 MW | 11.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 8.27 MW | 7.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 6.71 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 10.5 MW | 8.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 5.16 MW | 4.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 6.98 MW | 5.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.14 MW | 2.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 5.86 MW | 4.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 11.71 MW | 9.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 7.81 MW | 6.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.92 MW | 4.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 14.12 MW | 12.0 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 17.85 MW | 15.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 11.9 MW | 10.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 4.86 MW | 4.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 3.24 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 5.73 MW | 4.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 3.82 MW | 3.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 12.81 MW | 10.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 16.27 MW | 13.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 7.65 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 10.92 MW | 9.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 5.38 MW | 4.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 3.56 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 1.96 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 17.57 MW | 14.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 11.71 MW | 9.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | Adder | 28.15 MW | 23.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | Adder | 13.25 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 53.8 MW | 45.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 58.79 MW | 49.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 60.57 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 23.09 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 19.91 MW | 16.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 254.71 MW | 216.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.88 MW | 15.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.44 MW | 10.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.3 MW | 49.3 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 10.91 MW | 9.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 53.75 MW | 45.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 15.78 MW | 13.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.22 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.51 MW | 12.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.57 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.56 MW | 1.33 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.63 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.5 MW | 2.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 0.97 MW | 0.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.24 MW | 1.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.76 MW | 13.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.56 MW | 62.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.34 MW | 11.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.66 MW | 3.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.88 MW | 15.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.92 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.62 MW | 3.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.47 MW | 2.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.4 MW | 6.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.72 MW | 0.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.39 MW | 3.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.7 MW | 5.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.3 MW | 2.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.48 MW | 8.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.15 MW | 4.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.97 MW | 5.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.45 MW | 2.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.13 MW | 2.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.09 MW | 1.78 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.0 MW | 8.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.2 MW | 7.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.13 MW | 5.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.85 MW | 4.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.9 MW | 3.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.8 MW | 6.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.91 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.1 MW | 11.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.95 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.92 MW | 2.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.4 MW | 3.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.84 MW | 15.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.89 MW | 10.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.31 MW | 3.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.85 MW | 4.12 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.72 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.81 MW | 3.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.04 MW | 0.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.21 MW | 1.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.04 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.79 MW | 10.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 7.94 MW | 6.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.41 MW | 13.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.24 MW | 13.81 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.64 MW | 6.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.41 MW | 3.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 1.94 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.68 MW | 0.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.05 MW | 1.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.34 MW | 2.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.58 MW | 6.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.91 MW | 9.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.01 MW | 4.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.76 MW | 26.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.39 MW | 7.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.74 MW | 6.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 0.47 MW | 0.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 2.23 MW | 1.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.01 MW | 1.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.77 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.37 MW | 4.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.58 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.68 MW | 8.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.02 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.7 MW | 14.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.64 MW | 1.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.31 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.06 MW | 1.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.55 MW | 14.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.7 MW | 9.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.65 MW | 12.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.89 MW | 5.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.14 MW | 23.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.24 MW | 11.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274881 | PILOT HIL;1E | Adder | 15.08 MW | 12.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.13 MW | 0.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 53.74 MW | 45.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 58.84 MW | 50.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 60.56 MW | 51.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932931 | AC2-117 | Adder | 10.54 MW | 8.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.45 MW | 5.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.45 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 6.51 MW | 5.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 23.08 MW | 19.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.76 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.88 MW | 16.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274806 | UNIV PK N;2U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274809 | UNIV PK N;5U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274812 | UNIV PK N;8U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274814 | UNIV PK N;0U | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.86 MW | 1.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 253.78 MW | 215.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.08 MW | 3.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.13 MW | 0.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.64 MW | 14.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.92 MW | 0.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.85 MW | 10.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.1 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 15.87 MW | 15.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.43 MW | 10.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.07 MW | 0.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.65 MW | 1.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.56 MW | 0.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 49.26 MW | 49.26 MW |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 290051 | GSG-6; E | Adder | 8.26 MW | 7.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 295109 | WESTBROOK E | Adder | 4.42 MW | 3.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 295111 | SUBLETTE E | Adder | 2.15 MW | 1.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926311 | AC1-109 1 | Adder | 1.2 MW | 1.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926321 | AC1-109 2 | Adder | 1.2 MW | 1.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926331 | AC1-110 1 | 50/50 | 2.56 MW | 2.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926341 | AC1-110 2 | 50/50 | 2.56 MW | 2.