AF2-047 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:08
Creswell-Riders Creek 115 kV
99.8 MW Capacity / 150.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-047 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Washington County, North Carolina. The installed facilities will have a total capability of 150.0 MW with 99.8 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-047 |
| Project Name | Creswell-Riders Creek 115 kV |
| Developer Name | Creswell HWY 64 Solar LLC |
| State | North Carolina |
| County | Washington |
| Transmission Owner | Dominion |
| MFO | 150.0 MW |
| MWE | 150.0 MW |
| MWC | 99.8 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-047 will interconnect with the Dominion transmission system. The POI is a single line tap between Creswell 115 kV substation and Riders Creek 115 kV substation. The IC is responsible for securing right-of-way, permits and constructing the proposed attachment line from the solar facility site to the proposed new substation. Attachment 1 shows a one-line diagram of the proposed interconnection facilities. The IC may not install any facilities on Dominion’s right-of-way without first obtaining the necessary approval from Dominion Energy.
Summer Peak Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 99.8 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line
925120 to 314576 ckt 1 |
DVP_P7-1: LN 25-2034-A
CONTINGENCY 'DVP_P7-1: LN 25-2034-A' OPEN BRANCH FROM BUS 314573 TO BUS 314596 CKT 1 /*3EVERETS 115.0 - 3POPLR C 115.0 OPEN BRANCH FROM BUS 314596 TO BUS 314614 CKT 1 /*3POPLR C 115.0 - 3TRWBRDG2 115.0 OPEN BRANCH FROM BUS 314614 TO BUS 314616 CKT 1 /*3TRWBRDG2 115.0 - 6TRWBRDG 230.0 OPEN BRANCH FROM BUS 314616 TO BUS 933980 CKT 1 /*6TRWBRDG 230.0 - AD1-022 TAP 230.0 OPEN BUS 314596 /*3POPLR C 115.0 END |
Tower | AC | 117.71 % | 131.06 % | 91.0 | C | 119.26 | 14.23 | |
| CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 109.93 % | 114.37 % | 478.0 | B | 546.69 | 22.18 | |
| DVP |
3FIVE PT-3WHARTON 115.0 kV Ckt 1 line
314576 to 314622 ckt 1 |
DVP_P7-1: LN 25-2034-A
CONTINGENCY 'DVP_P7-1: LN 25-2034-A' OPEN BRANCH FROM BUS 314573 TO BUS 314596 CKT 1 /*3EVERETS 115.0 - 3POPLR C 115.0 OPEN BRANCH FROM BUS 314596 TO BUS 314614 CKT 1 /*3POPLR C 115.0 - 3TRWBRDG2 115.0 OPEN BRANCH FROM BUS 314614 TO BUS 314616 CKT 1 /*3TRWBRDG2 115.0 - 6TRWBRDG 230.0 OPEN BRANCH FROM BUS 314616 TO BUS 933980 CKT 1 /*6TRWBRDG 230.0 - AD1-022 TAP 230.0 OPEN BUS 314596 /*3POPLR C 115.0 END |
Tower | AC | 106.59 % | 119.94 % | 91.0 | C | 109.15 | 14.23 | |
| DVP |
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
314218 to 314908 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 162.3 % | 162.66 % | 1050.6 | C | 1708.91 | 22.59 | |
| DVP |
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
314638 to 314647 ckt 1 |
DVP_P4-2: 246T247
CONTINGENCY 'DVP_P4-2: 246T247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Breaker | AC | 127.36 % | 137.46 % | 699.0 | C | 960.85 | 69.21 | |
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 120.8 % | 121.1 % | 3144.0 | C | 3807.38 | 37.8 | |
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 110.94 % | 111.12 % | 3144.0 | C | 3493.61 | 37.96 | |
| DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P4-2: 56372
CONTINGENCY 'DVP_P4-2: 56372' OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Breaker | AC | 115.66 % | 115.86 % | 3144.0 | C | 3642.64 | 40.98 | |
| DVP |
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
314903 to 314908 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 114.64 % | 114.8 % | 3144.0 | C | 3609.31 | 42.69 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P4-2: 557T574
CONTINGENCY 'DVP_P4-2: 557T574' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 115.48 % | 115.53 % | 3637.0 | C | 4201.83 | 43.28 | |
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: 557T574
CONTINGENCY 'DVP_P4-2: 557T574' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Breaker | AC | 114.39 % | 114.58 % | 3938.0 | C | 4512.16 | 41.96 | |
| DVP |
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
314902 to 314914 ckt 1 |
DVP_P4-2: H2T557
CONTINGENCY 'DVP_P4-2: H2T557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Breaker | AC | 107.79 % | 107.98 % | 3938.0 | C | 4252.25 | 40.51 | |
| DVP |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line
313714 to 314662 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 95.96 % | 105.18 % | 897.0 | C | 943.46 | 81.31 | |
| DVP |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
314662 to 314651 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 94.05 % | 103.26 % | 897.0 | C | 926.24 | 81.31 | |
| DVP |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line
314209 to 314386 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 122.13 % | 122.54 % | 441.8 | B | 541.38 | 6.78 | |
| DVP |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line
314209 to 314386 ckt 1 |
DVP_P1-2: LN 557
CONTINGENCY 'DVP_P1-2: LN 557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 113.35 % | 113.48 % | 441.8 | B | 501.35 | 5.92 | |
| DVP |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line
314386 to 314296 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 114.43 % | 114.84 % | 441.8 | B | 507.36 | 6.78 | |
| DVP |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line
314386 to 314296 ckt 1 |
DVP_P1-2: LN 557
CONTINGENCY 'DVP_P1-2: LN 557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 105.65 % | 105.78 % | 441.8 | B | 467.34 | 5.92 | |
| DVP |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line
314296 to 314415 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 110.81 % | 111.22 % | 441.8 | B | 491.37 | 6.78 | |
| DVP |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line
314296 to 314415 ckt 1 |
DVP_P1-2: LN 557
CONTINGENCY 'DVP_P1-2: LN 557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 102.03 % | 102.16 % | 441.8 | B | 451.34 | 5.92 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 129.76 % | 132.46 % | 375.06 | B | 496.8 | 10.07 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
314572 3EMPORIA 115 925170 AB2-174 TAP 115 1
CONTINGENCY '314572 3EMPORIA 115 925170 AB2-174 TAP 115 1' OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 END |
Single | AC | 125.43 % | 127.6 % | 375.06 | B | 478.58 | 8.09 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
Base Case | Single | AC | 107.01 % | 108.99 % | 375.06 | A | 408.78 | 7.42 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 109.22 % | 115.36 % | 571.52 | B | 659.31 | 35.46 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 109.14 % | 115.27 % | 571.52 | B | 658.79 | 35.46 | |
| DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 102.76 % | 108.88 % | 571.52 | B | 622.27 | 35.46 | |
| DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 102.67 % | 108.8 % | 571.52 | B | 621.81 | 35.46 | |
| DVP |
6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line
314583 to 924510 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 113.95 % | 116.63 % | 375.06 | B | 437.43 | 10.1 | |
| DVP |
6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line
314583 to 924510 ckt 1 |
314572 3EMPORIA 115 925170 AB2-174 TAP 115 1
CONTINGENCY '314572 3EMPORIA 115 925170 AB2-174 TAP 115 1' OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 END |
Single | AC | 109.7 % | 111.85 % | 375.06 | B | 419.5 | 8.13 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 574
CONTINGENCY 'DVP_P1-2: LN 574' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 127.76 % | 128.69 % | 2442.12 | B | 3142.76 | 26.27 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 557
CONTINGENCY 'DVP_P1-2: LN 557' OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1 /*6CHCKAHM 230.0 - 8CHCKAHM 500.0 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1 /*8CHCKAHM 500.0 - 8ELMONT 500.0 END |
Single | AC | 109.87 % | 110.78 % | 2442.12 | B | 2705.38 | 25.41 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 99.78 % | 100.62 % | 2442.12 | B | 2457.26 | 23.42 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 2028-A
CONTINGENCY 'DVP_P1-2: LN 2028-A' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 99.41 % | 100.14 % | 2442.12 | B | 2445.54 | 20.41 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 99.53 % | 100.84 % | 678.68 | B | 684.38 | 10.36 | |
| Details for AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 934521 | AD1-076 C | 50/50 | 37.49 MW | 37.49 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 934522 | AD1-076 E | 50/50 | 19.09 MW | 19.09 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315294 | 1DOMTR10 | 50/50 | 13.39 MW | 13.39 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 925121 | AB2-169 C | 50/50 | 3.44 MW | 3.44 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 925122 | AB2-169 E | 50/50 | 17.8 MW | 17.8 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 940491 | AE2-034 C | Adder | 3.98 MW | 3.39 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 940492 | AE2-034 E | Adder | 1.71 MW | 1.45 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 957531 | AF2-047 C | Adder | 9.47 MW | 8.05 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 957532 | AF2-047 E | Adder | 4.76 MW | 4.05 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 916042 | Z1-036 E | Adder | 9.5 MW | 8.07 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315292 | 1DOMTR78 | 50/50 | 1.79 MW | 1.79 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315611 | 6Z1-036WIND | Adder | 1.41 MW | 1.2 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 920692 | AA2-178 E | Adder | 2.28 MW | 1.94 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.19 MW | 0.19 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.01 MW | 0.01 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.13 MW | 0.13 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.34 MW | 0.34 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.51 MW | 0.51 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.04 MW | 0.04 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.06 MW | 0.06 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.1 MW | 0.1 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.15 MW | 0.15 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.28 MW | 0.28 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| AB2-169 TAP-3FIVE PT 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.16 MW | 0.16 MW |
| Details for 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314541 | 3WATKINS | Adder | 0.35 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314582 | 3KELFORD | 50/50 | 0.39 MW | 0.39 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315131 | 1EDGECMA | 50/50 | 8.42 MW | 8.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315132 | 1EDGECMB | 50/50 | 8.42 MW | 8.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315136 | 1ROSEMG1 | 50/50 | 1.71 MW | 1.71 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315137 | 1ROSEMS1 | 50/50 | 1.06 MW | 1.06 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315138 | 1ROSEMG2 | 50/50 | 0.8 MW | 0.8 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918492 | AA1-063AE OP | Adder | 2.41 MW | 2.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918532 | AA1-067 E | 50/50 | 1.6 MW | 1.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919692 | AA2-053 E OP | Adder | 2.48 MW | 2.11 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919702 | AA2-057 E OP | Adder | 1.74 MW | 1.48 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920042 | AA2-088 E OP | Adder | 6.19 MW | 5.26 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920592 | AA2-165 E | Adder | 0.29 MW | 0.25 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926201 | AC1-098 C | Adder | 4.02 MW | 3.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926202 | AC1-098 E | Adder | 2.39 MW | 2.03 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926211 | AC1-099 C | Adder | 1.35 MW | 1.14 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926212 | AC1-099 E | Adder | 0.79 MW | 0.67 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934331 | AD1-057 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934332 | AD1-057 E O1 | 50/50 | 4.77 MW | 4.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934521 | AD1-076 C | 50/50 | 55.08 MW | 55.08 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934522 | AD1-076 E | 50/50 | 28.05 MW | 28.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943171 | AE2-346 C | 50/50 | 1.25 MW | 1.25 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943172 | AE2-346 E | 50/50 | 0.54 MW | 0.54 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944141 | AF1-082 | Adder | 1.36 MW | 1.15 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960081 | AF2-299 C | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960082 | AF2-299 E | Adder | 0.79 MW | 0.67 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315294 | 1DOMTR10 | 50/50 | 13.82 MW | 13.82 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 900672 | V4-068 E | Adder | 0.21 MW | 0.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917332 | Z2-043 E | 50/50 | 0.98 MW | 0.98 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917342 | Z2-044 E | Adder | 0.26 MW | 0.23 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922922 | AB1-081 C OP | Adder | 4.22 MW | 3.59 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922923 | AB1-081 E OP | Adder | 1.81 MW | 1.54 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923262 | AB1-132 C OP | Adder | 10.39 MW | 8.83 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923263 | AB1-132 E OP | Adder | 4.45 MW | 3.78 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923573 | AB1-173 E OP | Adder | 0.56 MW | 0.47 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923991 | AB2-040 C O1 | Adder | 3.88 MW | 3.29 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924152 | AB2-059 E OP | Adder | 2.56 MW | 2.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925121 | AB2-169 C | 50/50 | 1.75 MW | 1.75 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925122 | AB2-169 E | 50/50 | 9.05 MW | 9.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925591 | AC1-034 C | Adder | 3.22 MW | 2.74 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925592 | AC1-034 E | Adder | 2.43 MW | 2.07 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932631 | AC2-084 C | Adder | 5.73 MW | 4.87 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932632 | AC2-084 E | Adder | 2.82 MW | 2.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938222 | AE1-035 E | 50/50 | 1.19 MW | 1.19 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940491 | AE2-034 C | 50/50 | 6.21 MW | 6.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940492 | AE2-034 E | 50/50 | 2.66 MW | 2.66 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940571 | AE2-044 C | Adder | 2.11 MW | 1.79 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940572 | AE2-044 E | Adder | 0.9 MW | 0.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946281 | AF1-292 C | Adder | 0.71 MW | 0.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946282 | AF1-292 E | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957521 | AF2-046 C | 50/50 | 12.48 MW | 12.48 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957522 | AF2-046 E | 50/50 | 6.28 MW | 6.28 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957531 | AF2-047 C | 50/50 | 14.76 MW | 14.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957532 | AF2-047 E | 50/50 | 7.42 MW | 7.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957861 | AF2-080 C | 50/50 | 14.16 MW | 14.16 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957862 | AF2-080 E | 50/50 | 6.28 MW | 6.28 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314539 | 3UNCAMP | Adder | 1.16 MW | 0.98 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 916042 | Z1-036 E | Adder | 17.69 MW | 15.03 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940481 | AE2-033 C | Adder | 5.39 MW | 4.58 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940482 | AE2-033 E | Adder | 3.64 MW | 3.09 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946011 | AF1-266 | Adder | 4.51 MW | 3.84 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919152 | AA1-139 E | Adder | 2.13 MW | 1.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 937221 | AD2-160 C O1 | Adder | 1.86 MW | 1.58 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 937222 | AD2-160 E O1 | Adder | 0.97 MW | 0.83 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 942401 | AE2-253 C | Adder | 1.95 MW | 1.66 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 942402 | AE2-253 E | Adder | 0.88 MW | 0.75 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943611 | AF1-032 C | Adder | 0.59 MW | 0.5 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943612 | AF1-032 E | Adder | 0.31 MW | 0.27 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944871 | AF1-152 C | Adder | 2.55 MW | 2.17 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944872 | AF1-152 E | Adder | 1.7 MW | 1.45 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315141 | 1GASTONB | 50/50 | 2.36 MW | 2.36 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315292 | 1DOMTR78 | 50/50 | 1.85 MW | 1.85 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315611 | 6Z1-036WIND | Adder | 2.63 MW | 2.24 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 913392 | Y1-086 E | Adder | 0.91 MW | 0.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923832 | AB2-022 E | Adder | 0.51 MW | 0.43 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923852 | AB2-025 E | Adder | 0.35 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938221 | AE1-035 C | 50/50 | 2.44 MW | 2.44 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941101 | AE2-104 C O1 | Adder | 1.16 MW | 0.99 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941102 | AE2-104 E O1 | Adder | 1.85 MW | 1.57 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957491 | AF2-043 C | Adder | 0.72 MW | 0.61 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957492 | AF2-043 E | Adder | 0.48 MW | 0.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 901082 | W1-029 E | Adder | 15.4 MW | 13.09 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917122 | Z2-027 E | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941501 | AE2-147 C | Adder | 7.66 MW | 6.51 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941502 | AE2-147 E | Adder | 5.11 MW | 4.34 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957871 | AF2-081 C | Adder | 3.31 MW | 2.82 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957872 | AF2-081 E | Adder | 1.42 MW | 1.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 958161 | AF2-110 C | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 958162 | AF2-110 E | Adder | 0.75 MW | 0.64 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314574 | 6EVERETS | 50/50 | 0.65 MW | 0.65 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917512 | Z2-088 E OP1 | 50/50 | 12.96 MW | 12.96 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920672 | AA2-174 E OP | Adder | 0.29 MW | 0.24 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923911 | AB2-031 C O1 | Adder | 1.18 MW | 1.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923912 | AB2-031 E O1 | Adder | 0.58 MW | 0.49 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924501 | AB2-099 C | 50/50 | 0.52 MW | 0.52 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924502 | AB2-099 E | 50/50 | 0.22 MW | 0.22 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924512 | AB2-100 E | Adder | 2.88 MW | 2.45 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925172 | AB2-174 E O1 | Adder | 3.25 MW | 2.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926071 | AC1-086 C | Adder | 15.3 MW | 13.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926072 | AC1-086 E | Adder | 6.96 MW | 5.92 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927021 | AC1-189 C | 50/50 | 15.6 MW | 15.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927022 | AC1-189 E | 50/50 | 7.77 MW | 7.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927141 | AC1-208 C | Adder | 5.2 MW | 4.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927142 | AC1-208 E | Adder | 2.31 MW | 1.96 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923572 | AB1-173 C OP | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923582 | AB1-173AC OP | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923583 | AB1-173AE OP | Adder | 0.56 MW | 0.47 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960331 | AF2-324 C O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960332 | AF2-324 E O1 | 50/50 | 4.41 MW | 4.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315614 | AA2-178 C | 50/50 | 1.44 MW | 1.44 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 907092 | X1-038 E | Adder | 2.89 MW | 2.46 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920692 | AA2-178 E | 50/50 | 3.55 MW | 3.55 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923831 | AB2-022 C | Adder | 0.95 MW | 0.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938531 | AE1-072 C O1 | Adder | 6.1 MW | 5.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938532 | AE1-072 E O1 | Adder | 3.18 MW | 2.7 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938771 | AE1-103 C O1 | Adder | 1.39 MW | 1.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938772 | AE1-103 E O1 | Adder | 1.91 MW | 1.63 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940541 | AE2-040 O1 | Adder | 0.89 MW | 0.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918561 | AA1-072 C | 50/50 | 0.29 MW | 0.29 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918562 | AA1-072 E | 50/50 | 0.14 MW | 0.14 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 933981 | AD1-022 C | 50/50 | 9.04 MW | 9.04 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 933982 | AD1-022 E | 50/50 | 4.92 MW | 4.92 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315602 | 1HOLLOMANSOL | 50/50 | 1.7 MW | 1.7 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918512 | AA1-065 E OP | 50/50 | 4.81 MW | 4.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.63 MW | 1.63 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.19 MW | 1.19 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 3.17 MW | 3.17 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.46 MW | 4.46 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.73 MW | 5.73 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.38 MW | 1.38 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.49 MW | 0.49 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.86 MW | 0.86 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.34 MW | 1.34 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.39 MW | 2.39 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.76 MW | 0.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.46 MW | 1.46 MW |
| Details for 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 934521 | AD1-076 C | 50/50 | 37.49 MW | 37.49 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 934522 | AD1-076 E | 50/50 | 19.09 MW | 19.09 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315294 | 1DOMTR10 | 50/50 | 13.39 MW | 13.39 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 925121 | AB2-169 C | 50/50 | 3.44 MW | 3.44 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 925122 | AB2-169 E | 50/50 | 17.8 MW | 17.8 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 940491 | AE2-034 C | Adder | 3.98 MW | 3.39 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 940492 | AE2-034 E | Adder | 1.71 MW | 1.45 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 957531 | AF2-047 C | Adder | 9.47 MW | 8.05 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 957532 | AF2-047 E | Adder | 4.76 MW | 4.05 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 916042 | Z1-036 E | Adder | 9.5 MW | 8.07 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315292 | 1DOMTR78 | 50/50 | 1.79 MW | 1.79 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 315611 | 6Z1-036WIND | Adder | 1.41 MW | 1.2 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | 920692 | AA2-178 E | Adder | 2.28 MW | 1.94 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.19 MW | 0.19 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.01 MW | 0.01 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.13 MW | 0.13 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.34 MW | 0.34 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.51 MW | 0.51 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.04 MW | 0.04 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.06 MW | 0.06 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.1 MW | 0.1 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.15 MW | 0.15 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.28 MW | 0.28 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| 3FIVE PT-3WHARTON 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 25-2034-A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.16 MW | 0.16 MW |
| Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 0.62 MW | 0.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 5.49 MW | 4.67 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 2.76 MW | 2.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 2.2 MW | 1.87 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 25.91 MW | 22.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940481 | AE2-033 C | Adder | 15.41 MW | 13.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940482 | AE2-033 E | Adder | 10.39 MW | 8.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946011 | AF1-266 | Adder | 12.9 MW | 10.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314189 | 6PAPERMILL | Adder | 8.74 MW | 7.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314229 | 6MT RD221 | 50/50 | 0.24 MW | 0.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314236 | 6NRTHEST | 50/50 | 0.33 MW | 0.33 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314241 | 6OLDCHRC | 50/50 | 1.37 MW | 1.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 314250 | 6ROCKVILLE | 50/50 | 0.55 MW | 0.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315060 | 1CHESTF5 | Adder | 88.4 MW | 75.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315065 | 1CHESTF6 | Adder | 172.48 MW | 146.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315067 | 1DARBY 1 | 50/50 | 4.41 MW | 4.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315068 | 1DARBY 2 | 50/50 | 4.41 MW | 4.41 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315069 | 1DARBY 3 | 50/50 | 4.43 MW | 4.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315070 | 1DARBY 4 | 50/50 | 4.43 MW | 4.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315073 | 1STONECA | Adder | 9.36 MW | 7.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315074 | 1HOPCGN1 | Adder | 11.29 MW | 9.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315075 | 1HOPCGN2 | Adder | 11.14 MW | 9.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315083 | 1SPRUNCA | Adder | 14.9 MW | 12.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315084 | 1SPRUNCB | Adder | 14.9 MW | 12.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | Adder | 5.94 MW | 5.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926412 | AC1-112 E | 50/50 | 1.93 MW | 1.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926661 | AC1-147 C | Adder | 2.13 MW | 1.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 1.25 MW | 1.06 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | Adder | 6.99 MW | 5.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | Adder | 4.66 MW | 3.96 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934141 | AD1-041 C | Adder | 6.7 MW | 5.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934142 | AD1-041 E | Adder | 4.47 MW | 3.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934392 | AD1-063 E | Adder | 1.38 MW | 1.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934781 | AD1-105 C | Adder | 11.68 MW | 9.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934782 | AD1-105 E | Adder | 7.78 MW | 6.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935111 | AD1-144 C | Adder | 1.68 MW | 1.43 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 0.92 MW | 0.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936151 | AD2-021 | 50/50 | 0.36 MW | 0.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936581 | AD2-073 C | Adder | 2.12 MW | 1.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936582 | AD2-073 E | Adder | 1.05 MW | 0.89 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936591 | AD2-074 C | Adder | 6.23 MW | 5.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936592 | AD2-074 E | Adder | 10.16 MW | 8.63 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936661 | AD2-085 C | Adder | 3.5 MW | 2.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936662 | AD2-085 E | Adder | 5.71 MW | 4.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936762 | AD2-097 E | Adder | 14.13 MW | 12.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | Adder | 5.42 MW | 4.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | Adder | 2.84 MW | 2.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942151 | AE2-227 C | Adder | 3.29 MW | 2.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942152 | AE2-227 E | Adder | 2.19 MW | 1.86 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942161 | AE2-228 C | Adder | 3.0 MW | 2.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942162 | AE2-228 E | Adder | 2.0 MW | 1.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942191 | AE2-231 C O1 | Adder | 4.16 MW | 3.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942192 | AE2-231 E O1 | Adder | 2.77 MW | 2.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942341 | AE2-247 C | Adder | 1.52 MW | 1.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942342 | AE2-247 E | Adder | 2.1 MW | 1.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942371 | AE2-250 C O1 | Adder | 12.68 MW | 10.78 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942372 | AE2-250 E O1 | Adder | 6.69 MW | 5.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | Adder | 5.7 MW | 4.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | Adder | 2.56 MW | 2.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943431 | AF1-014 C | Adder | 1.64 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943432 | AF1-014 E | Adder | 2.89 MW | 2.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943461 | AF1-017 C | Adder | 1.37 MW | 1.17 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943462 | AF1-017 E | Adder | 2.24 MW | 1.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943471 | AF1-018 | Adder | 9.22 MW | 7.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 1.63 MW | 1.39 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 0.86 MW | 0.73 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943621 | AF1-033 C | Adder | 2.61 MW | 2.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943622 | AF1-033 E | Adder | 1.35 MW | 1.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943741 | AF1-042 C | Adder | 3.26 MW | 2.77 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 943742 | AF1-042 E | Adder | 5.32 MW | 4.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944631 | AF1-128 O1 | Adder | 68.79 MW | 58.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 4.84 MW | 4.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 3.23 MW | 2.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945361 | AF1-201 C O1 | Adder | 18.2 MW | 15.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945362 | AF1-201 E O1 | Adder | 12.13 MW | 10.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 945831 | AF1-248 | Adder | 0.36 MW | 0.31 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960091 | AF2-300 C | Adder | 1.89 MW | 1.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 960092 | AF2-300 E | Adder | 1.26 MW | 1.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315611 | 6Z1-036WIND | Adder | 3.86 MW | 3.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 2.02 MW | 1.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | Adder | 1.76 MW | 1.5 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 1.14 MW | 0.97 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923842 | AB2-024 E | Adder | 1.48 MW | 1.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923852 | AB2-025 E | Adder | 1.09 MW | 0.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 930122 | AB1-027 E | 50/50 | 1.9 MW | 1.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932591 | AC2-079 C O1 | Adder | 5.82 MW | 4.95 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932592 | AC2-079 E O1 | Adder | 9.5 MW | 8.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938551 | AE1-074 C | Adder | 3.13 MW | 2.66 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938552 | AE1-074 E | Adder | 1.58 MW | 1.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939312 | AE1-162 E | Adder | 1.5 MW | 1.27 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939431 | AE1-175 C | Adder | 2.89 MW | 2.