AF2-183 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:04
Nelson-Lee County 345 kV
32.0 MW Capacity / 80.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-183 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Storage generating facility located in the ComEd zone — Lee County, Illinois. This project is an increase to the Interconnection Customer's original project, which will share the same point of interconnection. The AF2-183 queue position is a 80.0 MW uprate (32.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 600.0 MW.
Project Information | |
---|---|
Queue Number | AF2-183 |
Project Name | Nelson-Lee County 345 kV |
Developer Name | Duke Energy Renewables Solar, LLC |
State | Illinois |
County | Lee |
Transmission Owner | ComEd |
MFO | 600.0 MW |
MWE | 80.0 MW |
MWC | 32.0 MW |
Fuel Type | Storage |
Basecase Study Year | 2023 |
Point of Interconnection
AF2-183 will interconnect on the ComEd transmission system by tying to South Dixon Solar I (to be built under PJM queue AF1-280), South Dixon Battery Storage (AF1-281) and South Dixon Solar II (AF2-182), interconnected to a new substation on 345 kV line 15501. The proposed interconnection is behind the Point of Interconnection between ComEd and South Dixon Solar.
Summer Peak Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 32.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 101.95 % | 103.2 % | 1837.0 | STE | 1895.79 | 25.84 | |
CE |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line
270678 to 270694 ckt 1 |
COMED_P4_006-45-BT7-8__
CONTINGENCY 'COMED_P4_006-45-BT7-8__' TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT 1 /*BYRON ; B 345.0 - BYRON ; R 345.0 TRIP BRANCH FROM BUS 270678 TO BUS 930480 CKT 1 /*BYRON ; B 345.0 - AB1-089 TAP 345.0 END |
Breaker | AC | 109.49 % | 110.81 % | 1585.0 | STE | 1756.29 | 22.65 |
Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 7.95 MW | 6.76 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.26 MW | 3.62 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | Adder | 2.07 MW | 1.76 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.8 MW | 8.8 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927201 | AC1-214 C O1 | Adder | 1.78 MW | 1.52 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.67 MW | 4.82 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.34 MW | 1.14 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.14 MW | 1.82 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | Adder | 3.0 MW | 2.55 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | Adder | 4.9 MW | 4.17 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934431 | AD1-067 C | Adder | 0.1 MW | 0.09 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.42 MW | 0.36 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 1.92 MW | 1.64 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 7.69 MW | 6.54 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 58.14 MW | 58.14 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 38.76 MW | 38.76 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.34 MW | 10.34 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 15.5 MW | 15.5 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959081 | AF2-199 C | 50/50 | 37.33 MW | 37.33 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959082 | AF2-199 E | 50/50 | 24.89 MW | 24.89 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959091 | AF2-200 C O1 | 50/50 | 74.66 MW | 74.66 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959092 | AF2-200 E O1 | 50/50 | 49.77 MW | 49.77 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.42 MW | 9.42 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.11 MW | 44.11 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.06 MW | 16.06 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.71 MW | 10.71 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 37.1 MW | 37.1 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.51 MW | 6.51 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.51 MW | 6.51 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.32 MW | 7.32 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.44 MW | 9.44 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 6.89 MW | 6.89 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.51 MW | 9.51 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 6.95 MW | 6.95 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 1.34 MW | 1.34 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 1.34 MW | 1.34 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 31.0 MW | 31.0 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 31.0 MW | 31.0 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.45 MW | 0.45 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.89 MW | 0.89 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.84 MW | 0.84 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.42 MW | 0.42 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.3 MW | 19.3 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 9.8 MW | 9.8 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 10.79 MW | 10.79 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 20.63 MW | 20.63 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.31 MW | 11.31 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.4 MW | 10.4 