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926351 | AC1-111 1 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926361 | AC1-111 2 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926371 | AC1-111 3 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926381 | AC1-111 4 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926391 | AC1-111 5 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926401 | AC1-111 6 | Adder | 0.57 MW | 0.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 926431 | AC1-114 | Adder | 1.07 MW | 0.91 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 927511 | AC1-113 1 | Adder | 0.54 MW | 0.46 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 927521 | AC1-113 2 | Adder | 0.54 MW | 0.46 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 933911 | AD1-013 C | Adder | 1.46 MW | 1.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 933912 | AD1-013 E | Adder | 2.33 MW | 1.98 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 934431 | AD1-067 C | Adder | 0.1 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 934971 | AD1-129 C | Adder | 0.38 MW | 0.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 934972 | AD1-129 E | Adder | 0.25 MW | 0.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 937001 | AD2-134 C | Adder | 2.0 MW | 1.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 937002 | AD2-134 E | Adder | 7.98 MW | 6.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 937311 | AD2-172 C | Adder | 1.21 MW | 1.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 937312 | AD2-172 E | Adder | 1.68 MW | 1.42 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 943121 | AE2-341 C | 50/50 | 10.64 MW | 10.64 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 943122 | AE2-341 E | 50/50 | 5.22 MW | 5.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 943591 | AF1-030 C O1 | 50/50 | 7.08 MW | 7.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 943592 | AF1-030 E O1 | 50/50 | 3.5 MW | 3.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 958911 | AF2-182 C | Adder | 13.37 MW | 11.36 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 958912 | AF2-182 E | Adder | 8.91 MW | 7.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 958921 | AF2-183 C | Adder | 2.38 MW | 2.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 958922 | AF2-183 E | Adder | 3.56 MW | 3.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959081 | AF2-199 C | 50/50 | 9.43 MW | 9.43 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959082 | AF2-199 E | 50/50 | 6.29 MW | 6.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959091 | AF2-200 C O1 | 50/50 | 18.86 MW | 18.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959092 | AF2-200 E O1 | 50/50 | 12.57 MW | 12.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959101 | AF2-201 C O1 | Adder | 2.97 MW | 2.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 959102 | AF2-201 E O1 | Adder | 8.53 MW | 7.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 960381 | AF2-329 | 50/50 | 4.46 MW | 4.46 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 960721 | AF2-363 C O1 | Adder | 4.14 MW | 3.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 960722 | AF2-363 E O1 | Adder | 2.76 MW | 2.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 960751 | AF2-366 C | 50/50 | 5.88 MW | 5.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 960752 | AF2-366 E | 50/50 | 3.92 MW | 3.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 961011 | AF2-392 C O1 | Adder | 2.64 MW | 2.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 961012 | AF2-392 E O1 | Adder | 12.36 MW | 10.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 961021 | AF2-393 O1 | Adder | 4.5 MW | 3.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 961031 | AF2-394 O1 | Adder | 3.0 MW | 2.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 274738 | AURORA EC;3P | 50/50 | 4.5 MW | 4.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 274740 | AURORA EC;4P | 50/50 | 4.5 MW | 4.5 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 274859 | EASYR;U1 E | Adder | 6.92 MW | 5.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 274860 | EASYR;U2 E | Adder | 6.92 MW | 5.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 276167 | Z1-106 E2 | 50/50 | 1.13 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 276168 | Z1-106 E1 | 50/50 | 1.13 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293516 | O-009 E1 | Adder | 5.31 MW | 4.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293517 | O-009 E2 | Adder | 2.7 MW | 2.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293518 | O-009 E3 | Adder | 2.97 MW | 2.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293715 | O-029 E | Adder | 5.67 MW | 4.82 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293716 | O-029 E | Adder | 3.11 MW | 2.64 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 293717 | O-029 E | Adder | 2.86 MW | 2.43 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 294763 | P-046 E | Adder | 4.62 MW | 3.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 916221 | Z1-073 E | Adder | 4.26 MW | 3.62 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 932881 | AC2-115 1 | Adder | 1.07 MW | 0.91 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 932891 | AC2-115 2 | Adder | 1.07 MW | 0.91 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 932921 | AC2-116 | Adder | 0.38 MW | 0.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 938861 | AE1-114 C O1 | Adder | 2.19 MW | 1.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 938862 | AE1-114 E O1 | Adder | 7.49 MW | 6.36 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 939051 | AE1-134 1 | Adder | 0.97 MW | 0.82 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 939061 | AE1-134 2 | Adder | 0.97 MW | 0.82 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 940501 | AE2-035 C | Adder | 1.21 MW | 1.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 940502 | AE2-035 E | Adder | 1.68 MW | 1.42 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 941131 | AE2-107 C | 50/50 | 5.47 MW | 5.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 941132 | AE2-107 E | 50/50 | 3.65 MW | 3.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946151 | AF1-280 C O1 | Adder | 10.18 MW | 8.65 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946152 | AF1-280 E O1 | Adder | 4.68 MW | 3.98 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946321 | AF1-296 C O1 | Adder | 2.18 MW | 1.85 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946322 | AF1-296 E O1 | Adder | 10.2 MW | 8.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946501 | AF1-314 C | Adder | 2.15 MW | 1.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946502 | AF1-314 E | Adder | 10.1 MW | 8.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946671 | AF1-331 | Adder | 1.9 MW | 1.61 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 957471 | AF2-041 C | 50/50 | 28.29 MW | 28.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 957472 | AF2-041 E | 50/50 | 18.86 MW | 18.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 919581 | AA2-030 | Adder | 12.44 MW | 10.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 925302 | AB2-191 E | Adder | 1.09 MW | 0.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 930481 | AB1-089 | Adder | 37.01 MW | 31.46 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946161 | AF1-281 C | Adder | 0.22 MW | 0.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 946162 | AF1-281 E | Adder | 1.26 MW | 1.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 292543 | L-013 2 | 50/50 | 0.57 MW | 0.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 274872 | LEE DEKAL;1U | 50/50 | 0.84 MW | 0.84 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 290108 | LEEDK;1U E | 50/50 | 20.28 MW | 20.28 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 276165 | Z1-106 BAT2 | 50/50 | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 276166 | Z1-106 BAT1 | 50/50 | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 945351 | AF1-200 FTIR | Adder | 203.57 MW | 173.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 957333 | AF2-027 BAT | Adder | 3.31 MW | 2.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | 955971 | J1084 | External Queue | 7.86 MW | 7.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 4.06 MW | 4.06 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.11 MW | 0.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.42 MW | 0.42 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.3 MW | 1.3 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.1 MW | 0.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.92 MW | 1.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.01 MW | 0.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.24 MW | 3.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.01 MW | 4.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.22 MW | 0.22 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002_ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.03 MW | 4.03 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290021 | O50 E | Adder | 20.43 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290051 | GSG-6; E | Adder | 10.84 MW | 9.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 5.8 MW | 4.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.82 MW | 2.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 15.81 MW | 13.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 920272 | AA2-123 E | Adder | 2.55 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926311 | AC1-109 1 | Adder | 1.99 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926321 | AC1-109 2 | Adder | 1.99 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 1.98 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 1.98 MW | 1.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 926431 | AC1-114 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927511 | AC1-113 1 | Adder | 1.24 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 927521 | AC1-113 2 | Adder | 1.24 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933911 | AD1-013 C | Adder | 1.91 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933912 | AD1-013 E | Adder | 3.05 MW | 2.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.58 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934721 | AD1-100 C | Adder | 19.63 MW | 16.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934722 | AD1-100 E | Adder | 91.62 MW | 77.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.63 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937001 | AD2-134 C | Adder | 2.62 MW | 2.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937002 | AD2-134 E | Adder | 10.48 MW | 8.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937311 | AD2-172 C | Adder | 2.55 MW | 2.