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939432 | AE1-175 E | Adder | 1.43 MW | 1.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939611 | AE1-191 C | Adder | 13.41 MW | 11.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939612 | AE1-191 E | Adder | 8.94 MW | 7.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940231 | AE2-005 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940232 | AE2-005 E | Adder | 2.82 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940431 | AE2-027 C O1 | Adder | 17.91 MW | 15.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940432 | AE2-027 E O1 | Adder | 11.94 MW | 10.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940651 | AE2-052 | Adder | 4.23 MW | 3.6 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 3.2 MW | 2.72 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 5.08 MW | 4.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | Adder | 26.62 MW | 22.63 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | Adder | 107.43 MW | 91.32 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | Adder | 27.36 MW | 23.26 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | Adder | 106.7 MW | 90.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | Adder | 24.85 MW | 21.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | Adder | 109.06 MW | 92.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946261 | AF1-291 C | Adder | 3.0 MW | 2.55 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 946262 | AF1-291 E | Adder | 2.0 MW | 1.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957411 | AF2-035 C | Adder | 7.55 MW | 6.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957412 | AF2-035 E | Adder | 5.04 MW | 4.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 2.0 MW | 1.7 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 1.33 MW | 1.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957601 | AF2-054 C | Adder | 2.6 MW | 2.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957602 | AF2-054 E | Adder | 1.74 MW | 1.48 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 3.38 MW | 2.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 29.21 MW | 24.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 0.97 MW | 0.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925332 | AB2-190 E | Adder | 9.95 MW | 8.46 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | Adder | 1.07 MW | 0.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 14.52 MW | 12.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 9.68 MW | 8.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941581 | AE2-155 C | 50/50 | 1.11 MW | 1.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941582 | AE2-155 E | 50/50 | 0.47 MW | 0.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | Adder | 16.91 MW | 14.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942001 | AE2-212 C | Adder | 2.84 MW | 2.42 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942002 | AE2-212 E | Adder | 1.9 MW | 1.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957831 | AF2-077 C | Adder | 2.47 MW | 2.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957832 | AF2-077 E | Adder | 1.65 MW | 1.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | Adder | 9.24 MW | 7.85 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | Adder | 3.96 MW | 3.37 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957911 | AF2-085 | Adder | 3.86 MW | 3.28 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 1.3 MW | 1.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 2.07 MW | 1.76 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958261 | AF2-120 C | Adder | 6.94 MW | 5.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 958262 | AF2-120 E | Adder | 4.62 MW | 3.93 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924512 | AB2-100 E | Adder | 5.17 MW | 4.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 907092 | X1-038 E | Adder | 5.51 MW | 4.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 923831 | AB2-022 C | Adder | 2.12 MW | 1.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924812 | AB2-134 E OP | Adder | 15.45 MW | 13.13 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925051 | AB2-160 C O1 | Adder | 7.14 MW | 6.07 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925052 | AB2-160 E O1 | Adder | 11.65 MW | 9.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925061 | AB2-161 C O1 | Adder | 3.79 MW | 3.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925062 | AB2-161 E O1 | Adder | 6.18 MW | 5.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925331 | AB2-190 C | Adder | 23.22 MW | 19.74 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926751 | AC1-161 C O1 | Adder | 27.22 MW | 23.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926752 | AC1-161 E O1 | Adder | 11.62 MW | 9.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927222 | AC1-216 E O1 | Adder | 9.43 MW | 8.02 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932041 | AC2-012 C | Adder | 7.59 MW | 6.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932042 | AC2-012 E | Adder | 12.38 MW | 10.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933291 | AC2-141 C | Adder | 27.22 MW | 23.14 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933292 | AC2-141 E | Adder | 11.62 MW | 9.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934011 | AD1-025 C | Adder | 20.62 MW | 17.53 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934012 | AD1-025 E | Adder | 12.21 MW | 10.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934571 | AD1-082 C | Adder | 8.63 MW | 7.34 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 934572 | AD1-082 E | Adder | 4.92 MW | 4.18 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935161 | AD1-151 C O1 | Adder | 20.24 MW | 17.21 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 935162 | AD1-151 E O1 | Adder | 13.5 MW | 11.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938531 | AE1-072 C O1 | Adder | 16.23 MW | 13.8 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938532 | AE1-072 E O1 | Adder | 8.46 MW | 7.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C O1 | Adder | 2.65 MW | 2.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E O1 | Adder | 3.65 MW | 3.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939191 | AE1-149 C O1 | Adder | 12.69 MW | 10.79 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939192 | AE1-149 E O1 | Adder | 8.46 MW | 7.19 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939311 | AE1-162 C | Adder | 2.25 MW | 1.91 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940541 | AE2-040 O1 | Adder | 2.76 MW | 2.35 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 942551 | AE2-270 | Adder | 32.84 MW | 27.92 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957711 | AF2-065 C | Adder | 16.92 MW | 14.38 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 957712 | AF2-065 E | Adder | 16.26 MW | 13.82 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925861 | AC1-065 C | Adder | 4.33 MW | 3.68 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 925862 | AC1-065 E | Adder | 7.06 MW | 6.0 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926551 | AC1-134 | 50/50 | 2.51 MW | 2.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926781 | AC1-164 C | Adder | 58.25 MW | 49.51 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 926782 | AC1-164 E | Adder | 26.17 MW | 22.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927041 | AC1-191 C O1 | 50/50 | 17.69 MW | 17.69 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 927042 | AC1-191 E O1 | 50/50 | 8.81 MW | 8.81 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936242 | AD2-030 E | Adder | 1.46 MW | 1.24 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936301 | AD2-039 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936302 | AD2-039 E | Adder | 2.82 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936341 | AD2-044 C | Adder | 0.26 MW | 0.22 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 936342 | AD2-044 E | Adder | 0.3 MW | 0.25 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938031 | AE1-004 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315610 | 6AA1-145GAS | 50/50 | 17.09 MW | 17.09 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 924061 | AB2-050 | 50/50 | 1.01 MW | 1.01 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 938032 | AE1-004 E | Adder | 2.82 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939241 | AE1-155 C | Adder | 14.21 MW | 12.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 939242 | AE1-155 E | Adder | 9.47 MW | 8.05 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932831 | AC2-110 C | Adder | 1.73 MW | 1.47 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 932832 | AC2-110 E | Adder | 2.82 MW | 2.4 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933261 | AC2-137 C | 50/50 | 3.15 MW | 3.15 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933262 | AC2-137 E | 50/50 | 2.04 MW | 2.04 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933271 | AC2-138 C | Adder | 0.83 MW | 0.71 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 933272 | AC2-138 E | Adder | 1.04 MW | 0.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 940551 | AE2-041 O1 | Adder | 9.22 MW | 7.83 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | Adder | 44.14 MW | 37.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | Adder | 101.06 MW | 85.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | Adder | 44.14 MW | 37.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | Adder | 101.06 MW | 85.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | Adder | 44.14 MW | 37.52 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | Adder | 101.06 MW | 85.9 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315043 | 1FOUR RIVERA | 50/50 | 4.88 MW | 4.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315044 | 1FOUR RIVERB | 50/50 | 4.88 MW | 4.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315045 | 1FOUR RIVERC | 50/50 | 5.98 MW | 5.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315046 | 1FOUR RIVERD | 50/50 | 4.88 MW | 4.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315047 | 1FOUR RIVERE | 50/50 | 4.88 MW | 4.88 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | 315048 | 1FOUR RIVERF | 50/50 | 5.98 MW | 5.98 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.11 MW | 0.11 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.23 MW | 0.23 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 4.94 MW | 4.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.45 MW | 10.45 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.08 MW | 1.08 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 13.94 MW | 13.94 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 31.12 MW | 31.12 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.61 MW | 13.61 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.16 MW | 2.16 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 1.29 MW | 1.29 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 3.36 MW | 3.36 MW |
| 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: H2T557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 3.5 MW | 3.5 MW |
| Details for 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314582 | 3KELFORD | 50/50 | 0.43 MW | 0.43 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918532 | AA1-067 E | 50/50 | 0.73 MW | 0.73 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919692 | AA2-053 E OP | 50/50 | 2.35 MW | 2.35 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919702 | AA2-057 E OP | Adder | 2.09 MW | 1.78 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920592 | AA2-165 E | Adder | 0.35 MW | 0.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926201 | AC1-098 C | 50/50 | 4.44 MW | 4.44 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926202 | AC1-098 E | 50/50 | 2.65 MW | 2.65 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926211 | AC1-099 C | 50/50 | 1.49 MW | 1.49 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926212 | AC1-099 E | 50/50 | 0.87 MW | 0.87 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934521 | AD1-076 C | 50/50 | 120.46 MW | 120.46 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934522 | AD1-076 E | 50/50 | 61.34 MW | 61.34 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943171 | AE2-346 C | 50/50 | 1.3 MW | 1.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943172 | AE2-346 E | 50/50 | 0.56 MW | 0.56 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315294 | 1DOMTR10 | 50/50 | 21.21 MW | 21.21 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315606 | 3AA2-053SOLA | 50/50 | 0.95 MW | 0.95 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 900672 | V4-068 E | 50/50 | 0.18 MW | 0.18 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917332 | Z2-043 E | 50/50 | 1.07 MW | 1.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923262 | AB1-132 C OP | Adder | 8.36 MW | 7.11 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923263 | AB1-132 E OP | Adder | 3.58 MW | 3.04 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925121 | AB2-169 C | 50/50 | 1.86 MW | 1.86 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925122 | AB2-169 E | 50/50 | 9.61 MW | 9.61 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932631 | AC2-084 C | 50/50 | 6.33 MW | 6.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932632 | AC2-084 E | 50/50 | 3.12 MW | 3.12 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938222 | AE1-035 E | 50/50 | 1.33 MW | 1.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940491 | AE2-034 C | 50/50 | 19.38 MW | 19.38 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940492 | AE2-034 E | 50/50 | 8.3 MW | 8.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957521 | AF2-046 C | 50/50 | 11.31 MW | 11.31 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957522 | AF2-046 E | 50/50 | 5.69 MW | 5.69 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957531 | AF2-047 C | 50/50 | 46.05 MW | 46.05 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957532 | AF2-047 E | 50/50 | 23.16 MW | 23.16 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957861 | AF2-080 C | 50/50 | 6.7 MW | 6.7 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957862 | AF2-080 E | 50/50 | 2.97 MW | 2.97 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 916042 | Z1-036 E | 50/50 | 99.72 MW | 99.72 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314638 | 6ELIZ CT | 50/50 | 1.02 MW | 1.02 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314639 | 6TANGLEW | 50/50 | 1.8 MW | 1.8 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 944871 | AF1-152 C | 50/50 | 20.22 MW | 20.22 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 944872 | AF1-152 E | 50/50 | 13.48 MW | 13.48 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315292 | 1DOMTR78 | 50/50 | 2.84 MW | 2.84 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315605 | 6W1-029WIND | 50/50 | 3.16 MW | 3.16 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315611 | 6Z1-036WIND | 50/50 | 14.85 MW | 14.85 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 913392 | Y1-086 E | 50/50 | 9.61 MW | 9.61 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923832 | AB2-022 E | 50/50 | 5.42 MW | 5.42 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938221 | AE1-035 C | 50/50 | 2.74 MW | 2.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 901082 | W1-029 E | 50/50 | 122.02 MW | 122.02 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917122 | Z2-027 E | 50/50 | 4.44 MW | 4.44 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 941501 | AE2-147 C | 50/50 | 60.67 MW | 60.67 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 941502 | AE2-147 E | 50/50 | 40.45 MW | 40.45 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314574 | 6EVERETS | 50/50 | 0.29 MW | 0.29 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917512 | Z2-088 E OP1 | 50/50 | 6.28 MW | 6.28 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920671 | AA2-174 C OP | 50/50 | 0.04 MW | 0.04 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920672 | AA2-174 E OP | 50/50 | 0.27 MW | 0.27 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924501 | AB2-099 C | 50/50 | 0.54 MW | 0.54 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924502 | AB2-099 E | 50/50 | 0.23 MW | 0.23 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926071 | AC1-086 C | Adder | 12.31 MW | 10.46 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926072 | AC1-086 E | Adder | 5.6 MW | 4.76 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927021 | AC1-189 C | 50/50 | 7.37 MW | 7.37 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927022 | AC1-189 E | 50/50 | 3.67 MW | 3.67 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927141 | AC1-208 C | 50/50 | 5.68 MW | 5.68 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927142 | AC1-208 E | 50/50 | 2.52 MW | 2.52 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315614 | AA2-178 C | 50/50 | 4.49 MW | 4.49 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920692 | AA2-178 E | 50/50 | 11.07 MW | 11.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923831 | AB2-022 C | 50/50 | 10.07 MW | 10.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918561 | AA1-072 C | 50/50 | 0.32 MW | 0.32 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918562 | AA1-072 E | 50/50 | 0.15 MW | 0.15 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933981 | AD1-022 C | 50/50 | 17.14 MW | 17.14 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933982 | AD1-022 E | 50/50 | 9.33 MW | 9.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315602 | 1HOLLOMANSOL | 50/50 | 1.9 MW | 1.9 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918512 | AA1-065 E OP | 50/50 | 5.39 MW | 5.39 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.27 MW | 2.27 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 7.53 MW | 7.53 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.19 MW | 0.19 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.57 MW | 1.57 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.74 MW | 2.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 13.74 MW | 13.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.76 MW | 8.76 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.43 MW | 0.43 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.42 MW | 0.42 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.55 MW | 1.55 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.29 MW | 7.29 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314541 | 3WATKINS | Adder | 0.92 MW | 0.78 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918492 | AA1-063AE OP | Adder | 3.18 MW | 2.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918532 | AA1-067 E | Adder | 0.88 MW | 0.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920042 | AA2-088 E OP | Adder | 13.14 MW | 11.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934521 | AD1-076 C | Adder | 76.71 MW | 65.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934522 | AD1-076 E | Adder | 39.06 MW | 33.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935171 | AD1-152 C O1 | Adder | 9.45 MW | 8.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935172 | AD1-152 E O1 | Adder | 6.3 MW | 5.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937481 | AD2-202 C O1 | Adder | 2.73 MW | 2.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937482 | AD2-202 E O1 | Adder | 1.28 MW | 1.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942931 | AE2-313 C | Adder | 53.59 MW | 45.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942932 | AE2-313 E | Adder | 35.73 MW | 30.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943171 | AE2-346 C | Adder | 1.75 MW | 1.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943172 | AE2-346 E | Adder | 0.75 MW | 0.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944011 | AF1-069 C | Adder | 19.52 MW | 16.59 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944012 | AF1-069 E | Adder | 7.58 MW | 6.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945811 | AF1-246 C O1 | Adder | 9.85 MW | 8.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945812 | AF1-246 E O1 | Adder | 13.61 MW | 11.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315294 | 1DOMTR10 | Adder | 14.85 MW | 12.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 900672 | V4-068 E | Adder | 0.37 MW | 0.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917332 | Z2-043 E | Adder | 1.39 MW | 1.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925122 | AB2-169 E | Adder | 7.63 MW | 6.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938222 | AE1-035 E | Adder | 1.41 MW | 1.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940491 | AE2-034 C | Adder | 10.58 MW | 9.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940492 | AE2-034 E | Adder | 4.54 MW | 3.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941031 | AE2-094 C | Adder | 59.74 MW | 50.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941032 | AE2-094 E | Adder | 26.75 MW | 22.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957481 | AF2-042 C | Adder | 70.38 MW | 59.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957482 | AF2-042 E | Adder | 46.92 MW | 39.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957521 | AF2-046 C | Adder | 20.84 MW | 17.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957522 | AF2-046 E | Adder | 10.48 MW | 8.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957531 | AF2-047 C | Adder | 25.15 MW | 21.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957532 | AF2-047 E | Adder | 12.65 MW | 10.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957861 | AF2-080 C | Adder | 9.02 MW | 7.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957862 | AF2-080 E | Adder | 4.0 MW | 3.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314539 | 3UNCAMP | Adder | 3.33 MW | 2.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916042 | Z1-036 E | Adder | 45.01 MW | 38.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940641 | AE2-051 C O1 | 50/50 | 28.23 MW | 28.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940642 | AE2-051 E O1 | 50/50 | 18.82 MW | 18.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314491 | 3PENDLTN | 50/50 | 0.6 MW | 0.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 919152 | AA1-139 E | Adder | 10.97 MW | 9.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926661 | AC1-147 C | 50/50 | 3.85 MW | 3.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | 50/50 | 2.26 MW | 2.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | 50/50 | 13.05 MW | 13.05 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | 50/50 | 8.7 MW | 8.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935111 | AD1-144 C | Adder | 2.69 MW | 2.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935112 | AD1-144 E | Adder | 1.47 MW | 1.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936661 | AD2-085 C | Adder | 4.3 MW | 3.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936662 | AD2-085 E | Adder | 7.01 MW | 5.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | 50/50 | 10.06 MW | 10.06 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | 50/50 | 5.28 MW | 5.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942341 | AE2-247 C | Adder | 1.86 MW | 1.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942342 | AE2-247 E | Adder | 2.56 MW | 2.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | 50/50 | 10.58 MW | 10.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | 50/50 | 4.75 MW | 4.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943461 | AF1-017 C | Adder | 1.68 MW | 1.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943462 | AF1-017 E | Adder | 2.74 MW | 2.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943611 | AF1-032 C | Adder | 2.87 MW | 2.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943612 | AF1-032 E | Adder | 1.52 MW | 1.29 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943621 | AF1-033 C | Adder | 2.85 MW | 2.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943622 | AF1-033 E | Adder | 1.47 MW | 1.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944871 | AF1-152 C | Adder | 8.55 MW | 7.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944872 | AF1-152 E | Adder | 5.7 MW | 4.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945361 | AF1-201 C O1 | Adder | 17.42 MW | 14.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945362 | AF1-201 E O1 | Adder | 11.61 MW | 9.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315098 | 1CHESPKA | 50/50 | 0.79 MW | 0.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315099 | 1CHESPKB | 50/50 | 1.31 MW | 1.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315108 | 1ELIZAR1 | 50/50 | 5.85 MW | 5.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315109 | 1ELIZAR2 | 50/50 | 5.75 MW | 5.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315110 | 1ELIZAR3 | 50/50 | 5.93 MW | 5.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315233 | 1SURRY 2 | 50/50 | 57.95 MW | 57.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315611 | 6Z1-036WIND | Adder | 6.7 MW | 5.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 913392 | Y1-086 E | Adder | 3.66 MW | 3.11 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | 50/50 | 3.24 MW | 3.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923832 | AB2-022 E | Adder | 2.06 MW | 1.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932591 | AC2-079 C O1 | Adder | 7.21 MW | 6.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932592 | AC2-079 E O1 | Adder | 11.77 MW | 10.0 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938221 | AE1-035 C | Adder | 2.91 MW | 2.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939312 | AE1-162 E | Adder | 1.98 MW | 1.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941101 | AE2-104 C O1 | Adder | 5.09 MW | 4.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941102 | AE2-104 E O1 | Adder | 8.09 MW | 6.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | 50/50 | 49.03 MW | 49.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | 50/50 | 197.84 MW | 197.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | 50/50 | 50.38 MW | 50.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | 50/50 | 196.48 MW | 196.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | 50/50 | 45.86 MW | 45.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | 50/50 | 201.21 MW | 201.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957491 | AF2-043 C | Adder | 3.51 MW | 2.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957492 | AF2-043 E | Adder | 2.34 MW | 1.99 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | 50/50 | 6.12 MW | 6.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 901082 | W1-029 E | Adder | 51.56 MW | 43.82 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917122 | Z2-027 E | Adder | 1.75 MW | 1.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | 50/50 | 1.97 MW | 1.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941501 | AE2-147 C | Adder | 25.64 MW | 21.79 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941502 | AE2-147 E | Adder | 17.09 MW | 14.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | 50/50 | 30.68 MW | 30.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957871 | AF2-081 C | Adder | 17.07 MW | 14.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957872 | AF2-081 E | Adder | 7.32 MW | 6.22 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958161 | AF2-110 C | Adder | 2.08 MW | 1.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958162 | AF2-110 E | Adder | 3.3 MW | 2.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 924501 | AB2-099 C | Adder | 0.73 MW | 0.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 924502 | AB2-099 E | Adder | 0.31 MW | 0.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927021 | AC1-189 C | Adder | 9.93 MW | 8.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927022 | AC1-189 E | Adder | 4.95 MW | 4.21 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934611 | AD1-087 C O1 | Adder | 9.33 MW | 7.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934612 | AD1-087 E O1 | Adder | 4.38 MW | 3.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 907092 | X1-038 E | Adder | 8.32 MW | 7.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920692 | AA2-178 E | Adder | 6.05 MW | 5.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923831 | AB2-022 C | Adder | 3.83 MW | 3.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926751 | AC1-161 C O1 | 50/50 | 61.33 MW | 61.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926752 | AC1-161 E O1 | 50/50 | 26.18 MW | 26.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932041 | AC2-012 C | 50/50 | 13.71 MW | 13.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932042 | AC2-012 E | 50/50 | 22.38 MW | 22.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933291 | AC2-141 C | 50/50 | 61.33 MW | 61.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933292 | AC2-141 E | 50/50 | 26.18 MW | 26.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938531 | AE1-072 C O1 | Adder | 29.87 MW | 25.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938532 | AE1-072 E O1 | Adder | 15.57 MW | 13.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938771 | AE1-103 C O1 | Adder | 3.99 MW | 3.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938772 | AE1-103 E O1 | Adder | 5.51 MW | 4.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939311 | AE1-162 C | Adder | 2.97 MW | 2.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939411 | AE1-173 C | 50/50 | 150.54 MW | 150.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939412 | AE1-173 E | 50/50 | 100.36 MW | 100.36 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918561 | AA1-072 C | Adder | 0.42 MW | 0.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918562 | AA1-072 E | Adder | 0.2 MW | 0.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944581 | AF1-123 C O1 | 50/50 | 86.42 MW | 86.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944582 | AF1-123 E O1 | 50/50 | 197.89 MW | 197.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944591 | AF1-124 C O1 | 50/50 | 86.42 MW | 86.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944592 | AF1-124 E O1 | 50/50 | 197.89 MW | 197.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944601 | AF1-125 C O1 | 50/50 | 86.42 MW | 86.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944602 | AF1-125 E O1 | 50/50 | 197.89 MW | 197.89 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933981 | AD1-022 C | Adder | 12.1 MW | 10.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933982 | AD1-022 E | Adder | 6.58 MW | 5.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918512 | AA1-065 E OP | Adder | 5.74 MW | 4.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.69 MW | 0.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.32 MW | 1.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.46 MW | 9.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 31.64 MW | 31.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.72 MW | 1.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.93 MW | 6.93 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 23.37 MW | 23.37 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 63.34 MW | 63.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.02 MW | 38.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 3.64 MW | 3.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.28 MW | 2.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.47 MW | 4.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.44 MW | 6.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 25.57 MW | 25.57 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 0.96 MW | 0.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918492 | AA1-063AE OP | Adder | 4.91 MW | 4.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918532 | AA1-067 E | Adder | 0.9 MW | 0.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919692 | AA2-053 E OP | Adder | 4.44 MW | 3.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920042 | AA2-088 E OP | Adder | 13.97 MW | 11.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926201 | AC1-098 C | Adder | 7.38 MW | 6.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926202 | AC1-098 E | Adder | 4.4 MW | 3.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926211 | AC1-099 C | Adder | 2.47 MW | 2.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926212 | AC1-099 E | Adder | 1.45 MW | 1.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 77.79 MW | 66.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 39.61 MW | 33.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937481 | AD2-202 C O1 | Adder | 2.46 MW | 2.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937482 | AD2-202 E O1 | Adder | 1.15 MW | 0.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 47.03 MW | 39.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 31.36 MW | 26.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943171 | AE2-346 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943172 | AE2-346 E | Adder | 0.79 MW | 0.