AF1-176 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:13
Corey 138 kV
155.684 MW Capacity / 300.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AF1-176 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the AEP zone — St. Joseph County, Michigan. The installed facilities will have a total capability of 300.0 MW with 155.684 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AF1-176 |
| Project Name | Corey 138 kV |
| Developer Name | Three Lakes Solar LLC |
| State | Michigan |
| County | St. Joseph |
| Transmission Owner | AEP |
| MFO | 300.0 MW |
| MWE | 300.0 MW |
| MWC | 155.684 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2023 |
Point of Interconnection
AF1-176 will interconnect on the AEP transmission system at the Corey 138 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 300.0 MW (Capacity 155.684 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer
243212 to 243250 ckt 1 |
AEP_P4_#7027_05COOK 345_N
CONTINGENCY 'AEP_P4_#7027_05COOK 345_N' OPEN BRANCH FROM BUS 243212 TO BUS 243215 CKT 1 /*05BENTON 345.0 - 05COOK 345.0 OPEN BRANCH FROM BUS 243215 TO BUS 247803 CKT 1 /*05COOK 345.0 - 05SEGRETO 345.0 END |
Breaker | AC | 138.35 % | 140.78 % | 564.0 | B | 794.0 | 13.73 | |
| AEP |
05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line
243287 to 243346 ckt 1 |
AEP_P4_#9220_05KENZIE 138_J2
CONTINGENCY 'AEP_P4_#9220_05KENZIE 138_J2' OPEN BRANCH FROM BUS 243265 TO BUS 243322 CKT 1 /*05COREY 138.0 - 05KENZIE 138.0 OPEN BRANCH FROM BUS 243322 TO BUS 243360 CKT 1 /*05KENZIE 138.0 - 05POKAGO 138.0 OPEN BRANCH FROM BUS 243355 TO BUS 246764 CKT 1 /*05ONTWAZ 138.0 - 05SAUKTR 138.0 OPEN BRANCH FROM BUS 243360 TO BUS 246480 CKT 1 /*05POKAGO 138.0 - 05POKAGON 69.0 OPEN BRANCH FROM BUS 243360 TO BUS 246764 CKT 1 /*05POKAGO 138.0 - 05SAUKTR 138.0 END |
Breaker | AC | 64.24 % | 100.35 % | 185.0 | B | 185.65 | 63.75 | |
| AEP |
05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer
243212 to 243250 ckt 1 |
AEP_P7-1_#10998
CONTINGENCY 'AEP_P7-1_#10998' OPEN BRANCH FROM BUS 243212 TO BUS 243215 CKT 1 /*05BENTON 345.0 - 05COOK 345.0 OPEN BRANCH FROM BUS 243215 TO BUS 247803 CKT 1 /*05COOK 345.0 - 05SEGRETO 345.0 END |
Tower | AC | 138.35 % | 140.78 % | 564.0 | B | 794.0 | 13.73 | |
| Details for 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 938261 | AE1-039 | Adder | -0.35 MW | -0.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247528 | 05COVRT1 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247529 | 05COVRT2 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247530 | 05COVRT3 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247531 | 05COVRT4 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247532 | 05COVRT5 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 247533 | 05COVRT6 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 925961 | AC1-072 | 50/50 | 0.78 MW | 0.78 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 943023 | AE2-325 BAT | 50/50 | 11.58 MW | 11.58 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 944963 | AF1-161 BAT | 50/50 | 11.09 MW | 11.09 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 945113 | AF1-176 BAT | 50/50 | 13.73 MW | 13.73 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 945352 | AF1-200 NFTW | Adder | 58.03 MW | 49.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950311 | G934 C | External Queue | 3.49 MW | 3.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950791 | J201 C | External Queue | 0.37 MW | 0.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950871 | J246 C | External Queue | 0.16 MW | 0.16 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 951531 | J533 C | External Queue | 4.46 MW | 4.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 951571 | J538 C | External Queue | 2.07 MW | 2.07 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952201 | J589 C | External Queue | 3.34 MW | 3.34 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952401 | J752 C | External Queue | 1.35 MW | 1.35 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952611 | J717 C | External Queue | 3.13 MW | 3.13 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952761 | J728 C | External Queue | 2.91 MW | 2.91 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953071 | J794 C | External Queue | 0.2 MW | 0.2 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953271 | J701 C | External Queue | 0.67 MW | 0.67 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 955071 | J984 C | External Queue | 3.63 MW | 3.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950312 | G934 E | External Queue | 13.96 MW | 13.96 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950351 | J466 | External Queue | 2.56 MW | 2.56 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950792 | J201 E | External Queue | 1.49 MW | 1.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950872 | J246 E | External Queue | 0.62 MW | 0.62 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 950942 | J325 E | External Queue | 0.33 MW | 0.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 951532 | J533 E | External Queue | 17.84 MW | 17.84 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 951572 | J538 E | External Queue | 8.28 MW | 8.