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937312 | AD2-172 E | Adder | 3.52 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 9.58 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 5.18 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942991 | AE2-321 C | Adder | 8.51 MW | 7.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 942992 | AE2-321 E | Adder | 4.19 MW | 3.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943121 | AE2-341 C | Adder | 13.24 MW | 11.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943122 | AE2-341 E | Adder | 6.5 MW | 5.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 8.81 MW | 7.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 4.36 MW | 3.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943801 | AF1-048 C | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 943802 | AF1-048 E | Adder | 2.65 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958481 | AF2-142 C | Adder | 10.9 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958491 | AF2-143 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959081 | AF2-199 C | Adder | 7.45 MW | 6.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959082 | AF2-199 E | Adder | 4.97 MW | 4.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 14.9 MW | 12.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 9.94 MW | 8.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 6.24 MW | 5.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 17.92 MW | 15.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960381 | AF2-329 | Adder | 5.56 MW | 4.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960581 | AF2-349 C | Adder | 22.66 MW | 19.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960582 | AF2-349 E | Adder | 15.1 MW | 12.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 6.15 MW | 5.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 4.1 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960751 | AF2-366 C | Adder | 7.25 MW | 6.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 960752 | AF2-366 E | Adder | 4.83 MW | 4.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274654 | BRAIDWOOD;1U | 50/50 | 30.03 MW | 30.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.21 MW | 29.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276167 | Z1-106 E2 | Adder | 1.32 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276168 | Z1-106 E1 | Adder | 1.32 MW | 1.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276170 | Z1-108 E | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293061 | N-015 E | Adder | 16.33 MW | 13.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 293645 | O22 E2 | 50/50 | 23.75 MW | 23.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294392 | P-010 E | Adder | 20.74 MW | 17.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 294763 | P-046 E | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 916221 | Z1-073 E | Adder | 5.59 MW | 4.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932881 | AC2-115 1 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932891 | AC2-115 2 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 8.91 MW | 7.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 36.29 MW | 30.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940501 | AE2-035 C | Adder | 2.55 MW | 2.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940502 | AE2-035 E | Adder | 3.52 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941131 | AE2-107 C | Adder | 6.81 MW | 5.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941132 | AE2-107 E | Adder | 4.54 MW | 3.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 12.14 MW | 10.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946501 | AF1-314 C | Adder | 4.52 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946502 | AF1-314 E | Adder | 21.22 MW | 18.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946661 | AF1-330 C | Adder | 2.09 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 946671 | AF1-331 | Adder | 2.48 MW | 2.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957332 | AF2-027 E | Adder | 3.92 MW | 3.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957471 | AF2-041 C | Adder | 22.36 MW | 19.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 957472 | AF2-041 E | Adder | 14.9 MW | 12.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 16.38 MW | 13.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 7.71 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958021 | AF2-096 C | 50/50 | 40.33 MW | 40.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 958022 | AF2-096 E | 50/50 | 18.98 MW | 18.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 925302 | AB2-191 E | Adder | 1.44 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930481 | AB1-089 | Adder | 68.28 MW | 58.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930741 | AB1-122 1O1 | Adder | 73.42 MW | 62.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 930751 | AB1-122 2O1 | Adder | 78.73 MW | 66.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 8.3 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 8.29 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938851 | AE1-113 C | Adder | 8.43 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 938852 | AE1-113 E | Adder | 29.88 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 5.94 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 6.37 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 25.21 MW | 21.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 324.28 MW | 275.64 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.91 MW | 3.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.19 MW | 1.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 14.0 MW | 14.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.26 MW | 20.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.2 MW | 13.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.29 MW | 2.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.23 MW | 56.23 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 20.33 MW | 17.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 10.73 MW | 9.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 5.75 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 2.79 MW | 2.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.78 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 4.45 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 1.22 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 1.22 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.89 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 3.02 MW | 2.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.56 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 19.56 MW | 16.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 91.29 MW | 77.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.34 MW | 1.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 15.67 MW | 13.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 0.59 MW | 0.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 8.56 MW | 7.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 5.7 MW | 4.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 10.38 MW | 8.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937311 | AD2-172 C | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937312 | AD2-172 E | Adder | 3.49 MW | 2.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 3.18 MW | 2.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 9.53 MW | 8.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 5.16 MW | 4.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 8.44 MW | 7.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 4.16 MW | 3.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 13.07 MW | 11.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 6.42 MW | 5.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 8.69 MW | 7.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 4.3 MW | 3.65 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 3.94 MW | 3.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.63 MW | 2.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 10.81 MW | 9.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 7.38 MW | 6.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 4.92 MW | 4.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 9.84 MW | 8.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 6.19 MW | 5.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 17.77 MW | 15.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | 50/50 | 2.99 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | 50/50 | 4.48 MW | 4.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | 50/50 | 2.99 MW | 2.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | 50/50 | 4.48 MW | 4.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 5.48 MW | 4.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 22.46 MW | 19.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 14.97 MW | 12.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 7.18 MW | 6.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 4.79 MW | 4.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 6.09 MW | 5.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 7.17 MW | 6.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 4.78 MW | 4.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274654 | BRAIDWOOD;1U | 50/50 | 29.83 MW | 29.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274655 | BRAIDWOOD;2U | 50/50 | 29.02 MW | 29.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274751 | CRETE EC ;1U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274752 | CRETE EC ;2U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274753 | CRETE EC ;3U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274754 | CRETE EC ;4U | 50/50 | 6.5 MW | 6.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.3 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.3 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 2.5 MW | 2.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.57 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 16.16 MW | 13.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | 50/50 | 12.19 MW | 12.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | 50/50 | 23.66 MW | 23.66 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 20.53 MW | 17.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294763 | P-046 E | Adder | 9.63 MW | 8.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 5.54 MW | 4.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 2.45 MW | 2.