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.56 MW | 4.72 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | Adder | 9.08 MW | 7.72 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | Adder | 9.08 MW | 7.72 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.2 MW | 3.57 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.1 MW | 3.49 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | Adder | 1.49 MW | 1.26 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | Adder | 9.96 MW | 8.46 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | Adder | 4.71 MW | 4.0 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | Adder | 16.07 MW | 13.66 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 3.94 MW | 3.94 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 3.94 MW | 3.94 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 44.25 MW | 44.25 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 20.35 MW | 20.35 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | Adder | 8.56 MW | 7.28 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | Adder | 40.08 MW | 34.07 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.74 MW | 1.48 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957471 | AF2-041 C | 50/50 | 111.99 MW | 111.99 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957472 | AF2-041 E | 50/50 | 74.66 MW | 74.66 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.17 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.67 MW | 0.57 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.29 MW | 0.25 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.41 MW | 1.2 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.22 MW | 10.39 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 | 50/50 | 50.72 MW | 50.72 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925302 | AB2-191 E | Adder | 1.05 MW | 0.9 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C | 50/50 | 0.97 MW | 0.97 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E | 50/50 | 5.49 MW | 5.49 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950401 | J041 C | External Queue | 1.54 MW | 1.54 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950402 | J041 E | External Queue | 6.14 MW | 6.14 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950471 | J438 C | External Queue | 3.15 MW | 3.15 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.84 MW | 2.84 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.52 MW | 8.52 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951221 | J475 C | External Queue | 3.47 MW | 3.47 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951222 | J475 E | External Queue | 13.89 MW | 13.89 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.4 MW | 5.4 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.23 MW | 3.23 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 5.14 MW | 5.14 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 20.56 MW | 20.56 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.9 MW | 1.9 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 10.26 MW | 10.26 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 950472 | J438 E | External Queue | 12.59 MW | 12.59 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 13.22 MW | 13.22 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954901 | J963 | External Queue | 1.32 MW | 1.32 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.53 MW | 29.53 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.83 MW | 15.83 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956832 | J1181 E | External Queue | 17.98 MW | 17.98 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 21.05 MW | 21.05 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.09 MW | 0.09 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.93 MW | 0.93 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 3.94 MW | 3.94 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.89 MW | 12.89 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.14 MW | 0.14 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 13.69 MW | 13.69 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 17.15 MW | 17.15 MW |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 45.54 MW | 45.54 MW |
Details for BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 926431 | AC1-114 | Adder | -4.1 MW | -3.48 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 927511 | AC1-113 1 | Adder | -2.05 MW | -1.74 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 927521 | AC1-113 2 | Adder | -2.05 MW | -1.74 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958911 | AF2-182 C | Adder | 50.96 MW | 43.31 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958912 | AF2-182 E | Adder | 33.97 MW | 28.88 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958921 | AF2-183 C | Adder | 9.06 MW | 7.7 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 958922 | AF2-183 E | Adder | 13.59 MW | 11.55 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959081 | AF2-199 C | Adder | 5.43 MW | 4.62 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959082 | AF2-199 E | Adder | 3.62 MW | 3.08 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959091 | AF2-200 C O1 | Adder | 10.86 MW | 9.23 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 959092 | AF2-200 E O1 | Adder | 7.24 MW | 6.16 