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952161 | J571 | External Queue | 0.65 MW | 0.65 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952202 | J589 E | External Queue | 18.05 MW | 18.05 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952312 | J646 E | External Queue | 0.12 MW | 0.12 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952402 | J752 E | External Queue | 7.33 MW | 7.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952612 | J717 E | External Queue | 16.96 MW | 16.96 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952762 | J728 E | External Queue | 15.79 MW | 15.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952881 | J758 | External Queue | 18.86 MW | 18.86 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 952971 | J793 | External Queue | 100.29 MW | 100.29 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953072 | J794 E | External Queue | 1.1 MW | 1.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953272 | J701 E | External Queue | 3.61 MW | 3.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953291 | J796 | External Queue | 23.45 MW | 23.45 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953321 | J799 | External Queue | 11.71 MW | 11.71 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953361 | J806 | External Queue | 13.23 MW | 13.23 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 953941 | J857 | External Queue | 11.4 MW | 11.4 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 954111 | J875 | External Queue | 10.3 MW | 10.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 955072 | J984 E | External Queue | 19.64 MW | 19.64 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 955181 | J996 | External Queue | 4.76 MW | 4.76 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 955781 | J1062 | External Queue | 7.63 MW | 7.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 955861 | J1071 | External Queue | 12.6 MW | 12.6 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | 956741 | J1172 | External Queue | 4.57 MW | 4.57 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.52 MW | 1.52 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.73 MW | 2.73 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.61 MW | 0.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.64 MW | 3.64 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.32 MW | 0.32 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.75 MW | 0.75 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.45 MW | 1.45 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.46 MW | 0.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.11 MW | 0.11 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P4_#7027_05COOK 345_N | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.36 MW | 23.36 MW |
| Details for 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 938261 | AE1-039 | Adder | -0.04 MW | -0.04 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 943023 | AE2-325 BAT | 50/50 | 8.77 MW | 8.77 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 944963 | AF1-161 BAT | 50/50 | 8.4 MW | 8.4 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | 945113 | AF1-176 BAT | 50/50 | 63.75 MW | 63.75 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.02 MW | 0.02 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.01 MW | 0.01 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 0.27 MW | 0.27 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.04 MW | 0.04 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.12 MW | 0.12 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.26 MW | 0.26 MW |
| 05E.ELKHART-05MOTTV 138.0 kV Ckt 1 line l/o AEP_P4_#9220_05KENZIE 138_J2 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 938261 | AE1-039 | Adder | -0.35 MW | -0.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247528 | 05COVRT1 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247529 | 05COVRT2 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247530 | 05COVRT3 | 50/50 | 8.37 MW | 8.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247531 | 05COVRT4 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247532 | 05COVRT5 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 247533 | 05COVRT6 | 50/50 | 5.02 MW | 5.02 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 925961 | AC1-072 | 50/50 | 0.78 MW | 0.78 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 943023 | AE2-325 BAT | 50/50 | 11.58 MW | 11.58 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 944963 | AF1-161 BAT | 50/50 | 11.09 MW | 11.09 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 945113 | AF1-176 BAT | 50/50 | 13.73 MW | 13.73 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 945352 | AF1-200 NFTW | Adder | 58.03 MW | 49.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950311 | G934 C | External Queue | 3.49 MW | 3.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950791 | J201 C | External Queue | 0.37 MW | 0.37 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950871 | J246 C | External Queue | 0.16 MW | 0.16 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951531 | J533 C | External Queue | 4.46 MW | 4.