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 17.11 MW | 14.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 6.65 MW | 5.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945811 | AF1-246 C O1 | Adder | 8.8 MW | 7.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945812 | AF1-246 E O1 | Adder | 12.15 MW | 10.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 15.1 MW | 12.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 900672 | V4-068 E | Adder | 0.39 MW | 0.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917332 | Z2-043 E | Adder | 1.48 MW | 1.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925122 | AB2-169 E | Adder | 7.79 MW | 6.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932631 | AC2-084 C | Adder | 10.52 MW | 8.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932632 | AC2-084 E | Adder | 5.18 MW | 4.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938222 | AE1-035 E | Adder | 1.47 MW | 1.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 10.63 MW | 9.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 4.56 MW | 3.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 52.37 MW | 44.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 23.45 MW | 19.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957481 | AF2-042 C | Adder | 62.83 MW | 53.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957482 | AF2-042 E | Adder | 41.88 MW | 35.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957521 | AF2-046 C | Adder | 22.13 MW | 18.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957522 | AF2-046 E | Adder | 11.13 MW | 9.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 25.25 MW | 21.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 12.7 MW | 10.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957861 | AF2-080 C | Adder | 9.34 MW | 7.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957862 | AF2-080 E | Adder | 4.14 MW | 3.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 3.43 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 44.54 MW | 37.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 25.15 MW | 21.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 16.77 MW | 14.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314491 | 3PENDLTN | 50/50 | 0.58 MW | 0.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 10.67 MW | 9.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926661 | AC1-147 C | 50/50 | 3.74 MW | 3.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | 50/50 | 2.2 MW | 2.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | 50/50 | 12.65 MW | 12.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | 50/50 | 8.43 MW | 8.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935111 | AD1-144 C | Adder | 2.65 MW | 2.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 1.45 MW | 1.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 4.6 MW | 3.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 7.51 MW | 6.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | 50/50 | 9.77 MW | 9.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | 50/50 | 5.12 MW | 5.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 1.99 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 2.75 MW | 2.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | 50/50 | 10.27 MW | 10.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | 50/50 | 4.62 MW | 4.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 1.8 MW | 1.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 2.94 MW | 2.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 2.81 MW | 2.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 1.49 MW | 1.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 2.92 MW | 2.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 1.51 MW | 1.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 8.4 MW | 7.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 5.6 MW | 4.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945361 | AF1-201 C O1 | Adder | 17.6 MW | 14.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945362 | AF1-201 E O1 | Adder | 11.73 MW | 9.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315098 | 1CHESPKA | 50/50 | 0.77 MW | 0.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315099 | 1CHESPKB | 50/50 | 1.27 MW | 1.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315108 | 1ELIZAR1 | 50/50 | 5.68 MW | 5.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315109 | 1ELIZAR2 | 50/50 | 5.58 MW | 5.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315110 | 1ELIZAR3 | 50/50 | 5.75 MW | 5.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315233 | 1SURRY 2 | 50/50 | 56.38 MW | 56.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315611 | 6Z1-036WIND | Adder | 6.63 MW | 5.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 3.57 MW | 3.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | 50/50 | 3.14 MW | 3.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 2.02 MW | 1.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | Adder | 7.7 MW | 6.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | Adder | 12.57 MW | 10.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938221 | AE1-035 C | Adder | 3.04 MW | 2.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 1.98 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 5.1 MW | 4.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 8.11 MW | 6.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | 50/50 | 47.55 MW | 47.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | 50/50 | 191.88 MW | 191.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | 50/50 | 48.87 MW | 48.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | 50/50 | 190.56 MW | 190.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | 50/50 | 44.47 MW | 44.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | 50/50 | 195.13 MW | 195.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 3.44 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 2.29 MW | 1.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | 50/50 | 5.94 MW | 5.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 50.67 MW | 43.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 1.71 MW | 1.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | 50/50 | 1.91 MW | 1.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 25.2 MW | 21.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 16.8 MW | 14.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | 50/50 | 29.77 MW | 29.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 16.59 MW | 14.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 7.11 MW | 6.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 2.08 MW | 1.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 3.31 MW | 2.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920672 | AA2-174 E OP | Adder | 0.51 MW | 0.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924501 | AB2-099 C | Adder | 0.77 MW | 0.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924502 | AB2-099 E | Adder | 0.33 MW | 0.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926071 | AC1-086 C | Adder | 7.37 MW | 6.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926072 | AC1-086 E | Adder | 3.35 MW | 2.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927021 | AC1-189 C | Adder | 10.28 MW | 8.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927022 | AC1-189 E | Adder | 5.12 MW | 4.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934611 | AD1-087 C O1 | Adder | 8.41 MW | 7.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934612 | AD1-087 E O1 | Adder | 3.94 MW | 3.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 907092 | X1-038 E | Adder | 8.58 MW | 7.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 6.07 MW | 5.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923831 | AB2-022 C | Adder | 3.75 MW | 3.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926751 | AC1-161 C O1 | 50/50 | 58.62 MW | 58.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926752 | AC1-161 E O1 | 50/50 | 25.02 MW | 25.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932041 | AC2-012 C | 50/50 | 13.31 MW | 13.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932042 | AC2-012 E | 50/50 | 21.72 MW | 21.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933291 | AC2-141 C | 50/50 | 58.62 MW | 58.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933292 | AC2-141 E | 50/50 | 25.02 MW | 25.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938531 | AE1-072 C O1 | Adder | 29.06 MW | 24.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938532 | AE1-072 E O1 | Adder | 15.15 MW | 12.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C O1 | Adder | 4.12 MW | 3.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E O1 | Adder | 5.69 MW | 4.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939311 | AE1-162 C | Adder | 2.98 MW | 2.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939411 | AE1-173 C | Adder | 137.05 MW | 116.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939412 | AE1-173 E | Adder | 91.37 MW | 77.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918561 | AA1-072 C | Adder | 0.44 MW | 0.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918562 | AA1-072 E | Adder | 0.21 MW | 0.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944581 | AF1-123 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944582 | AF1-123 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944591 | AF1-124 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944592 | AF1-124 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944601 | AF1-125 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 12.35 MW | 10.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 6.72 MW | 5.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918512 | AA1-065 E OP | Adder | 5.98 MW | 5.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.65 MW | 0.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.24 MW | 1.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.98 MW | 8.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 29.7 MW | 29.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.66 MW | 1.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.52 MW | 6.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 22.63 MW | 22.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 59.8 MW | 59.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 35.73 MW | 35.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 3.52 MW | 3.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.15 MW | 2.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.19 MW | 4.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.12 MW | 6.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.84 MW | 23.84 MW |
| Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314541 | 3WATKINS | Adder | 1.04 MW | 0.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920042 | AA2-088 E OP | Adder | 15.05 MW | 12.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934521 | AD1-076 C | Adder | 83.9 MW | 71.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934522 | AD1-076 E | Adder | 42.72 MW | 36.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942931 | AE2-313 C | Adder | 53.59 MW | 45.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942932 | AE2-313 E | Adder | 35.73 MW | 30.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944011 | AF1-069 C | Adder | 19.5 MW | 16.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944012 | AF1-069 E | Adder | 7.58 MW | 6.44 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315294 | 1DOMTR10 | Adder | 16.28 MW | 13.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938222 | AE1-035 E | Adder | 1.58 MW | 1.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940491 | AE2-034 C | Adder | 11.47 MW | 9.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940492 | AE2-034 E | Adder | 4.92 MW | 4.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941031 | AE2-094 C | Adder | 59.68 MW | 50.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941032 | AE2-094 E | Adder | 26.73 MW | 22.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957531 | AF2-047 C | Adder | 27.26 MW | 23.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957532 | AF2-047 E | Adder | 13.71 MW | 11.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314539 | 3UNCAMP | Adder | 3.74 MW | 3.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916042 | Z1-036 E | Adder | 48.15 MW | 40.93 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940641 | AE2-051 C O1 | Adder | 28.0 MW | 23.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940642 | AE2-051 E O1 | Adder | 18.67 MW | 15.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314189 | 6PAPERMILL | Adder | 10.32 MW | 8.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314421 | 6WINCHST | 50/50 | 0.25 MW | 0.25 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 314491 | 3PENDLTN | 50/50 | 0.63 MW | 0.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315092 | 1YORKTN3 | 50/50 | 45.04 MW | 45.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 919152 | AA1-139 E | Adder | 11.48 MW | 9.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926661 | AC1-147 C | Adder | 4.06 MW | 3.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926662 | AC1-147 E | Adder | 2.39 MW | 2.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934061 | AD1-033 C | 50/50 | 13.61 MW | 13.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934062 | AD1-033 E | 50/50 | 9.07 MW | 9.07 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934141 | AD1-041 C | Adder | 7.99 MW | 6.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934142 | AD1-041 E | Adder | 5.32 MW | 4.53 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934392 | AD1-063 E | Adder | 1.65 MW | 1.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935111 | AD1-144 C | Adder | 3.0 MW | 2.55 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 935112 | AD1-144 E | Adder | 1.64 MW | 1.39 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936661 | AD2-085 C | Adder | 5.19 MW | 4.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936662 | AD2-085 E | Adder | 8.46 MW | 7.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937221 | AD2-160 C O1 | Adder | 10.51 MW | 8.93 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 937222 | AD2-160 E O1 | Adder | 5.51 MW | 4.68 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942341 | AE2-247 C | Adder | 2.24 MW | 1.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942342 | AE2-247 E | Adder | 3.1 MW | 2.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942401 | AE2-253 C | Adder | 11.06 MW | 9.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942402 | AE2-253 E | Adder | 4.97 MW | 4.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943431 | AF1-014 C | Adder | 1.91 MW | 1.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943432 | AF1-014 E | Adder | 3.37 MW | 2.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943461 | AF1-017 C | Adder | 2.03 MW | 1.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943462 | AF1-017 E | Adder | 3.31 MW | 2.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943471 | AF1-018 | Adder | 11.01 MW | 9.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943611 | AF1-032 C | Adder | 3.06 MW | 2.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943612 | AF1-032 E | Adder | 1.62 MW | 1.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943621 | AF1-033 C | Adder | 3.79 MW | 3.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 943622 | AF1-033 E | Adder | 1.95 MW | 1.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944871 | AF1-152 C | Adder | 9.1 MW | 7.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944872 | AF1-152 E | Adder | 6.06 MW | 5.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945361 | AF1-201 C O1 | Adder | 27.87 MW | 23.69 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 945362 | AF1-201 E O1 | Adder | 18.58 MW | 15.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315098 | 1CHESPKA | 50/50 | 0.83 MW | 0.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315099 | 1CHESPKB | 50/50 | 1.38 MW | 1.38 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315108 | 1ELIZAR1 | 50/50 | 6.15 MW | 6.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315109 | 1ELIZAR2 | 50/50 | 6.04 MW | 6.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315110 | 1ELIZAR3 | 50/50 | 6.23 MW | 6.23 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315233 | 1SURRY 2 | 50/50 | 55.54 MW | 55.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 315611 | 6Z1-036WIND | Adder | 7.17 MW | 6.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 913392 | Y1-086 E | Adder | 3.85 MW | 3.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 916192 | Z1-068 E | 50/50 | 3.39 MW | 3.39 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923832 | AB2-022 E | Adder | 2.18 MW | 1.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923842 | AB2-024 E | Adder | 1.74 MW | 1.48 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932591 | AC2-079 C O1 | Adder | 8.68 MW | 7.37 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932592 | AC2-079 E O1 | Adder | 14.15 MW | 12.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938221 | AE1-035 C | Adder | 3.26 MW | 2.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939312 | AE1-162 E | Adder | 2.37 MW | 2.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939431 | AE1-175 C | Adder | 4.27 MW | 3.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939432 | AE1-175 E | Adder | 2.12 MW | 1.8 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939611 | AE1-191 C | Adder | 15.98 MW | 13.58 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939612 | AE1-191 E | Adder | 10.65 MW | 9.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940231 | AE2-005 C | Adder | 2.02 MW | 1.71 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940232 | AE2-005 E | Adder | 3.29 MW | 2.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941101 | AE2-104 C O1 | Adder | 5.6 MW | 4.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941102 | AE2-104 E O1 | Adder | 8.91 MW | 7.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941281 | AE2-122 C O1 | 50/50 | 51.36 MW | 51.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941282 | AE2-122 E O1 | 50/50 | 207.26 MW | 207.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941291 | AE2-123 C O1 | 50/50 | 52.78 MW | 52.78 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941292 | AE2-123 E O1 | 50/50 | 205.84 MW | 205.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941301 | AE2-124 C O1 | 50/50 | 48.01 MW | 48.01 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941302 | AE2-124 E O1 | 50/50 | 210.66 MW | 210.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957491 | AF2-043 C | Adder | 3.75 MW | 3.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957492 | AF2-043 E | Adder | 2.5 MW | 2.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957601 | AF2-054 C | Adder | 3.2 MW | 2.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957602 | AF2-054 E | Adder | 2.13 MW | 1.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957631 | AF2-057 | Adder | 6.45 MW | 5.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 901082 | W1-029 E | Adder | 54.88 MW | 46.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 917122 | Z2-027 E | Adder | 1.85 MW | 1.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925522 | AC1-027 E | 50/50 | 2.07 MW | 2.07 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941501 | AE2-147 C | Adder | 27.29 MW | 23.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941502 | AE2-147 E | Adder | 18.19 MW | 15.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 941591 | AE2-156 O1 | 50/50 | 32.31 MW | 32.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957831 | AF2-077 C | Adder | 3.6 MW | 3.06 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957832 | AF2-077 E | Adder | 2.4 MW | 2.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957871 | AF2-081 C | Adder | 17.86 MW | 15.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 957872 | AF2-081 E | Adder | 7.66 MW | 6.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958161 | AF2-110 C | Adder | 2.29 MW | 1.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 958162 | AF2-110 E | Adder | 3.64 MW | 3.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 907092 | X1-038 E | Adder | 9.34 MW | 7.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 920692 | AA2-178 E | Adder | 6.56 MW | 5.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 923831 | AB2-022 C | Adder | 4.04 MW | 3.44 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 924812 | AB2-134 E OP | Adder | 17.07 MW | 14.51 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926751 | AC1-161 C O1 | 50/50 | 59.82 MW | 59.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926752 | AC1-161 E O1 | 50/50 | 25.54 MW | 25.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 927222 | AC1-216 E O1 | Adder | 10.42 MW | 8.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932041 | AC2-012 C | 50/50 | 14.47 MW | 14.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932042 | AC2-012 E | 50/50 | 23.6 MW | 23.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933291 | AC2-141 C | 50/50 | 59.82 MW | 59.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933292 | AC2-141 E | 50/50 | 25.54 MW | 25.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934011 | AD1-025 C | Adder | 22.78 MW | 19.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 934012 | AD1-025 E | Adder | 13.49 MW | 11.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938531 | AE1-072 C O1 | Adder | 31.3 MW | 26.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938532 | AE1-072 E O1 | Adder | 16.32 MW | 13.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938771 | AE1-103 C O1 | Adder | 4.48 MW | 3.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938772 | AE1-103 E O1 | Adder | 6.19 MW | 5.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939311 | AE1-162 C | Adder | 3.56 MW | 3.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939411 | AE1-173 C | Adder | 151.05 MW | 128.39 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 939412 | AE1-173 E | Adder | 100.7 MW | 85.6 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 942551 | AE2-270 | Adder | 11.18 MW | 9.5 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925861 | AC1-065 C | Adder | 5.04 MW | 4.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 925862 | AC1-065 E | Adder | 8.22 MW | 6.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926781 | AC1-164 C | Adder | 63.72 MW | 54.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 926782 | AC1-164 E | Adder | 28.63 MW | 24.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936242 | AD2-030 E | Adder | 1.79 MW | 1.52 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936301 | AD2-039 C | Adder | 2.02 MW | 1.71 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 936302 | AD2-039 E | Adder | 3.29 MW | 2.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938031 | AE1-004 C | Adder | 2.02 MW | 1.71 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 938032 | AE1-004 E | Adder | 3.29 MW | 2.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932831 | AC2-110 C | Adder | 2.02 MW | 1.71 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 932832 | AC2-110 E | Adder | 3.29 MW | 2.79 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 940551 | AE2-041 O1 | Adder | 11.01 MW | 9.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944581 | AF1-123 C O1 | 50/50 | 88.54 MW | 88.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944582 | AF1-123 E O1 | 50/50 | 202.73 MW | 202.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944591 | AF1-124 C O1 | 50/50 | 88.54 MW | 88.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944592 | AF1-124 E O1 | 50/50 | 202.73 MW | 202.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944601 | AF1-125 C O1 | 50/50 | 88.54 MW | 88.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 944602 | AF1-125 E O1 | 50/50 | 202.73 MW | 202.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933981 | AD1-022 C | Adder | 13.31 MW | 11.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 933982 | AD1-022 E | Adder | 7.24 MW | 6.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | 918512 | AA1-065 E OP | Adder | 6.43 MW | 5.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.63 MW | 0.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.2 MW | 1.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.87 MW | 9.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 30.68 MW | 30.68 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.9 MW | 1.9 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.85 MW | 6.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 25.54 MW | 25.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 65.31 MW | 65.31 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 37.28 MW | 37.28 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 3.98 MW | 3.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.42 MW | 2.42 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.19 MW | 4.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.72 MW | 6.72 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 22.86 MW | 22.86 MW |
| Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 1.1 MW | 0.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 87.95 MW | 74.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 44.78 MW | 38.07 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 51.8 MW | 44.03 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 34.54 MW | 29.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 18.83 MW | 16.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 7.31 MW | 6.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 17.11 MW | 14.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 11.95 MW | 10.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 5.12 MW | 4.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 57.62 MW | 48.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 25.81 MW | 21.93 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 28.4 MW | 24.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 14.29 MW | 12.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 3.96 MW | 3.36 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 49.69 MW | 42.23 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 27.2 MW | 23.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 18.13 MW | 15.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314189 | 6PAPERMILL | Adder | 10.99 MW | 9.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314295 | 6BIRDNECK | 50/50 | 0.09 MW | 0.09 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314421 | 6WINCHST | 50/50 | 0.26 MW | 0.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314491 | 3PENDLTN | 50/50 | 0.64 MW | 0.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315092 | 1YORKTN3 | 50/50 | 46.54 MW | 46.54 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 11.7 MW | 9.95 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926661 | AC1-147 C | Adder | 4.14 MW | 3.52 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | Adder | 2.43 MW | 2.07 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | 50/50 | 13.84 MW | 13.84 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | 50/50 | 9.23 MW | 9.23 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934141 | AD1-041 C | Adder | 8.51 MW | 7.23 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934142 | AD1-041 E | Adder | 5.67 MW | 4.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934392 | AD1-063 E | Adder | 1.76 MW | 1.49 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935111 | AD1-144 C | Adder | 3.09 MW | 2.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 1.69 MW | 1.43 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 5.6 MW | 4.76 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 9.14 MW | 7.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | Adder | 10.71 MW | 9.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | Adder | 5.61 MW | 4.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 2.43 MW | 2.06 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 3.35 MW | 2.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | Adder | 11.26 MW | 9.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | Adder | 5.06 MW | 4.3 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943431 | AF1-014 C | Adder | 2.04 MW | 1.73 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943432 | AF1-014 E | Adder | 3.6 MW | 3.06 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 2.2 MW | 1.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 3.58 MW | 3.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943471 | AF1-018 | Adder | 11.72 MW | 9.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 3.14 MW | 2.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 1.66 MW | 1.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 4.0 MW | 3.4 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 2.06 MW | 1.75 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 9.34 MW | 7.94 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 6.23 MW | 5.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945361 | AF1-201 C O1 | Adder | 29.0 MW | 24.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945362 | AF1-201 E O1 | Adder | 19.34 MW | 16.44 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315098 | 1CHESPKA | 50/50 | 0.85 MW | 0.85 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315099 | 1CHESPKB | 50/50 | 1.41 MW | 1.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315108 | 1ELIZAR1 | 50/50 | 6.26 MW | 6.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315109 | 1ELIZAR2 | 50/50 | 6.15 MW | 6.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315110 | 1ELIZAR3 | 50/50 | 6.34 MW | 6.34 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315233 | 1SURRY 2 | 50/50 | 56.17 MW | 56.17 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315611 | 6Z1-036WIND | Adder | 7.4 MW | 6.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 3.94 MW | 3.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | 50/50 | 3.46 MW | 3.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 2.23 MW | 1.89 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923842 | AB2-024 E | Adder | 1.85 MW | 1.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | Adder | 9.36 MW | 7.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | Adder | 15.27 MW | 12.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 2.48 MW | 2.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939431 | AE1-175 C | 50/50 | 4.46 MW | 4.46 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939432 | AE1-175 E | 50/50 | 2.21 MW | 2.21 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939611 | AE1-191 C | Adder | 17.02 MW | 14.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939612 | AE1-191 E | Adder | 11.35 MW | 9.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940231 | AE2-005 C | Adder | 2.15 MW | 1.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940232 | AE2-005 E | Adder | 3.51 MW | 2.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 5.83 MW | 4.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 9.27 MW | 7.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | 50/50 | 52.29 MW | 52.29 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | 50/50 | 211.01 MW | 211.01 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | 50/50 | 53.74 MW | 53.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | 50/50 | 209.56 MW | 209.56 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | 50/50 | 48.87 MW | 48.87 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | 50/50 | 214.44 MW | 214.44 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 3.84 MW | 3.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 2.56 MW | 2.18 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957601 | AF2-054 C | Adder | 3.39 MW | 2.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957602 | AF2-054 E | Adder | 2.26 MW | 1.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | Adder | 6.58 MW | 5.59 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 56.37 MW | 47.91 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 1.89 MW | 1.61 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | 50/50 | 2.1 MW | 2.1 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 28.03 MW | 23.82 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 18.68 MW | 15.88 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | 50/50 | 32.92 MW | 32.92 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957831 | AF2-077 C | Adder | 3.76 MW | 3.19 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957832 | AF2-077 E | Adder | 2.51 MW | 2.13 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 18.21 MW | 15.48 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 7.8 MW | 6.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 2.38 MW | 2.02 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 3.78 MW | 3.22 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 907092 | X1-038 E | Adder | 9.89 MW | 8.41 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 6.83 MW | 5.81 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923831 | AB2-022 C | Adder | 4.14 MW | 3.52 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924812 | AB2-134 E OP | Adder | 18.82 MW | 16.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926751 | AC1-161 C O1 | 50/50 | 60.05 MW | 60.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926752 | AC1-161 E O1 | 50/50 | 25.63 MW | 25.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927222 | AC1-216 E O1 | Adder | 11.49 MW | 9.77 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932041 | AC2-012 C | 50/50 | 14.74 MW | 14.74 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932042 | AC2-012 E | 50/50 | 24.05 MW | 24.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933291 | AC2-141 C | 50/50 | 60.05 MW | 60.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933292 | AC2-141 E | 50/50 | 25.63 MW | 25.63 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934011 | AD1-025 C | Adder | 25.11 MW | 21.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934012 | AD1-025 E | Adder | 14.88 MW | 12.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938531 | AE1-072 C O1 | Adder | 31.93 MW | 27.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938532 | AE1-072 E O1 | Adder | 16.64 MW | 14.15 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C O1 | Adder | 4.75 MW | 4.04 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E O1 | Adder | 6.56 MW | 5.57 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939311 | AE1-162 C | Adder | 3.71 MW | 3.16 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939411 | AE1-173 C | Adder | 148.47 MW | 126.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939412 | AE1-173 E | Adder | 98.98 MW | 84.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942551 | AE2-270 | Adder | 39.97 MW | 33.98 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957711 | AF2-065 C | Adder | 0.14 MW | 0.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957712 | AF2-065 E | Adder | 0.13 MW | 0.11 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925861 | AC1-065 C | Adder | 5.38 MW | 4.58 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925862 | AC1-065 E | Adder | 8.78 MW | 7.47 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926781 | AC1-164 C | Adder | 68.4 MW | 58.14 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926782 | AC1-164 E | Adder | 30.73 MW | 26.12 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936242 | AD2-030 E | Adder | 1.9 MW | 1.62 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936301 | AD2-039 C | Adder | 2.15 MW | 1.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936302 | AD2-039 E | Adder | 3.51 MW | 2.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938031 | AE1-004 C | Adder | 2.15 MW | 1.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938032 | AE1-004 E | Adder | 3.51 MW | 2.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932831 | AC2-110 C | Adder | 2.15 MW | 1.83 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932832 | AC2-110 E | Adder | 3.51 MW | 2.99 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940551 | AE2-041 O1 | Adder | 11.72 MW | 9.96 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944581 | AF1-123 C O1 | 50/50 | 89.67 MW | 89.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944582 | AF1-123 E O1 | 50/50 | 205.33 MW | 205.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944591 | AF1-124 C O1 | 50/50 | 89.67 MW | 89.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944592 | AF1-124 E O1 | 50/50 | 205.33 MW | 205.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944601 | AF1-125 C O1 | 50/50 | 89.67 MW | 89.67 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | 50/50 | 205.33 MW | 205.33 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 14.01 MW | 11.9 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 7.62 MW | 6.48 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.65 MW | 0.65 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.26 MW | 1.26 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.08 MW | 10.08 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 31.66 MW | 31.66 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.0 MW | 2.0 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.05 MW | 7.05 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 26.95 MW | 26.95 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 66.64 MW | 66.64 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 38.42 MW | 38.42 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 4.2 MW | 4.2 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.45 MW | 2.45 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.35 MW | 4.35 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.86 MW | 6.86 MW |
