AE2-130 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 11:13
Rockport 765 kV
480.0 MW Capacity / 800.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AE2-130 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the AEP zone — Spencer County, Indiana. The installed facilities will have a total capability of 800.0 MW with 480.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AE2-130 |
| Project Name | Rockport 765 kV |
| Developer Name | OSER LLC |
| State | Indiana |
| County | Spencer |
| Transmission Owner | AEP |
| MFO | 800.0 MW |
| MWE | 800.0 MW |
| MWC | 480.0 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2022 |
Point of Interconnection
AE2-130 will interconnect with the AEP transmission system at the Rockport 765kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 800.0 MW (Capacity 480.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/AMIL |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
966790 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 109.41 % | 110.73 % | 1685.0 | B | 1865.78 | 31.58 | |
| OVEC |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line
248000 to 248001 ckt 1 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 108.16 % | 115.91 % | 956.0 | B | 1108.1 | 87.22 | |
| AEP |
05DARWIN-05EUGENE 345.0 kV Ckt 1 line
243216 to 243221 ckt 1 |
AEP_P4_#8648_05JEFRSO 765_B
CONTINGENCY 'AEP_P4_#8648_05JEFRSO 765_B' OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1 /*05JEFRSO 345.0 - 06CLIFTY 345.0 OPEN BRANCH FROM BUS 243208 TO BUS 242865 CKT 2 /*05JEFRSO 765.0 - 05JEFRSO 345.0 OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Breaker | DC | 99.39 % | 114.0 % | 1195.0 | B | 1362.3 | 174.54 | |
| AEP |
05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line
247712 to 243216 ckt 1 |
AEP_P4_#8648_05JEFRSO 765_B
CONTINGENCY 'AEP_P4_#8648_05JEFRSO 765_B' OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1 /*05JEFRSO 345.0 - 06CLIFTY 345.0 OPEN BRANCH FROM BUS 243208 TO BUS 242865 CKT 2 /*05JEFRSO 765.0 - 05JEFRSO 345.0 OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Breaker | DC | 88.97 % | 102.04 % | 1335.0 | B | 1362.3 | 174.54 | |
| AEP/OVEC |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line
242865 to 248000 ckt Z1 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | DC | 96.86 % | 114.07 % | 2255.0 | B | 2572.22 | 386.32 | |
| LGEE/OVEC |
7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line
324114 to 248000 ckt 1 |
AEP_P1-2_#363
CONTINGENCY 'AEP_P1-2_#363' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 137.74 % | 139.86 % | 1451.0 | B | 2029.37 | 36.01 | |
| LGEE/OVEC |
7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line
324114 to 248000 ckt 1 |
AEP_P1-2_#10136
CONTINGENCY 'AEP_P1-2_#10136' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 243443 CKT 2 /*05ROCKPT 765.0 - 05RKG2 26.0 REMOVE UNIT 2H FROM BUS 243443 /*05RKG2 26.0 REMOVE UNIT 2L FROM BUS 243443 /*05RKG2 26.0 END |
Single | DC | 132.21 % | 134.71 % | 1451.0 | B | 1954.64 | 36.26 | |
| AEP |
05DARWIN-05EUGENE 345.0 kV Ckt 1 line
243216 to 243221 ckt 1 |
AEP_P1-2_#363
CONTINGENCY 'AEP_P1-2_#363' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | AC | 94.73 % | 103.48 % | 1195.0 | B | 1236.59 | 104.54 | |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290021 | O50 E | Adder | 10.79 MW | 9.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290051 | GSG-6; E | Adder | 5.7 MW | 4.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.38 MW | 19.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.38 MW | 19.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295109 | WESTBROOK E | Adder | 3.05 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.48 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 920272 | AA2-123 E | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926431 | AC1-114 | Adder | 1.3 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.82 MW | 0.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.54 MW | 4.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927201 | AC1-214 C O1 | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 5.28 MW | 4.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927511 | AC1-113 1 | Adder | 0.65 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927521 | AC1-113 2 | Adder | 0.65 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 933911 | AD1-013 C | Adder | 1.0 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 933912 | AD1-013 E | Adder | 1.59 MW | 1.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 933931 | AD1-016 C | Adder | 0.46 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 933932 | AD1-016 E | Adder | 0.76 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.35 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.83 MW | 3.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934431 | AD1-067 C | Adder | 0.07 MW | 0.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934971 | AD1-129 C | Adder | 0.47 MW | 0.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934972 | AD1-129 E | Adder | 0.32 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 7.46 MW | 7.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936291 | AD2-038 C O1 | Adder | 1.34 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936292 | AD2-038 E O1 | Adder | 9.0 MW | 7.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936511 | AD2-066 C O1 | Adder | 4.76 MW | 4.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936512 | AD2-066 E O1 | Adder | 3.17 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937001 | AD2-134 C | Adder | 1.38 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937002 | AD2-134 E | Adder | 5.51 MW | 4.