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951571 | J538 C | External Queue | 2.07 MW | 2.07 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952201 | J589 C | External Queue | 3.34 MW | 3.34 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952401 | J752 C | External Queue | 1.35 MW | 1.35 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952611 | J717 C | External Queue | 3.13 MW | 3.13 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952761 | J728 C | External Queue | 2.91 MW | 2.91 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953071 | J794 C | External Queue | 0.2 MW | 0.2 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953271 | J701 C | External Queue | 0.67 MW | 0.67 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955071 | J984 C | External Queue | 3.63 MW | 3.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950312 | G934 E | External Queue | 13.96 MW | 13.96 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950351 | J466 | External Queue | 2.56 MW | 2.56 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950792 | J201 E | External Queue | 1.49 MW | 1.49 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950872 | J246 E | External Queue | 0.62 MW | 0.62 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 950942 | J325 E | External Queue | 0.33 MW | 0.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951532 | J533 E | External Queue | 17.84 MW | 17.84 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 951572 | J538 E | External Queue | 8.28 MW | 8.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952161 | J571 | External Queue | 0.65 MW | 0.65 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952202 | J589 E | External Queue | 18.05 MW | 18.05 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952312 | J646 E | External Queue | 0.12 MW | 0.12 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952402 | J752 E | External Queue | 7.33 MW | 7.33 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952612 | J717 E | External Queue | 16.96 MW | 16.96 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952762 | J728 E | External Queue | 15.79 MW | 15.79 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952881 | J758 | External Queue | 18.86 MW | 18.86 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 952971 | J793 | External Queue | 100.29 MW | 100.29 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953072 | J794 E | External Queue | 1.1 MW | 1.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953272 | J701 E | External Queue | 3.61 MW | 3.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953291 | J796 | External Queue | 23.45 MW | 23.45 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953321 | J799 | External Queue | 11.71 MW | 11.71 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953361 | J806 | External Queue | 13.23 MW | 13.23 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 953941 | J857 | External Queue | 11.4 MW | 11.4 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 954111 | J875 | External Queue | 10.3 MW | 10.3 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955072 | J984 E | External Queue | 19.64 MW | 19.64 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955181 | J996 | External Queue | 4.76 MW | 4.76 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955781 | J1062 | External Queue | 7.63 MW | 7.63 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 955861 | J1071 | External Queue | 12.6 MW | 12.6 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | 956741 | J1172 | External Queue | 4.57 MW | 4.57 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | NEWTON | LTFEXP_NEWTON->LTFIMP_NEWTON | CLTF | 1.52 MW | 1.52 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | FARMERCITY | LTFEXP_FARMERCITY->LTFIMP_FARMERCITY | CLTF | 0.1 MW | 0.1 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.73 MW | 2.73 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.61 MW | 0.61 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.64 MW | 3.64 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | COFFEEN | LTFEXP_COFFEEN->LTFIMP_COFFEEN | CLTF | 0.32 MW | 0.32 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.75 MW | 0.75 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 1.01 MW | 1.01 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.28 MW | 0.28 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 1.45 MW | 1.45 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.46 MW | 0.46 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.11 MW | 0.11 MW |
| 05BENTON-05BENTON 345.0/138.0 kV Ckt 1 transformer l/o AEP_P7-1_#10998 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 23.36 MW | 23.36 MW |
Light Load Analysis
The Queue Project was evaluated as a 300.0 MW (Capacity 155.684 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441
CONTINGENCY 'AEP_P1-2_#7441' OPEN BRANCH FROM BUS 242928 TO BUS 246999 CKT 1 /*05MARYSV 765.0 - 05SORENS 765.0 END |
