AF1-202 Transition Sort Retool Results -- Qualifies for Expedited Process
v1.00 released 2023-12-14 11:12
Keystone-Desoto 345 kV
34.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Eligible for Expedited Process:
The AF1-202 project has been determined to meet the initial screen to be eligible for the Expedited Process according to the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304. Though your project initially screens as eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project from the Expedited Process into TC1. Please see "Expedited Process Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Next Steps for your project:
Refreshed Retool for Projects in Expedited Process:
After the initial sorting retool, PJM will conduct a refreshed analysis of the projects in the Expedited Process with the Transition Cycle #1 projects lifted from the study case model. After this refreshed analysis (including load flow, short circuit and stability analysis), retooled System Impact Study reports can be delivered to the Project Developers. Once the project's Facilities Study report is completed (and no conditions exist that would require the project to shift to TC1, see "Expedited Process Rules" below), the final GIA will be tendered along with the Facilities Study report.
Expedited Process Rules:
Though your project initially screens to be eligible for the Expedited Process, there are several conditions identified under Tariff Part VII, Subpart B, section 304 (B) that could shift your project into TC1 until the final GIA is tendered.
- If stability analysis or a sag study is completed during the expedited process, and it is determined that a project has an estimated Network Upgrade cost greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If it is determined during the Facilities Study that the cost of a Network Upgrade is now estimated to be greater than $5,000,000, the project will be removed from the expedited process and shifted to Transition Cycle #1.
- If a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
- If the interconnected Transmission Owner identifies the need for a Network Upgrade due to a violation of their criteria that is in excess of $5M, the project will be removed from the expedited process and shifted to Transition Cycle #1.
General
The Interconnection Customer (IC), has proposed a Wind generating facility located in the AEP zone — Blackford County, Indiana. The installed facilities will have a total capability of 200.0 MW with 34.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF1-202 |
| Project Name | Keystone-Desoto 345 kV |
| Developer Name | Blackford Wind Energy, LLC |
| State | Indiana |
| County | Blackford |
| Transmission Owner | AEP |
| MFO | 200.0 MW |
| MWE | 200.0 MW |
| MWC | 34.0 MW |
| Fuel Type | Wind |
| Basecase Study Year | 2023 |
Point of Interconnection
AF1-202 will interconnect with the AEP transmission system via a new station cut into the Desoto – Keystone (Customer Owned) 345 kV circuit.
To accommodate the interconnection on the Desoto – Keystone (Customer Owned) 345 kV circuit, a new three (3) circuit breaker 345 kV switching station physically configured in a breaker and half bus arrangement but operated as a ring-bus will be constructed. Installation of associated protection and control equipment, 345 kV line risers, SCADA, and 345 kV revenue metering will also be required. AEP reserves the right to specify the final acceptable configuration considering design practices, future expansion, and compliance requirements.
