AF2-046 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:07
Tunis-Mapleton 115 kV
99.8 MW Capacity / 150.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF2-046 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Hertford County, North Carolina. The installed facilities will have a total capability of 150.0 MW with 99.8 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF2-046 |
| Project Name | Tunis-Mapleton 115 kV |
| Developer Name | Murphy Solar, LLC |
| State | North Carolina |
| County | Hertford |
| Transmission Owner | Dominion |
| MFO | 150.0 MW |
| MWE | 150.0 MW |
| MWC | 99.8 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2023 |
Point of Interconnection
AF2-046 will interconnect with the Dominion on transmission system tapping the line between Mapleton DP 115 kV substation and Tunis 115 kV substation. The IC is responsible for securing right-of-way, permits and constructing the proposed attachment line from the solar facility site to the proposed new substation. Attachment 1 shows a one-line diagram of the proposed interconnection facilities. The IC may not install any facilities on Dominion’s right-of-way without first obtaining the necessary approval from Dominion Energy.
Summer Peak Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 99.8 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CPLE/DVP |
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
314554 to 304223 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 217.04 % | 223.37 % | 164.0 | B | 366.33 | 12.53 | |
| CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 106.18 % | 109.93 % | 478.0 | B | 525.47 | 18.76 | |
| DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 151.16 % | 152.51 % | 684.0 | C | 1043.17 | 10.62 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 148.32 % | 149.67 % | 684.0 | C | 1023.74 | 10.62 | |
| DVP |
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
314638 to 314647 ckt 1 |
DVP_P4-2: 246T247
CONTINGENCY 'DVP_P4-2: 246T247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Breaker | AC | 124.88 % | 127.36 % | 699.0 | C | 890.25 | 17.0 | |
| DVP |
6LOCKS-6HARR205 230.0 kV Ckt 1 line
314316 to 314301 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 119.26 % | 120.64 % | 541.0 | C | 652.66 | 8.73 | |
| DVP |
3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer
314568 to 314569 ckt 2 |
DVP_P4-2: 201262
CONTINGENCY 'DVP_P4-2: 201262' OPEN BRANCH FROM BUS 314266 TO BUS 314569 CKT 1 /*6NORTHAMPTON 230.0 - 6EARLEYS 230.0 OPEN BRANCH FROM BUS 314266 TO BUS 314599 CKT 1 /*6NORTHAMPTON 230.0 - 6ROA VAL 230.0 OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 1 /*3EARLEYS 115.0 - 6EARLEYS 230.0 OPEN BUS 314266 /*6NORTHAMPTON 230.0 END |
Breaker | AC | 97.47 % | 122.43 % | 208.0 | C | 254.65 | 51.93 | |
| DVP |
3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer
314568 to 314569 ckt 2 |
DVP_P4-2: WT2171
CONTINGENCY 'DVP_P4-2: WT2171' OPEN BRANCH FROM BUS 313709 TO BUS 313710 CKT 1 /*6HOLLOMAN 230.0 - 1HOLLOMAN 34.5 OPEN BRANCH FROM BUS 313709 TO BUS 313710 CKT 2 /*6HOLLOMAN 230.0 - 1HOLLOMAN 34.5 OPEN BRANCH FROM BUS 313709 TO BUS 314569 CKT Z1 /*6HOLLOMAN 230.0 - 6EARLEYS 230.0 OPEN BRANCH FROM BUS 313710 TO BUS 315602 CKT 1 /*1HOLLOMAN 34.5 - 1HOLLOMANSOL 0.7 OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 1 /*3EARLEYS 115.0 - 6EARLEYS 230.0 OPEN BUS 313709 /*6HOLLOMAN 230.0 OPEN BUS 313710 /*1HOLLOMAN 34.5 OPEN BUS 315602 /*1HOLLOMANSOL 0.7 OPEN BUS 918512 /*AA1-065 E OP 0.7 END |
Breaker | AC | 75.72 % | 100.78 % | 208.0 | C | 209.62 | 52.6 | |
| DVP |
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
314924 to 314903 ckt 1 |
DVP_P4-2: 563T576
CONTINGENCY 'DVP_P4-2: 563T576' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 END |
Breaker | AC | 110.77 % | 110.94 % | 3144.0 | C | 3487.95 | 33.26 | |
| DVP |
6HARR205-6TYLER 230.0 kV Ckt 1 line
314301 to 314346 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 114.94 % | 116.32 % | 541.0 | C | 629.29 | 8.73 | |
| DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 113.09 % | 114.56 % | 541.0 | C | 619.77 | 9.26 | |
| DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 101.64 % | 104.18 % | 541.0 | C | 563.61 | 16.26 | |
| DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 113.06 % | 114.52 % | 541.0 | C | 619.55 | 9.26 | |
| DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 101.61 % | 104.16 % | 541.0 | C | 563.51 | 16.26 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 94.14 % | 101.92 % | 288.6 | C | 294.14 | 24.05 | |
| DVP |
6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line
314209 to 314386 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 121.79 % | 122.13 % | 441.8 | B | 539.57 | 5.59 | |
| DVP |
6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line
314386 to 314296 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 114.1 % | 114.43 % | 441.8 | B | 505.55 | 5.59 | |
| DVP |
6PENNIMAN-6WALR209 230.0 kV Ckt 1 line
314296 to 314415 ckt 1 |
DVP_P1-2: LN 567
CONTINGENCY 'DVP_P1-2: LN 567' OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1 /*8CHCKAHM 500.0 - 8SURRY 500.0 END |
Single | AC | 110.47 % | 110.81 % | 441.8 | B | 489.56 | 5.59 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 125.89 % | 129.76 % | 375.06 | B | 486.68 | 14.43 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
314572 3EMPORIA 115 925170 AB2-174 TAP 115 1
CONTINGENCY '314572 3EMPORIA 115 925170 AB2-174 TAP 115 1' OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 END |
Single | AC | 121.62 % | 125.43 % | 375.06 | B | 470.44 | 14.25 | |
| DVP |
AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line
924510 to 314563 ckt 1 |
Base Case | Single | AC | 104.08 % | 107.01 % | 375.06 | A | 401.35 | 11.0 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 105.69 % | 109.22 % | 571.52 | B | 624.21 | 20.41 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 105.6 % | 109.14 % | 571.52 | B | 623.76 | 20.41 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 END |
Single | AC | 98.02 % | 101.66 % | 571.52 | B | 581.01 | 20.56 | |
| DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 97.88 % | 101.52 % | 571.52 | B | 580.21 | 20.56 | |
| DVP |
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
314287 to 314276 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 119.61 % | 120.47 % | 663.64 | B | 799.49 | 6.67 | |
| DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 99.23 % | 102.76 % | 571.52 | B | 587.29 | 20.41 | |
| DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 99.15 % | 102.67 % | 571.52 | B | 586.78 | 20.41 | |
| DVP |
6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line
314583 to 924510 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Single | AC | 110.11 % | 113.95 % | 375.06 | B | 427.38 | 14.46 | |
| DVP |
6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line
314583 to 924510 ckt 1 |
314572 3EMPORIA 115 925170 AB2-174 TAP 115 1
CONTINGENCY '314572 3EMPORIA 115 925170 AB2-174 TAP 115 1' OPEN BRANCH FROM BUS 314572 TO BUS 925170 CKT 1 /*3EMPORIA 115.0 - AB2-174 TAP 115.0 END |
Single | AC | 105.92 % | 109.7 % | 375.06 | B | 411.44 | 14.28 | |
| DVP |
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
314914 to 314918 ckt 1 |
DVP_P1-2: LN 574
CONTINGENCY 'DVP_P1-2: LN 574' OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT 500.0 - 8LADYSMITH 500.0 END |
Single | AC | 126.85 % | 127.76 % | 2442.12 | B | 3120.05 | 25.48 | |
| DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 127.45 % | 128.72 % | 559.3 | B | 719.93 | 6.98 | |
| DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P1-2: LN 2002
CONTINGENCY 'DVP_P1-2: LN 2002' OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1 /*6CARSON 230.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1 /*3POE 115.0 - 6POE 230.0 END |
Single | AC | 110.98 % | 112.07 % | 559.3 | B | 626.81 | 6.41 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 124.11 % | 125.38 % | 559.3 | B | 701.25 | 6.98 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P1-2: LN 2002
CONTINGENCY 'DVP_P1-2: LN 2002' OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1 /*6CARSON 230.0 - 6POE 230.0 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1 /*3POE 115.0 - 6POE 230.0 END |
Single | AC | 107.68 % | 108.75 % | 559.3 | B | 608.24 | 6.41 | |
| DVP |
6LOCKS-6HARR205 230.0 kV Ckt 1 line
314316 to 314301 ckt 1 |
DVP_P1-2: LN 563
CONTINGENCY 'DVP_P1-2: LN 563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 99.74 % | 101.06 % | 441.8 | B | 446.48 | 5.75 | |
| Details for 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314541 | 3WATKINS | Adder | 0.25 MW | 0.21 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314582 | 3KELFORD | 50/50 | 0.39 MW | 0.39 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314623 | 3WITAKRS | 50/50 | 0.56 MW | 0.56 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315131 | 1EDGECMA | 50/50 | 10.47 MW | 10.47 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315132 | 1EDGECMB | 50/50 | 10.47 MW | 10.47 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315136 | 1ROSEMG1 | 50/50 | 1.6 MW | 1.6 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315137 | 1ROSEMS1 | 50/50 | 0.99 MW | 0.99 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315138 | 1ROSEMG2 | 50/50 | 0.75 MW | 0.75 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315139 | 1GASTONA | 50/50 | 2.06 MW | 2.06 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918492 | AA1-063AE OP | Adder | 2.29 MW | 1.94 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918532 | AA1-067 E | Adder | 0.29 MW | 0.25 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919692 | AA2-053 E OP | Adder | 2.33 MW | 1.98 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919702 | AA2-057 E OP | 50/50 | 7.06 MW | 7.06 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920042 | AA2-088 E OP | Adder | 4.73 MW | 4.02 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920591 | AA2-165 C | 50/50 | 0.3 MW | 0.3 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920592 | AA2-165 E | 50/50 | 1.19 MW | 1.19 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926201 | AC1-098 C | 50/50 | 8.48 MW | 8.48 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926202 | AC1-098 E | 50/50 | 5.05 MW | 5.05 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926211 | AC1-099 C | 50/50 | 2.84 MW | 2.84 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926212 | AC1-099 E | 50/50 | 1.67 MW | 1.67 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934331 | AD1-057 C O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934332 | AD1-057 E O1 | 50/50 | 5.38 MW | 5.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943171 | AE2-346 C | Adder | 0.74 MW | 0.63 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943172 | AE2-346 E | Adder | 0.32 MW | 0.27 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944141 | AF1-082 | 50/50 | 7.38 MW | 7.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960081 | AF2-299 C | Adder | 1.1 MW | 0.94 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960082 | AF2-299 E | Adder | 0.73 MW | 0.62 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 900672 | V4-068 E | Adder | 0.15 MW | 0.12 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917332 | Z2-043 E | 50/50 | 0.98 MW | 0.98 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917342 | Z2-044 E | 50/50 | 1.38 MW | 1.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922922 | AB1-081 C OP | 50/50 | 22.97 MW | 22.97 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922923 | AB1-081 E OP | 50/50 | 9.84 MW | 9.84 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923262 | AB1-132 C OP | 50/50 | 9.07 MW | 9.07 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923263 | AB1-132 E OP | 50/50 | 3.89 MW | 3.89 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923573 | AB1-173 E OP | Adder | 0.55 MW | 0.47 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923991 | AB2-040 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923992 | AB2-040 E O1 | Adder | 3.16 MW | 2.69 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924152 | AB2-059 E OP | 50/50 | 13.95 MW | 13.95 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925591 | AC1-034 C | 50/50 | 17.54 MW | 17.54 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925592 | AC1-034 E | 50/50 | 13.23 MW | 13.23 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932631 | AC2-084 C | 50/50 | 12.1 MW | 12.1 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932632 | AC2-084 E | 50/50 | 5.96 MW | 5.96 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938222 | AE1-035 E | Adder | 0.46 MW | 0.39 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940571 | AE2-044 C | 50/50 | 11.48 MW | 11.48 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940572 | AE2-044 E | 50/50 | 4.92 MW | 4.92 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946281 | AF1-292 C | Adder | 0.66 MW | 0.56 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946282 | AF1-292 E | Adder | 0.44 MW | 0.37 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957521 | AF2-046 C | Adder | 8.33 MW | 7.08 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957522 | AF2-046 E | Adder | 4.19 MW | 3.56 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957861 | AF2-080 C | 50/50 | 5.51 MW | 5.51 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957862 | AF2-080 E | 50/50 | 2.44 MW | 2.44 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315141 | 1GASTONB | 50/50 | 2.06 MW | 2.06 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938221 | AE1-035 C | Adder | 0.94 MW | 0.8 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315612 | 3AA2-057SOLA | 50/50 | 2.57 MW | 2.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917512 | Z2-088 E OP1 | 50/50 | 6.82 MW | 6.82 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920672 | AA2-174 E OP | Adder | 0.27 MW | 0.23 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923911 | AB2-031 C O1 | Adder | 1.18 MW | 1.0 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923912 | AB2-031 E O1 | Adder | 0.58 MW | 0.49 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924151 | AB2-059 C OP | 50/50 | 4.7 MW | 4.7 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924501 | AB2-099 C | Adder | 0.31 MW | 0.26 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924502 | AB2-099 E | Adder | 0.13 MW | 0.11 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924512 | AB2-100 E | Adder | 2.46 MW | 2.09 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925172 | AB2-174 E O1 | Adder | 3.19 MW | 2.71 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926071 | AC1-086 C | 50/50 | 13.35 MW | 13.35 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926072 | AC1-086 E | 50/50 | 6.08 MW | 6.08 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927021 | AC1-189 C | 50/50 | 6.07 MW | 6.07 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927022 | AC1-189 E | 50/50 | 3.02 MW | 3.02 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927141 | AC1-208 C | 50/50 | 13.52 MW | 13.52 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927142 | AC1-208 E | 50/50 | 6.0 MW | 6.0 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923572 | AB1-173 C OP | Adder | 1.19 MW | 1.01 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923582 | AB1-173AC OP | Adder | 1.19 MW | 1.01 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923583 | AB1-173AE OP | Adder | 0.55 MW | 0.47 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960331 | AF2-324 C O1 | 50/50 | 10.22 MW | 10.22 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960332 | AF2-324 E O1 | 50/50 | 5.49 MW | 5.49 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918561 | AA1-072 C | 50/50 | 0.29 MW | 0.29 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918562 | AA1-072 E | 50/50 | 0.14 MW | 0.14 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918512 | AA1-065 E OP | Adder | 1.85 MW | 1.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 0.85 MW | 0.85 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.05 MW | 0.05 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.52 MW | 0.52 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.41 MW | 0.41 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.31 MW | 2.31 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.16 MW | 0.16 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.7 MW | 0.7 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.26 MW | 0.26 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.46 MW | 0.46 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.27 MW | 1.27 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.4 MW | 0.4 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.74 MW | 0.74 MW |
| Details for 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314541 | 3WATKINS | Adder | 0.35 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314582 | 3KELFORD | 50/50 | 0.39 MW | 0.39 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315131 | 1EDGECMA | 50/50 | 8.42 MW | 8.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315132 | 1EDGECMB | 50/50 | 8.42 MW | 8.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315136 | 1ROSEMG1 | 50/50 | 1.71 MW | 1.71 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315137 | 1ROSEMS1 | 50/50 | 1.06 MW | 1.06 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315138 | 1ROSEMG2 | 50/50 | 0.8 MW | 0.8 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918492 | AA1-063AE OP | Adder | 2.41 MW | 2.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918532 | AA1-067 E | 50/50 | 1.6 MW | 1.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919692 | AA2-053 E OP | Adder | 2.48 MW | 2.11 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919702 | AA2-057 E OP | Adder | 1.74 MW | 1.48 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920042 | AA2-088 E OP | Adder | 6.19 MW | 5.26 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920592 | AA2-165 E | Adder | 0.29 MW | 0.25 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926201 | AC1-098 C | Adder | 4.02 MW | 3.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926202 | AC1-098 E | Adder | 2.39 MW | 2.03 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926211 | AC1-099 C | Adder | 1.35 MW | 1.14 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926212 | AC1-099 E | Adder | 0.79 MW | 0.67 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934331 | AD1-057 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934332 | AD1-057 E O1 | 50/50 | 4.77 MW | 4.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934521 | AD1-076 C | 50/50 | 55.08 MW | 55.08 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934522 | AD1-076 E | 50/50 | 28.05 MW | 28.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943171 | AE2-346 C | 50/50 | 1.25 MW | 1.25 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943172 | AE2-346 E | 50/50 | 0.54 MW | 0.54 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944141 | AF1-082 | Adder | 1.36 MW | 1.15 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960081 | AF2-299 C | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960082 | AF2-299 E | Adder | 0.79 MW | 0.67 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315294 | 1DOMTR10 | 50/50 | 13.82 MW | 13.82 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 900672 | V4-068 E | Adder | 0.21 MW | 0.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917332 | Z2-043 E | 50/50 | 0.98 MW | 0.98 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917342 | Z2-044 E | Adder | 0.26 MW | 0.23 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922922 | AB1-081 C OP | Adder | 4.22 MW | 3.59 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922923 | AB1-081 E OP | Adder | 1.81 MW | 1.54 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923262 | AB1-132 C OP | Adder | 10.39 MW | 8.83 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923263 | AB1-132 E OP | Adder | 4.45 MW | 3.78 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923573 | AB1-173 E OP | Adder | 0.56 MW | 0.47 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923991 | AB2-040 C O1 | Adder | 3.88 MW | 3.29 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924152 | AB2-059 E OP | Adder | 2.56 MW | 2.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925121 | AB2-169 C | 50/50 | 1.75 MW | 1.75 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925122 | AB2-169 E | 50/50 | 9.05 MW | 9.05 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925591 | AC1-034 C | Adder | 3.22 MW | 2.74 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925592 | AC1-034 E | Adder | 2.43 MW | 2.07 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932631 | AC2-084 C | Adder | 5.73 MW | 4.87 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932632 | AC2-084 E | Adder | 2.82 MW | 2.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938222 | AE1-035 E | 50/50 | 1.19 MW | 1.19 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940491 | AE2-034 C | 50/50 | 6.21 MW | 6.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940492 | AE2-034 E | 50/50 | 2.66 MW | 2.66 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940571 | AE2-044 C | Adder | 2.11 MW | 1.79 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940572 | AE2-044 E | Adder | 0.9 MW | 0.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946281 | AF1-292 C | Adder | 0.71 MW | 0.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946282 | AF1-292 E | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957521 | AF2-046 C | 50/50 | 12.48 MW | 12.48 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957522 | AF2-046 E | 50/50 | 6.28 MW | 6.28 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957531 | AF2-047 C | 50/50 | 14.76 MW | 14.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957532 | AF2-047 E | 50/50 | 7.42 MW | 7.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957861 | AF2-080 C | 50/50 | 14.16 MW | 14.16 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957862 | AF2-080 E | 50/50 | 6.28 MW | 6.28 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314539 | 3UNCAMP | Adder | 1.16 MW | 0.98 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 916042 | Z1-036 E | Adder | 17.69 MW | 15.03 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940481 | AE2-033 C | Adder | 5.39 MW | 4.58 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940482 | AE2-033 E | Adder | 3.64 MW | 3.09 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946011 | AF1-266 | Adder | 4.51 MW | 3.84 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919152 | AA1-139 E | Adder | 2.13 MW | 1.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 937221 | AD2-160 C O1 | Adder | 1.86 MW | 1.58 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 937222 | AD2-160 E O1 | Adder | 0.97 MW | 0.83 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 942401 | AE2-253 C | Adder | 1.95 MW | 1.66 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 942402 | AE2-253 E | Adder | 0.88 MW | 0.75 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943611 | AF1-032 C | Adder | 0.59 MW | 0.5 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943612 | AF1-032 E | Adder | 0.31 MW | 0.27 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944871 | AF1-152 C | Adder | 2.55 MW | 2.17 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944872 | AF1-152 E | Adder | 1.7 MW | 1.45 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315141 | 1GASTONB | 50/50 | 2.36 MW | 2.36 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315292 | 1DOMTR78 | 50/50 | 1.85 MW | 1.85 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315611 | 6Z1-036WIND | Adder | 2.63 MW | 2.24 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 913392 | Y1-086 E | Adder | 0.91 MW | 0.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923832 | AB2-022 E | Adder | 0.51 MW | 0.43 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923852 | AB2-025 E | Adder | 0.35 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938221 | AE1-035 C | 50/50 | 2.44 MW | 2.44 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941101 | AE2-104 C O1 | Adder | 1.16 MW | 0.99 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941102 | AE2-104 E O1 | Adder | 1.85 MW | 1.57 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957491 | AF2-043 C | Adder | 0.72 MW | 0.61 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957492 | AF2-043 E | Adder | 0.48 MW | 0.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 901082 | W1-029 E | Adder | 15.4 MW | 13.09 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917122 | Z2-027 E | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941501 | AE2-147 C | Adder | 7.66 MW | 6.51 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 941502 | AE2-147 E | Adder | 5.11 MW | 4.34 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957871 | AF2-081 C | Adder | 3.31 MW | 2.82 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957872 | AF2-081 E | Adder | 1.42 MW | 1.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 958161 | AF2-110 C | Adder | 0.47 MW | 0.4 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 958162 | AF2-110 E | Adder | 0.75 MW | 0.64 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314574 | 6EVERETS | 50/50 | 0.65 MW | 0.65 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917512 | Z2-088 E OP1 | 50/50 | 12.96 MW | 12.96 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920672 | AA2-174 E OP | Adder | 0.29 MW | 0.24 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923911 | AB2-031 C O1 | Adder | 1.18 MW | 1.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923912 | AB2-031 E O1 | Adder | 0.58 MW | 0.49 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924501 | AB2-099 C | 50/50 | 0.52 MW | 0.52 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924502 | AB2-099 E | 50/50 | 0.22 MW | 0.22 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924512 | AB2-100 E | Adder | 2.88 MW | 2.45 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925172 | AB2-174 E O1 | Adder | 3.25 MW | 2.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926071 | AC1-086 C | Adder | 15.3 MW | 13.0 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926072 | AC1-086 E | Adder | 6.96 MW | 5.92 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927021 | AC1-189 C | 50/50 | 15.6 MW | 15.6 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927022 | AC1-189 E | 50/50 | 7.77 MW | 7.77 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927141 | AC1-208 C | Adder | 5.2 MW | 4.42 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927142 | AC1-208 E | Adder | 2.31 MW | 1.96 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923572 | AB1-173 C OP | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923582 | AB1-173AC OP | Adder | 1.19 MW | 1.01 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923583 | AB1-173AE OP | Adder | 0.56 MW | 0.47 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960331 | AF2-324 C O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960332 | AF2-324 E O1 | 50/50 | 4.41 MW | 4.41 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315614 | AA2-178 C | 50/50 | 1.44 MW | 1.44 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 907092 | X1-038 E | Adder | 2.89 MW | 2.46 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920692 | AA2-178 E | 50/50 | 3.55 MW | 3.55 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923831 | AB2-022 C | Adder | 0.95 MW | 0.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938531 | AE1-072 C O1 | Adder | 6.1 MW | 5.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938532 | AE1-072 E O1 | Adder | 3.18 MW | 2.7 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938771 | AE1-103 C O1 | Adder | 1.39 MW | 1.18 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938772 | AE1-103 E O1 | Adder | 1.91 MW | 1.63 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940541 | AE2-040 O1 | Adder | 0.89 MW | 0.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918561 | AA1-072 C | 50/50 | 0.29 MW | 0.29 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918562 | AA1-072 E | 50/50 | 0.14 MW | 0.14 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 933981 | AD1-022 C | 50/50 | 9.04 MW | 9.04 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 933982 | AD1-022 E | 50/50 | 4.92 MW | 4.92 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315602 | 1HOLLOMANSOL | 50/50 | 1.7 MW | 1.7 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918512 | AA1-065 E OP | 50/50 | 4.81 MW | 4.81 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.63 MW | 1.63 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.19 MW | 1.19 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 3.17 MW | 3.17 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.46 MW | 4.46 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | LTF | 5.73 MW | 5.73 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.3 MW | 0.3 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.38 MW | 1.38 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.49 MW | 0.49 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 0.86 MW | 0.86 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.34 MW | 1.34 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 2.39 MW | 2.39 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.76 MW | 0.76 MW |
| 6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.46 MW | 1.46 MW |
| Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.23 MW | 0.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.06 MW | 0.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 4.02 MW | 3.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 4.02 MW | 3.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.45 MW | 1.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.68 MW | 0.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.16 MW | 2.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.07 MW | 1.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.08 MW | 1.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.76 MW | 1.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.22 MW | 3.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.3 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.08 MW | 2.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.83 MW | 1.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.03 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.61 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.92 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.92 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.46 MW | 1.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.39 MW | 1.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.01 MW | 0.86 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.74 MW | 4.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.31 MW | 1.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934521 | AD1-076 C | Adder | 17.72 MW | 15.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934522 | AD1-076 E | Adder | 9.02 MW | 7.67 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.76 MW | 0.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.41 MW | 2.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936161 | AD2-022 C O1 | Adder | 3.27 MW | 2.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936162 | AD2-022 E O1 | Adder | 1.96 MW | 1.67 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936171 | AD2-023 C O1 | Adder | 1.91 MW | 1.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936172 | AD2-023 E O1 | Adder | 1.04 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.02 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.48 MW | 0.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.47 MW | 19.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.98 MW | 12.98 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.6 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.81 MW | 0.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.54 MW | 0.46 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.75 MW | 2.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.44 MW | 1.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.65 MW | 3.1 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 5.04 MW | 4.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958801 | AF2-171 C | Adder | 4.9 MW | 4.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958802 | AF2-171 E | Adder | 3.26 MW | 2.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.21 MW | 5.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.16 MW | 3.54 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.23 MW | 2.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.15 MW | 1.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315294 | 1DOMTR10 | Adder | 3.78 MW | 3.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.53 MW | 0.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 4.48 MW | 3.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.92 MW | 1.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.5 MW | 9.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.07 MW | 4.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.22 MW | 5.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.72 MW | 2.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.88 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.16 MW | 1.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.42 MW | 2.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.58 MW | 2.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.39 MW | 3.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.16 MW | 1.84 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.12 MW | 1.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.03 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.24 MW | 1.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.96 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.53 MW | 1.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.68 MW | 21.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.71 MW | 9.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.21 MW | 1.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 26.06 MW | 22.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.38 MW | 14.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 7.06 MW | 6.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.55 MW | 3.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.53 MW | 3.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.56 MW | 1.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.97 MW | 17.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.11 MW | 12.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 15.04 MW | 15.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.81 MW | -2.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.05 MW | -3.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 4.71 MW | 4.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 4.71 MW | 4.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 9.78 MW | 9.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.16 MW | 2.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.7 MW | 3.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.24 MW | 0.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | 50/50 | 0.78 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.25 MW | 1.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | 50/50 | 4.68 MW | 4.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.69 MW | 1.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | 50/50 | 13.99 MW | 13.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | 50/50 | 6.37 MW | 6.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 2.34 MW | 1.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 1.16 MW | 0.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.89 MW | 3.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.94 MW | 1.65 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 4.75 MW | 4.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 2.11 MW | 1.79 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 3.49 MW | 2.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.64 MW | 1.39 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936261 | AD2-033 C | Adder | 5.1 MW | 4.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936262 | AD2-033 E | Adder | 3.4 MW | 2.89 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 4.14 MW | 3.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940241 | AE2-006 | Adder | 0.18 MW | 0.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925611 | AC1-036 C | Adder | 0.36 MW | 0.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.92 MW | 3.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 2.1 MW | 1.79 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314947 | 8GREENSVILLE | 50/50 | 28.73 MW | 28.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.84 MW | 1.84 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925171 | AB2-174 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 36.98 MW | 31.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 24.66 MW | 20.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 3.27 MW | 3.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.16 MW | 0.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.08 MW | 0.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 3.03 MW | 2.57 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.65 MW | 1.4 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.78 MW | 1.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.69 MW | 0.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.82 MW | 3.82 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.69 MW | 14.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.09 MW | 3.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 7.38 MW | 7.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 26.01 MW | 26.01 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 17.24 MW | 17.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.15 MW | 1.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.87 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.21 MW | 2.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.6 MW | 2.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.7 MW | 13.7 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.23 MW | 0.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.06 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 4.02 MW | 3.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 4.02 MW | 3.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.45 MW | 1.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.68 MW | 0.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.16 MW | 2.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.07 MW | 1.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.08 MW | 1.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.76 MW | 1.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.22 MW | 3.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.3 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.08 MW | 2.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.83 MW | 1.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.03 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.61 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.92 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.92 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.46 MW | 1.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.39 MW | 1.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.01 MW | 0.86 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.74 MW | 4.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.31 MW | 1.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934521 | AD1-076 C | Adder | 17.72 MW | 15.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934522 | AD1-076 E | Adder | 9.02 MW | 7.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.76 MW | 0.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.41 MW | 2.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936161 | AD2-022 C O1 | Adder | 3.27 MW | 2.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936162 | AD2-022 E O1 | Adder | 1.96 MW | 1.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936171 | AD2-023 C O1 | Adder | 1.91 MW | 1.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936172 | AD2-023 E O1 | Adder | 1.04 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.02 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.48 MW | 0.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.47 MW | 19.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.98 MW | 12.98 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.6 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.81 MW | 0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.54 MW | 0.46 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.08 MW | 7.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.75 MW | 2.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.44 MW | 1.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.65 MW | 3.1 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 5.04 MW | 4.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958801 | AF2-171 C | Adder | 4.9 MW | 4.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958802 | AF2-171 E | Adder | 3.26 MW | 2.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.21 MW | 5.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.16 MW | 3.54 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.23 MW | 2.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.15 MW | 1.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.03 MW | 2.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315294 | 1DOMTR10 | Adder | 3.78 MW | 3.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.53 MW | 0.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 4.48 MW | 3.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.92 MW | 1.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.5 MW | 9.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.07 MW | 4.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.22 MW | 5.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.72 MW | 2.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.88 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.89 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.16 MW | 1.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.42 MW | 2.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.58 MW | 2.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.39 MW | 3.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.16 MW | 1.84 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.12 MW | 1.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.03 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.24 MW | 1.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.96 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.53 MW | 1.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.68 MW | 21.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.71 MW | 9.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.21 MW | 1.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 26.06 MW | 22.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.38 MW | 14.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 7.06 MW | 6.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.55 MW | 3.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.53 MW | 3.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.56 MW | 1.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.97 MW | 17.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.11 MW | 12.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 15.04 MW | 15.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.81 MW | -2.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.05 MW | -3.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315103 | 1BRUNSWICKG2 | 50/50 | 4.71 MW | 4.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315104 | 1BRUNSWICKG3 | 50/50 | 4.71 MW | 4.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315105 | 1BRUNSWICKS1 | 50/50 | 9.78 MW | 9.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.16 MW | 2.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.7 MW | 3.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.24 MW | 0.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | 50/50 | 1.59 MW | 1.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | 50/50 | 0.78 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.25 MW | 1.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | 50/50 | 4.68 MW | 4.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.69 MW | 1.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | 50/50 | 13.99 MW | 13.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | 50/50 | 6.37 MW | 6.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 2.34 MW | 1.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 1.16 MW | 0.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.89 MW | 3.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.94 MW | 1.65 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 4.75 MW | 4.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 2.11 MW | 1.79 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 3.49 MW | 2.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.64 MW | 1.39 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936261 | AD2-033 C | Adder | 5.1 MW | 4.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936262 | AD2-033 E | Adder | 3.4 MW | 2.89 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 4.14 MW | 3.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.76 MW | 2.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940241 | AE2-006 | Adder | 0.18 MW | 0.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | 50/50 | 1.6 MW | 1.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | 50/50 | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925611 | AC1-036 C | Adder | 0.36 MW | 0.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.92 MW | 3.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 2.1 MW | 1.79 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314947 | 8GREENSVILLE | 50/50 | 28.73 MW | 28.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.84 MW | 1.84 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925171 | AB2-174 C O1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 36.98 MW | 31.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 24.66 MW | 20.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 3.27 MW | 3.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.16 MW | 0.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.08 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 3.03 MW | 2.57 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.65 MW | 1.4 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.78 MW | 1.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.69 MW | 0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.82 MW | 3.82 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.69 MW | 14.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.52 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.09 MW | 3.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 7.38 MW | 7.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 26.01 MW | 26.01 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 17.24 MW | 17.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.15 MW | 1.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.87 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.21 MW | 2.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.6 MW | 2.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 13.7 MW | 13.7 MW |
| Details for 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314582 | 3KELFORD | 50/50 | 0.43 MW | 0.43 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918532 | AA1-067 E | 50/50 | 0.73 MW | 0.73 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919692 | AA2-053 E OP | 50/50 | 2.35 MW | 2.35 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 919702 | AA2-057 E OP | Adder | 2.09 MW | 1.78 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920592 | AA2-165 E | Adder | 0.35 MW | 0.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926201 | AC1-098 C | 50/50 | 4.44 MW | 4.44 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926202 | AC1-098 E | 50/50 | 2.65 MW | 2.65 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926211 | AC1-099 C | 50/50 | 1.49 MW | 1.49 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926212 | AC1-099 E | 50/50 | 0.87 MW | 0.87 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934521 | AD1-076 C | 50/50 | 120.46 MW | 120.46 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 934522 | AD1-076 E | 50/50 | 61.34 MW | 61.34 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943171 | AE2-346 C | 50/50 | 1.3 MW | 1.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 943172 | AE2-346 E | 50/50 | 0.56 MW | 0.56 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315294 | 1DOMTR10 | 50/50 | 21.21 MW | 21.21 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315601 | 1CONETOE2SOL | 50/50 | 0.0 MW | 0.0 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315606 | 3AA2-053SOLA | 50/50 | 0.95 MW | 0.95 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 900672 | V4-068 E | 50/50 | 0.18 MW | 0.18 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917332 | Z2-043 E | 50/50 | 1.07 MW | 1.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923262 | AB1-132 C OP | Adder | 8.36 MW | 7.11 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923263 | AB1-132 E OP | Adder | 3.58 MW | 3.04 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925121 | AB2-169 C | 50/50 | 1.86 MW | 1.86 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 925122 | AB2-169 E | 50/50 | 9.61 MW | 9.61 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932631 | AC2-084 C | 50/50 | 6.33 MW | 6.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 932632 | AC2-084 E | 50/50 | 3.12 MW | 3.12 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938222 | AE1-035 E | 50/50 | 1.33 MW | 1.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940491 | AE2-034 C | 50/50 | 19.38 MW | 19.38 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 940492 | AE2-034 E | 50/50 | 8.3 MW | 8.3 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957521 | AF2-046 C | 50/50 | 11.31 MW | 11.31 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957522 | AF2-046 E | 50/50 | 5.69 MW | 5.69 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957531 | AF2-047 C | 50/50 | 46.05 MW | 46.05 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957532 | AF2-047 E | 50/50 | 23.16 MW | 23.16 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957861 | AF2-080 C | 50/50 | 6.7 MW | 6.7 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 957862 | AF2-080 E | 50/50 | 2.97 MW | 2.97 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 916042 | Z1-036 E | 50/50 | 99.72 MW | 99.72 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314638 | 6ELIZ CT | 50/50 | 1.02 MW | 1.02 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314639 | 6TANGLEW | 50/50 | 1.8 MW | 1.8 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 944871 | AF1-152 C | 50/50 | 20.22 MW | 20.22 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 944872 | AF1-152 E | 50/50 | 13.48 MW | 13.48 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315292 | 1DOMTR78 | 50/50 | 2.84 MW | 2.84 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315605 | 6W1-029WIND | 50/50 | 3.16 MW | 3.16 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315611 | 6Z1-036WIND | 50/50 | 14.85 MW | 14.85 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 913392 | Y1-086 E | 50/50 | 9.61 MW | 9.61 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923832 | AB2-022 E | 50/50 | 5.42 MW | 5.42 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 938221 | AE1-035 C | 50/50 | 2.74 MW | 2.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 901082 | W1-029 E | 50/50 | 122.02 MW | 122.02 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917122 | Z2-027 E | 50/50 | 4.44 MW | 4.44 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 941501 | AE2-147 C | 50/50 | 60.67 MW | 60.67 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 941502 | AE2-147 E | 50/50 | 40.45 MW | 40.45 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 314574 | 6EVERETS | 50/50 | 0.29 MW | 0.29 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 917512 | Z2-088 E OP1 | 50/50 | 6.28 MW | 6.28 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920671 | AA2-174 C OP | 50/50 | 0.04 MW | 0.04 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920672 | AA2-174 E OP | 50/50 | 0.27 MW | 0.27 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924501 | AB2-099 C | 50/50 | 0.54 MW | 0.54 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 924502 | AB2-099 E | 50/50 | 0.23 MW | 0.23 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926071 | AC1-086 C | Adder | 12.31 MW | 10.46 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 926072 | AC1-086 E | Adder | 5.6 MW | 4.76 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927021 | AC1-189 C | 50/50 | 7.37 MW | 7.37 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927022 | AC1-189 E | 50/50 | 3.67 MW | 3.67 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927141 | AC1-208 C | 50/50 | 5.68 MW | 5.68 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 927142 | AC1-208 E | 50/50 | 2.52 MW | 2.52 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315614 | AA2-178 C | 50/50 | 4.49 MW | 4.49 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 920692 | AA2-178 E | 50/50 | 11.07 MW | 11.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 923831 | AB2-022 C | 50/50 | 10.07 MW | 10.07 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918561 | AA1-072 C | 50/50 | 0.32 MW | 0.32 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918562 | AA1-072 E | 50/50 | 0.15 MW | 0.15 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933981 | AD1-022 C | 50/50 | 17.14 MW | 17.14 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 933982 | AD1-022 E | 50/50 | 9.33 MW | 9.33 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 315602 | 1HOLLOMANSOL | 50/50 | 1.9 MW | 1.9 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | 918512 | AA1-065 E OP | 50/50 | 5.39 MW | 5.39 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.27 MW | 2.27 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 7.53 MW | 7.53 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.19 MW | 0.19 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.57 MW | 1.57 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 2.74 MW | 2.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 13.74 MW | 13.74 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 8.76 MW | 8.76 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.43 MW | 0.43 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.42 MW | 0.42 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.55 MW | 1.55 MW |
| 6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line l/o DVP_P4-2: 246T247 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.29 MW | 7.29 MW |
| Details for 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.04 MW | 0.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.18 MW | 2.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.18 MW | 2.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.67 MW | 1.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.66 MW | 1.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.39 MW | 1.19 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.54 MW | 3.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.45 MW | 2.08 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.46 MW | 1.24 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.53 MW | 3.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.42 MW | 2.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.84 MW | 2.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.89 MW | 1.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.8 MW | 0.68 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.38 MW | 0.32 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 15.28 MW | 12.99 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 10.19 MW | 8.66 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.49 MW | 0.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.63 MW | 0.54 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.42 MW | 0.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.56 MW | 4.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.16 MW | 1.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.14 MW | 0.97 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.86 MW | 2.43 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.95 MW | 3.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 2.54 MW | 2.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 1.69 MW | 1.44 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.59 MW | 1.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.06 MW | 1.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.1 MW | 0.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.23 MW | 0.2 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 3.54 MW | 3.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.52 MW | 1.29 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.47 MW | 6.35 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.2 MW | 2.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 0.59 MW | 0.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 4.1 MW | 3.49 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.36 MW | 2.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.15 MW | 1.83 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.48 MW | 1.26 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.7 MW | 2.3 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.04 MW | 1.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.5 MW | 2.97 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.72 MW | 1.46 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.35 MW | 0.3 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.77 MW | 1.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.76 MW | 0.65 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.21 MW | 1.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 17.02 MW | 14.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.62 MW | 6.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 0.95 MW | 0.95 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.63 MW | 0.63 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 20.45 MW | 17.38 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 13.63 MW | 11.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 5.81 MW | 4.94 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 2.92 MW | 2.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.81 MW | 2.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.25 MW | 1.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 13.94 MW | 13.94 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 9.4 MW | 9.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 11.67 MW | 11.67 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314314 | 3LOCKS | 50/50 | 0.45 MW | 0.45 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.39 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.4 MW | -2.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.63 MW | -3.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942371 | AE2-250 C O1 | 50/50 | 14.04 MW | 14.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942372 | AE2-250 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.0 MW | 1.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.73 MW | 0.62 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940431 | AE2-027 C O1 | 50/50 | 11.72 MW | 11.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940432 | AE2-027 E O1 | 50/50 | 7.82 MW | 7.82 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | Adder | 1.21 MW | 1.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.94 MW | 2.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.19 MW | 0.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | Adder | 1.25 MW | 1.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | Adder | 0.62 MW | 0.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.98 MW | 0.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.09 MW | 0.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 4.07 MW | 4.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | Adder | 3.67 MW | 3.12 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 2.89 MW | 2.46 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.33 MW | 1.13 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | Adder | 11.01 MW | 9.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | Adder | 5.01 MW | 4.26 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 1.84 MW | 1.56 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 0.91 MW | 0.78 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.1 MW | 2.63 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.54 MW | 1.31 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 3.78 MW | 3.21 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 1.68 MW | 1.43 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 2.74 MW | 2.33 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.28 MW | 1.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936261 | AD2-033 C | Adder | 4.0 MW | 3.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936262 | AD2-033 E | Adder | 2.67 MW | 2.27 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 3.26 MW | 2.77 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.17 MW | 1.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | Adder | 1.26 MW | 1.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | Adder | 1.26 MW | 1.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | Adder | 0.59 MW | 0.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.1 MW | 2.64 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 1.66 MW | 1.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.43 MW | 1.43 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925051 | AB2-160 C O1 | 50/50 | 7.9 MW | 7.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925052 | AB2-160 E O1 | 50/50 | 12.9 MW | 12.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925061 | AB2-161 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925062 | AB2-161 E O1 | Adder | 1.62 MW | 1.37 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934571 | AD1-082 C | Adder | 2.26 MW | 1.92 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934572 | AD1-082 E | Adder | 1.29 MW | 1.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939191 | AE1-149 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939192 | AE1-149 E O1 | Adder | 2.42 MW | 2.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 29.48 MW | 25.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 19.65 MW | 16.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 2.54 MW | 2.54 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.13 MW | 0.11 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.06 MW | 0.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.44 MW | 1.22 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.28 MW | 0.28 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.54 MW | 0.54 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.01 MW | 3.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 11.52 MW | 11.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.43 MW | 2.43 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.87 MW | 5.87 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 20.48 MW | 20.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.53 MW | 13.53 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.92 MW | 0.92 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.69 MW | 0.69 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.73 MW | 1.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.05 MW | 2.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.7 MW | 10.7 MW |