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 9.71 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 5.88 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 36.14 MW | 30.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 10.47 MW | 8.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 9.66 MW | 8.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940501 | AE2-035 C | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940502 | AE2-035 E | Adder | 3.49 MW | 2.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 6.74 MW | 5.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 12.08 MW | 10.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 8.05 MW | 6.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946501 | AF1-314 C | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 21.04 MW | 17.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.45 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 2.45 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.51 MW | 1.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 1.29 MW | 1.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 22.15 MW | 18.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 16.27 MW | 13.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 7.66 MW | 6.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | 50/50 | 40.09 MW | 40.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | 50/50 | 18.87 MW | 18.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.42 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 67.68 MW | 57.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 73.22 MW | 62.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 78.27 MW | 66.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 8.27 MW | 7.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 8.25 MW | 7.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 8.39 MW | 7.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 29.73 MW | 25.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 5.92 MW | 5.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 6.33 MW | 5.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 24.95 MW | 21.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 317.6 MW | 269.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.88 MW | 3.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 18.31 MW | 18.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.14 MW | 1.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.93 MW | 13.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.88 MW | 3.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.15 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.06 MW | 20.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.16 MW | 13.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.02 MW | 2.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.69 MW | 0.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.3 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 55.23 MW | 55.23 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 20.42 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.79 MW | 9.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.78 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.04 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 91.66 MW | 77.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.43 MW | 8.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.19 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.18 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.15 MW | 11.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.46 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.75 MW | 7.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.33 MW | 3.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.97 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 10.86 MW | 9.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.42 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 4.95 MW | 4.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.9 MW | 8.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 6.22 MW | 5.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 17.85 MW | 15.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.52 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.58 MW | 19.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.81 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 16.25 MW | 13.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 20.64 MW | 17.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 9.68 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.57 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.77 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.92 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 36.31 MW | 30.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.52 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 21.14 MW | 17.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.27 MW | 18.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 16.37 MW | 13.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 7.7 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.27 MW | 40.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930481 | AB1-089 | Adder | 68.04 MW | 57.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 73.64 MW | 62.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 78.69 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.3 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E | Adder | 29.87 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.96 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.09 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 320.0 MW | 272.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.22 MW | 20.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.17 MW | 13.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.07 MW | 56.07 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 20.42 MW | 17.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 10.79 MW | 9.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 5.78 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926311 | AC1-109 1 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926321 | AC1-109 2 | Adder | 1.98 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 3.03 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 91.67 MW | 77.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 19.98 MW | 16.99 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.41 MW | 2.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 8.6 MW | 7.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 10.43 MW | 8.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 5.19 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 4.18 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 13.15 MW | 11.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 6.46 MW | 5.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 8.74 MW | 7.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 4.33 MW | 3.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.97 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 10.86 MW | 9.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 7.42 MW | 6.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 4.95 MW | 4.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 9.89 MW | 8.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 6.22 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 5.52 MW | 4.69 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 22.58 MW | 19.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 2.52 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 1.68 MW | 1.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 6.13 MW | 5.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 4.81 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 16.25 MW | 13.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 20.64 MW | 17.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 9.68 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 5.57 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.73 MW | 3.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 8.92 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 36.31 MW | 30.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 3.51 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 4.51 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 21.14 MW | 17.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.61 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 22.26 MW | 18.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 14.84 MW | 12.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 40.27 MW | 40.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930481 | AB1-089 | Adder | 68.03 MW | 57.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930741 | AB1-122 1O1 | Adder | 73.63 MW | 62.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930751 | AB1-122 2O1 | Adder | 78.68 MW | 66.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 8.3 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E | Adder | 29.87 MW | 25.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 25.08 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 319.88 MW | 271.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.7 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.19 MW | 3.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.22 MW | 20.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.17 MW | 13.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.06 MW | 56.06 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290021 | O50 E | Adder | 20.41 MW | 17.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.78 MW | 9.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.77 MW | 4.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.81 MW | 2.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 15.82 MW | 13.44 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.97 MW | 1.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.47 MW | 3.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.48 MW | 3.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.61 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.03 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.57 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.14 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.66 MW | 16.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934722 | AD1-100 E | Adder | 91.76 MW | 78.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.74 MW | 13.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936461 | AD2-060 | Adder | 0.6 MW | 0.