Committees & Groups

Issue Details

Distributed Energy Resources in PJM Markets

The market for distributed resources is gaining momentum and warrants PJM stakeholder consideration on the most effective and least cost solution to integrate these systems into the PJM market. Customers are installing generation and storage that is capable of injecting power past their load meter. Part of the purpose of this Problem Statement is to establish a framework for distributed resources to participate when both reducing load and injecting power past the load meter.
 
This Problem Statement also addresses concerns about the PJM interconnection process as applied to distributed resources.

Issue Details

Strategic Focus Area: Markets
Issue Status: Solution Alternatives Proposed
Stakeholder Body: Distributed Energy Resources Subcommittee
Stakeholder Process Status: Packages
Issue Catalyst: A.F. Mensah
Date Created: 1.28.2016
MC Approval Date:
Target Completion Date: 8.31.2017
Actual Completion Date:
FERC Filing(s): Yes
Agreement Change(s): Open Access Transmission Tariff, Operating Agreement, Reliability Assurance Agreement
Manual Change(s): No
MC Annual Plan: 2019
Date Documents
1.28.2016 Meeting materials from the MRC meeting
Item 05 - Distributed Battery Storage Issue Charge  PDF
Item 05 - Distributed Battery Storage Issue Charge - Revised - Redline  PDF
Item 05 - Distributed Battery Storage Problem Statement  PDF
Item 05 - Distributed Battery Storage Problem Statement - Revised - Clean  PDF
Item 05 - Distributed Battery Storage Issue Charge  PDF
Item 05 - Distributed Battery Storage Problem Statement - Revised - Redline  PDF
Item 05 - Distributed Battery Storage Issue Charge - Revised - Redline  PDF
Item 05 - Distributed Battery Storage Problem Statement  PDF
Item 05 - Distributed Battery Storage Problem Statement - Revised - Clean  PDF
Item 05 - Distributed Battery Storage Problem Statement - Revised - Redline  PDF
2.1.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 4 – DER Definition  PDF
Item 4 – DER Definition  PDF
Item 5 – Interconnection Process Review  PDF
Item 5 – Interconnection Process Review  PDF
Item 8 – FERC NOPR Discussion  PDF
Item 8 – FERC NOPR Discussion  PDF
Item 8 – FERC NOPR – Electric Storage Resources & DER Aggregation (RM16-23-000)  PDF
Item 8 – FERC NOPR – Electric Storage Resources & DER Aggregation (RM16-23-000)  PDF
DER Solutions Matrix  XLS
DER Solutions Matrix  XLS
DER Solutions Matrix - Post-Meeting  XLS
DER Solutions Matrix - Post-Meeting  XLS
8.18.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  DOC
Item 2 – Draft Minutes – 8.1.2017  PDF
Item 4 – Icetec Case Studies  PDF
Agenda  PDF
Item 6 – Draft Manual 14A – Clean  PDF
Item 6 – Draft Manual 14A – Redline  PDF
Agenda  DOC
Item 2 – Draft Minutes – 8.1.2017  PDF
Item 6 – Manual 14A Updates  PDF
Item 4 – Icetec Case Studies  PDF
Item 6 – Draft Manual 14A – Clean  PDF
Item 6 – Draft Manual 14A – Redline  PDF
Item 6 – Manual 14A Updates  PDF
6.30.2016 Meeting materials from the MRC meeting
Item 1 - Draft Minutes - MRC - 6.17.2016  PDF
Item 1 - Draft Minutes - MRC - 6.17.2016  PDF
12.6.2018 Meeting materials from the MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 9 - DERS Manual 11 Revisions Redline  PDF
Item 9 - DERS Manual 14D Revisions Redline  PDF
Item 9 - DERS OATT Revisions Redline  PDF
Item 9 - DERS Manual 11 Revisions Redline  PDF
Item 9 - DERS Proposal Final Report  PDF
Item 9 - DERS Manual 14D Revisions Redline  PDF
Item 9 - DERS Proposal Presentation  PDF
Item 9 - DERS OATT Revisions Redline  PDF
Item 9 - DERS Wholesale DER Solutions Matrix - Ancillary Services  XLS
Item 9 - DERS Proposal Final Report  PDF
Item 9 - DERS Proposal Presentation  PDF
Item 9 - DERS Wholesale DER Solutions Matrix - Ancillary Services  XLS
3.20.2017 Meeting materials from the MC Information Webinar meeting
Item 4 - DER - Queue Processes Changes  PDF
Item 4 - DER - Queue Processes Changes  PDF
3.2.2017 Meeting materials from the MIC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 6 – 2016 DER Annual Report  PDF
Item 6 – 2016 DER Annual Report  PDF
10.31.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Draft Minutes - DERS - 10.4.2018  PDF
Draft Minutes - DERS - 10.4.2018  PDF
Item 6 - Interconnection Solutions Matrix  XLS
Item 6 - Interconnection Solutions Matrix  XLS
Item 6 - Interconnection Solutions Matrix - Updated  XLS
Item 6 - Interconnection Solutions Matrix - Updated  XLS