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937311 | AD2-172 C | Adder | 1.42 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937312 | AD2-172 E | Adder | 1.96 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | Adder | 1.94 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | Adder | 13.01 MW | 11.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942421 | AE2-255 C O1 | Adder | 1.69 MW | 1.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942422 | AE2-255 E O1 | Adder | 5.06 MW | 4.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.32 MW | 31.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.88 MW | 20.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942651 | AE2-281 C O1 | Adder | 0.48 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942652 | AE2-281 E O1 | Adder | 2.96 MW | 2.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942991 | AE2-321 C | Adder | 4.1 MW | 3.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942992 | AE2-321 E | Adder | 2.02 MW | 1.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 14.88 MW | 14.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 14.9 MW | 14.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.82 MW | 5.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.82 MW | 5.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.29 MW | 5.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.2 MW | 2.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293644 | O22 E1 | Adder | 4.91 MW | 4.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293645 | O22 E2 | Adder | 9.53 MW | 8.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.72 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.39 MW | 2.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 5.18 MW | 4.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 7.06 MW | 6.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 7.06 MW | 6.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294763 | P-046 E | Adder | 5.4 MW | 4.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.92 MW | 3.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916221 | Z1-073 E | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | Adder | 17.34 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.16 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.74 MW | 6.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 932881 | AC2-115 1 | Adder | 1.3 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 932891 | AC2-115 2 | Adder | 1.3 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 932921 | AC2-116 | Adder | 0.46 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938851 | AE1-113 C O1 | Adder | 4.45 MW | 3.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938852 | AE1-113 E O1 | Adder | 15.78 MW | 13.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.37 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 8.1 MW | 6.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.91 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.91 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939321 | AE1-163 C O1 | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939322 | AE1-163 E O1 | Adder | 20.75 MW | 17.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.02 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | Adder | 8.37 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | Adder | 11.56 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 940501 | AE2-035 C | Adder | 1.42 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 940502 | AE2-035 E | Adder | 1.96 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941131 | AE2-107 C | Adder | 3.36 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941132 | AE2-107 E | Adder | 2.24 MW | 1.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | Adder | 4.98 MW | 4.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 11.16 MW | 9.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274890 | CAYUG;1U E | Adder | 10.15 MW | 8.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274891 | CAYUG;2U E | Adder | 10.15 MW | 8.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 | Adder | 11.68 MW | 9.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.84 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 25.7 MW | 25.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.88 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 25.95 MW | 25.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930481 | AB1-089 | Adder | 35.4 MW | 30.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930741 | AB1-122 1O1 | Adder | 35.01 MW | 29.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 2.83 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276150 | W2-048 E | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 905081 | W4-005 C | 50/50 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 905082 | W4-005 E | 50/50 | 37.17 MW | 37.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 909052 | X2-022 E | 50/50 | 28.53 MW | 28.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 918052 | AA1-018 E | Adder | 7.93 MW | 6.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919221 | AA1-146 | Adder | 11.68 MW | 9.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | Adder | 21.68 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925302 | AB2-191 E | Adder | 0.75 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C O1 | 50/50 | 22.65 MW | 22.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E O1 | 50/50 | 15.1 MW | 15.