Single | DC | 109.12 % | 110.43 % | 897.0 | B | 990.56 | 10.75 | |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247255 | 05WLD G2 C | 80/20 | 0.35 MW | 0.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243859 | 05FR-11G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243862 | 05FR-12G C | 80/20 | 0.51 MW | 0.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243864 | 05FR-21G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243866 | 05FR-22G C | 80/20 | 0.52 MW | 0.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243870 | 05FR-3G C | 80/20 | 1.06 MW | 1.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243873 | 05FR-4G C | 80/20 | 0.82 MW | 0.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247901 | 05FR-12G E | 80/20 | 2.04 MW | 2.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247902 | 05FR-21G E | 80/20 | 2.19 MW | 2.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247904 | 05FR-3G E | 80/20 | 4.24 MW | 4.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247905 | 05FR-4G E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247906 | 05MDL-1G E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247907 | 05MDL-2G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247912 | 05MDL-3G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247913 | 05MDL-4G E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247958 | 05WLD G2 E | 80/20 | 4.63 MW | 4.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274847 | GR RIDGE ;BU | 80/20 | 0.87 MW | 0.87 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274848 | CAMPGROVE;RU | 80/20 | 0.79 MW | 0.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274850 | MENDOTA H;RU | 80/20 | 0.14 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274851 | PROVIDENC;RU | 80/20 | 0.4 MW | 0.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274853 | TWINGROVE;U1 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274854 | TWINGROVE;U2 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274855 | GSG-6 ;RU | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274856 | ECOGROVE ;U1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274857 | BIG SKY ;U1 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274858 | BIG SKY ;U2 | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274859 | EASYR;U1 E | 80/20 | 2.6 MW | 2.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274860 | EASYR;U2 E | 80/20 | 2.6 MW | 2.6 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274861 | TOP CROP ;1U | 80/20 | 0.58 MW | 0.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274862 | TOP CROP ;2U | 80/20 | 1.13 MW | 1.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274863 | CAYUGA RI;1U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274864 | CAYUGA RI;2U | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274871 | GR RIDGE ;2U | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274872 | LEE DEKAL;1U | 80/20 | 1.35 MW | 1.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274877 | BISHOP HL;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274878 | BISHOP HL;2U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274879 | MINONK ;1U | 80/20 | 1.12 MW | 1.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274887 | PILOT HIL;1U | 80/20 | 1.03 MW | 1.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 275149 | KELLYCK ;1E | 80/20 | 4.13 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 276158 | O-029 C | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290021 | O50 E | 80/20 | 4.48 MW | 4.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290051 | GSG-6; E | 80/20 | 2.44 MW | 2.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290108 | LEEDK;1U E | 80/20 | 5.61 MW | 5.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290261 | S-027 E | 80/20 | 4.04 MW | 4.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 290265 | S-028 E | 80/20 | 4.04 MW | 4.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293061 | N-015 E | 80/20 | 3.48 MW | 3.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293516 | O-009 E1 | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293517 | O-009 E2 | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293518 | O-009 E3 | 80/20 | 1.23 MW | 1.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293644 | O22 E1 | 80/20 | 2.33 MW | 2.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293645 | O22 E2 | 80/20 | 4.53 MW | 4.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293715 | O-029 E | 80/20 | 2.35 MW | 2.35 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293716 | O-029 E | 80/20 | 1.29 MW | 1.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293717 | O-029 E | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 293771 | O-035 E | 80/20 | 1.58 MW | 1.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294392 | P-010 E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294401 | BSHIL;1U E | 80/20 | 2.12 MW | 2.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294410 | BSHIL;2U E | 80/20 | 2.12 MW | 2.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 294763 | P-046 E | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 295108 | WESTBROOK C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 917502 | Z2-087 E | 80/20 | 4.67 MW | 4.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924041 | AB2-047 C O1 | 80/20 | 1.75 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924042 | AB2-047 E O1 | 80/20 | 11.68 MW | 11.