| 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.88 MW | 23.88 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314541 | 3WATKINS | Adder | 1.15 MW | 0.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934521 | AD1-076 C | Adder | 4.5 MW | 3.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934522 | AD1-076 E | Adder | 2.29 MW | 1.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942931 | AE2-313 C | 50/50 | 63.26 MW | 63.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942932 | AE2-313 E | 50/50 | 42.17 MW | 42.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944011 | AF1-069 C | 50/50 | 22.93 MW | 22.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944012 | AF1-069 E | 50/50 | 8.91 MW | 8.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945811 | AF1-246 C O1 | Adder | 12.42 MW | 10.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945812 | AF1-246 E O1 | Adder | 17.15 MW | 14.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940491 | AE2-034 C | Adder | 12.12 MW | 10.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940492 | AE2-034 E | Adder | 5.19 MW | 4.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941031 | AE2-094 C | 50/50 | 70.17 MW | 70.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941032 | AE2-094 E | 50/50 | 31.43 MW | 31.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957481 | AF2-042 C | Adder | 88.72 MW | 75.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957482 | AF2-042 E | Adder | 59.15 MW | 50.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957531 | AF2-047 C | Adder | 28.79 MW | 24.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957532 | AF2-047 E | Adder | 14.48 MW | 12.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314539 | 3UNCAMP | Adder | 4.06 MW | 3.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916042 | Z1-036 E | Adder | 48.99 MW | 41.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940481 | AE2-033 C | Adder | 25.88 MW | 22.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940482 | AE2-033 E | Adder | 17.44 MW | 14.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940641 | AE2-051 C O1 | 50/50 | 31.13 MW | 31.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940642 | AE2-051 E O1 | 50/50 | 20.75 MW | 20.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 946011 | AF1-266 | Adder | 21.66 MW | 18.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314491 | 3PENDLTN | 50/50 | 0.61 MW | 0.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 919152 | AA1-139 E | Adder | 11.16 MW | 9.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926661 | AC1-147 C | Adder | 3.92 MW | 3.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926662 | AC1-147 E | Adder | 2.3 MW | 1.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934061 | AD1-033 C | 50/50 | 13.11 MW | 13.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934062 | AD1-033 E | 50/50 | 8.74 MW | 8.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935111 | AD1-144 C | Adder | 2.94 MW | 2.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935112 | AD1-144 E | Adder | 1.61 MW | 1.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 936661 | AD2-085 C | Adder | 5.77 MW | 4.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 936662 | AD2-085 E | Adder | 9.42 MW | 8.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937221 | AD2-160 C O1 | Adder | 10.19 MW | 8.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937222 | AD2-160 E O1 | Adder | 5.34 MW | 4.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942341 | AE2-247 C | Adder | 2.5 MW | 2.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942342 | AE2-247 E | Adder | 3.45 MW | 2.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942401 | AE2-253 C | Adder | 10.71 MW | 9.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942402 | AE2-253 E | Adder | 4.81 MW | 4.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943461 | AF1-017 C | Adder | 2.26 MW | 1.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943462 | AF1-017 E | Adder | 3.69 MW | 3.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943611 | AF1-032 C | Adder | 3.01 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943612 | AF1-032 E | Adder | 1.6 MW | 1.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943621 | AF1-033 C | Adder | 3.83 MW | 3.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943622 | AF1-033 E | Adder | 1.98 MW | 1.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944871 | AF1-152 C | Adder | 9.08 MW | 7.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944872 | AF1-152 E | Adder | 6.06 MW | 5.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315102 | 1BRUNSWICKG1 | 50/50 | 15.32 MW | 15.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315103 | 1BRUNSWICKG2 | 50/50 | 15.32 MW | 15.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315104 | 1BRUNSWICKG3 | 50/50 | 15.32 MW | 15.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315105 | 1BRUNSWICKS1 | 50/50 | 31.84 MW | 31.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315108 | 1ELIZAR1 | 50/50 | 5.92 MW | 5.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315109 | 1ELIZAR2 | 50/50 | 5.82 MW | 5.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315110 | 1ELIZAR3 | 50/50 | 6.0 MW | 6.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315233 | 1SURRY 2 | 50/50 | 46.13 MW | 46.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315611 | 6Z1-036WIND | Adder | 7.3 MW | 6.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 913392 | Y1-086 E | Adder | 3.8 MW | 3.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916192 | Z1-068 E | 50/50 | 3.27 MW | 3.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923832 | AB2-022 E | Adder | 2.14 MW | 1.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923852 | AB2-025 E | Adder | 1.81 MW | 1.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932591 | AC2-079 C O1 | Adder | 9.63 MW | 8.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932592 | AC2-079 E O1 | Adder | 15.71 MW | 13.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938551 | AE1-074 C | Adder | 3.9 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938552 | AE1-074 E | Adder | 1.96 MW | 1.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939312 | AE1-162 E | Adder | 2.39 MW | 2.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940651 | AE2-052 | Adder | 5.67 MW | 4.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941101 | AE2-104 C O1 | Adder | 5.74 MW | 4.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941102 | AE2-104 E O1 | Adder | 9.12 MW | 7.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941281 | AE2-122 C O1 | 50/50 | 49.55 MW | 49.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941282 | AE2-122 E O1 | 50/50 | 199.93 MW | 199.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941291 | AE2-123 C O1 | 50/50 | 50.92 MW | 50.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941292 | AE2-123 E O1 | 50/50 | 198.55 MW | 198.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941301 | AE2-124 C O1 | 50/50 | 46.31 MW | 46.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941302 | AE2-124 E O1 | 50/50 | 203.19 MW | 203.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957491 | AF2-043 C | Adder | 3.69 MW | 3.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957492 | AF2-043 E | Adder | 2.46 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957631 | AF2-057 | Adder | 6.23 MW | 5.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 901082 | W1-029 E | Adder | 54.81 MW | 46.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 917122 | Z2-027 E | Adder | 1.83 MW | 1.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925522 | AC1-027 E | 50/50 | 2.0 MW | 2.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941501 | AE2-147 C | Adder | 27.25 MW | 23.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941502 | AE2-147 E | Adder | 18.17 MW | 15.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941591 | AE2-156 O1 | 50/50 | 31.17 MW | 31.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957871 | AF2-081 C | Adder | 17.35 MW | 14.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957872 | AF2-081 E | Adder | 7.44 MW | 6.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957911 | AF2-085 | 50/50 | 6.67 MW | 6.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958161 | AF2-110 C | Adder | 2.34 MW | 1.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958162 | AF2-110 E | Adder | 3.72 MW | 3.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314947 | 8GREENSVILLE | 50/50 | 93.32 MW | 93.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 907092 | X1-038 E | Adder | 10.16 MW | 8.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 920692 | AA2-178 E | Adder | 6.92 MW | 5.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923831 | AB2-022 C | Adder | 3.98 MW | 3.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925061 | AB2-161 C O1 | Adder | 5.5 MW | 4.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925062 | AB2-161 E O1 | Adder | 8.97 MW | 7.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926751 | AC1-161 C O1 | 50/50 | 54.15 MW | 54.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926752 | AC1-161 E O1 | 50/50 | 23.11 MW | 23.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932041 | AC2-012 C | Adder | 13.96 MW | 11.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932042 | AC2-012 E | Adder | 22.78 MW | 19.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933291 | AC2-141 C | 50/50 | 54.15 MW | 54.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933292 | AC2-141 E | 50/50 | 23.11 MW | 23.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934571 | AD1-082 C | Adder | 12.52 MW | 10.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934572 | AD1-082 E | Adder | 7.14 MW | 6.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938531 | AE1-072 C O1 | Adder | 30.49 MW | 25.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938532 | AE1-072 E O1 | Adder | 15.89 MW | 13.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938771 | AE1-103 C O1 | Adder | 4.88 MW | 4.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938772 | AE1-103 E O1 | Adder | 6.74 MW | 5.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939191 | AE1-149 C O1 | Adder | 17.02 MW | 14.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939192 | AE1-149 E O1 | Adder | 11.34 MW | 9.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939311 | AE1-162 C | Adder | 3.58 MW | 3.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939411 | AE1-173 C | 50/50 | 162.03 MW | 162.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939412 | AE1-173 E | 50/50 | 108.02 MW | 108.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940541 | AE2-040 O1 | Adder | 4.59 MW | 3.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944581 | AF1-123 C O1 | 50/50 | 84.37 MW | 84.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944582 | AF1-123 E O1 | 50/50 | 193.18 MW | 193.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944591 | AF1-124 C O1 | 50/50 | 84.37 MW | 84.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944592 | AF1-124 E O1 | 50/50 | 193.18 MW | 193.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944601 | AF1-125 C O1 | 50/50 | 84.37 MW | 84.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944602 | AF1-125 E O1 | 50/50 | 193.18 MW | 193.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.4 MW | 1.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.69 MW | 2.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.98 MW | 12.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 54.91 MW | 54.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.19 MW | 3.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.52 MW | 11.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 44.67 MW | 44.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 90.6 MW | 90.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 64.53 MW | 64.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 6.97 MW | 6.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.98 MW | 2.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.39 MW | 8.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 8.85 MW | 8.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 52.13 MW | 52.13 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314541 | 3WATKINS | Adder | 1.07 MW | 0.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934521 | AD1-076 C | Adder | 87.82 MW | 74.65 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934522 | AD1-076 E | Adder | 44.72 MW | 38.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937481 | AD2-202 C O1 | Adder | 3.6 MW | 3.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937482 | AD2-202 E O1 | Adder | 1.69 MW | 1.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942931 | AE2-313 C | 50/50 | 69.78 MW | 69.78 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942932 | AE2-313 E | 50/50 | 46.52 MW | 46.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944011 | AF1-069 C | 50/50 | 25.4 MW | 25.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944012 | AF1-069 E | 50/50 | 9.87 MW | 9.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945811 | AF1-246 C O1 | 50/50 | 12.94 MW | 12.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 945812 | AF1-246 E O1 | 50/50 | 17.87 MW | 17.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940491 | AE2-034 C | Adder | 11.75 MW | 9.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940492 | AE2-034 E | Adder | 5.04 MW | 4.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941031 | AE2-094 C | 50/50 | 77.75 MW | 77.75 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941032 | AE2-094 E | 50/50 | 34.82 MW | 34.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957481 | AF2-042 C | 50/50 | 92.41 MW | 92.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957482 | AF2-042 E | 50/50 | 61.61 MW | 61.61 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957531 | AF2-047 C | Adder | 27.92 MW | 23.73 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957532 | AF2-047 E | Adder | 14.04 MW | 11.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314539 | 3UNCAMP | Adder | 3.86 MW | 3.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916042 | Z1-036 E | Adder | 47.64 MW | 40.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940641 | AE2-051 C O1 | 50/50 | 34.22 MW | 34.22 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 940642 | AE2-051 E O1 | 50/50 | 22.81 MW | 22.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314491 | 3PENDLTN | 50/50 | 0.59 MW | 0.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 919152 | AA1-139 E | 50/50 | 10.93 MW | 10.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926661 | AC1-147 C | Adder | 3.81 MW | 3.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926662 | AC1-147 E | Adder | 2.24 MW | 1.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934061 | AD1-033 C | 50/50 | 12.86 MW | 12.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934062 | AD1-033 E | 50/50 | 8.57 MW | 8.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935111 | AD1-144 C | Adder | 2.78 MW | 2.36 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 935112 | AD1-144 E | Adder | 1.52 MW | 1.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937221 | AD2-160 C O1 | 50/50 | 9.99 MW | 9.99 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 937222 | AD2-160 E O1 | 50/50 | 5.24 MW | 5.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942401 | AE2-253 C | 50/50 | 10.5 MW | 10.5 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 942402 | AE2-253 E | 50/50 | 4.72 MW | 4.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943611 | AF1-032 C | Adder | 2.93 MW | 2.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 943612 | AF1-032 E | Adder | 1.55 MW | 1.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944871 | AF1-152 C | Adder | 8.84 MW | 7.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944872 | AF1-152 E | Adder | 5.9 MW | 5.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315099 | 1CHESPKB | 50/50 | 1.3 MW | 1.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315102 | 1BRUNSWICKG1 | 50/50 | 16.83 MW | 16.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315103 | 1BRUNSWICKG2 | 50/50 | 16.83 MW | 16.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315104 | 1BRUNSWICKG3 | 50/50 | 16.83 MW | 16.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315105 | 1BRUNSWICKS1 | 50/50 | 34.97 MW | 34.97 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315108 | 1ELIZAR1 | 50/50 | 5.77 MW | 5.77 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315109 | 1ELIZAR2 | 50/50 | 5.67 MW | 5.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315110 | 1ELIZAR3 | 50/50 | 5.85 MW | 5.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315233 | 1SURRY 2 | 50/50 | 45.57 MW | 45.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315603 | 6AA1-139SOLA | 50/50 | 4.43 MW | 4.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 315611 | 6Z1-036WIND | Adder | 7.1 MW | 6.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 913392 | Y1-086 E | Adder | 3.71 MW | 3.15 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 916192 | Z1-068 E | 50/50 | 3.2 MW | 3.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923832 | AB2-022 E | Adder | 2.09 MW | 1.78 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941101 | AE2-104 C O1 | Adder | 5.46 MW | 4.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941102 | AE2-104 E O1 | Adder | 8.68 MW | 7.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941281 | AE2-122 C O1 | 50/50 | 48.42 MW | 48.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941282 | AE2-122 E O1 | 50/50 | 195.39 MW | 195.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941291 | AE2-123 C O1 | 50/50 | 49.76 MW | 49.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941292 | AE2-123 E O1 | 50/50 | 194.05 MW | 194.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941301 | AE2-124 C O1 | 50/50 | 45.28 MW | 45.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941302 | AE2-124 E O1 | 50/50 | 198.69 MW | 198.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957491 | AF2-043 C | Adder | 3.58 MW | 3.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957492 | AF2-043 E | Adder | 2.39 MW | 2.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957631 | AF2-057 | Adder | 6.05 MW | 5.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 901082 | W1-029 E | Adder | 53.36 MW | 45.35 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 917122 | Z2-027 E | Adder | 1.78 MW | 1.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 925522 | AC1-027 E | 50/50 | 1.95 MW | 1.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941501 | AE2-147 C | Adder | 26.53 MW | 22.55 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941502 | AE2-147 E | Adder | 17.69 MW | 15.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 941591 | AE2-156 O1 | 50/50 | 30.32 MW | 30.32 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957871 | AF2-081 C | 50/50 | 17.0 MW | 17.0 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 957872 | AF2-081 E | 50/50 | 7.29 MW | 7.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958161 | AF2-110 C | Adder | 2.23 MW | 1.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 958162 | AF2-110 E | Adder | 3.55 MW | 3.01 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934611 | AD1-087 C O1 | Adder | 12.3 MW | 10.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 934612 | AD1-087 E O1 | Adder | 5.77 MW | 4.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 314947 | 8GREENSVILLE | 50/50 | 102.79 MW | 102.79 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 907092 | X1-038 E | Adder | 9.65 MW | 8.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 920692 | AA2-178 E | Adder | 6.71 MW | 5.71 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 923831 | AB2-022 C | Adder | 3.89 MW | 3.31 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926751 | AC1-161 C O1 | 50/50 | 54.96 MW | 54.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 926752 | AC1-161 E O1 | 50/50 | 23.46 MW | 23.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932041 | AC2-012 C | Adder | 13.57 MW | 11.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 932042 | AC2-012 E | Adder | 22.14 MW | 18.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933291 | AC2-141 C | 50/50 | 54.96 MW | 54.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 933292 | AC2-141 E | 50/50 | 23.46 MW | 23.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938531 | AE1-072 C O1 | 50/50 | 29.86 MW | 29.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938532 | AE1-072 E O1 | 50/50 | 15.56 MW | 15.56 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938771 | AE1-103 C O1 | Adder | 4.63 MW | 3.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 938772 | AE1-103 E O1 | Adder | 6.4 MW | 5.44 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939411 | AE1-173 C | 50/50 | 173.83 MW | 173.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 939412 | AE1-173 E | 50/50 | 115.89 MW | 115.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944581 | AF1-123 C O1 | 50/50 | 83.69 MW | 83.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944582 | AF1-123 E O1 | 50/50 | 191.62 MW | 191.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944591 | AF1-124 C O1 | 50/50 | 83.69 MW | 83.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944592 | AF1-124 E O1 | 50/50 | 191.62 MW | 191.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944601 | AF1-125 C O1 | 50/50 | 83.69 MW | 83.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | 944602 | AF1-125 E O1 | 50/50 | 191.62 MW | 191.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.2 MW | 1.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.3 MW | 2.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.93 MW | 12.93 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 49.69 MW | 49.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.63 MW | 2.63 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 10.58 MW | 10.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 36.57 MW | 36.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 88.68 MW | 88.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 58.81 MW | 58.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 5.7 MW | 5.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 3.03 MW | 3.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.39 MW | 7.39 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 8.81 MW | 8.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 44.72 MW | 44.72 MW |
| Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314541 | 3WATKINS | Adder | 1.05 MW | 0.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934521 | AD1-076 C | Adder | 84.73 MW | 72.02 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934522 | AD1-076 E | Adder | 43.14 MW | 36.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937481 | AD2-202 C O1 | Adder | 3.5 MW | 2.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937482 | AD2-202 E O1 | Adder | 1.64 MW | 1.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942931 | AE2-313 C | 50/50 | 68.53 MW | 68.53 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942932 | AE2-313 E | 50/50 | 45.68 MW | 45.68 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944011 | AF1-069 C | 50/50 | 24.96 MW | 24.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944012 | AF1-069 E | 50/50 | 9.7 MW | 9.7 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 945811 | AF1-246 C O1 | 50/50 | 12.62 MW | 12.62 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 945812 | AF1-246 E O1 | 50/50 | 17.42 MW | 17.42 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940491 | AE2-034 C | Adder | 11.34 MW | 9.64 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940492 | AE2-034 E | Adder | 4.86 MW | 4.13 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941031 | AE2-094 C | 50/50 | 76.38 MW | 76.38 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941032 | AE2-094 E | 50/50 | 34.21 MW | 34.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957481 | AF2-042 C | 50/50 | 90.11 MW | 90.11 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957482 | AF2-042 E | 50/50 | 60.07 MW | 60.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957531 | AF2-047 C | Adder | 26.95 MW | 22.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957532 | AF2-047 E | Adder | 13.56 MW | 11.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314539 | 3UNCAMP | Adder | 3.72 MW | 3.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 916042 | Z1-036 E | Adder | 46.04 MW | 39.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940641 | AE2-051 C O1 | 50/50 | 33.6 MW | 33.6 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 940642 | AE2-051 E O1 | 50/50 | 22.4 MW | 22.4 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314491 | 3PENDLTN | 50/50 | 0.57 MW | 0.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 919152 | AA1-139 E | 50/50 | 10.59 MW | 10.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926661 | AC1-147 C | Adder | 3.69 MW | 3.14 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926662 | AC1-147 E | Adder | 2.17 MW | 1.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934061 | AD1-033 C | 50/50 | 12.46 MW | 12.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934062 | AD1-033 E | 50/50 | 8.3 MW | 8.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 935111 | AD1-144 C | Adder | 2.68 MW | 2.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 935112 | AD1-144 E | Adder | 1.46 MW | 1.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937221 | AD2-160 C O1 | 50/50 | 9.67 MW | 9.67 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 937222 | AD2-160 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942401 | AE2-253 C | 50/50 | 10.17 MW | 10.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 942402 | AE2-253 E | 50/50 | 4.57 MW | 4.57 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 943611 | AF1-032 C | Adder | 2.83 MW | 2.41 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 943612 | AF1-032 E | Adder | 1.5 MW | 1.28 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944871 | AF1-152 C | Adder | 8.55 MW | 7.27 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944872 | AF1-152 E | Adder | 5.7 MW | 4.85 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315102 | 1BRUNSWICKG1 | 50/50 | 16.51 MW | 16.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315103 | 1BRUNSWICKG2 | 50/50 | 16.51 MW | 16.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315104 | 1BRUNSWICKG3 | 50/50 | 16.51 MW | 16.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315105 | 1BRUNSWICKS1 | 50/50 | 34.3 MW | 34.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315108 | 1ELIZAR1 | 50/50 | 5.59 MW | 5.59 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315109 | 1ELIZAR2 | 50/50 | 5.49 MW | 5.49 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315110 | 1ELIZAR3 | 50/50 | 5.66 MW | 5.66 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315233 | 1SURRY 2 | 50/50 | 44.17 MW | 44.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315603 | 6AA1-139SOLA | 50/50 | 4.29 MW | 4.29 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 315611 | 6Z1-036WIND | Adder | 6.86 MW | 5.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 913392 | Y1-086 E | Adder | 3.59 MW | 3.05 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 916192 | Z1-068 E | 50/50 | 3.1 MW | 3.1 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 923832 | AB2-022 E | Adder | 2.03 MW | 1.72 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941101 | AE2-104 C O1 | Adder | 5.27 MW | 4.48 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941102 | AE2-104 E O1 | Adder | 8.38 MW | 7.12 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941281 | AE2-122 C O1 | 50/50 | 46.88 MW | 46.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941282 | AE2-122 E O1 | 50/50 | 189.17 MW | 189.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941291 | AE2-123 C O1 | 50/50 | 48.18 MW | 48.18 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941292 | AE2-123 E O1 | 50/50 | 187.87 MW | 187.87 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941301 | AE2-124 C O1 | 50/50 | 43.84 MW | 43.84 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941302 | AE2-124 E O1 | 50/50 | 192.37 MW | 192.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957491 | AF2-043 C | Adder | 3.47 MW | 2.95 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957492 | AF2-043 E | Adder | 2.31 MW | 1.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957631 | AF2-057 | Adder | 5.86 MW | 4.98 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 901082 | W1-029 E | Adder | 51.6 MW | 43.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 917122 | Z2-027 E | Adder | 1.73 MW | 1.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 925522 | AC1-027 E | 50/50 | 1.89 MW | 1.89 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941501 | AE2-147 C | Adder | 25.66 MW | 21.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941502 | AE2-147 E | Adder | 17.1 MW | 14.54 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 941591 | AE2-156 O1 | 50/50 | 29.34 MW | 29.34 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957871 | AF2-081 C | 50/50 | 16.46 MW | 16.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 957872 | AF2-081 E | 50/50 | 7.06 MW | 7.06 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 958161 | AF2-110 C | Adder | 2.15 MW | 1.83 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 958162 | AF2-110 E | Adder | 3.42 MW | 2.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934611 | AD1-087 C O1 | Adder | 11.95 MW | 10.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 934612 | AD1-087 E O1 | Adder | 5.61 MW | 4.76 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 314947 | 8GREENSVILLE | 50/50 | 100.88 MW | 100.88 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 907092 | X1-038 E | Adder | 9.29 MW | 7.9 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 920692 | AA2-178 E | Adder | 6.48 MW | 5.51 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 923831 | AB2-022 C | Adder | 3.76 MW | 3.2 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926751 | AC1-161 C O1 | 50/50 | 53.46 MW | 53.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 926752 | AC1-161 E O1 | 50/50 | 22.82 MW | 22.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 932041 | AC2-012 C | Adder | 13.13 MW | 11.16 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 932042 | AC2-012 E | Adder | 21.42 MW | 18.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933291 | AC2-141 C | 50/50 | 53.46 MW | 53.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933292 | AC2-141 E | 50/50 | 22.82 MW | 22.82 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938531 | AE1-072 C O1 | 50/50 | 28.91 MW | 28.91 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938532 | AE1-072 E O1 | 50/50 | 15.07 MW | 15.07 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938771 | AE1-103 C O1 | Adder | 4.46 MW | 3.79 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 938772 | AE1-103 E O1 | Adder | 6.16 MW | 5.24 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939411 | AE1-173 C | 50/50 | 170.21 MW | 170.21 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 939412 | AE1-173 E | 50/50 | 113.47 MW | 113.47 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944581 | AF1-123 C O1 | 50/50 | 81.17 MW | 81.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944582 | AF1-123 E O1 | 50/50 | 185.86 MW | 185.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944591 | AF1-124 C O1 | 50/50 | 81.17 MW | 81.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944592 | AF1-124 E O1 | 50/50 | 185.86 MW | 185.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944601 | AF1-125 C O1 | 50/50 | 81.17 MW | 81.17 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 944602 | AF1-125 E O1 | 50/50 | 185.86 MW | 185.86 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933981 | AD1-022 C | Adder | 1.13 MW | 0.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | 933982 | AD1-022 E | Adder | 0.61 MW | 0.52 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.96 MW | 1.96 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.37 MW | 12.37 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 44.43 MW | 44.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.3 MW | 2.3 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.58 MW | 9.58 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 31.69 MW | 31.69 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 83.81 MW | 83.81 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 52.94 MW | 52.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 4.94 MW | 4.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.94 MW | 2.94 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.46 MW | 6.46 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 8.43 MW | 8.43 MW |