Item 7 - Progress Update on State Regulatory Code Comparison for Wholesale DER Interconnecting Under State Jurisdiction  PDF
Item 7 - Progress Update on State Regulatory Code Comparison for Wholesale DER Interconnecting Under State Jurisdiction  PDF
Item 7 - State Interconnection Policy Scope Language  PDF
Item 7 - State Interconnection Policy Scope Language  PDF
Item 9 - IMM Co-Located Demand Response and Generation  PDF
Item 9 - IMM Co-Located Demand Response and Generation  PDF
Item 10 - DER Ancillary Services Solutions Matrix  XLS
Item 10 - DER Ancillary Services Solutions Matrix  XLS
Work Plan  XLS
Work Plan  XLS
6.17.2016 Meeting materials from the Special MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 1 - Draft Minutes - MRC - 5.26.2016  PDF
Item 1 - Draft Minutes - MRC - 5.26.2016  PDF
Item 2 - PJM Net Energy Injections Quarterly Review  PDF
Item 2 - PJM Net Energy Injections Quarterly Review  PDF
Item 3 - Jurisdictional Over Interconnection of Generation onto Distribution Facilities  PDF
Item 3 - Jurisdictional Over Interconnection of Generation onto Distribution Facilities  PDF
Item 4 - DER Path to PJM Participation  PDF
Item 4 - DER Path to PJM Participation  PDF
Item 5 - Benefits from Generation & Storage on the Distribution System  PDF
Item 5 - Benefits from Generation & Storage on the Distribution System  PDF
Item 6 - Distributed Energy Resource Scenarios  PDF
Item 6 - Distributed Energy Resource Scenarios  PDF
Item 7 - DER RTO Benchmarking  PDF
Item 7 - DER RTO Benchmarking  PDF
3.4.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Draft Minutes - DERS - 2.4.2019  PDF
Agenda  DOC
Item 4 - Utility Microgrid Issue Discussion  PDF
Draft Minutes - DERS - 2.4.2019  PDF
Item 5 - State Interconnection Rules & Regulations  PDF
Item 4 - Utility Microgrid Issue Discussion  PDF
Item 5 - State Interconnection Rules & Regulations  PDF
Item 7 - Interconnection Matrix Package Review  PDF
Item 7 - Interconnection Matrix Package Review - Updated  PDF
Item 7 - Interconnection Matrix Package Review  PDF
Work Plan  XLS
Item 7 - Interconnection Matrix Package Review - Updated  PDF
Work Plan  XLS
12.13.2017 Meeting materials from the MIC meeting
Item 1 - Draft Minutes - MIC - 11.8.2017  PDF
Item 1 - Draft Minutes - MIC - 11.8.2017  PDF
6.29.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 6.8.2018  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 6.8.2018  PDF
Item 5 - Wholesale DER Solution Matrix  XLS
Item 5A - Ancillary Services Measurements  PDF
Item 5A - Demand Response Metering Requirements  PDF
Item 5 - Wholesale DER Solution Matrix  XLS
Item 5A - Ancillary Services Measurements  PDF
Item 5A - Demand Response Metering Requirements  PDF
12.20.2018 Meeting materials from the MRC meeting
Consent Agenda A - Draft 12.6.2018 MRC Minutes  PDF
Consent Agenda A - Draft 12.6.2018 MRC Minutes  PDF
Item 6 - DERS Final Proposal Report  PDF
Item 6 - DERS Final Proposal Report  PDF
Item 6 - DERS Manual 11 Revisions Redline  PDF
Item 6 - DERS Manual 11 Revisions Redline  PDF
Item 6 - DERS OATT Revisions Redline  PDF
Item 6 - DERS OATT Revisions Redline  PDF
Item 6 - DERS Proposal Presentation  PDF
Item 6 - DERS Proposal Presentation  PDF
Item 6 - DERS Solution Matrix Ancillary Services  XLS
Item 6 - DERS Solution Matrix Ancillary Services  XLS
Item 6 - Manual 14D Revisions Redline  PDF
Item 6 - Manual 14D Revisions Redline  PDF
12.17.2015 Meeting materials from the MRC meeting
Item 08 - Distributed Battery Storage - Issue Charge  PDF
Item 08 - Distributed Battery Storage - Problem Statement  PDF
Item 08 - Distributed Battery Storage - Issue Charge  PDF
Item 08 - Distributed Battery Storage - Problem Statement  PDF
9.26.2016 Meeting materials from the MC Information Webinar meeting
Item 13A - MRC - DER Report  PDF
Item 13A - MRC - DER Report  PDF
10.10.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 9.9.2019  PDF
Item 2 - Draft Minutes - DERS - 9.9.2019  PDF
Item 4 - 2019 Stakeholder Survey Reminder  PDF
Item 4 - 2019 Stakeholder Survey Reminder  PDF
Item 5 - Wholesale DER Interconnection Proposal Voting Results  PDF
Item 5 - Wholesale DER Interconnection Proposal Voting Results  PDF
Item 6 - Declaration of Authority Presentation  PDF
Item 6 - Declaration of Authority Presentation  PDF
Item 6 - Declaration of Authority Template  PDF
Item 6 - Declaration of Authority Template  PDF