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925581 | AC1-033 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925582 | AC1-033 E | 80/20 | 4.66 MW | 4.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926821 | AC1-168 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926822 | AC1-168 E O1 | 80/20 | 3.73 MW | 3.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 927201 | AC1-214 C O1 | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 927202 | AC1-214 E O1 | 80/20 | 3.23 MW | 3.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 930041 | AB1-006 C | 80/20 | 0.72 MW | 0.72 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 930042 | AB1-006 E | 80/20 | 4.82 MW | 4.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933281 | AC2-140 C | 80/20 | 3.09 MW | 3.09 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934432 | AD1-067 E | 80/20 | 0.26 MW | 0.26 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934721 | AD1-100 C | 80/20 | 8.76 MW | 8.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 934722 | AD1-100 E | 80/20 | 40.86 MW | 40.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 935141 | AD1-148 | 80/20 | 1.77 MW | 1.77 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936371 | AD2-047 C O1 | 80/20 | 2.01 MW | 2.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936372 | AD2-047 E O1 | 80/20 | 9.8 MW | 9.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 937001 | AD2-134 C | 80/20 | 1.18 MW | 1.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 937002 | AD2-134 E | 80/20 | 4.71 MW | 4.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938861 | AE1-114 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938862 | AE1-114 E O1 | 80/20 | 6.32 MW | 6.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939321 | AE1-163 C O1 | 80/20 | 2.74 MW | 2.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939322 | AE1-163 E O1 | 80/20 | 16.81 MW | 16.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939401 | AE1-172 C O1 | 80/20 | 2.52 MW | 2.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939402 | AE1-172 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 941731 | AE2-173 O1 | 80/20 | 3.36 MW | 3.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942111 | AE2-223 C | 80/20 | 1.05 MW | 1.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942112 | AE2-223 E | 80/20 | 7.01 MW | 7.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942421 | AE2-255 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942422 | AE2-255 E O1 | 80/20 | 4.2 MW | 4.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942651 | AE2-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942652 | AE2-281 E O1 | 80/20 | 2.4 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943021 | AE2-325 C | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943801 | AF1-048 C | 80/20 | 2.2 MW | 2.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 943802 | AF1-048 E | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944242 | AF1-092 E O1 | 80/20 | 12.45 MW | 12.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944532 | AF1-118 E O1 | 80/20 | 35.36 MW | 35.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944542 | AF1-119 E O1 | 80/20 | 18.03 MW | 18.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944832 | AF1-148 E O1 | 80/20 | 15.7 MW | 15.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944932 | AF1-158 E O1 | 80/20 | 12.33 MW | 12.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944961 | AF1-161 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944962 | AF1-161 E | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945111 | AF1-176 C O1 | 80/20 | 4.3 MW | 4.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945112 | AF1-176 E O1 | 80/20 | 6.45 MW | 6.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945371 | AF1-202 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945372 | AF1-202 E O1 | 80/20 | 11.19 MW | 11.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945391 | AF1-204 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945392 | AF1-204 E O1 | 80/20 | 8.51 MW | 8.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946321 | AF1-296 C O1 | 80/20 | 1.94 MW | 1.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946322 | AF1-296 E O1 | 80/20 | 9.06 MW | 9.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946501 | AF1-314 C | 80/20 | 2.04 MW | 2.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946502 | AF1-314 E | 80/20 | 9.59 MW | 9.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246953 | 05TIMB G C | 80/20 | 1.1 MW | 1.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246991 | 05WLD G1 C | 80/20 | 0.34 MW | 0.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247536 | 05BLUFF P WF | 80/20 | 0.62 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247543 | V3-007 C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247911 | 05TIMB G E | 80/20 | 4.42 MW | 4.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247929 | S-071 E | 80/20 | 2.48 MW | 2.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247963 | 05HDWTR1G E | 80/20 | 4.33 MW | 4.