| 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 38.14 MW | 38.14 MW |
| Details for 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314623 | 3WITAKRS | 50/50 | 0.16 MW | 0.16 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315131 | 1EDGECMA | Adder | 5.4 MW | 4.59 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315132 | 1EDGECMB | Adder | 5.4 MW | 4.59 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315136 | 1ROSEMG1 | 50/50 | 1.53 MW | 1.53 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315137 | 1ROSEMS1 | 50/50 | 0.95 MW | 0.95 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315138 | 1ROSEMG2 | 50/50 | 0.72 MW | 0.72 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315139 | 1GASTONA | 50/50 | 2.22 MW | 2.22 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918492 | AA1-063AE OP | Adder | 2.27 MW | 1.93 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918532 | AA1-067 E | 50/50 | 0.85 MW | 0.85 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 919692 | AA2-053 E OP | 50/50 | 2.74 MW | 2.74 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 919702 | AA2-057 E OP | 50/50 | 2.44 MW | 2.44 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920591 | AA2-165 C | 50/50 | 0.1 MW | 0.1 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920592 | AA2-165 E | 50/50 | 0.41 MW | 0.41 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926201 | AC1-098 C | 50/50 | 5.18 MW | 5.18 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926202 | AC1-098 E | 50/50 | 3.09 MW | 3.09 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926211 | AC1-099 C | 50/50 | 1.74 MW | 1.74 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926212 | AC1-099 E | 50/50 | 1.02 MW | 1.02 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934331 | AD1-057 C O1 | 50/50 | 6.72 MW | 6.72 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934332 | AD1-057 E O1 | 50/50 | 3.6 MW | 3.6 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934521 | AD1-076 C | 50/50 | 141.46 MW | 141.46 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934522 | AD1-076 E | 50/50 | 72.03 MW | 72.03 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 943171 | AE2-346 C | 50/50 | 1.52 MW | 1.52 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 943172 | AE2-346 E | 50/50 | 0.65 MW | 0.65 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 944141 | AF1-082 | Adder | 1.9 MW | 1.61 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315294 | 1DOMTR10 | 50/50 | 24.91 MW | 24.91 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315606 | 3AA2-053SOLA | 50/50 | 1.11 MW | 1.11 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 900672 | V4-068 E | 50/50 | 0.21 MW | 0.21 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917332 | Z2-043 E | 50/50 | 1.25 MW | 1.25 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917342 | Z2-044 E | 50/50 | 0.4 MW | 0.4 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 922922 | AB1-081 C OP | Adder | 5.89 MW | 5.01 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 922923 | AB1-081 E OP | Adder | 2.53 MW | 2.15 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923262 | AB1-132 C OP | 50/50 | 9.77 MW | 9.77 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923263 | AB1-132 E OP | 50/50 | 4.18 MW | 4.18 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923573 | AB1-173 E OP | Adder | 0.54 MW | 0.46 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923991 | AB2-040 C O1 | Adder | 3.76 MW | 3.2 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923992 | AB2-040 E O1 | Adder | 3.08 MW | 2.62 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924152 | AB2-059 E OP | Adder | 3.58 MW | 3.04 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925121 | AB2-169 C | 50/50 | 2.18 MW | 2.18 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925122 | AB2-169 E | 50/50 | 11.28 MW | 11.28 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925591 | AC1-034 C | Adder | 4.5 MW | 3.83 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925592 | AC1-034 E | Adder | 3.39 MW | 2.88 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 932631 | AC2-084 C | 50/50 | 7.39 MW | 7.39 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 932632 | AC2-084 E | 50/50 | 3.64 MW | 3.64 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 938222 | AE1-035 E | 50/50 | 1.56 MW | 1.56 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940491 | AE2-034 C | 50/50 | 22.77 MW | 22.77 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940492 | AE2-034 E | 50/50 | 9.76 MW | 9.76 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940571 | AE2-044 C | Adder | 2.95 MW | 2.5 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940572 | AE2-044 E | Adder | 1.26 MW | 1.07 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957521 | AF2-046 C | 50/50 | 12.92 MW | 12.92 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957522 | AF2-046 E | 50/50 | 6.5 MW | 6.5 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957531 | AF2-047 C | 50/50 | 54.1 MW | 54.1 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957532 | AF2-047 E | 50/50 | 27.21 MW | 27.21 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957861 | AF2-080 C | 50/50 | 7.85 MW | 7.85 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957862 | AF2-080 E | 50/50 | 3.48 MW | 3.48 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 916042 | Z1-036 E | 50/50 | 117.19 MW | 117.19 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314589 | 3MURPHYS | 50/50 | 0.07 MW | 0.07 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315141 | 1GASTONB | 50/50 | 2.22 MW | 2.22 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315292 | 1DOMTR78 | 50/50 | 3.33 MW | 3.33 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315611 | 6Z1-036WIND | 50/50 | 17.45 MW | 17.45 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 938221 | AE1-035 C | 50/50 | 3.21 MW | 3.21 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314574 | 6EVERETS | 50/50 | 0.34 MW | 0.34 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315612 | 3AA2-057SOLA | 50/50 | 0.89 MW | 0.89 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917512 | Z2-088 E OP1 | 50/50 | 7.37 MW | 7.37 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920671 | AA2-174 C OP | 50/50 | 0.05 MW | 0.05 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920672 | AA2-174 E OP | 50/50 | 0.32 MW | 0.32 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923911 | AB2-031 C O1 | Adder | 1.15 MW | 0.97 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923912 | AB2-031 E O1 | Adder | 0.56 MW | 0.48 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924501 | AB2-099 C | 50/50 | 0.63 MW | 0.63 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924502 | AB2-099 E | 50/50 | 0.27 MW | 0.27 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925172 | AB2-174 E O1 | Adder | 3.1 MW | 2.63 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926071 | AC1-086 C | 50/50 | 14.38 MW | 14.38 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926072 | AC1-086 E | 50/50 | 6.54 MW | 6.54 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927021 | AC1-189 C | 50/50 | 8.64 MW | 8.64 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927022 | AC1-189 E | 50/50 | 4.31 MW | 4.31 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927141 | AC1-208 C | 50/50 | 6.62 MW | 6.62 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927142 | AC1-208 E | 50/50 | 2.94 MW | 2.94 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923572 | AB1-173 C OP | Adder | 1.16 MW | 0.98 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923582 | AB1-173AC OP | Adder | 1.16 MW | 0.98 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923583 | AB1-173AE OP | Adder | 0.54 MW | 0.46 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 960331 | AF2-324 C O1 | Adder | 5.27 MW | 4.48 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 960332 | AF2-324 E O1 | Adder | 2.83 MW | 2.41 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315614 | AA2-178 C | 50/50 | 5.27 MW | 5.27 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920692 | AA2-178 E | 50/50 | 13.01 MW | 13.01 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923831 | AB2-022 C | Adder | -1.96 MW | -1.67 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918561 | AA1-072 C | 50/50 | 0.37 MW | 0.37 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918562 | AA1-072 E | 50/50 | 0.18 MW | 0.18 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 933981 | AD1-022 C | 50/50 | 20.12 MW | 20.12 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 933982 | AD1-022 E | 50/50 | 10.95 MW | 10.95 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315602 | 1HOLLOMANSOL | 50/50 | 2.23 MW | 2.23 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918512 | AA1-065 E OP | 50/50 | 6.32 MW | 6.32 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.68 MW | 2.68 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.03 MW | 9.03 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.87 MW | 1.87 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.06 MW | 3.06 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.25 MW | 16.25 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.48 MW | 10.48 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.48 MW | 0.48 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.5 MW | 0.5 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.39 MW | 1.39 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.83 MW | 1.83 MW |
| 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.85 MW | 8.85 MW |
| Details for 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314623 | 3WITAKRS | 50/50 | 0.16 MW | 0.16 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315131 | 1EDGECMA | Adder | 5.4 MW | 4.59 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315132 | 1EDGECMB | Adder | 5.4 MW | 4.59 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315136 | 1ROSEMG1 | 50/50 | 1.53 MW | 1.53 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315137 | 1ROSEMS1 | 50/50 | 0.95 MW | 0.95 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315138 | 1ROSEMG2 | 50/50 | 0.72 MW | 0.72 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315139 | 1GASTONA | 50/50 | 2.22 MW | 2.22 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918492 | AA1-063AE OP | Adder | 2.27 MW | 1.93 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918532 | AA1-067 E | 50/50 | 0.85 MW | 0.85 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 919692 | AA2-053 E OP | 50/50 | 2.74 MW | 2.74 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 919702 | AA2-057 E OP | 50/50 | 2.44 MW | 2.44 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920591 | AA2-165 C | 50/50 | 0.1 MW | 0.1 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920592 | AA2-165 E | 50/50 | 0.41 MW | 0.41 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926201 | AC1-098 C | 50/50 | 5.18 MW | 5.18 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926202 | AC1-098 E | 50/50 | 3.09 MW | 3.09 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926211 | AC1-099 C | 50/50 | 1.74 MW | 1.74 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926212 | AC1-099 E | 50/50 | 1.02 MW | 1.02 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934331 | AD1-057 C O1 | 50/50 | 6.72 MW | 6.72 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934332 | AD1-057 E O1 | 50/50 | 3.6 MW | 3.6 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934521 | AD1-076 C | 50/50 | 141.46 MW | 141.46 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 934522 | AD1-076 E | 50/50 | 72.03 MW | 72.03 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 943171 | AE2-346 C | 50/50 | 1.52 MW | 1.52 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 943172 | AE2-346 E | 50/50 | 0.65 MW | 0.65 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 944141 | AF1-082 | Adder | 1.9 MW | 1.61 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315294 | 1DOMTR10 | 50/50 | 24.91 MW | 24.91 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315606 | 3AA2-053SOLA | 50/50 | 1.11 MW | 1.11 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 900672 | V4-068 E | 50/50 | 0.21 MW | 0.21 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917332 | Z2-043 E | 50/50 | 1.25 MW | 1.25 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917342 | Z2-044 E | 50/50 | 0.4 MW | 0.4 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 922922 | AB1-081 C OP | Adder | 5.89 MW | 5.01 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 922923 | AB1-081 E OP | Adder | 2.53 MW | 2.15 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923262 | AB1-132 C OP | 50/50 | 9.77 MW | 9.77 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923263 | AB1-132 E OP | 50/50 | 4.18 MW | 4.18 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923573 | AB1-173 E OP | Adder | 0.54 MW | 0.46 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923991 | AB2-040 C O1 | Adder | 3.76 MW | 3.2 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923992 | AB2-040 E O1 | Adder | 3.08 MW | 2.62 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924152 | AB2-059 E OP | Adder | 3.58 MW | 3.04 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925121 | AB2-169 C | 50/50 | 2.18 MW | 2.18 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925122 | AB2-169 E | 50/50 | 11.28 MW | 11.28 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925591 | AC1-034 C | Adder | 4.5 MW | 3.83 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925592 | AC1-034 E | Adder | 3.39 MW | 2.88 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 932631 | AC2-084 C | 50/50 | 7.39 MW | 7.39 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 932632 | AC2-084 E | 50/50 | 3.64 MW | 3.64 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 938222 | AE1-035 E | 50/50 | 1.56 MW | 1.56 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940491 | AE2-034 C | 50/50 | 22.77 MW | 22.77 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940492 | AE2-034 E | 50/50 | 9.76 MW | 9.76 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940571 | AE2-044 C | Adder | 2.95 MW | 2.5 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 940572 | AE2-044 E | Adder | 1.26 MW | 1.07 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957521 | AF2-046 C | 50/50 | 12.92 MW | 12.92 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957522 | AF2-046 E | 50/50 | 6.5 MW | 6.5 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957531 | AF2-047 C | 50/50 | 54.1 MW | 54.1 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957532 | AF2-047 E | 50/50 | 27.21 MW | 27.21 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957861 | AF2-080 C | 50/50 | 7.85 MW | 7.85 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 957862 | AF2-080 E | 50/50 | 3.48 MW | 3.48 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 916042 | Z1-036 E | 50/50 | 117.19 MW | 117.19 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314589 | 3MURPHYS | 50/50 | 0.07 MW | 0.07 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315141 | 1GASTONB | 50/50 | 2.22 MW | 2.22 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315292 | 1DOMTR78 | 50/50 | 3.33 MW | 3.33 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315611 | 6Z1-036WIND | 50/50 | 17.45 MW | 17.45 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 938221 | AE1-035 C | 50/50 | 3.21 MW | 3.21 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 314574 | 6EVERETS | 50/50 | 0.34 MW | 0.34 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315612 | 3AA2-057SOLA | 50/50 | 0.89 MW | 0.89 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 917512 | Z2-088 E OP1 | 50/50 | 7.37 MW | 7.37 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920671 | AA2-174 C OP | 50/50 | 0.05 MW | 0.05 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920672 | AA2-174 E OP | 50/50 | 0.32 MW | 0.32 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923911 | AB2-031 C O1 | Adder | 1.15 MW | 0.97 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923912 | AB2-031 E O1 | Adder | 0.56 MW | 0.48 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924501 | AB2-099 C | 50/50 | 0.63 MW | 0.63 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 924502 | AB2-099 E | 50/50 | 0.27 MW | 0.27 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 925172 | AB2-174 E O1 | Adder | 3.1 MW | 2.63 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926071 | AC1-086 C | 50/50 | 14.38 MW | 14.38 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 926072 | AC1-086 E | 50/50 | 6.54 MW | 6.54 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927021 | AC1-189 C | 50/50 | 8.64 MW | 8.64 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927022 | AC1-189 E | 50/50 | 4.31 MW | 4.31 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927141 | AC1-208 C | 50/50 | 6.62 MW | 6.62 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 927142 | AC1-208 E | 50/50 | 2.94 MW | 2.94 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923572 | AB1-173 C OP | Adder | 1.16 MW | 0.98 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923582 | AB1-173AC OP | Adder | 1.16 MW | 0.98 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923583 | AB1-173AE OP | Adder | 0.54 MW | 0.46 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 960331 | AF2-324 C O1 | Adder | 5.27 MW | 4.48 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 960332 | AF2-324 E O1 | Adder | 2.83 MW | 2.41 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315614 | AA2-178 C | 50/50 | 5.27 MW | 5.27 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 920692 | AA2-178 E | 50/50 | 13.01 MW | 13.01 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 923831 | AB2-022 C | Adder | -1.96 MW | -1.67 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918561 | AA1-072 C | 50/50 | 0.37 MW | 0.37 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918562 | AA1-072 E | 50/50 | 0.18 MW | 0.18 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 933981 | AD1-022 C | 50/50 | 20.12 MW | 20.12 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 933982 | AD1-022 E | 50/50 | 10.95 MW | 10.95 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 315602 | 1HOLLOMANSOL | 50/50 | 2.23 MW | 2.23 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | 918512 | AA1-065 E OP | 50/50 | 6.32 MW | 6.32 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.68 MW | 2.68 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.03 MW | 9.03 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.21 MW | 0.21 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.87 MW | 1.87 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.06 MW | 3.06 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.25 MW | 16.25 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.48 MW | 10.48 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.48 MW | 0.48 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.5 MW | 0.5 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.39 MW | 1.39 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.83 MW | 1.83 MW |
| 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 24642 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.85 MW | 8.85 MW |
| Details for 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934521 | AD1-076 C | Adder | 17.9 MW | 15.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315294 | 1DOMTR10 | Adder | 3.42 MW | 2.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940491 | AE2-034 C | Adder | 2.49 MW | 2.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957531 | AF2-047 C | Adder | 5.92 MW | 5.03 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940641 | AE2-051 C O1 | Adder | 4.69 MW | 3.98 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314421 | 6WINCHST | 80/20 | 0.11 MW | 0.11 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314491 | 3PENDLTN | 80/20 | 0.14 MW | 0.14 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314507 | 3THOMPSN | 80/20 | 0.14 MW | 0.14 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314638 | 6ELIZ CT | 80/20 | 0.09 MW | 0.09 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314639 | 6TANGLEW | 80/20 | 0.17 MW | 0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314643 | 3O INLET | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315092 | 1YORKTN3 | 80/20 | 19.92 MW | 19.92 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926661 | AC1-147 C | 80/20 | 0.92 MW | 0.92 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934061 | AD1-033 C | 80/20 | 3.1 MW | 3.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935111 | AD1-144 C | 80/20 | 0.74 MW | 0.74 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936151 | AD2-021 | Adder | -0.11 MW | -0.09 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936581 | AD2-073 C | Adder | -1.88 MW | -1.6 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936661 | AD2-085 C | Adder | 1.0 MW | 0.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937221 | AD2-160 C O1 | 80/20 | 2.39 MW | 2.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942341 | AE2-247 C | Adder | 0.43 MW | 0.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942401 | AE2-253 C | 80/20 | 2.51 MW | 2.51 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943461 | AF1-017 C | Adder | 0.39 MW | 0.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943611 | AF1-032 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943621 | AF1-033 C | 80/20 | 0.95 MW | 0.95 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944871 | AF1-152 C | 80/20 | 2.06 MW | 2.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945361 | AF1-201 C O1 | Adder | 5.24 MW | 4.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945831 | AF1-248 | Adder | -0.31 MW | -0.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315098 | 1CHESPKA | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315099 | 1CHESPKB | 80/20 | 0.31 MW | 0.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315108 | 1ELIZAR1 | 80/20 | 1.39 MW | 1.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315109 | 1ELIZAR2 | 80/20 | 1.37 MW | 1.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315110 | 1ELIZAR3 | 80/20 | 1.41 MW | 1.41 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315233 | 1SURRY 2 | 80/20 | 14.25 MW | 14.25 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315260 | 1GOSPORTA | 80/20 | 0.15 MW | 0.15 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315261 | 1GOSPORTB | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315262 | 1GOSPORTC | 80/20 | 0.16 MW | 0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315603 | 6AA1-139SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315605 | 6W1-029WIND | 80/20 | 0.32 MW | 0.32 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315611 | 6Z1-036WIND | 80/20 | 1.6 MW | 1.6 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932591 | AC2-079 C O1 | Adder | 1.67 MW | 1.42 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938221 | AE1-035 C | Adder | 0.67 MW | 0.57 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939431 | AE1-175 C | 80/20 | 1.08 MW | 1.08 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941101 | AE2-104 C O1 | 80/20 | 1.24 MW | 1.24 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941281 | AE2-122 C O1 | 80/20 | 11.67 MW | 11.67 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941291 | AE2-123 C O1 | 80/20 | 12.0 MW | 12.0 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941301 | AE2-124 C O1 | 80/20 | 10.91 MW | 10.91 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957491 | AF2-043 C | 80/20 | 0.87 MW | 0.87 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957631 | AF2-057 | 80/20 | 1.46 MW | 1.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941501 | AE2-147 C | 80/20 | 6.18 MW | 6.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941581 | AE2-155 C | Adder | -0.24 MW | -0.2 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941591 | AE2-156 O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957871 | AF2-081 C | 80/20 | 4.06 MW | 4.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958161 | AF2-110 C | 80/20 | 0.51 MW | 0.51 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923831 | AB2-022 C | 80/20 | 0.92 MW | 0.92 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926751 | AC1-161 C O1 | 80/20 | 14.03 MW | 14.03 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932041 | AC2-012 C | 80/20 | 3.28 MW | 3.28 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933291 | AC2-141 C | 80/20 | 14.03 MW | 14.03 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938531 | AE1-072 C O1 | 80/20 | 7.1 MW | 7.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938771 | AE1-103 C O1 | Adder | 0.95 MW | 0.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939311 | AE1-162 C | 80/20 | 0.78 MW | 0.78 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939411 | AE1-173 C | Adder | 27.72 MW | 23.56 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936341 | AD2-044 C | Adder | -0.22 MW | -0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933261 | AC2-137 C | Adder | -0.94 MW | -0.8 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933271 | AC2-138 C | Adder | -0.7 MW | -0.59 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944581 | AF1-123 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944591 | AF1-124 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944601 | AF1-125 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933981 | AD1-022 C | Adder | 2.82 MW | 2.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.22 MW | 0.22 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.36 MW | 5.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.18 MW | 1.18 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 10.84 MW | 10.84 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.45 MW | 6.45 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.39 MW | 0.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.76 MW | 0.76 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.29 MW | 4.29 MW |
