AF2-081 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:09
Moyock 230 kV
56.0 MW Capacity / 80.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-081 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Currituck County, North Carolina. The installed facilities will have a total capability of 80.0 MW with 56.0 MW of this output being recognized by PJM as Capacity.
Project Information | |
---|---|
Queue Number | AF2-081 |
Project Name | Moyock 230 kV |
Developer Name | Currituck Solar, LLC |
State | North Carolina |
County | Currituck |
Transmission Owner | Dominion |
MFO | 80.0 MW |
MWE | 80.0 MW |
MWC | 56.0 MW |
Fuel Type | Solar |
Basecase Study Year | 2023 |
Point of Interconnection
AF2-081 will interconnect with the Dominion’s transmission system via an existing substation Moyock 230 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 56.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 164.58 % | 165.15 % | 1050.6 | C | 1735.07 | 13.2 | |
DVP |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line
314481 to 314486 ckt 1 |
DVP_P4-2: 231T2128
CONTINGENCY 'DVP_P4-2: 231T2128' OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1 /*6FENTRES 230.0 - 6THRASHER 230.0 OPEN BRANCH FROM BUS 314481 TO BUS 314502 CKT 1 /*6LANDSTN 230.0 - 6STUMPY 230.0 OPEN BRANCH FROM BUS 314502 TO BUS 314508 CKT 1 /*6STUMPY 230.0 - 6THRASHER 230.0 OPEN BUS 314502 /*6STUMPY 230.0 END |
Breaker | AC | 107.62 % | 109.2 % | 830.0 | C | 906.36 | 13.62 | |
DVP |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line
314486 to 314504 ckt 1 |
DVP_P4-2: 231T2128
CONTINGENCY 'DVP_P4-2: 231T2128' OPEN BRANCH FROM BUS 314466 TO BUS 314508 CKT 1 /*6FENTRES 230.0 - 6THRASHER 230.0 OPEN BRANCH FROM BUS 314481 TO BUS 314502 CKT 1 /*6LANDSTN 230.0 - 6STUMPY 230.0 OPEN BRANCH FROM BUS 314502 TO BUS 314508 CKT 1 /*6STUMPY 230.0 - 6THRASHER 230.0 OPEN BUS 314502 /*6STUMPY 230.0 END |
Breaker | AC | 99.2 % | 100.41 % | 906.0 | C | 909.71 | 11.16 | |
DVP |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line
314209 to 314386 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 122.65 % | 122.98 % | 441.8 | B | 543.33 | 4.6 | |
DVP |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line
314386 to 314296 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 114.96 % | 115.28 % | 441.8 | B | 509.31 | 4.6 | |
DVP |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line
314296 to 314415 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 111.33 % | 111.66 % | 441.8 | B | 493.31 | 4.6 |
Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 0.62 MW | 0.53 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 5.49 MW | 4.67 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 2.76 MW | 2.35 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 2.2 MW | 1.87 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 25.91 MW | 22.02 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940481 | AE2-033 C | Adder | 15.41 MW | 13.1 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940482 | AE2-033 E | Adder | 10.39 MW | 8.83 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946011 | AF1-266 | Adder | 12.9 MW | 10.97 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314189 | 6PAPERMILL | Adder | 8.74 MW | 7.43 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314229 | 6MT RD221 | 50/50 | 0.24 MW | 0.24 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314236 | 6NRTHEST | 50/50 | 0.33 MW | 0.33 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314241 | 6OLDCHRC | 50/50 | 1.37 MW | 1.37 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314250 | 6ROCKVILLE | 50/50 | 0.55 MW | 0.55 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315060 | 1CHESTF5 | Adder | 88.4 MW | 75.14 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315065 | 1CHESTF6 | Adder | 172.48 MW | 146.61 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315067 | 1DARBY 1 | 50/50 | 4.41 MW | 4.41 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315068 | 1DARBY 2 | 50/50 | 4.41 MW | 4.41 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315069 | 1DARBY 3 | 50/50 | 4.43 MW | 4.43 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315070 | 1DARBY 4 | 50/50 | 4.43 MW | 4.43 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315073 | 1STONECA | Adder | 9.36 MW | 7.96 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315074 | 1HOPCGN1 | Adder | 11.29 MW | 9.6 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315075 | 1HOPCGN2 | Adder | 11.14 MW | 9.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315083 | 1SPRUNCA | Adder | 14.9 MW | 12.66 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315084 | 1SPRUNCB | Adder | 14.9 MW | 12.66 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | Adder | 5.94 MW | 5.05 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926412 | AC1-112 E | 50/50 | 1.93 MW | 1.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926661 | AC1-147 C | Adder | 2.13 MW | 1.81 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 1.25 MW | 1.06 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | Adder | 6.99 MW | 5.94 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | Adder | 4.66 MW | 3.96 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934141 | AD1-041 C | Adder | 6.7 MW | 5.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934142 | AD1-041 E | Adder | 4.47 MW | 3.