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E O1 | 50/50 | 7.5 MW | 7.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290108 | LEEDK;1U E | Adder | 12.43 MW | 10.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.58 MW | 31.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.95 MW | 13.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952271 | J644 | External Queue | 9.55 MW | 9.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952871 | J757 C | External Queue | 4.05 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952872 | J757 E | External Queue | 21.94 MW | 21.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 9.04 MW | 9.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 17.75 MW | 17.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.08 MW | 32.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 8.93 MW | 8.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953851 | J845 C | External Queue | 1.72 MW | 1.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953852 | J845 E | External Queue | 9.31 MW | 9.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.22 MW | 14.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954721 | J750 C | External Queue | 2.1 MW | 2.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954722 | J750 E | External Queue | 11.38 MW | 11.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964971 | J976 | External Queue | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966041 | J1094 | External Queue | 13.77 MW | 13.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966061 | J1096 | External Queue | 1.95 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 950291 | J291 | External Queue | 3.2 MW | 3.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 950701 | J196 C | External Queue | 1.32 MW | 1.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 950702 | J196 E | External Queue | 5.3 MW | 5.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 951001 | J339 | External Queue | 6.02 MW | 6.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952321 | J734 | External Queue | 5.06 MW | 5.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952651 | J756 C | External Queue | 2.46 MW | 2.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 952652 | J756 E | External Queue | 13.3 MW | 13.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 43.77 MW | 43.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 4.95 MW | 4.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 27.31 MW | 27.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 | External Queue | 38.89 MW | 38.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954761 | J468 C | External Queue | 7.07 MW | 7.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954762 | J468 E | External Queue | 28.29 MW | 28.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964791 | J955 | External Queue | 110.95 MW | 110.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966121 | J1102 | External Queue | 5.45 MW | 5.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966251 | J1115 C | External Queue | 2.92 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966252 | J1115 E | External Queue | 15.82 MW | 15.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966791 | J1180 | External Queue | 36.73 MW | 36.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965101 | J991 | External Queue | 30.92 MW | 30.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965372 | J1022 E | External Queue | 15.86 MW | 15.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966421 | J1139 | External Queue | 20.2 MW | 20.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 3.88 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 10.33 MW | 10.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 201.07 MW | 201.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 28.29 MW | 28.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LGE-0092018 | LTFEXP_LGE-0092018->LTFIMP_LGE-0092018 | LTF | 0.0 MW | 0.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.14 MW | 4.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 5.03 MW | 5.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 2.37 MW | 2.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.29 MW | 0.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 13.16 MW | 13.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 45.67 MW | 45.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | CHOCTAW | LTFEXP_CHOCTAW->LTFIMP_CHOCTAW | LTF | 0.0 MW | 0.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.23 MW | 0.23 MW |
| Details for 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 926881 | AC1-175 C | Adder | -4.31 MW | -3.66 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942601 | AE2-276 | Adder | 2.82 MW | 2.4 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941341 | AE2-130 C | Adder | 52.33 MW | 44.48 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941342 | AE2-130 E | Adder | 34.89 MW | 29.66 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930461 | AB1-087 | Adder | 31.05 MW | 26.39 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930471 | AB1-088 | Adder | 31.05 MW | 26.39 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933441 | AC2-157 C | Adder | 4.29 MW | 3.65 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933442 | AC2-157 E | Adder | 7.0 MW | 5.95 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247543 | V3-007 C | Adder | -1.47 MW | -1.25 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 6.83 MW | 6.83 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 7.0 MW | 7.0 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.51 MW | 0.51 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.09 MW | 0.09 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 59.42 MW | 59.42 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 5.91 MW | 5.91 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.65 MW | 0.65 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 0.6 MW | 0.6 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 1.69 MW | 1.69 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.05 MW | 0.05 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 12.54 MW | 12.54 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.91 MW | 7.91 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.04 MW | 0.04 MW |