Installation of the generator lead first span exiting the POI station, including the first structure outside the AEP fence, will also be included in AEP's scope. In the case where the generator lead is a single span, the structure in the customer station will be the customer's responsibility.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 34.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
AF1-268 TAP-05JAY 138.0 kV Ckt 1 line
946030 to 243319 ckt 1 |
AEP_P7-1_#11019
CONTINGENCY 'AEP_P7-1_#11019' OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1 /*05KEYSTN 345.0 - 05SORENS 345.0 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2 /*AF1-118 TAP 345.0 - 05SORENS 345.0 END |
Tower | AC | 100.31 % | 103.51 % | 409.0 | B | 423.34 | 15.51 | |
| Details for AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 247935 | V3-007 E | Adder | 11.78 MW | 10.01 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 247963 | 05HDWTR1G E | Adder | 11.78 MW | 10.01 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 926881 | AC1-175 C | Adder | 5.14 MW | 4.37 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 926882 | AC1-175 E | Adder | 8.4 MW | 7.14 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 934961 | AD1-128 C | Adder | 3.99 MW | 3.39 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 934962 | AD1-128 E | Adder | 6.5 MW | 5.53 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 942081 | AE2-220 C | Adder | 3.55 MW | 3.02 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 942082 | AE2-220 E | Adder | 4.91 MW | 4.17 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944531 | AF1-118 C O1 | Adder | 20.85 MW | 17.72 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944532 | AF1-118 E O1 | Adder | 6.29 MW | 5.34 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944541 | AF1-119 C O1 | Adder | 10.86 MW | 9.23 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944542 | AF1-119 E O1 | Adder | 4.65 MW | 3.96 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944831 | AF1-148 C O1 | Adder | 7.4 MW | 6.29 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 944832 | AF1-148 E O1 | Adder | 4.93 MW | 4.19 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 945371 | AF1-202 C O1 | Adder | 2.64 MW | 2.24 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 945372 | AF1-202 E O1 | Adder | 12.87 MW | 10.94 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 945581 | AF1-223 C O1 | Adder | 6.98 MW | 5.93 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 945582 | AF1-223 E O1 | Adder | 4.65 MW | 3.96 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 932681 | AC2-090 C | Adder | 2.57 MW | 2.19 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 932682 | AC2-090 E | Adder | 4.2 MW | 3.57 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939761 | AE1-207 C | Adder | 3.55 MW | 3.02 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939762 | AE1-207 E | Adder | 4.9 MW | 4.17 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939771 | AE1-208 C | Adder | 2.91 MW | 2.47 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939772 | AE1-208 E | Adder | 3.96 MW | 3.37 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939781 | AE1-209 C O1 | Adder | 1.01 MW | 0.86 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939782 | AE1-209 E O1 | Adder | 6.75 MW | 5.74 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939791 | AE1-210 C O1 | Adder | 1.01 MW | 0.86 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 939792 | AE1-210 E O1 | Adder | 6.75 MW | 5.74 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 941691 | AE2-169 | Adder | 1.74 MW | 1.48 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 941721 | AE2-172 | Adder | 2.11 MW | 1.8 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 946031 | AF1-268 C O1 | 50/50 | 12.94 MW | 12.94 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | 946032 | AF1-268 E O1 | 50/50 | 5.87 MW | 5.87 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.01 MW | 0.01 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 6.55 MW | 6.55 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.81 MW | 0.81 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.47 MW | 0.47 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.62 MW | 1.62 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 5.85 MW | 5.85 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.07 MW | 0.07 MW |
| AF1-268 TAP-05JAY 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
Light Load Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 34.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441
CONTINGENCY 'AEP_P1-2_#7441' OPEN BRANCH FROM BUS 242928 TO BUS 246999 CKT 1 /*05MARYSV 765.0 - 05SORENS 765.0 END |
Single | DC | 125.01 % | 126.65 % | 897.0 | B | 1136.05 | 13.48 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P4_#7445_05MARYSV 765_B
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B' OPEN BRANCH FROM BUS 242922 TO BUS 242928 CKT 1 /*05FLTLCK 765.0 - 05MARYSV 765.0 OPEN BRANCH FROM BUS 242928 TO BUS 246999 CKT 1 /*05MARYSV 765.0 - 05SORENS 765.0 END |