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934392 | AD1-063 E | Adder | 1.38 MW | 1.18 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934781 | AD1-105 C | Adder | 11.68 MW | 9.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934782 | AD1-105 E | Adder | 7.78 MW | 6.62 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935111 | AD1-144 C | Adder | 1.68 MW | 1.43 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 0.92 MW | 0.78 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936151 | AD2-021 | 50/50 | 0.36 MW | 0.36 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936581 | AD2-073 C | Adder | 2.12 MW | 1.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936582 | AD2-073 E | Adder | 1.05 MW | 0.89 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936591 | AD2-074 C | Adder | 6.23 MW | 5.29 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936592 | AD2-074 E | Adder | 10.16 MW | 8.63 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936661 | AD2-085 C | Adder | 3.5 MW | 2.98 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936662 | AD2-085 E | Adder | 5.71 MW | 4.85 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936762 | AD2-097 E | Adder | 14.13 MW | 12.01 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | Adder | 5.42 MW | 4.61 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | Adder | 2.84 MW | 2.42 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942151 | AE2-227 C | Adder | 3.29 MW | 2.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942152 | AE2-227 E | Adder | 2.19 MW | 1.86 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942161 | AE2-228 C | Adder | 3.0 MW | 2.55 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942162 | AE2-228 E | Adder | 2.0 MW | 1.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942191 | AE2-231 C O1 | Adder | 4.16 MW | 3.53 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942192 | AE2-231 E O1 | Adder | 2.77 MW | 2.35 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942341 | AE2-247 C | Adder | 1.52 MW | 1.29 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942342 | AE2-247 E | Adder | 2.1 MW | 1.78 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942371 | AE2-250 C O1 | Adder | 12.68 MW | 10.78 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942372 | AE2-250 E O1 | Adder | 6.69 MW | 5.69 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | Adder | 5.7 MW | 4.85 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | Adder | 2.56 MW | 2.18 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943431 | AF1-014 C | Adder | 1.64 MW | 1.39 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943432 | AF1-014 E | Adder | 2.89 MW | 2.46 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943461 | AF1-017 C | Adder | 1.37 MW | 1.17 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943462 | AF1-017 E | Adder | 2.24 MW | 1.91 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943471 | AF1-018 | Adder | 9.22 MW | 7.83 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 1.63 MW | 1.39 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 0.86 MW | 0.73 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943621 | AF1-033 C | Adder | 2.61 MW | 2.22 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943622 | AF1-033 E | Adder | 1.35 MW | 1.15 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943741 | AF1-042 C | Adder | 3.26 MW | 2.77 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943742 | AF1-042 E | Adder | 5.32 MW | 4.52 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944631 | AF1-128 O1 | Adder | 68.79 MW | 58.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 4.84 MW | 4.12 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 3.23 MW | 2.74 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945361 | AF1-201 C O1 | Adder | 18.2 MW | 15.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945362 | AF1-201 E O1 | Adder | 12.13 MW | 10.31 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945831 | AF1-248 | Adder | 0.36 MW | 0.31 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960091 | AF2-300 C | Adder | 1.89 MW | 1.6 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960092 | AF2-300 E | Adder | 1.26 MW | 1.07 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315611 | 6Z1-036WIND | Adder | 3.86 MW | 3.28 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 2.02 MW | 1.72 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | Adder | 1.76 MW | 1.5 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 1.14 MW | 0.97 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923842 | AB2-024 E | Adder | 1.48 MW | 1.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923852 | AB2-025 E | Adder | 1.09 MW | 0.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 930122 | AB1-027 E | 50/50 | 1.9 MW | 1.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932591 | AC2-079 C O1 | Adder | 5.82 MW | 4.95 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932592 | AC2-079 E O1 | Adder | 9.5 MW | 8.07 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938551 | AE1-074 C | Adder | 3.13 MW | 2.66 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938552 | AE1-074 E | Adder | 1.58 MW | 1.34 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939312 | AE1-162 E | Adder | 1.5 MW | 1.27 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939431 | AE1-175 C | Adder | 2.89 MW | 2.46 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939432 | AE1-175 E | Adder | 1.43 MW | 1.22 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939611 | AE1-191 C | Adder | 13.41 MW | 11.