| 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 2.29 MW | 2.29 MW |
| Details for 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 942601 | AE2-276 | 50/50 | 10.91 MW | 10.91 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941341 | AE2-130 C | 50/50 | 104.72 MW | 104.72 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941342 | AE2-130 E | 50/50 | 69.81 MW | 69.81 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 930461 | AB1-087 | 50/50 | 119.99 MW | 119.99 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 930471 | AB1-088 | 50/50 | 119.99 MW | 119.99 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 933441 | AC2-157 C | 50/50 | 16.58 MW | 16.58 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 933442 | AC2-157 E | 50/50 | 27.05 MW | 27.05 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243442 | 05RKG1 | 50/50 | 45.85 MW | 45.85 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243443 | 05RKG2 | 50/50 | 43.96 MW | 43.96 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966791 | J1180 | External Queue | 11.13 MW | 11.13 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 965101 | J991 | External Queue | 7.9 MW | 7.9 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.3 MW | 0.3 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 30.58 MW | 30.58 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.91 MW | 1.91 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.45 MW | 0.45 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.11 MW | 0.11 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.07 MW | 0.07 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.32 MW | 3.32 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 4.54 MW | 4.54 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.15 MW | 3.15 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.09 MW | 0.09 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 4.65 MW | 4.65 MW |
| Details for 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 942601 | AE2-276 | 50/50 | 10.91 MW | 10.91 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941341 | AE2-130 C | 50/50 | 104.72 MW | 104.72 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941342 | AE2-130 E | 50/50 | 69.81 MW | 69.81 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 930461 | AB1-087 | 50/50 | 119.99 MW | 119.99 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 930471 | AB1-088 | 50/50 | 119.99 MW | 119.99 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 933441 | AC2-157 C | 50/50 | 16.58 MW | 16.58 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 933442 | AC2-157 E | 50/50 | 27.05 MW | 27.05 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243442 | 05RKG1 | 50/50 | 45.85 MW | 45.85 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243443 | 05RKG2 | 50/50 | 43.96 MW | 43.96 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966791 | J1180 | External Queue | 11.13 MW | 11.13 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 965101 | J991 | External Queue | 7.9 MW | 7.9 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.3 MW | 0.3 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 30.58 MW | 30.58 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 1.91 MW | 1.91 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.45 MW | 0.45 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.11 MW | 0.11 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.07 MW | 0.07 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 3.32 MW | 3.32 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 4.54 MW | 4.54 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.15 MW | 3.15 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.09 MW | 0.09 MW |
| 05SULLIVAN-05DARWIN 345.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 4.65 MW | 4.65 MW |
| Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247913 | 05MDL-4G E | Adder | 5.39 MW | 4.58 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 290261 | S-027 E | Adder | 11.01 MW | 9.36 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 290265 | S-028 E | Adder | 11.01 MW | 9.36 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 935141 | AD1-148 | Adder | 3.8 MW | 3.23 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942481 | AE2-261 C | Adder | 14.84 MW | 12.61 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942482 | AE2-261 E | Adder | 9.89 MW | 8.41 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942601 | AE2-276 | 50/50 | 11.81 MW | 11.81 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930042 | AB1-006 E | Adder | 11.73 MW | 9.97 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941341 | AE2-130 C | 50/50 | 231.79 MW | 231.79 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941342 | AE2-130 E | 50/50 | 154.53 MW | 154.53 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247943 | T-127 E | Adder | 5.39 MW | 