| Details for 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934521 | AD1-076 C | Adder | 17.9 MW | 15.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315294 | 1DOMTR10 | Adder | 3.42 MW | 2.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940491 | AE2-034 C | Adder | 2.49 MW | 2.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957531 | AF2-047 C | Adder | 5.92 MW | 5.03 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940641 | AE2-051 C O1 | Adder | 4.69 MW | 3.98 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314421 | 6WINCHST | 80/20 | 0.11 MW | 0.11 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314491 | 3PENDLTN | 80/20 | 0.14 MW | 0.14 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314507 | 3THOMPSN | 80/20 | 0.14 MW | 0.14 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314638 | 6ELIZ CT | 80/20 | 0.09 MW | 0.09 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314639 | 6TANGLEW | 80/20 | 0.17 MW | 0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314643 | 3O INLET | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315092 | 1YORKTN3 | 80/20 | 19.92 MW | 19.92 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926661 | AC1-147 C | 80/20 | 0.92 MW | 0.92 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934061 | AD1-033 C | 80/20 | 3.1 MW | 3.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935111 | AD1-144 C | 80/20 | 0.74 MW | 0.74 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936151 | AD2-021 | Adder | -0.11 MW | -0.09 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936581 | AD2-073 C | Adder | -1.88 MW | -1.6 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936661 | AD2-085 C | Adder | 1.0 MW | 0.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937221 | AD2-160 C O1 | 80/20 | 2.39 MW | 2.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942341 | AE2-247 C | Adder | 0.43 MW | 0.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942401 | AE2-253 C | 80/20 | 2.51 MW | 2.51 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943461 | AF1-017 C | Adder | 0.39 MW | 0.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943611 | AF1-032 C | 80/20 | 0.71 MW | 0.71 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943621 | AF1-033 C | 80/20 | 0.95 MW | 0.95 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944871 | AF1-152 C | 80/20 | 2.06 MW | 2.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945361 | AF1-201 C O1 | Adder | 5.24 MW | 4.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945831 | AF1-248 | Adder | -0.31 MW | -0.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315098 | 1CHESPKA | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315099 | 1CHESPKB | 80/20 | 0.31 MW | 0.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315108 | 1ELIZAR1 | 80/20 | 1.39 MW | 1.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315109 | 1ELIZAR2 | 80/20 | 1.37 MW | 1.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315110 | 1ELIZAR3 | 80/20 | 1.41 MW | 1.41 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315233 | 1SURRY 2 | 80/20 | 14.25 MW | 14.25 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315260 | 1GOSPORTA | 80/20 | 0.15 MW | 0.15 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315261 | 1GOSPORTB | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315262 | 1GOSPORTC | 80/20 | 0.16 MW | 0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315603 | 6AA1-139SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315605 | 6W1-029WIND | 80/20 | 0.32 MW | 0.32 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315611 | 6Z1-036WIND | 80/20 | 1.6 MW | 1.6 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932591 | AC2-079 C O1 | Adder | 1.67 MW | 1.42 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938221 | AE1-035 C | Adder | 0.67 MW | 0.57 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939431 | AE1-175 C | 80/20 | 1.08 MW | 1.08 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941101 | AE2-104 C O1 | 80/20 | 1.24 MW | 1.24 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941281 | AE2-122 C O1 | 80/20 | 11.67 MW | 11.67 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941291 | AE2-123 C O1 | 80/20 | 12.0 MW | 12.0 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941301 | AE2-124 C O1 | 80/20 | 10.91 MW | 10.91 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957491 | AF2-043 C | 80/20 | 0.87 MW | 0.87 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957631 | AF2-057 | 80/20 | 1.46 MW | 1.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941501 | AE2-147 C | 80/20 | 6.18 MW | 6.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941581 | AE2-155 C | Adder | -0.24 MW | -0.2 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941591 | AE2-156 O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957871 | AF2-081 C | 80/20 | 4.06 MW | 4.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958161 | AF2-110 C | 80/20 | 0.51 MW | 0.51 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923831 | AB2-022 C | 80/20 | 0.92 MW | 0.92 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926751 | AC1-161 C O1 | 80/20 | 14.03 MW | 14.03 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932041 | AC2-012 C | 80/20 | 3.28 MW | 3.28 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933291 | AC2-141 C | 80/20 | 14.03 MW | 14.03 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938531 | AE1-072 C O1 | 80/20 | 7.1 MW | 7.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938771 | AE1-103 C O1 | Adder | 0.95 MW | 0.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939311 | AE1-162 C | 80/20 | 0.78 MW | 0.78 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939411 | AE1-173 C | Adder | 27.72 MW | 23.56 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936341 | AD2-044 C | Adder | -0.22 MW | -0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933261 | AC2-137 C | Adder | -0.94 MW | -0.8 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933271 | AC2-138 C | Adder | -0.7 MW | -0.59 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944581 | AF1-123 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944591 | AF1-124 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944601 | AF1-125 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933981 | AD1-022 C | Adder | 2.82 MW | 2.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.22 MW | 0.22 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.36 MW | 5.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.18 MW | 1.18 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 10.84 MW | 10.84 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.45 MW | 6.45 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.39 MW | 0.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.76 MW | 0.76 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.29 MW | 4.29 MW |
| Details for 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934521 | AD1-076 C | Adder | 17.9 MW | 15.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315294 | 1DOMTR10 | Adder | 3.42 MW | 2.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940491 | AE2-034 C | Adder | 2.49 MW | 2.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957531 | AF2-047 C | Adder | 5.92 MW | 5.03 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940641 | AE2-051 C O1 | Adder | 4.69 MW | 3.98 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314421 | 6WINCHST | 80/20 | 0.11 MW | 0.11 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314491 | 3PENDLTN | 80/20 | 0.14 MW | 0.14 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314507 | 3THOMPSN | 80/20 | 0.14 MW | 0.14 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314638 | 6ELIZ CT | 80/20 | 0.09 MW | 0.09 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314639 | 6TANGLEW | 80/20 | 0.17 MW | 0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314643 | 3O INLET | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315092 | 1YORKTN3 | 80/20 | 19.92 MW | 19.92 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926661 | AC1-147 C | 80/20 | 0.92 MW | 0.92 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934061 | AD1-033 C | 80/20 | 3.1 MW | 3.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935111 | AD1-144 C | 80/20 | 0.74 MW | 0.74 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936151 | AD2-021 | Adder | -0.11 MW | -0.09 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936581 | AD2-073 C | Adder | -1.88 MW | -1.6 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936661 | AD2-085 C | Adder | 1.0 MW | 0.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937221 | AD2-160 C O1 | 80/20 | 2.39 MW | 2.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942341 | AE2-247 C | Adder | 0.43 MW | 0.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942401 | AE2-253 C | 80/20 | 2.51 MW | 2.51 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943461 | AF1-017 C | Adder | 0.39 MW | 0.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943611 | AF1-032 C | 80/20 | 0.71 MW | 0.71 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943621 | AF1-033 C | 80/20 | 0.95 MW | 0.95 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944871 | AF1-152 C | 80/20 | 2.06 MW | 2.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945361 | AF1-201 C O1 | Adder | 5.24 MW | 4.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945831 | AF1-248 | Adder | -0.31 MW | -0.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315098 | 1CHESPKA | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315099 | 1CHESPKB | 80/20 | 0.31 MW | 0.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315108 | 1ELIZAR1 | 80/20 | 1.39 MW | 1.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315109 | 1ELIZAR2 | 80/20 | 1.37 MW | 1.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315110 | 1ELIZAR3 | 80/20 | 1.41 MW | 1.41 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315233 | 1SURRY 2 | 80/20 | 14.25 MW | 14.25 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315260 | 1GOSPORTA | 80/20 | 0.15 MW | 0.15 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315261 | 1GOSPORTB | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315262 | 1GOSPORTC | 80/20 | 0.16 MW | 0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315603 | 6AA1-139SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315605 | 6W1-029WIND | 80/20 | 0.32 MW | 0.32 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315611 | 6Z1-036WIND | 80/20 | 1.6 MW | 1.6 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932591 | AC2-079 C O1 | Adder | 1.67 MW | 1.42 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938221 | AE1-035 C | Adder | 0.67 MW | 0.57 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939431 | AE1-175 C | 80/20 | 1.08 MW | 1.08 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941101 | AE2-104 C O1 | 80/20 | 1.24 MW | 1.24 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941281 | AE2-122 C O1 | 80/20 | 11.67 MW | 11.67 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941291 | AE2-123 C O1 | 80/20 | 12.0 MW | 12.0 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941301 | AE2-124 C O1 | 80/20 | 10.91 MW | 10.91 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957491 | AF2-043 C | 80/20 | 0.87 MW | 0.87 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957631 | AF2-057 | 80/20 | 1.46 MW | 1.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941501 | AE2-147 C | 80/20 | 6.18 MW | 6.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941581 | AE2-155 C | Adder | -0.24 MW | -0.2 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941591 | AE2-156 O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957871 | AF2-081 C | 80/20 | 4.06 MW | 4.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958161 | AF2-110 C | 80/20 | 0.51 MW | 0.51 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923831 | AB2-022 C | 80/20 | 0.92 MW | 0.92 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926751 | AC1-161 C O1 | 80/20 | 14.03 MW | 14.03 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932041 | AC2-012 C | 80/20 | 3.28 MW | 3.28 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933291 | AC2-141 C | 80/20 | 14.03 MW | 14.03 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938531 | AE1-072 C O1 | 80/20 | 7.1 MW | 7.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938771 | AE1-103 C O1 | Adder | 0.95 MW | 0.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939311 | AE1-162 C | 80/20 | 0.78 MW | 0.78 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939411 | AE1-173 C | Adder | 27.72 MW | 23.56 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936341 | AD2-044 C | Adder | -0.22 MW | -0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933261 | AC2-137 C | Adder | -0.94 MW | -0.8 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933271 | AC2-138 C | Adder | -0.7 MW | -0.59 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944581 | AF1-123 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944591 | AF1-124 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944601 | AF1-125 C O1 | 80/20 | 20.18 MW | 20.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933981 | AD1-022 C | Adder | 2.82 MW | 2.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.22 MW | 0.22 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 5.36 MW | 5.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.18 MW | 1.18 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 10.84 MW | 10.84 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 6.45 MW | 6.45 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.39 MW | 0.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.76 MW | 0.76 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.29 MW | 4.29 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.5 MW | 0.5 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.45 MW | 1.45 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.38 MW | 1.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.56 MW | 4.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.83 MW | 2.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.14 MW | 2.14 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 7.0 MW | 7.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.43 MW | 6.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.15 MW | 2.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.71 MW | 15.71 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 41.25 MW | 41.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.45 MW | 1.45 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.98 MW | 2.98 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.53 MW | 1.53 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 9.28 MW | 9.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.8 MW | 30.8 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.96 MW | 0.96 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.09 MW | 7.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.16 MW | 9.16 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.24 MW | 4.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.64 MW | 4.64 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.43 MW | 14.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.07 MW | 10.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.9 MW | 7.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.74 MW | 0.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 7.0 MW | 7.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.17 MW | 1.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.29 MW | 1.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.63 MW | 2.63 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.29 MW | 0.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.29 MW | 1.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.07 MW | 0.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 1.9 MW | 1.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 45.35 MW | 45.35 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 8.7 MW | 8.7 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 9.28 MW | 9.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.54 MW | 8.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924511 | AB2-100 C | 80/20 | 7.4 MW | 7.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938771 | AE1-103 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.38 MW | 0.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.58 MW | 7.58 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.83 MW | 1.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.48 MW | 0.48 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.16 MW | 3.16 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.33 MW | 10.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.17 MW | 2.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.26 MW | 19.26 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.07 MW | 12.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.61 MW | 0.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.15 MW | 2.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 9.74 MW | 9.74 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314582 | 3KELFORD | 80/20 | 0.44 MW | 0.44 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315126 | 1ROARAP2 | 80/20 | 1.85 MW | 1.85 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315128 | 1ROARAP4 | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315131 | 1EDGECMA | 80/20 | 7.95 MW | 7.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315132 | 1EDGECMB | 80/20 | 7.95 MW | 7.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315136 | 1ROSEMG1 | 80/20 | 4.27 MW | 4.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315137 | 1ROSEMS1 | 80/20 | 2.65 MW | 2.65 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315138 | 1ROSEMG2 | 80/20 | 2.0 MW | 2.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315139 | 1GASTONA | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926201 | AC1-098 C | 80/20 | 6.32 MW | 6.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926211 | AC1-099 C | 80/20 | 2.12 MW | 2.12 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934331 | AD1-057 C O1 | 80/20 | 14.57 MW | 14.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934521 | AD1-076 C | 80/20 | 31.96 MW | 31.96 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 943171 | AE2-346 C | 80/20 | 1.25 MW | 1.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 944141 | AF1-082 | 80/20 | 2.76 MW | 2.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315294 | 1DOMTR10 | 80/20 | 6.83 MW | 6.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.83 MW | 1.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923262 | AB1-132 C OP | 80/20 | 28.9 MW | 28.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923991 | AB2-040 C O1 | 80/20 | 9.31 MW | 9.31 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925121 | AB2-169 C | 80/20 | 0.76 MW | 0.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 932631 | AC2-084 C | 80/20 | 9.02 MW | 9.02 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940491 | AE2-034 C | 80/20 | 3.41 MW | 3.41 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957521 | AF2-046 C | 80/20 | 14.25 MW | 14.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957531 | AF2-047 C | 80/20 | 8.09 MW | 8.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957861 | AF2-080 C | 80/20 | 6.63 MW | 6.63 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315115 | 1S HAMPT1 | 80/20 | 0.91 MW | 0.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315141 | 1GASTONB | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315292 | 1DOMTR78 | 80/20 | 0.92 MW | 0.92 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.61 MW | 1.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.87 MW | 0.87 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938221 | AE1-035 C | 80/20 | 1.91 MW | 1.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314574 | 6EVERETS | 80/20 | 0.23 MW | 0.23 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315612 | 3AA2-057SOLA | 80/20 | 1.27 MW | 1.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923911 | AB2-031 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924501 | AB2-099 C | 80/20 | 0.52 MW | 0.52 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925781 | AC1-054 C O1 | 80/20 | 4.17 MW | 4.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926071 | AC1-086 C | 80/20 | 42.56 MW | 42.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927021 | AC1-189 C | 80/20 | 7.3 MW | 7.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927141 | AC1-208 C | 80/20 | 9.79 MW | 9.79 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923572 | AB1-173 C OP | 80/20 | 2.86 MW | 2.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923582 | AB1-173AC OP | 80/20 | 2.86 MW | 2.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 960331 | AF2-324 C O1 | 80/20 | 7.76 MW | 7.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315614 | AA2-178 C | 80/20 | 0.79 MW | 0.79 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924511 | AB2-100 C | 80/20 | 6.88 MW | 6.88 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925171 | AB2-174 C O1 | 80/20 | 1.54 MW | 1.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938771 | AE1-103 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 918561 | AA1-072 C | 80/20 | 0.33 MW | 0.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 933981 | AD1-022 C | 80/20 | 5.75 MW | 5.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.33 MW | 1.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.74 MW | 2.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.8 MW | 8.8 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.69 MW | 16.69 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.32 MW | 10.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.54 MW | 0.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.32 MW | 1.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.86 MW | 1.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.16 MW | 8.16 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.2 MW | 0.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 1.21 MW | 1.21 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 1.15 MW | 1.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.49 MW | 7.49 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.49 MW | 7.49 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 4.17 MW | 4.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.59 MW | 2.59 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 6.42 MW | 6.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.13 MW | 0.13 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 5.09 MW | 5.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 1.71 MW | 1.71 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.36 MW | 29.36 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.04 MW | 1.04 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.54 MW | 2.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 6.3 MW | 6.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 1.24 MW | 1.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 7.89 MW | 7.89 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 28.25 MW | 28.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.7 MW | 0.7 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.02 MW | 6.02 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 7.25 MW | 7.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940491 | AE2-034 C | 80/20 | 3.12 MW | 3.12 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 3.94 MW | 3.94 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 11.0 MW | 11.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | 80/20 | 7.42 MW | 7.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.2 MW | 6.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.06 MW | 0.06 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.65 MW | 0.65 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 6.42 MW | 6.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.84 MW | 0.84 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.61 MW | 0.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314574 | 6EVERETS | 80/20 | 0.21 MW | 0.21 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315612 | 3AA2-057SOLA | 80/20 | 1.07 MW | 1.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 920671 | AA2-174 C OP | 80/20 | 0.06 MW | 0.06 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924151 | AB2-059 C OP | 80/20 | 1.61 MW | 1.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924501 | AB2-099 C | 80/20 | 0.43 MW | 0.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925781 | AC1-054 C O1 | 80/20 | 2.91 MW | 2.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926071 | AC1-086 C | 80/20 | 41.61 MW | 41.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927021 | AC1-189 C | 80/20 | 6.82 MW | 6.82 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927141 | AC1-208 C | 80/20 | 7.59 MW | 7.59 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315614 | AA2-178 C | 80/20 | 0.72 MW | 0.72 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924511 | AB2-100 C | 80/20 | 7.19 MW | 7.19 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 938771 | AE1-103 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 918561 | AA1-072 C | 80/20 | 0.28 MW | 0.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.28 MW | 5.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.22 MW | 1.22 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.55 MW | 2.55 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.27 MW | 8.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 15.57 MW | 15.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 9.69 MW | 9.69 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.5 MW | 0.5 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.74 MW | 1.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.72 MW | 7.72 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315611 | 6Z1-036WIND | Adder | -2.17 MW | -1.85 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 8.71 MW | 8.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315611 | 6Z1-036WIND | Adder | -2.17 MW | -1.85 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 8.71 MW | 8.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.5 MW | 0.5 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.45 MW | 1.45 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.38 MW | 1.38 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.57 MW | 4.57 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.83 MW | 2.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.14 MW | 2.14 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 7.01 MW | 7.01 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.44 MW | 6.44 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.73 MW | 15.73 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 41.36 MW | 41.36 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.45 MW | 1.45 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.99 MW | 2.99 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.54 MW | 1.54 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 9.3 MW | 9.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.82 MW | 30.82 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.96 MW | 0.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.1 MW | 7.1 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.18 MW | 9.18 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.25 MW | 4.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.65 MW | 4.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.46 MW | 14.46 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.1 MW | 10.1 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.92 MW | 7.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.74 MW | 0.74 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 7.01 MW | 7.01 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.17 MW | 1.17 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.64 MW | 2.64 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.29 MW | 0.29 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.29 MW | 1.29 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.07 MW | 0.07 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 1.9 MW | 1.9 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 3.68 MW | 3.68 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 45.39 MW | 45.39 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 8.72 MW | 8.72 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 9.3 MW | 9.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.55 MW | 8.55 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938771 | AE1-103 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.38 MW | 0.38 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.6 MW | 7.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.83 MW | 1.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.18 MW | 3.18 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.61 MW | 10.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.21 MW | 2.21 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.46 MW | 19.46 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.37 MW | 12.37 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.61 MW | 0.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.17 MW | 2.17 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.18 MW | 10.18 MW |
| Details for 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314582 | 3KELFORD | 80/20 | 0.44 MW | 0.44 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315126 | 1ROARAP2 | 80/20 | 1.85 MW | 1.85 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315128 | 1ROARAP4 | 80/20 | 1.77 MW | 1.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315131 | 1EDGECMA | 80/20 | 7.96 MW | 7.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315132 | 1EDGECMB | 80/20 | 7.96 MW | 7.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315136 | 1ROSEMG1 | 80/20 | 4.28 MW | 4.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315137 | 1ROSEMS1 | 80/20 | 2.65 MW | 2.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315138 | 1ROSEMG2 | 80/20 | 2.0 MW | 2.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315139 | 1GASTONA | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926201 | AC1-098 C | 80/20 | 6.34 MW | 6.34 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926211 | AC1-099 C | 80/20 | 2.12 MW | 2.12 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934331 | AD1-057 C O1 | 80/20 | 14.59 MW | 14.59 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934521 | AD1-076 C | 80/20 | 32.07 MW | 32.07 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 943171 | AE2-346 C | 80/20 | 1.25 MW | 1.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315294 | 1DOMTR10 | 80/20 | 6.86 MW | 6.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.83 MW | 1.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 922922 | AB1-081 C OP | 80/20 | 8.62 MW | 8.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923262 | AB1-132 C OP | 80/20 | 28.93 MW | 28.93 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923991 | AB2-040 C O1 | 80/20 | 9.33 MW | 9.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925121 | AB2-169 C | 80/20 | 0.76 MW | 0.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925591 | AC1-034 C | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 932631 | AC2-084 C | 80/20 | 9.03 MW | 9.03 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940491 | AE2-034 C | 80/20 | 3.42 MW | 3.42 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940571 | AE2-044 C | 80/20 | 4.31 MW | 4.31 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957521 | AF2-046 C | 80/20 | 14.28 MW | 14.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957531 | AF2-047 C | 80/20 | 8.13 MW | 8.13 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957861 | AF2-080 C | 80/20 | 6.65 MW | 6.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315115 | 1S HAMPT1 | 80/20 | 0.92 MW | 0.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315141 | 1GASTONB | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315292 | 1DOMTR78 | 80/20 | 0.92 MW | 0.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.61 MW | 1.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.87 MW | 0.87 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938221 | AE1-035 C | 80/20 | 1.92 MW | 1.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314574 | 6EVERETS | 80/20 | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315612 | 3AA2-057SOLA | 80/20 | 1.28 MW | 1.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923911 | AB2-031 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924501 | AB2-099 C | 80/20 | 0.52 MW | 0.52 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925781 | AC1-054 C O1 | 80/20 | 4.19 MW | 4.19 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926071 | AC1-086 C | 80/20 | 42.6 MW | 42.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927021 | AC1-189 C | 80/20 | 7.32 MW | 7.32 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927141 | AC1-208 C | 80/20 | 9.81 MW | 9.81 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923572 | AB1-173 C OP | 80/20 | 2.86 MW | 2.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923582 | AB1-173AC OP | 80/20 | 2.86 MW | 2.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 960331 | AF2-324 C O1 | 80/20 | 7.77 MW | 7.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315614 | AA2-178 C | 80/20 | 0.79 MW | 0.79 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925171 | AB2-174 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938771 | AE1-103 C O1 | 80/20 | 1.36 MW | 1.36 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 918561 | AA1-072 C | 80/20 | 0.33 MW | 0.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 933981 | AD1-022 C | 80/20 | 5.76 MW | 5.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.33 MW | 1.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.76 MW | 2.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.08 MW | 9.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.9 MW | 1.9 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.89 MW | 16.89 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.62 MW | 10.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.54 MW | 0.54 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.37 MW | 1.37 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.88 MW | 1.88 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.59 MW | 8.59 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315131 | 1EDGECMA | Adder | 11.39 MW | 9.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315132 | 1EDGECMB | Adder | 11.39 MW | 9.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926201 | AC1-098 C | Adder | 9.08 MW | 7.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926211 | AC1-099 C | Adder | 3.04 MW | 2.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927261 | AC1-222 C | Adder | 4.79 MW | 4.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934311 | AD1-055 C | Adder | 3.33 MW | 2.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934331 | AD1-057 C O1 | Adder | 14.42 MW | 12.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934521 | AD1-076 C | Adder | 83.09 MW | 70.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935171 | AD1-152 C O1 | Adder | 11.89 MW | 10.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937481 | AD2-202 C O1 | Adder | 3.37 MW | 2.