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939612 | AE1-191 E | Adder | 8.94 MW | 7.6 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940231 | AE2-005 C | Adder | 1.73 MW | 1.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940232 | AE2-005 E | Adder | 2.82 MW | 2.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940431 | AE2-027 C O1 | Adder | 17.91 MW | 15.23 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940432 | AE2-027 E O1 | Adder | 11.94 MW | 10.15 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940651 | AE2-052 | Adder | 4.23 MW | 3.6 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 3.2 MW | 2.72 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 5.08 MW | 4.32 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | Adder | 26.62 MW | 22.63 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | Adder | 107.43 MW | 91.32 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | Adder | 27.36 MW | 23.26 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | Adder | 106.7 MW | 90.69 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | Adder | 24.85 MW | 21.13 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | Adder | 109.06 MW | 92.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946261 | AF1-291 C | Adder | 3.0 MW | 2.55 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946262 | AF1-291 E | Adder | 2.0 MW | 1.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957411 | AF2-035 C | Adder | 7.55 MW | 6.42 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957412 | AF2-035 E | Adder | 5.04 MW | 4.28 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 2.0 MW | 1.7 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 1.33 MW | 1.13 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957601 | AF2-054 C | Adder | 2.6 MW | 2.21 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957602 | AF2-054 E | Adder | 1.74 MW | 1.48 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 3.38 MW | 2.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 29.21 MW | 24.83 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 0.97 MW | 0.83 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925332 | AB2-190 E | Adder | 9.95 MW | 8.46 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | Adder | 1.07 MW | 0.91 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 14.52 MW | 12.35 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 9.68 MW | 8.23 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941581 | AE2-155 C | 50/50 | 1.11 MW | 1.11 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941582 | AE2-155 E | 50/50 | 0.47 MW | 0.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | Adder | 16.91 MW | 14.37 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942001 | AE2-212 C | Adder | 2.84 MW | 2.42 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942002 | AE2-212 E | Adder | 1.9 MW | 1.61 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957831 | AF2-077 C | Adder | 2.47 MW | 2.1 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957832 | AF2-077 E | Adder | 1.65 MW | 1.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | Adder | 9.24 MW | 7.85 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | Adder | 3.96 MW | 3.37 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957911 | AF2-085 | Adder | 3.86 MW | 3.28 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 1.3 MW | 1.11 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 2.07 MW | 1.76 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958261 | AF2-120 C | Adder | 6.94 MW | 5.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958262 | AF2-120 E | Adder | 4.62 MW | 3.93 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924512 | AB2-100 E | Adder | 5.17 MW | 4.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 907092 | X1-038 E | Adder | 5.51 MW | 4.68 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923831 | AB2-022 C | Adder | 2.12 MW | 1.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924812 | AB2-134 E OP | Adder | 15.45 MW | 13.13 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925051 | AB2-160 C O1 | Adder | 7.14 MW | 6.07 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925052 | AB2-160 E O1 | Adder | 11.65 MW | 9.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925061 | AB2-161 C O1 | Adder | 3.79 MW | 3.22 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925062 | AB2-161 E O1 | Adder | 6.18 MW | 5.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925331 | AB2-190 C | Adder | 23.22 MW | 19.74 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926751 | AC1-161 C O1 | Adder | 27.22 MW | 23.14 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926752 | AC1-161 E O1 | Adder | 11.62 MW | 9.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927222 | AC1-216 E O1 | Adder | 9.43 MW | 8.02 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932041 | AC2-012 C | Adder | 7.59 MW | 6.45 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932042 | AC2-012 E | Adder | 12.38 MW | 10.53 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933291 | AC2-141 C | Adder | 27.22 MW | 23.14 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933292 | AC2-141 E | Adder | 11.62 MW | 9.