Item 7 - PJM Response to FERC Request for Information Docket No. RM18-9-000  PDF
Item 8 - PJM DER Considerations  PDF
Item 7 - PJM Response to FERC Request for Information Docket No. RM18-9-000  PDF
Item 09 – Utility Microgrid Poll Results  PDF
Item 8 - PJM DER Considerations  PDF
Item 09 – Utility Microgrid Poll Results  PDF
10.2.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - 9.18.2017  PDF
Item 2 - Draft Minutes - 9.18.2017  PDF
Item 5 - PJM Straw Proposal for DER in the Energy Market  PDF
Item 5 - PJM Straw Proposal for DER in the Energy Market  PDF
Item 6 - PJM Straw Proposal for DER Ruleset & Aggregation  PDF
Item 6 - PJM Straw Proposal for DER Ruleset & Aggregation  PDF
9.18.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 – Draft Minutes – MIC - 8.31.2017  PDF
Item 2 – Draft Minutes – MIC - 8.31.2017  PDF
Item 3 – Energy Market Settlements Education  PDF
Item 3 – Energy Market Settlements Education  PDF
Item 4 – DR Energy Market Settlements Education  PDF
Item 4 – DR Energy Market Settlements Education  PDF
Item 5A – DER Stakeholder Group Charter Presentation  PDF
Item 5A – DER Stakeholder Group Charter Presentation  PDF
10.12.2016 Meeting materials from the MRC - Special meeting
Agenda  PDF
Agenda  DOC
Item 1 - Small Generator Interconnection Queue Process Issues  PDF
Item 2 - Market Participation Rules   PDF
Agenda  PDF
Agenda  DOC
Item 1 - Small Generator Interconnection Queue Process Issues  PDF
Item 2 - Market Participation Rules   PDF
7.10.2018 Meeting materials from the OC meeting
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - OC - 6.5.2018  PDF
Item 13 - DERS Behind-the-Meter Generation Observability Manual Changes - 2018 V4  PDF
Item 2 - Draft Minutes - OC - 6.5.2018  PDF
Item 13 - DERS Behind-the-Meter Generation Observability Manual Changes - 2018 V4  PDF
8.24.2016 Meeting materials from the MRC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 1A - Benefits from Generation & Storage on the Distribution System  PDF
Item 1A - Benefits from Generation & Storage on the Distribution System  PDF
Item 1B - Summary of FERC 792 in Context of DER  PDF
Item 1B - Summary of FERC 792 in Context of DER  PDF
Item 1C - DER Telemetry Metering & Communication Requirements  PDF
Item 1C - DER Telemetry Metering & Communication Requirements  PDF
Item 1D - V2G Project  PDF
Item 1D - V2G Project  PDF
Item 2 - DER RTO Benchmarking  PDF
Item 2 - DER RTO Benchmarking  PDF
Item 3 - Third Party Arrangements  PDF
Item 3 - Third Party Arrangements  PDF
Item 4 - Distributed Battery Storage - Issue Charge Revised 1.28.2016 - Clean  PDF
Item 4 - Distributed Battery Storage - Issue Charge Revised 1.28.2016 - Clean  PDF
7.7.2017 Meeting materials from the Special MIC – Distributed Energy Resources meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - MIC - 6.20.2017  PDF
Item 2 - Draft Minutes - MIC - 6.20.2017  PDF
Item 5 - Solutions Matrix  XLS
Item 5 - Solutions Matrix  XLS
Item 6 - Status Quo of Generation Aggregation  PDF
Item 6 - Status Quo of Generation Aggregation  PDF
PJM Staff Strawman Proposal for MIC on DER: Ancillary Services  PDF
PJM Staff Strawman Proposal for MIC on DER: Ancillary Services  PDF
Informational Only – IEEE 1547 DER Interconnection Standard Workshop  PDF
Informational Only – IEEE 1547 DER Interconnection Standard Workshop  PDF
12.21.2017 Meeting materials from the MRC meeting
Item 1 - Draft Minutes - MRC - 12.7.2017  PDF
Item 1 - Draft Minutes - MRC - 12.7.2017  PDF
10.23.2017 Meeting materials from the MC Information Webinar meeting
Item 9A - MRC Report  PDF
Item 9A - MRC Report  PDF
4.3.2018 Meeting materials from the OC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - OC - 3.6.2018  PDF
Item 2 - Draft Minutes - OC - 3.6.2018  PDF
Item 12 - DERS Update  PDF
Item 12 - DERS Update  PDF
11.27.2017 Meeting materials from the MC Information Webinar meeting
Item 10A - MRC Report  PDF
Item 10A - MRC Report  PDF
Item 10B - MIC Minutes Report  PDF
Item 10B - MIC Minutes Report  PDF
10.4.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - DERS - 8.27.2018  PDF
Item 2 - Draft Minutes - DERS - 8.27.2018  PDF
Item 4 - DERS Workplan 2018  XLS
Item 4 - DERS Workplan 2018  XLS
Item 5 - State Policies on Small Generation Interconnection  PDF
Item 5 - State Policies on Small Generation Interconnection  PDF
Item 6 - DER Interconnection Data Request  PDF
Item 6 - DER Interconnection Data Request  PDF
Item 8 - Wholesale DER Operational Requirements  PDF