Breaker | AC | 104.95 % | 106.21 % | 897.0 | B | 952.7 | 13.28 | |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247255 | 05WLD G2 C | 80/20 | 0.35 MW | 0.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243859 | 05FR-11G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243862 | 05FR-12G C | 80/20 | 0.51 MW | 0.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243864 | 05FR-21G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243866 | 05FR-22G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243870 | 05FR-3G C | 80/20 | 1.06 MW | 1.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243873 | 05FR-4G C | 80/20 | 0.82 MW | 0.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247901 | 05FR-12G E | 80/20 | 2.04 MW | 2.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247902 | 05FR-21G E | 80/20 | 2.19 MW | 2.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247904 | 05FR-3G E | 80/20 | 4.24 MW | 4.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247905 | 05FR-4G E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247906 | 05MDL-1G E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247907 | 05MDL-2G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247912 | 05MDL-3G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247913 | 05MDL-4G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247958 | 05WLD G2 E | 80/20 | 4.63 MW | 4.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274847 | GR RIDGE ;BU | 80/20 | 0.87 MW | 0.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274848 | CAMPGROVE;RU | 80/20 | 0.79 MW | 0.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274850 | MENDOTA H;RU | 80/20 | 0.14 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274851 | PROVIDENC;RU | 80/20 | 0.4 MW | 0.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274853 | TWINGROVE;U1 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274854 | TWINGROVE;U2 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274855 | GSG-6 ;RU | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274859 | EASYR;U1 E | 80/20 | 2.6 MW | 2.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274860 | EASYR;U2 E | 80/20 | 2.6 MW | 2.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274861 | TOP CROP ;1U | 80/20 | 0.58 MW | 0.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274862 | TOP CROP ;2U | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274863 | CAYUGA RI;1U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274864 | CAYUGA RI;2U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274871 | GR RIDGE ;2U | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274872 | LEE DEKAL;1U | 80/20 | 1.35 MW | 1.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274877 | BISHOP HL;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274878 | BISHOP HL;2U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274879 | MINONK ;1U | 80/20 | 1.12 MW | 1.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274887 | PILOT HIL;1U | 80/20 | 1.03 MW | 1.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 275149 | KELLYCK ;1E | 80/20 | 4.13 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276158 | O-029 C | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290021 | O50 E | 80/20 | 4.48 MW | 4.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290051 | GSG-6; E | 80/20 | 2.44 MW | 2.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290108 | LEEDK;1U E | 80/20 | 5.61 MW | 5.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290261 | S-027 E | 80/20 | 4.04 MW | 4.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290265 | S-028 E | 80/20 | 4.04 MW | 4.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293061 | N-015 E | 80/20 | 3.48 MW | 3.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293516 | O-009 E1 | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293517 | O-009 E2 | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293518 | O-009 E3 | 80/20 | 1.23 MW | 1.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293644 | O22 E1 | 80/20 | 2.33 MW | 2.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293645 | O22 E2 | 80/20 | 4.53 MW | 4.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293715 | O-029 E | 80/20 | 2.35 MW | 2.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293716 | O-029 E | 80/20 | 1.29 MW | 1.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293717 | O-029 E | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293771 | O-035 E | 80/20 | 1.58 MW | 1.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294392 | P-010 E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294401 | BSHIL;1U E | 80/20 | 2.12 MW | 2.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294410 | BSHIL;2U E | 80/20 | 2.12 MW | 2.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294763 | P-046 E | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 295108 | WESTBROOK C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 917502 | Z2-087 E | 80/20 | 4.67 MW | 4.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924041 | AB2-047 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924042 | AB2-047 E O1 | 80/20 | 11.68 MW | 11.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925581 | AC1-033 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925582 | AC1-033 E | 80/20 | 4.66 MW | 4.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926821 | AC1-168 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926822 | AC1-168 E O1 | 80/20 | 3.73 MW | 3.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 927201 | AC1-214 C O1 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 927202 | AC1-214 E O1 | 80/20 | 3.23 MW | 3.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 930041 | AB1-006 C | 80/20 | 0.72 MW | 0.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 930042 | AB1-006 E | 80/20 | 4.82 MW | 4.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933281 | AC2-140 C | 80/20 | 3.09 MW | 3.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934432 | AD1-067 E | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934721 | AD1-100 C | 80/20 | 8.76 MW | 8.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934722 | AD1-100 E | 80/20 | 40.86 MW | 40.