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942461 | AE2-259 C O1 | Adder | 12.48 MW | 10.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942931 | AE2-313 C | 80/20 | 59.39 MW | 59.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943171 | AE2-346 C | Adder | 2.13 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943901 | AF1-058 C | Adder | 2.62 MW | 2.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944011 | AF1-069 C | 80/20 | 21.52 MW | 21.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944141 | AF1-082 | Adder | 4.1 MW | 3.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945811 | AF1-246 C O1 | 80/20 | 11.71 MW | 11.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958801 | AF2-171 C | Adder | 19.24 MW | 16.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 959311 | AF2-222 C | Adder | 21.74 MW | 18.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960061 | AF2-297 C | Adder | 10.49 MW | 8.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960081 | AF2-299 C | Adder | 3.82 MW | 3.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315294 | 1DOMTR10 | Adder | 16.47 MW | 14.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 922922 | AB1-081 C OP | Adder | 12.75 MW | 10.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923262 | AB1-132 C OP | Adder | 21.08 MW | 17.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923991 | AB2-040 C O1 | Adder | 11.06 MW | 9.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924301 | AB2-077 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924311 | AB2-078 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924321 | AB2-079 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925591 | AC1-034 C | Adder | 9.73 MW | 8.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932631 | AC2-084 C | Adder | 12.95 MW | 11.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938371 | AE1-056 C | Adder | 8.23 MW | 7.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940491 | AE2-034 C | Adder | 11.06 MW | 9.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940571 | AE2-044 C | Adder | 6.37 MW | 5.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940661 | AE2-053 O1 | Adder | 4.48 MW | 3.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941031 | AE2-094 C | 80/20 | 65.85 MW | 65.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941791 | AE2-182 C | Adder | 2.59 MW | 2.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946281 | AF1-292 C | Adder | 2.28 MW | 1.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946301 | AF1-294 C | Adder | 5.25 MW | 4.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957481 | AF2-042 C | 80/20 | 83.65 MW | 83.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957521 | AF2-046 C | Adder | 25.48 MW | 21.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957531 | AF2-047 C | Adder | 26.27 MW | 22.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957861 | AF2-080 C | Adder | 11.34 MW | 9.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958211 | AF2-115 C | Adder | 3.2 MW | 2.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940481 | AE2-033 C | Adder | 24.52 MW | 20.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940641 | AE2-051 C O1 | 80/20 | 28.91 MW | 28.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946011 | AF1-266 | Adder | 20.53 MW | 17.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933501 | AC2-165 C | Adder | 14.21 MW | 12.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314491 | 3PENDLTN | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314507 | 3THOMPSN | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315060 | 1CHESTF5 | Adder | 81.51 MW | 69.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315065 | 1CHESTF6 | Adder | 172.86 MW | 146.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315074 | 1HOPCGN1 | Adder | 11.73 MW | 9.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315075 | 1HOPCGN2 | Adder | 11.58 MW | 9.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315083 | 1SPRUNCA | Adder | 15.54 MW | 13.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315084 | 1SPRUNCB | Adder | 15.54 MW | 13.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926661 | AC1-147 C | 80/20 | 3.53 MW | 3.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934061 | AD1-033 C | 80/20 | 11.79 MW | 11.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934141 | AD1-041 C | Adder | 6.5 MW | 5.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935111 | AD1-144 C | Adder | 2.66 MW | 2.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936151 | AD2-021 | Adder | 0.3 MW | 0.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936661 | AD2-085 C | Adder | 5.31 MW | 4.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937221 | AD2-160 C O1 | 80/20 | 9.17 MW | 9.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942151 | AE2-227 C | Adder | 2.93 MW | 2.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942161 | AE2-228 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942341 | AE2-247 C | Adder | 2.3 MW | 1.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942371 | AE2-250 C O1 | Adder | 14.13 MW | 12.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942401 | AE2-253 C | 80/20 | 9.64 MW | 9.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943431 | AF1-014 C | Adder | 1.57 MW | 1.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943461 | AF1-017 C | Adder | 2.08 MW | 1.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943471 | AF1-018 | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943611 | AF1-032 C | Adder | 2.72 MW | 2.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943621 | AF1-033 C | Adder | 3.51 MW | 2.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944631 | AF1-128 O1 | Adder | 63.43 MW | 53.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944871 | AF1-152 C | Adder | 8.22 MW | 6.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945361 | AF1-201 C O1 | Adder | 22.0 MW | 18.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958501 | AF2-144 C | Adder | 2.72 MW | 2.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315098 | 1CHESPKA | 80/20 | 0.72 MW | 0.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315099 | 1CHESPKB | 80/20 | 1.2 MW | 1.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315105 | 1BRUNSWICKS1 | 80/20 | 29.9 MW | 29.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315108 | 1ELIZAR1 | 80/20 | 5.33 MW | 5.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315109 | 1ELIZAR2 | 80/20 | 5.24 MW | 5.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315110 | 1ELIZAR3 | 80/20 | 5.4 MW | 5.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315260 | 1GOSPORTA | 80/20 | 0.58 MW | 0.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315261 | 1GOSPORTB | 80/20 | 0.74 MW | 0.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315262 | 1GOSPORTC | 80/20 | 0.63 MW | 0.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315603 | 6AA1-139SOLA | 80/20 | 4.07 MW | 4.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315611 | 6Z1-036WIND | Adder | 6.62 MW | 5.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932591 | AC2-079 C O1 | Adder | 8.84 MW | 7.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938221 | AE1-035 C | Adder | 3.41 MW | 2.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938551 | AE1-074 C | 80/20 | 3.89 MW | 3.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938561 | AE1-075 C | Adder | 3.2 MW | 2.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939431 | AE1-175 C | Adder | 3.31 MW | 2.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939611 | AE1-191 C | Adder | 12.99 MW | 11.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940231 | AE2-005 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940431 | AE2-027 C O1 | Adder | 18.3 MW | 15.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940651 | AE2-052 | Adder | 5.38 MW | 4.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941101 | AE2-104 C O1 | Adder | 5.21 MW | 4.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941281 | AE2-122 C O1 | 80/20 | 44.58 MW | 44.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941291 | AE2-123 C O1 | 80/20 | 45.81 MW | 45.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941301 | AE2-124 C O1 | 80/20 | 41.66 MW | 41.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946261 | AF1-291 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957491 | AF2-043 C | Adder | 3.33 MW | 2.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957601 | AF2-054 C | Adder | 2.55 MW | 2.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957631 | AF2-057 | 80/20 | 5.61 MW | 5.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941501 | AE2-147 C | Adder | 24.66 MW | 20.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941581 | AE2-155 C | Adder | 0.76 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941591 | AE2-156 O1 | 80/20 | 28.05 MW | 28.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942001 | AE2-212 C | Adder | 3.16 MW | 2.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957831 | AF2-077 C | Adder | 2.85 MW | 2.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957871 | AF2-081 C | 80/20 | 15.63 MW | 15.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957911 | AF2-085 | 80/20 | 6.63 MW | 6.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958161 | AF2-110 C | Adder | 2.13 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923911 | AB2-031 C O1 | Adder | 3.37 MW | 2.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924501 | AB2-099 C | Adder | 0.89 MW | 0.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925781 | AC1-054 C O1 | Adder | 10.23 MW | 8.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926071 | AC1-086 C | Adder | 31.05 MW | 26.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926271 | AC1-105 C O1 | Adder | 7.47 MW | 6.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927021 | AC1-189 C | Adder | 12.49 MW | 10.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927141 | AC1-208 C | Adder | 13.27 MW | 11.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934611 | AD1-087 C O1 | Adder | 11.52 MW | 9.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936261 | AD2-033 C | Adder | 17.07 MW | 14.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939181 | AE1-148 C O1 | Adder | 12.1 MW | 10.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940241 | AE2-006 | Adder | 0.63 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923572 | AB1-173 C OP | Adder | 3.39 MW | 2.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923582 | AB1-173AC OP | Adder | 3.39 MW | 2.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925611 | AC1-036 C | Adder | 1.24 MW | 1.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960331 | AF2-324 C O1 | Adder | 11.12 MW | 9.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314947 | 8GREENSVILLE | 80/20 | 87.61 MW | 87.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923831 | AB2-022 C | Adder | 3.59 MW | 3.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925051 | AB2-160 C O1 | Adder | 7.96 MW | 6.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925061 | AB2-161 C O1 | Adder | 5.15 MW | 4.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925331 | AB2-190 C | Adder | 27.31 MW | 23.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926751 | AC1-161 C O1 | 80/20 | 47.95 MW | 47.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932041 | AC2-012 C | 80/20 | 12.57 MW | 12.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933291 | AC2-141 C | 80/20 | 47.95 MW | 47.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934011 | AD1-025 C | Adder | 24.56 MW | 20.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934571 | AD1-082 C | Adder | 11.74 MW | 9.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934621 | AD1-088 C | Adder | 15.97 MW | 13.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935161 | AD1-151 C O1 | Adder | 23.31 MW | 19.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938531 | AE1-072 C O1 | 80/20 | 27.47 MW | 27.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938771 | AE1-103 C O1 | Adder | 4.47 MW | 3.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939191 | AE1-149 C O1 | Adder | 16.16 MW | 13.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939311 | AE1-162 C | Adder | 3.26 MW | 2.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939411 | AE1-173 C | 80/20 | 149.38 MW | 149.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940541 | AE2-040 O1 | Adder | 4.36 MW | 3.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942551 | AE2-270 | Adder | 39.11 MW | 33.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957711 | AF2-065 C | Adder | 19.9 MW | 16.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925861 | AC1-065 C | Adder | 4.15 MW | 3.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926781 | AC1-164 C | Adder | 50.74 MW | 43.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936301 | AD2-039 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938031 | AE1-004 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932831 | AC2-110 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933261 | AC2-137 C | Adder | 2.63 MW | 2.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940551 | AE2-041 O1 | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 918561 | AA1-072 C | Adder | 0.52 MW | 0.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944581 | AF1-123 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944591 | AF1-124 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944601 | AF1-125 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933981 | AD1-022 C | Adder | 13.36 MW | 11.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.4 MW | 1.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.69 MW | 2.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.29 MW | 12.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 53.87 MW | 53.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.12 MW | 3.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.23 MW | 11.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 86.42 MW | 86.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 63.1 MW | 63.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.79 MW | 2.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.31 MW | 8.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 8.38 MW | 8.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 52.17 MW | 52.17 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315131 | 1EDGECMA | Adder | 10.68 MW | 9.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315132 | 1EDGECMB | Adder | 10.68 MW | 9.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926201 | AC1-098 C | Adder | 8.56 MW | 7.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926211 | AC1-099 C | Adder | 2.87 MW | 2.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927251 | AC1-221 C | Adder | 2.77 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927261 | AC1-222 C | Adder | 4.42 MW | 3.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934311 | AD1-055 C | Adder | 3.07 MW | 2.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934331 | AD1-057 C O1 | Adder | 13.49 MW | 11.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934341 | AD1-058 C | Adder | 6.94 MW | 5.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934521 | AD1-076 C | Adder | 80.0 MW | 68.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934991 | AD1-131 C | Adder | 2.28 MW | 1.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935171 | AD1-152 C O1 | Adder | 11.29 MW | 9.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937481 | AD2-202 C O1 | Adder | 3.23 MW | 2.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942461 | AE2-259 C O1 | Adder | 11.09 MW | 9.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942931 | AE2-313 C | 80/20 | 58.35 MW | 58.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943171 | AE2-346 C | Adder | 2.02 MW | 1.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943901 | AF1-058 C | Adder | 2.44 MW | 2.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944011 | AF1-069 C | 80/20 | 21.17 MW | 21.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944141 | AF1-082 | Adder | 3.84 MW | 3.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945811 | AF1-246 C O1 | Adder | 11.3 MW | 9.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958801 | AF2-171 C | Adder | 17.33 MW | 14.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 959311 | AF2-222 C | Adder | 19.74 MW | 16.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960061 | AF2-297 C | Adder | 9.75 MW | 8.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960081 | AF2-299 C | Adder | 3.53 MW | 3.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315294 | 1DOMTR10 | Adder | 15.8 MW | 13.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 922922 | AB1-081 C OP | Adder | 11.95 MW | 10.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923262 | AB1-132 C OP | Adder | 19.69 MW | 16.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923991 | AB2-040 C O1 | Adder | 10.28 MW | 8.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924301 | AB2-077 C O1 | Adder | 2.46 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924311 | AB2-078 C O1 | Adder | 2.46 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924321 | AB2-079 C O1 | Adder | 2.46 MW | 2.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925591 | AC1-034 C | Adder | 9.12 MW | 7.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932631 | AC2-084 C | Adder | 12.2 MW | 10.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932761 | AC2-100 C | Adder | 6.37 MW | 5.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938371 | AE1-056 C | Adder | 7.39 MW | 6.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940491 | AE2-034 C | Adder | 10.69 MW | 9.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940571 | AE2-044 C | Adder | 5.98 MW | 5.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940661 | AE2-053 O1 | Adder | 4.14 MW | 3.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941031 | AE2-094 C | 80/20 | 64.78 MW | 64.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941791 | AE2-182 C | Adder | 2.36 MW | 2.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946281 | AF1-292 C | Adder | 2.1 MW | 1.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946301 | AF1-294 C | Adder | 4.73 MW | 4.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957481 | AF2-042 C | Adder | 80.75 MW | 68.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957521 | AF2-046 C | Adder | 24.23 MW | 20.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957531 | AF2-047 C | Adder | 25.4 MW | 21.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957861 | AF2-080 C | Adder | 10.71 MW | 9.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958211 | AF2-115 C | Adder | 2.89 MW | 2.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940481 | AE2-033 C | Adder | 22.38 MW | 19.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940641 | AE2-051 C O1 | 80/20 | 28.66 MW | 28.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946011 | AF1-266 | Adder | 18.73 MW | 15.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933501 | AC2-165 C | Adder | 12.15 MW | 10.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314491 | 3PENDLTN | 80/20 | 0.54 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314507 | 3THOMPSN | 80/20 | 0.54 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315060 | 1CHESTF5 | Adder | 63.01 MW | 53.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315065 | 1CHESTF6 | Adder | 135.74 MW | 115.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315074 | 1HOPCGN1 | Adder | 9.56 MW | 8.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315075 | 1HOPCGN2 | Adder | 9.44 MW | 8.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315083 | 1SPRUNCA | Adder | 12.1 MW | 10.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315084 | 1SPRUNCB | Adder | 12.1 MW | 10.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926661 | AC1-147 C | 80/20 | 3.47 MW | 3.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934061 | AD1-033 C | 80/20 | 11.63 MW | 11.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934141 | AD1-041 C | Adder | 5.49 MW | 4.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935111 | AD1-144 C | Adder | 2.58 MW | 2.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936661 | AD2-085 C | Adder | 5.0 MW | 4.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 937221 | AD2-160 C O1 | 80/20 | 9.03 MW | 9.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942151 | AE2-227 C | Adder | 2.18 MW | 1.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942161 | AE2-228 C | Adder | 2.45 MW | 2.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942341 | AE2-247 C | Adder | 2.17 MW | 1.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942371 | AE2-250 C O1 | Adder | 11.65 MW | 9.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942401 | AE2-253 C | 80/20 | 9.5 MW | 9.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943431 | AF1-014 C | Adder | 1.32 MW | 1.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943461 | AF1-017 C | Adder | 1.96 MW | 1.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943471 | AF1-018 | Adder | 7.32 MW | 6.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943611 | AF1-032 C | Adder | 2.66 MW | 2.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 943621 | AF1-033 C | Adder | 3.25 MW | 2.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944631 | AF1-128 O1 | Adder | 49.03 MW | 41.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944871 | AF1-152 C | Adder | 8.03 MW | 6.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 945361 | AF1-201 C O1 | Adder | 20.32 MW | 17.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958501 | AF2-144 C | Adder | 2.34 MW | 1.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315098 | 1CHESPKA | 80/20 | 0.71 MW | 0.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315099 | 1CHESPKB | 80/20 | 1.18 MW | 1.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.1 MW | 14.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.1 MW | 14.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.1 MW | 14.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315105 | 1BRUNSWICKS1 | 80/20 | 29.3 MW | 29.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315108 | 1ELIZAR1 | 80/20 | 5.24 MW | 5.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315109 | 1ELIZAR2 | 80/20 | 5.15 MW | 5.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315110 | 1ELIZAR3 | 80/20 | 5.31 MW | 5.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315233 | 1SURRY 2 | 80/20 | 40.96 MW | 40.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315260 | 1GOSPORTA | 80/20 | 0.57 MW | 0.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315261 | 1GOSPORTB | 80/20 | 0.73 MW | 0.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315262 | 1GOSPORTC | 80/20 | 0.62 MW | 0.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315603 | 6AA1-139SOLA | 80/20 | 4.0 MW | 4.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 315611 | 6Z1-036WIND | Adder | 6.45 MW | 5.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932591 | AC2-079 C O1 | Adder | 8.34 MW | 7.09 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938221 | AE1-035 C | Adder | 3.26 MW | 2.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938551 | AE1-074 C | Adder | 3.18 MW | 2.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938561 | AE1-075 C | Adder | 2.76 MW | 2.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939431 | AE1-175 C | Adder | 2.98 MW | 2.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939611 | AE1-191 C | Adder | 10.97 MW | 9.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940231 | AE2-005 C | Adder | 1.39 MW | 1.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940431 | AE2-027 C O1 | Adder | 14.56 MW | 12.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940651 | AE2-052 | Adder | 4.71 MW | 4.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941101 | AE2-104 C O1 | Adder | 5.04 MW | 4.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941281 | AE2-122 C O1 | 80/20 | 43.88 MW | 43.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941291 | AE2-123 C O1 | 80/20 | 45.1 MW | 45.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941301 | AE2-124 C O1 | 80/20 | 41.02 MW | 41.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 946261 | AF1-291 C | Adder | 2.45 MW | 2.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957491 | AF2-043 C | Adder | 3.26 MW | 2.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957601 | AF2-054 C | Adder | 2.18 MW | 1.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957631 | AF2-057 | 80/20 | 5.51 MW | 5.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941501 | AE2-147 C | Adder | 24.1 MW | 20.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 941591 | AE2-156 O1 | 80/20 | 27.57 MW | 27.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942001 | AE2-212 C | Adder | 2.58 MW | 2.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957831 | AF2-077 C | Adder | 2.59 MW | 2.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957871 | AF2-081 C | 80/20 | 15.38 MW | 15.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957911 | AF2-085 | 80/20 | 5.84 MW | 5.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 958161 | AF2-110 C | Adder | 2.06 MW | 1.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923911 | AB2-031 C O1 | Adder | 3.13 MW | 2.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 924501 | AB2-099 C | Adder | 0.84 MW | 0.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925781 | AC1-054 C O1 | Adder | 9.5 MW | 8.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926071 | AC1-086 C | Adder | 29.0 MW | 24.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926271 | AC1-105 C O1 | Adder | 6.93 MW | 5.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927021 | AC1-189 C | Adder | 11.8 MW | 10.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 927141 | AC1-208 C | Adder | 12.47 MW | 10.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934611 | AD1-087 C O1 | Adder | 11.02 MW | 9.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936261 | AD2-033 C | Adder | 15.56 MW | 13.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939181 | AE1-148 C O1 | Adder | 11.18 MW | 9.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940241 | AE2-006 | Adder | 0.58 MW | 0.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923572 | AB1-173 C OP | Adder | 3.15 MW | 2.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923582 | AB1-173AC OP | Adder | 3.15 MW | 2.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925611 | AC1-036 C | Adder | 1.13 MW | 0.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 960331 | AF2-324 C O1 | Adder | 10.42 MW | 8.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 314947 | 8GREENSVILLE | 80/20 | 85.97 MW | 85.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 923831 | AB2-022 C | Adder | 3.52 MW | 3.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925051 | AB2-160 C O1 | Adder | 6.56 MW | 5.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925061 | AB2-161 C O1 | Adder | 4.64 MW | 3.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925331 | AB2-190 C | Adder | 23.78 MW | 20.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 926751 | AC1-161 C O1 | 80/20 | 48.52 MW | 48.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932041 | AC2-012 C | 80/20 | 12.35 MW | 12.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933291 | AC2-141 C | 80/20 | 48.52 MW | 48.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934011 | AD1-025 C | Adder | 21.52 MW | 18.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934571 | AD1-082 C | Adder | 10.57 MW | 8.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 934621 | AD1-088 C | Adder | 14.52 MW | 12.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 935161 | AD1-151 C O1 | Adder | 20.08 MW | 17.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938531 | AE1-072 C O1 | 80/20 | 27.02 MW | 27.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938771 | AE1-103 C O1 | Adder | 4.28 MW | 3.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939191 | AE1-149 C O1 | Adder | 14.12 MW | 12.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939311 | AE1-162 C | Adder | 3.09 MW | 2.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 939411 | AE1-173 C | 80/20 | 147.97 MW | 147.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940541 | AE2-040 O1 | Adder | 3.97 MW | 3.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 942551 | AE2-270 | Adder | 34.26 MW | 29.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 957711 | AF2-065 C | Adder | 17.32 MW | 14.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 925861 | AC1-065 C | Adder | 3.48 MW | 2.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 936301 | AD2-039 C | Adder | 1.39 MW | 1.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 938031 | AE1-004 C | Adder | 1.39 MW | 1.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 932831 | AC2-110 C | Adder | 1.39 MW | 1.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 940551 | AE2-041 O1 | Adder | 7.32 MW | 6.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 918561 | AA1-072 C | Adder | 0.5 MW | 0.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944581 | AF1-123 C O1 | 80/20 | 75.07 MW | 75.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944591 | AF1-124 C O1 | 80/20 | 75.07 MW | 75.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 944601 | AF1-125 C O1 | 80/20 | 75.07 MW | 75.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | 933981 | AD1-022 C | Adder | 12.83 MW | 10.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.03 MW | 1.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.98 MW | 1.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 11.36 MW | 11.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 43.18 MW | 43.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.42 MW | 2.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 9.23 MW | 9.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 77.72 MW | 77.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 51.24 MW | 51.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.67 MW | 2.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.38 MW | 6.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 7.74 MW | 7.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 38.34 MW | 38.34 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315131 | 1EDGECMA | Adder | 9.99 MW | 8.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315132 | 1EDGECMB | Adder | 9.99 MW | 8.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926201 | AC1-098 C | Adder | 7.96 MW | 6.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926211 | AC1-099 C | Adder | 2.67 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927251 | AC1-221 C | Adder | 2.62 MW | 2.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927261 | AC1-222 C | Adder | 4.19 MW | 3.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934311 | AD1-055 C | Adder | 2.91 MW | 2.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934331 | AD1-057 C O1 | Adder | 12.58 MW | 10.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934341 | AD1-058 C | Adder | 6.58 MW | 5.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 73.85 MW | 62.78 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934991 | AD1-131 C | Adder | 2.16 MW | 1.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935171 | AD1-152 C O1 | Adder | 10.71 MW | 9.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937481 | AD2-202 C O1 | Adder | 3.06 MW | 2.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942461 | AE2-259 C O1 | Adder | 10.55 MW | 8.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942931 | AE2-313 C | 80/20 | 55.36 MW | 55.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 1.87 MW | 1.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943901 | AF1-058 C | Adder | 2.31 MW | 1.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | 80/20 | 20.08 MW | 20.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944141 | AF1-082 | Adder | 3.59 MW | 3.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945811 | AF1-246 C O1 | 80/20 | 10.73 MW | 10.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958801 | AF2-171 C | Adder | 16.42 MW | 13.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 959311 | AF2-222 C | Adder | 18.66 MW | 15.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960061 | AF2-297 C | Adder | 9.24 MW | 7.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960081 | AF2-299 C | Adder | 3.28 MW | 2.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 14.61 MW | 12.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 922922 | AB1-081 C OP | Adder | 11.18 MW | 9.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923262 | AB1-132 C OP | Adder | 18.3 MW | 15.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923991 | AB2-040 C O1 | Adder | 9.56 MW | 8.