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.73 MW | 4.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.42 MW | 8.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937312 | AD2-172 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.19 MW | 2.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.57 MW | 8.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.84 MW | 0.72 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.18 MW | 4.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.48 MW | 7.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.17 MW | 3.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.13 MW | 11.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.45 MW | 5.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.73 MW | 7.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.32 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.96 MW | 3.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.91 MW | 9.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.27 MW | 6.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958491 | AF2-143 C | Adder | 10.85 MW | 9.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.24 MW | 6.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.41 MW | 6.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959082 | AF2-199 E | Adder | 4.94 MW | 4.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.83 MW | 12.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.88 MW | 8.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 6.21 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 17.84 MW | 15.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.0 MW | 3.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.5 MW | 4.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.51 MW | 4.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.56 MW | 19.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.04 MW | 12.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.82 MW | 4.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.44 MW | 1.23 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.12 MW | 5.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.98 MW | 29.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 29.17 MW | 29.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.52 MW | 6.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.53 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 1.03 MW | 1.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.31 MW | 1.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276169 | Z1-107 E | Adder | 2.52 MW | 2.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.58 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293061 | N-015 E | Adder | 16.24 MW | 13.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.24 MW | 12.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 23.76 MW | 23.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294392 | P-010 E | Adder | 20.63 MW | 17.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294763 | P-046 E | Adder | 9.67 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.56 MW | 4.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.46 MW | 2.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.86 MW | 0.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.91 MW | 7.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.91 MW | 5.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 36.29 MW | 30.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.52 MW | 8.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.71 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940502 | AE2-035 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.51 MW | 3.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.14 MW | 10.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.09 MW | 6.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946502 | AF1-314 E | Adder | 21.12 MW | 17.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.08 MW | 1.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.46 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.6 MW | 2.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.91 MW | 3.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.29 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.24 MW | 18.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957472 | AF2-041 E | Adder | 14.83 MW | 12.6 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 16.38 MW | 13.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 7.71 MW | 6.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.28 MW | 40.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 18.95 MW | 18.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.43 MW | 1.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930481 | AB1-089 | Adder | 67.96 MW | 57.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 73.52 MW | 62.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 78.64 MW | 66.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.31 MW | 7.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.29 MW | 7.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938851 | AE1-113 C | Adder | 8.42 MW | 7.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938852 | AE1-113 E | Adder | 29.85 MW | 25.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.06 MW | 21.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.01 MW | 0.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 319.26 MW | 271.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.28 MW | 2.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 17.68 MW | 17.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.04 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.9 MW | 3.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.98 MW | 13.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.13 MW | 0.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.18 MW | 3.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 20.21 MW | 20.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.16 MW | 13.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.25 MW | 0.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 56.01 MW | 56.01 MW |
| Details for LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 272364 | ESS H440N ;R | 80/20 | 0.28 MW | 0.28 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 295108 | WESTBROOK C | 80/20 | 0.1 MW | 0.1 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 295110 | SUBLETTE C | 80/20 | 0.04 MW | 0.04 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 919221 | AA1-146 | 80/20 | 10.64 MW | 10.64 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 926431 | AC1-114 | Adder | -3.08 MW | -2.62 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 926821 | AC1-168 C O1 | 80/20 | 0.68 MW | 0.68 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927201 | AC1-214 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927511 | AC1-113 1 | Adder | -1.54 MW | -1.31 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927521 | AC1-113 2 | Adder | -1.54 MW | -1.31 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 933911 | AD1-013 C | 80/20 | 1.11 MW | 1.11 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 934051 | AD1-031 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 934431 | AD1-067 C | 80/20 | 0.08 MW | 0.08 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 937001 | AD2-134 C | 80/20 | 1.62 MW | 1.62 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 958911 | AF2-182 C | 80/20 | 87.85 MW | 87.85 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 958921 | AF2-183 C | 80/20 | 15.62 MW | 15.62 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 959081 | AF2-199 C | 80/20 | 23.43 MW | 23.43 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 959091 | AF2-200 C O1 | 80/20 | 46.85 MW | 46.85 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 961011 | AF2-392 C O1 | 80/20 | 10.85 MW | 10.85 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 961021 | AF2-393 O1 | 80/20 | 18.5 MW | 18.5 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 961031 | AF2-394 O1 | 80/20 | 12.33 MW | 12.33 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274662 | QUAD CITI;1U | 80/20 | 43.67 MW | 43.67 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274663 | QUAD CITI;2U | 80/20 | 43.76 MW | 43.76 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274699 | CORDOVA ;1C | 80/20 | 7.68 MW | 7.68 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274700 | CORDOVA ;2C | 80/20 | 7.68 MW | 7.68 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274701 | CORDOVA ;1S | 80/20 | 8.65 MW | 8.65 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274715 | NELSON EC;1C | 80/20 | 11.41 MW | 11.41 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274716 | NELSON EC;1S | 80/20 | 8.32 MW | 8.32 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274717 | NELSON EC;2C | 80/20 | 11.5 MW | 11.5 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274718 | NELSON EC;2S | 80/20 | 8.4 MW | 8.4 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274760 | LEE CO EC;1U | 80/20 | 7.26 MW | 7.26 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274761 | LEE CO EC;2U | 80/20 | 7.26 MW | 7.26 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274762 | LEE CO EC;3U | 80/20 | 7.16 MW | 7.16 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274763 | LEE CO EC;4U | 80/20 | 7.19 MW | 7.19 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274764 | LEE CO EC;5U | 80/20 | 7.28 MW | 7.28 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274765 | LEE CO EC;6U | 80/20 | 7.28 MW | 7.28 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274766 | LEE CO EC;7U | 80/20 | 7.17 MW | 7.17 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274767 | LEE CO EC;8U | 80/20 | 7.17 MW | 7.17 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274848 | CAMPGROVE;RU | 80/20 | 0.63 MW | 0.63 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274849 | CRESCENT ;1U | 80/20 | 0.19 MW | 0.19 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274851 | PROVIDENC;RU | 80/20 | 0.29 MW | 0.29 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274855 | GSG-6 ;RU | 80/20 | 0.29 MW | 0.29 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274857 | BIG SKY ;U1 | 80/20 | 2.21 MW | 2.21 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274858 | BIG SKY ;U2 | 80/20 | 2.21 MW | 2.21 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274877 | BISHOP HL;1U | 80/20 | 0.47 MW | 0.47 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274878 | BISHOP HL;2U | 80/20 | 0.47 MW | 0.47 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 