4.58 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 924261 | AB2-070 C O1 | Adder | 1.99 MW | 1.69 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 924262 | AB2-070 E O1 | Adder | 13.32 MW | 11.32 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 925771 | AC1-053 C | Adder | 2.0 MW | 1.7 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 925772 | AC1-053 E | Adder | 13.38 MW | 11.37 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930461 | AB1-087 | 50/50 | 129.88 MW | 129.88 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930471 | AB1-088 | 50/50 | 129.88 MW | 129.88 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933441 | AC2-157 C | 50/50 | 17.95 MW | 17.95 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933442 | AC2-157 E | 50/50 | 29.28 MW | 29.28 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 243442 | 05RKG1 | 50/50 | 101.49 MW | 101.49 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 243443 | 05RKG2 | 50/50 | 97.3 MW | 97.3 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247900 | 05FR-11G E | Adder | 6.17 MW | 5.25 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247901 | 05FR-12G E | Adder | 6.07 MW | 5.16 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247902 | 05FR-21G E | Adder | 6.49 MW | 5.51 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247903 | 05FR-22G E | Adder | 6.21 MW | 5.28 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247904 | 05FR-3G E | Adder | 12.58 MW | 10.69 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247905 | 05FR-4G E | Adder | 9.46 MW | 8.04 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247906 | 05MDL-1G E | Adder | 10.77 MW | 9.15 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247907 | 05MDL-2G E | Adder | 5.34 MW | 4.54 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247912 | 05MDL-3G E | Adder | 5.58 MW | 4.75 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 276150 | W2-048 E | Adder | 1.05 MW | 0.89 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 905082 | W4-005 E | Adder | 19.76 MW | 16.8 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 909052 | X2-022 E | Adder | 14.54 MW | 12.36 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 915662 | Y3-099 E | Adder | 0.16 MW | 0.13 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 915672 | Y3-100 E | Adder | 0.16 MW | 0.13 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936771 | AD2-100 C O1 | Adder | 10.6 MW | 9.01 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936772 | AD2-100 E O1 | Adder | 7.06 MW | 6.0 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936971 | AD2-131 C O1 | Adder | 0.7 MW | 0.59 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936972 | AD2-131 E O1 | Adder | 3.51 MW | 2.98 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 954681 | J949 | External Queue | 13.19 MW | 13.19 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966791 | J1180 | External Queue | 10.79 MW | 10.79 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.32 MW | 0.32 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 12.05 MW | 12.05 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 54.18 MW | 54.18 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CHILHOWEE | LTFEXP_CHILHOWEE->LTFIMP_CHILHOWEE | CLTF | 0.09 MW | 0.09 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 1.68 MW | 1.68 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | LTF | 4.67 MW | 4.67 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 93.5 MW | 93.5 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 20.18 MW | 20.18 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LGE-0092018 | LTFEXP_LGE-0092018->LTFIMP_LGE-0092018 | LTF | 0.0 MW | 0.0 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | MECS | LTFEXP_MECS->LTFIMP_MECS | CLTF | 4.55 MW | 4.55 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.31 MW | 3.31 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 10.74 MW | 10.74 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.58 MW | 0.58 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.26 MW | 0.26 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | SANTEETLA | LTFEXP_SANTEETLA->LTFIMP_SANTEETLA | CLTF | 0.08 MW | 0.08 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.61 MW | 0.61 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 24.38 MW | 24.38 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CHOCTAW | LTFEXP_CHOCTAW->LTFIMP_CHOCTAW | LTF | 0.0 MW | 0.0 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.27 MW | 0.27 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 6.66 MW | 6.66 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.46 MW | 0.46 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.35 MW | 0.35 MW |
| 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 8.55 MW | 8.55 MW |