Item 8 - Wholesale DER Operational Requirements  PDF
Item 9 - Status Quo for DR with Injection  PDF
Item 9 - Status Quo for DR with Injection  PDF
DER Interconnection Solutions Matrix - Post-Meeting  XLS
DER Interconnection Solutions Matrix - Post-Meeting  XLS
6.20.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - MIC - 6.1.2017  PDF
Item 2 - Draft Minutes - MIC - 6.1.2017  PDF
Item 4 - DER Definitions  PDF
Item 4 - DER Definitions  PDF
Item 5 - Metering & Communication Requirements  PDF
Item 5 - Metering & Communication Requirements  PDF
1.24.2019 Meeting materials from the MC meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Agenda  DOC
Consent Agenda Item B - OA and OATT Revisions - On-Site Generator  PDF
Consent Agenda Item B - OA and OATT Revisions - On-Site Generator  PDF
6.1.2017 Meeting materials from the MIC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - MIC - 5.19.2017  PDF
Item 2 - Draft Minutes - MIC - 5.19.2017  PDF
Item 3 - Updated Work Plan  PDF
Item 3 - Updated Work Plan  PDF
Item 4 – DR Aggregation Rules  PDF
Item 4 – DR Aggregation Rules  PDF
Item 5 - CBIR Solutions Matrix  XLS
Item 5 - CBIR Solutions Matrix  XLS
12.22.2016 Meeting materials from the MRC meeting
Item 1 - Draft Minutes - MRC - 11.17.2016  PDF
Item 1 - Draft Minutes - MRC - 11.17.2016  PDF
11.30.2018 Meeting materials from the DERS meeting
Item 2 - Draft Minutes - DERS - 11.15.2018  PDF
Item 2 - Draft Minutes - DERS - 11.15.2018  PDF
Item 4 - Draft Statement on Applicability of PJM Requirements to WMPAs  PDF
Item 4 - Draft Statement on Applicability of PJM Requirements to WMPAs  PDF
Item 6 - Manual 11  PDF
Item 6 - Manual 11  PDF
Item 6 - Manual 14D  PDF
Item 6 - Manual 14D  PDF
Item 6 - Manual 14D - Revised  PDF
Item 6 - Manual 14D - Revised  PDF
Item 6 - Proposal Redlines - On-Site Generator  PDF
Item 6 - Proposal Redlines - On-Site Generator  PDF
DERS Solutions Matrix - Interconnection  XLS
DERS Solutions Matrix - Interconnection - Updated  XLS
DERS Solutions Matrix - Interconnection  XLS
DERS Solutions Matrix - Interconnection - Updated  XLS
6.10.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 5.20.2019  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 5.20.2019  PDF
Item 4 - Small Project Statistics  PDF
Item 5 - Solutions Matrix - Interconnection  XLS
Item 4 - Small Project Statistics  PDF
Item 6 - Utility Microgrid Generation - Solutions Matrix  XLS
Item 5 - Solutions Matrix - Interconnection  XLS
Item 6 – Utility Microgrid Generation – Solutions Matrix – Post-meeting Update  XLS
Item 6 - Utility Microgrid Generation - Solutions Matrix  XLS
Item 7 - Economic DR with On-site-Generator  PDF
Item 6 – Utility Microgrid Generation – Solutions Matrix – Post-meeting Update  XLS
Item 7 - PJM W-DER Draft Proposal Summary  PDF
Item 7 - Economic DR with On-site-Generator  PDF
Item 7 - PJM W-DER Draft Proposal Summary  PDF
11.8.2017 Meeting materials from the MIC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 8A - Distributed Energy Resources Subcommittee Draft Charter  PDF
Item 8B - Distributed Energy Resources Subcommittee Draft Charter Proposed Amendment  PDF
Item 8A - Distributed Energy Resources Subcommittee Draft Charter  PDF
Item 8B - Distributed Energy Resources Subcommittee Draft Charter Proposed Amendment  PDF
11.6.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - MIC - 10.18.2017  PDF
Agenda  PDF
Item 4 – Icetec DER Interconnection Proposal  PDF
Agenda  DOC
Item 5 – Unidirectional Metering Example  PDF
Item 2 - Draft Minutes - MIC - 10.18.2017  PDF
Jurisdictional Over Interconnection of Generation onto Distribution Facilities  PDF
Item 4 – Icetec DER Interconnection Proposal  PDF
DER Solutions Matrix  XLS
Item 5 – Unidirectional Metering Example  PDF
Jurisdictional Over Interconnection of Generation onto Distribution Facilities  PDF
DER Solutions Matrix  XLS
4.18.2016 Meeting materials from the Special MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 1 - Draft MRC Minutes - 3.31.2016  PDF
Item 1 - Draft MRC Minutes - 3.31.2016  PDF
Item 2A - Distributed Battery Storage Issue Charge - Revised  PDF
Item 2A - Distributed Battery Storage Issue Charge - Revised  PDF
Item 2A - Distributed Battery Storage Problem Statement Revised  PDF
Item 2A - Distributed Battery Storage Problem Statement Revised  PDF
Item 2A - Problem Statement Presentation  PDF
Item 2A - Problem Statement Presentation  PDF