276156 | O-029 C | 80/20 | 0.53 MW | 0.53 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 276157 | O-029 C | 80/20 | 0.57 MW | 0.57 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 276158 | O-029 C | 80/20 | 1.04 MW | 1.04 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 293513 | O-009 C1 | 80/20 | 0.97 MW | 0.97 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 293514 | O-009 C2 | 80/20 | 0.49 MW | 0.49 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 293515 | O-009 C3 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 925581 | AC1-033 C | 80/20 | 1.75 MW | 1.75 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 932881 | AC2-115 1 | Adder | -3.08 MW | -2.62 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 932891 | AC2-115 2 | Adder | -3.08 MW | -2.62 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 932921 | AC2-116 | Adder | -1.08 MW | -0.92 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 938861 | AE1-114 C O1 | 80/20 | 2.72 MW | 2.72 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 939051 | AE1-134 1 | 80/20 | 4.76 MW | 4.76 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 939061 | AE1-134 2 | 80/20 | 4.76 MW | 4.76 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946151 | AF1-280 C O1 | 80/20 | 66.87 MW | 66.87 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946321 | AF1-296 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946671 | AF1-331 | 80/20 | 1.44 MW | 1.44 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957471 | AF2-041 C | 80/20 | 70.28 MW | 70.28 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957751 | AF2-069 C | 80/20 | 0.24 MW | 0.24 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 957761 | AF2-070 C | 80/20 | 0.35 MW | 0.35 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 276160 | W4-084 | 80/20 | 0.15 MW | 0.15 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 919581 | AA2-030 | 80/20 | 61.32 MW | 61.32 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946541 | AF1-318 C O1 | 80/20 | 4.23 MW | 4.23 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 946161 | AF1-281 C | 80/20 | 1.46 MW | 1.46 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 958341 | AF2-128 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 925301 | AB2-191 | 80/20 | 0.11 MW | 0.11 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927531 | AC1-185 1 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927541 | AC1-185 2 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927551 | AC1-185 3 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927561 | AC1-185 4 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927571 | AC1-185 5 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927581 | AC1-185 6 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927591 | AC1-185 7 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 927601 | AC1-185 8 | 80/20 | 0.55 MW | 0.55 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 274850 | MENDOTA H;RU | 80/20 | 0.07 MW | 0.07 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 951421 | J514 | External Queue | 3.91 MW | 3.91 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 954901 | J963 | External Queue | 1.64 MW | 1.64 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 955971 | J1084 | External Queue | 37.19 MW | 37.19 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | 956411 | J1131 | External Queue | 19.98 MW | 19.98 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.19 MW | 0.19 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.42 MW | 0.42 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 23.13 MW | 23.13 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.82 MW | 2.82 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 4.84 MW | 4.84 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.52 MW | 14.52 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 10.03 MW | 10.03 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 17.64 MW | 17.64 MW |
| LEE CO EC;BP-BYRON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R-B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 22.62 MW | 22.62 MW |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 0.33 MW | 0.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.11 MW | 0.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.05 MW | 0.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 2.01 MW | 2.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926331 | AC1-110 1 | 80/20 | 2.39 MW | 2.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926341 | AC1-110 2 | 80/20 | 2.39 MW | 2.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926351 | AC1-111 1 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926361 | AC1-111 2 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926371 | AC1-111 3 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926381 | AC1-111 4 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926391 | AC1-111 5 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 926401 | AC1-111 6 | Adder | 0.37 MW | 0.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.32 MW | 1.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.09 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.81 MW | 1.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 943121 | AE2-341 C | 80/20 | 9.29 MW | 9.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 943591 | AF1-030 C O1 | 80/20 | 6.18 MW | 6.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 12.28 MW | 12.28 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 2.18 MW | 2.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959081 | AF2-199 C | 80/20 | 9.07 MW | 9.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959091 | AF2-200 C O1 | 80/20 | 18.13 MW | 18.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | Adder | 2.64 MW | 2.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960381 | AF2-329 | 80/20 | 3.9 MW | 3.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 3.7 MW | 3.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 960751 | AF2-366 C | 80/20 | 5.29 MW | 5.29 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 4.17 MW | 4.17 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.78 MW | 2.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 2.15 MW | 2.15 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.57 MW | 1.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 2.17 MW | 2.17 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.59 MW | 1.59 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274738 | AURORA EC;3P | 80/20 | 4.2 MW | 4.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274740 | AURORA EC;4P | 80/20 | 4.2 MW | 4.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 0.89 MW | 0.89 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274818 | ELGIN EC ;1P | 80/20 | 1.57 MW | 1.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274820 | ELGIN EC ;2P | 80/20 | 1.57 MW | 1.57 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.33 MW | 0.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | Adder | 1.98 MW | 1.69 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 0.9 MW | 0.9 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 941131 | AE2-107 C | 80/20 | 4.95 MW | 4.95 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 9.34 MW | 9.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | Adder | 2.02 MW | 1.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | Adder | 1.91 MW | 1.62 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.72 MW | 1.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 957471 | AF2-041 C | 80/20 | 27.2 MW | 27.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 276160 | W4-084 | 80/20 | 0.04 MW | 0.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 | 80/20 | 11.58 MW | 11.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 930481 | AB1-089 | Adder | 31.83 MW | 27.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 292543 | L-013 2 | 80/20 | 0.47 MW | 0.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 925301 | AB2-191 | 80/20 | 0.12 MW | 0.12 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 0.76 MW | 0.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.08 MW | 0.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | 80/20 | 140.94 MW | 140.94 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.03 MW | 0.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 3.69 MW | 3.69 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.39 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.11 MW | 0.11 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.76 MW | 1.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.03 MW | 0.03 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.97 MW | 2.97 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.71 MW | 3.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.2 MW | 0.2 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o Base Case | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.03 MW | 4.03 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 22.21 MW | 18.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 12.0 MW | 10.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 6.43 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295111 | SUBLETTE E | Adder | 3.12 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 910542 | X3-005 E | Adder | 1.0 MW | 0.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 18.65 MW | 15.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 2.8 MW | 2.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926311 | AC1-109 1 | Adder | 2.18 MW | 1.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926321 | AC1-109 2 | Adder | 2.18 MW | 1.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 2.18 MW | 1.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926351 | AC1-111 1 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926361 | AC1-111 2 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926371 | AC1-111 3 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926381 | AC1-111 4 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926391 | AC1-111 5 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926401 | AC1-111 6 | Adder | 0.87 MW | 0.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926431 | AC1-114 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 4.82 MW | 4.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 4.82 MW | 4.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927511 | AC1-113 1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927521 | AC1-113 2 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 2.11 MW | 1.