| Details for 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 936381 | AD2-048 C | 80/20 | 4.34 MW | 4.34 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942411 | AE2-254 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942481 | AE2-261 C | Adder | 9.14 MW | 7.77 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942591 | AE2-275 C O1 | 80/20 | 8.4 MW | 8.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942601 | AE2-276 | 80/20 | 3.75 MW | 3.75 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942891 | AE2-308 C O1 | 80/20 | 14.13 MW | 14.13 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 943111 | AE2-339 C | 80/20 | 3.16 MW | 3.16 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342900 | 1COOPER1 G | 80/20 | 2.66 MW | 2.66 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342903 | 1COOPER2 G | 80/20 | 5.15 MW | 5.15 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342918 | 1JKCT 1G | 80/20 | 2.1 MW | 2.1 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342921 | 1JKCT 2G | 80/20 | 2.1 MW | 2.1 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342924 | 1JKCT 3G | 80/20 | 2.1 MW | 2.1 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342927 | 1JKCT 4G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342930 | 1JKCT 5G | 80/20 | 1.39 MW | 1.39 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342933 | 1JKCT 6G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342936 | 1JKCT 7G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342939 | 1JKCT 9G | 80/20 | 1.43 MW | 1.43 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342942 | 1JKCT 10G | 80/20 | 1.43 MW | 1.43 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 342945 | 1LAUREL 1G | 80/20 | 1.5 MW | 1.5 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 939131 | AE1-143 C | 80/20 | 11.68 MW | 11.68 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 940831 | AE2-071 C | 80/20 | 3.69 MW | 3.69 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 941341 | AE2-130 C | Adder | 36.01 MW | 30.61 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 941411 | AE2-138 C | 80/20 | 18.79 MW | 18.79 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 941981 | AE2-210 C O1 | 80/20 | 6.47 MW | 6.47 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 925981 | AC1-074 C O1 | 80/20 | 4.96 MW | 4.96 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 930461 | AB1-087 | 80/20 | 41.3 MW | 41.3 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 930471 | AB1-088 | 80/20 | 41.3 MW | 41.3 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 932551 | AC2-075 C | 80/20 | 1.18 MW | 1.18 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 933441 | AC2-157 C | 80/20 | 5.71 MW | 5.71 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 936571 | AD2-072 C O1 | 80/20 | 12.31 MW | 12.31 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 243442 | 05RKG1 | 80/20 | 15.77 MW | 15.77 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 936771 | AD2-100 C O1 | Adder | 6.57 MW | 5.58 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 936971 | AD2-131 C O1 | Adder | 0.43 MW | 0.37 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 940041 | AE2-000D CO1 | 80/20 | 10.33 MW | 10.33 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 952821 | J762 | External Queue | 35.64 MW | 35.64 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 952861 | J783 C | External Queue | 10.9 MW | 10.9 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 953611 | J800 | External Queue | 16.58 MW | 16.58 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 952811 | J759 | External Queue | 11.49 MW | 11.49 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 27.68 MW | 27.68 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 28.86 MW | 28.86 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.33 MW | 1.33 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 191.47 MW | 191.47 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 9.47 MW | 9.47 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.48 MW | 1.48 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 4.74 MW | 4.74 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.22 MW | 0.22 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 45.96 MW | 45.96 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 20.17 MW | 20.17 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CHOCTAW | LTFEXP_CHOCTAW->LTFIMP_CHOCTAW | LTF | 0.0 MW | 0.0 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.17 MW | 0.17 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 15.41 MW | 15.41 MW |
| Details for 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936381 | AD2-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942411 | AE2-254 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942481 | AE2-261 C | Adder | 9.23 MW | 7.85 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942591 | AE2-275 C O1 | 80/20 | 8.43 MW | 8.43 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942601 | AE2-276 | 80/20 | 3.78 MW | 3.78 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942891 | AE2-308 C O1 | 80/20 | 14.19 MW | 14.19 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 943111 | AE2-339 C | 80/20 | 3.18 MW | 3.18 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342900 | 1COOPER1 G | 80/20 | 2.67 MW | 2.67 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342903 | 1COOPER2 G | 80/20 | 5.17 MW | 5.17 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342918 | 1JKCT 1G | 80/20 | 2.11 MW | 2.11 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342921 | 1JKCT 2G | 80/20 | 2.11 MW | 2.11 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342924 | 1JKCT 3G | 80/20 | 2.11 MW | 2.11 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342927 | 1JKCT 4G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342930 | 1JKCT 5G | 80/20 | 1.39 MW | 1.39 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342933 | 1JKCT 6G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342936 | 1JKCT 7G | 80/20 | 1.4 MW | 1.4 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342939 | 1JKCT 9G | 80/20 | 1.44 MW | 1.44 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342942 | 1JKCT 10G | 80/20 | 1.44 MW | 1.44 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 342945 | 1LAUREL 1G | 80/20 | 1.51 MW | 1.51 