Item 2B - Problem Statement - AF Mensah Presentation  PDF
Item 2B - Problem Statement - AF Mensah Presentation  PDF
Item 2C - Distributed Battery Storage Problem Statement Proposed Revision  PDF
Item 2C - Distributed Battery Storage Problem Statement Proposed Revision  PDF
Item 3A - State & Federal Jurisdictional Rules & Regulations Related to DER  PDF
Item 3A - State & Federal Jurisdictional Rules & Regulations Related to DER  PDF
Item 3B - DER Scenarios  PDF
Item 3B - DER Scenarios  PDF
12.7.2017 Meeting materials from the MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 1 - Draft Minutes - MRC - 10.26.2017  PDF
Item 1 - Draft Minutes - MRC - 10.26.2017  PDF
Item 3 - Distributed Energy Resources Subcommittee - Draft Charter  PDF
Item 3 - Distributed Energy Resources Subcommittee - Draft Charter  PDF
8.27.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Draft Minutes - DERS - 7.30.2018  PDF
Draft Minutes - DERS - 7.30.2018  PDF
Item 7 - Wholesale DER Interconnections  PDF
Item 7 - Issue Description: Wholesale Market Participation Agreement Operational Requirements  PDF
Item 7 - Wholesale DER Interconnections  PDF
Item 7 - Issue Description: Wholesale Market Participation Agreement Operational Requirements  PDF
Item 8 - Order 841: Straw Proposal  PDF
Item 9 - PJM Straw Proposal AS for BTCM DER  PDF
Item 8 - Order 841: Straw Proposal  PDF
Item 9 - PJM Straw Proposal AS for BTCM DER  PDF
Wholesale DER Solutions Matrix Ancillary Services  XLS
Wholesale DER Solutions Matrix Ancillary Services  XLS
5.21.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 4.25.2018  PDF
Agenda  PDF
Agenda  DOC
Item 5 - Method to Calculate WSE for FTM ESR  PDF
Item 2 - Draft Minutes - DERS - 4.25.2018  PDF
Item 5 - OA Schedule 1 Section 1.7 - Redline  PDF
Item 5 - OATT Attachment K Appendix Section 1.7 - Redline  PDF
Item 5 - OATT Definitions E-F - Redline  PDF
Item 5 - OATT Definitions R-S - Redline  PDF
Item 5 - OATT Definitions -W-X-Y-Z - Redline  PDF
Item 5 - Method to Calculate WSE for FTM ESR  PDF
Item 5 - Wholesale DER Solutions Matrix  XLS
Item 5 - OA Schedule 1 Section 1.7 - Redline  PDF
Item 5 - OATT Attachment K Appendix Section 1.7 - Redline  PDF
Item 5 - OATT Definitions E-F - Redline  PDF
Item 5 - OATT Definitions R-S - Redline  PDF
Item 5 - OATT Definitions -W-X-Y-Z - Redline  PDF
Item 5 - Wholesale DER Solutions Matrix  XLS
3.2.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - DERS - 1.31.2018  PDF
Item 2 - Draft Minutes - DERS - 1.31.2018  PDF
Item 3 - Informational Updates  PDF
Item 3 - Informational Updates  PDF
Item 3C - Order 841 - Electric Storage Resources in RTO ISO Markets  PDF
Item 3C - Order 841 - Electric Storage Resources in RTO ISO Markets  PDF
Item 3D - FERC Notice of DER Tech Conference  PDF
Item 3D - FERC Notice of DER Tech Conference  PDF
Item 4 - Compensating Curtailed MWh from Sites with Wholesale DER  PDF
Item 4 - Compensating Curtailed MWh from Sites with Wholesale DER  PDF
Item 5A - PJM W-DER Proposal – Roles & Responsibilities Example  PDF
Item 5A - PJM W-DER Proposal – Roles & Responsibilities Example  PDF
Item 5B - Icetec Grid Integrated Resource Proposal - Roles & Responsibilities Example  PDF
Item 5B - Icetec Grid Integrated Resource Proposal - Roles & Responsibilities Example  PDF
DERS Solutions Matrix - Wholesale DER  XLS
DERS Solutions Matrix - Wholesale DER  XLS
Basic Settlement Proposal – Calculation Examples  XLS
Basic Settlement Proposal – Calculation Examples  XLS
6.8.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 5.21.2018  PDF
Agenda  PDF
Agenda  DOC
Item 4 - Icetec Work Plan Proposal  PDF
Item 2 - Draft Minutes - DERS - 5.21.2018  PDF
Item 4 - Work Plan Discussion  PDF
Item 4A - 2018 Work Plan  XLS
Item 4 - Icetec Work Plan Proposal  PDF
Item 4A - 2018 Work Plan (Icetec Proposal)  XLS
Item 4 - Work Plan Discussion  PDF
Item 4A - 2018 Work Plan  XLS
Item 4A - 2018 Work Plan (Icetec Proposal)  XLS
8.31.2017 Meeting materials from the MIC - Special DER meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 – Draft Minutes – MIC – 8.18.2017  PDF
Item 2 – Draft Minutes – MIC – 8.18.2017  PDF
Item 4 - Comparison of Interconnection Process Under Proposals  PDF
Item 4 - Comparison of Interconnection Process Under Proposals  PDF
Item 6A – CAISO Coordination of Transmission & Distribution Operations  PDF
Item 6A – CAISO Coordination of Transmission & Distribution Operations  PDF
Item 6B – CAISO Coordination of Transmission & Distribution Operations Report  PDF