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961011 | AF2-392 C O1 | Adder | 5.11 MW | 4.34 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961012 | AF2-392 E O1 | Adder | 23.92 MW | 20.34 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961021 | AF2-393 O1 | Adder | 8.71 MW | 7.4 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 961031 | AF2-394 O1 | Adder | 5.81 MW | 4.94 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274656 | BYRON ;1U | 50/50 | 101.86 MW | 101.86 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274760 | LEE CO EC;1U | 50/50 | 4.37 MW | 4.37 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274761 | LEE CO EC;2U | 50/50 | 4.37 MW | 4.37 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274763 | LEE CO EC;4U | 50/50 | 4.33 MW | 4.33 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274764 | LEE CO EC;5U | 50/50 | 4.38 MW | 4.38 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274765 | LEE CO EC;6U | 50/50 | 4.38 MW | 4.38 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274766 | LEE CO EC;7U | 50/50 | 4.32 MW | 4.32 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274767 | LEE CO EC;8U | 50/50 | 4.32 MW | 4.32 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274859 | EASYR;U1 E | Adder | 30.66 MW | 26.06 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 274860 | EASYR;U2 E | Adder | 30.66 MW | 26.06 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293516 | O-009 E1 | Adder | 10.74 MW | 9.13 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293517 | O-009 E2 | Adder | 5.45 MW | 4.63 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293518 | O-009 E3 | Adder | 6.01 MW | 5.11 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293715 | O-029 E | Adder | 11.48 MW | 9.76 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293716 | O-029 E | Adder | 6.29 MW | 5.35 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 293717 | O-029 E | Adder | 5.78 MW | 4.92 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932881 | AC2-115 1 | Adder | -4.1 MW | -3.48 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932891 | AC2-115 2 | Adder | -4.1 MW | -3.48 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 932921 | AC2-116 | Adder | -1.43 MW | -1.22 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 939051 | AE1-134 1 | Adder | 2.43 MW | 2.07 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 939061 | AE1-134 2 | Adder | 2.43 MW | 2.07 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946151 | AF1-280 C O1 | Adder | 38.78 MW | 32.97 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946152 | AF1-280 E O1 | Adder | 17.83 MW | 15.16 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946321 | AF1-296 C O1 | Adder | 4.78 MW | 4.06 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946322 | AF1-296 E O1 | Adder | 22.37 MW | 19.01 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 957471 | AF2-041 C | Adder | 16.3 MW | 13.85 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 957472 | AF2-041 E | Adder | 10.86 MW | 9.23 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 919581 | AA2-030 | Adder | 31.29 MW | 26.59 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946161 | AF1-281 C | Adder | 0.85 MW | 0.72 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 946162 | AF1-281 E | Adder | 4.81 MW | 4.09 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 276172 | Z1-108 BAT | Adder | 2.09 MW | 1.78 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 920273 | AA2-123 BAT | Adder | 3.41 MW | 2.9 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 943803 | AF1-048 BAT | Adder | 9.14 MW | 7.77 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 954901 | J963 | External Queue | 0.88 MW | 0.88 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 955971 | J1084 | External Queue | 20.17 MW | 20.17 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | 956411 | J1131 | External Queue | 10.86 MW | 10.86 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 7.45 MW | 7.45 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.18 MW | 0.18 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.76 MW | 0.76 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.16 MW | 2.16 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.24 MW | 0.24 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.53 MW | 3.53 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.33 MW | 0.33 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.57 MW | 1.57 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.8 MW | 6.8 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.32 MW | 0.32 MW |
BYRON ; B-CHERRY VA; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT7-8__ | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
Light Load Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 32.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Light Load Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11216__-S
CONTINGENCY 'COMED_P1-2_765-L11216__-S' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 END |
Single | DC | 99.87 % | 100.36 % | 1399.0 | B | 1404.04 | 6.86 | |
AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
COMED_P1-2_695_B2
CONTINGENCY 'COMED_P1-2_695_B2' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 99.86 % | 100.46 % | 971.0 | B | 975.47 | 5.82 |
Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.19 MW | 1.19 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.94 MW | 0.94 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274849 | CRESCENT ;1U | 80/20 | 0.31 MW | 0.31 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274850 | MENDOTA H;RU | 80/20 | 0.19 MW | 0.19 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274851 | PROVIDENC;RU | 80/20 | 0.47 MW | 0.47 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274853 | TWINGROVE;U1 | 80/20 | 0.92 MW | 0.92 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274854 | TWINGROVE;U2 | 80/20 | 0.92 MW | 0.92 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274855 | GSG-6 ;RU | 80/20 | 0.79 MW | 0.79 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.83 MW | 0.83 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.83 MW | 0.83 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274859 | EASYR;U1 E | 80/20 | 3.32 MW | 3.32 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274860 | EASYR;U2 E | 80/20 | 3.32 MW | 3.32 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274861 | TOP CROP ;1U | 80/20 | 0.93 MW | 0.93 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274862 | TOP CROP ;2U | 80/20 | 1.81 MW | 1.81 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274863 | CAYUGA RI;1U | 80/20 | 0.88 MW | 0.88 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274864 | CAYUGA RI;2U | 80/20 | 0.88 MW | 0.88 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274871 | GR RIDGE ;2U | 80/20 | 1.52 MW | 1.52 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274872 | LEE DEKAL;1U | 80/20 | 1.77 MW | 1.77 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274877 | BISHOP HL;1U | 80/20 | 0.64 MW | 0.64 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274878 | BISHOP HL;2U | 80/20 | 0.64 MW | 0.64 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274879 | MINONK ;1U | 80/20 | 1.51 MW | 1.51 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274887 | PILOT HIL;1U | 80/20 | 1.16 MW | 1.16 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 275149 | KELLYCK ;1E | 80/20 | 4.63 MW | 4.63 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276156 | O-029 C | 80/20 | 0.37 MW | 0.37 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276157 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276158 | O-029 C | 80/20 | 0.73 MW | 0.73 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290021 | O50 E | 80/20 | 6.03 MW | 6.03 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290051 | GSG-6; E | 80/20 | 3.17 MW | 3.17 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290108 | LEEDK;1U E | 80/20 | 7.39 MW | 7.39 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290261 | S-027 E | 80/20 | 3.67 MW | 3.67 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290265 | S-028 E | 80/20 | 3.67 MW | 3.67 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293061 | N-015 E | 80/20 | 4.78 MW | 4.78 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293513 | O-009 C1 | 80/20 | 0.68 MW | 0.68 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293514 | O-009 C2 | 80/20 | 0.35 MW | 0.35 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293515 | O-009 C3 | 80/20 | 0.38 MW | 0.38 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293516 | O-009 E1 | 80/20 | 2.73 MW | 2.73 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293517 | O-009 E2 | 80/20 | 1.39 MW | 1.39 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293518 | O-009 E3 | 80/20 | 1.53 MW | 1.53 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293644 | O22 E1 | 80/20 | 3.73 MW | 3.73 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293645 | O22 E2 | 80/20 | 7.25 MW | 7.25 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293715 | O-029 E | 80/20 | 2.92 MW | 2.92 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293716 | O-029 E | 80/20 | 1.6 MW | 1.6 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293717 | O-029 E | 80/20 | 1.47 MW | 1.47 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293771 | O-035 E | 80/20 | 1.9 MW | 1.9 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294392 | P-010 E | 80/20 | 6.06 MW | 6.06 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294401 | BSHIL;1U E | 80/20 | 2.55 MW | 2.55 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294410 | BSHIL;2U E | 80/20 | 2.55 MW | 2.55 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294763 | P-046 E | 80/20 | 2.85 MW | 2.85 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295108 | WESTBROOK C | 80/20 | 0.29 MW | 0.29 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295110 | SUBLETTE C | 80/20 | 0.13 MW | 0.13 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917502 | Z2-087 E | 80/20 | 4.79 MW | 4.79 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924041 | AB2-047 C O1 | 80/20 | 1.79 MW | 1.79 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924042 | AB2-047 E O1 | 80/20 | 11.98 MW | 11.98 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925581 | AC1-033 C | 80/20 | 0.84 MW | 0.84 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925582 | AC1-033 E | 80/20 | 5.59 MW | 5.59 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926821 | AC1-168 C O1 | 80/20 | 0.69 MW | 0.69 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926822 | AC1-168 