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 939131 | AE1-143 C | 80/20 | 11.71 MW | 11.71 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 940831 | AE2-071 C | 80/20 | 3.71 MW | 3.71 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941341 | AE2-130 C | 80/20 | 36.26 MW | 36.26 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941411 | AE2-138 C | 80/20 | 18.89 MW | 18.89 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941981 | AE2-210 C O1 | 80/20 | 6.51 MW | 6.51 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 925981 | AC1-074 C O1 | 80/20 | 4.99 MW | 4.99 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930461 | AB1-087 | 80/20 | 41.58 MW | 41.58 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930471 | AB1-088 | 80/20 | 41.58 MW | 41.58 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 932551 | AC2-075 C | 80/20 | 1.19 MW | 1.19 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933441 | AC2-157 C | 80/20 | 5.75 MW | 5.75 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936571 | AD2-072 C O1 | 80/20 | 12.35 MW | 12.35 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243442 | 05RKG1 | 80/20 | 15.88 MW | 15.88 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936771 | AD2-100 C O1 | Adder | 6.63 MW | 5.64 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936971 | AD2-131 C O1 | Adder | 0.44 MW | 0.37 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 940041 | AE2-000D CO1 | 80/20 | 10.36 MW | 10.36 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 952821 | J762 | External Queue | 35.64 MW | 35.64 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 952861 | J783 C | External Queue | 10.9 MW | 10.9 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953611 | J800 | External Queue | 16.58 MW | 16.58 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 952811 | J759 | External Queue | 11.49 MW | 11.49 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 27.72 MW | 27.72 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 28.99 MW | 28.99 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.37 MW | 1.37 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 192.7 MW | 192.7 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 9.77 MW | 9.77 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.51 MW | 1.51 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 4.83 MW | 4.83 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.2 MW | 0.2 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 46.12 MW | 46.12 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 20.41 MW | 20.41 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | CHOCTAW | LTFEXP_CHOCTAW->LTFIMP_CHOCTAW | LTF | 0.0 MW | 0.0 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.16 MW | 0.16 MW |
| 7TRIMBLE CO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 15.49 MW | 15.49 MW |
| Details for 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 942601 | AE2-276 | 80/20 | 10.89 MW | 10.89 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 941341 | AE2-130 C | 80/20 | 104.54 MW | 104.54 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 930461 | AB1-087 | 80/20 | 119.79 MW | 119.79 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 930471 | AB1-088 | 80/20 | 119.79 MW | 119.79 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 933441 | AC2-157 C | 80/20 | 16.55 MW | 16.55 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 243442 | 05RKG1 | 80/20 | 45.77 MW | 45.77 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | 243443 | 05RKG2 | 80/20 | 43.88 MW | 43.88 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 29.36 MW | 29.36 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CLTF | 0.43 MW | 0.43 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.11 MW | 0.11 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | EDWARDS | LTFEXP_EDWARDS->LTFIMP_EDWARDS | CLTF | 0.06 MW | 0.06 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 2.99 MW | 2.99 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | TILTON | LTFEXP_TILTON->LTFIMP_TILTON | CLTF | 4.55 MW | 4.55 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.14 MW | 3.14 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.09 MW | 0.09 MW |
| 05DARWIN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363 | IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 4.49 MW | 4.49 MW |
Light Load Analysis
The Queue Project was evaluated as a 800.0 MW (Capacity 480.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7980.1 | Rebuild 3.83 miles of 2303.5 ACAR , conductor section 1 | $7,660,000 | |
| n4106.3 | Extend One (1) Tower on the Jefferson - Clifty Creek (IKEC) 345 kV Circuit | $409,714 | |
| n4106 | Replace Two (2) Switches at the Clifty Creek 345 kV Station | $412,916 | |
| b3748 | Replace four Clifty Creek 345 kV 3000A switches with 5000 A 345 kV switches | $850,000 | |
| b2878 | Upgrade the Clifty Creek 345 kV risers | $3,675,000 | |
| b2943 | PJM Baseline Upgrade b2943. Perform a LIDAR study on the Clifty Creek - Dea [...] rating. The baseline project had a projected in-service date of 12/01/2020. | $127,896 | |
| n7979 | Replace one 1600 A Wavetrap at Clifty Creek, $200k, 12-18 months. The new SE rating is 1281 MVA SE. | $200,000 | |
| (TBD) | No OVEC end upgrade required. The line is owned by LG&E. | $0 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
| n6628 | Add a 765 kV breaker ‘B2’ at Jefferson 765 kV to eliminate stuck breaker contingency ‘AEP_P4_#8648_05JEFRSO 765_B’ | $4,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AE2-130 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.