Item 6B – CAISO Coordination of Transmission & Distribution Operations Report  PDF
Solution Matrix  XLS
Solution Matrix  XLS
1.5.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 12.15.2017  PDF
Agenda  DOC
Item 5A - Capacity Market Considerations for BTCM  PDF
Item 5B - Demand Response Offers  PDF
Item 2 - Draft Minutes - DERS - 12.15.2017  PDF
Item 5B - Fuel Cost Policy Requirements & Cost-Based Offers  PDF
Item 5A - Capacity Market Considerations for BTCM  PDF
Item 6 – Icetec Proposal  PDF
Item 5B - Demand Response Offers  PDF
Item 5B - Fuel Cost Policy Requirements & Cost-Based Offers  PDF
Item 6 – Icetec Proposal  PDF
6.27.2016 Meeting materials from the MC Information Webinar meeting
Item 13A - Draft Minutes - MRC - 5.26.2016  PDF
Item 13A - Draft Minutes - MRC - 5.26.2016  PDF
Item 13A - Draft Minutes - MRC - 6.17.2016  PDF
Item 13A - Draft Minutes - MRC - 6.17.2016  PDF
10.18.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 – Draft Minutes – 10.2.2017  PDF
Item 2 – Draft Minutes – 10.2.2017  PDF
Item 3 – Solutions Matrix  XLS
Item 3 – Solutions Matrix  XLS
3.26.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - DRS - 3.2.2018  PDF
Item 2 - Draft Minutes - DRS - 3.2.2018  PDF
Item 3 – DER Poll Results  PDF
Item 3A – Polling Comments  XLS
Item 3 – DER Poll Results  PDF
Item 5 – PSEG Solar 4 All Example  PDF
Item 3A – Polling Comments  XLS
Item 6 – Icetec Accounting Proposal for Wholesale Energy Storage   PDF
Item 5 – PSEG Solar 4 All Example  PDF
Item 8 – PJM DER Ride Through Workshop  PDF
Item 6 – Icetec Accounting Proposal for Wholesale Energy Storage   PDF
Wholesale DER Solutions Matrix  XLS
Item 8 – PJM DER Ride Through Workshop  PDF
Wholesale DER Solutions Matrix  XLS
8.1.2017 Meeting materials from the Special MIC – Distributed Energy Resources meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - MIC - 7.7.2017  PDF
Item 2 - Draft Minutes - MIC - 7.7.2017  PDF
Item 3 – Icetec Draft Proposal  PDF
Item 3 – Icetec Draft Proposal  PDF
Item 5 – EDC in DR Process  PDF
Item 5 – EDC in DR Process  PDF
4.10.2017 Meeting materials from the MIC meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 – Draft Minutes – 3.2.2017  PDF
Agenda  DOC
Item 4 - Front of Meter Solar/Storage DER in PJM  PDF
Item 2 – Draft Minutes – 3.2.2017  PDF
Item 5 – DER Annual Report  PDF
Item 4 - Front of Meter Solar/Storage DER in PJM  PDF
Item 5 – DER Annual Report  PDF
Item 6 – CBIR Solutions Matrix  XLS
Item 6 – CBIR Solutions Matrix  XLS
Item 7 – Planning Committee Update  PDF
Item 7 – Planning Committee Update  PDF
Item 9 – Small DER Aggregation Example  PDF
Item 9 – Small DER Aggregation Example  PDF
3.19.2018 Meeting materials from the MC Webinar meeting
Item 8C - OC Report  PDF
Item 8C - OC Report  PDF
4.16.2018 Meeting materials from the MC Webinar meeting
Item 11C - OC Report  PDF
Item 11C - OC Report  PDF
6.6.2017 Meeting materials from the OC meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 17 - DER Stakeholder Process Update  PDF
Agenda  DOC
Item 17 - DER Stakeholder Process Update  PDF
7.30.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - DERS - 6.29.2018  PDF
Item 2 - Draft Minutes - DERS - 6.29.2018  PDF
Item 3 – Work Plan  XLS
Item 3 – Work Plan  XLS
Item 5 - Synchronized Reserve Performance Measurement  PDF
Item 5 - Synchronized Reserve Performance Measurement  PDF
Item 6 - Ancillary Services Measurement for BTCM  PDF
Item 6 - Ancillary Services Measurement for BTCM  PDF
Item 8 - Wholesale DER Interconnections  PDF
Item 8 - Wholesale DER Interconnections  PDF
7.23.2018 Meeting materials from the MC Information Webinar meeting
Item 9C - OC Report  PDF
Item 9C - OC Report  PDF
11.17.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - MIC - 11.6.2017  PDF
Agenda  PDF
Item 4 - DER Interconnection Q&A  PDF
Agenda  DOC
Item 5 – PJM Proposal Overview  PDF
MIC DER Solutions Matrix  XLS
Item 2 - Draft Minutes - MIC - 11.6.2017  PDF
Item 4 - DER Interconnection Q&A  PDF
Item 5 – PJM Proposal Overview  PDF
MIC DER Solutions Matrix  XLS
9.28.2017 Meeting materials from the MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 6 - Distributed Energy Resources  PDF
Item 6 - Distributed Energy Resources  PDF
Item 6 - Distributed Energy Resources Subcommittee Draft Charter  PDF
Item 6 - Distributed Energy Resources Subcommittee Draft Charter  PDF