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934011 | AD1-025 C | Adder | 20.62 MW | 17.53 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934012 | AD1-025 E | Adder | 12.21 MW | 10.38 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934571 | AD1-082 C | Adder | 8.63 MW | 7.34 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934572 | AD1-082 E | Adder | 4.92 MW | 4.18 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935161 | AD1-151 C O1 | Adder | 20.24 MW | 17.21 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935162 | AD1-151 E O1 | Adder | 13.5 MW | 11.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938531 | AE1-072 C O1 | Adder | 16.23 MW | 13.8 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938532 | AE1-072 E O1 | Adder | 8.46 MW | 7.19 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C O1 | Adder | 2.65 MW | 2.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E O1 | Adder | 3.65 MW | 3.11 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939191 | AE1-149 C O1 | Adder | 12.69 MW | 10.79 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939192 | AE1-149 E O1 | Adder | 8.46 MW | 7.19 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939311 | AE1-162 C | Adder | 2.25 MW | 1.91 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940541 | AE2-040 O1 | Adder | 2.76 MW | 2.35 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942551 | AE2-270 | Adder | 32.84 MW | 27.92 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957711 | AF2-065 C | Adder | 16.92 MW | 14.38 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957712 | AF2-065 E | Adder | 16.26 MW | 13.82 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925861 | AC1-065 C | Adder | 4.33 MW | 3.68 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925862 | AC1-065 E | Adder | 7.06 MW | 6.0 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926551 | AC1-134 | 50/50 | 2.51 MW | 2.51 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926781 | AC1-164 C | Adder | 58.25 MW | 49.51 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926782 | AC1-164 E | Adder | 26.17 MW | 22.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927041 | AC1-191 C O1 | 50/50 | 17.69 MW | 17.69 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927042 | AC1-191 E O1 | 50/50 | 8.81 MW | 8.81 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936242 | AD2-030 E | Adder | 1.46 MW | 1.24 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936301 | AD2-039 C | Adder | 1.73 MW | 1.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936302 | AD2-039 E | Adder | 2.82 MW | 2.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936341 | AD2-044 C | Adder | 0.26 MW | 0.22 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936342 | AD2-044 E | Adder | 0.3 MW | 0.25 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938031 | AE1-004 C | Adder | 1.73 MW | 1.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315610 | 6AA1-145GAS | 50/50 | 17.09 MW | 17.09 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924061 | AB2-050 | 50/50 | 1.01 MW | 1.01 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938032 | AE1-004 E | Adder | 2.82 MW | 2.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939241 | AE1-155 C | Adder | 14.21 MW | 12.08 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939242 | AE1-155 E | Adder | 9.47 MW | 8.05 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932831 | AC2-110 C | Adder | 1.73 MW | 1.47 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932832 | AC2-110 E | Adder | 2.82 MW | 2.4 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933261 | AC2-137 C | 50/50 | 3.15 MW | 3.15 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933262 | AC2-137 E | 50/50 | 2.04 MW | 2.04 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933271 | AC2-138 C | Adder | 0.83 MW | 0.71 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933272 | AC2-138 E | Adder | 1.04 MW | 0.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940551 | AE2-041 O1 | Adder | 9.22 MW | 7.83 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | Adder | 44.14 MW | 37.52 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | Adder | 101.06 MW | 85.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | Adder | 44.14 MW | 37.52 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | Adder | 101.06 MW | 85.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | Adder | 44.14 MW | 37.52 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | Adder | 101.06 MW | 85.9 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315043 | 1FOUR RIVERA | 50/50 | 4.88 MW | 4.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315044 | 1FOUR RIVERB | 50/50 | 4.88 MW | 4.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315045 | 1FOUR RIVERC | 50/50 | 5.98 MW | 5.98 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315046 | 1FOUR RIVERD | 50/50 | 4.88 MW | 4.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315047 | 1FOUR RIVERE | 50/50 | 4.88 MW | 4.88 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315048 | 1FOUR RIVERF | 50/50 | 5.98 MW | 5.98 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.23 MW | 0.23 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.94 MW | 4.94 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.45 MW | 10.45 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.08 MW | 1.08 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.94 MW | 13.94 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 31.12 MW | 31.12 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.61 MW | 13.61 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.29 MW | 1.29 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 3.36 MW | 3.36 MW |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 3.5 MW | 3.5 MW |