| Details for 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314541 | 3WATKINS | 50/50 | 0.51 MW | 0.51 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314582 | 3KELFORD | 50/50 | 1.26 MW | 1.26 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315126 | 1ROARAP2 | 50/50 | 1.15 MW | 1.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315128 | 1ROARAP4 | 50/50 | 1.09 MW | 1.09 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 918492 | AA1-063AE OP | 50/50 | 3.74 MW | 3.74 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 919692 | AA2-053 E OP | 50/50 | 4.71 MW | 4.71 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 919702 | AA2-057 E OP | 50/50 | 2.49 MW | 2.49 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920042 | AA2-088 E OP | 50/50 | 11.43 MW | 11.43 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920591 | AA2-165 C | 50/50 | 0.11 MW | 0.11 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920592 | AA2-165 E | 50/50 | 0.42 MW | 0.42 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926201 | AC1-098 C | 50/50 | 9.37 MW | 9.37 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926202 | AC1-098 E | 50/50 | 5.58 MW | 5.58 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926211 | AC1-099 C | 50/50 | 3.14 MW | 3.14 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926212 | AC1-099 E | 50/50 | 1.84 MW | 1.84 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 943171 | AE2-346 C | 50/50 | 4.23 MW | 4.23 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 943172 | AE2-346 E | 50/50 | 1.81 MW | 1.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 960081 | AF2-299 C | Adder | 0.96 MW | 0.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 960082 | AF2-299 E | Adder | 0.64 MW | 0.54 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315294 | 1DOMTR10 | Adder | -4.79 MW | -4.07 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315606 | 3AA2-053SOLA | 50/50 | 1.91 MW | 1.91 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 900672 | V4-068 E | 50/50 | 0.55 MW | 0.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 917332 | Z2-043 E | 50/50 | 3.16 MW | 3.16 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923262 | AB1-132 C OP | Adder | 5.08 MW | 4.32 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923263 | AB1-132 E OP | Adder | 2.18 MW | 1.85 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923573 | AB1-173 E OP | Adder | 0.59 MW | 0.5 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923991 | AB2-040 C O1 | Adder | 4.12 MW | 3.5 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923992 | AB2-040 E O1 | Adder | 3.37 MW | 2.86 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 932631 | AC2-084 C | 50/50 | 13.36 MW | 13.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 932632 | AC2-084 E | 50/50 | 6.58 MW | 6.58 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 946281 | AF1-292 C | Adder | 0.57 MW | 0.48 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 946282 | AF1-292 E | Adder | 0.38 MW | 0.32 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 957521 | AF2-046 C | 50/50 | 34.55 MW | 34.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 957522 | AF2-046 E | 50/50 | 17.38 MW | 17.38 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314539 | 3UNCAMP | 50/50 | 1.42 MW | 1.42 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314589 | 3MURPHYS | 50/50 | 0.17 MW | 0.17 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315115 | 1S HAMPT1 | 50/50 | 1.21 MW | 1.21 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315607 | 3AA1-063SOLA | 50/50 | 1.38 MW | 1.38 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315608 | 3AA2-088SOLA | 50/50 | 1.22 MW | 1.22 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 938221 | AE1-035 C | Adder | -1.65 MW | -1.4 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315612 | 3AA2-057SOLA | 50/50 | 0.91 MW | 0.91 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920671 | AA2-174 C OP | 50/50 | 0.09 MW | 0.09 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920672 | AA2-174 E OP | 50/50 | 0.55 MW | 0.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923911 | AB2-031 C O1 | Adder | 1.25 MW | 1.06 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923912 | AB2-031 E O1 | Adder | 0.62 MW | 0.53 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 924501 | AB2-099 C | 50/50 | 1.76 MW | 1.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 924502 | AB2-099 E | 50/50 | 0.76 MW | 0.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 925172 | AB2-174 E O1 | Adder | 3.24 MW | 2.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 925781 | AC1-054 C O1 | Adder | 3.26 MW | 2.77 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 925782 | AC1-054 E O1 | Adder | 1.5 MW | 1.28 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926071 | AC1-086 C | Adder | 7.48 MW | 6.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926072 | AC1-086 E | Adder | 3.41 MW | 2.9 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 927141 | AC1-208 C | 50/50 | 9.0 MW | 9.0 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 927142 | AC1-208 E | 50/50 | 4.0 MW | 4.0 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923572 | AB1-173 C OP | Adder | 1.26 MW | 1.07 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923582 | AB1-173AC OP | Adder | 1.26 MW | 1.07 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923583 | AB1-173AE OP | Adder | 0.59 MW | 0.5 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 907092 | X1-038 E | 50/50 | 3.54 MW | 3.54 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 938771 | AE1-103 C O1 | 50/50 | 1.7 MW | 1.7 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 938772 | AE1-103 E O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 918561 | AA1-072 C | 50/50 | 0.95 MW | 0.95 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 918562 | AA1-072 E | 50/50 | 0.45 MW | 0.45 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.03 MW | 0.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.69 MW | 0.69 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.15 MW | 0.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.6 MW | 0.6 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.08 MW | 1.08 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.82 MW | 0.82 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.1 MW | 0.1 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.1 MW | 0.1 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.64 MW | 0.64 MW |
| Details for 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 314541 | 3WATKINS | 50/50 | 0.51 MW | 0.51 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 314582 | 3KELFORD | 50/50 | 1.29 MW | 1.29 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315126 | 1ROARAP2 | 50/50 | 0.94 MW | 0.94 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315128 | 1ROARAP4 | 50/50 | 0.9 MW | 0.9 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 918492 | AA1-063AE OP | 50/50 | 3.36 MW | 3.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 919692 | AA2-053 E OP | 50/50 | 4.35 MW | 4.35 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 919702 | AA2-057 E OP | 50/50 | 2.3 MW | 2.3 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 920042 | AA2-088 E OP | 50/50 | 11.19 MW | 11.19 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 920591 | AA2-165 C | 50/50 | 0.1 MW | 0.1 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 920592 | AA2-165 E | 50/50 | 0.39 MW | 0.39 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 926201 | AC1-098 C | 50/50 | 9.23 MW | 9.23 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 926202 | AC1-098 E | 50/50 | 5.5 MW | 5.5 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 926211 | AC1-099 C | 50/50 | 3.09 MW | 3.09 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 926212 | AC1-099 E | 50/50 | 1.82 MW | 1.82 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 943171 | AE2-346 C | 50/50 | 4.35 MW | 4.35 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 943172 | AE2-346 E | 50/50 | 1.86 MW | 1.86 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315606 | 3AA2-053SOLA | 50/50 | 1.76 MW | 1.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 900672 | V4-068 E | 50/50 | 0.55 MW | 0.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 917332 | Z2-043 E | 50/50 | 3.23 MW | 3.23 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 917342 | Z2-044 E | Adder | 0.26 MW | 0.22 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923573 | AB1-173 E OP | Adder | 0.44 MW | 0.38 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923991 | AB2-040 C O1 | Adder | 3.09 MW | 2.63 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923992 | AB2-040 E O1 | Adder | 2.53 MW | 2.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 932631 | AC2-084 C | 50/50 | 13.16 MW | 13.16 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 932632 | AC2-084 E | 50/50 | 6.48 MW | 6.48 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 957521 | AF2-046 C | 50/50 | 35.0 MW | 35.0 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 957522 | AF2-046 E | 50/50 | 17.6 MW | 17.6 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 314539 | 3UNCAMP | 50/50 | 1.42 MW | 1.42 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 314589 | 3MURPHYS | 50/50 | 0.17 MW | 0.17 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315115 | 1S HAMPT1 | 50/50 | 1.2 MW | 1.2 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315607 | 3AA1-063SOLA | 50/50 | 1.24 MW | 1.24 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315608 | 3AA2-088SOLA | 50/50 | 1.19 MW | 1.19 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 938221 | AE1-035 C | Adder | -1.11 MW | -0.94 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 315612 | 3AA2-057SOLA | 50/50 | 0.84 MW | 0.84 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 920671 | AA2-174 C OP | 50/50 | 0.08 MW | 0.08 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 920672 | AA2-174 E OP | 50/50 | 0.5 MW | 0.5 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923911 | AB2-031 C O1 | Adder | 0.94 MW | 0.8 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923912 | AB2-031 E O1 | Adder | 0.46 MW | 0.39 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 924501 | AB2-099 C | 50/50 | 1.81 MW | 1.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 924502 | AB2-099 E | 50/50 | 0.78 MW | 0.78 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 925172 | AB2-174 E O1 | Adder | 2.36 MW | 2.01 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 925781 | AC1-054 C O1 | Adder | 2.64 MW | 2.24 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 925782 | AC1-054 E O1 | Adder | 1.21 MW | 1.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 927141 | AC1-208 C | 50/50 | 8.41 MW | 8.41 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 927142 | AC1-208 E | 50/50 | 3.73 MW | 3.73 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923572 | AB1-173 C OP | Adder | 0.95 MW | 0.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923582 | AB1-173AC OP | Adder | 0.95 MW | 0.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 923583 | AB1-173AE OP | Adder | 0.44 MW | 0.38 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 907092 | X1-038 E | 50/50 | 3.56 MW | 3.56 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 938771 | AE1-103 C O1 | 50/50 | 1.71 MW | 1.71 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 938772 | AE1-103 E O1 | 50/50 | 2.36 MW | 2.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 918561 | AA1-072 C | 50/50 | 0.97 MW | 0.97 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | 918562 | AA1-072 E | 50/50 | 0.46 MW | 0.46 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.43 MW | 0.43 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.09 MW | 0.09 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.48 MW | 0.48 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.71 MW | 0.71 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.52 MW | 0.52 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.07 MW | 0.07 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.03 MW | 0.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.06 MW | 0.06 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: WT2171 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.38 MW | 0.38 MW |
| Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314541 | 3WATKINS | Adder | 0.96 MW | 0.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918492 | AA1-063AE OP | Adder | 4.91 MW | 4.17 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918532 | AA1-067 E | Adder | 0.9 MW | 0.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919692 | AA2-053 E OP | Adder | 4.44 MW | 3.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920042 | AA2-088 E OP | Adder | 13.97 MW | 11.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926201 | AC1-098 C | Adder | 7.38 MW | 6.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926202 | AC1-098 E | Adder | 4.4 MW | 3.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926211 | AC1-099 C | Adder | 2.47 MW | 2.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926212 | AC1-099 E | Adder | 1.45 MW | 1.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934521 | AD1-076 C | Adder | 77.79 MW | 66.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934522 | AD1-076 E | Adder | 39.61 MW | 33.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937481 | AD2-202 C O1 | Adder | 2.46 MW | 2.09 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937482 | AD2-202 E O1 | Adder | 1.15 MW | 0.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942931 | AE2-313 C | Adder | 47.03 MW | 39.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942932 | AE2-313 E | Adder | 31.36 MW | 26.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943171 | AE2-346 C | Adder | 1.85 MW | 1.57 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943172 | AE2-346 E | Adder | 0.79 MW | 0.67 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944011 | AF1-069 C | Adder | 17.11 MW | 14.54 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944012 | AF1-069 E | Adder | 6.65 MW | 5.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945811 | AF1-246 C O1 | Adder | 8.8 MW | 7.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945812 | AF1-246 E O1 | Adder | 12.15 MW | 10.32 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315294 | 1DOMTR10 | Adder | 15.1 MW | 12.83 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 900672 | V4-068 E | Adder | 0.39 MW | 0.33 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917332 | Z2-043 E | Adder | 1.48 MW | 1.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925122 | AB2-169 E | Adder | 7.79 MW | 6.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932631 | AC2-084 C | Adder | 10.52 MW | 8.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932632 | AC2-084 E | Adder | 5.18 MW | 4.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938222 | AE1-035 E | Adder | 1.47 MW | 1.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940491 | AE2-034 C | Adder | 10.63 MW | 9.03 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940492 | AE2-034 E | Adder | 4.56 MW | 3.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941031 | AE2-094 C | Adder | 52.37 MW | 44.51 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941032 | AE2-094 E | Adder | 23.45 MW | 19.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957481 | AF2-042 C | Adder | 62.83 MW | 53.4 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957482 | AF2-042 E | Adder | 41.88 MW | 35.6 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957521 | AF2-046 C | Adder | 22.13 MW | 18.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957522 | AF2-046 E | Adder | 11.13 MW | 9.46 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957531 | AF2-047 C | Adder | 25.25 MW | 21.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957532 | AF2-047 E | Adder | 12.7 MW | 10.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957861 | AF2-080 C | Adder | 9.34 MW | 7.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957862 | AF2-080 E | Adder | 4.14 MW | 3.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314539 | 3UNCAMP | Adder | 3.43 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916042 | Z1-036 E | Adder | 44.54 MW | 37.86 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940641 | AE2-051 C O1 | Adder | 25.15 MW | 21.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 940642 | AE2-051 E O1 | Adder | 16.77 MW | 14.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314295 | 6BIRDNECK | 50/50 | 0.08 MW | 0.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 314491 | 3PENDLTN | 50/50 | 0.58 MW | 0.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 919152 | AA1-139 E | Adder | 10.67 MW | 9.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926661 | AC1-147 C | 50/50 | 3.74 MW | 3.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926662 | AC1-147 E | 50/50 | 2.2 MW | 2.2 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934061 | AD1-033 C | 50/50 | 12.65 MW | 12.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934062 | AD1-033 E | 50/50 | 8.43 MW | 8.43 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935111 | AD1-144 C | Adder | 2.65 MW | 2.25 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 935112 | AD1-144 E | Adder | 1.45 MW | 1.23 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936661 | AD2-085 C | Adder | 4.6 MW | 3.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 936662 | AD2-085 E | Adder | 7.51 MW | 6.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937221 | AD2-160 C O1 | 50/50 | 9.77 MW | 9.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 937222 | AD2-160 E O1 | 50/50 | 5.12 MW | 5.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942341 | AE2-247 C | Adder | 1.99 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942342 | AE2-247 E | Adder | 2.75 MW | 2.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942401 | AE2-253 C | 50/50 | 10.27 MW | 10.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 942402 | AE2-253 E | 50/50 | 4.62 MW | 4.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943461 | AF1-017 C | Adder | 1.8 MW | 1.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943462 | AF1-017 E | Adder | 2.94 MW | 2.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943611 | AF1-032 C | Adder | 2.81 MW | 2.39 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943612 | AF1-032 E | Adder | 1.49 MW | 1.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943621 | AF1-033 C | Adder | 2.92 MW | 2.48 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 943622 | AF1-033 E | Adder | 1.51 MW | 1.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944871 | AF1-152 C | Adder | 8.4 MW | 7.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944872 | AF1-152 E | Adder | 5.6 MW | 4.76 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945361 | AF1-201 C O1 | Adder | 17.6 MW | 14.96 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 945362 | AF1-201 E O1 | Adder | 11.73 MW | 9.97 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315098 | 1CHESPKA | 50/50 | 0.77 MW | 0.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315099 | 1CHESPKB | 50/50 | 1.27 MW | 1.27 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315108 | 1ELIZAR1 | 50/50 | 5.68 MW | 5.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315109 | 1ELIZAR2 | 50/50 | 5.58 MW | 5.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315110 | 1ELIZAR3 | 50/50 | 5.75 MW | 5.75 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315233 | 1SURRY 2 | 50/50 | 56.38 MW | 56.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 315611 | 6Z1-036WIND | Adder | 6.63 MW | 5.64 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 913392 | Y1-086 E | Adder | 3.57 MW | 3.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 916192 | Z1-068 E | 50/50 | 3.14 MW | 3.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923832 | AB2-022 E | Adder | 2.02 MW | 1.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932591 | AC2-079 C O1 | Adder | 7.7 MW | 6.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932592 | AC2-079 E O1 | Adder | 12.57 MW | 10.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938221 | AE1-035 C | Adder | 3.04 MW | 2.58 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939312 | AE1-162 E | Adder | 1.98 MW | 1.69 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941101 | AE2-104 C O1 | Adder | 5.1 MW | 4.34 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941102 | AE2-104 E O1 | Adder | 8.11 MW | 6.9 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941281 | AE2-122 C O1 | 50/50 | 47.55 MW | 47.55 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941282 | AE2-122 E O1 | 50/50 | 191.88 MW | 191.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941291 | AE2-123 C O1 | 50/50 | 48.87 MW | 48.87 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941292 | AE2-123 E O1 | 50/50 | 190.56 MW | 190.56 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941301 | AE2-124 C O1 | 50/50 | 44.47 MW | 44.47 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941302 | AE2-124 E O1 | 50/50 | 195.13 MW | 195.13 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957491 | AF2-043 C | Adder | 3.44 MW | 2.92 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957492 | AF2-043 E | Adder | 2.29 MW | 1.95 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957631 | AF2-057 | 50/50 | 5.94 MW | 5.94 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 901082 | W1-029 E | Adder | 50.67 MW | 43.07 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 917122 | Z2-027 E | Adder | 1.71 MW | 1.45 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 925522 | AC1-027 E | 50/50 | 1.91 MW | 1.91 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941501 | AE2-147 C | Adder | 25.2 MW | 21.42 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941502 | AE2-147 E | Adder | 16.8 MW | 14.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 941591 | AE2-156 O1 | 50/50 | 29.77 MW | 29.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957871 | AF2-081 C | Adder | 16.59 MW | 14.1 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 957872 | AF2-081 E | Adder | 7.11 MW | 6.04 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958161 | AF2-110 C | Adder | 2.08 MW | 1.77 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 958162 | AF2-110 E | Adder | 3.31 MW | 2.81 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920672 | AA2-174 E OP | Adder | 0.51 MW | 0.44 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924501 | AB2-099 C | Adder | 0.77 MW | 0.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 924502 | AB2-099 E | Adder | 0.33 MW | 0.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926071 | AC1-086 C | Adder | 7.37 MW | 6.26 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926072 | AC1-086 E | Adder | 3.35 MW | 2.85 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927021 | AC1-189 C | Adder | 10.28 MW | 8.74 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 927022 | AC1-189 E | Adder | 5.12 MW | 4.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934611 | AD1-087 C O1 | Adder | 8.41 MW | 7.14 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 934612 | AD1-087 E O1 | Adder | 3.94 MW | 3.35 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 907092 | X1-038 E | Adder | 8.58 MW | 7.3 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 920692 | AA2-178 E | Adder | 6.07 MW | 5.16 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 923831 | AB2-022 C | Adder | 3.75 MW | 3.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926751 | AC1-161 C O1 | 50/50 | 58.62 MW | 58.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 926752 | AC1-161 E O1 | 50/50 | 25.02 MW | 25.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932041 | AC2-012 C | 50/50 | 13.31 MW | 13.31 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 932042 | AC2-012 E | 50/50 | 21.72 MW | 21.72 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933291 | AC2-141 C | 50/50 | 58.62 MW | 58.62 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933292 | AC2-141 E | 50/50 | 25.02 MW | 25.02 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938531 | AE1-072 C O1 | Adder | 29.06 MW | 24.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938532 | AE1-072 E O1 | Adder | 15.15 MW | 12.88 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938771 | AE1-103 C O1 | Adder | 4.12 MW | 3.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 938772 | AE1-103 E O1 | Adder | 5.69 MW | 4.84 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939311 | AE1-162 C | Adder | 2.98 MW | 2.53 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939411 | AE1-173 C | Adder | 137.05 MW | 116.5 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 939412 | AE1-173 E | Adder | 91.37 MW | 77.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918561 | AA1-072 C | Adder | 0.44 MW | 0.38 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918562 | AA1-072 E | Adder | 0.21 MW | 0.18 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944581 | AF1-123 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944582 | AF1-123 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944591 | AF1-124 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944592 | AF1-124 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944601 | AF1-125 C O1 | 50/50 | 83.28 MW | 83.28 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 944602 | AF1-125 E O1 | 50/50 | 190.68 MW | 190.68 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933981 | AD1-022 C | Adder | 12.35 MW | 10.49 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 933982 | AD1-022 E | Adder | 6.72 MW | 5.71 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | 918512 | AA1-065 E OP | Adder | 5.98 MW | 5.08 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.65 MW | 0.65 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.24 MW | 1.24 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 8.98 MW | 8.98 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 29.7 MW | 29.7 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.66 MW | 1.66 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.52 MW | 6.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 22.63 MW | 22.63 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 59.8 MW | 59.8 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 35.73 MW | 35.73 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 3.52 MW | 3.52 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.15 MW | 2.15 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.19 MW | 4.19 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 6.12 MW | 6.12 MW |
| 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 563T576 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.84 MW | 23.84 MW |