E O1 | 80/20 | 4.6 MW | 4.6 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927201 | AC1-214 C O1 | 80/20 | 1.22 MW | 1.22 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927202 | AC1-214 E O1 | 80/20 | 3.88 MW | 3.88 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934431 | AD1-067 C | 80/20 | 0.08 MW | 0.08 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934432 | AD1-067 E | 80/20 | 0.34 MW | 0.34 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934721 | AD1-100 C | 80/20 | 10.48 MW | 10.48 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934722 | AD1-100 E | 80/20 | 48.9 MW | 48.9 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936371 | AD2-047 C O1 | 80/20 | 2.25 MW | 2.25 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936372 | AD2-047 E O1 | 80/20 | 10.98 MW | 10.98 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937001 | AD2-134 C | 80/20 | 1.54 MW | 1.54 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937002 | AD2-134 E | 80/20 | 6.14 MW | 6.14 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938861 | AE1-114 C O1 | 80/20 | 2.38 MW | 2.38 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938862 | AE1-114 E O1 | 80/20 | 8.11 MW | 8.11 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939321 | AE1-163 C O1 | 80/20 | 3.44 MW | 3.44 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939322 | AE1-163 E O1 | 80/20 | 21.16 MW | 21.16 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939401 | AE1-172 C O1 | 80/20 | 2.71 MW | 2.71 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939402 | AE1-172 E O1 | 80/20 | 12.74 MW | 12.74 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 941731 | AE2-173 O1 | 80/20 | 3.44 MW | 3.44 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942111 | AE2-223 C | 80/20 | 1.07 MW | 1.07 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942112 | AE2-223 E | 80/20 | 7.19 MW | 7.19 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942421 | AE2-255 C O1 | 80/20 | 1.89 MW | 1.89 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942422 | AE2-255 E O1 | 80/20 | 5.66 MW | 5.66 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942651 | AE2-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942652 | AE2-281 E O1 | 80/20 | 3.02 MW | 3.02 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943801 | AF1-048 C | 80/20 | 2.92 MW | 2.92 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943802 | AF1-048 E | 80/20 | 1.95 MW | 1.95 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946321 | AF1-296 C O1 | 80/20 | 2.35 MW | 2.35 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946322 | AF1-296 E O1 | 80/20 | 10.98 MW | 10.98 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946501 | AF1-314 C | 80/20 | 2.65 MW | 2.65 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946502 | AF1-314 E | 80/20 | 12.43 MW | 12.43 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957331 | AF2-027 C | 80/20 | 1.93 MW | 1.93 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957332 | AF2-027 E | 80/20 | 2.89 MW | 2.89 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957401 | AF2-034 C | 80/20 | 1.13 MW | 1.13 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957402 | AF2-034 E | 80/20 | 0.97 MW | 0.97 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957751 | AF2-069 C | 80/20 | 0.14 MW | 0.14 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957752 | AF2-069 E | 80/20 | 0.46 MW | 0.46 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957761 | AF2-070 C | 80/20 | 0.2 MW | 0.2 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957762 | AF2-070 E | 80/20 | 0.97 MW | 0.97 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958921 | AF2-183 C | 80/20 | 2.74 MW | 2.74 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958922 | AF2-183 E | 80/20 | 4.12 MW | 4.12 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959102 | AF2-201 E O1 | 80/20 | 12.45 MW | 12.45 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959351 | AF2-226 C | 80/20 | 2.29 MW | 2.29 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959352 | AF2-226 E | 80/20 | 3.43 MW | 3.43 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959611 | AF2-252 C | 80/20 | 1.16 MW | 1.16 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959612 | AF2-252 E | 80/20 | 1.74 MW | 1.74 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960281 | AF2-319 C | 80/20 | 2.29 MW | 2.29 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960282 | AF2-319 E | 80/20 | 3.43 MW | 3.43 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960381 | AF2-329 | 80/20 | 4.07 MW | 4.07 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960601 | AF2-351 C O1 | 80/20 | 0.66 MW | 0.66 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960602 | AF2-351 E O1 | 80/20 | 0.99 MW | 0.99 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960611 | AF2-352 C | 80/20 | 1.16 MW | 1.16 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960612 | AF2-352 E | 80/20 | 1.74 MW | 1.74 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961011 | AF2-392 C O1 | 80/20 | 2.38 MW | 2.38 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961012 | AF2-392 E O1 | 80/20 | 11.15 MW | 11.15 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961031 | AF2-394 O1 | 80/20 | 3.38 MW | 3.38 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936291 | AD2-038 C O1 | 80/20 | 1.37 MW | 1.37 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936292 | AD2-038 E O1 | 80/20 | 9.17 MW | 9.17 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274880 | GENERATOR; | 80/20 | 0.91 MW | 0.91 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274881 | PILOT HIL;1E | 80/20 | 4.63 MW | 4.63 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274882 | W4-005 E | 80/20 | 5.22 MW | 5.22 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274888 | KELLYCK ;1U | 80/20 | 1.16 MW | 1.16 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274890 | CAYUG;1U E | 80/20 | 3.52 MW | 3.52 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274891 | CAYUG;2U E | 80/20 | 3.52 MW | 3.52 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917501 | Z2-087 C | 80/20 | 0.72 MW | 0.72 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 918051 | AA1-018 C OP | 80/20 | 0.68 MW | 0.68 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925301 | AB2-191 | 80/20 | 0.34 MW | 0.34 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925302 | AB2-191 E | 80/20 | 0.84 MW | 0.84 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938851 | AE1-113 C | 80/20 | 4.98 MW | 4.98 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938852 | AE1-113 E | 80/20 | 17.65 MW | 17.65 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 940752 | AE2-062 E | 80/20 | 0.1 MW | 0.1 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946161 | AF1-281 C | 80/20 | 0.26 MW | 0.26 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946162 | AF1-281 E | 80/20 | 1.46 MW | 1.46 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946541 | AF1-318 C O1 | 80/20 | 3.42 MW | 3.42 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946542 | AF1-318 E O1 | 80/20 | 15.99 MW | 15.99 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958341 | AF2-128 C O1 | 80/20 | 0.91 MW | 0.91 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958342 | AF2-128 E O1 | 80/20 | 4.25 MW | 4.25 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 990901 | L-005 E | 80/20 | 3.77 MW | 3.77 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961021 | AF2-393 C | 80/20 | 4.65 MW | 4.65 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961023 | AF2-393 E | 80/20 | 0.42 MW | 0.42 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945351 | AF1-200 FTIR | 80/20 | 161.01 MW | 161.01 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 953201 | J715 C | External Queue | 0.82 MW | 0.82 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 953202 | J715 E | External Queue | 4.43 MW | 4.43 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 954741 | J928 C | External Queue | 0.71 MW | 0.71 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 954742 | J928 E | External Queue | 3.82 MW | 3.82 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 956141 | J1101 | External Queue | 1.17 MW | 1.17 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 954981 | J974 C | External Queue | 1.75 MW | 1.75 MW |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 954982 | J974 E | External Queue | 9.48 MW | 9.48 MW |
Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274847 | GR RIDGE ;BU | 80/20 | 1.0 MW | 1.0 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274848 | CAMPGROVE;RU | 80/20 | 0.81 MW | 0.81 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274850 | MENDOTA H;RU | 80/20 | 0.16 MW | 0.16 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274851 | PROVIDENC;RU | 80/20 | 0.41 MW | 0.41 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274853 | TWINGROVE;U1 | 80/20 | 0.87 MW | 0.87 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274854 | TWINGROVE;U2 | 80/20 | 0.87 MW | 0.87 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274855 | GSG-6 ;RU | 80/20 | 0.67 MW | 0.67 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.6 MW | 0.6 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274857 | BIG SKY ;U1 | 80/20 | 0.7 MW | 0.7 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274858 | BIG SKY ;U2 | 80/20 | 0.7 MW | 0.7 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274859 | EASYR;U1 E | 80/20 | 2.82 MW | 2.82 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274860 | EASYR;U2 E | 80/20 | 2.82 MW | 2.82 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274861 | TOP CROP ;1U | 80/20 | 0.7 MW | 0.7 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274862 | TOP CROP ;2U | 80/20 | 1.37 MW | 1.37 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274863 | CAYUGA RI;1U | 80/20 | 0.85 MW | 0.85 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274864 | CAYUGA RI;2U | 80/20 | 0.85 MW | 0.85 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274871 | GR RIDGE ;2U | 80/20 | 1.27 MW | 1.27 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274872 | LEE DEKAL;1U | 80/20 | 1.5 MW | 1.5 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274879 | MINONK ;1U | 80/20 | 1.26 MW | 1.26 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274887 | PILOT HIL;1U | 80/20 | 1.21 MW | 1.21 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 275149 | KELLYCK ;1E | 80/20 | 4.84 MW | 4.84 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276156 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290021 | O50 E | 80/20 | 