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 3.38 MW | 2.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 1.06 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.74 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934431 | AD1-067 C | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.63 MW | 0.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 22.37 MW | 19.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 104.38 MW | 88.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 1.04 MW | 0.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.69 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.68 MW | 2.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 17.93 MW | 15.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 5.4 MW | 4.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 26.37 MW | 22.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 3.18 MW | 2.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 9.66 MW | 8.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 6.44 MW | 5.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 2.9 MW | 2.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 11.61 MW | 9.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 3.47 MW | 2.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 10.41 MW | 8.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.96 MW | 0.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 5.91 MW | 5.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 9.38 MW | 7.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 4.62 MW | 3.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 14.62 MW | 12.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 7.18 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 9.72 MW | 8.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 4.81 MW | 4.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 4.38 MW | 3.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 12.86 MW | 10.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 8.58 MW | 7.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 12.37 MW | 10.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 8.24 MW | 7.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 8.22 MW | 6.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 5.48 MW | 4.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 16.44 MW | 13.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 10.96 MW | 9.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959101 | AF2-201 C O1 | Adder | 1.24 MW | 1.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 3.57 MW | 3.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 6.13 MW | 5.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 24.98 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 16.66 MW | 14.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 9.53 MW | 8.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 6.35 MW | 5.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.91 MW | 1.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 6.8 MW | 5.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 4.53 MW | 3.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 8.0 MW | 6.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 5.34 MW | 4.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 14.66 MW | 12.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 21.98 MW | 18.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274724 | RIVER EC ;11 | 50/50 | 5.37 MW | 5.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274788 | SE CHICAG;5U | 50/50 | 7.29 MW | 7.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274789 | SE CHICAG;6U | 50/50 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274790 | SE CHICAG;7U | 50/50 | 7.4 MW | 7.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274791 | SE CHICAG;8U | 50/50 | 7.4 MW | 7.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274792 | SE CHICAG;9U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274793 | SE CHICAG;0U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274794 | SE CHICAG;1U | Adder | 7.31 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274795 | SE CHICAG;2U | 50/50 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 22.24 MW | 18.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276167 | Z1-106 E2 | Adder | 1.45 MW | 1.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276168 | Z1-106 E1 | Adder | 1.45 MW | 1.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276169 | Z1-107 E | Adder | 3.02 MW | 2.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 2.85 MW | 2.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 17.51 MW | 14.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 11.91 MW | 10.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 23.13 MW | 19.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 22.24 MW | 18.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932881 | AC2-115 1 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932891 | AC2-115 2 | Adder | 2.73 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 932921 | AC2-116 | Adder | 0.96 MW | 0.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 3.02 MW | 2.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 4.92 MW | 4.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 10.49 MW | 8.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 9.59 MW | 8.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 41.36 MW | 35.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 11.76 MW | 9.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 10.85 MW | 9.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939401 | AE1-172 C O1 | Adder | 6.08 MW | 5.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939402 | AE1-172 E O1 | Adder | 28.5 MW | 24.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 7.52 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 5.02 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 13.57 MW | 11.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 9.04 MW | 7.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 2.3 MW | 1.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.5 MW | 0.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 2.74 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 2.86 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 4.3 MW | 3.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957371 | AF2-031 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957372 | AF2-031 E O1 | 50/50 | 2.29 MW | 2.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 1.37 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 24.67 MW | 20.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 16.44 MW | 13.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 21.6 MW | 18.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 10.17 MW | 8.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 38.54 MW | 32.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 18.14 MW | 15.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274881 | PILOT HIL;1E | Adder | 22.24 MW | 18.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 925302 | AB2-191 E | Adder | 1.59 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930481 | AB1-089 | Adder | 75.42 MW | 64.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930741 | AB1-122 1O1 | Adder | 82.1 MW | 69.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930751 | AB1-122 2O1 | Adder | 84.71 MW | 72.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 8.93 MW | 7.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 8.92 MW | 7.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C | Adder | 9.16 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E | Adder | 32.49 MW | 27.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 6.64 MW | 5.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 6.85 MW | 5.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 27.87 MW | 23.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276165 | Z1-106 BAT2 | Adder | 0.01 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276166 | Z1-106 BAT1 | Adder | 0.01 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276171 | Z1-107 BAT | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 353.64 MW | 300.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.32 MW | 4.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 29.02 MW | 29.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.31 MW | 1.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.35 MW | 2.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 15.49 MW | 15.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 11.6 MW | 11.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.39 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 22.07 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.38 MW | 15.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.04 MW | 0.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 78.25 MW | 78.25 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290021 | O50 E | Adder | 22.71 MW | 19.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290051 | GSG-6; E | Adder | 12.29 MW | 10.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 6.58 MW | 5.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 3.2 MW | 2.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 910542 | X3-005 E | Adder | 1.03 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 19.14 MW | 16.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.87 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926311 | AC1-109 1 | Adder | 2.24 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926321 | AC1-109 2 | Adder | 2.24 MW | 1.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 2.24 MW | 1.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 2.24 MW | 1.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926351 | AC1-111 1 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926361 | AC1-111 2 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926371 | AC1-111 3 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926381 | AC1-111 4 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926391 | AC1-111 5 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926401 | AC1-111 6 | Adder | 0.9 MW | 0.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 926431 | AC1-114 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.96 MW | 4.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.96 MW | 4.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927511 | AC1-113 1 | Adder | 1.4 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 927521 | AC1-113 2 | Adder | 1.4 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.46 MW | 2.