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936291 | AD2-038 C O1 | 80/20 | 1.47 MW | 1.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936292 | AD2-038 E O1 | 80/20 | 6.9 MW | 6.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939781 | AE1-209 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939782 | AE1-209 E O1 | 80/20 | 4.94 MW | 4.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939791 | AE1-210 C O1 | 80/20 | 0.74 MW | 0.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 939792 | AE1-210 E O1 | 80/20 | 4.94 MW | 4.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 941721 | AE2-172 | 80/20 | 2.85 MW | 2.85 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246909 | 05MDL-1G C | 80/20 | 1.11 MW | 1.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246910 | 05MDL-2G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246976 | 05MDL-3G C | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 246979 | 05MDL-4G C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247521 | T-131 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247556 | T-127 C | 80/20 | 0.55 MW | 0.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247925 | T-131 E | 80/20 | 5.12 MW | 5.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 247943 | T-127 E | 80/20 | 2.21 MW | 2.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274880 | GENERATOR; | 80/20 | 0.98 MW | 0.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274881 | PILOT HIL;1E | 80/20 | 4.13 MW | 4.13 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274882 | W4-005 E | 80/20 | 6.54 MW | 6.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274888 | KELLYCK ;1U | 80/20 | 1.03 MW | 1.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274890 | CAYUG;1U E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 274891 | CAYUG;2U E | 80/20 | 3.32 MW | 3.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 917501 | Z2-087 C | 80/20 | 0.7 MW | 0.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 918051 | AA1-018 C OP | 80/20 | 0.56 MW | 0.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924261 | AB2-070 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 924262 | AB2-070 E O1 | 80/20 | 8.55 MW | 8.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925301 | AB2-191 | 80/20 | 0.23 MW | 0.23 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925302 | AB2-191 E | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925771 | AC1-053 C | 80/20 | 1.27 MW | 1.27 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 925772 | AC1-053 E | 80/20 | 8.53 MW | 8.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926861 | AC1-173 C | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 926862 | AC1-173 E | 80/20 | 2.86 MW | 2.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933591 | AC2-176 C O1 | 80/20 | 0.24 MW | 0.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 933592 | AC2-176 E O1 | 80/20 | 3.17 MW | 3.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938851 | AE1-113 C | 80/20 | 3.7 MW | 3.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 938852 | AE1-113 E | 80/20 | 13.12 MW | 13.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 940752 | AE2-062 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944221 | AF1-090 C O1 | 80/20 | 1.57 MW | 1.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 944222 | AF1-090 E O1 | 80/20 | 7.34 MW | 7.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945871 | AF1-252 O1 | 80/20 | 3.47 MW | 3.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945881 | AF1-253 O1 | 80/20 | 2.4 MW | 2.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946161 | AF1-281 C | 80/20 | 0.2 MW | 0.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946162 | AF1-281 E | 80/20 | 1.15 MW | 1.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946541 | AF1-318 C O1 | 80/20 | 2.84 MW | 2.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946542 | AF1-318 E O1 | 80/20 | 13.31 MW | 13.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 243795 | 05HDWTR1G C | 80/20 | 0.65 MW | 0.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 990901 | L-005 E | 80/20 | 3.17 MW | 3.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936722 | AD2-091 BAT | 80/20 | 6.84 MW | 6.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 936752 | AD2-096 BAT | 80/20 | 3.15 MW | 3.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 942042 | AE2-216 BAT | 80/20 | 7.52 MW | 7.52 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 945351 | AF1-200 FTIR | 80/20 | 119.41 MW | 119.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441 | 946203 | AF1-285 BAT | 80/20 | 2.51 MW | 2.51 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7508 | Add another 345/138kV transformer with associated equipment | $7,912,565 | |
| n7017 | A Sag Study will be required on the 7.8 mile section of ACSR 477 26/7 HAWK [...] n time would be 24 to 36 months after signing an interconnection agreement. | $31,200 | |
| n6740 | Sag Study - Allen and Rpmone 345 kV line (12.25 miles). Completed, Rate B should be 1057MVA. | $49,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AF1-176 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.