Details for 6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 916042 | Z1-036 E | Adder | 11.0 MW | 9.35 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314491 | 3PENDLTN | 50/50 | 0.24 MW | 0.24 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314638 | 6ELIZ CT | 50/50 | 0.17 MW | 0.17 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314639 | 6TANGLEW | 50/50 | 0.26 MW | 0.26 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314643 | 3O INLET | 50/50 | 0.41 MW | 0.41 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 919152 | AA1-139 E | 50/50 | 6.13 MW | 6.13 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 926661 | AC1-147 C | Adder | -1.17 MW | -1.0 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 934061 | AD1-033 C | 50/50 | 9.72 MW | 9.72 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 934062 | AD1-033 E | 50/50 | 6.48 MW | 6.48 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 937221 | AD2-160 C O1 | 50/50 | 5.85 MW | 5.85 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 937222 | AD2-160 E O1 | 50/50 | 3.07 MW | 3.07 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 942401 | AE2-253 C | 50/50 | 6.16 MW | 6.16 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 942402 | AE2-253 E | 50/50 | 2.77 MW | 2.77 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944871 | AF1-152 C | Adder | 1.98 MW | 1.68 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944872 | AF1-152 E | Adder | 1.32 MW | 1.12 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 315603 | 6AA1-139SOLA | 50/50 | 2.48 MW | 2.48 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 315611 | 6Z1-036WIND | Adder | 1.64 MW | 1.39 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 913392 | Y1-086 E | 50/50 | 1.55 MW | 1.55 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 923832 | AB2-022 E | 50/50 | 0.88 MW | 0.88 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941281 | AE2-122 C O1 | 50/50 | 26.49 MW | 26.49 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941282 | AE2-122 E O1 | 50/50 | 106.89 MW | 106.89 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941291 | AE2-123 C O1 | 50/50 | 27.22 MW | 27.22 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941292 | AE2-123 E O1 | 50/50 | 106.16 MW | 106.16 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941301 | AE2-124 C O1 | 50/50 | 57.85 MW | 57.85 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941302 | AE2-124 E O1 | 50/50 | 253.83 MW | 253.83 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 901082 | W1-029 E | Adder | 11.93 MW | 10.14 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 917122 | Z2-027 E | 50/50 | 0.65 MW | 0.65 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 925522 | AC1-027 E | 50/50 | 0.79 MW | 0.79 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941501 | AE2-147 C | Adder | 5.93 MW | 5.04 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941502 | AE2-147 E | Adder | 3.95 MW | 3.36 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957871 | AF2-081 C | 50/50 | 9.53 MW | 9.53 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957872 | AF2-081 E | 50/50 | 4.09 MW | 4.09 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 923831 | AB2-022 C | 50/50 | 1.63 MW | 1.63 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 938531 | AE1-072 C O1 | 50/50 | 15.94 MW | 15.94 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 938532 | AE1-072 E O1 | 50/50 | 8.31 MW | 8.31 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944581 | AF1-123 C O1 | Adder | 16.45 MW | 13.98 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944582 | AF1-123 E O1 | Adder | 37.66 MW | 32.01 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944591 | AF1-124 C O1 | Adder | 16.45 MW | 13.98 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944592 | AF1-124 E O1 | Adder | 37.66 MW | 32.01 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944601 | AF1-125 C O1 | Adder | 16.45 MW | 13.98 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944602 | AF1-125 E O1 | Adder | 37.66 MW | 32.01 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941592 | AE2-156 BAT | Adder | 9.72 MW | 8.26 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957632 | AF2-057 BAT | Adder | 2.19 MW | 1.86 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.22 MW | 0.22 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.93 MW | 0.93 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.09 MW | 0.09 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.43 MW | 1.43 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.06 MW | 1.06 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
6LANDSTN-6LYNHAVN 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 1.01 MW | 1.01 MW |