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924301 | AB2-077 C O1 | Adder | 2.32 MW | 1.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924311 | AB2-078 C O1 | Adder | 2.32 MW | 1.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924321 | AB2-079 C O1 | Adder | 2.32 MW | 1.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925591 | AC1-034 C | Adder | 8.53 MW | 7.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932631 | AC2-084 C | Adder | 11.35 MW | 9.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932761 | AC2-100 C | Adder | 6.04 MW | 5.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938371 | AE1-056 C | Adder | 7.01 MW | 5.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 9.86 MW | 8.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940571 | AE2-044 C | Adder | 5.59 MW | 4.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940661 | AE2-053 O1 | Adder | 3.89 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | 80/20 | 61.46 MW | 61.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941791 | AE2-182 C | Adder | 2.25 MW | 1.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946281 | AF1-292 C | Adder | 1.96 MW | 1.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946301 | AF1-294 C | Adder | 4.48 MW | 3.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957481 | AF2-042 C | 80/20 | 76.63 MW | 76.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 22.41 MW | 19.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 23.42 MW | 19.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957861 | AF2-080 C | Adder | 9.99 MW | 8.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958211 | AF2-115 C | Adder | 2.73 MW | 2.32 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940481 | AE2-033 C | Adder | 20.73 MW | 17.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | 80/20 | 27.07 MW | 27.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946011 | AF1-266 | Adder | 17.36 MW | 14.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933501 | AC2-165 C | Adder | 11.64 MW | 9.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.49 MW | 0.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.49 MW | 0.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315065 | 1CHESTF6 | Adder | 120.72 MW | 102.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315074 | 1HOPCGN1 | Adder | 8.22 MW | 6.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315075 | 1HOPCGN2 | Adder | 8.11 MW | 6.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315083 | 1SPRUNCA | Adder | 10.92 MW | 9.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315084 | 1SPRUNCB | Adder | 10.92 MW | 9.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 3.18 MW | 3.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | Adder | 2.35 MW | 1.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 4.56 MW | 3.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 8.29 MW | 8.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942161 | AE2-228 C | Adder | 2.18 MW | 1.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 1.98 MW | 1.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942371 | AE2-250 C O1 | Adder | 10.38 MW | 8.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 8.72 MW | 8.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 1.79 MW | 1.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | Adder | 2.44 MW | 2.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | Adder | 2.89 MW | 2.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | Adder | 7.38 MW | 6.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | Adder | 17.17 MW | 14.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958501 | AF2-144 C | Adder | 2.24 MW | 1.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.65 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 1.08 MW | 1.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315102 | 1BRUNSWICKG1 | 80/20 | 13.38 MW | 13.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315103 | 1BRUNSWICKG2 | 80/20 | 13.38 MW | 13.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315104 | 1BRUNSWICKG3 | 80/20 | 13.38 MW | 13.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315105 | 1BRUNSWICKS1 | 80/20 | 27.8 MW | 27.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 4.8 MW | 4.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 4.72 MW | 4.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 4.86 MW | 4.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 37.37 MW | 37.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.52 MW | 0.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.67 MW | 0.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.56 MW | 0.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 3.67 MW | 3.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | Adder | 5.93 MW | 5.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 7.61 MW | 6.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 3.01 MW | 2.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938551 | AE1-074 C | Adder | 2.95 MW | 2.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938561 | AE1-075 C | Adder | 2.64 MW | 2.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | Adder | 2.44 MW | 2.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940431 | AE2-027 C O1 | Adder | 12.76 MW | 10.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940651 | AE2-052 | Adder | 4.25 MW | 3.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | Adder | 4.62 MW | 3.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 40.23 MW | 40.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 41.34 MW | 41.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 37.61 MW | 37.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 946261 | AF1-291 C | Adder | 2.18 MW | 1.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | Adder | 2.99 MW | 2.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 5.04 MW | 5.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | Adder | 22.13 MW | 18.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 25.24 MW | 25.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942001 | AE2-212 C | Adder | 2.32 MW | 1.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957831 | AF2-077 C | Adder | 2.15 MW | 1.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 14.12 MW | 14.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957911 | AF2-085 | 80/20 | 5.58 MW | 5.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | Adder | 1.88 MW | 1.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923911 | AB2-031 C O1 | Adder | 2.91 MW | 2.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.78 MW | 0.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925781 | AC1-054 C O1 | Adder | 8.9 MW | 7.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926071 | AC1-086 C | Adder | 26.95 MW | 22.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926271 | AC1-105 C O1 | Adder | 6.56 MW | 5.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927021 | AC1-189 C | Adder | 11.0 MW | 9.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 927141 | AC1-208 C | Adder | 11.61 MW | 9.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934611 | AD1-087 C O1 | Adder | 10.46 MW | 8.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936261 | AD2-033 C | Adder | 14.7 MW | 12.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939181 | AE1-148 C O1 | Adder | 10.51 MW | 8.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940241 | AE2-006 | Adder | 0.54 MW | 0.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923572 | AB1-173 C OP | Adder | 2.93 MW | 2.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923582 | AB1-173AC OP | Adder | 2.93 MW | 2.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925611 | AC1-036 C | Adder | 1.07 MW | 0.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 960331 | AF2-324 C O1 | Adder | 9.75 MW | 8.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314947 | 8GREENSVILLE | 80/20 | 81.56 MW | 81.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | Adder | 3.24 MW | 2.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925051 | AB2-160 C O1 | Adder | 5.84 MW | 4.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925061 | AB2-161 C O1 | Adder | 4.21 MW | 3.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 925331 | AB2-190 C | Adder | 20.84 MW | 17.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 44.7 MW | 44.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 11.31 MW | 11.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 44.7 MW | 44.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934011 | AD1-025 C | Adder | 18.9 MW | 16.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934571 | AD1-082 C | Adder | 9.59 MW | 8.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934621 | AD1-088 C | Adder | 13.82 MW | 11.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935161 | AD1-151 C O1 | Adder | 17.55 MW | 14.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 24.8 MW | 24.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 3.94 MW | 3.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939191 | AE1-149 C O1 | Adder | 12.75 MW | 10.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | Adder | 2.78 MW | 2.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | 80/20 | 138.83 MW | 138.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940541 | AE2-040 O1 | Adder | 3.68 MW | 3.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942551 | AE2-270 | Adder | 30.09 MW | 25.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957711 | AF2-065 C | Adder | 15.19 MW | 12.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.46 MW | 0.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 68.99 MW | 68.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 68.99 MW | 68.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 68.99 MW | 68.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 11.85 MW | 10.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.01 MW | 1.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.94 MW | 1.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.75 MW | 10.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 41.7 MW | 41.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.29 MW | 2.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.88 MW | 8.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 73.84 MW | 73.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 49.37 MW | 49.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.52 MW | 2.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.21 MW | 6.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 7.33 MW | 7.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 37.6 MW | 37.6 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 313853 | 3PONTONDP | 80/20 | 0.12 MW | 0.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314429 | 3JTRSVLE | 80/20 | 0.47 MW | 0.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315131 | 1EDGECMA | Adder | 9.24 MW | 7.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315132 | 1EDGECMB | Adder | 9.24 MW | 7.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315153 | 1CLOVER1 | 80/20 | 18.08 MW | 18.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315154 | 1CLOVER2 | 80/20 | 17.9 MW | 17.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926201 | AC1-098 C | Adder | 7.3 MW | 6.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926211 | AC1-099 C | Adder | 2.45 MW | 2.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 927251 | AC1-221 C | Adder | 2.52 MW | 2.14 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 927261 | AC1-222 C | Adder | 4.15 MW | 3.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934311 | AD1-055 C | Adder | 2.88 MW | 2.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934331 | AD1-057 C O1 | Adder | 11.64 MW | 9.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934341 | AD1-058 C | Adder | 6.31 MW | 5.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934521 | AD1-076 C | Adder | 64.9 MW | 55.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934991 | AD1-131 C | Adder | 2.07 MW | 1.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 935171 | AD1-152 C O1 | 80/20 | 10.52 MW | 10.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 937481 | AD2-202 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942461 | AE2-259 C O1 | 80/20 | 13.28 MW | 13.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942931 | AE2-313 C | 80/20 | 51.52 MW | 51.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 943171 | AE2-346 C | Adder | 1.68 MW | 1.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 943901 | AF1-058 C | Adder | 2.28 MW | 1.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944011 | AF1-069 C | 80/20 | 18.63 MW | 18.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944141 | AF1-082 | Adder | 3.32 MW | 2.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 945811 | AF1-246 C O1 | 80/20 | 10.36 MW | 10.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 958801 | AF2-171 C | 80/20 | 19.18 MW | 19.18 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 959311 | AF2-222 C | Adder | 20.81 MW | 17.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 960061 | AF2-297 C | Adder | 9.14 MW | 7.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 960081 | AF2-299 C | Adder | 3.12 MW | 2.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 960111 | AF2-302 C | Adder | 1.9 MW | 1.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315294 | 1DOMTR10 | Adder | 12.92 MW | 10.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 922922 | AB1-081 C OP | Adder | 10.34 MW | 8.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923262 | AB1-132 C OP | Adder | 16.94 MW | 14.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923991 | AB2-040 C O1 | Adder | 9.0 MW | 7.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 924301 | AB2-077 C O1 | Adder | 2.39 MW | 2.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 924311 | AB2-078 C O1 | Adder | 2.39 MW | 2.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 924321 | AB2-079 C O1 | Adder | 2.39 MW | 2.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925591 | AC1-034 C | Adder | 7.9 MW | 6.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 932631 | AC2-084 C | Adder | 10.41 MW | 8.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 932761 | AC2-100 C | Adder | 5.79 MW | 4.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938371 | AE1-056 C | 80/20 | 8.36 MW | 8.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940491 | AE2-034 C | Adder | 8.59 MW | 7.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940571 | AE2-044 C | Adder | 5.17 MW | 4.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940661 | AE2-053 O1 | Adder | 3.9 MW | 3.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941031 | AE2-094 C | 80/20 | 57.02 MW | 57.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941791 | AE2-182 C | 80/20 | 2.67 MW | 2.67 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946281 | AF1-292 C | Adder | 1.86 MW | 1.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946291 | AF1-293 C O1 | Adder | 19.35 MW | 16.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946301 | AF1-294 C | 80/20 | 5.25 MW | 5.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946591 | AF1-323 C | Adder | 5.23 MW | 4.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957481 | AF2-042 C | 80/20 | 74.02 MW | 74.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957521 | AF2-046 C | Adder | 20.15 MW | 17.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957531 | AF2-047 C | Adder | 20.41 MW | 17.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957861 | AF2-080 C | Adder | 9.11 MW | 7.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 958211 | AF2-115 C | 80/20 | 3.2 MW | 3.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940481 | AE2-033 C | 80/20 | 19.62 MW | 19.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940641 | AE2-051 C O1 | 80/20 | 24.52 MW | 24.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946011 | AF1-266 | 80/20 | 16.42 MW | 16.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 933501 | AC2-165 C | 80/20 | 14.94 MW | 14.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314295 | 6BIRDNECK | 80/20 | 0.06 MW | 0.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314333 | 6POWHATN | 80/20 | 0.65 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314435 | 6SAPONY | 80/20 | 0.53 MW | 0.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314491 | 3PENDLTN | 80/20 | 0.41 MW | 0.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314677 | 6BUCKING | 80/20 | 0.54 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315060 | 1CHESTF5 | Adder | 53.2 MW | 45.22 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315065 | 1CHESTF6 | Adder | 121.88 MW | 103.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315074 | 1HOPCGN1 | Adder | 8.14 MW | 6.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315075 | 1HOPCGN2 | Adder | 8.03 MW | 6.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315083 | 1SPRUNCA | Adder | 11.56 MW | 9.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315084 | 1SPRUNCB | Adder | 11.56 MW | 9.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926661 | AC1-147 C | Adder | 2.68 MW | 2.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934061 | AD1-033 C | 80/20 | 8.98 MW | 8.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 935111 | AD1-144 C | Adder | 2.0 MW | 1.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 936661 | AD2-085 C | Adder | 4.03 MW | 3.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 937221 | AD2-160 C O1 | 80/20 | 6.99 MW | 6.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942151 | AE2-227 C | Adder | 1.95 MW | 1.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942161 | AE2-228 C | Adder | 2.2 MW | 1.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942341 | AE2-247 C | Adder | 1.75 MW | 1.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942371 | AE2-250 C O1 | Adder | 10.28 MW | 8.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942401 | AE2-253 C | 80/20 | 7.35 MW | 7.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 943461 | AF1-017 C | Adder | 1.58 MW | 1.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 943611 | AF1-032 C | Adder | 2.08 MW | 1.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 943621 | AF1-033 C | Adder | 2.54 MW | 2.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944631 | AF1-128 O1 | Adder | 41.4 MW | 35.19 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944871 | AF1-152 C | Adder | 6.3 MW | 5.36 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 945361 | AF1-201 C O1 | Adder | 15.03 MW | 12.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 958501 | AF2-144 C | 80/20 | 2.75 MW | 2.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315102 | 1BRUNSWICKG1 | 80/20 | 12.46 MW | 12.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315103 | 1BRUNSWICKG2 | 80/20 | 12.46 MW | 12.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315104 | 1BRUNSWICKG3 | 80/20 | 12.46 MW | 12.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315105 | 1BRUNSWICKS1 | 80/20 | 25.88 MW | 25.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315108 | 1ELIZAR1 | 80/20 | 4.04 MW | 4.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315109 | 1ELIZAR2 | 80/20 | 3.98 MW | 3.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315110 | 1ELIZAR3 | 80/20 | 4.1 MW | 4.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315191 | 1BEARGRDN G1 | 80/20 | 6.17 MW | 6.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315192 | 1BEARGRDN G2 | 80/20 | 6.17 MW | 6.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315193 | 1BEARGRDN S1 | 80/20 | 12.69 MW | 12.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315603 | 6AA1-139SOLA | 80/20 | 3.1 MW | 3.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 315611 | 6Z1-036WIND | Adder | 5.1 MW | 4.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 932591 | AC2-079 C O1 | Adder | 6.72 MW | 5.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938221 | AE1-035 C | Adder | 2.68 MW | 2.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938551 | AE1-074 C | 80/20 | 3.15 MW | 3.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938561 | AE1-075 C | 80/20 | 3.23 MW | 3.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 939431 | AE1-175 C | Adder | 2.2 MW | 1.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940431 | AE2-027 C O1 | Adder | 12.91 MW | 10.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940651 | AE2-052 | Adder | 4.03 MW | 3.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941101 | AE2-104 C O1 | Adder | 3.98 MW | 3.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941281 | AE2-122 C O1 | 80/20 | 33.89 MW | 33.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941291 | AE2-123 C O1 | 80/20 | 34.83 MW | 34.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941301 | AE2-124 C O1 | 80/20 | 31.68 MW | 31.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 946261 | AF1-291 C | Adder | 2.19 MW | 1.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957491 | AF2-043 C | Adder | 2.54 MW | 2.16 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957631 | AF2-057 | Adder | 4.25 MW | 3.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941501 | AE2-147 C | Adder | 18.91 MW | 16.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 941591 | AE2-156 O1 | 80/20 | 21.28 MW | 21.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942001 | AE2-212 C | Adder | 2.3 MW | 1.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957831 | AF2-077 C | Adder | 1.92 MW | 1.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957871 | AF2-081 C | 80/20 | 11.92 MW | 11.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957911 | AF2-085 | 80/20 | 5.91 MW | 5.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 958161 | AF2-110 C | Adder | 1.62 MW | 1.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923911 | AB2-031 C O1 | Adder | 2.74 MW | 2.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 924501 | AB2-099 C | Adder | 0.7 MW | 0.6 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925781 | AC1-054 C O1 | Adder | 8.69 MW | 7.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926071 | AC1-086 C | Adder | 24.94 MW | 21.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926271 | AC1-105 C O1 | Adder | 6.55 MW | 5.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 927021 | AC1-189 C | Adder | 10.03 MW | 8.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 927141 | AC1-208 C | Adder | 10.72 MW | 9.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934611 | AD1-087 C O1 | 80/20 | 10.3 MW | 10.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 936261 | AD2-033 C | Adder | 16.06 MW | 13.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938821 | AE1-108 C | Adder | 15.34 MW | 13.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 939181 | AE1-148 C O1 | Adder | 10.52 MW | 8.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940241 | AE2-006 | Adder | 0.6 MW | 0.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923572 | AB1-173 C OP | Adder | 2.76 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923582 | AB1-173AC OP | Adder | 2.76 MW | 2.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925611 | AC1-036 C | Adder | 1.18 MW | 1.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 960331 | AF2-324 C O1 | Adder | 9.01 MW | 7.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 314947 | 8GREENSVILLE | 80/20 | 75.84 MW | 75.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 923831 | AB2-022 C | Adder | 2.75 MW | 2.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925051 | AB2-160 C O1 | Adder | 5.79 MW | 4.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925061 | AB2-161 C O1 | Adder | 3.87 MW | 3.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925331 | AB2-190 C | Adder | 19.41 MW | 16.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 925831 | AC1-062 | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 926751 | AC1-161 C O1 | 80/20 | 36.28 MW | 36.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 932041 | AC2-012 C | Adder | 9.53 MW | 8.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 933291 | AC2-141 C | 80/20 | 36.28 MW | 36.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934011 | AD1-025 C | Adder | 17.5 MW | 14.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934571 | AD1-082 C | Adder | 8.83 MW | 7.5 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 934621 | AD1-088 C | 80/20 | 16.46 MW | 16.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 935161 | AD1-151 C O1 | Adder | 16.5 MW | 14.03 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938531 | AE1-072 C O1 | Adder | 20.96 MW | 17.82 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 938771 | AE1-103 C O1 | Adder | 3.47 MW | 2.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 939191 | AE1-149 C O1 | Adder | 12.08 MW | 10.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 939311 | AE1-162 C | Adder | 2.41 MW | 2.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 939411 | AE1-173 C | 80/20 | 123.79 MW | 123.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 940541 | AE2-040 O1 | 80/20 | 3.48 MW | 3.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 942551 | AE2-270 | Adder | 27.86 MW | 23.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 957711 | AF2-065 C | Adder | 14.14 MW | 12.02 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 920291 | AA2-127 | 80/20 | 1.28 MW | 1.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 918561 | AA1-072 C | Adder | 0.42 MW | 0.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944581 | AF1-123 C O1 | 80/20 | 57.72 MW | 57.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944591 | AF1-124 C O1 | 80/20 | 57.72 MW | 57.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 944601 | AF1-125 C O1 | 80/20 | 57.72 MW | 57.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | 933981 | AD1-022 C | Adder | 10.46 MW | 8.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.94 MW | 0.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.81 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 10.1 MW | 10.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 39.07 MW | 39.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.15 MW | 2.15 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.33 MW | 8.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 69.38 MW | 69.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 46.3 MW | 46.3 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.37 MW | 2.37 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.8 MW | 5.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.88 MW | 6.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 35.08 MW | 35.08 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 0.18 MW | 0.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.59 MW | 0.59 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.28 MW | 0.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.66 MW | 0.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.31 MW | 2.31 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 9.05 MW | 9.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 9.05 MW | 9.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.38 MW | 4.38 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.05 MW | 2.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.68 MW | 6.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.14 MW | 8.14 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.73 MW | 2.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.47 MW | 15.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | Adder | 42.84 MW | 36.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.72 MW | 1.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 959311 | AF2-222 C | Adder | 10.56 MW | 8.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.51 MW | 6.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | Adder | 9.11 MW | 7.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.41 MW | 29.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.07 MW | 16.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.63 MW | 7.63 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.61 MW | 11.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | Adder | 4.36 MW | 3.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 5.0 MW | 5.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.04 MW | 3.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.88 MW | 3.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.88 MW | 18.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | Adder | 10.36 MW | 8.8 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.25 MW | 8.25 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.97 MW | 63.97 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.55 MW | 53.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.68 MW | 6.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.09 MW | 2.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.09 MW | 1.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.76 MW | 2.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.3 MW | 0.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.56 MW | 1.56 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.11 MW | 0.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923911 | AB2-031 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924021 | AB2-043 C O1 | 80/20 | 0.46 MW | 0.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 2.05 MW | 2.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 8.26 MW | 8.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 43.3 MW | 43.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 9.09 MW | 9.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 12.44 MW | 12.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936261 | AD2-033 C | Adder | 8.98 MW | 7.63 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C O1 | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940241 | AE2-006 | Adder | 0.32 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923572 | AB1-173 C OP | 80/20 | 4.93 MW | 4.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923582 | AB1-173AC OP | 80/20 | 4.93 MW | 4.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925611 | AC1-036 C | Adder | 0.62 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.83 MW | 8.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924511 | AB2-100 C | 80/20 | 6.22 MW | 6.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925171 | AB2-174 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.9 MW | 7.9 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.92 MW | 1.92 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.54 MW | 12.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.71 MW | 22.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.64 MW | 14.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.91 MW | 1.91 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.49 MW | 2.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.04 MW | 12.04 MW |
Light Load Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 99.8 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3121 | PJM Baseline Upgrade b3121: Rebuild Clubhouse-Lakeview 230 kV Line #254. | $0 | |
| n6138 | Rebuild 13.7 miles of 230 kV Line 246 from Earleys to Nucor Tap with 2-636 ACSR. | $20,550,000 | |
| n6314 | Rebuild 10.28 miles of 230 kV Line 2021 from Elizabeth City to Shawboro with 2-636 ACSR. | $15,420,000 | |
| n8149 | Add Additional 500/230 kV Transformer at Elmont Substation | $22,000,000 | |
| (TBD) | Rebuild aging double circuit 230kV towers of Everets to Greenvile Line | $19,000,000 | |
| (TBD) | Reconductor one side of Everets to Greenvile 230 kV Line. | $350,000 | |
| n6144 | Rebuild 20.5 miles of 230 kV Line #218 from Everetts to Greenville with 2-636 ACSR | $39,923,299 | |
| n6438 | Rebuild 4.65 miles of 230 kV Line 2131 from Perquimans to South Hertford with 2-636 ACSR. | $6,975,000 | |
| n6452 | Rebuild 2.47 miles of 230 kV Line 238 from AE2-033 TAP to Sapony with 2-795 150C ACSR. | $3,705,000 | |
| b3057 | PJM Baseline Upgrade b3057: Rebuild Waller-Skiff's Creek 230 kV Line#2154. | $0 | |
| n6849 | Rebuild 30.6 miles of 230 kV Line 246 from Nuco TP to Suffolk with 2-636 ACSR. | $45,900,000 | |
| n6439 | Rebuild 3.3 miles of 230 kV Line 2131 from South Hertford to Winfall with 2-636 ACSR. | $4,950,000 | |
| n6172 | Rebuild 37.41 miles of 500 kV Line 563 from Carson to Midlothian with 3-1351.5 125C ACSR. | $115,971,000 | |
| b3692 | Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy. | $0 | |
| n6324 | Replace Terminal Equipment at Surry and Chickahominy Substations | $4,000,000 | |
| n6055 | Replace Wave traps at Midlothian and North Anna 500kV substations | $300,000 | |
| n5609 | Rebuild 41.13 miles of 500 kV Line 576 from Midlothian to North Anna with 3-1351.5 125C ACSR. | $127,503,000 | |
| n8113 | Reinforcement for Contingency Removal : DVP_P7-1: LN 25-2034-A | $4,737,743 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-047 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.