| Details for 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.04 MW | 0.04 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.18 MW | 2.7 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.18 MW | 2.7 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.67 MW | 1.42 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.66 MW | 1.41 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.39 MW | 1.19 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.54 MW | 3.01 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.45 MW | 2.08 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.46 MW | 1.24 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.7 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.53 MW | 3.85 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.42 MW | 2.06 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.84 MW | 2.42 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.89 MW | 1.61 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.8 MW | 0.68 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.38 MW | 0.32 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 15.28 MW | 12.99 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 10.19 MW | 8.66 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.49 MW | 0.41 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.63 MW | 0.54 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.42 MW | 0.36 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.56 MW | 4.73 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.16 MW | 1.84 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.14 MW | 0.97 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.86 MW | 2.43 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.95 MW | 3.36 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 2.54 MW | 2.16 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 1.69 MW | 1.44 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.59 MW | 1.59 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.06 MW | 1.06 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.1 MW | 0.09 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.23 MW | 0.2 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 3.54 MW | 3.01 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.52 MW | 1.29 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.47 MW | 6.35 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.2 MW | 2.72 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 0.59 MW | 0.5 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 4.1 MW | 3.49 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.36 MW | 2.85 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.15 MW | 1.83 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.48 MW | 1.26 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.7 MW | 0.59 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.7 MW | 2.3 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.04 MW | 1.73 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.5 MW | 2.97 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.72 MW | 1.46 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.35 MW | 0.3 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.77 MW | 1.5 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.76 MW | 0.65 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.21 MW | 1.03 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 17.02 MW | 14.47 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.62 MW | 6.48 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 0.95 MW | 0.95 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.63 MW | 0.63 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 20.45 MW | 17.38 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 13.63 MW | 11.59 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 5.81 MW | 4.94 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 2.92 MW | 2.48 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.81 MW | 2.39 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.25 MW | 1.06 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 13.94 MW | 13.94 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 9.4 MW | 9.4 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 11.67 MW | 11.67 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314314 | 3LOCKS | 50/50 | 0.45 MW | 0.45 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.39 MW | 0.39 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.4 MW | -2.04 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.63 MW | -3.09 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942371 | AE2-250 C O1 | 50/50 | 14.04 MW | 14.04 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942372 | AE2-250 E O1 | 50/50 | 7.41 MW | 7.41 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.0 MW | 1.0 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.73 MW | 0.62 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940431 | AE2-027 C O1 | 50/50 | 11.72 MW | 11.72 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940432 | AE2-027 E O1 | 50/50 | 7.82 MW | 7.82 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | Adder | 1.21 MW | 1.03 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942001 | AE2-212 C | 50/50 | 7.62 MW | 7.62 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942002 | AE2-212 E | 50/50 | 5.08 MW | 5.08 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.94 MW | 2.5 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.19 MW | 0.16 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | Adder | 1.25 MW | 1.06 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | Adder | 0.62 MW | 0.52 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.98 MW | 0.84 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.09 MW | 0.07 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 4.07 MW | 4.07 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | Adder | 3.67 MW | 3.12 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 2.89 MW | 2.46 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.33 MW | 1.13 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | Adder | 11.01 MW | 9.36 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | Adder | 5.01 MW | 4.26 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 1.84 MW | 1.56 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 0.91 MW | 0.78 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.1 MW | 2.63 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.54 MW | 1.31 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 3.78 MW | 3.21 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 1.68 MW | 1.43 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 2.74 MW | 2.33 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.28 MW | 1.09 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 3.26 MW | 2.77 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.17 MW | 1.85 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | Adder | 1.26 MW | 1.07 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | Adder | 1.26 MW | 1.07 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | Adder | 0.59 MW | 0.5 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 3.1 MW | 2.64 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 1.66 MW | 1.42 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.43 MW | 1.43 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925051 | AB2-160 C O1 | 50/50 | 7.9 MW | 7.9 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925052 | AB2-160 E O1 | 50/50 | 12.9 MW | 12.9 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925061 | AB2-161 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925062 | AB2-161 E O1 | Adder | 1.62 MW | 1.37 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934571 | AD1-082 C | Adder | 2.26 MW | 1.92 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934572 | AD1-082 E | Adder | 1.29 MW | 1.09 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939191 | AE1-149 C O1 | Adder | 3.62 MW | 3.08 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939192 | AE1-149 E O1 | Adder | 2.42 MW | 2.05 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 29.48 MW | 25.05 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 19.65 MW | 16.7 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 2.54 MW | 2.54 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.13 MW | 0.11 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.06 MW | 0.05 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.44 MW | 1.22 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.28 MW | 0.28 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.54 MW | 0.54 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.01 MW | 3.01 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 11.52 MW | 11.52 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.43 MW | 2.43 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.87 MW | 5.87 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 20.48 MW | 20.48 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.53 MW | 13.53 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.92 MW | 0.92 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.69 MW | 0.69 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.73 MW | 1.73 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.05 MW | 2.05 MW |
| 6HARR205-6TYLER 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.7 MW | 10.7 MW |
| Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.24 MW | 0.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.69 MW | 1.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.35 MW | 1.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.91 MW | 3.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.23 MW | 0.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.4 MW | 2.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.43 MW | 1.22 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.8 MW | 0.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.47 MW | 0.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.67 MW | 2.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.78 MW | 1.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.75 MW | 0.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.32 MW | 12.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.55 MW | 8.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.5 MW | 0.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.21 MW | 4.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.02 MW | 1.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.69 MW | 2.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.71 MW | 3.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.48 MW | 1.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.99 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 3.41 MW | 2.9 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.04 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 0.56 MW | 0.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.88 MW | 3.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.7 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.4 MW | 1.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.78 MW | 1.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.43 MW | 2.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.69 MW | 1.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.36 MW | 0.31 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.98 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.95 MW | 13.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.14 MW | 6.07 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.88 MW | 0.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 19.18 MW | 16.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.79 MW | 10.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.16 MW | 5.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.1 MW | 2.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.76 MW | 2.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.22 MW | 1.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 0.81 MW | 0.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.71 MW | 12.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.57 MW | 8.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.64 MW | 10.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.35 MW | 0.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.86 MW | 1.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.03 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.46 MW | -2.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.81 MW | 0.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.12 MW | 0.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.73 MW | 0.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.2 MW | 1.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.91 MW | 0.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | Adder | 3.05 MW | 2.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | Adder | 4.97 MW | 4.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.74 MW | 0.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.27 MW | 4.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 0.97 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.55 MW | 1.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.4 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.63 MW | 0.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.87 MW | 2.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.19 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | Adder | 1.18 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | Adder | 0.58 MW | 0.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 3.76 MW | 3.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | Adder | 3.46 MW | 2.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 2.77 MW | 2.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.27 MW | 1.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | Adder | 10.43 MW | 8.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | Adder | 4.75 MW | 4.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 1.73 MW | 1.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 0.86 MW | 0.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.03 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.51 MW | 1.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 3.67 MW | 3.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 1.63 MW | 1.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 2.57 MW | 2.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.21 MW | 1.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 3.1 MW | 2.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.07 MW | 1.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | Adder | 1.19 MW | 1.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | Adder | 1.19 MW | 1.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | Adder | 0.56 MW | 0.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 2.98 MW | 2.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 1.6 MW | 1.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 907092 | X1-038 E | Adder | 2.02 MW | 1.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.32 MW | 1.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925061 | AB2-161 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925062 | AB2-161 E O1 | 50/50 | 5.18 MW | 5.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934571 | AD1-082 C | 50/50 | 7.23 MW | 7.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934572 | AD1-082 E | 50/50 | 4.13 MW | 4.13 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C O1 | Adder | 0.97 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E O1 | Adder | 1.34 MW | 1.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939191 | AE1-149 C O1 | 50/50 | 12.8 MW | 12.8 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939192 | AE1-149 E O1 | 50/50 | 8.53 MW | 8.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 28.59 MW | 24.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 19.06 MW | 16.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.13 MW | 0.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.06 MW | 0.05 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.46 MW | 1.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.86 MW | 2.86 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.88 MW | 10.88 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.3 MW | 2.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.63 MW | 5.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.43 MW | 19.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.79 MW | 12.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.88 MW | 0.88 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.65 MW | 0.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.63 MW | 1.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.95 MW | 1.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.07 MW | 10.07 MW |
| Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.38 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.1 MW | 0.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.37 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.95 MW | 4.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.95 MW | 4.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.38 MW | 2.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.48 MW | 1.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.12 MW | 1.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.64 MW | 3.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | Adder | 3.3 MW | 2.8 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | Adder | 3.26 MW | 2.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | Adder | 2.34 MW | 1.99 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | Adder | 6.8 MW | 5.78 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | Adder | 0.4 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | Adder | 4.32 MW | 3.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | Adder | 2.58 MW | 2.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | Adder | 1.45 MW | 1.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | Adder | 0.85 MW | 0.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | Adder | 8.44 MW | 7.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | Adder | 4.51 MW | 3.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934521 | AD1-076 C | Adder | 22.4 MW | 19.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934522 | AD1-076 E | Adder | 11.4 MW | 9.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | Adder | 0.88 MW | 0.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | Adder | 0.38 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.76 MW | 1.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.64 MW | 3.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.42 MW | 2.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315294 | 1DOMTR10 | Adder | 4.71 MW | 4.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | Adder | 0.19 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | Adder | 0.75 MW | 0.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | Adder | 0.37 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922922 | AB1-081 C OP | Adder | 5.49 MW | 4.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 16.0 MW | 16.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.86 MW | 6.86 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 1.28 MW | 1.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.96 MW | 8.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.33 MW | 7.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.33 MW | 2.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.1 MW | 1.78 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.66 MW | 2.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | Adder | 6.16 MW | 5.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | Adder | 3.04 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.61 MW | 0.52 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.74 MW | 2.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.17 MW | 2.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.45 MW | 1.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | Adder | 10.82 MW | 9.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | Adder | 5.44 MW | 4.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.28 MW | 3.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 1.21 MW | 1.03 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.94 MW | 35.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 24.23 MW | 24.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 30.08 MW | 30.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 1.0 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | Adder | 2.47 MW | 2.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | Adder | 4.02 MW | 3.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | Adder | 1.08 MW | 0.92 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | Adder | 1.49 MW | 1.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | Adder | 0.97 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | Adder | 1.59 MW | 1.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.64 MW | 3.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.6 MW | 2.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | Adder | 4.04 MW | 3.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | Adder | 6.58 MW | 5.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938221 | AE1-035 C | Adder | 1.25 MW | 1.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.16 MW | 6.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920672 | AA2-174 E OP | Adder | 0.38 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923911 | AB2-031 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923912 | AB2-031 E O1 | 50/50 | 1.34 MW | 1.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.4 MW | 1.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924501 | AB2-099 C | Adder | 0.37 MW | 0.31 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924502 | AB2-099 E | Adder | 0.16 MW | 0.13 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924512 | AB2-100 E | 50/50 | 9.84 MW | 9.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925172 | AB2-174 E O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925781 | AC1-054 C O1 | Adder | 4.72 MW | 4.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925782 | AC1-054 E O1 | Adder | 2.18 MW | 1.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 C | 50/50 | 23.56 MW | 23.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926072 | AC1-086 E | 50/50 | 10.72 MW | 10.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927021 | AC1-189 C | Adder | 4.71 MW | 4.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927022 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927141 | AC1-208 C | Adder | 6.76 MW | 5.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927142 | AC1-208 E | Adder | 3.0 MW | 2.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936261 | AD2-033 C | Adder | 5.34 MW | 4.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936262 | AD2-033 E | Adder | 3.56 MW | 3.03 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C O1 | Adder | 4.79 MW | 4.07 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E O1 | Adder | 3.19 MW | 2.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923572 | AB1-173 C OP | 50/50 | 2.75 MW | 2.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923582 | AB1-173AC OP | 50/50 | 2.75 MW | 2.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923583 | AB1-173AE OP | 50/50 | 1.28 MW | 1.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C O1 | Adder | 4.83 MW | 4.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E O1 | Adder | 2.6 MW | 2.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 907092 | X1-038 E | Adder | 3.04 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924511 | AB2-100 C | 50/50 | 3.47 MW | 3.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925061 | AB2-161 C O1 | 50/50 | 4.5 MW | 4.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925062 | AB2-161 E O1 | 50/50 | 7.34 MW | 7.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925171 | AB2-174 C O1 | 50/50 | 1.56 MW | 1.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934571 | AD1-082 C | 50/50 | 10.25 MW | 10.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934572 | AD1-082 E | 50/50 | 5.85 MW | 5.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C O1 | Adder | 1.46 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E O1 | Adder | 2.01 MW | 1.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939191 | AE1-149 C O1 | 50/50 | 18.48 MW | 18.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939192 | AE1-149 E O1 | 50/50 | 12.32 MW | 12.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 O1 | 50/50 | 6.59 MW | 6.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918561 | AA1-072 C | Adder | 0.23 MW | 0.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918562 | AA1-072 E | Adder | 0.11 MW | 0.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 3.94 MW | 3.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.14 MW | 1.82 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.46 MW | 2.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.36 MW | 2.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.25 MW | 8.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.9 MW | 3.9 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 15.09 MW | 15.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 9.67 MW | 9.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.61 MW | 0.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.49 MW | 0.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.61 MW | 1.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.72 MW | 7.72 MW |
| Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.24 MW | 0.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.69 MW | 1.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.35 MW | 1.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.91 MW | 3.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.23 MW | 0.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.4 MW | 2.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.43 MW | 1.22 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.8 MW | 0.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.47 MW | 0.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.67 MW | 2.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.78 MW | 1.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.75 MW | 0.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.32 MW | 12.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.55 MW | 8.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.5 MW | 0.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.21 MW | 4.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.02 MW | 1.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.69 MW | 2.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.71 MW | 3.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.48 MW | 1.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.99 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.42 MW | 0.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922922 | AB1-081 C OP | Adder | 3.41 MW | 2.9 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.04 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 0.56 MW | 0.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.88 MW | 3.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.7 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.4 MW | 1.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.78 MW | 1.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.43 MW | 2.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.69 MW | 1.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.36 MW | 0.31 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.98 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.95 MW | 13.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.14 MW | 6.07 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.88 MW | 0.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 19.18 MW | 16.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.79 MW | 10.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.16 MW | 5.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.1 MW | 2.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.76 MW | 2.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.22 MW | 1.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 0.81 MW | 0.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.71 MW | 12.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.57 MW | 8.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.64 MW | 10.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.35 MW | 0.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.86 MW | 1.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.03 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.46 MW | -2.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.81 MW | 0.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.12 MW | 0.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.73 MW | 0.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.2 MW | 1.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.91 MW | 0.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | Adder | 3.05 MW | 2.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | Adder | 4.97 MW | 4.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938221 | AE1-035 C | Adder | 0.74 MW | 0.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.27 MW | 4.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 0.97 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.55 MW | 1.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.4 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.63 MW | 0.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.87 MW | 2.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920672 | AA2-174 E OP | Adder | 0.19 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923911 | AB2-031 C O1 | Adder | 1.18 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923912 | AB2-031 E O1 | Adder | 0.58 MW | 0.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924501 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924502 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924512 | AB2-100 E | 50/50 | 3.76 MW | 3.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925172 | AB2-174 E O1 | Adder | 3.46 MW | 2.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925781 | AC1-054 C O1 | Adder | 2.77 MW | 2.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925782 | AC1-054 E O1 | Adder | 1.27 MW | 1.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 C | Adder | 10.43 MW | 8.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926072 | AC1-086 E | Adder | 4.75 MW | 4.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926271 | AC1-105 C O1 | Adder | 1.73 MW | 1.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926272 | AC1-105 E O1 | Adder | 0.86 MW | 0.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927021 | AC1-189 C | Adder | 3.03 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927022 | AC1-189 E | Adder | 1.51 MW | 1.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927141 | AC1-208 C | Adder | 3.67 MW | 3.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927142 | AC1-208 E | Adder | 1.63 MW | 1.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934611 | AD1-087 C O1 | Adder | 2.57 MW | 2.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934612 | AD1-087 E O1 | Adder | 1.21 MW | 1.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C O1 | Adder | 3.1 MW | 2.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E O1 | Adder | 2.07 MW | 1.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923572 | AB1-173 C OP | Adder | 1.19 MW | 1.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923582 | AB1-173AC OP | Adder | 1.19 MW | 1.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923583 | AB1-173AE OP | Adder | 0.56 MW | 0.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C O1 | Adder | 2.98 MW | 2.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E O1 | Adder | 1.6 MW | 1.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 907092 | X1-038 E | Adder | 2.02 MW | 1.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924511 | AB2-100 C | 50/50 | 1.32 MW | 1.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925061 | AB2-161 C O1 | 50/50 | 3.17 MW | 3.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925062 | AB2-161 E O1 | 50/50 | 5.18 MW | 5.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934571 | AD1-082 C | 50/50 | 7.23 MW | 7.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934572 | AD1-082 E | 50/50 | 4.13 MW | 4.13 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C O1 | Adder | 0.97 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E O1 | Adder | 1.34 MW | 1.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939191 | AE1-149 C O1 | 50/50 | 12.8 MW | 12.8 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939192 | AE1-149 E O1 | 50/50 | 8.53 MW | 8.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939411 | AE1-173 C | Adder | 28.59 MW | 24.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939412 | AE1-173 E | Adder | 19.06 MW | 16.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918561 | AA1-072 C | Adder | 0.13 MW | 0.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918562 | AA1-072 E | Adder | 0.06 MW | 0.05 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.46 MW | 1.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.51 MW | 0.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.86 MW | 2.86 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.88 MW | 10.88 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.3 MW | 2.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.63 MW | 5.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.43 MW | 19.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.79 MW | 12.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.88 MW | 0.88 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.65 MW | 0.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.63 MW | 1.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.95 MW | 1.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.07 MW | 10.07 MW |
| Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.38 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.1 MW | 0.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.37 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.95 MW | 4.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.95 MW | 4.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.38 MW | 2.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.48 MW | 1.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.12 MW | 1.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.64 MW | 3.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | Adder | 3.3 MW | 2.8 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | Adder | 3.26 MW | 2.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | Adder | 2.34 MW | 1.99 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | Adder | 6.8 MW | 5.78 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | Adder | 0.4 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | Adder | 4.32 MW | 3.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | Adder | 2.58 MW | 2.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | Adder | 1.45 MW | 1.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | Adder | 0.85 MW | 0.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | Adder | 8.44 MW | 7.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | Adder | 4.51 MW | 3.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934521 | AD1-076 C | Adder | 22.4 MW | 19.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934522 | AD1-076 E | Adder | 11.4 MW | 9.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | Adder | 0.88 MW | 0.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | Adder | 0.38 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.76 MW | 1.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.64 MW | 3.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.42 MW | 2.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315294 | 1DOMTR10 | Adder | 4.71 MW | 4.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | Adder | 0.19 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | Adder | 0.75 MW | 0.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | Adder | 0.37 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922922 | AB1-081 C OP | Adder | 5.49 MW | 4.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 16.0 MW | 16.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.86 MW | 6.86 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 1.28 MW | 1.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.96 MW | 8.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.33 MW | 7.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.33 MW | 2.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.1 MW | 1.78 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.99 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.66 MW | 2.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | Adder | 6.16 MW | 5.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | Adder | 3.04 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.61 MW | 0.52 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.74 MW | 2.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.17 MW | 2.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.45 MW | 1.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | Adder | 10.82 MW | 9.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | Adder | 5.44 MW | 4.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.28 MW | 3.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 1.21 MW | 1.03 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.94 MW | 35.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 24.23 MW | 24.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 30.08 MW | 30.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 1.0 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | Adder | 2.47 MW | 2.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | Adder | 4.02 MW | 3.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | Adder | 1.08 MW | 0.92 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | Adder | 1.49 MW | 1.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | Adder | 0.97 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | Adder | 1.59 MW | 1.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.64 MW | 3.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.6 MW | 2.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | Adder | 4.04 MW | 3.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | Adder | 6.58 MW | 5.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938221 | AE1-035 C | Adder | 1.25 MW | 1.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.16 MW | 6.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920672 | AA2-174 E OP | Adder | 0.38 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923911 | AB2-031 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923912 | AB2-031 E O1 | 50/50 | 1.34 MW | 1.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.4 MW | 1.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924501 | AB2-099 C | Adder | 0.37 MW | 0.31 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924502 | AB2-099 E | Adder | 0.16 MW | 0.13 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924512 | AB2-100 E | 50/50 | 9.84 MW | 9.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925172 | AB2-174 E O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925781 | AC1-054 C O1 | Adder | 4.72 MW | 4.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925782 | AC1-054 E O1 | Adder | 2.18 MW | 1.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 C | 50/50 | 23.56 MW | 23.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926072 | AC1-086 E | 50/50 | 10.72 MW | 10.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927021 | AC1-189 C | Adder | 4.71 MW | 4.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927022 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927141 | AC1-208 C | Adder | 6.76 MW | 5.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927142 | AC1-208 E | Adder | 3.0 MW | 2.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936261 | AD2-033 C | Adder | 5.34 MW | 4.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936262 | AD2-033 E | Adder | 3.56 MW | 3.03 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C O1 | Adder | 4.79 MW | 4.07 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E O1 | Adder | 3.19 MW | 2.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923572 | AB1-173 C OP | 50/50 | 2.75 MW | 2.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923582 | AB1-173AC OP | 50/50 | 2.75 MW | 2.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923583 | AB1-173AE OP | 50/50 | 1.28 MW | 1.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C O1 | Adder | 4.83 MW | 4.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E O1 | Adder | 2.6 MW | 2.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 907092 | X1-038 E | Adder | 3.04 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924511 | AB2-100 C | 50/50 | 3.47 MW | 3.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925061 | AB2-161 C O1 | 50/50 | 4.5 MW | 4.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925062 | AB2-161 E O1 | 50/50 | 7.34 MW | 7.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925171 | AB2-174 C O1 | 50/50 | 1.56 MW | 1.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934571 | AD1-082 C | 50/50 | 10.25 MW | 10.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934572 | AD1-082 E | 50/50 | 5.85 MW | 5.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C O1 | Adder | 1.46 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E O1 | Adder | 2.01 MW | 1.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939191 | AE1-149 C O1 | 50/50 | 18.48 MW | 18.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939192 | AE1-149 E O1 | 50/50 | 12.32 MW | 12.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 O1 | 50/50 | 6.59 MW | 6.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918561 | AA1-072 C | Adder | 0.23 MW | 0.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918562 | AA1-072 E | Adder | 0.11 MW | 0.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 3.94 MW | 3.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.14 MW | 1.82 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.46 MW | 2.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.39 MW | 0.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.36 MW | 2.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.25 MW | 8.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.9 MW | 3.9 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 15.09 MW | 15.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 9.67 MW | 9.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.61 MW | 0.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.49 MW | 0.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.61 MW | 1.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.72 MW | 7.72 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.94 MW | 3.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.76 MW | 3.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.61 MW | 8.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.28 MW | 1.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.29 MW | 13.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.7 MW | 4.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.4 MW | 2.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.91 MW | 1.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.12 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.79 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 8.14 MW | 6.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.45 MW | 4.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.24 MW | 1.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.69 MW | 0.59 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.86 MW | 19.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.25 MW | 16.25 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.69 MW | 2.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.29 MW | 1.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.13 MW | 6.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.14 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.0 MW | 13.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.05 MW | 6.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 1.75 MW | 1.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.19 MW | 3.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.41 MW | 1.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920671 | AA2-174 C OP | 50/50 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920672 | AA2-174 E OP | 50/50 | 0.99 MW | 0.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923911 | AB2-031 C O1 | 50/50 | 6.05 MW | 6.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923912 | AB2-031 E O1 | 50/50 | 2.98 MW | 2.98 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.8 MW | 1.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924501 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924502 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925172 | AB2-174 E O1 | 50/50 | 17.15 MW | 17.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925781 | AC1-054 C O1 | 50/50 | 10.69 MW | 10.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925782 | AC1-054 E O1 | 50/50 | 4.92 MW | 4.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927141 | AC1-208 C | 50/50 | 11.27 MW | 11.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927142 | AC1-208 E | 50/50 | 5.01 MW | 5.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936261 | AD2-033 C | Adder | 6.88 MW | 5.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936262 | AD2-033 E | Adder | 4.58 MW | 3.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C O1 | Adder | 8.48 MW | 7.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E O1 | Adder | 5.65 MW | 4.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940241 | AE2-006 | Adder | 0.24 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923572 | AB1-173 C OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923582 | AB1-173AC OP | 50/50 | 6.09 MW | 6.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923583 | AB1-173AE OP | 50/50 | 2.84 MW | 2.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925611 | AC1-036 C | Adder | 0.48 MW | 0.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.78 MW | 0.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 907092 | X1-038 E | Adder | 4.38 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925171 | AB2-174 C O1 | 50/50 | 3.29 MW | 3.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C O1 | Adder | 2.1 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E O1 | Adder | 2.9 MW | 2.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918561 | AA1-072 C | Adder | 0.21 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918562 | AA1-072 E | Adder | 0.1 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.86 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.23 MW | 1.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 1.02 MW | 1.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 0.84 MW | 0.84 MW |
| Details for 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6SKIFF CREEK-6KINGS M 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6KINGS M-6PENNIMAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934521 | AD1-076 C | Adder | 20.56 MW | 17.48 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944011 | AF1-069 C | Adder | 3.39 MW | 2.88 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315294 | 1DOMTR10 | Adder | 3.93 MW | 3.34 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940491 | AE2-034 C | Adder | 2.85 MW | 2.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941031 | AE2-094 C | Adder | 10.39 MW | 8.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957521 | AF2-046 C | Adder | 5.6 MW | 4.76 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957531 | AF2-047 C | Adder | 6.78 MW | 5.77 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 940641 | AE2-051 C O1 | Adder | 5.38 MW | 4.57 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314295 | 6BIRDNECK | 80/20 | 0.02 MW | 0.02 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314421 | 6WINCHST | 80/20 | 0.12 MW | 0.12 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314491 | 3PENDLTN | 80/20 | 0.16 MW | 0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314507 | 3THOMPSN | 80/20 | 0.16 MW | 0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314638 | 6ELIZ CT | 80/20 | 0.1 MW | 0.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314639 | 6TANGLEW | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 314643 | 3O INLET | 80/20 | 0.21 MW | 0.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315092 | 1YORKTN3 | 80/20 | 21.83 MW | 21.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926661 | AC1-147 C | 80/20 | 1.05 MW | 1.05 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 934061 | AD1-033 C | 80/20 | 3.51 MW | 3.51 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 935111 | AD1-144 C | 80/20 | 0.84 MW | 0.84 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936581 | AD2-073 C | Adder | -1.72 MW | -1.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936661 | AD2-085 C | Adder | 1.18 MW | 1.01 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 937221 | AD2-160 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942341 | AE2-247 C | Adder | 0.51 MW | 0.43 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 942401 | AE2-253 C | 80/20 | 2.85 MW | 2.85 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943461 | AF1-017 C | Adder | 0.46 MW | 0.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943611 | AF1-032 C | 80/20 | 0.81 MW | 0.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 943621 | AF1-033 C | 80/20 | 1.1 MW | 1.1 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944871 | AF1-152 C | 80/20 | 2.34 MW | 2.34 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945361 | AF1-201 C O1 | 80/20 | 6.61 MW | 6.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 945831 | AF1-248 | Adder | -0.28 MW | -0.23 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315098 | 1CHESPKA | 80/20 | 0.21 MW | 0.21 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315099 | 1CHESPKB | 80/20 | 0.36 MW | 0.36 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315108 | 1ELIZAR1 | 80/20 | 1.58 MW | 1.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315109 | 1ELIZAR2 | 80/20 | 1.56 MW | 1.56 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315110 | 1ELIZAR3 | 80/20 | 1.61 MW | 1.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315233 | 1SURRY 2 | 80/20 | 15.81 MW | 15.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315260 | 1GOSPORTA | 80/20 | 0.17 MW | 0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315261 | 1GOSPORTB | 80/20 | 0.22 MW | 0.22 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315262 | 1GOSPORTC | 80/20 | 0.19 MW | 0.19 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315603 | 6AA1-139SOLA | 80/20 | 1.2 MW | 1.2 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315605 | 6W1-029WIND | 80/20 | 0.37 MW | 0.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 315611 | 6Z1-036WIND | 80/20 | 1.82 MW | 1.82 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932591 | AC2-079 C O1 | Adder | 1.99 MW | 1.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938221 | AE1-035 C | Adder | 0.78 MW | 0.66 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939431 | AE1-175 C | 80/20 | 1.31 MW | 1.31 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941101 | AE2-104 C O1 | 80/20 | 1.42 MW | 1.42 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941281 | AE2-122 C O1 | 80/20 | 13.26 MW | 13.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941291 | AE2-123 C O1 | 80/20 | 13.62 MW | 13.62 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941301 | AE2-124 C O1 | 80/20 | 12.39 MW | 12.39 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957491 | AF2-043 C | 80/20 | 0.99 MW | 0.99 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957631 | AF2-057 | 80/20 | 1.66 MW | 1.66 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941501 | AE2-147 C | 80/20 | 7.03 MW | 7.03 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941581 | AE2-155 C | Adder | -0.18 MW | -0.16 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 941591 | AE2-156 O1 | 80/20 | 8.33 MW | 8.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 957871 | AF2-081 C | 80/20 | 4.6 MW | 4.6 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 958161 | AF2-110 C | 80/20 | 0.58 MW | 0.58 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 924501 | AB2-099 C | Adder | 0.19 MW | 0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 923831 | AB2-022 C | 80/20 | 1.04 MW | 1.04 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 926751 | AC1-161 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 932041 | AC2-012 C | 80/20 | 3.73 MW | 3.73 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933291 | AC2-141 C | 80/20 | 15.69 MW | 15.69 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938531 | AE1-072 C O1 | 80/20 | 8.06 MW | 8.06 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 938771 | AE1-103 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939311 | AE1-162 C | 80/20 | 0.91 MW | 0.91 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 939411 | AE1-173 C | Adder | 31.67 MW | 26.92 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 936341 | AD2-044 C | Adder | -0.2 MW | -0.17 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933261 | AC2-137 C | Adder | -0.71 MW | -0.61 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933271 | AC2-138 C | Adder | -0.63 MW | -0.54 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 918561 | AA1-072 C | Adder | 0.11 MW | 0.09 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944581 | AF1-123 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944591 | AF1-124 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 944601 | AF1-125 C O1 | 80/20 | 22.81 MW | 22.81 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | 933981 | AD1-022 C | Adder | 3.24 MW | 2.75 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.9 MW | 1.9 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.0 MW | 6.0 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.33 MW | 1.33 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 12.52 MW | 12.52 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 7.26 MW | 7.26 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.46 MW | 0.46 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.83 MW | 0.83 MW |
| 6PENNIMAN-6WALR209 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 567 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 4.62 MW | 4.62 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.5 MW | 0.5 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.45 MW | 1.45 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.38 MW | 1.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.56 MW | 4.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.83 MW | 2.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.14 MW | 2.14 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 7.0 MW | 7.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.43 MW | 6.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.15 MW | 2.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.71 MW | 15.71 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 41.25 MW | 41.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.45 MW | 1.45 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.98 MW | 2.98 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 8.75 MW | 8.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.53 MW | 1.53 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 9.28 MW | 9.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.8 MW | 30.8 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.96 MW | 0.96 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.09 MW | 7.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.16 MW | 9.16 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.24 MW | 4.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.64 MW | 4.64 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.43 MW | 14.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.07 MW | 10.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.9 MW | 7.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.74 MW | 0.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 7.0 MW | 7.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.17 MW | 1.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.29 MW | 1.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.63 MW | 2.63 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.29 MW | 0.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.29 MW | 1.29 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.07 MW | 0.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 1.9 MW | 1.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 45.35 MW | 45.35 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 8.7 MW | 8.7 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 9.28 MW | 9.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.54 MW | 8.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924511 | AB2-100 C | 80/20 | 7.4 MW | 7.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938771 | AE1-103 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.38 MW | 0.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.58 MW | 7.58 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.83 MW | 1.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.48 MW | 0.48 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.16 MW | 3.16 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.33 MW | 10.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.17 MW | 2.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.26 MW | 19.26 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.07 MW | 12.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.61 MW | 0.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.15 MW | 2.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 9.74 MW | 9.74 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314582 | 3KELFORD | 80/20 | 0.44 MW | 0.44 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315126 | 1ROARAP2 | 80/20 | 1.85 MW | 1.85 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315128 | 1ROARAP4 | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315131 | 1EDGECMA | 80/20 | 7.95 MW | 7.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315132 | 1EDGECMB | 80/20 | 7.95 MW | 7.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315136 | 1ROSEMG1 | 80/20 | 4.27 MW | 4.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315137 | 1ROSEMS1 | 80/20 | 2.65 MW | 2.65 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315138 | 1ROSEMG2 | 80/20 | 2.0 MW | 2.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315139 | 1GASTONA | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926201 | AC1-098 C | 80/20 | 6.32 MW | 6.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926211 | AC1-099 C | 80/20 | 2.12 MW | 2.12 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934331 | AD1-057 C O1 | 80/20 | 14.57 MW | 14.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934521 | AD1-076 C | 80/20 | 31.96 MW | 31.96 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 943171 | AE2-346 C | 80/20 | 1.25 MW | 1.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 944141 | AF1-082 | 80/20 | 2.76 MW | 2.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315294 | 1DOMTR10 | 80/20 | 6.83 MW | 6.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.83 MW | 1.83 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923262 | AB1-132 C OP | 80/20 | 28.9 MW | 28.9 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923991 | AB2-040 C O1 | 80/20 | 9.31 MW | 9.31 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925121 | AB2-169 C | 80/20 | 0.76 MW | 0.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 932631 | AC2-084 C | 80/20 | 9.02 MW | 9.02 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940491 | AE2-034 C | 80/20 | 3.41 MW | 3.41 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957521 | AF2-046 C | 80/20 | 14.25 MW | 14.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957531 | AF2-047 C | 80/20 | 8.09 MW | 8.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957861 | AF2-080 C | 80/20 | 6.63 MW | 6.63 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315115 | 1S HAMPT1 | 80/20 | 0.91 MW | 0.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315141 | 1GASTONB | 80/20 | 6.57 MW | 6.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315292 | 1DOMTR78 | 80/20 | 0.92 MW | 0.92 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.61 MW | 1.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.87 MW | 0.87 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938221 | AE1-035 C | 80/20 | 1.91 MW | 1.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314574 | 6EVERETS | 80/20 | 0.23 MW | 0.23 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315612 | 3AA2-057SOLA | 80/20 | 1.27 MW | 1.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923911 | AB2-031 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924501 | AB2-099 C | 80/20 | 0.52 MW | 0.52 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925781 | AC1-054 C O1 | 80/20 | 4.17 MW | 4.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926071 | AC1-086 C | 80/20 | 42.56 MW | 42.56 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927021 | AC1-189 C | 80/20 | 7.3 MW | 7.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927141 | AC1-208 C | 80/20 | 9.79 MW | 9.79 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923572 | AB1-173 C OP | 80/20 | 2.86 MW | 2.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923582 | AB1-173AC OP | 80/20 | 2.86 MW | 2.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 960331 | AF2-324 C O1 | 80/20 | 7.76 MW | 7.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315614 | AA2-178 C | 80/20 | 0.79 MW | 0.79 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924511 | AB2-100 C | 80/20 | 6.88 MW | 6.88 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925171 | AB2-174 C O1 | 80/20 | 1.54 MW | 1.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938771 | AE1-103 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 918561 | AA1-072 C | 80/20 | 0.33 MW | 0.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 933981 | AD1-022 C | 80/20 | 5.75 MW | 5.75 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.33 MW | 1.33 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.74 MW | 2.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.8 MW | 8.8 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.85 MW | 1.85 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.69 MW | 16.69 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.32 MW | 10.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.54 MW | 0.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.32 MW | 1.32 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.86 MW | 1.86 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.16 MW | 8.16 MW |