Details for 6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 916042 | Z1-036 E | Adder | 8.98 MW | 7.63 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314295 | 6BIRDNECK | 50/50 | 0.09 MW | 0.09 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314491 | 3PENDLTN | 50/50 | 0.57 MW | 0.57 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314638 | 6ELIZ CT | 50/50 | 0.14 MW | 0.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 314643 | 3O INLET | 50/50 | 0.34 MW | 0.34 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 919152 | AA1-139 E | 50/50 | 5.02 MW | 5.02 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 926661 | AC1-147 C | Adder | -0.88 MW | -0.75 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 934061 | AD1-033 C | 50/50 | 7.97 MW | 7.97 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 934062 | AD1-033 E | 50/50 | 5.31 MW | 5.31 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 937221 | AD2-160 C O1 | 50/50 | 4.79 MW | 4.79 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 937222 | AD2-160 E O1 | 50/50 | 2.51 MW | 2.51 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 942401 | AE2-253 C | 50/50 | 5.04 MW | 5.04 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 942402 | AE2-253 E | 50/50 | 2.27 MW | 2.27 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944871 | AF1-152 C | Adder | 1.61 MW | 1.37 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944872 | AF1-152 E | Adder | 1.08 MW | 0.91 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 315603 | 6AA1-139SOLA | 50/50 | 2.03 MW | 2.03 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 315611 | 6Z1-036WIND | Adder | 1.34 MW | 1.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 913392 | Y1-086 E | 50/50 | 1.27 MW | 1.27 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 916192 | Z1-068 E | 50/50 | 3.72 MW | 3.72 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 923832 | AB2-022 E | 50/50 | 0.72 MW | 0.72 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941281 | AE2-122 C O1 | 50/50 | 54.09 MW | 54.09 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941282 | AE2-122 E O1 | 50/50 | 218.28 MW | 218.28 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941291 | AE2-123 C O1 | 50/50 | 55.59 MW | 55.59 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941292 | AE2-123 E O1 | 50/50 | 216.78 MW | 216.78 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941301 | AE2-124 C O1 | 50/50 | 47.43 MW | 47.43 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941302 | AE2-124 E O1 | 50/50 | 208.13 MW | 208.13 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 901082 | W1-029 E | Adder | 9.74 MW | 8.28 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 917122 | Z2-027 E | Adder | 0.53 MW | 0.45 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 925522 | AC1-027 E | 50/50 | 1.86 MW | 1.86 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941501 | AE2-147 C | Adder | 4.84 MW | 4.12 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941502 | AE2-147 E | Adder | 3.23 MW | 2.74 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957871 | AF2-081 C | 50/50 | 7.81 MW | 7.81 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957872 | AF2-081 E | 50/50 | 3.35 MW | 3.35 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 923831 | AB2-022 C | 50/50 | 1.33 MW | 1.33 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 938531 | AE1-072 C O1 | 50/50 | 13.06 MW | 13.06 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 938532 | AE1-072 E O1 | 50/50 | 6.81 MW | 6.81 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944581 | AF1-123 C O1 | Adder | 13.43 MW | 11.42 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944582 | AF1-123 E O1 | Adder | 30.75 MW | 26.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944591 | AF1-124 C O1 | Adder | 13.43 MW | 11.42 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944592 | AF1-124 E O1 | Adder | 30.75 MW | 26.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944601 | AF1-125 C O1 | Adder | 13.43 MW | 11.42 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 944602 | AF1-125 E O1 | Adder | 30.75 MW | 26.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 941592 | AE2-156 BAT | Adder | 7.51 MW | 6.38 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | 957632 | AF2-057 BAT | Adder | 1.64 MW | 1.4 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.73 MW | 0.73 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.15 MW | 0.15 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.08 MW | 0.08 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.14 MW | 1.14 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.83 MW | 0.83 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.01 MW | 0.01 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.12 MW | 0.12 MW |
6LYNHAVN-6THALIA 230.0 kV Ckt 1 line l/o DVP_P4-2: 231T2128 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.8 MW | 0.8 MW |
Details for 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
Details for 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
Details for 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
Light Load Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 56.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
n8149 | Add Additional 500/230 kV Transformer at Elmont Substation | $22,000,000 | |
n6607 | Rebuild 5.88 miles of 230 kV Line 2026 from Landstown to Lynnhaven with 2-636 ACSR. | $14,700,000 | |
n7061 | Rebuild 3.37 miles of 230 kV Line 2007 from Lynnhaven to Thalia with 2-636 ACSR. | $5,055,000 | |
b3057 | PJM Baseline Upgrade b3057: Rebuild Waller-Skiff's Creek 230 kV Line#2154. | $0 |
Attachments
Attachment 1: One Line Diagram for Queue Project AF2-081.
Download all tables in report
Conclusion
The Transition Sort load flow retool results indicate that AF2-081 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.