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 935141 | AD1-148 | 80/20 | 1.77 MW | 1.77 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936371 | AD2-047 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936372 | AD2-047 E O1 | 80/20 | 9.8 MW | 9.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 937001 | AD2-134 C | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 937002 | AD2-134 E | 80/20 | 4.71 MW | 4.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938861 | AE1-114 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938862 | AE1-114 E O1 | 80/20 | 6.32 MW | 6.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939321 | AE1-163 C O1 | 80/20 | 2.74 MW | 2.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939322 | AE1-163 E O1 | 80/20 | 16.81 MW | 16.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939401 | AE1-172 C O1 | 80/20 | 2.52 MW | 2.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939402 | AE1-172 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 941731 | AE2-173 O1 | 80/20 | 3.36 MW | 3.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942111 | AE2-223 C | 80/20 | 1.05 MW | 1.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942112 | AE2-223 E | 80/20 | 7.01 MW | 7.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942421 | AE2-255 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942422 | AE2-255 E O1 | 80/20 | 4.2 MW | 4.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942651 | AE2-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942652 | AE2-281 E O1 | 80/20 | 2.4 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943021 | AE2-325 C | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943801 | AF1-048 C | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943802 | AF1-048 E | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944242 | AF1-092 E O1 | 80/20 | 12.45 MW | 12.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944532 | AF1-118 E O1 | 80/20 | 35.36 MW | 35.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944542 | AF1-119 E O1 | 80/20 | 18.03 MW | 18.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944832 | AF1-148 E O1 | 80/20 | 15.7 MW | 15.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944932 | AF1-158 E O1 | 80/20 | 12.33 MW | 12.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944961 | AF1-161 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944962 | AF1-161 E | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945111 | AF1-176 C O1 | 80/20 | 4.3 MW | 4.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945112 | AF1-176 E O1 | 80/20 | 6.45 MW | 6.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945371 | AF1-202 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945372 | AF1-202 E O1 | 80/20 | 11.19 MW | 11.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945391 | AF1-204 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945392 | AF1-204 E O1 | 80/20 | 8.51 MW | 8.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946321 | AF1-296 C O1 | 80/20 | 1.94 MW | 1.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946322 | AF1-296 E O1 | 80/20 | 9.06 MW | 9.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946501 | AF1-314 C | 80/20 | 2.04 MW | 2.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946502 | AF1-314 E | 80/20 | 9.59 MW | 9.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246953 | 05TIMB G C | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246991 | 05WLD G1 C | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247536 | 05BLUFF P WF | 80/20 | 0.62 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247543 | V3-007 C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247911 | 05TIMB G E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247929 | S-071 E | 80/20 | 2.48 MW | 2.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247963 | 05HDWTR1G E | 80/20 | 4.33 MW | 4.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936291 | AD2-038 C O1 | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936292 | AD2-038 E O1 | 80/20 | 6.9 MW | 6.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939781 | AE1-209 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939782 | AE1-209 E O1 | 80/20 | 4.94 MW | 4.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939791 | AE1-210 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939792 | AE1-210 E O1 | 80/20 | 4.94 MW | 4.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 941721 | AE2-172 | 80/20 | 2.85 MW | 2.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246909 | 05MDL-1G C | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246910 | 05MDL-2G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246976 | 05MDL-3G C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246979 | 05MDL-4G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247521 | T-131 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247556 | T-127 C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247925 | T-131 E | 80/20 | 5.12 MW | 5.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247943 | T-127 E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274880 | GENERATOR; | 80/20 | 0.98 MW | 0.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274881 | PILOT HIL;1E | 80/20 | 4.13 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274882 | W4-005 E | 80/20 | 6.54 MW | 6.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274888 | KELLYCK ;1U | 80/20 | 1.03 MW | 1.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274890 | CAYUG;1U E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274891 | CAYUG;2U E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 917501 | Z2-087 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 918051 | AA1-018 C OP | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924261 | AB2-070 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924262 | AB2-070 E O1 | 80/20 | 8.55 MW | 8.