Item 6 - Distributed Energy Resources Subcommittee Draft Charter - Proposed Friendly Amendment  PDF
Item 6 - Distributed Energy Resources Subcommittee Draft Charter - Proposed Friendly Amendment  PDF
1.22.2019 Meeting materials from the MC Webinar meeting
Item 7A - MRC Report - 12.6.2018  PDF
Item 7A - MRC Report - 12.6.2018  PDF
Item 7A - MRC Report - 12.20.2018  PDF
Item 7A - MRC Report - 12.20.2018  PDF
5.26.2016 Meeting materials from the MRC meeting
Item 10 - Distributed Battery Storage - Problem Statement - Proposed Revision  PDF
Item 10 - Draft DER Problem Statement Revision - Presentation  PDF
Item 10 - Distributed Battery Storage - Problem Statement - Proposed Revision  PDF
Item 10 - Draft DER Problem Statement Revision - Presentation  PDF
12.15.2017 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 11.17.2017  PDF
Agenda  DOC
Item 5 – Clarification on Point of Interconnection  PDF
Item 2 - Draft Minutes - DERS - 11.17.2017  PDF
Item 6 - Monitoring Analytics DER Comments  PDF
Item 5 – Clarification on Point of Interconnection  PDF
Item 6 - Monitoring Analytics DER Comments  PDF
Item 7 – Co-sited Wholesale DER & Demand Response  PDF
Item 7 – Co-sited Wholesale DER & Demand Response  PDF
Solutions Matrix  XLS
Solutions Matrix  XLS
Solutions Matrix – Updated  XLS
Solutions Matrix – Updated  XLS
9.9.2019 Meeting materials from the DERS meeting
Agenda  PDF
Draft Minutes - DERS - 8.21.2019  PDF
Item 4 - DERS Work Plan  XLS
Item 5 - Interconnection Solutions Matrix  XLS
Item 5 - Proposed Draft Manual Language for Package B  PDF
Agenda  PDF
Item 6 - Additional DER Interconnection Issues for Continued Exploration  PDF
Draft Minutes - DERS - 8.21.2019  PDF
Item 7 - PJM Wholesale Market Participation Agreement  PDF
Item 4 - DERS Work Plan  XLS
Item 8 - Utility Microgrid Islanding & PJM Energy Settlements  PDF
Item 5 - Interconnection Solutions Matrix  XLS
Item 9 - Utility Microgrid Solutions Matrix  XLS
Item 5 - Proposed Draft Manual Language for Package B  PDF
Informational Only - FERC Data Request on DER Interconnection  PDF
Item 6 - Additional DER Interconnection Issues for Continued Exploration  PDF
Item 7 - PJM Wholesale Market Participation Agreement  PDF
Item 8 - Utility Microgrid Islanding & PJM Energy Settlements  PDF
Item 9 - Utility Microgrid Solutions Matrix  XLS
Informational Only - FERC Data Request on DER Interconnection  PDF
4.28.2016 Meeting materials from the MRC meeting
Item 12 - Distributed Battery Storage - Problem Statement - Proposed Revision  PDF
Item 12 - Distributed Battery Storage - Problem Statement - Proposed Revision  PDF
Item 12 - Draft DER Problem Statement Revision - Presentation  PDF
Item 12 - Draft DER Problem Statement Revision - Presentation  PDF
7.15.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 6.10.2019  PDF
Item 4 - Third-Party Arrangements  PDF
Agenda  PDF
Item 5 - Solutions Matrix Interconnection  XLS
Item 6 - Utility Microgrid - IMM Presentation  PDF
Agenda  DOC
Item 7 - Solutions Matrix - Utility Microgrid Generation  XLS
Item 2 - Draft Minutes - DERS - 6.10.2019  PDF
Item 7 - Solutions Matrix - Utility Microgrid Generation - Post Meeting Update  XLS
Item 4 - Third-Party Arrangements  PDF
Item 5 - Solutions Matrix Interconnection  XLS
Item 6 - Utility Microgrid - IMM Presentation  PDF
Item 7 - Solutions Matrix - Utility Microgrid Generation  XLS
Item 7 - Solutions Matrix - Utility Microgrid Generation - Post Meeting Update  XLS
1.31.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 1.5.2018  PDF
Agenda  DOC
Item 3 - GIR Energy Market Example  PDF
Item 2 - Draft Minutes - DERS - 1.5.2018  PDF
Item 4 - Interactions Between Co-Sited Curtailment & W-DER  PDF
Item 6 - Wholesale Energy Storage  PDF
Item 3 - GIR Energy Market Example  PDF
Item 4 - Interactions Between Co-Sited Curtailment & W-DER  PDF
Item 6 - Wholesale Energy Storage  PDF
10.26.2017 Meeting materials from the MRC meeting
Item 1 - Draft Minutes - MRC - 9.28.2017  PDF
Item 1 - Draft Minutes - MRC - 9.28.2017  PDF
4.25.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - DERS - 3.26.2018  PDF
Item 2 - Draft Minutes - DERS - 3.26.2018  PDF
Item 5 - Informational Item  PDF
Item 5 - Informational Item  PDF
Item 5B - Icetec Wholesale Stored Energy Accounting Proposal  PDF
Item 5B - Icetec Wholesale Stored Energy Accounting Proposal  PDF
DERS Solutions Matrix Wholesale DER  XLS
DERS Solutions Matrix Wholesale DER  XLS