| Details for AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.2 MW | 0.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 1.21 MW | 1.21 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 1.15 MW | 1.15 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.49 MW | 7.49 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.49 MW | 7.49 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 4.17 MW | 4.17 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.59 MW | 2.59 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 6.42 MW | 6.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.13 MW | 0.13 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 5.09 MW | 5.09 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 1.71 MW | 1.71 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.36 MW | 29.36 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.04 MW | 1.04 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.54 MW | 2.54 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 6.3 MW | 6.3 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 1.24 MW | 1.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 7.89 MW | 7.89 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 28.25 MW | 28.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.7 MW | 0.7 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.02 MW | 6.02 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 7.25 MW | 7.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940491 | AE2-034 C | 80/20 | 3.12 MW | 3.12 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 3.94 MW | 3.94 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 11.0 MW | 11.0 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | 80/20 | 7.42 MW | 7.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.2 MW | 6.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.06 MW | 0.06 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.65 MW | 0.65 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 6.42 MW | 6.42 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.84 MW | 0.84 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.61 MW | 0.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 1.76 MW | 1.76 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314574 | 6EVERETS | 80/20 | 0.21 MW | 0.21 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315612 | 3AA2-057SOLA | 80/20 | 1.07 MW | 1.07 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 920671 | AA2-174 C OP | 80/20 | 0.06 MW | 0.06 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924151 | AB2-059 C OP | 80/20 | 1.61 MW | 1.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924501 | AB2-099 C | 80/20 | 0.43 MW | 0.43 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925781 | AC1-054 C O1 | 80/20 | 2.91 MW | 2.91 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926071 | AC1-086 C | 80/20 | 41.61 MW | 41.61 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927021 | AC1-189 C | 80/20 | 6.82 MW | 6.82 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927141 | AC1-208 C | 80/20 | 7.59 MW | 7.59 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315614 | AA2-178 C | 80/20 | 0.72 MW | 0.72 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 924511 | AB2-100 C | 80/20 | 7.19 MW | 7.19 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 938771 | AE1-103 C O1 | 80/20 | 0.97 MW | 0.97 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 918561 | AA1-072 C | 80/20 | 0.28 MW | 0.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.28 MW | 5.28 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.22 MW | 1.22 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.55 MW | 2.55 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.27 MW | 8.27 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 15.57 MW | 15.57 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 9.69 MW | 9.69 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.5 MW | 0.5 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.74 MW | 1.74 MW |
| AB2-100 TAP-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.72 MW | 7.72 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315611 | 6Z1-036WIND | Adder | -2.17 MW | -1.85 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 8.71 MW | 8.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.76 MW | 0.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.25 MW | 0.25 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.3 MW | 0.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.69 MW | 1.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.61 MW | 1.61 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 8.08 MW | 8.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 8.08 MW | 8.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 2.9 MW | 2.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 1.36 MW | 1.36 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 4.31 MW | 4.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926201 | AC1-098 C | 80/20 | 8.23 MW | 8.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926211 | AC1-099 C | 80/20 | 2.76 MW | 2.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 11.47 MW | 11.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 65.93 MW | 65.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 2.32 MW | 2.32 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 2.87 MW | 2.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 2.87 MW | 2.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315294 | 1DOMTR10 | 80/20 | 13.66 MW | 13.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.94 MW | 1.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 8.94 MW | 8.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 18.98 MW | 18.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 8.46 MW | 8.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925121 | AB2-169 C | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 6.83 MW | 6.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 932631 | AC2-084 C | 80/20 | 11.73 MW | 11.73 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940491 | AE2-034 C | 80/20 | 6.26 MW | 6.26 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 4.47 MW | 4.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | Adder | 1.95 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 1.71 MW | 1.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 20.56 MW | 20.56 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957531 | AF2-047 C | 80/20 | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957861 | AF2-080 C | 80/20 | 9.98 MW | 9.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 18.98 MW | 18.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 15.89 MW | 15.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.11 MW | 0.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 935111 | AD1-144 C | Adder | -0.77 MW | -0.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943611 | AF1-032 C | Adder | -0.87 MW | -0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 4.31 MW | 4.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.83 MW | 1.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.52 MW | 1.52 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.85 MW | 0.85 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 4.74 MW | 4.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314574 | 6EVERETS | 80/20 | 0.42 MW | 0.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315612 | 3AA2-057SOLA | 80/20 | 1.41 MW | 1.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 920671 | AA2-174 C OP | 80/20 | 0.09 MW | 0.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923911 | AB2-031 C O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924151 | AB2-059 C OP | 80/20 | 1.83 MW | 1.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924501 | AB2-099 C | 80/20 | 0.97 MW | 0.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925781 | AC1-054 C O1 | 80/20 | 5.54 MW | 5.54 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926071 | AC1-086 C | 80/20 | 27.94 MW | 27.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 927021 | AC1-189 C | 80/20 | 10.99 MW | 10.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 927141 | AC1-208 C | 80/20 | 10.87 MW | 10.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C O1 | Adder | 5.26 MW | 4.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923572 | AB1-173 C OP | 80/20 | 2.6 MW | 2.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923582 | AB1-173AC OP | 80/20 | 2.6 MW | 2.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C O1 | 80/20 | 7.88 MW | 7.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315614 | AA2-178 C | 80/20 | 1.45 MW | 1.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924511 | AB2-100 C | 80/20 | 2.5 MW | 2.5 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925171 | AB2-174 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 918561 | AA1-072 C | 80/20 | 0.57 MW | 0.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 12.65 MW | 12.65 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 3.29 MW | 3.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.71 MW | 3.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.65 MW | 12.65 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.63 MW | 2.63 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.73 MW | 22.73 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.71 MW | 14.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.7 MW | 0.7 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.95 MW | 1.95 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.53 MW | 2.53 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.37 MW | 12.37 MW |
| Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.08 MW | 0.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314582 | 3KELFORD | 80/20 | 0.76 MW | 0.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.25 MW | 0.25 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.3 MW | 0.3 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.69 MW | 1.69 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.61 MW | 1.61 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 8.08 MW | 8.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 8.08 MW | 8.08 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 2.9 MW | 2.9 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 1.8 MW | 1.8 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 1.36 MW | 1.36 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 4.31 MW | 4.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926201 | AC1-098 C | 80/20 | 8.23 MW | 8.23 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926211 | AC1-099 C | 80/20 | 2.76 MW | 2.76 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 11.47 MW | 11.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934521 | AD1-076 C | 80/20 | 65.93 MW | 65.93 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | 80/20 | 2.32 MW | 2.32 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 2.87 MW | 2.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 2.87 MW | 2.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315294 | 1DOMTR10 | 80/20 | 13.66 MW | 13.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.94 MW | 1.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 8.94 MW | 8.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 18.98 MW | 18.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 8.46 MW | 8.46 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925121 | AB2-169 C | 80/20 | 1.47 MW | 1.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 6.83 MW | 6.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 932631 | AC2-084 C | 80/20 | 11.73 MW | 11.73 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940491 | AE2-034 C | 80/20 | 6.26 MW | 6.26 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 4.47 MW | 4.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | Adder | 1.95 MW | 1.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 1.71 MW | 1.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957521 | AF2-046 C | 80/20 | 20.56 MW | 20.56 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957531 | AF2-047 C | 80/20 | 14.88 MW | 14.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957861 | AF2-080 C | 80/20 | 9.98 MW | 9.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 18.98 MW | 18.98 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 15.89 MW | 15.89 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314589 | 3MURPHYS | 80/20 | 0.11 MW | 0.11 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 935111 | AD1-144 C | Adder | -0.77 MW | -0.66 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943611 | AF1-032 C | Adder | -0.87 MW | -0.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 4.31 MW | 4.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315292 | 1DOMTR78 | 80/20 | 1.83 MW | 1.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.52 MW | 1.52 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.85 MW | 0.85 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938221 | AE1-035 C | 80/20 | 4.74 MW | 4.74 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314574 | 6EVERETS | 80/20 | 0.42 MW | 0.42 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315612 | 3AA2-057SOLA | 80/20 | 1.41 MW | 1.41 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 920671 | AA2-174 C OP | 80/20 | 0.09 MW | 0.09 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923911 | AB2-031 C O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924151 | AB2-059 C OP | 80/20 | 1.83 MW | 1.83 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924501 | AB2-099 C | 80/20 | 0.97 MW | 0.97 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925781 | AC1-054 C O1 | 80/20 | 5.54 MW | 5.54 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926071 | AC1-086 C | 80/20 | 27.94 MW | 27.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 927021 | AC1-189 C | 80/20 | 10.99 MW | 10.99 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 927141 | AC1-208 C | 80/20 | 10.87 MW | 10.87 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C O1 | Adder | 5.26 MW | 4.47 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923572 | AB1-173 C OP | 80/20 | 2.6 MW | 2.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923582 | AB1-173AC OP | 80/20 | 2.6 MW | 2.6 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C O1 | 80/20 | 7.88 MW | 7.88 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315614 | AA2-178 C | 80/20 | 1.45 MW | 1.45 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924511 | AB2-100 C | 80/20 | 2.5 MW | 2.5 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925171 | AB2-174 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 918561 | AA1-072 C | 80/20 | 0.57 MW | 0.57 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 933981 | AD1-022 C | 80/20 | 12.65 MW | 12.65 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315602 | 1HOLLOMANSOL | 80/20 | 3.29 MW | 3.29 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.61 MW | 0.61 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.71 MW | 3.71 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.64 MW | 12.64 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 22.72 MW | 22.72 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.7 MW | 14.7 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.7 MW | 0.7 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.94 MW | 1.94 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.53 MW | 2.53 MW |
| 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.36 MW | 12.36 MW |
| Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.04 MW | 0.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | Adder | 2.88 MW | 2.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | Adder | 2.88 MW | 2.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.0 MW | 1.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.48 MW | 1.48 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | Adder | 2.38 MW | 2.03 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | Adder | 0.8 MW | 0.68 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | Adder | 4.02 MW | 3.42 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 19.8 MW | 16.83 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | Adder | 11.92 MW | 10.13 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | Adder | 0.55 MW | 0.47 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | Adder | 4.35 MW | 3.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | Adder | 1.03 MW | 0.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.94 MW | 3.35 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | Adder | 3.21 MW | 2.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 6.5 MW | 6.5 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | Adder | 2.45 MW | 2.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | Adder | 3.4 MW | 2.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 2.58 MW | 2.19 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | Adder | 1.61 MW | 1.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | Adder | 13.3 MW | 11.31 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | Adder | 6.67 MW | 5.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 6.12 MW | 5.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 2.8 MW | 2.38 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 10.4 MW | 10.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | Adder | 5.74 MW | 4.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 8.71 MW | 8.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.29 MW | 0.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315065 | 1CHESTF6 | 80/20 | 172.36 MW | 172.36 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315074 | 1HOPCGN1 | 80/20 | 6.06 MW | 6.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315075 | 1HOPCGN2 | 80/20 | 5.98 MW | 5.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315076 | 1HOPPOLC | 80/20 | 1.21 MW | 1.21 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315077 | 1HOPHCF1 | 80/20 | 1.89 MW | 1.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315078 | 1HOPHCF2 | 80/20 | 1.89 MW | 1.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315079 | 1HOPHCF3 | 80/20 | 1.89 MW | 1.89 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315080 | 1HOPHCF4 | 80/20 | 2.86 MW | 2.86 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926661 | AC1-147 C | Adder | 0.76 MW | 0.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934061 | AD1-033 C | Adder | 2.47 MW | 2.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935111 | AD1-144 C | Adder | 0.6 MW | 0.51 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936661 | AD2-085 C | 80/20 | 1.69 MW | 1.69 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937221 | AD2-160 C O1 | Adder | 1.94 MW | 1.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942161 | AE2-228 C | 80/20 | 2.92 MW | 2.92 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942341 | AE2-247 C | 80/20 | 0.73 MW | 0.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942401 | AE2-253 C | Adder | 2.04 MW | 1.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943461 | AF1-017 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943611 | AF1-032 C | Adder | 0.6 MW | 0.51 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943621 | AF1-033 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944871 | AF1-152 C | Adder | 1.81 MW | 1.54 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958501 | AF2-144 C | Adder | -0.62 MW | -0.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315116 | 1SURRY 1 | 80/20 | 11.65 MW | 11.65 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315117 | 1GRAVELC | 80/20 | 0.41 MW | 0.41 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315119 | 1GRAVEL3 | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315120 | 1GRAVEL4 | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315121 | 1GRAVEL5 | 80/20 | 1.18 MW | 1.18 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315122 | 1GRAVEL6 | 80/20 | 1.2 MW | 1.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.48 MW | 1.48 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315611 | 6Z1-036WIND | Adder | 1.49 MW | 1.26 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932591 | AC2-079 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | Adder | 0.86 MW | 0.73 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | Adder | 4.11 MW | 3.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 2.75 MW | 2.75 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941101 | AE2-104 C O1 | Adder | 1.29 MW | 1.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941281 | AE2-122 C O1 | Adder | 9.44 MW | 8.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941291 | AE2-123 C O1 | Adder | 9.7 MW | 8.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941301 | AE2-124 C O1 | Adder | 8.81 MW | 7.49 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946261 | AF1-291 C | 80/20 | 2.94 MW | 2.94 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957491 | AF2-043 C | Adder | 0.73 MW | 0.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957631 | AF2-057 | Adder | 1.2 MW | 1.02 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941501 | AE2-147 C | Adder | 5.44 MW | 4.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941591 | AE2-156 O1 | Adder | 6.01 MW | 5.11 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942001 | AE2-212 C | 80/20 | 2.53 MW | 2.53 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957871 | AF2-081 C | Adder | 3.31 MW | 2.81 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 958161 | AF2-110 C | Adder | 0.53 MW | 0.45 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923911 | AB2-031 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924501 | AB2-099 C | Adder | 0.23 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925781 | AC1-054 C O1 | Adder | 2.44 MW | 2.08 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926071 | AC1-086 C | 80/20 | 9.58 MW | 9.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927021 | AC1-189 C | Adder | 3.08 MW | 2.62 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927141 | AC1-208 C | Adder | 3.53 MW | 3.0 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923572 | AB1-173 C OP | 80/20 | 1.06 MW | 1.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923582 | AB1-173AC OP | 80/20 | 1.06 MW | 1.06 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C O1 | Adder | 2.81 MW | 2.39 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923831 | AB2-022 C | Adder | 0.78 MW | 0.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924511 | AB2-100 C | 80/20 | 1.13 MW | 1.13 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924811 | AB2-134 C OP | 80/20 | 1.28 MW | 1.28 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925051 | AB2-160 C O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925061 | AB2-161 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925171 | AB2-174 C O1 | 80/20 | 0.58 MW | 0.58 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925331 | AB2-190 C | 80/20 | 11.04 MW | 11.04 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927221 | AC1-216 C O1 | 80/20 | 0.98 MW | 0.98 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932041 | AC2-012 C | Adder | 2.7 MW | 2.29 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934011 | AD1-025 C | 80/20 | 9.66 MW | 9.66 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934571 | AD1-082 C | 80/20 | 5.1 MW | 5.1 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935161 | AD1-151 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938531 | AE1-072 C O1 | Adder | 5.84 MW | 4.96 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C O1 | Adder | 1.15 MW | 0.97 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939191 | AE1-149 C O1 | 80/20 | 8.25 MW | 8.25 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939311 | AE1-162 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939411 | AE1-173 C | Adder | 29.93 MW | 25.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 O1 | 80/20 | 1.88 MW | 1.88 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942551 | AE2-270 | 80/20 | 15.4 MW | 15.4 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957711 | AF2-065 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 918561 | AA1-072 C | Adder | 0.14 MW | 0.12 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944581 | AF1-123 C O1 | Adder | 15.25 MW | 12.96 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944591 | AF1-124 C O1 | Adder | 15.25 MW | 12.96 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944601 | AF1-125 C O1 | Adder | 15.25 MW | 12.96 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 3.23 MW | 2.74 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.51 MW | 2.51 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 8.6 MW | 8.6 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.86 MW | 1.86 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.71 MW | 16.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.27 MW | 10.27 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.59 MW | 0.59 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.71 MW | 1.71 MW |
| 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.24 MW | 7.24 MW |
| Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315611 | 6Z1-036WIND | Adder | -2.17 MW | -1.85 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.79 MW | 0.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.8 MW | 7.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.37 MW | 2.37 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.47 MW | 1.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.11 MW | 1.11 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.16 MW | 0.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.08 MW | 10.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.96 MW | 113.96 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.6 MW | 0.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 21.59 MW | 21.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.74 MW | 1.74 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 8.6 MW | 8.6 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.23 MW | 15.23 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.09 MW | 2.09 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.46 MW | 11.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.92 MW | 14.92 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | Adder | 1.56 MW | 1.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.99 MW | 0.99 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.41 MW | 20.41 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.46 MW | 35.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.81 MW | 10.81 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 935111 | AD1-144 C | Adder | -0.91 MW | -0.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.46 MW | 3.46 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.89 MW | 2.89 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 8.71 MW | 8.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 5.16 MW | 5.16 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314574 | 6EVERETS | 80/20 | 0.47 MW | 0.47 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315612 | 3AA2-057SOLA | 80/20 | 1.34 MW | 1.34 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923911 | AB2-031 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924501 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925781 | AC1-054 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926071 | AC1-086 C | 80/20 | 22.43 MW | 22.43 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927021 | AC1-189 C | 80/20 | 11.9 MW | 11.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927141 | AC1-208 C | 80/20 | 10.15 MW | 10.15 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C O1 | Adder | 4.23 MW | 3.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923572 | AB1-173 C OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923582 | AB1-173AC OP | 80/20 | 1.8 MW | 1.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C O1 | 80/20 | 7.62 MW | 7.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.45 MW | 3.45 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923831 | AB2-022 C | Adder | -1.06 MW | -0.9 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924511 | AB2-100 C | 80/20 | 1.27 MW | 1.27 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925171 | AB2-174 C O1 | 80/20 | 0.93 MW | 0.93 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 918561 | AA1-072 C | 80/20 | 0.59 MW | 0.59 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.8 MW | 18.8 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.58 MW | 3.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.78 MW | 3.78 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.82 MW | 12.82 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 23.0 MW | 23.0 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.88 MW | 14.88 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.71 MW | 0.71 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.97 MW | 1.97 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.58 MW | 2.58 MW |
| 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.59 MW | 12.59 MW |