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925301 | AB2-191 | 80/20 | 0.23 MW | 0.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925302 | AB2-191 E | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925771 | AC1-053 C | 80/20 | 1.27 MW | 1.27 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925772 | AC1-053 E | 80/20 | 8.53 MW | 8.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926861 | AC1-173 C | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926862 | AC1-173 E | 80/20 | 2.86 MW | 2.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933591 | AC2-176 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933592 | AC2-176 E O1 | 80/20 | 3.17 MW | 3.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938851 | AE1-113 C | 80/20 | 3.7 MW | 3.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938852 | AE1-113 E | 80/20 | 13.12 MW | 13.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 940752 | AE2-062 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944221 | AF1-090 C O1 | 80/20 | 1.57 MW | 1.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944222 | AF1-090 E O1 | 80/20 | 7.34 MW | 7.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945871 | AF1-252 O1 | 80/20 | 3.47 MW | 3.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945881 | AF1-253 O1 | 80/20 | 2.4 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946162 | AF1-281 E | 80/20 | 1.15 MW | 1.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946541 | AF1-318 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946542 | AF1-318 E O1 | 80/20 | 13.31 MW | 13.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243795 | 05HDWTR1G C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 990901 | L-005 E | 80/20 | 3.17 MW | 3.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936722 | AD2-091 BAT | 80/20 | 6.84 MW | 6.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936752 | AD2-096 BAT | 80/20 | 3.15 MW | 3.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942042 | AE2-216 BAT | 80/20 | 7.52 MW | 7.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945351 | AF1-200 FTIR | 80/20 | 119.41 MW | 119.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946203 | AF1-285 BAT | 80/20 | 2.51 MW | 2.51 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 276170 | Z1-108 E | Adder | 1.4 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 916211 | Z1-072 E | Adder | 2.37 MW | 2.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 920272 | AA2-123 E | Adder | 1.39 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 924041 | AB2-047 C O1 | Adder | 1.73 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 924042 | AB2-047 E O1 | Adder | 11.56 MW | 9.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 925581 | AC1-033 C | Adder | 0.69 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 925582 | AC1-033 E | Adder | 4.61 MW | 3.92 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926821 | AC1-168 C O1 | Adder | 0.55 MW | 0.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926822 | AC1-168 E O1 | Adder | 3.69 MW | 3.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 927201 | AC1-214 C O1 | Adder | 1.0 MW | 0.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 927202 | AC1-214 E O1 | Adder | 3.2 MW | 2.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 933281 | AC2-140 C | Adder | 3.05 MW | 2.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934431 | AD1-067 C | Adder | 0.06 MW | 0.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934432 | AD1-067 E | Adder | 0.25 MW | 0.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934721 | AD1-100 C | Adder | 8.66 MW | 7.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934722 | AD1-100 E | Adder | 40.42 MW | 34.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 935141 | AD1-148 | Adder | 1.75 MW | 1.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936371 | AD2-047 C O1 | Adder | 1.98 MW | 1.69 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936372 | AD2-047 E O1 | Adder | 9.69 MW | 8.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 937001 | AD2-134 C | Adder | 1.17 MW | 0.99 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 937002 | AD2-134 E | Adder | 4.66 MW | 3.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 938861 | AE1-114 C O1 | Adder | 1.84 MW | 1.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 938862 | AE1-114 E O1 | Adder | 6.26 MW | 5.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939321 | AE1-163 C O1 | Adder | 2.71 MW | 2.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939322 | AE1-163 E O1 | Adder | 16.63 MW | 14.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939401 | AE1-172 C O1 | Adder | 2.49 MW | 2.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939402 | AE1-172 E O1 | Adder | 11.68 MW | 9.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 941731 | AE2-173 O1 | Adder | 3.32 MW | 2.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942111 | AE2-223 C | Adder | 1.04 MW | 0.88 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942112 | AE2-223 E | Adder | 6.94 MW | 5.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942421 | AE2-255 C O1 | Adder | 1.39 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942422 | AE2-255 E O1 | Adder | 4.16 MW | 3.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942651 | AE2-281 C O1 | Adder | 0.39 MW | 0.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942652 | AE2-281 E O1 | Adder | 2.38 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943021 | AE2-325 C | Adder | 2.57 MW | 2.