5.02 MW | 5.02 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290051 | GSG-6; E | 80/20 | 2.69 MW | 2.69 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290108 | LEEDK;1U E | 80/20 | 6.27 MW | 6.27 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290261 | S-027 E | 80/20 | 3.48 MW | 3.48 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 290265 | S-028 E | 80/20 | 3.48 MW | 3.48 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293061 | N-015 E | 80/20 | 3.99 MW | 3.99 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293515 | O-009 C3 | 80/20 | 0.33 MW | 0.33 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293516 | O-009 E1 | 80/20 | 2.32 MW | 2.32 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293517 | O-009 E2 | 80/20 | 1.18 MW | 1.18 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293518 | O-009 E3 | 80/20 | 1.3 MW | 1.3 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293644 | O22 E1 | 80/20 | 2.81 MW | 2.81 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293645 | O22 E2 | 80/20 | 5.46 MW | 5.46 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293715 | O-029 E | 80/20 | 2.48 MW | 2.48 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293716 | O-029 E | 80/20 | 1.36 MW | 1.36 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293717 | O-029 E | 80/20 | 1.25 MW | 1.25 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 293771 | O-035 E | 80/20 | 1.63 MW | 1.63 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294392 | P-010 E | 80/20 | 5.07 MW | 5.07 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294401 | BSHIL;1U E | 80/20 | 2.18 MW | 2.18 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294410 | BSHIL;2U E | 80/20 | 2.18 MW | 2.18 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 294763 | P-046 E | 80/20 | 2.41 MW | 2.41 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295108 | WESTBROOK C | 80/20 | 0.25 MW | 0.25 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 295110 | SUBLETTE C | 80/20 | 0.11 MW | 0.11 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917502 | Z2-087 E | 80/20 | 4.52 MW | 4.52 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924041 | AB2-047 C O1 | 80/20 | 1.69 MW | 1.69 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 924042 | AB2-047 E O1 | 80/20 | 11.31 MW | 11.31 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925581 | AC1-033 C | 80/20 | 0.71 MW | 0.71 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925582 | AC1-033 E | 80/20 | 4.79 MW | 4.79 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926821 | AC1-168 C O1 | 80/20 | 0.58 MW | 0.58 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 926822 | AC1-168 E O1 | 80/20 | 3.93 MW | 3.93 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927201 | AC1-214 C O1 | 80/20 | 1.05 MW | 1.05 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 927202 | AC1-214 E O1 | 80/20 | 3.32 MW | 3.32 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934431 | AD1-067 C | 80/20 | 0.07 MW | 0.07 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934432 | AD1-067 E | 80/20 | 0.28 MW | 0.28 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934721 | AD1-100 C | 80/20 | 10.07 MW | 10.07 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 934722 | AD1-100 E | 80/20 | 47.0 MW | 47.0 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936371 | AD2-047 C O1 | 80/20 | 2.35 MW | 2.35 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936372 | AD2-047 E O1 | 80/20 | 11.48 MW | 11.48 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937001 | AD2-134 C | 80/20 | 1.3 MW | 1.3 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 937002 | AD2-134 E | 80/20 | 5.21 MW | 5.21 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938861 | AE1-114 C O1 | 80/20 | 2.02 MW | 2.02 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938862 | AE1-114 E O1 | 80/20 | 6.88 MW | 6.88 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939321 | AE1-163 C O1 | 80/20 | 2.99 MW | 2.99 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939322 | AE1-163 E O1 | 80/20 | 18.39 MW | 18.39 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939401 | AE1-172 C O1 | 80/20 | 2.68 MW | 2.68 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 939402 | AE1-172 E O1 | 80/20 | 12.56 MW | 12.56 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 941731 | AE2-173 O1 | 80/20 | 3.25 MW | 3.25 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942111 | AE2-223 C | 80/20 | 1.01 MW | 1.01 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942112 | AE2-223 E | 80/20 | 6.79 MW | 6.79 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942421 | AE2-255 C O1 | 80/20 | 1.57 MW | 1.57 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942422 | AE2-255 E O1 | 80/20 | 4.71 MW | 4.71 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942651 | AE2-281 C O1 | 80/20 | 0.43 MW | 0.43 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 942652 | AE2-281 E O1 | 80/20 | 2.63 MW | 2.63 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943801 | AF1-048 C | 80/20 | 2.47 MW | 2.47 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 943802 | AF1-048 E | 80/20 | 1.65 MW | 1.65 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946321 | AF1-296 C O1 | 80/20 | 2.0 MW | 2.0 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946322 | AF1-296 E O1 | 80/20 | 9.37 MW | 9.37 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946501 | AF1-314 C | 80/20 | 2.24 MW | 2.24 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946502 | AF1-314 E | 80/20 | 10.53 MW | 10.53 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957331 | AF2-027 C | 80/20 | 1.62 MW | 1.62 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957332 | AF2-027 E | 80/20 | 2.43 MW | 2.43 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957371 | AF2-031 C O1 | 80/20 | 0.73 MW | 0.73 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957372 | AF2-031 E O1 | 80/20 | 1.1 MW | 1.1 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957401 | AF2-034 C | 80/20 | 0.93 MW | 0.93 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957402 | AF2-034 E | 80/20 | 0.79 MW | 0.79 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 957762 | AF2-070 E | 80/20 | 0.83 MW | 0.83 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958921 | AF2-183 C | 80/20 | 2.33 MW | 2.33 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958922 | AF2-183 E | 80/20 | 3.49 MW | 3.49 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959102 | AF2-201 E O1 | 80/20 | 10.54 MW | 10.54 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959351 | AF2-226 C | 80/20 | 1.73 MW | 1.73 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959352 | AF2-226 E | 80/20 | 2.59 MW | 2.59 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959611 | AF2-252 C | 80/20 | 1.1 MW | 1.1 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 959612 | AF2-252 E | 80/20 | 1.65 MW | 1.65 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960281 | AF2-319 C | 80/20 | 1.73 MW | 1.73 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960282 | AF2-319 E | 80/20 | 2.59 MW | 2.59 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960381 | AF2-329 | 80/20 | 3.46 MW | 3.46 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960601 | AF2-351 C O1 | 80/20 | 0.69 MW | 0.69 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960602 | AF2-351 E O1 | 80/20 | 1.04 MW | 1.04 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960611 | AF2-352 C | 80/20 | 1.1 MW | 1.1 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 960612 | AF2-352 E | 80/20 | 1.65 MW | 1.65 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961011 | AF2-392 C O1 | 80/20 | 2.02 MW | 2.02 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961012 | AF2-392 E O1 | 80/20 | 9.47 MW | 9.47 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961031 | AF2-394 O1 | 80/20 | 2.87 MW | 2.87 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936291 | AD2-038 C O1 | 80/20 | 1.19 MW | 1.19 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 936292 | AD2-038 E O1 | 80/20 | 7.97 MW | 7.97 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274881 | PILOT HIL;1E | 80/20 | 4.84 MW | 4.84 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274888 | KELLYCK ;1U | 80/20 | 1.21 MW | 1.21 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274890 | CAYUG;1U E | 80/20 | 3.42 MW | 3.42 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 274891 | CAYUG;2U E | 80/20 | 3.42 MW | 3.42 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 917501 | Z2-087 C | 80/20 | 0.68 MW | 0.68 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 918051 | AA1-018 C OP | 80/20 | 0.62 MW | 0.62 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925301 | AB2-191 | 80/20 | 0.29 MW | 0.29 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 925302 | AB2-191 E | 80/20 | 0.71 MW | 0.71 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938851 | AE1-113 C | 80/20 | 4.14 MW | 4.14 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 938852 | AE1-113 E | 80/20 | 14.69 MW | 14.69 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 940752 | AE2-062 E | 80/20 | 0.09 MW | 0.09 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946161 | AF1-281 C | 80/20 | 0.22 MW | 0.22 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946162 | AF1-281 E | 80/20 | 1.24 MW | 1.24 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946541 | AF1-318 C O1 | 80/20 | 2.94 MW | 2.94 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 946542 | AF1-318 E O1 | 80/20 | 13.75 MW | 13.75 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958341 | AF2-128 C O1 | 80/20 | 0.78 MW | 0.78 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 958342 | AF2-128 E O1 | 80/20 | 3.65 MW | 3.65 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 990901 | L-005 E | 80/20 | 3.23 MW | 3.23 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961021 | AF2-393 C | 80/20 | 3.95 MW | 3.95 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 961023 | AF2-393 E | 80/20 | 0.36 MW | 0.36 MW |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_695_B2 | 945351 | AF1-200 FTIR | 80/20 | 136.26 MW | 136.26 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
s2631 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
n6824 | Mitigate sag on the line and replace a 345kV circuit breaker at Cherry Valley | $12,200,000 | |
n6639.1 | Replace station conductor at TSS111 EJ, replace MOD. Relay upgrades, re-conductor part of the line. | $22,300,000 |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-183 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.