| Details for 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.5 MW | 0.5 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.45 MW | 1.45 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.38 MW | 1.38 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.57 MW | 4.57 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.83 MW | 2.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.14 MW | 2.14 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 7.01 MW | 7.01 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.44 MW | 6.44 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.16 MW | 2.16 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.73 MW | 15.73 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 41.36 MW | 41.36 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.45 MW | 1.45 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.99 MW | 2.99 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 8.77 MW | 8.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.54 MW | 1.54 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 9.3 MW | 9.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.82 MW | 30.82 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.96 MW | 0.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.1 MW | 7.1 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.18 MW | 9.18 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.25 MW | 4.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.65 MW | 4.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.46 MW | 14.46 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.1 MW | 10.1 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.92 MW | 7.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.74 MW | 0.74 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 7.01 MW | 7.01 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.17 MW | 1.17 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.3 MW | 1.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 2.64 MW | 2.64 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314574 | 6EVERETS | 80/20 | 0.29 MW | 0.29 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315612 | 3AA2-057SOLA | 80/20 | 1.29 MW | 1.29 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920671 | AA2-174 C OP | 80/20 | 0.07 MW | 0.07 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924151 | AB2-059 C OP | 80/20 | 1.9 MW | 1.9 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924501 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925781 | AC1-054 C O1 | 80/20 | 3.68 MW | 3.68 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926071 | AC1-086 C | 80/20 | 45.39 MW | 45.39 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927021 | AC1-189 C | 80/20 | 8.72 MW | 8.72 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927141 | AC1-208 C | 80/20 | 9.3 MW | 9.3 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C O1 | 80/20 | 8.55 MW | 8.55 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938771 | AE1-103 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 918561 | AA1-072 C | 80/20 | 0.38 MW | 0.38 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.6 MW | 7.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.83 MW | 1.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.18 MW | 3.18 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.61 MW | 10.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.21 MW | 2.21 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.46 MW | 19.46 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.37 MW | 12.37 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.61 MW | 0.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.17 MW | 2.17 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.18 MW | 10.18 MW |
| Details for 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314582 | 3KELFORD | 80/20 | 0.44 MW | 0.44 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315126 | 1ROARAP2 | 80/20 | 1.85 MW | 1.85 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315128 | 1ROARAP4 | 80/20 | 1.77 MW | 1.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315131 | 1EDGECMA | 80/20 | 7.96 MW | 7.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315132 | 1EDGECMB | 80/20 | 7.96 MW | 7.96 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315136 | 1ROSEMG1 | 80/20 | 4.28 MW | 4.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315137 | 1ROSEMS1 | 80/20 | 2.65 MW | 2.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315138 | 1ROSEMG2 | 80/20 | 2.0 MW | 2.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315139 | 1GASTONA | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920591 | AA2-165 C | 80/20 | 0.15 MW | 0.15 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926201 | AC1-098 C | 80/20 | 6.34 MW | 6.34 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926211 | AC1-099 C | 80/20 | 2.12 MW | 2.12 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934331 | AD1-057 C O1 | 80/20 | 14.59 MW | 14.59 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 934521 | AD1-076 C | 80/20 | 32.07 MW | 32.07 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 943171 | AE2-346 C | 80/20 | 1.25 MW | 1.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315294 | 1DOMTR10 | 80/20 | 6.86 MW | 6.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.83 MW | 1.83 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 922922 | AB1-081 C OP | 80/20 | 8.62 MW | 8.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923262 | AB1-132 C OP | 80/20 | 28.93 MW | 28.93 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923991 | AB2-040 C O1 | 80/20 | 9.33 MW | 9.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925121 | AB2-169 C | 80/20 | 0.76 MW | 0.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925591 | AC1-034 C | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 932631 | AC2-084 C | 80/20 | 9.03 MW | 9.03 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940491 | AE2-034 C | 80/20 | 3.42 MW | 3.42 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 940571 | AE2-044 C | 80/20 | 4.31 MW | 4.31 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957521 | AF2-046 C | 80/20 | 14.28 MW | 14.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957531 | AF2-047 C | 80/20 | 8.13 MW | 8.13 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 957861 | AF2-080 C | 80/20 | 6.65 MW | 6.65 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315115 | 1S HAMPT1 | 80/20 | 0.92 MW | 0.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315141 | 1GASTONB | 80/20 | 6.58 MW | 6.58 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315292 | 1DOMTR78 | 80/20 | 0.92 MW | 0.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.61 MW | 1.61 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.87 MW | 0.87 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938221 | AE1-035 C | 80/20 | 1.92 MW | 1.92 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 314574 | 6EVERETS | 80/20 | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315612 | 3AA2-057SOLA | 80/20 | 1.28 MW | 1.28 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 920671 | AA2-174 C OP | 80/20 | 0.08 MW | 0.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923911 | AB2-031 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924151 | AB2-059 C OP | 80/20 | 1.76 MW | 1.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 924501 | AB2-099 C | 80/20 | 0.52 MW | 0.52 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925781 | AC1-054 C O1 | 80/20 | 4.19 MW | 4.19 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 926071 | AC1-086 C | 80/20 | 42.6 MW | 42.6 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927021 | AC1-189 C | 80/20 | 7.32 MW | 7.32 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 927141 | AC1-208 C | 80/20 | 9.81 MW | 9.81 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923572 | AB1-173 C OP | 80/20 | 2.86 MW | 2.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 923582 | AB1-173AC OP | 80/20 | 2.86 MW | 2.86 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 960331 | AF2-324 C O1 | 80/20 | 7.77 MW | 7.77 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315614 | AA2-178 C | 80/20 | 0.79 MW | 0.79 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 925171 | AB2-174 C O1 | 80/20 | 1.55 MW | 1.55 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 938771 | AE1-103 C O1 | 80/20 | 1.36 MW | 1.36 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 918561 | AA1-072 C | 80/20 | 0.33 MW | 0.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 933981 | AD1-022 C | 80/20 | 5.76 MW | 5.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.33 MW | 1.33 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.76 MW | 2.76 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.08 MW | 9.08 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.9 MW | 1.9 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 16.89 MW | 16.89 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 10.62 MW | 10.62 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.54 MW | 0.54 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.37 MW | 1.37 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.88 MW | 1.88 MW |
| 6LAKEVEW-AB2-100 TAP 230.0 kV Ckt 1 line l/o 314572 3EMPORIA 115 925170 AB2-174 TAP 115 1 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.59 MW | 8.59 MW |
| Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315131 | 1EDGECMA | Adder | 11.39 MW | 9.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315132 | 1EDGECMB | Adder | 11.39 MW | 9.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926201 | AC1-098 C | Adder | 9.08 MW | 7.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926211 | AC1-099 C | Adder | 3.04 MW | 2.59 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927261 | AC1-222 C | Adder | 4.79 MW | 4.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934311 | AD1-055 C | Adder | 3.33 MW | 2.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934331 | AD1-057 C O1 | Adder | 14.42 MW | 12.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934521 | AD1-076 C | Adder | 83.09 MW | 70.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935171 | AD1-152 C O1 | Adder | 11.89 MW | 10.11 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937481 | AD2-202 C O1 | Adder | 3.37 MW | 2.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942461 | AE2-259 C O1 | Adder | 12.48 MW | 10.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942931 | AE2-313 C | 80/20 | 59.39 MW | 59.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943171 | AE2-346 C | Adder | 2.13 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943901 | AF1-058 C | Adder | 2.62 MW | 2.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944011 | AF1-069 C | 80/20 | 21.52 MW | 21.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944141 | AF1-082 | Adder | 4.1 MW | 3.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945811 | AF1-246 C O1 | 80/20 | 11.71 MW | 11.71 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958801 | AF2-171 C | Adder | 19.24 MW | 16.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 959311 | AF2-222 C | Adder | 21.74 MW | 18.48 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960061 | AF2-297 C | Adder | 10.49 MW | 8.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960081 | AF2-299 C | Adder | 3.82 MW | 3.25 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315294 | 1DOMTR10 | Adder | 16.47 MW | 14.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 922922 | AB1-081 C OP | Adder | 12.75 MW | 10.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923262 | AB1-132 C OP | Adder | 21.08 MW | 17.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923991 | AB2-040 C O1 | Adder | 11.06 MW | 9.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924301 | AB2-077 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924311 | AB2-078 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924321 | AB2-079 C O1 | Adder | 2.68 MW | 2.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925591 | AC1-034 C | Adder | 9.73 MW | 8.27 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932631 | AC2-084 C | Adder | 12.95 MW | 11.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938371 | AE1-056 C | Adder | 8.23 MW | 7.0 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940491 | AE2-034 C | Adder | 11.06 MW | 9.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940571 | AE2-044 C | Adder | 6.37 MW | 5.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940661 | AE2-053 O1 | Adder | 4.48 MW | 3.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941031 | AE2-094 C | 80/20 | 65.85 MW | 65.85 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941791 | AE2-182 C | Adder | 2.59 MW | 2.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946281 | AF1-292 C | Adder | 2.28 MW | 1.94 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946301 | AF1-294 C | Adder | 5.25 MW | 4.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957481 | AF2-042 C | 80/20 | 83.65 MW | 83.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957521 | AF2-046 C | Adder | 25.48 MW | 21.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957531 | AF2-047 C | Adder | 26.27 MW | 22.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957861 | AF2-080 C | Adder | 11.34 MW | 9.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958211 | AF2-115 C | Adder | 3.2 MW | 2.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940481 | AE2-033 C | Adder | 24.52 MW | 20.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940641 | AE2-051 C O1 | 80/20 | 28.91 MW | 28.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946011 | AF1-266 | Adder | 20.53 MW | 17.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933501 | AC2-165 C | Adder | 14.21 MW | 12.08 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314295 | 6BIRDNECK | 80/20 | 0.07 MW | 0.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314491 | 3PENDLTN | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314507 | 3THOMPSN | 80/20 | 0.55 MW | 0.55 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315060 | 1CHESTF5 | Adder | 81.51 MW | 69.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315065 | 1CHESTF6 | Adder | 172.86 MW | 146.93 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315074 | 1HOPCGN1 | Adder | 11.73 MW | 9.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315075 | 1HOPCGN2 | Adder | 11.58 MW | 9.84 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315083 | 1SPRUNCA | Adder | 15.54 MW | 13.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315084 | 1SPRUNCB | Adder | 15.54 MW | 13.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926661 | AC1-147 C | 80/20 | 3.53 MW | 3.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934061 | AD1-033 C | 80/20 | 11.79 MW | 11.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934141 | AD1-041 C | Adder | 6.5 MW | 5.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935111 | AD1-144 C | Adder | 2.66 MW | 2.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936151 | AD2-021 | Adder | 0.3 MW | 0.26 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936661 | AD2-085 C | Adder | 5.31 MW | 4.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 937221 | AD2-160 C O1 | 80/20 | 9.17 MW | 9.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942151 | AE2-227 C | Adder | 2.93 MW | 2.49 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942161 | AE2-228 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942341 | AE2-247 C | Adder | 2.3 MW | 1.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942371 | AE2-250 C O1 | Adder | 14.13 MW | 12.01 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942401 | AE2-253 C | 80/20 | 9.64 MW | 9.64 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943431 | AF1-014 C | Adder | 1.57 MW | 1.34 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943461 | AF1-017 C | Adder | 2.08 MW | 1.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943471 | AF1-018 | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943611 | AF1-032 C | Adder | 2.72 MW | 2.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 943621 | AF1-033 C | Adder | 3.51 MW | 2.98 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944631 | AF1-128 O1 | Adder | 63.43 MW | 53.92 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944871 | AF1-152 C | Adder | 8.22 MW | 6.99 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 945361 | AF1-201 C O1 | Adder | 22.0 MW | 18.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958501 | AF2-144 C | Adder | 2.72 MW | 2.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315098 | 1CHESPKA | 80/20 | 0.72 MW | 0.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315099 | 1CHESPKB | 80/20 | 1.2 MW | 1.2 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315102 | 1BRUNSWICKG1 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315103 | 1BRUNSWICKG2 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315104 | 1BRUNSWICKG3 | 80/20 | 14.39 MW | 14.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315105 | 1BRUNSWICKS1 | 80/20 | 29.9 MW | 29.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315108 | 1ELIZAR1 | 80/20 | 5.33 MW | 5.33 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315109 | 1ELIZAR2 | 80/20 | 5.24 MW | 5.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315110 | 1ELIZAR3 | 80/20 | 5.4 MW | 5.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315260 | 1GOSPORTA | 80/20 | 0.58 MW | 0.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315261 | 1GOSPORTB | 80/20 | 0.74 MW | 0.74 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315262 | 1GOSPORTC | 80/20 | 0.63 MW | 0.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315603 | 6AA1-139SOLA | 80/20 | 4.07 MW | 4.07 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 315611 | 6Z1-036WIND | Adder | 6.62 MW | 5.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932591 | AC2-079 C O1 | Adder | 8.84 MW | 7.52 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938221 | AE1-035 C | Adder | 3.41 MW | 2.9 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938551 | AE1-074 C | 80/20 | 3.89 MW | 3.89 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938561 | AE1-075 C | Adder | 3.2 MW | 2.72 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939431 | AE1-175 C | Adder | 3.31 MW | 2.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939611 | AE1-191 C | Adder | 12.99 MW | 11.04 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940231 | AE2-005 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940431 | AE2-027 C O1 | Adder | 18.3 MW | 15.56 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940651 | AE2-052 | Adder | 5.38 MW | 4.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941101 | AE2-104 C O1 | Adder | 5.21 MW | 4.43 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941281 | AE2-122 C O1 | 80/20 | 44.58 MW | 44.58 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941291 | AE2-123 C O1 | 80/20 | 45.81 MW | 45.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941301 | AE2-124 C O1 | 80/20 | 41.66 MW | 41.66 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 946261 | AF1-291 C | Adder | 3.08 MW | 2.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957491 | AF2-043 C | Adder | 3.33 MW | 2.83 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957601 | AF2-054 C | Adder | 2.55 MW | 2.17 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957631 | AF2-057 | 80/20 | 5.61 MW | 5.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941501 | AE2-147 C | Adder | 24.66 MW | 20.96 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941581 | AE2-155 C | Adder | 0.76 MW | 0.65 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 941591 | AE2-156 O1 | 80/20 | 28.05 MW | 28.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942001 | AE2-212 C | Adder | 3.16 MW | 2.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957831 | AF2-077 C | Adder | 2.85 MW | 2.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957871 | AF2-081 C | 80/20 | 15.63 MW | 15.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957911 | AF2-085 | 80/20 | 6.63 MW | 6.63 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 958161 | AF2-110 C | Adder | 2.13 MW | 1.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923911 | AB2-031 C O1 | Adder | 3.37 MW | 2.86 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 924501 | AB2-099 C | Adder | 0.89 MW | 0.75 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925781 | AC1-054 C O1 | Adder | 10.23 MW | 8.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926071 | AC1-086 C | Adder | 31.05 MW | 26.39 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926271 | AC1-105 C O1 | Adder | 7.47 MW | 6.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927021 | AC1-189 C | Adder | 12.49 MW | 10.62 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 927141 | AC1-208 C | Adder | 13.27 MW | 11.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934611 | AD1-087 C O1 | Adder | 11.52 MW | 9.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936261 | AD2-033 C | Adder | 17.07 MW | 14.51 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939181 | AE1-148 C O1 | Adder | 12.1 MW | 10.28 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940241 | AE2-006 | Adder | 0.63 MW | 0.54 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923572 | AB1-173 C OP | Adder | 3.39 MW | 2.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923582 | AB1-173AC OP | Adder | 3.39 MW | 2.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925611 | AC1-036 C | Adder | 1.24 MW | 1.06 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 960331 | AF2-324 C O1 | Adder | 11.12 MW | 9.45 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 314947 | 8GREENSVILLE | 80/20 | 87.61 MW | 87.61 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 923831 | AB2-022 C | Adder | 3.59 MW | 3.05 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925051 | AB2-160 C O1 | Adder | 7.96 MW | 6.76 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925061 | AB2-161 C O1 | Adder | 5.15 MW | 4.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925331 | AB2-190 C | Adder | 27.31 MW | 23.21 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926751 | AC1-161 C O1 | 80/20 | 47.95 MW | 47.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932041 | AC2-012 C | 80/20 | 12.57 MW | 12.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933291 | AC2-141 C | 80/20 | 47.95 MW | 47.95 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934011 | AD1-025 C | Adder | 24.56 MW | 20.88 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934571 | AD1-082 C | Adder | 11.74 MW | 9.97 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 934621 | AD1-088 C | Adder | 15.97 MW | 13.57 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 935161 | AD1-151 C O1 | Adder | 23.31 MW | 19.81 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938531 | AE1-072 C O1 | 80/20 | 27.47 MW | 27.47 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938771 | AE1-103 C O1 | Adder | 4.47 MW | 3.8 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939191 | AE1-149 C O1 | Adder | 16.16 MW | 13.73 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939311 | AE1-162 C | Adder | 3.26 MW | 2.77 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 939411 | AE1-173 C | 80/20 | 149.38 MW | 149.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940541 | AE2-040 O1 | Adder | 4.36 MW | 3.7 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 942551 | AE2-270 | Adder | 39.11 MW | 33.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 957711 | AF2-065 C | Adder | 19.9 MW | 16.91 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 925861 | AC1-065 C | Adder | 4.15 MW | 3.53 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 926781 | AC1-164 C | Adder | 50.74 MW | 43.13 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 936301 | AD2-039 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 938031 | AE1-004 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 932831 | AC2-110 C | Adder | 1.66 MW | 1.41 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933261 | AC2-137 C | Adder | 2.63 MW | 2.24 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 940551 | AE2-041 O1 | Adder | 8.78 MW | 7.46 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 918561 | AA1-072 C | Adder | 0.52 MW | 0.44 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944581 | AF1-123 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944591 | AF1-124 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 944601 | AF1-125 C O1 | 80/20 | 75.68 MW | 75.68 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | 933981 | AD1-022 C | Adder | 13.36 MW | 11.35 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.4 MW | 1.4 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 2.69 MW | 2.69 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 12.29 MW | 12.29 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 53.87 MW | 53.87 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.12 MW | 3.12 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 11.23 MW | 11.23 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 86.42 MW | 86.42 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 63.1 MW | 63.1 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 2.79 MW | 2.79 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.31 MW | 8.31 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 8.38 MW | 8.38 MW |
| 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 52.17 MW | 52.17 MW |
| Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.2 MW | 0.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.76 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 3.66 MW | 3.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 3.66 MW | 3.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.85 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.64 MW | 0.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 2.04 MW | 2.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.9 MW | 2.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.97 MW | 0.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927251 | AC1-221 C | Adder | 0.75 MW | 0.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927261 | AC1-222 C | Adder | 1.19 MW | 1.01 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934311 | AD1-055 C | Adder | 0.82 MW | 0.7 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934341 | AD1-058 C | Adder | 1.88 MW | 1.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 18.46 MW | 15.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934991 | AD1-131 C | Adder | 0.62 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 2.84 MW | 2.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 0.79 MW | 0.67 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 14.76 MW | 14.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943901 | AF1-058 C | Adder | 0.66 MW | 0.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 5.37 MW | 5.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.31 MW | 1.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 2.8 MW | 2.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 959311 | AF2-222 C | Adder | 5.33 MW | 4.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960061 | AF2-297 C | Adder | 2.63 MW | 2.23 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.5 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.84 MW | 3.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.8 MW | 0.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 4.07 MW | 4.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 9.0 MW | 9.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 3.11 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 4.14 MW | 4.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932761 | AC2-100 C | Adder | 1.72 MW | 1.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 2.24 MW | 1.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 1.36 MW | 1.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 16.43 MW | 16.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 1.14 MW | 1.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 20.02 MW | 17.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.98 MW | 6.98 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 5.32 MW | 4.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 3.29 MW | 2.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 17.05 MW | 17.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 6.71 MW | 6.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 14.27 MW | 14.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.47 MW | 0.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.58 MW | 3.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.58 MW | 3.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.58 MW | 3.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 7.45 MW | 7.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 2.04 MW | 2.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.73 MW | 0.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315612 | 3AA2-057SOLA | 80/20 | 0.59 MW | 0.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920671 | AA2-174 C OP | 80/20 | 0.04 MW | 0.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923911 | AB2-031 C O1 | 80/20 | 1.5 MW | 1.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924151 | AB2-059 C OP | 80/20 | 0.83 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924501 | AB2-099 C | 80/20 | 0.25 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925781 | AC1-054 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926071 | AC1-086 C | 80/20 | 13.25 MW | 13.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926271 | AC1-105 C O1 | Adder | 1.94 MW | 1.65 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927021 | AC1-189 C | Adder | 3.62 MW | 3.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927141 | AC1-208 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934611 | AD1-087 C O1 | Adder | 2.7 MW | 2.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936261 | AD2-033 C | Adder | 4.4 MW | 3.74 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940241 | AE2-006 | Adder | 0.16 MW | 0.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923572 | AB1-173 C OP | 80/20 | 1.51 MW | 1.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923582 | AB1-173AC OP | 80/20 | 1.51 MW | 1.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925611 | AC1-036 C | Adder | 0.31 MW | 0.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314947 | 8GREENSVILLE | 80/20 | 21.83 MW | 21.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924511 | AB2-100 C | 80/20 | 1.74 MW | 1.74 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925171 | AB2-174 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C O1 | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939411 | AE1-173 C | Adder | 31.3 MW | 26.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 O1 | 80/20 | 3.11 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 918561 | AA1-072 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 3.11 MW | 2.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.18 MW | 3.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.01 MW | 12.01 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.53 MW | 2.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 21.45 MW | 21.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.11 MW | 14.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.72 MW | 0.72 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.17 MW | 2.17 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.13 MW | 11.13 MW |
| Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314572 | 3EMPORIA | 80/20 | 0.06 MW | 0.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314582 | 3KELFORD | 80/20 | 0.2 MW | 0.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314704 | 3LAWRENC | 80/20 | 0.24 MW | 0.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315126 | 1ROARAP2 | 80/20 | 0.87 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315128 | 1ROARAP4 | 80/20 | 0.83 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315131 | 1EDGECMA | 80/20 | 3.73 MW | 3.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315132 | 1EDGECMB | 80/20 | 3.73 MW | 3.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315136 | 1ROSEMG1 | 80/20 | 1.54 MW | 1.54 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315137 | 1ROSEMS1 | 80/20 | 0.96 MW | 0.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315138 | 1ROSEMG2 | 80/20 | 0.72 MW | 0.72 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315139 | 1GASTONA | 80/20 | 2.33 MW | 2.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315158 | 1KERR 1 | 80/20 | 0.18 MW | 0.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315159 | 1KERR 2 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315160 | 1KERR 3 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315161 | 1KERR 4 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315162 | 1KERR 5 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926201 | AC1-098 C | 80/20 | 2.96 MW | 2.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926211 | AC1-099 C | 80/20 | 0.99 MW | 0.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934331 | AD1-057 C O1 | 80/20 | 5.78 MW | 5.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 942931 | AE2-313 C | 80/20 | 11.84 MW | 11.84 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 943171 | AE2-346 C | 80/20 | 0.56 MW | 0.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944011 | AF1-069 C | 80/20 | 4.3 MW | 4.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944141 | AF1-082 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960081 | AF2-299 C | 80/20 | 2.28 MW | 2.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315163 | 1KERR 6 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315164 | 1KERR 7 | 80/20 | 0.51 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315606 | 3AA2-053SOLA | 80/20 | 0.85 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 922922 | AB1-081 C OP | 80/20 | 4.14 MW | 4.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923262 | AB1-132 C OP | 80/20 | 10.23 MW | 10.23 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923991 | AB2-040 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924301 | AB2-077 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924311 | AB2-078 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924321 | AB2-079 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925591 | AC1-034 C | 80/20 | 3.16 MW | 3.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 932631 | AC2-084 C | 80/20 | 4.21 MW | 4.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940571 | AE2-044 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941031 | AE2-094 C | 80/20 | 13.15 MW | 13.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946281 | AF1-292 C | 80/20 | 1.36 MW | 1.36 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957521 | AF2-046 C | 80/20 | 6.41 MW | 6.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957861 | AF2-080 C | 80/20 | 3.19 MW | 3.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940481 | AE2-033 C | 80/20 | 21.68 MW | 21.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940641 | AE2-051 C O1 | Adder | 5.16 MW | 4.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946011 | AF1-266 | 80/20 | 18.15 MW | 18.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314435 | 6SAPONY | 80/20 | 0.6 MW | 0.6 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315141 | 1GASTONB | 80/20 | 2.33 MW | 2.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315607 | 3AA1-063SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 938221 | AE1-035 C | Adder | 0.83 MW | 0.71 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941581 | AE2-155 C | Adder | -0.2 MW | -0.17 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315612 | 3AA2-057SOLA | 80/20 | 0.61 MW | 0.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920671 | AA2-174 C OP | 80/20 | 0.04 MW | 0.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923911 | AB2-031 C O1 | 80/20 | 1.73 MW | 1.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924021 | AB2-043 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924151 | AB2-059 C OP | 80/20 | 0.85 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924161 | AB2-060 C OP | 80/20 | 0.63 MW | 0.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924501 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925781 | AC1-054 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926071 | AC1-086 C | 80/20 | 15.06 MW | 15.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927021 | AC1-189 C | 80/20 | 3.52 MW | 3.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927141 | AC1-208 C | 80/20 | 4.62 MW | 4.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936261 | AD2-033 C | Adder | 4.5 MW | 3.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 939181 | AE1-148 C O1 | 80/20 | 3.77 MW | 3.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923572 | AB1-173 C OP | 80/20 | 1.74 MW | 1.74 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923582 | AB1-173AC OP | 80/20 | 1.74 MW | 1.74 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960331 | AF2-324 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924511 | AB2-100 C | 80/20 | 2.13 MW | 2.13 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925171 | AB2-174 C O1 | 80/20 | 0.99 MW | 0.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925331 | AB2-190 C | Adder | -8.13 MW | -6.91 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940541 | AE2-040 O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 933261 | AC2-137 C | Adder | -0.73 MW | -0.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 918561 | AA1-072 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.87 MW | 2.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.91 MW | 10.91 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.29 MW | 2.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.28 MW | 19.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.76 MW | 12.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.63 MW | 0.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.65 MW | 1.65 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.96 MW | 1.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.36 MW | 10.36 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.05 MW | 0.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.2 MW | 0.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.21 MW | 0.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.8 MW | 0.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.76 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 3.66 MW | 3.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 3.66 MW | 3.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.37 MW | 1.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.85 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.64 MW | 0.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 2.04 MW | 2.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315160 | 1KERR 3 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.9 MW | 2.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.97 MW | 0.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927251 | AC1-221 C | Adder | 0.75 MW | 0.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927261 | AC1-222 C | Adder | 1.19 MW | 1.01 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934311 | AD1-055 C | Adder | 0.82 MW | 0.7 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934341 | AD1-058 C | Adder | 1.88 MW | 1.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934521 | AD1-076 C | Adder | 18.46 MW | 15.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934991 | AD1-131 C | Adder | 0.62 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 935171 | AD1-152 C O1 | Adder | 2.84 MW | 2.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 937481 | AD2-202 C O1 | Adder | 0.79 MW | 0.67 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 14.76 MW | 14.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943901 | AF1-058 C | Adder | 0.66 MW | 0.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 5.37 MW | 5.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.31 MW | 1.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 2.8 MW | 2.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 959311 | AF2-222 C | Adder | 5.33 MW | 4.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960061 | AF2-297 C | Adder | 2.63 MW | 2.23 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.91 MW | 1.91 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.5 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315294 | 1DOMTR10 | Adder | 3.84 MW | 3.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.8 MW | 0.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 4.07 MW | 4.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 9.0 MW | 9.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | Adder | 0.78 MW | 0.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 3.11 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 4.14 MW | 4.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932761 | AC2-100 C | Adder | 1.72 MW | 1.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940491 | AE2-034 C | Adder | 2.24 MW | 1.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 1.36 MW | 1.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 16.43 MW | 16.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 1.14 MW | 1.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 20.02 MW | 17.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 6.98 MW | 6.98 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957531 | AF2-047 C | Adder | 5.32 MW | 4.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | Adder | 3.29 MW | 2.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 17.05 MW | 17.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 6.71 MW | 6.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 14.27 MW | 14.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.47 MW | 0.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 3.58 MW | 3.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 3.58 MW | 3.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 3.58 MW | 3.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 7.45 MW | 7.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 2.04 MW | 2.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.73 MW | 0.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | Adder | 0.9 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315612 | 3AA2-057SOLA | 80/20 | 0.59 MW | 0.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920671 | AA2-174 C OP | 80/20 | 0.04 MW | 0.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923911 | AB2-031 C O1 | 80/20 | 1.5 MW | 1.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924151 | AB2-059 C OP | 80/20 | 0.83 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924501 | AB2-099 C | 80/20 | 0.25 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925781 | AC1-054 C O1 | 80/20 | 3.31 MW | 3.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926071 | AC1-086 C | 80/20 | 13.25 MW | 13.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926271 | AC1-105 C O1 | Adder | 1.94 MW | 1.65 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927021 | AC1-189 C | Adder | 3.62 MW | 3.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927141 | AC1-208 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934611 | AD1-087 C O1 | Adder | 2.7 MW | 2.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 936261 | AD2-033 C | Adder | 4.4 MW | 3.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C O1 | Adder | 3.66 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940241 | AE2-006 | Adder | 0.16 MW | 0.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923572 | AB1-173 C OP | 80/20 | 1.51 MW | 1.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923582 | AB1-173AC OP | 80/20 | 1.51 MW | 1.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925611 | AC1-036 C | Adder | 0.31 MW | 0.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314947 | 8GREENSVILLE | 80/20 | 21.83 MW | 21.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924511 | AB2-100 C | 80/20 | 1.74 MW | 1.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925171 | AB2-174 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938771 | AE1-103 C O1 | Adder | 0.9 MW | 0.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939411 | AE1-173 C | Adder | 31.3 MW | 26.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 O1 | 80/20 | 3.11 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 918561 | AA1-072 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 933981 | AD1-022 C | Adder | 3.11 MW | 2.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.18 MW | 3.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.01 MW | 12.01 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.53 MW | 2.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 21.45 MW | 21.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 14.11 MW | 14.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.72 MW | 0.72 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 2.17 MW | 2.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 11.13 MW | 11.13 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314572 | 3EMPORIA | 80/20 | 0.06 MW | 0.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314582 | 3KELFORD | 80/20 | 0.2 MW | 0.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314704 | 3LAWRENC | 80/20 | 0.24 MW | 0.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315126 | 1ROARAP2 | 80/20 | 0.87 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315128 | 1ROARAP4 | 80/20 | 0.83 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315131 | 1EDGECMA | 80/20 | 3.73 MW | 3.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315132 | 1EDGECMB | 80/20 | 3.73 MW | 3.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315136 | 1ROSEMG1 | 80/20 | 1.54 MW | 1.54 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315137 | 1ROSEMS1 | 80/20 | 0.96 MW | 0.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315138 | 1ROSEMG2 | 80/20 | 0.72 MW | 0.72 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315139 | 1GASTONA | 80/20 | 2.33 MW | 2.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315158 | 1KERR 1 | 80/20 | 0.18 MW | 0.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315159 | 1KERR 2 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315160 | 1KERR 3 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315161 | 1KERR 4 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315162 | 1KERR 5 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926201 | AC1-098 C | 80/20 | 2.96 MW | 2.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926211 | AC1-099 C | 80/20 | 0.99 MW | 0.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 934331 | AD1-057 C O1 | 80/20 | 5.78 MW | 5.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 942931 | AE2-313 C | 80/20 | 11.84 MW | 11.84 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 943171 | AE2-346 C | 80/20 | 0.56 MW | 0.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944011 | AF1-069 C | 80/20 | 4.3 MW | 4.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 944141 | AF1-082 | 80/20 | 1.33 MW | 1.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960081 | AF2-299 C | 80/20 | 2.28 MW | 2.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315163 | 1KERR 6 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315164 | 1KERR 7 | 80/20 | 0.51 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315606 | 3AA2-053SOLA | 80/20 | 0.85 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 922922 | AB1-081 C OP | 80/20 | 4.14 MW | 4.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923262 | AB1-132 C OP | 80/20 | 10.23 MW | 10.23 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923991 | AB2-040 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924301 | AB2-077 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924311 | AB2-078 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924321 | AB2-079 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925591 | AC1-034 C | 80/20 | 3.16 MW | 3.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 932631 | AC2-084 C | 80/20 | 4.21 MW | 4.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940571 | AE2-044 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941031 | AE2-094 C | 80/20 | 13.15 MW | 13.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946281 | AF1-292 C | 80/20 | 1.36 MW | 1.36 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957521 | AF2-046 C | 80/20 | 6.41 MW | 6.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 957861 | AF2-080 C | 80/20 | 3.19 MW | 3.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940481 | AE2-033 C | 80/20 | 21.68 MW | 21.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940641 | AE2-051 C O1 | Adder | 5.16 MW | 4.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 946011 | AF1-266 | 80/20 | 18.15 MW | 18.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314435 | 6SAPONY | 80/20 | 0.6 MW | 0.6 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936151 | AD2-021 | Adder | -0.08 MW | -0.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315141 | 1GASTONB | 80/20 | 2.33 MW | 2.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315607 | 3AA1-063SOLA | 80/20 | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 938221 | AE1-035 C | Adder | 0.83 MW | 0.71 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 941581 | AE2-155 C | Adder | -0.2 MW | -0.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 315612 | 3AA2-057SOLA | 80/20 | 0.61 MW | 0.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 920671 | AA2-174 C OP | 80/20 | 0.04 MW | 0.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923911 | AB2-031 C O1 | 80/20 | 1.73 MW | 1.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924021 | AB2-043 C O1 | 80/20 | 0.22 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924151 | AB2-059 C OP | 80/20 | 0.85 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924161 | AB2-060 C OP | 80/20 | 0.63 MW | 0.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924501 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925781 | AC1-054 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 926071 | AC1-086 C | 80/20 | 15.06 MW | 15.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927021 | AC1-189 C | 80/20 | 3.52 MW | 3.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 927141 | AC1-208 C | 80/20 | 4.62 MW | 4.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 936261 | AD2-033 C | Adder | 4.5 MW | 3.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 939181 | AE1-148 C O1 | 80/20 | 3.77 MW | 3.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923572 | AB1-173 C OP | 80/20 | 1.74 MW | 1.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 923582 | AB1-173AC OP | 80/20 | 1.74 MW | 1.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 960331 | AF2-324 C O1 | 80/20 | 3.64 MW | 3.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 924511 | AB2-100 C | 80/20 | 2.13 MW | 2.13 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925171 | AB2-174 C O1 | 80/20 | 0.99 MW | 0.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 925331 | AB2-190 C | Adder | -8.13 MW | -6.91 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 940541 | AE2-040 O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 933261 | AC2-137 C | Adder | -0.73 MW | -0.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | 918561 | AA1-072 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.87 MW | 2.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 10.91 MW | 10.91 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.29 MW | 2.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 19.28 MW | 19.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.76 MW | 12.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.63 MW | 0.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.65 MW | 1.65 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.96 MW | 1.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 10.36 MW | 10.36 MW |
| Details for 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314572 | 3EMPORIA | 80/20 | 0.04 MW | 0.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315126 | 1ROARAP2 | 80/20 | 0.64 MW | 0.64 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315128 | 1ROARAP4 | 80/20 | 0.61 MW | 0.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315131 | 1EDGECMA | 80/20 | 2.91 MW | 2.91 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315132 | 1EDGECMB | 80/20 | 2.91 MW | 2.91 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315136 | 1ROSEMG1 | 80/20 | 1.08 MW | 1.08 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315137 | 1ROSEMS1 | 80/20 | 0.67 MW | 0.67 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315138 | 1ROSEMG2 | 80/20 | 0.51 MW | 0.51 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315139 | 1GASTONA | 80/20 | 1.61 MW | 1.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920591 | AA2-165 C | 80/20 | 0.06 MW | 0.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926201 | AC1-098 C | 80/20 | 2.32 MW | 2.32 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926211 | AC1-099 C | 80/20 | 0.78 MW | 0.78 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934331 | AD1-057 C O1 | 80/20 | 4.22 MW | 4.22 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942931 | AE2-313 C | 80/20 | 11.7 MW | 11.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 943171 | AE2-346 C | 80/20 | 0.48 MW | 0.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944011 | AF1-069 C | 80/20 | 4.26 MW | 4.26 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 944141 | AF1-082 | 80/20 | 1.04 MW | 1.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 945811 | AF1-246 C O1 | Adder | 2.22 MW | 1.89 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960081 | AF2-299 C | 80/20 | 1.5 MW | 1.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315601 | 1CONETOE2SOL | 80/20 | 0.0 MW | 0.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315606 | 3AA2-053SOLA | 80/20 | 0.64 MW | 0.64 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 922922 | AB1-081 C OP | 80/20 | 3.24 MW | 3.24 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923262 | AB1-132 C OP | 80/20 | 7.09 MW | 7.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923991 | AB2-040 C O1 | 80/20 | 3.87 MW | 3.87 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924301 | AB2-077 C O1 | Adder | 0.61 MW | 0.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924311 | AB2-078 C O1 | Adder | 0.61 MW | 0.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924321 | AB2-079 C O1 | Adder | 0.61 MW | 0.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925591 | AC1-034 C | 80/20 | 2.47 MW | 2.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 932631 | AC2-084 C | 80/20 | 3.31 MW | 3.31 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940571 | AE2-044 C | 80/20 | 1.62 MW | 1.62 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940661 | AE2-053 O1 | Adder | 1.07 MW | 0.91 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 941031 | AE2-094 C | 80/20 | 13.03 MW | 13.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946281 | AF1-292 C | 80/20 | 0.89 MW | 0.89 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957481 | AF2-042 C | Adder | 15.86 MW | 13.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957521 | AF2-046 C | 80/20 | 5.75 MW | 5.75 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 957861 | AF2-080 C | 80/20 | 2.63 MW | 2.63 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940481 | AE2-033 C | 80/20 | 13.25 MW | 13.25 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940641 | AE2-051 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 946011 | AF1-266 | 80/20 | 11.09 MW | 11.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314314 | 3LOCKS | 80/20 | 0.45 MW | 0.45 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314435 | 6SAPONY | 80/20 | 0.37 MW | 0.37 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314589 | 3MURPHYS | 80/20 | 0.03 MW | 0.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 942371 | AE2-250 C O1 | 80/20 | 13.95 MW | 13.95 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315102 | 1BRUNSWICKG1 | 80/20 | 2.84 MW | 2.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315103 | 1BRUNSWICKG2 | 80/20 | 2.84 MW | 2.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315104 | 1BRUNSWICKG3 | 80/20 | 2.84 MW | 2.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315105 | 1BRUNSWICKS1 | 80/20 | 5.91 MW | 5.91 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315141 | 1GASTONB | 80/20 | 1.61 MW | 1.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315607 | 3AA1-063SOLA | 80/20 | 0.59 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315608 | 3AA2-088SOLA | 80/20 | 0.38 MW | 0.38 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 938221 | AE1-035 C | 80/20 | 0.73 MW | 0.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940431 | AE2-027 C O1 | 80/20 | 11.73 MW | 11.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940651 | AE2-052 | 80/20 | 1.19 MW | 1.19 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315612 | 3AA2-057SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 920671 | AA2-174 C OP | 80/20 | 0.03 MW | 0.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923911 | AB2-031 C O1 | 80/20 | 1.18 MW | 1.18 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924151 | AB2-059 C OP | 80/20 | 0.66 MW | 0.66 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924501 | AB2-099 C | 80/20 | 0.2 MW | 0.2 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925781 | AC1-054 C O1 | 80/20 | 2.62 MW | 2.62 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 926071 | AC1-086 C | 80/20 | 10.45 MW | 10.45 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927021 | AC1-189 C | 80/20 | 2.9 MW | 2.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 927141 | AC1-208 C | 80/20 | 3.54 MW | 3.54 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939181 | AE1-148 C O1 | Adder | 2.9 MW | 2.46 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923572 | AB1-173 C OP | 80/20 | 1.19 MW | 1.19 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 923582 | AB1-173AC OP | 80/20 | 1.19 MW | 1.19 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 960331 | AF2-324 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 314947 | 8GREENSVILLE | 80/20 | 17.31 MW | 17.31 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 924511 | AB2-100 C | 80/20 | 1.36 MW | 1.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925051 | AB2-160 C O1 | 80/20 | 7.85 MW | 7.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925061 | AB2-161 C O1 | Adder | 1.0 MW | 0.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 925171 | AB2-174 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 934571 | AD1-082 C | Adder | 2.29 MW | 1.95 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939191 | AE1-149 C O1 | 80/20 | 3.56 MW | 3.56 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 939411 | AE1-173 C | Adder | 25.16 MW | 21.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 940541 | AE2-040 O1 | 80/20 | 2.41 MW | 2.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 918561 | AA1-072 C | 80/20 | 0.12 MW | 0.12 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | 315602 | 1HOLLOMANSOL | 80/20 | 0.51 MW | 0.51 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.52 MW | 2.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.48 MW | 9.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.0 MW | 2.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 17.01 MW | 17.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 11.14 MW | 11.14 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MADISON | LTFEXP_MADISON->LTFIMP_MADISON | CLTF | 0.57 MW | 0.57 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.42 MW | 1.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | LTF | 1.72 MW | 1.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.74 MW | 8.74 MW |
Light Load Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 99.8 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n7541 | 230/115 kV Transformer Addition | $6,000,000 | |
| n6618.1 | Hathaway 115 kV Bus Split. | $20,749 | |
| n6118 | Upgrade the breaker leads at DVPs Battleboro terminal will bring the rating to 239/239/239 MVA (Limited by terminal equipment at Rocky Mount) | $100,000 | |
| s2825.2 | Rebuild line #55 Tarboro to Hart Mills. | $3,500,000 | |
| (TBD) | Reconductor 8.5 miles RockyMt-Battleborro with single 795 ACSS-TW per phase, upgrade disconnect switches and CT ratios. | $31,000,000 | |
| s2825.1 | Rebuild entire line#2167 Edgecombe NUG to Hathaway. | $39,500,000 | |
| b2990 | PJM Baseline Upgrade b2990. | $350,000 | |
| n6130 | Rebuild 12.4 miles of 230 kV Line 259 from Chesterfield to Basin with 2-636 ACSR. | $31,000,000 | |
| b3694.8 | Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. | $15,365,000 | |
| b3121 | PJM Baseline Upgrade b3121: Rebuild Clubhouse-Lakeview 230 kV Line #254. | $0 | |
| n6138 | Rebuild 13.7 miles of 230 kV Line 246 from Earleys to Nucor Tap with 2-636 ACSR. | $20,550,000 | |
| n6314 | Rebuild 10.28 miles of 230 kV Line 2021 from Elizabeth City to Shawboro with 2-636 ACSR. | $15,420,000 | |
| n6144 | Rebuild 20.5 miles of 230 kV Line #218 from Everetts to Greenville with 2-636 ACSR | $39,923,299 | |
| s2609.8 | Rebuild approximately 10 miles segment of 230kV Line #205 from Locks to Tyler and upgrade the terminal equipment. The minimum summer normal rating of the line segment will be 1572MVA. | $27,000,000 | |
| n6328 | Reconductor 0.64 miles of 230 kV Line 205 from Harrowgate to Tyler with 1033.5 ACSR. Uprate 4.09 miles of 230 kV Line 205 from Harrowgate to Tyler. | $2,148,000 | |
| n6179 | Rebuild 12.3 miles of 230 kV Line 2003 from Poe to Harrowgate with 2-636 ACSR. | $30,750,000 | |
| b3057 | PJM Baseline Upgrade b3057: Rebuild Waller-Skiff's Creek 230 kV Line#2154. | $0 | |
| n6849 | Rebuild 30.6 miles of 230 kV Line 246 from Nuco TP to Suffolk with 2-636 ACSR. | $45,900,000 | |
| n6178 | Rebuild 4.5 miles of 230 kV Line 2003 from Harrowgate to Tyler with 2-636 ACSR. | $11,250,000 | |
| n6324 | Replace Terminal Equipment at Surry and Chickahominy Substations | $4,000,000 | |
| n6055 | Replace Wave traps at Midlothian and North Anna 500kV substations | $300,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF2-046 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.