11.17.2016 Meeting materials from the MRC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 13 - Special MRC – Distributed Energy Resources Report  PDF
Item 13 - Special MRC – Distributed Energy Resources Report  PDF
11.22.2016 Meeting materials from the MRC - Special meeting
Agenda  PDF
Agenda  DOC
Item 1 - Special MRC – Distributed Energy Resources Report  PDF
Item 2 - Comparison DR vs Gen Measurement  PDF
Agenda  PDF
Item 3 - Consensus Based Issue Resolution Process  PDF
Agenda  DOC
Item 1 - Special MRC – Distributed Energy Resources Report  PDF
Item 2 - Comparison DR vs Gen Measurement  PDF
Item 3 - Consensus Based Issue Resolution Process  PDF
1.26.2018 Meeting materials from the DERS - Special meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
DERS Background  PDF
Agenda  DOC
DERS Education - PJM Proposal  PDF
DERS Background  PDF
DERS Status Quo Jurisdiction  PDF
DERS Education - PJM Proposal  PDF
DERS Status Quo Jurisdiction  PDF
2.4.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 3 - DERS Work Plan  XLS
Item 3 - DERS Work Plan  XLS
Item 4 - Non-Wholesale Distributed Energy Resources Visibility  PDF
Item 4 - Non-Wholesale Distributed Energy Resources Visibility  PDF
Item 5 - Economic DR with On-Site Generator  PDF
Item 5 - Economic DR with On-Site Generator  PDF
Item 8 - Interconnection Solutions Matrix  XLS
Item 8 - Interconnection Solutions Matrix  XLS
Informational Only - PJM Energy Storage Resource Accounting Proposal  PDF
Informational Only - PJM Energy Storage Resource Accounting Proposal  PDF
6.5.2018 Meeting materials from the OC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
9.25.2017 Meeting materials from the MC Information Webinar meeting
Item 10C - OC Report  PDF
Item 10C - OC Report  PDF
5.20.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Item 2 - Draft Minutes - DERS - 3.4.2019  PDF
Item 3 - Workplan  XLS
Agenda  DOC
Item 6 - Solutions Matrix - Interconnection  XLS
Item 7 - Draft Utility Microgrid Generation Considerations  PDF
Item 2 - Draft Minutes - DERS - 3.4.2019  PDF
Item 3 - Workplan  XLS
Item 6 - Solutions Matrix - Interconnection  XLS
Item 7 - Draft Utility Microgrid Generation Considerations  PDF
11.15.2018 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 10.31.2018  PDF
Item 2 - Draft Minutes - DERS - 10.31.2018  PDF
Item 4 - Wholesale DER Solutions Matrix  XLS
Item 4 - Wholesale DER Solutions Matrix  XLS
Item 4 - DR and Status Quo Draft Tariff and Manual Language  PDF
Item 4 - DR and Status Quo Draft Tariff and Manual Language  PDF
Item 5 - Primary Frequency Response and WMPA Projects  PDF
Item 5 - Primary Frequency Response and WMPA Projects  PDF
5.19.2017 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 2 - Draft Minutes - MIC - 4.10.2017  PDF
Item 3 - Behind-the-Meter Visibility  PDF
Item 2 - Draft Minutes - MIC - 4.10.2017  PDF
Item 4A – Wholesale DER Configurations  PDF
Item 3 - Behind-the-Meter Visibility  PDF
Item 4A – Wholesale DER Configurations  PDF
Item 4 - CBIR Solutions Matrix  XLS
Item 4 - CBIR Solutions Matrix  XLS
12.16.2016 Meeting materials from the MIC - Special meeting
Agenda  PDF
Agenda  DOC
Item 1 - Consensus Based Issue Resolution Process  PDF
Post-Meeting Matrix  XLS
Agenda  PDF
Agenda  DOC
Item 1 - Consensus Based Issue Resolution Process  PDF
Post-Meeting Matrix  XLS
6.19.2017 Meeting materials from the MC Information Webinar meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Item 6 - Distributed Energy Resources Stakeholder Process Update  PDF
Agenda  DOC
Item 6 - Distributed Energy Resources Stakeholder Process Update  PDF
Item 12C - OC Report  PDF
Item 12C - OC Report  PDF
12.11.2018 Meeting materials from the OC meeting
Agenda  PDF
Agenda  PDF
Agenda  DOC
Agenda  DOC
Item 11 - DERS Update  PDF
Item 11 - DERS Update  PDF
8.21.2019 Meeting materials from the DERS meeting
Agenda  PDF
Agenda  DOC
Item 2 - Draft Minutes - DERS - 7.15.2019  PDF
Item 4 - Interconnection Solutions Matrix  XLS
Agenda  PDF
Item 4 - Interconnection Solutions Matrix - Working Version  XLS
Agenda  DOC
Item 5 - Third-Party Ownership  PDF
Item 2 - Draft Minutes - DERS - 7.15.2019  PDF
Item 6 - Utility Microgrid Generation Solutions Matrix  XLS
Item 4 - Interconnection Solutions Matrix  XLS
Item 4 - Interconnection Solutions Matrix - Working Version  XLS
Item 5 - Third-Party Ownership  PDF
Item 6 - Utility Microgrid Generation Solutions Matrix  XLS
Date Type Documents
There are no governing documents currently associated with this issue