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933931 | AD1-016 C | Adder | 1.09 MW | 0.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.78 MW | 1.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934431 | AD1-067 C | Adder | 0.15 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.65 MW | 0.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934721 | AD1-100 C | Adder | 23.03 MW | 19.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934722 | AD1-100 E | Adder | 107.46 MW | 91.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.71 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.74 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 18.33 MW | 15.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 5.57 MW | 4.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 27.2 MW | 23.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936461 | AD2-060 | Adder | 3.28 MW | 2.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 9.88 MW | 8.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 6.59 MW | 5.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937002 | AD2-134 E | Adder | 11.88 MW | 10.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.55 MW | 3.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 10.65 MW | 9.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.98 MW | 0.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 6.04 MW | 5.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942991 | AE2-321 C | Adder | 9.61 MW | 8.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.73 MW | 4.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943121 | AE2-341 C | Adder | 15.03 MW | 12.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943122 | AE2-341 E | Adder | 7.38 MW | 6.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 10.0 MW | 8.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.95 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943801 | AF1-048 C | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 943802 | AF1-048 E | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958481 | AF2-142 C | Adder | 13.2 MW | 11.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958482 | AF2-142 E | Adder | 8.8 MW | 7.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958491 | AF2-143 C | Adder | 12.64 MW | 10.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958492 | AF2-143 E | Adder | 8.43 MW | 7.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959081 | AF2-199 C | Adder | 8.42 MW | 7.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959082 | AF2-199 E | Adder | 5.61 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 16.83 MW | 14.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 11.22 MW | 9.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 1.27 MW | 1.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 3.65 MW | 3.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959351 | AF2-226 C | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 959352 | AF2-226 E | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960281 | AF2-319 C | Adder | 3.0 MW | 2.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960282 | AF2-319 E | Adder | 4.49 MW | 3.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960381 | AF2-329 | Adder | 6.31 MW | 5.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960581 | AF2-349 C | Adder | 25.59 MW | 21.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960582 | AF2-349 E | Adder | 17.06 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 9.83 MW | 8.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 6.55 MW | 5.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 1.31 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.97 MW | 1.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.96 MW | 5.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.64 MW | 3.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960751 | AF2-366 C | Adder | 8.21 MW | 6.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 960752 | AF2-366 E | Adder | 5.47 MW | 4.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961501 | AF2-441 C O1 | Adder | 15.13 MW | 12.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 961502 | AF2-441 E O1 | Adder | 22.69 MW | 19.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274724 | RIVER EC ;11 | 50/50 | 5.55 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274788 | SE CHICAG;5U | 50/50 | 7.53 MW | 7.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274789 | SE CHICAG;6U | 50/50 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274790 | SE CHICAG;7U | 50/50 | 7.65 MW | 7.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274791 | SE CHICAG;8U | 50/50 | 7.65 MW | 7.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274792 | SE CHICAG;9U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274793 | SE CHICAG;0U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274794 | SE CHICAG;1U | Adder | 7.56 MW | 6.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274795 | SE CHICAG;2U | 50/50 | 7.56 MW | 7.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 22.94 MW | 19.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276167 | Z1-106 E2 | Adder | 1.49 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276168 | Z1-106 E1 | Adder | 1.49 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276169 | Z1-107 E | Adder | 3.11 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.93 MW | 2.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293061 | N-015 E | Adder | 18.02 MW | 15.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293644 | O22 E1 | Adder | 12.22 MW | 10.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 293645 | O22 E2 | Adder | 23.73 MW | 20.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 294392 | P-010 E | Adder | 22.89 MW | 19.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 916221 | Z1-073 E | Adder | 6.34 MW | 5.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932881 | AC2-115 1 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932891 | AC2-115 2 | Adder | 2.79 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 932921 | AC2-116 | Adder | 0.98 MW | 0.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933411 | AC2-154 C | Adder | 3.11 MW | 2.65 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 933412 | AC2-154 E | Adder | 5.08 MW | 4.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 10.77 MW | 9.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 9.85 MW | 8.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 6.88 MW | 5.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 42.29 MW | 35.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 12.12 MW | 10.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 11.18 MW | 9.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 6.2 MW | 5.27 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 29.08 MW | 24.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941131 | AE2-107 C | Adder | 7.71 MW | 6.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941132 | AE2-107 E | Adder | 5.14 MW | 4.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 13.98 MW | 11.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 9.32 MW | 7.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.36 MW | 2.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.52 MW | 0.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.94 MW | 2.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957332 | AF2-027 E | Adder | 4.41 MW | 3.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957371 | AF2-031 C O1 | 50/50 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957372 | AF2-031 E O1 | 50/50 | 2.37 MW | 2.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.65 MW | 1.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.41 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957471 | AF2-041 C | Adder | 25.25 MW | 21.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 957472 | AF2-041 E | Adder | 16.83 MW | 14.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 22.28 MW | 18.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 10.49 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958021 | AF2-096 C | Adder | 39.77 MW | 33.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 958022 | AF2-096 E | Adder | 18.72 MW | 15.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 274881 | PILOT HIL;1E | Adder | 22.94 MW | 19.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 925302 | AB2-191 E | Adder | 1.63 MW | 1.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930481 | AB1-089 | Adder | 77.19 MW | 65.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930741 | AB1-122 1O1 | Adder | 83.76 MW | 71.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 930751 | AB1-122 2O1 | Adder | 86.99 MW | 73.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 9.17 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 9.16 MW | 7.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938851 | AE1-113 C | Adder | 9.37 MW | 7.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 938852 | AE1-113 E | Adder | 33.21 MW | 28.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 6.77 MW | 5.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 28.56 MW | 24.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276165 | Z1-106 BAT2 | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276166 | Z1-106 BAT1 | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 276171 | Z1-107 BAT | Adder | 0.02 MW | 0.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 364.98 MW | 310.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 25.05 MW | 25.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 15.77 MW | 15.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.18 MW | 7.18 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 22.98 MW | 22.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.35 MW | 15.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.68 MW | 1.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 83.08 MW | 83.08 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| n6824 | Mitigate sag on the line and replace a 345kV circuit breaker at Cherry Valley | $12,200,000 | |
| n5254 | Reconductor Bryon - Lee County 345 kV Line | $17,200,000 | |
| n7023.1 | Reconductor Electric Junction - Lombard L11124 345 kV Line | $14,600,000 | |
| n6639.1 | Replace station conductor at TSS111 EJ, replace MOD. Relay upgrades, re-conductor part of the line. | $22,300,000 | |
| n6639.3 | Install BT 2-3 345KV CB AT STATION 6. | $8,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-200 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.