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943022 | AE2-325 E | Adder | 1.71 MW | 1.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943801 | AF1-048 C | Adder | 2.18 MW | 1.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943802 | AF1-048 E | Adder | 1.45 MW | 1.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944241 | AF1-092 C O1 | 50/50 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944242 | AF1-092 E O1 | 50/50 | 12.3 MW | 12.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944532 | AF1-118 E O1 | Adder | 34.9 MW | 29.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944542 | AF1-119 E O1 | Adder | 17.78 MW | 15.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944831 | AF1-148 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944832 | AF1-148 E O1 | Adder | 15.5 MW | 13.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944931 | AF1-158 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944932 | AF1-158 E O1 | Adder | 12.16 MW | 10.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944961 | AF1-161 C | Adder | 2.05 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944962 | AF1-161 E | Adder | 2.05 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945111 | AF1-176 C O1 | Adder | 4.24 MW | 3.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945112 | AF1-176 E O1 | Adder | 6.36 MW | 5.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945371 | AF1-202 C O1 | Adder | 2.26 MW | 1.92 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945372 | AF1-202 E O1 | Adder | 11.03 MW | 9.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945391 | AF1-204 C O1 | Adder | 2.81 MW | 2.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945392 | AF1-204 E O1 | Adder | 8.43 MW | 7.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946321 | AF1-296 C O1 | Adder | 1.92 MW | 1.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946322 | AF1-296 E O1 | Adder | 8.98 MW | 7.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946501 | AF1-314 C | Adder | 2.02 MW | 1.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946502 | AF1-314 E | Adder | 9.5 MW | 8.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936291 | AD2-038 C O1 | Adder | 1.46 MW | 1.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936292 | AD2-038 E O1 | Adder | 6.83 MW | 5.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939781 | AE1-209 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939782 | AE1-209 E O1 | Adder | 4.86 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939791 | AE1-210 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939792 | AE1-210 E O1 | Adder | 4.86 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 941721 | AE2-172 | Adder | 2.81 MW | 2.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247521 | T-131 C | 50/50 | 1.25 MW | 1.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247925 | T-131 E | 50/50 | 5.0 MW | 5.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 924261 | AB2-070 C O1 | Adder | 1.27 MW | 1.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 924262 | AB2-070 E O1 | Adder | 8.48 MW | 7.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 925302 | AB2-191 E | Adder | 0.64 MW | 0.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 925771 | AC1-053 C | Adder | 1.26 MW | 1.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 925772 | AC1-053 E | Adder | 8.45 MW | 7.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926861 | AC1-173 C | 50/50 | 0.42 MW | 0.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926862 | AC1-173 E | 50/50 | 2.79 MW | 2.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 938851 | AE1-113 C | Adder | 3.66 MW | 3.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 938852 | AE1-113 E | Adder | 12.98 MW | 11.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944221 | AF1-090 C O1 | Adder | 1.56 MW | 1.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944222 | AF1-090 E O1 | Adder | 7.29 MW | 6.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945871 | AF1-252 O1 | Adder | 3.45 MW | 2.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945881 | AF1-253 O1 | Adder | 2.39 MW | 2.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946161 | AF1-281 C | Adder | 0.2 MW | 0.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946162 | AF1-281 E | Adder | 1.14 MW | 0.97 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946541 | AF1-318 C O1 | Adder | 2.81 MW | 2.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946542 | AF1-318 E O1 | Adder | 13.18 MW | 11.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936722 | AD2-091 BAT | 50/50 | 7.17 MW | 7.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942042 | AE2-216 BAT | 50/50 | 7.89 MW | 7.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945351 | AF1-200 FTIR | Adder | 173.67 MW | 147.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946203 | AF1-285 BAT | 50/50 | 2.65 MW | 2.65 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note: Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6279.2 | Preliminary Sag study results confirm that the line rating is 442 MVA SE. | $0 | |
| n8196.1 | AEP will replace two (2) existing double circuit towers with steel double circuit single pole structures on the Allen - RPMone 345kV line. | $916,437 | |
| n6740 | Sag Study - Allen and Rpmone 345 kV line (12.25 miles). Completed, Rate B should be 1057MVA. | $49,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF1-202 is eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A). See next steps for your project in the "Introduction" section above.